Page 1 of 6 SAUDI ARAMCO ID/PID - MAY-18-05 - REV 0 (Standards Cutoff - June 2008) REV 3 30-Jun-08 SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER Fire Damper Receiving Inspection SAIC-K-4010 15-Dec-09 HVAC PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO. SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRA SAUDI ARAMCO USE ONLY SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-I A1 Delivered equipment and material shall be free of damage. A2 A3 A4 A5 A6 A7 A8 Table 2-2 Minimum Sleeve Thickness for Fire Dampers Duct Duct Dimension Sleeve Gauge 12" down 26 13"-30" 24 31"-54" 22 55"-84" 20 ITEM No. Schedule “Q” Attachment IV Para 7.1 Fire dampers shall bear a label from a recognized (by Saudi Aramco) testing laboratory (such as UL) or be tested in accordance with the requirements of Uniform Building Code, UBC STD 43-7. Note: Whether Fire Damper or Combination Fire/Smoke Damper is UL listed or not can be determined from UL web page. Please visit UL site at WWW.UL.COM. You need to check and make sure that the supplied model is listed. Also check for size, position, System type and rating of the supplied dampers. For more clarifications you may contact Fire Damper Remediation committee members. SAES-K-001 Para 4.8.17.4 Fire Damper shall be labeled for both maximum airflow permitted and direction of flow. (UMC Para 605.2) SAES-K-100 Section 1 Minimum size of retaining angle provided shall be 1-1/2 “x 1-1/2” x 0.054 (SMACNA Chapter 2, Typical Inspection Details) Note: Where fire dampers arrive at site without retaining angles (retaining angles are considered bulk items), the requirements above shall be verified at the time of installation. SAES-K-001 Para 4.8.17.6 Minimum sleeve thickness shall be 26 gauge for ducts 12” and down, 24 gauge for 13”-30”, 22 gauge for 31”-54”, 20 for 55”-84” and 18 gauge for 85” and up. (SMACNA Chapter 2, Typical Installation Detail) Note: Where sleeves are not delivered at the same time as fire dampers, the requirements above shall be verified at the time of installation. SAES-K-001 Para 4.8.17.6 Fire damper shall have a 1-1/2 hour fire protection rating (shown on the nameplate) for walls, partitions or floor with fire resistance rating of less than 3 hours (SMACNA Para 3.2.1 / NFPA 90 A Para 5.4.1.1) SAES-K-001 Para 4.8.17.6 Fire damper shall have a 3 hour fire protection rating (shown on the name plate) for walls, partitions or floor with fire resistance rating of more than 3 hours (SMACNA Para 3.2.1 / NFPA 90 A Para 5.4.1.2) SAES-K-001 Para 4.8.17.6 Minimum sleeve thickness for breakaway connection shall be as shown on table below: (SMACNA Chapter 2, Typical Installation Detail-Table 2- 2)ê SAES-K-001 Para 4.8.17.6 Round or Rectangular Round or Rectangular Round or Rectangular Round or Rectangular

Upload: mohamad

Post on 05-Jan-2016

216 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: SAIC-K-4010.xls

Page 1 of 3

SAUDI ARAMCO ID/PID - MAY-18-05 - REV 0 (Standards Cutoff - June 2008) REV 3 30-Jun-08

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Fire Damper Receiving Inspection SAIC-K-4010 15-Dec-09 HVAC

PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIMESAUDI ARAMCO USE ONLY

SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE

A1 Delivered equipment and material shall be free of damage.

A2

A3

A4

A5

A6

A7

A8

Table 2-2 Minimum Sleeve Thickness for Fire Dampers

Duct Duct Dimension Sleeve Gauge

Round or Rectangular 12" down 26

Round or Rectangular 13"-30" 24

Round or Rectangular 31"-54" 22

Round or Rectangular 55"-84" 20

ITEM No.

Schedule “Q” Attachment IV

Para 7.1

Fire dampers shall bear a label from a recognized (by Saudi Aramco) testing laboratory (such as UL) or be tested in accordance with the requirements of Uniform Building Code, UBC STD 43-7.

Note: Whether Fire Damper or Combination Fire/Smoke Damper is UL listed or not can be determined from UL web page. Please visit UL site at WWW.UL.COM. You need to check and make sure that the supplied model is listed. Also check for size, position, System type and rating of the supplied dampers. For more clarifications you may contact Fire Damper Remediation committee members.

SAES-K-001 Para 4.8.17.4

Fire Damper shall be labeled for both maximum airflow permitted and direction of flow. (UMC Para 605.2)

SAES-K-100Section 1

Minimum size of retaining angle provided shall be 1-1/2 “x 1-1/2” x 0.054 (SMACNA Chapter 2, Typical Inspection Details)Note: Where fire dampers arrive at site without retaining angles (retaining angles are considered bulk items), the requirements above shall be verified at the time of installation.

SAES-K-001 Para 4.8.17.6

Minimum sleeve thickness shall be 26 gauge for ducts 12” and down, 24 gauge for 13”-30”, 22 gauge for 31”-54”, 20 for 55”-84” and 18 gauge for 85” and up. (SMACNA Chapter 2, Typical Installation Detail)Note: Where sleeves are not delivered at the same time as fire dampers, the requirements above shall be verified at the time of installation.

SAES-K-001 Para 4.8.17.6

Fire damper shall have a 1-1/2 hour fire protection rating (shown on the nameplate) for walls, partitions or floor with fire resistance rating of less than 3 hours (SMACNA Para 3.2.1 / NFPA 90 A Para 5.4.1.1)

SAES-K-001 Para 4.8.17.6

Fire damper shall have a 3 hour fire protection rating (shown on the name plate) for walls, partitions or floor with fire resistance rating of more than 3 hours (SMACNA Para 3.2.1 / NFPA 90 A Para 5.4.1.2)

SAES-K-001 Para 4.8.17.6

Minimum sleeve thickness for breakaway connection shall be as shown on table below: (SMACNA Chapter 2, Typical Installation Detail-Table 2-2)ê

SAES-K-001 Para 4.8.17.6

Page 2: SAIC-K-4010.xls

Page 2 of 3

Round or Rectangular 85" up 18

Page 3: SAIC-K-4010.xls

Page 3 of 3

SAUDI ARAMCO ID/PID - MAY-18-05 - REV 0 (Standards Cutoff - June 2008) REV 3 30-Jun-08

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Fire Damper Receiving Inspection SAIC-K-4010 15-Dec-09 HVAC

PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

REFERENCE DOCUMENTS:

1-SAES-K-001-- Heating, Ventilating, and Air Conditioning, 25 November 20062-SAES-K-100 -- Saudi Aramco Mechanical Code (HVAC), 31 May, 20043-Schedule "Q" Saudi Aramco Quality Requirements4-Uniform Mechanical Code (UMC), 1997

5-SMACNA -- "Fire Smoke and Radiation Damper Installation Guides", 4th Edition

6- NFPA 90 A -- Standard for Installation of the Air-Conditioning and Ventilating Systems, 2002

Contractor / Third-Party Saudi Aramco

Name, Initials and Date:Work is Complete and Ready for Inspection:

Name, Initials and Date:T&I Witnessed QC Record Reviewed Work Verified

QC Inspector PID Representative

Name, Initials and Date:Performed Inspection Work / Rework May Proceed

Name, Initials and Date:T&I Witnessed QC Record Reviewed Work Verified

QC Supervisor Proponent and Others

Name, Sign and Date: Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

REMARKS:

Construction Representative* PMT Representative

Name, Organization,Initials and Date: