Page 1: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL1

Electrical Safety In The Workplace

Page 2: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL2

Electrical Safety

SALISBURY by Honeywell - CONFIDENTIAL

2

Page 3: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL3

What Is Arc Flash

Page 4: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL4© ABB2/07/2012 | Slide 4

Residual DamageBehind Where the Person was Standing

Page 5: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL5© ABB2/07/2012 | Slide 5

5 KV 1200 Amp Breaker

Racking Handle

Page 6: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL6© ABB2/07/2012 | Slide 6

Residual Damage

Page 7: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL7

40 Cal/cm2 Arc Flash Suit

© ABB2/07/2012 | Slide 7

Page 8: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL8

10/17/12 Statement

• A serious violation occurs when there is substantial probability that death or serious physical harm could result from a hazard about which the employer knew or should have known.

• "This company exposed workers to serious safety hazards that could cause amputations or electrocutions," said Jack Rector, OSHA's area director in Fort Worth. "OSHA will not tolerate an employer's disregard for workplace safety.“

http://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=NEWS_RELEASES&p_id=23085

OSHA News’Release 12-1771-DAL

Page 9: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL9

4 Criteria for OSHA to Issue A Fine $$

• It must be a Recognized Standard In Industry.- LOTO, Fall Protection, NFPA 70E-All are recognized

standards in Industry.

• Serious injury, or death, could occur if not followed.- 3rd Degree Burns, Life Altering Scenario, Death.-All can and

do occur if NFPA70E is not followed.

• Employees must be at Risk.- Any employee with a multi-meter (testing), energizing, de-

energizing, or working live (hot) would be at risk.

• There must be an Abatement Method.- Salisbury has PPE, Tools and Equipment that can negate or

“abate” the hazard.

Page 10: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL10

Hazards and PPE Identification

• Electrical Safety Requirements for Employee Workplaces- This requirement covers all aspects of worker

safety associated with electrical hazards in the workplace. Within this standard are recommendations for proper PPE (Personal Protective Equipment)

- Addresses hazards: Shock Arc Flash Arc Blast

- Requirements for shock and arc flash boundaries

- Requirements for personal protective equipment

SALISBURY by Honeywell - CONFIDENTIAL

10

Page 11: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL11

Hazard 1: Shock/Electrocution

• Current, not voltage is lethal.• Current enters the body and seeks a pathway back

to ground.• The human body which is made of water, bone, and

muscle tissue is an EXCELLENT conducter.• Easiest to prevent.

Page 12: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL12

Shock Illustration

Current passage paths through the body

SALISBURY by Honeywell - CONFIDENTIAL

12

Current passing through the heart and lungs is the most serious

Touch Potential Step Potential Touch / Step Potential Touch / Step Potential

Page 13: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL13

How Do I Protect Against Shock?

•Insulating Gloves OSHA 1910.333(a)(1)

Rubber Insulating Gloves are among the most important articles of personal protective equipment for electrical workers. They are the first line of defense for contact with any energized components or lines.

Page 14: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL14

Gloves Must Be Inspected

• Working around sharp object, in close proximity to energized parts

• Gloves must be inspected prior to each use

• There are two ways to inspect gloves- Manual

- Portable glove inflator

SALISBURY by Honeywell - CONFIDENTIAL

14

Page 15: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL15

…and Tested.

• The interval between electrical retest for issued Rubber Gloves shall not exceed six months

• Gloves that have been electrically tested but not issued shall not be placed into service unless they have been electrically tested within previous twelve months

SALISBURY by Honeywell - CONFIDENTIAL

15

Page 16: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL16

Gloves Storage

• Rubber gloves should be stored in glove bags

• Do not store more than one pair of gloves in each bag

• Do not store on or in front of truck heaters.

• Do not roll , fold or tape

SALISBURY by Honeywell - CONFIDENTIAL

16

Page 17: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL17

Hazard 2: Arc Blast

• Expansion Of Air Due to Very Quick Heating Of Air At Ambient Temperature

• 25 kA can create as much as 480 pounds of pressure on a worker 2 feet away

• 30% of Deaths in WWII Attributed to concussion waves

• Air Related Organs Effected 1st – Lungs, Intestines, Brain

• Approximately 12% of the deaths are caused by the blast.

Page 18: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL18

Hazard 3: Arc Flash

• As much as 80% of all electrical injuries are burns resulting from an arc-flash and ignition of flammable clothing.

• Arc temperature can reach 35,000°F - this is four times hotter than the surface of the sun

Fatal burns can occur at distances over 10 ft.

• Over 2000 people are admitted into burn centers each year with severe electrical burns

Page 19: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL19

Face Shields

• Must Meet ASTM F2178-02• Must Meet ANSI Z87.1• Meet Same Criteria for ATPV Rating Given to

Garments Based on ASTM F1958• Clean With Mild Soap and Warm Water

SALISBURY by Honeywell - CONFIDENTIAL

19

Page 20: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL20

130.7(C)(1) Parts to be Protected.

• (C) Personal Protective Equipment.• (1) General. When an employee is working within the

Arc Flash Protection Boundary he or she shall wear protective clothing and other personal protective equipment in accordance with 130.3. All parts of the body inside the Arc Flash Protection Boundary shall be protected.

Page 21: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL21

NFPA 70E provides choices for selecting PPE

• Perform an arc flash hazard analysis, and document the incident energy exposure

- EasyPower

- Duke Flux Software (Freeware)

- ETAP

- IEEE 1584 Standard• As an alternate, use the “Hazard Risk

Category Classifications” table to choose the PPE level required for the task

• 40 Cal Option

SALISBURY by Honeywell - CONFIDENTIAL

21

Page 22: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL22

Method 1 (Arc Flash Analysis)

- 130.3 Requirement for Analysis

- “The flash hazard analysis shall be updated when a major modification or renovation takes place. It

shall be reviewed periodically, not to exceed 5 years to account for changes in the electrical

distribution system that could affect the results of the analysis”

Page 23: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL23

Salisbury Assessment Solutions (SAS)

• This is the best way to identify the proper PPE requirements. Salisbury Assessment Solutions.

Variables that effect the size and energy of an electric arc flash are:

AmperageVoltageArc gapClosure timeDistance away from arc3 phase v single phaseConfined spaceCharacteristics of equipment

Page 24: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL24

130.3(C) PPE Requirements Spelled Out.

• (C) Equipment Labeling. Equipment shall be field marked with a label containing the available incident energy or required level of PPE

WARNING !Arc Flash and Shock HazardAppropriate PPE Required

Page 25: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL25

Hazard Risk Category Tables (Method 2)

Tasks Performed on Energized EquipmentHazard/ Risk

CategoryRubber

InsulatingGloves

Insulatedand

InsulatingHand Tools

Panel boards rated 240 V and below – Notes 1 — — —

Circuit breaker (CB) or fused switch operation with covers on 0 N N

CB or fused switch operation with covers off 0 N N

Work on energized parts, including voltage testing 1 Y Y

Remove/install CBs or fused switches 1 Y Y

Removal of bolted covers (conductors and circuit expose bare, energized t parts) 1 N N

Opening hinged covers (conductors and circuit expose bare, energized t parts) 0 N N

Panel boards or Switchboards rated >240 V and up to 600 V (with molded case or insulated case circuit breakers) — Notes1

— — —

CB or fused switch operation with covers on 0 N N

CB or fused switch operation with covers off 1 N N

Work on energized parts, including voltage testing 2* Y Y

Table 130.7(C)(9) Hazard Risk Category Classifications and Use of Rubber Insulating Gloves and Insulated and Insulating Hand Tools

Page 26: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL26

Drawbacks to using Tables (Method 2 cont)

• When using the tables provided in the NFPA 70E manual, only voltage is taken into consideration. This usually causes over protection as all other variables are maxed out.

Variables that effect the size and energy of an electric arc flash are:

AmperageVoltageArc gapClosure timeDistance away from arc3 phase v single phaseConfined spaceCharacteristics of equipment

Page 27: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL27

Cat 4

• If a Hazard Level Assessment has not been done and the end user does not wish to reference the tables; then a Category 4 Level of PPE is required.

Page 28: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL28

Tools/Meters As PPE

70E 130.7(D)(1)• employees must use insulated tools and/or handling

equipment when working inside the limited approach boundary of exposed live parts where tools or handling equipment might make accidental contact

• OSHA 1910.335(a)(2)(i)• When working near exposed energized conductors or

circuit parts, each employee shall use insulated tools or handling equipment…

Page 29: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL29

NFPA 70E 2012 Summary of Significant Changes

• All references to “FR” now changed to “Arc Rated”. This identifies that FR clothing is not necessarily tested to the ASTM test for arc rating.

• Addition of incident energy tables for direct current (DC) systems.

• Terms such as “flash protection boundary”, “flash hazard boundary”, and “flash boundary” changed to new term “arc flash boundary”.

• The nose was added to the coverage needed from a balaclava.

• Retraining shall be performed at intervals not to exceed 3 years.

• Electrical safety program shall identify procedures for working: within the limited approach boundary and arc flash boundary to clarify the separation between the two boundaries.

• Removal of 2* category. For 2012, all is included in category 2.

• Arc Blast is now a recognized hazard by NFPA 70E. Inclusion of this hazard may require updated assessments.

• Employees must report any perceived contact to supervision.

• Employers must inform contractors of any known hazards.

29

Page 30: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL30

Determining Who Is to Be Trained

110.4 Use of Equipment. Formally Section 130.4

(A) Test Instruments and Equipment

(1) Testing. Only qualified persons shall perform tasks such as testing troubleshooting and voltage measuring with the limited approach boundary of energized electrical conductors or circuits parts operating at 50volts or more or where an electrical hazard exists.

Page 31: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL31

Often Heard Phrase

• “It Can’t Happen to Me”.

• A frequently-cited study* by Chicago-based safety contractors Capelli-Schellpfeffer, Inc. reports that between 5 and 10 arc-flash incidents causing serious injuries that require treatment in a burn center occur each day. Of these, 1 or 2 result in death. A CDC/NIOSH study** puts the total number of arc-flash injuries from 1992 through 2001 at 17,101.

Page 32: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL32

Statistics (Annual data)

SALISBURY by Honeywell - CONFIDENTIAL

32

4,0003,600

365

4

2,000+

Electrical contact injuries,

non-disabling

Electrical contact injuries, disabling

Person is electrocute

d

ElectrocutionsLeading cause

of occupational

fatalities

Workers are sent to

burn centers

with electrical

burns

Page 33: SALISBURY BY HONEYWELL - CONFIDENTIAL 1 Electrical Safety In The Workplace

SALISBURY BY HONEYWELL - CONFIDENTIAL33

Changing Profession, Changing Attitudes