Sample Report: ASHI SOP: Sample Report: ASHI SOP: Table Layout Table Layout 2112 Walnut Ct. Walnut Hills 12345 Inspected by Inspected by: M S Adkins Date of Inspection Date of Inspection: June 2016 Prepared By Prepared By: Tim Taylor Buyer Buyer: Ray & Julie Buyer Seller Seller: Charles & Sharon Seller C6 Home Inspections : 123 Plantana Road, Greenstem

Upload: vuongnhu

Post on 06-May-2019

235 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

Sample Report: ASHI SOP:Sample Report: ASHI SOP:Table LayoutTable Layout

2112 Walnut Ct.Walnut Hills12345

Inspected byInspected by:: M S Adkins

Date of InspectionDate of Inspection:: June 2016

Prepared ByPrepared By:: Tim Taylor

BuyerBuyer:: Ray & Julie Buyer

SellerSeller:: Charles & Sharon Seller

C6 Home Inspections : 123 Plantana Road, Greenstem

Page 2: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

Table of ContentsTable of Contents

Inspection InformationInspection Information ............................................................................................................................................................

CertificatesCertificates ............................................................................................................................................................

Structural ............................................................................................................................................................

Exterior ............................................................................................................................................................

Roof ............................................................................................................................................................

Insultation & Ventalation ............................................................................................................................................................

Interiors ............................................................................................................................................................

Plumbing ............................................................................................................................................................

Electrical ............................................................................................................................................................

Heating ............................................................................................................................................................

Cooling ............................................................................................................................................................

Fireplace / Fuel Burning ............................................................................................................................................................

ObservationsObservations ............................................................................................................................................................

Photo IndexPhoto Index ............................................................................................................................................................

DisclaimerDisclaimer ............................................................................................................................................................

Flagged AddendumFlagged Addendum ............................................................................................................................................................

11

33

4

6

8

9

10

12

14

16

17

18

44

2020

3535

3636

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 3: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

INSPECTION INFORMATIONINSPECTION INFORMATION

Inspected ByInspected By Tim Taylor

Home StyleHome Style Single Story

ModelModel 3-bed/2-bath

Occupancy StatusOccupancy Status Vacant

Water OperationalWater Operational Yes

WeatherWeather Dry

Electricity OperationalElectricity Operational Yes

TemperatureTemperature 60- 70

Gas OperationalGas Operational Yes

Radon Test PerformedRadon Test Performed No

Water Test PerformedWater Test Performed No

OrientationOrientation North East

StyleStyle Single Family

Type of DwellingType of Dwelling Ranch

In AttendanceIn Attendance Seller

CONDITION SUMMARYCONDITION SUMMARY

Immediate Repairs

ExteriorExterior || WalkwaysWalkways

Hardscape in serviceable condition. Significant concrete pad heave is a tripping hazard. Likely tree root-related upheaval.

[Photo 17] 6' of heave to concrete hardscape

[Photo 18] +2.5" of lift

[Photo 19] Left side yard

[Photo 20] Further detail

PlumbingPlumbing || Water DistributionWater Distribution

[Photo 43] Water pipes penetrating the 1-hour firewall in garage do not have fire-stopping material.

[Photo 44] Detail

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 1 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 4: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

Necessary Repairs

StructuralStructural || Door FramesDoor Frames

The front door is out of square. Additional insulation tape added and lockset has been filed to deal with out-of-squaredoorframe.

[Photo 7] Evidence of lock repairs due to movement

[Photo 8] Double door front entry with visible gaps

ExteriorExterior || Flashing/ TrimFlashing/ Trim

Holes in underfloor venting mest that would permit rodent access.

[Photo 15] Large mesh

[Photo 16] Large and fine mesh with hole

RoofRoof || GuttersGutters

Gutters are rusted at all locations. They are end end of service life. Evidence of sealant failure at joints at back elevation.Rust marks on read patio.

[Photo 29] Detail of typical condition

[Photo 30] Front entry as representative

RoofRoof || DownspoutsDownspouts

Downspout missing at front entry.

InteriorsInteriors || DoorsDoors

[Photo 37] No visible label for fire rating

[Photo 38] Garage to interior access

[Photo 39] Door should be fire rated

ElectricalElectrical || Connected Devices & FixturesConnected Devices & Fixtures

[Photo 60] Undersink electric supply to disposal and diswasher

[Photo 61] Poor repair indicates prior issue

CoolingCooling || Refrigerant LinesRefrigerant Lines

[Photo 67] Part of the refrigerant line is not insulated

[Photo 68] Gap detail

[Photo 69] Refrigerant lines penetrating the stucco. Open gap should be sealed.

Fireplace / Fuel BurningFireplace / Fuel Burning || Chimney(s)Chimney(s)

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 2 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 5: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

Damper is not operational. Locked open.

CERTIFICATESCERTIFICATES

Pest ControlPest Control

Pest Certificate

01/20/201701/20/201701/20/2017

1

Certificate #Certificate #:: NA

Issued OnIssued On:: August 02, 2011

OrganisationOrganisation:: Charles Mayer

EngineerEngineer:: NA

Renew ByRenew By:: August 02, 2021

GENERAL NOTESGENERAL NOTES

Standard of PracticeStandard of Practice

This home inspection was conducted based on the ASHI Standards of Practice which defines the scope of a professional

home inspection.

http://www.homeinspector.org/files/docs/standards_updated3-4-2015.pdf

Exterior Components:Exterior Components:

A home inspection shall evaluate observable and/or accessible structural components, as well as the foundation, roof and

any other exterior components. Adjacent walkways and driveways are included in a typical home inspection, as well as

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 3 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 6: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

patios, decks, stairs and fences. Surface drainage/grading and exterior components like retaining walls will be inspected as

they relate to the home's structural integrity or possible degradation due to water intrusion etc.

Interior Components:Interior Components:

The heating/AC will be inspected along with exhaust systems, fireplaces, plumbing, electrical, doors, windows and other

accessible interior components like trim, stairs and railings. The inspector shall access crawlspaces, attics and areas where

interior foundation components can be inspected. The garage will be inspected along with HVAC, plumbing and electrical

systems original to the home like sub-panels, water heaters and FAU's located in the garage.

OBSERVATIONSOBSERVATIONS

StructuralStructural

Notes:Notes:

Inspect:

The inspector shall inspect the basement, foundation, crawlspace, and structure.

Report:

The inspector shall describe the type of the foundation and identify the location of the access to the crawlspace.

The inspector shall report observed indications of wood in contact or near-contact with soil; indications of water intrusion;indications of foundation movement, e.g., drywall cracks, stone or brick cracks, out-of-square door frames, and unlevelfloors; and observed modifications to framing members (e.g., cuts, holes, & notches) that create a structural or safetyissue.

Exclusions:

The inspector is not required to enter any crawlspace that is not readily accessible or is unsafe; move items that impactthe ability to access or inspect an area; or identify the size, spacing, span or location of construction components.

The inspector is also not required to operate submersible pumps with inaccessible floats, determine the adequacy ofstructural systems including foundation bolting, bracing, beam & joist spans, or support systems; or provide anyengineering or architectural support.

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

FoundationInspected;OK

The foundation system incorporates a perimeter grade beam withconcrete piers and wood posts with a wood framed floor diaphragmwood frame structure.

Basement/CrawlSpace

Inspected;OK

This is not a structural inspection. No representation is made to thestructural integrity of the home. If a structural evaluation is desired, aspecialist should be consulted. Opinions vary widely as to whatamount of movement, cracking of foundations, or unevenness orsloping of floors is considered excessive.

Access to crawl space is through Bedroom 3 closet floor. Accessed toconduct visual inspection.

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 4 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 7: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

AccessInspected;OK

IntegrityFramingMembers

Inspected;OK

Wood toSoilContact

Inspected;OK

None observed.

WaterPenetration

Inspected;OK

There is no vapor barrier in the crawl space. The existing gradeexhibits cracking. Recommend monitoring this condition. There is noevidence that this condition is contributing to any kind of deleteriousperformance of the foundation in house.[Photo 2] Prior indication of moisture.[Photo 3] The floors are dry. Measurement taken with a Wagner L606moisture meter indicates moisture at sub floor is 10%[Photo 4] Access to crawl area.

2, 3,4

FoundationMovement

Inspected;OK

FloorStructure

Inspected;OK

The house is supported by a pillar and post foundation system, allappears in good serviceable condition.[Photo 5] Underfloor pillar and post system[Photo 6] Pillar with concrete footing

5, 6

WallStructure

Not able to be determined by a visual inspection. There is some smallmovement as noted in Interior Wall section. This is typical for thehouse construction type and area soil.

DoorFrames

NecessaryRepairs

The front door is out of square. Additional insulation tape added andlockset has been filed to deal with out-of-square doorframe.[Photo 7] Evidence of lock repairs due to movement[Photo 8] Double door front entry with visible gaps

7, 8

CeilingStructure

Inspected;OK [Photo 9] Ceiling

9

RoofStructure

Inspected;OK

The roof framing is comprised of manufactured wood trusses, skipsheathing over the trusses extending the entire roof surface, and ashear panel for the roof framing.

10,11,12

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 5 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 8: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

The existing attic has 2 x 4 truss frames with skip sheathing. The skipsheathing has been over layed with OSB sheer panels to bring thebuilding to current seismic requirements.[Photo 10] Access through Master Walk-in closet[Photo 11] Framework[Photo 12] Framework with side vent

ExteriorExterior

Notes:Notes:

Inspect:

The inspector shall inspect the following construction components associated with the exterior: exterior wall-coveringcomponents including flashing and trim; roof eaves, soffits, & facia; all exterior doors & a representative number ofwindows; decks, balconies, & carports; flatwork including driveways, walkways,& patios; stairs, steps, & ramps; guardrails& handrails; and general landscaping including general grading, surface drainage, retaining walls, and vegetation.

Report:

The inspector shall describe the exterior wall cladding components and report improper spacing between intermediateblusters, spindles, & rails.

Exclusions:

The inspector is not required to inspect items that are not visible or accessible from the ground; fenestration related itemssuch as safety-type glass, integrity of insulated glazing, screens, storm windows, shutters, and awnings; outbuildings,fences, playground equipment; subgrade items including utilities; exterior accent lighting; and irrigation systems.

The inspector is also not required to inspect wastewater treatment systems including septic systems and cesspools;swimming pools and spas; wells and springs; drywalls & drainfields; geothermal systems; erosion control and earth-stabilization systems; seawalls, breakwalls, and docks; geological, geotechnical, hydrological, and soil conditions; solarsystems; and wind systems.

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

WallCladding

Inspected;OK

Stucco[Photo 13] Front[Photo 14] Front

13,14

Flashing/Trim

NecessaryRepairs

Holes in underfloor venting mest that would permit rodent access.[Photo 15] Large mesh[Photo 16] Large and fine mesh with hole

15,16

Eaves/Soffits/Fascias

Inspected;OK

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 6 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 9: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

DoorsInspected;OK

WindowsInspected;OK

StepsInspected;OK

WalkwaysImmediateRepairs

Hardscape in serviceable condition. Significant concrete pad heave isa tripping hazard. Likely tree root-related upheaval.[Photo 17] 6' of heave to concrete hardscape[Photo 18] +2.5" of lift[Photo 19] Left side yard[Photo 20] Further detail

17,18,19,20

DrivewayInspected;OK

The driveway is approximately 20' X 30'. Concrete slab-on-grade inserviceable condition.[Photo 21] Closeup[Photo 22] Right garage door access[Photo 23] Cracking across field

21,22,23

SurfaceDrainage

Inspected;OK

VegetationInspected;OK

Landscaping incorporates lawn and plant areas and isolated trees withan automatic sprinkler system, generally in good serviceablecondition.

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 7 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 10: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

RoofRoof

Roof Components

01/19/201701/19/201701/19/2017

24

Aerial

01/20/201701/20/201701/20/2017

25

Notes:Notes:

Inspect:

The inspector shall inspect, from ground level or roof eaves, the following construction components associated with theroof assembly: roof covering materials, associated roof flashing materials, roof gutter & downspout assembly, roofpenetrations including vents, skylights, & chimneys.

Report:

The inspector shall describe the roof-covering materials and report observed indications of leaks.

Exclusions:

The inspector is not required to walk on any roof surface, remove items that impact the ability to inspect a roof surface,inspect attachments (e.g., satellite dishes), perform a water test, inspect sub-grade downspout drainage pipes or otherinaccessible components, confirm proper installation of any roof-covering component, or predict service life. A detailedRoof Inspection has been ordered and has therefore not been included in this report. General photos of roof to show visualcondition.

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

InspectionMethod

Visual inspection from stepladder of all roof fields.

CoveringMaterials

Inspected;OK

Composition shingle.[Photo 26] Garage[Photo 27] Rear[Photo 28] Master bedroom

26,27,28

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 8 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 11: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

GeneralStructure

Inspected;OK

FlashingsInspected;OK

ChimneyPenetrations

Inspected;OK

OtherPenetrations

Inspected;OK

GuttersNecessaryRepairs

Gutters are rusted at all locations. They are end end of service life.Evidence of sealant failure at joints at back elevation. Rust marks onread patio.[Photo 29] Detail of typical condition[Photo 30] Front entry as representative

29,30

Downspouts

NecessaryRepairs

Downspout missing at front entry.

Insultation & VentalationInsultation & Ventalation

Notes:Notes:

Inspect:

The inspector shall inspect insulation and ventilation in the unfinished spaces including attics, crawlspaces and foundationareas as well as the exhaust systems in the kitchen, bathroom, and laundry areas.

Report:

The inspector shall describe the type and average thickness of insulation observed at the unfinished areas.

The inspector shall report deficiencies in insulation and ventilation in unfished areas, particularly absence of insulation orventilation.

Exclusions:

The inspector is not required to enter unfinished spaces such as attics and crawlspaces that are not readily accessible orwhere entry could cause damage or pose a safety hazard.

The inspector is not required to move, touch, or disturb insulation or vapor retarders or activate / operate thermostaticallyoperated fans.

The inspector is not required to identify the composition or R-value of insulation material; determine the types ofmaterials used in insulation or wrapping of pipes, ducts, jackets, boilers or wiring; or determine the adequacy ofventilation.

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 9 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 12: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

AtticInsulation

Monitor

Blown insulation throughout[Photo 31] Attic access from master closet[Photo 32] A1.jpg[Photo 33] Insulation field[Photo 34] Plywood access over insulation

31,32,33,34

AtticVenting

Inspected;OK

Under FloorInsulation

There is no underfloor insulation.

Under FloorVenting

Inspected;OK

Thermostatic Controls

Inspected;OK

Present in main hallway.

InteriorsInteriors

Notes:Notes:

Inspect:

The inspector shall inspect and operate a representative number of doors and windows; inspect floors, walls, & ceilings;inspect stairs, stairways, ramps, and landings as well as railings, guards, and handrails; garage vehicle doors andassociated opening mechanisms using normal operating controls.

Report:

The inspector shall describe the vehicle door and indicate if it is operated manually or through an automatic opener.

The inspector shall report deficiencies related to spacing between balusters, spindles, and rails for stairs, guardrails andrailings; non-functioning safety sensors (for automatic garage door openers); and window glazing units.

Exclusions:

The inspector is not required to move items to inspect the concealed floor structure or move suspended ceiling tiles.

The inspector is not required to inspect paint, wallpaper, window treatments or other finish treatments; floor coverings;central vacuum systems; security systems and associated components.

The inspector is not required to operate any system, appliance, or component that requires special keys, codes, orcombinations; operate or evaluate self-cleaning oven cycles, tilt guards/ latches, or signal devices; operate or examine anysauna, steam-generating equipment, kiln, hot water dispenser, small household appliances; items not permanentlyinstalled; inspect or operate equipment located in the garage (unless specifically notes);

The inspector is not required to identify safety glazing.

The inspector is not required to identify firewall compromises.

The inspector is not required to operate or evaluate any security bar release and opening mechanisms, including theircompliance with state or federal standards; or verify or certify the proper operation of any pressure-activated auto-reverserelated safety feature of a garage door.

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 10 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 13: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

The inspector is not required to evaluate the fastening of cabinetry (and islands), countertops, sinks, and fixtures.

The inspector is not required to inspect elevators, pools, spas, or fountains.

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

Floors Monitor

Walls Monitor [Photo 35] Living room at firplace cracking[Photo 36] Detail

35,36

CeilingsInspected;OK

DoorsNecessaryRepairs

[Photo 37] No visible label for fire rating[Photo 38] Garage to interior access[Photo 39] Door should be fire rated

37,38,39

WindowsInspected;OK

StepsInspected;OK

CountersInspected;OK

CabinetsInspected;OK

Evidence of water leaks[Photo 40] Tested and found dry.[Photo 41] Master vanity

40,41

KitchenAppliances

Inspected;OK

LaundryInspected;OK

GarageVehicleDoors

Inspected;OK

SafetySensors

Inspected;OK

Smoke Alarms and Carbon Monoxide sensors functional.

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 11 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 14: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

PlumbingPlumbing

Water Heater Components

01/19/201701/19/201701/19/2017

42

Notes:Notes:

Inspect:

The inspector shall inspect the main water supply shut-off valve and the main fuel supply shut-off valve; the drain, waste,& vent system; drainage sump pumps with accessible floats.

The inspector shall also inspect the water heating equipment and the associated energy source, venting connections,temperature / pressure relief valves, automatic gas shutoff valves, and seismic bracing.

Test:

Inspect interior water supply and test all fixtures by ‘running the water’ and flushing toilets. Inspect functionality ofsanitary drainage by flushing toilets and draining sinks, tubs, & showers.

Report:

The inspector shall describe the water supply as public or private based upon observed conditions; the locations of themain water supply valve and main fuel supply valve; the location of any observed fuel-storage system; and the capacity ofwater heating equipment.

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 12 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 15: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

The inspector shall report, as need in correction, deficiencies in the installation of hot and cold water faucets; deficienciesin the water supply through observation of functional flow of through two fixtures operating simultaneously; damaged,leaking, non-functional, or incorrectly installed toilets; and missing or non-operational drain stops at sinks or tubs.

type of cooling system and identify the location of the thermostat. The inspector shall identify any cooling system that isnot operational and if the heating system is inaccessible.

Exclusions:

The inspector is not required to open sealed plumbing access panels; operate any valve; ignite pilot flames; test, operate,open or close safety controls, manual stop valves, temperature / pressure relief valves, control valves, safety shut-offvalves, or check valves; or examine auxiliary systems such as solar water heating systems or hot water circulation systems.

The inspector is not required to inspect or evaluate wastewater treatment systems; water treatment systems (includingfilters); drain cleanouts; storage tanks, pressure pumps, or bladder tanks; design or sizing of water, waste, or ventingcomponents, fixtures, or piping; anti-siphon, backflow prevention, or drain stop devices.

The inspector is not required to measure the capacity, temperature, age, life expectancy or adequacy of the water heateror evaluate wait-time to obtain hot water at fixtures, or perform testing of any kind to water heater elements.

The inspector is not required to determine the water flow rate, volume, pressure, temperature; compliance withconservation, energy, of building standards; or adequacy of the water supply including quality, potability, and reliability ofthe water supply.

The inspector is not required to identify the existence r condition of polybutylene plumbing.

The inspector is not required to test shower pans, tub, and shower surrounds or enclosures for leakage or functionaloverflow protection.

The inspector is not required to inspect the interior of flues or chimneys, combustion air systems or evaluate or determinethe adequacy of combustion air.

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

WaterSupply

Inspected;OK

WaterDistribution

ImmediateRepairs

[Photo 43] Water pipes penetrating the 1-hour firewall in garage donot have fire-stopping material.[Photo 44] Detail

43,44

Main WaterShutoff

Inspected;OK

Water meter shutoff is directly adjacent to the curb at the front entryto the house.[Photo 45] Access to water shutoff[Photo 46] .[Photo 47] Water shutoff valve

45,46,47

Drain/Waste/Vent

Inspected;OK

The drain from the hot water heater is combined with the condensatedrain for the air conditioning system to a common, sloped, copperpipe extending to the exterior through the back wall of the garage.[Photo 48] Vent 2[Photo 49] Vent 1[Photo 50] Vented to roof[Photo 51] Combined and sloped to exterior

48,49,50,51

Hot WaterEquipment

Inspected;OK

Water heater located in Garage.[Photo 52] Manufacturer label

52,53

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 13 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 16: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

[Photo 53] Water heater in garage. Seismically secured.

Hot WaterSupply

Inspected;OK

Emergency shutoff easily accessed.[Photo 54] Valve[Photo 55] Shutoff

54,55

ToiletsInspected;OK

Sink/ Tub/Shower

Monitor

Base of wet bar faucet shows some discoloration. Monitor to checkthat there are no ongoing leaks. Below sink is clear.[Photo 56] Detail[Photo 57] Wet bar at dining room

56,57

Faucets Monitor

DrainsInspected;OK

Drains functional

ElectricalElectrical

Notes:Notes:

Inspect:

The inspector shall inspect the service drop; the overhead service conductors and attachment point;, service conduit andraceway; the electric meter and base; service-entrance conductors; and the main service disconnect. The inspector shallinspect over-protection devices including circuit breakers and fuses as well as service grounding and bonding.

The inspector shall inspect a representative number of switches, lighting fixtures, and receptacles.

Test:

The inspector shall inspect and test receptacles identified as arc-fault circuit interrupter (AFCI) using the AFCI button,receptacles identified as ground-fault circuit interrupter (GFCI) using a GFCI tester, and smoke and carbon monoxidedetectors.

Report:

The inspector shall report deficiencies in integrity of the service-entrance conductors’ insulation, drip loop, and verticalclearances from grade & roof; any unfilled circuit breaker panel openings; and presence of solid conductor aluminumbranch-circuit wiring.

The inspector shall also report deficiencies in tested receptacles including receptacles without power, without covers,incorrectly installed or non-performing GFCI devices, evidence of excessive heat or arcing, and conditions wherereceptacles are not grounded or not secured to the wall.

The inspector shall also report the absence of smoke detectors.

Exclusions:

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 14 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 17: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

The inspector is not required to insert any tool, probe, or device into panelboards or electrical fixtures; remove panelboardcovers; measure or determine the amperage or voltage of the main service equipment; operate electrical systems orbranch circuits that are shut down / not energized; or re-set over-current protection devices of overload devices.

The inspector is not required to inspect private or emergency electrical supply sources including generators, windmills,photovoltaic solar collectors, or battery of electrical storage facility; verify the service ground; inspect spark arrestors,lightning arrestors, de-icing equipment, or exterior lighting.

The inspector is not required operate smoke or carbon-monoxide detectors or inspect the fire alarm system orcomponents.

The inspector is not required to determine the accuracy of labeling or conduct voltage drop calculations.

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

MainDisconnects

Inspected;OK

Main disconnect with disconnects for all main services amounting to atotal amperage of 480 amps.[Photo 58] Panel[Photo 59] Located on back garage wall

58,59

GFCIInspected;OK

Present and fully operational in bathroom vanity areas.

ConnectedDevices &Fixtures

NecessaryRepairs

[Photo 60] Undersink electric supply to disposal and diswasher[Photo 61] Poor repair indicates prior issue

60,61

Polarity &Grounding

Inspected;OK

LightingFixtures

Inspected;OK

MainService

Inspected;OK

Wire SizeInspected;OK

SmokeDetectors

Inspected;OK

CarbonMonoxideDetectors

Inspected;OK

PanelCapacity

Inspected;OK

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 15 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 18: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

ServiceDrop

Inspected;OK

HeatingHeating

Notes:Notes:

Inspect:

The inspector shall inspect the heating system through the use of the normal operating controls.

Report:

The inspector shall describe the type of heating system (e.g., fuel source & heating method) and identify the location ofthe thermostat. The inspector shall report any heating system that is not operational and if the heating system isinaccessible.

Exclusions:

The inspector is not required to inspect or evaluate the interiors of combustion chambers, air intakes, exhausts, ordistribution systems, heat exchangers, humidifiers, dehumidifiers, electronic air filters, geothermal systems, or solarheating systems; inspect fuel tanks or sub-grade / concealed fuel supply systems; evaluate fuel quality; or determine thecapacity, uniformity, or adequacy of the heating system.

The inspector is also not required to ignite pilot flames; activate heating systems when environmental or operatingconditions are not conducive to safe operation or may damage the equipment; override / bypass electronic thermostats;verify thermostat calibration or control system functionality.

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 16 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 19: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

CoolingCooling

Cooling Components

01/19/201701/19/201701/19/2017

62

Notes:Notes:

Inspect:

The inspector shall inspect the cooling system through the use of the normal operating controls.

Report:

The inspector shall describe the type of cooling system and identify the location of the thermostat. The inspector shallidentify any cooling system that is not operational and if the heating system is inaccessible.

Exclusions:

The inspector is not required to inspect or examine the electrical current, coolant fluids, or coolant leaks; electronic airfilters; portable window mount or thru-wall conditioning units; or determine the capacity, uniformity, or adequacy of thecooling system.

The inspector is also not required to operate cooling systems when environmental or operating conditions are notconducive to safe operation or may damage the equipment, e.g., < 65°F; verify thermostat calibration or control systemfunctionality.

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 17 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 20: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

CoolingType

Inspected;OK

Condenser unit is located left of the garage with disconnect switch,attached to the wall of the garage.[Photo 63] Overview. Left elevation at garage.[Photo 64] A/C unit is a Lennox, model HS18-511-4p utilizing r-22refrigerant.

63,64

Distribution

Inspected;OK

Floor ducts throughout.

CondenserInspected;OK

[Photo 65] Located in garage[Photo 66] Detail

65,66

Evaporator& Drain

Inspected;OK

RefrigerantLines

NecessaryRepairs

[Photo 67] Part of the refrigerant line is not insulated[Photo 68] Gap detail[Photo 69] Refrigerant lines penetrating the stucco. Open gap shouldbe sealed.

67,68,69

ThermostatInspected;OK

Fireplace / Fuel BurningFireplace / Fuel Burning

Notes:Notes:

Inspect:

The inspector shall inspect the readily accessible and visible portions of the fireplaces and chimneys; lintels above thefireplace openings; and cleanout doors and frames.

Test:

The inspector shall inspect and operate damper doors (if readily accessible)

Report:

The inspector shall describe the type of fireplace.

The inspector shall report hearth assembly damage or deterioration; non-operable manual dampers; and cleanouts notconstructed of non-combustible material.

The inspector shall report conditions where smoke detectors and carbon-monoxide detectors are not located in the sameroom as the fireplace.

Exclusions:

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 18 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 21: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

The inspector is not required to ignite or extinguish fires, operate gas fireplace inserts, ignite pilot flames, move fireplaceinserts, stoves, or firebox contents or dismantle or remove any component.

The inspector is not required to inspect flue or vent systems; interiors of chimneys or flues, fire doors or screens, sealsand gaskets; combustion, make-up, automatic fuel loading devices; or heat-distribution assist devices.

The inspector is not required to perform a smoke test; determine the adequacy of drafts; or determine the need for achimney sweep; or determine the adequacy of any installation.

The inspector is not required to perform a National Fire Protection Association (NFPA) style inspection or a ‘Phase 1’fireplace and chimney inspection.

nicknamenickname conditionconditionflagflaggedged

notenotephophotostos

FireplaceLintels

Inspected;OK

FireplaceDamperDoors

Inspected;OK

FireplaceInserts

Gas starter / wood burning fireplace. Flue clean and clear based onvisual inspection from hearth.

Chimney(s)NecessaryRepairs

Damper is not operational. Locked open.

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 19 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 22: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

PHOTO INDEXPHOTO INDEX

CertificatesCertificates

Pest Certificate

01/20/201701/20/201701/20/2017

1

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 20 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 23: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

StructuralStructural

Prior indication of moisture. The floors are dry. Measurementtaken with a Wagner L606 moisturemeter indicates moisture at subfloor is 10%

Access to crawl area.

Underfloor pillar and post system Pillar with concrete footing Evidence of lock repairs due tomovement

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/20/2017 01/20/2017 01/20/2017

01/20/2017 01/20/2017 01/20/2017

2 3 4

5 6 7

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 21 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 24: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

StructuralStructural (continued)(continued)

Double door front entry with visiblegaps

Ceiling Access through Master Walk-incloset

Framework Framework with side vent

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/20/201701/20/2017 01/20/201701/20/2017

01/20/2017 01/20/2017 01/20/2017

01/20/2017 01/20/2017

8 9 10

11 12

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 22 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 25: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

ExteriorExterior

Front Front Large mesh

Large and fine mesh with hole 6' of heave to concrete hardscape +2.5" of lift

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/20/201701/20/2017 06/27/201606/27/2016 01/20/201701/20/2017

01/20/2017 01/20/2017 01/20/2017

01/20/2017 06/27/2016 01/20/2017

13 14 15

16 17 18

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 23 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 26: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

ExteriorExterior (continued)(continued)

Left side yard

Further detail

Closeup

Right garage door access Cracking across field

01/20/201701/20/2017

01/20/201701/20/2017

01/20/201701/20/2017

01/20/201701/20/2017 01/20/201701/20/2017

01/20/2017

01/20/2017

01/20/2017

01/20/2017 01/20/2017

19 20 21

22 23

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 24 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 27: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

RoofRoof

Roof ComponentsAerial

Garage

Rear Master bedroom Detail of typical condition

01/19/201701/19/201701/20/201701/20/2017

06/24/201606/24/2016

01/20/201701/20/2017 01/20/201701/20/2017 06/24/201606/24/2016

01/19/201701/20/2017

06/24/2016

01/20/2017 01/20/2017 06/24/2016

24 25 26

27 28 29

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 25 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 28: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

RoofRoof (continued)(continued)

Front entry as representative

Insultation & VentalationInsultation & Ventalation

Attic access from master closet A1.jpg Insulation field

01/20/201701/20/2017

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/20/2017

01/20/2017 01/20/2017 01/20/2017

30

31 32 33

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 26 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 29: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

Insultation & VentalationInsultation & Ventalation (continued)(continued)

Plywood access over insulation

InteriorsInteriors

Living room at firplace cracking Detail No visible label for fire rating

01/20/201701/20/2017

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/20/2017

01/20/2017 01/20/2017 01/20/2017

34

35 36 37

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 27 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 30: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

InteriorsInteriors (continued)(continued)

Garage to interior access Door should be fire rated Tested and found dry.

Master vanity

01/20/201701/20/2017 01/20/201701/20/2017 06/24/201606/24/2016

01/20/201701/20/2017

01/20/2017 01/20/2017 06/24/2016

01/20/2017

38 39 40

41

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 28 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 31: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

PlumbingPlumbing

Water Heater Components

Water pipes penetrating the 1-hourfirewall in garage do not have fire-stopping material.

Detail

Access to water shutoff . Water shutoff valve

01/19/201701/19/2017

01/18/201701/18/2017 01/20/201701/20/2017

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/19/2017

01/18/2017 01/20/2017

01/20/2017 01/20/2017 01/20/2017

42 43 44

45 46 47

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 29 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 32: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

PlumbingPlumbing (continued)(continued)

Vent 2 Vent 1 Vented to roof

Combined and sloped to exterior Manufacturer label Water heater in garage. Seismicallysecured.

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/20/2017 01/20/2017 01/20/2017

01/20/2017 01/20/2017 01/20/2017

48 49 50

51 52 53

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 30 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 33: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

PlumbingPlumbing (continued)(continued)

Valve Shutoff Detail

Wet bar at dining room

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/20/201701/20/2017

01/20/2017 01/20/2017 01/20/2017

01/20/2017

54 55 56

57

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 31 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 34: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

ElectricalElectrical

Panel Located on back garage wall Undersink electric supply to disposaland diswasher

Poor repair indicates prior issue

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/20/201701/20/2017

01/20/2017 01/20/2017 01/20/2017

01/20/2017

58 59 60

61

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 32 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 35: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

CoolingCooling

Cooling Components

Overview. Left elevation at garage. A/C unit is a Lennox, modelHS18-511-4p utilizing r-22refrigerant.

Located in garage Detail Part of the refrigerant line is notinsulated

01/19/201701/19/2017

06/24/201606/24/2016 01/20/201701/20/2017

01/20/201701/20/2017 01/20/201701/20/2017 01/20/201701/20/2017

01/19/2017

06/24/2016 01/20/2017

01/20/2017 01/20/2017 01/20/2017

62 63 64

65 66 67

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 33 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 36: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

CoolingCooling (continued)(continued)

Gap detail Refrigerant lines penetrating thestucco. Open gap should be sealed.

01/20/201701/20/2017 01/20/201701/20/201701/20/2017 01/20/2017

68 69

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 34 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 37: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

DISCLAIMERDISCLAIMER

Excluded Components & Systems (Disclaimer)Excluded Components & Systems (Disclaimer)

The inspector is conducting a visual inspection of the property. The inspector is not checking designs of the structure or

systems against local or national standards or codes.

The inspector is not required to inspect items not visible or readily accessible from the ground or evaluate geotechnical and

hydrological conditions. Recreational facilities and playground equipment are not included, along with sea walls and docks.

Solar, wind and geothermal equipment is excluded, as well as irrigation systems, pools, spas and underground septic

systems.

The inspector is not required to move stored items or furniture to access components. The inspector shall not evaluate

engineering or architectural design. It is not a requirement to identify or evaluate size, spacing, span, location and load

bearing qualities of any components.

The inspector is not required to inspect or evaluate flue or chimney interiors, heat exchangers, combustion air systems and

makeup air components. The inspection doesn't evaluate the uniformity of the AC system with respects to capacity, BTU's or

general adequacy. Portable window units are not included in the inspection.

The inspector is not required to re-light pilot flame igniters or evaluate the capacity and life expectancy of water heater(s).

Washers and dryers are excluded from the inspection, along with water softeners and water treatment systems. All household

appliances are excluded, along with any private or emergency power supply systems like generators and photovoltaic cells/

batteries.

In general, the inspector is not required to remove or dismantle any components or systems. The inspector is not required to

inspect paint, wallpaper, window treatments, central vacuums or security systems and the inspection does not include any

components or systems that require keys, special codes or combinations to operate/evaluate.

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 35 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 38: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

FLAGGED ADDENDUMFLAGGED ADDENDUM

ItemItem DescriptionDescription

Plumbing:WaterDistribution

Immediate RepairsImmediate Repairs FlaggedFlagged

Water pipes penetrating the 1-hour firewall in garage donot have fire-stopping material.

01/18/201701/18/201701/18/2017

43

Detail

01/20/201701/20/201701/20/2017

44

Exterior:Walkways

Immediate RepairsImmediate Repairs FlaggedFlagged

Hardscape in serviceable condition. Significant concrete pad heave is a tripping hazard. Likely treeroot-related upheaval.

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 36 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 39: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

Flagged AddendumFlagged Addendum (continued)(continued)

ItemItem DescriptionDescription

6' of heave to concrete hardscape

06/27/201606/27/201606/27/2016

17

+2.5" of lift

01/20/201701/20/201701/20/2017

18

Exterior:Walkways(continued)

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 37 of 38C6 Home Inspections : 123 Plantana Road,

Greenstem

Page 40: Sample Report: ASHI SOP: Table Layout - azashi.org · pho totoss Inspection Method Visual inspection from stepladder of all roof fields. Covering Materials Inspected; OK Composition

Flagged AddendumFlagged Addendum (continued)(continued)

ItemItem DescriptionDescription

Left side yard

01/20/201701/20/201701/20/2017

19

Further detail

01/20/201701/20/201701/20/2017

20

Exterior:Walkways(continued)

Sample Report: ASHI SOP: Table LayoutSample Report: ASHI SOP: Table Layout2112 Walnut Ct. Walnut Hills 12345

Page 38 of 38C6 Home Inspections : 123 Plantana Road,