sccr-1200a

1
Short-circuit Coordination Starter Type: Direct-On-Line & Reversing, Trip Class 10 Motor Protection Circuit Breaker (MPCB): 140M-C, D, F, I, J, L Contactor: 100-C, 100-K, 100-D Overload Relay: --- Rated Operational Voltage: 400 V, 50 Hz Test voltage: 436 V, 50Hz Rated Conditional S.C. Current (Iq): 65 kA (rms sym.) Level of S.C. Coordination: Type ''2'' (Type "1") per IEC 60947-4-1 Contactor Rated Operational Current I e Catalog Number Thermal Setting Range Magnetic Trip Current Catalog Number Coordination Type Test Summary Letter Remark [kW] [A] 1) [A] [A] 2) 0.06 0.20 140M-C2E-A25 0.16 - 0.25 3.3 100-C09... 0.09 0.30 140M-C2E-A40 0.25 - 0.40 5.2 100-C09... 0.12 0.44 140M-C2E-A63 0.40 - 0.63 8.2 100-C09... 0.18 0.60 140M-C2E-A63 0.40 - 0.63 8.2 100-C09... 0.25 0.85 140M-C2E-B10 0.63 - 1.00 13 100-C09... 0.37 1.1 140M-C2E-B16 1.0 - 1.6 21 100-C09... 0.55 1.5 140M-C2E-B16 1.0 - 1.6 21 100-C09... 0.75 1.9 140M-C2E-B25 1.6 - 2.5 33 100-C09... 1.1 2.7 140M-D8E-B40 2.5 - 4.0 52 100-C09... 1.5 3.6 140M-D8E-B40 2.5 - 4.0 52 100-C09... 2.2 4.9 140M-D8E-B63 4.0 - 6.3 82 100-C09... 3 6.5 140M-D8E-C10 6.3 - 10 130 100-C09... 4 8.5 140M-D8E-C10 6.3 - 10 130 100-C09... 5.5 11.5 140M-D8E-C16 10 - 16 208 100-C12... 7.5 15.5 140M-D8E-C20 14.5 - 20 260 100-C16... 11 22 140M-D8E-C25 18 - 25 325 100-C23... 15 29 140M-D8E-C32 27 - 32 448 100-C30... 18.5 35 140M-F8E-C45 32 - 45 585 100-C37... 22 41 140M-F8E-C45 32 - 45 585 100-C43... 30 55 140M-I8E-C80E 40 - 80 1200 100-C60... 37 66 140M-I8E-C80E 40 - 80 1200 100-C72... 45 80 140M-I8E-C80E 40 - 80 1200 100-C85... 55 97 140M-I8E-D10E 80 - 100 1500 100-C97... 63 113 140M-J8E-D16 64 - 160 2240 100-D210... Type "2" 63 113 140M-I8E-D16E 100 - 160 2400 100-D115... Type "1" 75 132 140M-J8E-D16 64 - 160 2240 100-D210... Type "2" 75 132 140M-I8E-D16E 100 - 160 2400 100-D140... Type "1" 90 160 140M-J8E-D25 100 - 250 3500 100-D210... Type "2" 90 160 140M-J8E-D25 100 - 250 3500 100-D180... Type "1" 110 195 140M-J8E-D25 100 - 250 3500 100-D210... 132 230 140M-J8E-D25 100 - 250 3500 100-D300... 160 280 140M-L8E-D40 160 - 400 4800 100-D300... 200 350 140M-L8E-D40 160 - 400 4800 100-D420... 250 430 140M-L8E-D63 250 - 630 7580 100-D630... 315 540 140M-L8E-D63 250 - 630 7580 100-D630... 355 610 140M-L8E-D63 250 - 630 7580 100-D630... 1) Typical motor currents according IEC 60947-4-1 Table G.1 2) Incomplete catalog number, add coil and auxiliary contact codes 3) 100-K05 can also be taken 4) Tested at 42 kA short circuit current Note: This data is subject to change by Rockwell Automation without notice. Go to www.rockwellautomation.com/products/certifcation for latest information. 4) E125316 Type "1" Type "2" TS-1200-1A Type "2" Type "1" TS-1200-2A Motor Circuit Breaker S.C. Coordination 3) TS-1200-1A Type "2" 400V_65_MPCB File: SCCR-1200A 07-2012 PH

Upload: nicolas-a-selvaggio

Post on 22-Sep-2015

215 views

Category:

Documents


1 download

DESCRIPTION

Selección de Arrancadores en 2 Componentes

TRANSCRIPT

  • Short-circuit Coordination

    Starter Type: Direct-On-Line & Reversing, Trip Class 10Motor Protection Circuit Breaker (MPCB): 140M-C, D, F, I, J, LContactor: 100-C, 100-K, 100-DOverload Relay: ---Rated Operational Voltage: 400 V, 50 HzTest voltage: 436 V, 50HzRated Conditional S.C. Current (Iq): 65 kA (rms sym.)Level of S.C. Coordination: Type ''2'' (Type "1") per IEC 60947-4-1

    ContactorRated

    Operational Current I e

    CatalogNumber

    ThermalSettingRange

    MagneticTrip Current

    CatalogNumber

    CoordinationType

    TestSummary

    Letter Remark

    [kW] [A] 1) [A] [A] 2)

    0.06 0.20 140M-C2E-A25 0.16 - 0.25 3.3 100-C09...0.09 0.30 140M-C2E-A40 0.25 - 0.40 5.2 100-C09...0.12 0.44 140M-C2E-A63 0.40 - 0.63 8.2 100-C09...0.18 0.60 140M-C2E-A63 0.40 - 0.63 8.2 100-C09...0.25 0.85 140M-C2E-B10 0.63 - 1.00 13 100-C09...0.37 1.1 140M-C2E-B16 1.0 - 1.6 21 100-C09...0.55 1.5 140M-C2E-B16 1.0 - 1.6 21 100-C09...0.75 1.9 140M-C2E-B25 1.6 - 2.5 33 100-C09...1.1 2.7 140M-D8E-B40 2.5 - 4.0 52 100-C09...1.5 3.6 140M-D8E-B40 2.5 - 4.0 52 100-C09...2.2 4.9 140M-D8E-B63 4.0 - 6.3 82 100-C09...3 6.5 140M-D8E-C10 6.3 - 10 130 100-C09...4 8.5 140M-D8E-C10 6.3 - 10 130 100-C09...

    5.5 11.5 140M-D8E-C16 10 - 16 208 100-C12...7.5 15.5 140M-D8E-C20 14.5 - 20 260 100-C16...11 22 140M-D8E-C25 18 - 25 325 100-C23...15 29 140M-D8E-C32 27 - 32 448 100-C30...

    18.5 35 140M-F8E-C45 32 - 45 585 100-C37...22 41 140M-F8E-C45 32 - 45 585 100-C43...30 55 140M-I8E-C80E 40 - 80 1200 100-C60...37 66 140M-I8E-C80E 40 - 80 1200 100-C72...45 80 140M-I8E-C80E 40 - 80 1200 100-C85...55 97 140M-I8E-D10E 80 - 100 1500 100-C97...63 113 140M-J8E-D16 64 - 160 2240 100-D210... Type "2"63 113 140M-I8E-D16E 100 - 160 2400 100-D115... Type "1"75 132 140M-J8E-D16 64 - 160 2240 100-D210... Type "2"75 132 140M-I8E-D16E 100 - 160 2400 100-D140... Type "1"90 160 140M-J8E-D25 100 - 250 3500 100-D210... Type "2"90 160 140M-J8E-D25 100 - 250 3500 100-D180... Type "1"110 195 140M-J8E-D25 100 - 250 3500 100-D210...132 230 140M-J8E-D25 100 - 250 3500 100-D300...160 280 140M-L8E-D40 160 - 400 4800 100-D300...200 350 140M-L8E-D40 160 - 400 4800 100-D420...250 430 140M-L8E-D63 250 - 630 7580 100-D630...315 540 140M-L8E-D63 250 - 630 7580 100-D630...355 610 140M-L8E-D63 250 - 630 7580 100-D630...

    1) Typical motor currents according IEC 60947-4-1 Table G.12) Incomplete catalog number, add coil and auxiliary contact codes 3) 100-K05 can also be taken4) Tested at 42 kA short circuit current

    Note: This data is subject to change by Rockwell Automation without notice. Go to www.rockwellautomation.com/products/certifcation for latest information.

    4)E125316

    Type "1"

    Type "2" TS-1200-1A

    Type "2"

    Type "1"

    TS-1200-2A

    Motor Circuit Breaker S.C. Coordination

    3)

    TS-1200-1AType "2"

    400V_65_MPCBFile: SCCR-1200A 07-2012 PH