SCE Fault Locating, Prediction and Protection Project

Bob YingerSouthern California Edison

DOE Peer Review, Golden, CONovember 2, 2010

Page 2: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

2

© Copyright 2010, Southern California Edison

Southern California Edison

• 50,000 square miles• ~23,000 MW peak demand• 4.8 million customers• 11 million people served• 845 cities and communities

Page 3: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

3

© Copyright 2010, Southern California Edison

DOE Project - Completed

• Advanced Protection Methods on the Circuit of the Future– July 2006 to June 2010

• Three tasks:– Design and test new distribution protection scheme– Design and test distribution protection scheme with fault current limiter– Investigate, design and test advanced fault location, sensing and prediction

methods

• Other Team Members: – KEMA – Dr. S. S. Venkata– Virginia Tech – Dr. Virgilio Centeno

Page 4: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

4

© Copyright 2010, Southern California Edison

Project Benefits

• Reduce number of customers seeing outage• Reduce duration of outages for most customers• Better locate faults and dispatch crews to problem quickly• Reduce equipment cost• More flexible protection to help with integration of DG/

renewables

Page 5: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

5

© Copyright 2010, Southern California Edison

Schedule

Task 1 – New Protection Scheme– Initial operation – 8/2007– Dedication – 10/2007– Monitor the performance of the protection system

Task 2 – Protection w/FCL– Model FCL – 2008 through early 2009– Put FCL in service – 3/2009– Monitor the performance of the protection system

Task 3 – Advanced Protection– Evaluate measures – 2009– Design, model Irvine Smart Grid Demo protection system - 2010

Page 6: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

6

© Copyright 2010, Southern California Edison

Task 1 – Protection on the CoF

• Performed literature review• Distributed questionnaire about advanced protection

practices and projects• Prepared summary of both• Installed advanced fault detection and isolation system on

the SCE Circuit of the Future• Monitored behavior of protection system

Page 7: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

7

© Copyright 2010, Southern California Edison

Literature Review/Survey Summary

• Drivers for fault location, detection and prediction– Improvement of system reliability– System automation– Increased customer focus– Distributed generation/ renewables

• Key technologies– Affordable IEDs– Better transducers/ sensors– Accessible communications channels

• Level of development and acceptance of each of these technologies determine the time frame for implementation

Page 8: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

8

© Copyright 2010, Southern California Edison

Circuit of the Future (CoF)

• New circuit• Approximately 23,000 amps

fault duty• Serves approximately 2,000

customers• Overhead / underground

facilities• New hardware and protection

schemes• High-speed communications

with fiber

Page 9: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

9

© Copyright 2010, Southern California Edison

Circuit Features

Circuit Tie Switch

Circuit Tie Switch

Sweetwater 12KV

Northpark

12KVM

Typ. Load Transformer

Shandin Substation

Tie RCS

RCI2

Tie RCS

Fiber Optic Duct temp Monitoring

SystemSolid State

Fault Current Limiter

TieRCS

RAR

DistributedGeneration

G

USAT

RCI3RCI

1

SCADA System Gateway

Comm.

Fiber

SEL 2100Logic Processor

RCI = Remote Controlled Fault InterrupterRCS = Remote Controlled SwitchRAR = Remote Automatic Recloser

Circuit Tie Switch

Multi-Stage Capacitor Banks

Page 10: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

10

© Copyright 2010, Southern California Edison

Trip Blocking Scheme

RCI RCI

RCI

RARBlock Trip

Typical Time OvercurrentProtection betweenSub and RAR

Tie RCS

Tie RCS

Tie RCS

FAULT

Logic Processor Block Trip

Trip

Block Trip

Page 11: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

11

© Copyright 2010, Southern California Edison

Lab Testing and Training – Summer 2007

Page 12: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

12

© Copyright 2010, Southern California Edison

Circuit Fault Status – Four Faults Recorded

• 10/21/2007 (high winds)– Relay pick-ups, but no trip

• 12/25/2007 (high winds)– Protection operated correctly– Post-fault isolate function did not work due to problem with voltage

sensor location – Problem corrected Summer 2008

• 11/14/2008 (high winds)– Protection and isolation operated correctly– Most customers restored in minutes

• 1/30/2009 (high winds)– Protection and isolation operated correctly– Most customers restored in minutes

Page 13: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

13

© Copyright 2010, Southern California Edison

Task 2 - Protection with FCL

• Investigate and model protection changes necessary– Obtain/ construct model for Zenergy superconducting FCL and circuit– No changes needed due to reduced fault current– No changes needed due to distorted wave shapes– Bypass switch could be operated safely

• Commission fault current limiter (2/2009)

Page 14: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

14

© Copyright 2010, Southern California Edison

Magnet Disconnection Event (3/16/2009)

• De-energize superconducting magnet– Caused by processor reboot– Insert FCL impedance– Initially, 4% rise in voltage caused by

resonance with capacitors– Capacitor trip cause 4% reduction– Another capacitor turn on causing 3%

voltage rise– FCL bypassed

• Models upgraded to simulate the event accurately

• Repairs made and re-energized on 12/18/2009

Page 15: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

15

© Copyright 2010, Southern California Edison

Fault with FCL in Service (1/14/2010)

• FCL properly limited fault current– 8% fault current reduction– Matched what expected from fault current tests and models

• Harmonics– FCL insertion increases current harmonics < 0.5% THD– Voltage – increase from 1-1.5% steady-state to 2-5% during fault– Current – increase from 4-5% steady-state to 6-16% during fault

AI BI CIRMS 1713.26 1247.71 1214.08FND 100.00 100.00 100.00DC 0.79 -7.04 1.07THD 6.02 7.21 8.32

FCL Current Harmonics

THDH02

H03H04

H05H06

H07H08

H09H10

H11H12

H13H14

H15

012345678

%

A IHarm B IHarm C IHarm

Page 16: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

16

© Copyright 2010, Southern California Edison

Task 3 - Advanced Protection Schemes

• Evaluate measures and select most promising ones for modeling/implementation (focus on standards)

• Measures implemented:– Measure power quality upstream and downstream of the FCL– De-centralized sensing, control, protection, and automation– Design and model the System of the Future relay protection system

• System of the Future protection improvements over CoF– Loop two circuits to eliminate loss of power to customers beyond the

faulted section– Implement low-latency radio in place of costly fiber communications

for fault interrupting switches– Distribute protection logic in each relay

Page 17: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

17

© Copyright 2010, Southern California Edison

Advanced Protection on the System of the Future

• Use fault-interrupting switches with relays supporting IEC 61850

• Use Ethernet-based radio communications

• Communicate using GOOSE messaging (IEC 61850)

• GOOSE message latency allowed to be 100 ms

• Use substation breaker as backup• Intelligence located in each relay• This project designed logic and built

model of the circuits• Construct and implement under DOE

ARRA Irvine Smart Grid Demo project

Page 18: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

18

© Copyright 2010, Southern California Edison

Technology Transfer and Collaborations

• Presentations at conferences and meetings– IEEE T&D– Several EPRI PQA/ADA (now PQA/SD) meetings

• Share information with EPRI fault anticipation project

– Northwest Energy Symposium– IEEE PES meetings

• Updated regulatory agencies– California PUC– California Energy Commission

• Public dedication of Circuit of the Future

Page 19: SCE Fault Locating, Prediction and Protection Project 2010 Peer Review...SCE Fault Locating, Prediction and Protection Project Bob Yinger Southern California Edison. DOE Peer Review,

19

© Copyright 2010, Southern California Edison

Recommendations

• De-centralize sensing, control, protection, and automation– New sensors– Distributed intelligence– Distribution system communications– Real-time analysis and control

• Advanced and adaptive protection– Integration of renewable generation (distribution-based)– Microgrid protection

• Advanced DMS system with supervisory control over:– protection settings– Volt/VAR settings– Demand response operations– Distributed generation and storage use