3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/relayscontrols
SE-325 MANUAL
NEUTRAL-GROUNDING-RESISTOR MONITOR
REVISION 13-D-070615
F 1
R E S E TG R O U N D
F A U L T
G F T R I P
T I M E ( s )
R E S I S TO R
F A U L T
R E S T R I P
L E V E L ( V A C )
C T 1 C T 2 A B L 1 L 2
M O D E R E SG F
2 0 4 0 0
2 0 0
0 . 1 2 . 0
1 . 0
4 . 0 A
2 . 0 A
0 . 5 A
S H
U V 2 0 K
P O W E R
R GR IG IS W
N G R M O N I T O R
SE-325
Copyright 2015 by Littelfuse Startco
All rights reserved. Document Number: PM-1220-EN Printed in Canada.
Page i SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
This page intentionally left blank.
Page ii SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
TABLE OF CONTENTS SECTION PAGE
1 General ....................................................................... 1 1.1 Modern Resistance-Grounded Systems..................... 1 1.2 SE-325 NGR Monitoring ........................................... 1 2 Operation ................................................................... 1 2.1 Settings ........................................................................ 1 2.1.1 GF Trip Time .................................................. 1 2.1.2 GF ................................................................... 1 2.1.3 Mode ............................................................... 2 2.1.4 RES ................................................................. 2 2.1.5 RES Trip Level ............................................... 2 2.2 Indication and Reset ................................................... 2 2.3 Fusing .......................................................................... 2 3 Installation ................................................................. 3 3.1 SE-325 ........................................................................ 3 3.2 Ground-Fault CT ........................................................ 5 3.3 Sensing Resistor ......................................................... 6 3.4 Isolated-Ground Connection .................................... 15 3.5 Overhead Lines ......................................................... 15 3.6 Remote Operation..................................................... 15 3.7 Ground-Fault Testing ............................................... 15 4 Technical Specifications ........................................ 15 4.1 SE-325 ...................................................................... 15 4.2 Sensing Resistors ...................................................... 16 4.3 Current Transformers ............................................... 17 5 Ordering Information ............................................ 18 6 Warranty ................................................................. 18 7 Test Procedures ...................................................... 19 7.1 Ground-Fault Performance Test .............................. 19 7.2 Resistor-Fault Tests .................................................. 20 7.2.1 Open Test ...................................................... 20 7.2.2 Voltage Test .................................................. 20 7.3 Sensing-Resistor Test ............................................... 20 Appendix A SE-325 Revision History .............................. 21
LIST OF FIGURES FIGURE PAGE
1 Typical Application ...................................................... 3 2 SE-325 Outline and Mounting Details ......................... 4 3 CT200 and CT200L Current Transformers ................. 5 4 ER-600VC Sensing Resistor ........................................ 6 5 SE-MRE-600 Moisture-Resistant Enclosure...............7 6 SE-MRE-600 with Installed ER-600VC .....................8 7 ER-5KV Sensing Resistor ............................................ 9 8 ER-5WP Sensing Resistor .......................................... 10 9 ER-15KV Sensing Resistor ........................................ 11 10 ER-25KV Sensing Resistor ........................................ 12 11 RK-302 Remote Indication and Reset Kit ................. 13 12 RK-325 Remote Indication-and-Reset Assembly ..... 13 13 RK-325I Remote Indication Assembly ...................... 14 14 RK-13 Relay Interface Module .................................. 14 15 Ground-Fault-Test Circuits ......................................... 19
LIST OF TABLES TABLE PAGE
1 Settings For Typical Systems ....................................... 2 2 Ground-Fault-Test Record .......................................... 19
DISCLAIMER Specifications are subject to change without notice. Littelfuse Startco is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction.
Page iii SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
This page intentionally left blank.
Page 1 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
1. GENERAL
1.1 MODERN RESISTANCE-GROUNDED SYSTEMS
A high-resistance-grounded system uses a neutral-grounding resistor (NGR) with a low let-through current to limit ground-fault current. This is an improvement over low-resistance- or solidly grounded systems because, in those systems, a ground-fault flash hazard exists and a ground fault can result in substantial point-of-fault damage. High-resistance grounding eliminates these problems and modern ground-fault protection operates reliably at these levels. Furthermore, the probability of an arc-flash incident is significantly reduced in a high-resistance-grounded system. NGR selection depends on system charging current and whether the system is an alarm-only or a tripping system. Alarm-only systems are usually restricted to system voltages up to 5 kV with NGR let-through currents of 5 A or less. Occasionally, alarm-only systems up to 15 kV and up to 10 A are used; however, they are not common because a ground fault on such a system tends to escalate to a phase-to-phase fault before the ground fault can be located and cleared. System charging current is the capacitive current that flows to ground when a bolted ground fault occurs. This current can be calculated or measured. For small systems, the magnitude of charging current can be conservatively estimated as ½ A per 1,000 kVA on low-voltage systems and 1 A per 1,000 kVA on medium-voltage systems. In an alarm-only system or in a tripping system without selective coordination, choose an NGR with a let-through current larger than the system charging current and set the pick-up current of ground-fault devices at or below 50% of the NGR let-through current. In a tripping system with selective coordination, use ground-fault devices with a definite-time characteristic to achieve time coordination. Use the same pick-up current for all ground-fault devices—this value must be larger than the charging current of the largest feeder. Select an NGR with a let-through current between five and ten times the pick-up current of the ground-fault devices. Do not use a grounding transformer with a low-voltage resistor: The combined cost of a transformer and a low-
voltage resistor is more than the cost of a resistor rated for line-to-neutral voltage.
A transformer saturated by a ground fault through a rectifier can make ground-fault protection inoperative.
Transformer inrush current up to twelve times rated current can cause a ground-fault voltage larger than expected.
A parallel transformer winding makes it difficult to monitor NGR continuity.
A transformer can provide the inductance necessary to cause ferroresonance if the NGR opens.
Following these guidelines will reduce the flash hazard, reduce point-of-fault damage, achieve reliable ground-fault protection, and ensure a stable system not subject to ferroresonance. 1.2 SE-325 NGR MONITORING
The SE-325 is a neutral-grounding-resistor monitor for resistance-grounded systems up to 25 kVac. It measures current in a transformer or generator neutral, neutral-to-ground voltage, and continuity of the neutral-grounding resistor. The SE-325 coordinates these three measurements to detect a failed NGR or a ground fault and provides one output contact for shunt or undervoltage operation in a main-breaker trip circuit. Trips are latched and indicated by LED’s. Ground-fault current is sensed by a CT200 window-type current transformer. Either CT input can be grounded to meet electrical codes. A trip level of 0.5, 2.0, or 4.0 A is switch selectable for use with a 5-, 15-, or 25-A grounding resistor. Trip time is adjustable from 0.1 to 2.0 seconds. Neutral-to-ground voltage and continuity of the neutral-grounding resistor are continuously measured through an ER-series external sensing resistor connected to the neutral. A resistor fault will be detected if ground-fault current is not detected and neutral-to-ground voltage exceeds the trip-level setting, or if NGR resistance exceeds the trip resistance. A resistor-fault hold-off circuit prevents nuisance trips in alarm-only systems. For additional information on neutral-grounding-resistor monitoring, see “Monitoring Neutral-Grounding Resistors – An Update” at www.littelfuse.com/relayscontrols.
2. OPERATION 2.1 SETTINGS 2.1.1 GF TRIP TIME Ground-fault trip time is adjustable from 0.1 to 2.0 seconds. Time-coordinated ground-fault protection requires this setting to be longer than the trip times of downstream ground-fault devices. For the extended ground-fault trip-time option (Option T), trip time is adjustable from 0.1 to 5.0 seconds. 2.1.2 GF The ground-fault-circuit trip level is 0.5, 2.0, or 4.0 A when current is sensed with a CT200 current transformer. These levels are appropriate for use with 5-, 15-, or 25-A grounding resistors, when a ground-fault trip level less than 20% of the grounding resistor let through current is desired. See Table 1. For other applications, the trip level of the ground-fault circuit is 0.25, 1.0, or 2.0% of the primary rating of the 5-A-secondary current transformer.
Page 2 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
2.1.3 MODE In the shunt-trip mode (SH), the output relay energizes and its contact closes if a resistor-fault or ground-fault trip occurs. The shunt-trip mode is not fail-safe because shunt-trip devices do not operate if supply voltage fails. In the undervoltage mode (UV), the output relay energizes and its contact closes if the resistor-fault and ground-fault circuits are not tripped. The undervoltage mode is referred to as fail-safe because undervoltage devices release if supply voltage fails. 2.1.4 RES This switch setting must correspond to the resistance of the external sensing resistor. For the ER-600VC and ER-5KV, select 20K. For the ER-15KV and ER-25KV, select 100K. 2.1.5 RES TRIP LEVEL Neutral-to-ground trip voltage is adjustable from 20 to 400 Vac with a 20-k sensing resistor, and 100 to 2,000 Vac with a 100-k sensing resistor. To prevent false resistor-fault trips, the RES TRIP LEVEL should be set higher than the voltage across the neutral-grounding resistor when neutral-to-ground current is equal to the operating value of the ground-fault circuit. Typical values for 5-, 15-, and 25-A tripping systems are shown in Table 1. For other systems, refer to the NGR Monitor Set-Point Assistant at www.littelfuse.com/relayscontrols.
2.2 INDICATION AND RESET The blue POWER LED indicates that the internal power supply is on. Red LED’s indicate ground-fault and resistor-fault trips. When a trip occurs, the SE-325 remains latched until Reset is pressed or supply voltage is cycled. Terminals are provided for remote indication and reset as shown in Fig. 1. For the non-latching option (Option N), the SE-325 resets when the fault clears. 2.3 FUSING The output contact is protected by fuse F1 (4.0 A, time delay).
TABLE 1. SETTINGS FOR TYPICAL SYSTEMS
System Voltage
Neutral-Grounding Resistor
Sensing Resistor
Ground-Fault Trip Level
ResTrip Level
(Volts)
Let Through (Amperes)
Resistance (Ohms)
Model Resistance (Ohms)
(Amperes)
(Volts)
480 600
2,400 4,160
480 600
2,400 4,160 7,200
14,400 7,200
14,400 25,000
5 5 5 5
15 15 15 15 15 15 25 25 25
55 69
277 480 18 23 92
160 277 554 166 332 577
ER-600VC ER-600VC ER-5KV ER-5KV ER-600VC ER-600VC ER-5KV ER-5KV ER-15KV ER-15KV ER-15KV ER-15KV ER-25KV
20,000 20,000 20,000 20,000 20,000 20,000 20,000 20,000
100,000 100,000 100,000 100,000 100,000
0.5 0.5 0.5 0.5 2.0 2.0 2.0 2.0 2.0 2.0 4.0 4.0 4.0
30 40
140 240 40 50
190 320 600
1,100 700
1,400 2,000
Page 3 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
3. INSTALLATION 3.1 SE-325 SE-325 outline and mounting details are shown in Fig. 2. Typical connections are shown in Fig. 1. Connect supply voltage to L1 and L2. For a 120-Vac supply, connect supply neutral to L2. For a direct-current supply, connect supply negative to L2. Connect chassis-bonding terminal to ground. Connect contact terminals A and B as required.
Faceplate LED’s are driven in series with remote-indication LED’s. When remote-indication LED’s are not used, terminals GI, +, and RI must be connected for the face-plate LED’s to operate. These jumpers are installed at the factory. Install the upper terminal-block cover to prevent inadvertent contact with line terminals.
R IG IS W R G
N G R M O N I T O RSE-325
RS1
RS2
CGI
GRI
+SW K1 K2
SW CI/GI + GI/RI
TB1
ALTERNATERESET CIRCUIT
+
R IG IS W R G
N G R M O N I T O RSE-325
RS1
RS2
CGI
GRI
+SW K1 K2
SW CI/GI + GI/RI
TB1
R IG IS W R G
N G R M O N I T O RSE-325
NOTES 2 & 3
F 1
R E S E TG R O U N DF A U L T
G F T R I PT I M E ( s )
R E S I STO RF A U L T
R E S T R I PL E V E L ( V A C )
C T 1 C T 2 A B L 1 L 2
M O D E R E SG F2 0 4 0 0
2 0 0
0 . 1 2 . 0
1 . 0
4 . 0 A
2 . 0 A0 . 5 A
S H
U V 2 0 KP O W E R
R GR IG IS W
N G R M O N I T O RSE-325
N
R
G
ER-600VCS E NS I N G R E S I STO R
2 0 K 6 0 0 V A C M A X
SUPPLY
4160 V 600 V
CT200GROUND-FAULT CT
LOAD
UV
120 VAC
L NNOTE 1
NEUTRALGROUNDING RESISTOR
NOTE 4ER
RESISTOR-FAULTINDICATOR
GROUND-FAULTINDICATOR
RESET SWITCH
RI
GI
SW
RED
RED
REMOTE INDICATION AND RESET
ER
RESISTOR-FAULTINDICATOR
GROUND-FAULTINDICATOR
RESET SWITCH
RI
GI
SW
RED
RED
K1 K2
24-120 Vac/Vdc
RK-13 CONNECTION WITH REMOTE INDICATION AND RESET
RK-13 CONNECTION WITHOUT REMOTE INDICATION AND RESET
ER
K1 K2
NOTES:
1. ALTERNATE SENSING-RESISTOR TERMINAL-N CONNECTION THE NEUTRAL CONNECTION IS NOT MONITORED.
2. K1 CLOSES ON GROUND-FAULT TRIP.
3. K2 CLOSES ON REISISTOR-FAULT TRIP.
4. VOLTAGE BETWEEN ER TERMINALS R AND G LIMITED TO 100 V BY INTERNAL CLAMP.
CAUTION: DO NOT USE K1 OR K2 IN A TRIP CIRCUIT.
FIGURE 1. Typical Application.
Page 4 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
F 1
R E S E TG R O U N DF A U L T
G F T R I PT I M E ( s )
R E S I S T O RF A U L T
R E S T R I PL E V E L ( V A C )
C T 1 C T 2 A B L 1 L 2
M O D E R E SG F2 0 4 0 0
2 0 0
0 . 1 2 . 0
1 . 0
4 . 0 A
2 . 0 A0 . 5 A
S H
U V 2 0 KP O W E R
R GR IG IS W
N G R M O N I T O RSE-325
109.0(4.29)
88.9(3.50)
43.5
(1.7
1)
139.
7(5
.50)
150.
0
(5.9
0)
4.8 (0.19) DIA
NOTE 5
100.0(3.93)
77.8(3.06)
NOTE 4
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25.
3. MOUNTING SCREWS: M4 OR 8-32.
4. SHOWN WITH TERMINAL-BLOCK COVER REMOVED.
5. MINIMUM CLEARANCE FOR FUSE REMOVAL.
FIGURE 2. SE-325 Outline and Mounting Details.
Page 5 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
3.2 GROUND-FAULT CT Outline and mounting details for CT200 and CT200L current transformers are shown in Fig. 3. Ground-fault-CT connections and the typical ground-fault-CT location are shown in Fig. 1. Connect the secondary of the ground-fault CT to SE-325 terminals CT1 and CT2. The CT connection to the SE-325 is not polarity sensitive. Ground one side of the CT secondary. For electrically noisy environments or lead
lengths in excess of 10 m (30”), use shielded, twisted-pair cable. NOTE: The CT200 and CT200L are 600-V-rated current transformers. When system voltage is above 600 V, ensure conductors passed through the sensor window are insulated to system voltage.
D
E
A
B
FRONT
44.5 MAX(1.75)
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. MOUNTING SCREWS: M4 OR 8-32.
X1 X2
BLACK
WHITE
SIDE
9.4(0.37)
F
B
C22
.2(0
.87)
44.5
(1.7
5)
TAP M4 OR 8-32
BOTTOM MOUNTING DETAIL
PARTNUMBER
DIMENSIONS
CT200
CT200L
A
55.9 (2.20)
88.9 (3.50)
B
120.7 (4.75)
154.0 (6.06)
C
101.6 (4.00)
133.4 (5.25)
D
98.3 (3.87)
139.7 (5.50)
E
108.0 (4.25)
144.5 (5.69)
F
5.6 (0.22)
7.1 (0.28)
FIGURE 3. CT200 and CT200L Current Transformers.
Page 6 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
3.3 SENSING RESISTOR Outline and mounting details for ER-600VC, ER-5KV, ER-15KV, and ER-25KV sensing resistors are shown in Figs. 4, 7, 9, and 10. Locate the NGR and the sensing resistor near the transformer or generator. When located outdoors, a sensing resistor must be installed in a suitable enclosure. An optional SE-MRE-600 Moisture Resistant Enclosure is available for applications which may expose an ER-600VC to moisture. See Figs. 5 and 6. The ER-5WP (shown in Fig. 8) is an ER-5KV with moisture-resistant terminal covers. The ER-15KV and ER-25KV include moisture resistant terminal covers. Use suitable water-tight fittings. Ground sensing-resistor terminal G. Pass the sensing-resistor-to-neutral conductor and the NGR-to-neutral conductor through the ground-fault-CT window as shown in Fig. 1.
Separately connect sensing-resistor terminal N and the NGR to the neutral to include neutral connections in the monitored loop. If a ground fault in the sensing-resistor conductor is unlikely, a minimal loss of protection will result if it does not pass through the ground-fault-CT window. CAUTION: Voltage at terminal N rises to line-to-neutral voltage when a ground fault occurs. The same clearances are required for sensing resistors as for NGR’s. NOTE: The neutral-to-sensing-resistor connection is not a neutral conductor as defined in Canadian Electrical Code Section 10-1108 and National Electrical Code Section 250.36(B). It is not required to be 8 AWG (8.36 mm2) or larger. Since current through this conductor is always less than 150 mA, a 14 AWG (2.08 mm2) conductor insulated to the system voltage is sufficient.
..
. . . . . . .
. . . . . . . . . .
. . . . . . . . . .
N
R
G
ER-600VCSE N S I N G RE S I STO R
20 K Ω6 00 V AC MA X
RATINGS:MAXIMUM VOLTAGE 600 VacMAXIMUM CURRENT 30 mARESISTANCE 20 kΩTHERMAL:
420 Vac CONTINUOUS
600 Vac 6 MINUTES ON,60 MINUTES OFF
40.0
(1.57)
105.
0
(4.1
3)
4.5 (0.18) DIAC’BORE 10.0 (0.39) DIA3.2 (0.13) DEEP
FRONT
41.5
(1.63)
22.2
(0.87)
8.0
(0.3
1)
10.5
(0.41)
40.0
(1.57)
19.0
(0.75)
10.5
(0.41)
NOTE 3
105.
0
(4.1
3)
89.0
(3.5
0)
8.0
(0.3
1)
SIDE MOUNTING DETAIL
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25.
3. MOUNTING SCREWS: M4 OR 8-32.
4. ON REVISION 2 UNITS ENCLOSURE IS ELECTRICALLY CONNECTED TO TERMINAL G THROUGH JUMPER FROM TERMINAL G TO SCREW. THIS CONNECTION MAY BE REMOVED FOR DIELECTRIC STRENGTH TESTING. ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING.
5. ON REVISION 1 UNITS, SCREW IS NOT PRESENT AND ENCLOSURE IS ELECTRICALLY CONNECTED TO TERMINAL G.
FIGURE 4. ER-600VC Sensing Resistor.
Page 7 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
COVER - INSIDE VIEW
GASKET
120.4(4.74)
122.0
(4.80)
ENCLOSURE - SIDE VIEW
84.6
(3.3
3)
120.4
(4.74)
20.4
(0.80) NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
120.4(4.74)
122.
0
(4.8
0)
ENCLOSURE - TOP VIEW
ENCLOSURE - TOP VIEW(COVER REMOVED)
122.
0
(4.8
0)
120.4(4.74)
MOUNTING DETAIL
9.5
(0.38)
82.5(3.25)
19.1
(0.75)
82.5
(13.25)
M6 OR 0.25-20
2. MOUNTING SCREWS: M6 OR 0.25-20.
FIGURE 5. SE-MRE-600 Moisture-Resistant Enclosure.
Page 8 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
N
R
G
ER-600VCSE N S I N G RE S I STO R
20 K Ω6 00 V AC MA X
ENCLOSURE - TOP VIEW(COVER REMOVED)
COVER - INSIDE VIEW
ASSEMBLY INSTRUCTIONS
1. DRILL HOLE FOR ENCLOSURE WIRE ENTRY. USE LIQUID-TIGHT FITTING.
3. ATTACH GROUND WIRE FROM ENCLOSURE TO COVER AND TO ER-600VC TERMINAL G.
2. REMOVE NYLON NUTS AND WASHERS. INSERT ER-600VC INTO ENCLOSURE. REPLACE NUTS AND WASHERS.
4. MOUNT SE-MRE-600 IN PLACE USING M6 OR 0.25-20.
5. COMPLETE OTHER WIRING AND REPLACE COVER.
NOTE 3
NOTE 2
NOTE 2
MOUNTING SCREWS 4 LOCATIONSNOTE 4
FIGURE 6. SE-MRE-600 with Installed ER-600VC.
Page 9 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
GR
N
.
.. . . . . . .
. . . . . . . . . .
ER -5 KVS E N S I N G R E S I TO RS
2 0 KΩ
2 5 0 0 V A C M A X
RATINGS:MAXIMUM VOLTAGEMAXIMUM CURRENTRESISTANCETHERMAL CONTINUOUS
20 kΩ125 mA2,500 Vac
105.
0(4
.13)
52.5
(2.0
7)7.
9(0
.31)
12.0(0.47)
21.0(0.83)
381.0(15.00)
ALTERNATE NEUTRAL CONNECTION
NEUTRAL CONNECTION
0.25-20 UNCTHREADED INSERT
10-32 THREADED INSERT
TOP VIEW316.0(12.44)
0.25-20 UNC STUD
188.
0(7
.40)
FRONT VIEW
NOTE 2
NOTES 5 & 6
SIDE VIEW
MINIMUM DISTANCETO ADJACENT OBJECTS
NOTE 3
MINIMUM CLEARANCE FROM BASE254.0 (10.00)
127.
0
(5.0
0)25
4.0
(10.
00)
355.6
(14.00)
457.0(18.00)
50.7(2.00)
MOUNTING DETAIL
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25.
3. MOUNTING SCREWS: M6 OR 0.25-20.
4. THIS DEVICE CAN DISSIPATE 300 WATTS. TO MINIMIZE SURFACE TEMPERATURES FOR SYSTEMS ALLOWED TO OPERATE CONTINUOUSLY WITH A GROUND FAULT, MOUNT VERTICALLY WITH R & G TERMINALS DOWN.
5. ON REVISION 2 UNITS BASE IS ELECTRICALLY CONNECTED TO TERMINAL G THROUGH JUMPER FROM TERMINAL G TO SCREW. THIS CONNECTION MAY BE REMOVED FOR DIELECTRIC STRENGTH TESTING. ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING.
6. ON REVISION 0 & 1 UNITS SCREW IS NOT PRESENT AND BASE IS ELECTRICALLY CONNECTED TO TERMINAL G.
7. CERTIFICATIONS NOT SHOWN.
. . . . .
TORQUE
5.6 N-m (50 in-lb)
N
N
TERMINAL N (3 LOCATIONS) 10-32 INSERTOTHERS . . . . . 9.0 N-m (80 in-lb). . ..
FIGURE 7. ER-5KV Sensing Resistor.
Page 10 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
N
ER -5WPS E N S I N G R E S I TO RS
2 0 KΩ
2 5 0 0 V A C M A X10
5.0
(4.1
3)52
.5(2
.07)
7.9
(0.3
1)
12.0(0.47)
21.0(0.83)
381.0(15.00)
ALTERNATE NEUTRAL CONNECTION
NEUTRAL CONNECTION
0.25-20 UNCTHREADED INSERT
10-32 THREADED INSERT
TOP VIEW316.0(12.44)
0.25-20 UNC STUD
188.
0(7
.40)
FRONT VIEWSIDE VIEW
MINIMUM DISTANCETO ADJACENT OBJECTS
NOTE 3
MINIMUM CLEARANCE FROM BASE254.0 (10.00)
127.
0
(5.0
0)25
4.0
(10.
00)
355.6
(14.00)
457.0(18.00)
50.7(2.00)
MOUNTING DETAIL
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25 CABLE ACCESS OPENING IS 1/2 NPT. USE A LIQUID-TIGHT FITTING FOR CABLE ENTRY.
3. MOUNTING SCREWS: M6 OR 0.25-20.
4. THIS DEVICE CAN DISSIPATE 300 WATTS. TO MINIMIZE SURFACE TEMPERATURES FOR SYSTEMS ALLOWED TO OPERATE CONTINUOUSLY WITH A GROUND FAULT, MOUNT VERTICALLY WITH R & G TERMINALS DOWN.
5. BASE IS ELECTRICALLY CONNECTED TO TERMINAL G THROUGH JUMPER FROM TERMINAL G TO SCREW. THIS CONNECTION MAY BE REMOVED FOR DIELECTRIC STRENGTH TESTING. ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING.
6. CERTIFICATIONS NOT SHOWN.
NOTE 2 AND 5
N
N
.
.. . . . . . .
. . . . . . . . . .
RATINGS:MAXIMUM VOLTAGEMAXIMUM CURRENTRESISTANCETHERMAL CONTINUOUS
20 kΩ125 mA2,500 Vac
. . . . .
TORQUE
5.6 N-m (50 in-lb)TERMINAL N (3 LOCATIONS)
10-32 INSERTOTHERS . . . . . 9.0 N-m (80 in-lb). . ..
FIGURE 8. ER-5WP Sensing Resistor.
Page 11 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
N
. ..
. . . . . . .
. . . . . . . . . .
R
G
ER - 1 5 KVS E N S I N G R E S I S T O R
1 0 0 K Ω
84 0 0 V A C M A X
1 M I N UT E M A X
144.
0(5
.67)
NOTES 2 AND 4
422.0
(16.61)
132.
0(5
.20)
20.5
(0.8
1)0.25-20 BINDING HEAD
TOP
RATINGS:MAXIMUM VOLTAGE 8,400 VacMAXIMUM CURRENT 84 mARESISTANCE . 100 kΩTHERMAL
1 MINUTE ON, 120 MINUTESOFFCONTINUOUS
215.
0
(8.4
6)
FRONT SIDE
39.5(1.56)
444.0
(17.50)365.0(14.37)
39.5
(1.56)
MINIMUM DISTANCETO ADJACENT OBJECTS
NOTE 3
MINIMUM CLEARANCE FROM BASE305.0 (12.00)
90.0
(3.5
3)10
0.0
(3.9
4)90
.0
(3.5
3)
280.
0(1
1.00
)
MOUNTING DETAIL
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25.
3. MOUNTING SCREWS: M6 OR 0.25-20.
4. USE LIQUID-TIGHT FITTING FOR TERMINAL-BLOCK- ENCLOSURE CABLE ENTRY.
5. CERTIFICATIONS NOT SHOWN.
TORQUE TERMINAL N . . . . . 9.0 N-m (80 in-lb). . .
8,400 Vac
1,900 Vac . . . . . . . . . .
FIGURE 9. ER-15KV Sensing Resistor.
Page 12 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
MINIMUM DISTANCETO ADJACENT OBJECTS
..
. . . . . . .R
G
N
ER-25 KVSE NS I NG R ES I ST O R
100 K Ω1 4 ,4 00 V A C MA X
1 M I N UT E MA X
144.
0(5
.67)
NOTES 2 AND 4
20.5
(0.8
1)0.25-20 BINDING HEAD
780.0(30.70)
RATINGS:MAXIMUM VOLTAGE 14,400 VacMAXIMUM CURRENT 144 mARESISTANCE 100 kΩ
TOP
320.
0(1
2.60
)
FRONT SIDE
60.0(2.40)
800.0(31.50)
340.0(13.38)
340.0(13.38)
534.
0(2
1.00
)21
7.0
(8.5
0)10
0.0
(3.9
4) NOTE 3
MINIMUM CLEARANCE FROM BASE508.0 (20.00)
MOUNTING DETAIL
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25.
3. MOUNTING SCREWS: M6 OR 0.25-204. USE LIQUID-TIGHT FITTING FOR TERMINAL-BLOCK- ENCLOSURE CABLE ENTRY.
5. MOUNT AS SHOWN WITH BASE HORIZONTAL.
6. CERTIFICATIONS NOT SHOWN.
TORQUE TERMINAL N . . . . . 9.0 N-m (80 in-lb). .
. . . . . . . . .THERMAL
1 MINUTE ON, 120 MINUTESOFFCONTINUOUS
14,400 Vac
2,500 Vac . . . . . . . . .
FIGURE 10. ER-25KV Sensing Resistor.
Page 13 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. ----- INDICATES CLEARANCE REQUIRED.
3. PANEL THICKNESS 1.0 TO 6.0 (0.04 TO 0.24).
4. NEMA 4X.
5. CERTIFICATIONS NOT SHOWN.
30.0(1.18)
22.2 (0.87) DIA
25.0
(0.9
8)
15.0
(0.5
9)
22.5
(0.8
9)
MOUNTING DETAIL
30.0 MINIMUM
(1.18)
40.0
MIN
IMU
M
(1.5
7)
36.6(1.44)
17.3(0.68)
29.9
(1.17)
43.5
(1.7
1)
36.6(1.44)
14.9
(0.59)
29.9(1.17)
43.5
(1.7
1)
LEGEND PLATE
LEGEND PLATES
RESET GROUND FAULT
NOTE 2
LED PILOT LIGHTS
PUSH BUTTON
RESISTOR FAULT
FIGURE 11. RK-302 Remote Indication and Reset Kit.
CI/RI+GISW
RK-325
R
RESISTOR FAULT
GROUND FAULT
RESET
30.0(1.18)
25.0(0.98)
96.0
(3.7
8) 76.0
(3.0
0)10
.0(0
.40)
7.7
(0.30)
60.0(2.36)
44.5(1.75)
28.6
(1.1
3)
22.3(0.88)
3.8 (0.15)DIA
1.25”CONDUIT
KNOCKOUT1.70” DIA
SIDE VIEW FRONT VIEW MOUNTING DETAIL
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. NEMA 1.
OUTLINE
FIGURE 12. RK-325 Remote Indication-and-Reset Assembly.
Page 14 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
CI/RI+GISW
RK-325 I
R
RESISTOR FAULT
GROUND FAULT
30.0(1.18)
25.0(0.98)
96.0
(3.7
8) 76.0
(3.0
0)10
.0(0
.40)
7.7
(0.30)
60.0(2.36)
44.5(1.75)
28.6
(1.1
3)
22.3(0.88)
3.8 (0.15)DIA
1.25”CONDUIT
KNOCKOUT1.70” DIA
SIDE VIEW FRONT VIEW MOUNTING DETAIL
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. NEMA 1.
OUTLINE
FIGURE 13. RK-325I Remote Indication Assembly.
RS1
RS2
CGI
GRI
+SW K1 K2
RS1
RS2
CGI
GRI
+SW K1 K2
TB1
SW CI/GI + GI/RI
31.0
(1.2
2)
47.5
(1.8
7)
60.2(2.37)
SIDE VIEWRK-13 SHOWN MOUNTED ON SE-105/SE-107/SE-325
21.0
(0.8
3)
INSTALLATION INSTRUCTIONS:
1. REMOVE FOUR LEFTMOST LOWER TERMINAL BLOCK SCREWS.
2. PLACE RK-13 ON TERMINAL BLOCK AND REPLACE SCREWS.
3. MAKE REQUIRED CONNECTIONS TO TERMINAL BLOCK TB1.
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. CERTIFICATIONS NOT SHOWN.
FIGURE 14. RK-13 Relay Interface Module.
Page 15 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
3.4 ISOLATED-GROUND CONNECTION The SE-325 is intended for use in installations where the NGR is connected to local ground. Some installations require the NGR to be isolated from local ground. See Technical Note RG-1 “NGR Monitoring with Isolated Ground Beds” at www.littelfuse.com/relayscontrols. 3.5 OVERHEAD LINES In overhead-line applications, atmospheric conditions can cause false resistor-fault trips. The “S” option or an SE-330 NGR Monitor is recommended for these applications. 3.6 REMOTE OPERATION Terminals SW, GI, +, and RI are provided for remote LED indication and remote reset as shown in Fig. 1. Remote LED’s are driven in series with the front-panel LED’s. Remove factory-installed jumpers from terminals GI, +, and RI, and connect a remote kit as shown in Fig. 1. Optional remote kits are shown in Figs. 11, 12, and 13. Standard LED indicator lamps are not compatible with the SE-325. For general-purpose applications, use the RK-325 Remote Indication-and-Reset Assembly or the RK-325I Remote Indication Assembly. Connect terminals SW, GI, +, and RI to remote-kit terminals SW, GI, +, and CI/RI. For 22-mm-component applications, use the RK-302 Remote Indication and Reset Kit. Connect terminal X2 of the red ground-fault indicator to GI, terminal X2 of the red resistor-fault indicator to RI, and connect indicator X1 terminals to +. For remote reset, connect the normally open push-button switch across terminals + and SW. If indication is required from a separate voltage source, or if separate ground-fault and resistor-fault contacts are required, use an RK-13 Relay Interface Module. The RK-13 mounts on the SE-325 lower terminal block and it is compatible with the RK-302, RK-325 and RK-325I. See Figs. 1 and 14. Contact K1 closes when the Ground-Fault LED is on and contact K2 closes when the Resistor-Fault LED is on. 3.7 GROUND-FAULT TESTING Use CT-primary current injection to test the ground-fault circuit. Fig. 15 shows test circuits using the SE-400 Ground-Fault-Relay Test Unit and the SE-100T Ground-Fault-Relay Tester. The SE-400 has a programmable output of 0.5 to 9.9 A for a duration of 0.1 to 9.9 seconds. The SE-100T has LO and HI outputs for 5- and 15-A resistance-grounded systems. A test-record form is provided in Section 7 of this manual. Record the test results and test dates on this form to meet the requirements of the National Electrical Code (NEC). Retain the form so that the test data can be made available to the authority having jurisdiction.
4. TECHNICAL SPECIFICATIONS
4.1 SE-325 Supply: ac ............................................ 10 VA, 120 or 240 Vac
(+10, -45%), 50/60 Hz ac/dc ....................................... 5 W, 120 Vdc (+40, -8%);
10 VA, 120 Vac (+10, -45%), 50/60 Hz
NOTE: Voltage between supply terminals (L1, L2) and ground terminal (G) must not exceed 300 Vac continuous or 1,250 Vac under transient conditions. Dimensions: Height .................................... 150 mm (5.9”) Width ..................................... 109 mm (4.3”) Depth ..................................... 100 mm (4.0”) Shipping Weight.......................... 1 kg (2.2 lb) Environment: Operating Temperature ......... -40 to 60°C (-40 to 140°F) Storage Temperature ............. -55 to 80°C (-67 to 176°F) Humidity ................................ 85% Non-Condensing Ground-Fault Circuit: CT Ratio ................................ 200:5 CT Input Burden ................... 0.02 Trip Level (1) .......................... 0.5, 2.0, or 4.0 A Frequency Response(2) ........ 25 to 110 Hz Trip Time ............................... 0.1 to 2.0 s,
0.1 to 5.0 s with Option T Thermal Withstand (1) ............ 200 A Continuous,
2,500 A for 2 s Trip-Level Accuracy ............. +10, -20% CT Lead Resistance Limit (3) 0.5 A Trip Level .............. 2 2 A Trip Level ................. 5 4 A Trip Level ................. 5 Trip-Time Accuracy .............. 10% Trip Mode .............................. Latching,
Non-latching with Option N
Page 16 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
Resistor-Fault Circuit: Neutral-To-Ground Trip Voltage (VN) .................. 20 to 2,000 Vac Adjustable NGR Trip Resistance, VN = 0: ER-600VC or ER-5KV ...... 2 k ER-15KV or ER-25KV ...... 6 k, 50 k with Option S Neutral-To-Ground DC-Voltage Rejection: ER-600VC or ER-5KV ...... 1.2 V ER-15KV or ER-25KV ...... 0.7 V, 4 V with Option S Trip-Resistance Accuracy ..... +5, -2% of Sensing Resistor Resistance Trip Time ............................... 5 ± 0.5 s, 20 ± 3 s with
Option S Trip Mode .............................. Latching, Non-latching
with Option N Output Relay: CSA/UL Contact Rating ....... 1 mA to 4 A Resistive,
240 Vac or 28 Vdc Supplemental Contact Ratings: Make/carry 0.2 s ................. 10 A Carry continuous ................ 4 A Break: dc ...................................... 20 W resistive,
10 W inductive (L/R = 0.04 s)
ac ...................................... 960 VA resistive, 700 VA inductive (PF = 0.4)
Subject to maximums of 4 A and 240 V (ac or dc) Contact Configuration ........... N.O. (Form A) Fuse Rating (F1) .................... 4.0 A, 250 Vac,
Time Delay Fuse Part Number .................. Bussman MSL-4 or
Littelfuse 313004. Operating Mode ..................... UV (Fail-Safe) or
SH (Non-Fail-Safe) Remote Indication: + ............................................. 12 Vdc GI/RI ...................................... Current Sink,
560 Internal Optional RK-13 Module: Contact Ratings................... 0.08 A, 120 V (ac or dc),
0.50 A, 24 Vdc Contact Configuration ........ N.O. (Form A) Reset Input .......................... 24 to 120 V (ac or dc),
Isolated PWB Conformal Coating ............ MIL-1-46058 qualified,
UL QMJU2 recognized
Certification ............................. CSA, Canada and USA
LR 53428
USC
R
UL Listed
Australia(4)
N11659
Commonwealth of Pennsylvania
SE-325 BOTE 1767-99 SE-325P BOTE 1797-00
FCC
NOTES: (1) Currents referred to primary of CT200 for prospective
ground-fault currents less than 4,000 A. (2) Prior to hardware revision 11, standard unit freq. rep.
was 25 to 400 Hz and option H was 25 to 110 Hz. (3) Typical maximum CT lead resistance to meet specified
trip level accuracy. (4) Applicable only on 240 Vac Supply (Option E in the
ordering information). 4.2 SENSING RESISTORS ER-600VC: Maximum Voltage .............. 600 Vac Maximum Current .............. 30 mA Resistance ........................... 20 k Thermal: 420 Vac ............................... Continuous 600 Vac ............................... 6 minutes on,
60 minutes off Shipping Weight ................... 300 g (0.7 lb) Extended Operating Temperature........................... -55 to 60°C (-67 to 140°F)(1) ER-5KV: Maximum Voltage .............. 2,500 Vac Maximum Current .............. 125 mA Resistance ........................... 20 k Thermal .................................. Continuous Torque: Terminal N: 10-32 Insert ..................... 5.6 N-m (50 in-lb) Others .............................. 9.0 N-m (80 in-lb) Shipping Weight ................... 5.0 kg (11 lb)
Page 17 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
ER-5WP: Maximum Voltage .............. 2,500 Vac Maximum Current .............. 125 mA Resistance ........................... 20 k Thermal .................................. Continuous Torque: Terminal N: 10-32 Insert ...................... 5.6 N-m (50 in-lb) Others ............................... 9.0 N-m (80 in-lb) Shipping Weight .................... 5.0 kg (11 lb) ER-15KV: Maximum Voltage .............. 8,400 Vac Maximum Current .............. 84 mA Resistance ........................... 100 k Thermal: 8,400 Vac ............................ 1 minute on, 120 minutes off 1,900 Vac ............................ Continuous Torque (Terminal N) ............. 9.0 N-m (80 in-lb) Shipping Weight .................... 5.0 kg (11 lb) ER-25KV: Maximum Voltage .............. 14,400 Vac Maximum Current .............. 144 mA Resistance ........................... 100 k Thermal: 14,400 Vac .......................... 1 minute on, 120 minutes off 2,500 Vac ............................ Continuous Torque (Terminal N) ............. 9.0 N-m (80 in-lb) Shipping Weight .................... 20 kg (44 lb) Certification .............................. CSA, Canada and USA
LR 53428
USC
R
UL Listed
CE, European Union
NOTES: (1) Electrical specifications have been verified at a Littelfuse
lab.
4.3 CURRENT TRANSFORMERS
CT200: Current Ratio ...................... 200:5 A Insulation ............................ 600-V Class Window Diameter .............. 56 mm (2.2”) Shipping Weight ................. 1 kg (2.2 lb) CT200L: Current Ratio ...................... 200:5 A Insulation ............................ 600-V Class Window Diameter .............. 89 mm (3.5”) Shipping Weight ................. 1.2 kg (2.6 lb)
Page 18 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
5. ORDERING INFORMATION
Option List (1)
SE-325
120-Vac Supply (2)
E 240-Vac Supply (3)
D 120-Vac/dc Supply
Extended Resistor Trip Time
Non-Latching Operation
Extended GF Trip Time
(1) List options required in order shown above.(2) Standard, leave blank.
SE-325P .... Approved byThe Commonwealth of Pennsylvaniafor 4,800-Ω NGR.Requires 20-kΩ sensing resistor.
(3) Only Supply option available with C-Tick certification.
S
N
T
Sensing Resistors: ER-600VC ............................. For system voltages up to 1
kVac SE-MRE-600 ......................... Optional ER-600VC
moisture- resistant enclosure
ER-5KV ................................. For system voltages up to 5 kVac
ER-5WP ................................. For system voltages up to 5 kVac
ER-15KV ............................... For system voltages up to 15 kVac
ER-25KV ............................... For system voltages up to 25 kVac
Ground-Fault CT: CT200 .................................... 56 mm (2.2”) window CT200L .................................. 89 mm (3.5”) window Remote Indication and Reset: RK-302 .................................. Includes two LED pilot
lights, a reset push button, and legend plates
RK-325 .................................. Indication-and-Reset Assembly
RK-325I ................................. Indication Assembly RK-13..................................... Relay Interface Module
6. WARRANTY
The SE-325 Neutral-Grounding-Resistor Monitor is warranted to be free from defects in material and workmanship for a period of five years from the date of purchase. Littelfuse Startco will (at Littelfuse Startco’s option) repair, replace, or refund the original purchase price of an SE-325 that is determined by Littelfuse Startco to be defective if it is returned to the Startco factory, freight prepaid, within the warranty period. This warranty does not apply to repairs required as a result of misuse, negligence, an accident, improper installation, tampering, or insufficient care. Littelfuse Startco does not warrant products repaired or modified by non-Littelfuse Startco personnel.
Page 19 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
7. TEST PROCEDURES
7.1 GROUND-FAULT PERFORMANCE TEST
To meet the requirements of the National Electrical Code (NEC), as applicable, the overall ground-fault protection system requires a performance test when first installed. A written record of the performance test is to be retained by those in charge of the electrical installation in order to make it available to the authority having jurisdiction. A test-record form is provided for recording the date and the final results of the performance tests. The following ground-fault system tests are to be conducted by qualified personnel:
a) Evaluate the interconnected system in accordance with the overall equipment manufacturer’s detailed instructions.
b) Verify proper location of the ground-fault current transformer. Ensure the cables pass through the ground-fault-current-transformer window. This check can be done visually with knowledge of the circuit. The connection of the current-transformer secondary to the SE-325 is not polarity sensitive.
c) Verify that the system is correctly grounded and that alternate ground paths do not exist that bypass the current transformer. High-voltage testers and resistance bridges can be used to determine the existence of alternate ground paths.
d) Verify proper reaction of the circuit-interrupting device in response to a simulated or controlled ground-fault current. To simulate ground-fault current, use CT-primary current injection. Fig. 15a shows a test circuit using an SE-400 Ground-Fault-Relay Test Unit. The SE-400 has a programmable output of 0.5 to 9.9 A for a duration of 0.1 to 9.9 seconds. Set the test current to 0.6, 2.3, or 4.6 A for SE-325 units set at 0.5, 2.0, or 4.0 A respectively. Fig. 15b shows a test circuit using an SE-100T Ground-Fault-Relay Tester. The SE-100T provides a test current of 0.65 or 2.75 A for testing 0.5- and 2.0-A trip levels. Inject the test current through the current-transformer window for at least 2.5 seconds. Verify that the circuit under test has reacted properly. Correct any problems and re-test until the proper reaction is verified.
e) Record the date and the results of the test on the attached test-record form.
a) USING SE-400
CT200GROUND-FAULT CT
NEUTRALGROUNDING
RESISTOR
CT2
CT1
L1
L2
R
L
N
R
N
G
OP1
L1
L2
RMT1
RMT2
L
N
OP211
3
5
1
8
9REMOTE
TEST
SE-325
SE-400
ER 12
b) USING SE-100T
CT200GROUND-FAULT CT
NEUTRALGROUNDING
RESISTOR
CT2
CT1
L1
L2
R
L
N
R
N
G
C
L1
L2
RMT
L
N
LO
REMOTE TEST
SE-325
SE-100T
ER 0.65 A
HI2.75 A
FIGURE 15. Ground-Fault-Test Circuits.
TABLE 2. GROUND-FAULT-TEST RECORD
DATE TEST RESULTS
Retain this record for the authority having jurisdiction.
Page 20 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
7.2 RESISTOR-FAULT TESTS
Perform tests with system de-energized and supply voltage applied to the SE-325. 7.2.1 OPEN TEST
Test Equipment: 20-k and 100-k, ¼-watt, 1% resistors (included with SE-325). Procedure: Remove connections to SE-325 R and G terminals. Connect the 20-k resistor to R and G terminals. Set the RES switch to 20K. Press RESET. The RESISTOR-FAULT LED should be off. Remove the test resistor and wait 5 seconds (20 seconds with Option S). PASS: The SE-325 should trip on RESISTOR FAULT. Connect the 100-k resistor to R and G terminals. Set the RES switch to 100K. Press RESET. The RESISTOR-FAULT LED should be off. Remove the test resistor and wait 5 seconds (20 seconds with Option S). PASS: The SE-325 should trip on RESISTOR FAULT. To test the connected wiring, sensing resistor, and NGR: Reconnect SE-325 R and G connections. Set the RES switch to match sensing resistor. Press RESET. PASS: The RESISTOR FAULT LED should be off. 7.2.2 VOLTAGE TEST
Test Equipment: 0 to 120 Vac voltage source and multimeter. NOTE: Also use an isolation transformer if the test-voltage source does not provide dc continuity for the SE-325 resistance-measurement circuit. NOTE: Applying the test voltage to the R and G terminals will damage the SE-325 and the ER sensing resistor. The RES TRIP LEVEL is the trip voltage at terminal N, not terminal R. Procedure: Check the ER sensing resistor connection to the SE-325. Disconnect the wire from sensing resistor terminal N. A
resistor-fault trip will occur. Set the voltage source to 0 V. Connect the voltage source between sensing resistor N and G terminals. Set the RES TRIP LEVEL (VAC) to 20. Press RESET. The RESISTOR-FAULT LED should be off. Increase the test voltage to 25 Vac for 20-k sensors or
120 Vac for 100-k sensors and wait 5 seconds (20 seconds with Option S). PASS: The SE-325 should trip on RESISTOR FAULT. 7.3 SENSING-RESISTOR TEST Test Equipment: Multimeter. Procedure: Disconnect the sensing resistor. Measure the resistance between sensing-resistor terminals
R and N. PASS: Resistance should be between 19.6 and 20.4 k for 20-k sensing resistors. Resistance should be between 98 and 102 k for 100-k sensing resistors.
Measure the resistance between sensing-resistor terminals R and G in both directions. PASS: Resistance should be greater than 10 M in both directions.
Page 21 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
APPENDIX A SE-325 REVISION HISTORY
MANUAL RELEASE DATE
MANUAL REVISION PRODUCT REVISION
(REVISION NUMBER ON PRODUCT LABEL) July 6, 2015 13-D-070615 13
September 23, 2014 13-C-092314
12 August 27, 2013 13-B-082713
August 13, 2013 13-A-081313
MANUAL REVISION HISTORY REVISION 13-D-070615 SECTION 5 FCC certification added. Updated Fuse F1 part number. APPENDIX A Revision history updated. REVISION 13-C-092314 SECTION 3 Updated Figs. 4, 7, 8, 9, 10, 12, and 13. SECTION 4 Updated RK-13 contact ratings. APPENDIX A Revision history updated. REVISION 13-B-082713 SECTION 3 Updated Figures 7, 8, 9, and 10. REVISION 13-A-081313 SECTION 3 Updated Figure 11. APPENDIX A Added Revision History. PRODUCT REVISION HISTORY HARDWARE REVISION 13 Minor hardware change. HARDWARE REVISION 12 Component change to improve stability of ground-fault detection circuit.
Page 22 SE-325 Neutral-Grounding-Resistor Monitor Rev. 13-D-070615
This page intentionally left blank.