GENERALCOVER SHEET, CODE ANALYSIS, VICINITY MAP, AREA OF WORK ------------------------ C-1
GENERAL SYMBOLS AND ABBREVIATIONS---------------------------------------------------- G-1
GENERAL AND DEMOLITION NOTES ------------------------------------------------------------ G-2
ELECTRICALELECTRICAL PARTIAL FLOOR PLAN --------------------------------------------------------------- E-1
ELECTRICAL PARTIAL FLOOR PLAN --------------------------------------------------------------- E-2
SECURITY DETAILS --------------------------------------------------------------------------------- E-3
PROJECT CRITERIAGENERAL PROJECT NARRATIVE:
THE PROJECT INCLUDES THE REPLACEMENT AND ADDITION OF DOOR SECURITY HARDWARE TO MAINTAIN A SAFE ENVIRONMENT FOR THE SCHOOL.
THIS PROJECT INCLUDES THE ELECTRICAL WIRING AND ALL OTHER GENERAL CONSTRUCTION ACTIVITIES NECESSARY TO MAKE FOR A COMPLETE ANDFINISHED SYSTEM AT THE CONCLUSION OF THE PROJECT.
THE BUILDING WILL REMAIN OCCUPIED AND OPERATING DURING THIS UPGRADE PROJECT. THE CONTRACTOR SHALL COORDINATE THE CLOSING OFROOMS WITH THE BUILDING FACILITIES MANAGER TO FACILITATE THEIR WORK. THE CONTRACTOR SHALL CONFINE THEMSELVES TO THE GIVEN WORKAREA TO MINIMIZE DISRUPTION OF NORMAL BUILDING ACTIVITIES.
CONTRACTOR SHALL FURNISH AND INSTALL ALL HARDWARE REQUIRED FOR BUILDING PERIMETER SECURITY AS DETAILED ON THE PLANS AND IN THESPECIFICATIONS. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL DOOR HARDWARE, ACCESS CONTROLS, ACCESS CONTROL HARDWARE, CAT 6PLENUM RATED WIRING, PUNCHDOWN BLOCKS, ACCESS CONTROL CABINETS AND CONTROLLERS, ELECTRICAL WIRING, PROGRAMMING, INTERFACES,AND SAFETIES TO PROVIDE A COMPLETE AND OPERATING PERIMETER DOOR SECURITY SYSTEM.
CONTRACTOR SHALL FURNISH AND INSTALL ALL WIRELESS ACCESS POINTS REQUIRED TO PROVIDE COMPLETE COVERAGE IN THE FACILITY FOR NEWWIRELESS CLASSROOM SECURITY LOCKSETS AND RESTROOM LOCKSETS. CONTRACTOR SHALL FURNISH 60 NEW WIRELESS LOCKSETS AND TRAINTHE SCHOOL PERSONNEL ON THEIR INSTALLATION AND PROGRAMMING. LOCKSETS FOR CLASSROOMS WILL BE INSTALLED BY BUILDING PERSONNEL.
CONTRACTOR SHALL PROVIDE WARRANTEE, TRAINING, AND SUPPORT FOR THE ENTIRE DOOR SYSTEM.
CODE DATA
BUILDING -------------------------------------------------- 1 STORY BUILDINGCONSTRUCTION CODE CLASSIFICATION ------------ II BBUILDING USE GROUP ---------------------------------- EDUCATIONAL "E"USE GROUP OF AREA OF CONSTRUCTION ---------- EDUCATIONAL "E"
BUILDING CALCULATIONS
AREA OF BUILDING -------------------------------------- 136,500 SQUARE FEETAREA OF FIRST FLOOR ---------------------------------- 136,500 SQUARE FEETAREA OF WORK ------------------------------------------- 136,500 SQUARE FEET
TOTAL AREA AFFECTED BY CONSTRUCTION --------- 136,500 SQUARE FEET
APPLICABLE CODES
BUILDING -------------------------------- 2015 INTERNATIONAL BUILDING CODE: NJ EDITION
BUILDING -------------------------------- REHABILITATION SUBCODE (NJAC 5:23-6)
MECHANICAL --------------------------- 2015 INTERNATIONAL MECHANICAL CODE
MECHANICAL---------------------------- 2015 INTERNATIONAL FUEL GAS CODE
PLUMBING------------------------------- 2009 NATIONAL STANDARD PLUMBING CODE
FIRE--------------------------------------- 2015 INTERNATIONAL FIRE CODE
ELECTRICAL------------------------------ 2014 NATIONAL ELECTRICAL CODE
ENERGY----------------------------------- ASHRAE 90.1-2013
AREA OF WORK
COMPUTER
AIDED
DRAFTING
SHOWER
DRYING
TOIL.
TOIL.
STORAGE
INSTRUC.
GYMNASIUM
62
STORAGE OFFICE
SHOWER
STOR.
TOIL.
OFFICE
INSTRUC.VEST.
MECHANICAL / ELECTRICAL
J.C.
C
2
C
3
C
4
C
5
C
6
C
1
C
17
C
31
C
32
C
30
C
29
C
28
C
27
C
26
C
25
C
33
C
35
C
34
C
36
C
37
C
38
C
39
C
40
C
41
C
42
B
71
B
65
B
59
C
23
C
22
C
21
C
20
C
18
C
19
B
15
C
7
C
8
C
9
C
10
C
11
CAR WASH
LOCKER /
TOILET ROOM
LOCKER RM
ENGINEERING
LOCKER RM
TOIL.
CLASSROOM
WELDING
CAREERS
47
STORAGE
C.R.
AREA
OFFICE
OFFICE OFFICE OFFICE OFFICE GUIDANCE OFFICE
MAIN
OFFICE
MEN
WOMEN
CONF.
ROOM
STUDENT
SERVICES
STORAGELOCKER
TOILET AREA
OFFICE/
STORAGE
STORAGE
TOIL.
STORAGE
ELECTRICAL
DRYING
APPRETICESHIP
GED / ESL
OFFICE
CHIEF
SCHOOL
ADMIN
HALLWAY
A
STORAGE
NURSE
OFFICE
TOILETSTORAGE
FOOD
SERVICES
28
CLASSROOM
31
DATA
PROCESSING
LAB
30
STORAGE
TRANSFORMER
ROOM
27
SOCIAL
STUDIES
25
SOCIAL
STUDIES
24
CHEM.
LAB
22
MATH
21
ART
CLASSROOM
19
ART
SUPPLY
ELEC.
ROOM
20
STORAGE
PREP.
ROOM
CLASSROOM
18
GIRLS
LAV.
LIBRARY
9
WOMENS
FAC. LAV.
23
WORKROOM
13
TEACHERS
LOUNGE
14
MATH
CLASSROOM
12
BOYS
LAV.
CLASSROOM
11
ELEC
ROOM
7
HALLWAY
B
HALLWAY
A
HALLWAY
D
TOILET
STOR.
TOILET
CLOSET
LOBBY
CAFETERIA
HALLWAY
C
HALLWAY
C
ELECTRICAL
ROOM
MECHANICAL
ROOM
STORAGE
STORAGE H.C.
TOILET
FACULTY DINNING /
KNIGHTS CAFE
FOOD SERVICE
MENS
TOILET
WOMENS
TOILET
MENS
LOCKER
WOMENS
LOCKER
4746
CLASSROOM
44
CLASSROOM
41
HALLWAY
D
AUTO
SHOP
48
LOCKER /
TOILET ROOM
BUILDING
CONSTRUCTION
50
J.C.
OFFICE
CLASSROOM
52
HALLWAY
E
HALLWAY
G
BOYS
LOCKER ROOM
57
GIRLS
LOCKER ROOM
57
COSMOTOLOGY
63
CLASSROOM
64
CLASSROOM
66
LOCKER ROOMOFFICE
TOILET
CLASSROOM
66
ADMISSIONS
OFFICE
65
ELECT.
ROOM
TOIL.
VESTIBULE STORAGE
ELECTRICAL
ROOM
WOMENS
TOILET
MENS
TOILET
J.C.
TV
STUDIO
74
CLASSROOM
75
ELECTIRIC
ROOM
STAGE
THEATER
LOBBY
CLASSROOM
76
CLASSROOM
77
CLASSROOM
78
CLASSROOM
79
CLASSROOM
80
CLASSROOM
81
CLASSROOM
82
OFFICE
OFFICE
COMMUNITY
HEALTH
88
GRAPHIC ART /
COMMCERCIAL ART
87
SPRINKLER
CONTROL
ROOM
CLASSROOM
86
CHEMISTRY
85
LAW &
PUBLIC
SAFETY
84
STORAGE
CLASSROOM
91
J.C.
WOMENS
TOILET
MENS
TOILET
CHILD
DEVELOPMENT
83
PRE-K
HALLWAY
I
HALLWAY
L
HALLWAY
I
HALLWAY
L
HALLWAY
H
UV
UV
UV
UV
UVUVUVUVUVUVUV
UV
UV
UVUVUVUVUV
TW TW TW TW TW
TW
TW TW
TW
TW
TW
TW
TW
TW
TW TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
ELECTRONICS
1A
2A
2B
2C
3A
4A
1
1.1
2
3
4
5
6
66A
30A
VICINITY MAP
COVER
C-1AS NOTED
1 -
WARREN COUNTY VOCATIONAL SCHOOLSECURITY UPGRADE
TOWNSHIP OF WASHINGTONWARREN COUNTY, NEW JERSEY
1C1 N.T.S.
SCALE
FACILITY LOCATION
4C1 N.T.S.
SCALE2C1 N.T.S.
SCALE
DANIEL B. GROVER, PE
THE STATE OF NEW JERSEYLICENSED
PROFESSIONAL ENGINEER24GE44239
The Great Meadows Design Group, LLCA Professional Engineering Company
24 Far View RoadGreat Meadows, New Jersey 07838
(908) 637-8233 Fax (908) 637-8234
www.TheGMDGroup.com
New Jersey Authorization Number: 24GA28095500
REVISIONS/ISSUES
MAY 3, 2017
17016
DBG
No. Revision/Issue Date
WARREN COUNTY VOCATIONALSCHOOL
SECURITY UPGRADE
TOWNSHIP OF WASHINGTONWARREN COUNTY, NEW JERSEY
3C1 N.T.S.
SCALE
B.D.D. BACK DRAFT DAMPERBFP BACK FLOW PREVENTERBHP BREEAK HOURSEPOWERBI BACKWARD INCLINEDBLDG BUILDINGBTUH BTU PER HOURC CONDUITCAM CAMERACAT CATALOGCATV CABLE TELEVISIONCRAC COMPUTER ROOM AIR CONDITIONERCB CIRCUIT BREAKERCD CEILING DIFFUSERCENTR. CENTRIFUGALCFM CUBIC FEET PER MINUTECHWR CHILLED WATER RETURNCHWS CHILLED WATER SUPPLYCHWP CHILLED WATER PUMPCKT CIRCUITCLG CEILINGCOL COLUMNCONC CONCRETECONN CONNECTION, CONNECTCONT CONTINUATIONC/O CLEAN OUTCR CEILING REGISTERCRAH COMPUTER ROOM AIR HANDLING UNITCT CURRENT TRANSFORMERCUH CABINET UNIT HEATERCW COLD WATER RETURNCU COPPERCL CENTER LINE
E WIRED ON EMERGENCY CIRCUITEAT ENTERING AIR TEMPERATUREEC/E.C. ELECTRICAL CONTRACTOREF EXHAUST FANELEC ELECTRICALELEV ELEVATIONENT ENTERINGEMT ELECTRICAL METALLIC CONDUITEPB EMERGENCY PUSH BUTTONEMR ELEVATOR MACHINE ROOMEOL END OF LINEEPO EMERGENCY POWER OFFESP EXTERNAL STATIC PRESSUREET EXPANSION TANKER EXHAUST REGISTEREWC ELECTRIC WATER COOLEREWT ENTERING WATER TEMPERATUREEXH EXHAUSTEXIST. EXISTING
F FLUSHF. FILLFF FLUSH FILLFA FIRE ALARMFBO FURNISHED BY OTHERSFC FORWARD CURVEDFND FOUNDATIONFD FLOOR DRAINFL FLOORFLA FULL LOAD AMPSFLEX. FLEXIBLEFMC FLEXIBLE METALLIC CONDUITFO FUEL OILFOF FUEL OIL FILLFOP FUEL OIL PUMPFOR FUEL OIL RETURNFOS FUEL OIL SUPPLYFOV FUEL OIL VENTFPC FIRE PROTECTION CONTRACTORFPM FEET PER MINUTEFPS FEET PER SECONDFT FEET
GA GAUGEGAL GALLONGALV GALVANIZEDGC GENERAL CONTRACTORGFCI GROUND FAULT- CIRCUIT INTERRUPTERGFPE GROUND FAULT- PROTECTION EQUIPMENTGND GROUNDEDGPM GALLONS PER MINUTEGR GRILLEGRC GALVANIZED RIGID CONDUIT
IAM INDIVIDUAL ADDRESSABLE MODULEI.D. INSIDE DIAMETERIG ISOLATED GROUNDIMC INTERMEDIATE METAL CONDUITIWG INCHES OF WATER GAUGE
OA OUTSIDE AIRP POLEPB PULL BOXP.C. PLUMBING CONTRACTORPD PRESSURE DROPPH ɸ ELECTRICAL PHASEPIV POST INDICATOR VALVEPNL PANEL(BOARD)PP POWER PANELPR PAIRPRI PRIMARYPSI(G) POUNDS PER SQUARE INCH (GAGE)PT POTENTIAL TRANSFORMERPV POLYVINYL CHLORIDE CONDUITPWR POWERRA RETURN AIRREC RECESSEDRH RELATIVE HUMIDITYRMC RIGID METAL CONDUITRT RAINTIGHTRTU ROOF TOP UNITRPM REVOLUTION PER MINUTES SURFACE MOUNTEDSEC SECONDARYSIG SIGNALSN SOLID NEUTRALSP SPARESPL SPLICESS STAINLESS STEELSTP / TSP SHIELDED TWISTED PAIRSTL CARBON STEELSY SHUNT TRIPSUSP SUSPENDEDSW SWITCHSWBD SWITCHBOARDTC TELEPHONE CABINETTCI TELECOMMUNICATIONS CABLING-INSTALLERTYP TYPICALUG UNDERGROUNDU.O.I. UNLESS OTHERWISE INDICATED.U.O.N. UNLESS OTHERWISE NOTEDV VOLTV. VENTVT VAPORTIGHT W WATTY WYEWH WATTHOURWP WEATHERPROOFWT WATERTIGHTXFMR TRANSFORMERXP EXPLOSION PROOF+72" MOUNTING UNITS TO CENTERLINE - ABOVE
FINISHED FLOOR OR GRADE
A AMPEREASS'LY ASSEMBLYA.C. INDOOR AIR CONDITIONING UNITAC ALTERNATING CURRENTAF AMP FRAMEAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAHU AIR HANDLING UNITAIC AMPRERE INTERUPTING CAPACITYAL ALUMINUMAPD AIR PRESSURE DROPAPPROX APPROXIMATEARCH ARCHITECT, ARCHITECTURALAS AMP SWITCHAST ABOVE GROUND STORAGE TANKAT AMP TRIPATR AIR TEMPERATURE RISEATC AUTOMATIC TEMPERATURE CONTROLATS AUTOMATIC TRANSFER SWITCHAUD AUDIO BOX CONNECTIONA/V AUDIO VISUAL
1P ONE POLE
2P TWO POLE
3P THREE POLE
4P FOUR POLE
1P1W ONE POLE, ONE WIRE
1P2W ONE POLE, TWO WIRE
2P2W TWO POLE, TWO WIRE
2P3W TWO POLE, THREE WIRE
3P3W THREE POLE, THREE WIRE
3P4W THREE POLE, FOUR WIRE
4P4W FOUR POLE, FOUR WIRE
JB JUNCTION BOXKCMIL THOUSAND CIRCULAR MILSKVA KILOVOLT AMPEREKVAR KILOVOLT AMPERE REACTIVEKW KILOWATTLAT LEAVING AIR TEMPERATURELFMC LIQUID TIGHT FLEXIBLE METAL CONDUITLFNC LIQUID TIGHT NON-FLEXIBLE METAL CONDUITLP LIGHTING PANELLS LIMIT SWITCHLTG LIGHTINGLV LOW VOLTAGEMAX MAXIMUMMBH THOUSAND BTU PER HOURMBS MANUAL BALANCING DAMPERMC METAL CLAD CABLEM.C. MECHANICAL CONTRACTORMCC MOTOR CONTROL CENTERMDP MAIN DISTRIBUTION PANELMECH MECHANICALMIN MINIMUMMISC MISCELLANEOUSMLO MAIN LUG ONLYMTD MOUNTEDMTG MOUNTINGMTS MANUAL TRANSFER SWITCHN. NEWN/A NOT APPLICABLENC NOISE CRITERIAN.C. NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENIC NOT IN CONTRACTNEMA NATIONAL ELECTRIC MANUFACTURER'S ASSOCIATIONNL NIGHT LIGHTNM NONMETALLICN.O. NORMALLY OPENNRTL NATIONALLY RECOGNIZED TESTING LABNO. / # NUMBERNTS NOT TO SCALE
EMERGENCY BATTERY UNIT WITH LIGHTING HEADS
BATTERY PACK AND CHARGER
EXIT LIGHT FIXTURE, ARROWS AND EXIT FACE(S)
EMERGENCY BATTERY UNIT WITH REMOTE LIGHTINGFIXTURE (1 HEAD)EMERGENCY BATTERY UNIT WITH REMOTE LIGHTINGFIXTURE (2 HEAD)
EXIT LIGHTING FIXTURE WITH EMERGENCY BATTERY,AND EMERGENCY BATTERY LIGHTING HEADS
TYPICAL LIGHT FIXTURE NOTATION: A = FIXTURE TYPE a = SWITCH LEG
TYPICAL LIGHT FIXTURE NOTATION:"EM" = EMERGENCY"NL" = NIGHT LIGHT"NL/EM" = NIGHT LIGHT & EMERGENCY"P" = PANEL"C" = CIRCUIT
NL/EM
P-C
1x1 FLUORESCENT FIXTURE
2x2 FLUORESCENT FIXTURE
2x2 FLUORESCENT PARABOLIC FIXTURE
2x4 FLUORESCENT PARABOLIC FIXTURE
2x4 FLUORESCENT FIXTURE
1x4 PENDANT-MOUNTED FIXTURE
1x4 FLUORESCENT FIXTURE
WALL-MOUNTED FIXTURE
DOWNLIGHT, SURFACE CEILING-MOUNTED
SCONCE, WALL-MOUNTED FIXTURE
BOLLARD, OUTDOOR FIXTURE
GROUND/FLOOR-MOUNTED FIXTURE
GROUND/FLOOR-MOUNTED FIXTURE WITH SHIELD
FLUORESCENT STRIP
TWIN LUMINAIRE POLE MOUNTED SITE LIGHT FIXTURE
SINGLE LUMINAIRE POLE MOUNTED SITE LIGHT FIXTURE
POLE MOUNTED WITH ARM
TRACK LIGHTING, LENGTH AND NUMBER OF HEADS AS INDICATED ON DRAWINGS
JUNCTION BOX
20A-125V DUPLEX RECEPTACLE
20A-125V DUPLEX GROUND FAULT CIRCUIT INTERRUPTERRECEPTACLE
20A-125V DUPLEX RECEPTACLE, MTG COUNTER HEIGHT
20A-125V SIMPLEX RECEPTACLE
ISOLATED GROUND DUPLEX RECEPTACLE
QUAD RECEPTACLE (DOUBLE DUPLEX)
ISOLATED GROUND QUAD RECEPTACLE(DOUBLE DUPLEX)IG
IG
GFCI
J
FLOOR MOUNTED DUPLEX RECEPTACLE F = FLUSH MOUNT S = SURFACE MOUNT
RECEPTACLE POWER STRIP, WALL MOUNTED
RECEPTACLE, WALL MOUNTED SPECIAL
FLOOR MOUNTED DOUBLE DUPLEX (QUAD) RECEPTACLE F = FLUSH MOUNT S = SURFACE MOUNT
COAXIAL SYSTEM OUTLET
F
W
DATA OUTLET
TELEPHONE OUTLET
TELEPHONE/DATA OUTLET
TELEPHONE/DATA OUTLET, FLOOR-MOUNTED
TELEPHONE OUTLET, FLOOR-MOUNTED
TELEPHONE OUTLET, WALL-MOUNTED
DATA OUTLET, FLOOR MOUNTED F = FLUSH-MOUNTEDS = SURFACE-MOUNTED
SINGLE POLE SWITCHTHREE WAY SWITCHTHREE WAY SWITCH WITH PILOT LIGHT
SINGLE POLE SWITCH WITH PILOT LIGHTWALL SWITCH MOTION DETECTOR, WATTSTOPPER WS-120/277-1,DECORATOR STYLE
KEY SWITCH
ROTARY TIMER SWITCH
0-18 HOUR TIME-OFF SWITCHSINGLE GANG TIMECLOCK SWITCHFRACTIONAL MOTOR STARTER WITH THERMAL OVERLOAD SWITCH
VOLUME CONTROL
S T
S V
TO
TC
FS
SS
PS
MS
S K
,PSS
S
TYPICAL SWITCH NOTATION: 2 = DOUBLE POLE SWITCH 3 = THREE-WAY SWITCH 4 = FOUR-WAY SWITCH a = SWITCH LEG W = WEATHERPROOF
Sa3
WP
HORIZONTALLY MOUNTED SWITCH, ON TO LEFT
SINGLE-POLE COUBLE-THROW SWITCHDIMMER SWITCH
CIRCUIT BREAKER SWITCH
LOW VOLTAGE MASTER SWITCHLOW VOLTAGE SWITCH
MOMENTARY CONTACT SWITCH
WEATHERPROOF SWITCH
GLOW SWITCH TOGGLE, GLOWS IN OFF POSITION,LIT WHEN POWER TO FIXTURE(S) IS OFF
CBSDSDTSGS
KEY SWITCH WITH PILOT LIGHTS KP
S H
S MC
S LV
S LM
S WP
TC
CLOCK RECEPTACLE, FLUSH WALL MOUNTED 84"AAFC
CAMERAC
CCTV
C
K
CARD-READER
CCTV COAXIAL CABLE AND POWER OUTLET
DOORCHIME
ELECTRIC DOOR STRIKE
SECURITY DOOR CONTACTS
FLUSH-MOUNTED INTERCOM UNIT
SECURITY KEYPAD
RB BEAM SMOKE DETECTOR
R = RECEIVING UNIT
BS S = SENDING UNIT
BEAM SMOKE DETECTOR
C CARBON MONOXIDE DETECTOR
DOOR HOLDER
VOICE EVACUATION PANEL
PILOT LIGHT
F FLAME DETECTOR
H
F HORN AND STROBE
HORN
AUTOMATIC HEAT DETECTOR
F HYDROGEN DETECTOR
FSD MOTOR-OPERATOR FIRE/SMOKE DUCT DAMPER
PRESSURE SWITCH
PIV POST INDICATOR VALVE
F FIRE PULL STATION
S SMOKE DETECTOR
CS SMOKE DETECTOR ABOVE FINISHED CEILING
DUCT SMOKE DETECTOR
H HEAT DETECTOR AT DUCT OPENING
S UNDER-RAISED-FLOOR SMOKE DETECTOR
S CEILING-MOUNTED SPEAKER
S WALL-MOUNTED SPEAKER
S
TS
FS WATER FLOW SWITCH
TAMPER SWITCH
STROBE
MONITOR MODULE
DS
FAA
FIRE FIGHTER'S PHONE
ANNUNCIATOR PANEL
M FIRE ALARM MASTER BOX
FIRE ALARM CONTROL PANEL
RP-1A,3
SIZE OF DISCONNECT NUMBER OF POLESNEMA ENCLOSURE
MOTOR STARTER
SIZE OF FUSE
MOTOR RATED DISCONNECT SWITCH
COMBINATION STARTER/DISCONNECT
MOTOR (NUMBER INDICATES HORSE POWER)
3R3
100100
CONDUIT DOWN
CONDUIT UP
HOMERUN TO PANEL, INDICATING PANEL & CIRCUITNUMBER
ASD
ADJUSTABLE SPEED DRIVE W/ DISCONNECT &STARTER & BYPASS
ADJUSTABLE SPEED DRIVE WITH BYPASS
ATC
F
ENCLOSED CIRCUIT BREAKER
FUSED DISCONNECT
AUTOMATIC TEMPERATURE CONTROL PANEL
E
CONDUIT STUB
CONDUIT DIRECTION CONNECTION
CONDUIT FLEXIBLE CONNECTION
PULLBOX
PUSHBUTTON
CT
M
T
MCC
CT CABINET
MOTOR CONTROL CABINET
METER
TRANSFORMER
SHUNT TRIP
CONDUIT TURNING DOWN
DH DUCT HEATER
277/480V ELECTRICAL PANEL
PP-XC, 8
P
WIREWAY, SIZE AS INDICATED OR REQUIRED
CABLETRAY, SIZE AS INDICATED
BUSWAY, RATING AND TYPE AS INDICATED ON DRAWINGS
POWER POLE WITH DEVICES INDICATED ON DRAWINGS "P" INDICATES TYPE, "PP-XC, 8" INDICATES CIRCUIT NUMBER
120/208V ELECTRICAL PANEL
COMBINATION STARTER/DISCONNECT:# = CB: CIRCUIT BREAKER# = F: FUSED
TIMECLOCK
INDICATES SPECIFIC DRAWING NOTES
INDICATES OVERALL PROJECT NOTES
POINT OF CONNECTION
DRAWING REVISION
NUMBER
EQUIPMENT OR FIXTURE TYPE
(NUMBERED SEQUENTIALLY)
(NUMBERED SEQUENTIALLY)
(NUMBERED SEQUENTIALLY)
EQUIPMENT TAG##
DC DOOR CONTACT
REQUEST TO EXIT (MOTION)
ELECTRIC MAGNETIC LOCK
ELECTRIC STRIKE
CARD READER
PUSH TO EXIT
DOOR CONTROL MODULE
MOTION ACTIVATED REQUEST TO EXIT
PUSH BUTTON REQUEST TO EXIT
MAGNETIC LOCK RELEASEWITH POLYCARBONATE COVER WITH SQUEELER BOX AND CONTACTS(UNIVERSAL STOPPER BY SAFETY TECHNOLOGY INTERNATIONAL, MODEL STI-13230CW)
CARD READER AND KEYPAD COMBINATION
ELECTRONIC RELEASE LATCH
PANIC BAR
EXISTING
WIRELESS ACCESS POINT
REX
MAG
ES
CR
PTE
DM
(e)
(2)2"C-(10)#12,(5)#12N,(5)#12GNUMBER OF CONDUCTORSGROUNDING CONDUCTORNEUTRAL CONDUCTORSIZE OF CONDUCTORCONDUIT SIZEQUANTITY OF PARALLELCONDUITS AND CONDUCTORS
N
SECTION MARKER
DETAIL MARKER
PROJECT "NORTH" INDICATOR
SECTION NO.
SHEET NO.
DETAIL NO.
SHEET NO.
REX
MR
ELR
PAN
X DOOR / WINDOW MARKER
DANIEL B. GROVER, PE
THE STATE OF NEW JERSEYLICENSED
PROFESSIONAL ENGINEER24GE44239
The Great Meadows Design Group, LLCA Professional Engineering Company
24 Far View RoadGreat Meadows, New Jersey 07838
(908) 637-8233 Fax (908) 637-8234
www.TheGMDGroup.com
New Jersey Authorization Number: 24GA28095500
REVISIONS/ISSUES
MAY 3, 2017
17016
DBG
No. Revision/Issue Date
WARREN COUNTY VOCATIONALSCHOOL
SECURITY UPGRADE
TOWNSHIP OF WASHINGTONWARREN COUNTY, NEW JERSEY
SYMBOLS
SYMBOLS ANDABBREVIATIONS
G-1N.T.S.
- -RASABBREVIATIONS
1. THE CONTRACT DOCUMENTS INCLUDE THE WORKING DRAWINGS, ADDENDA, CLARIFICATIONS,MODIFICATIONS, AND GENERAL CONDITIONS OF THE CONSTRUCTION CONTRACT ANDSPECIFICATIONS.
2. THE CONTRACT DOCUMENTS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTYOF THE ENGINEER WHETHER THE PROJECT FOR WHICH THEY ARE PREPARED IS EXECUTED ORNOT. THE CONTRACT DOCUMENTS SHALL NOT BE USED BY OWNER, CONTRACTOR, OR TENANTFOR OTHER PROJECTS OR EXTENSIONS TO THE PROJECT, NOR ARE THEY TO BE MODIFIED INANY MANNER WHATSOEVER EXCEPT BY AGREEMENT IN WRITING WITH THE ENGINEER.
3. CONTRACTOR SHALL EXAMINE THE CONTRACT DOCUMENTS AND SHALL FAMILIARIZE HIMSELFWITH ALL THE REQUIREMENTS OF THE PROJECT AND SHALL NOTIFY THE CONTRACTING OFFICEROF ANY OBSERVED FAULTS AND AMBIGUITY IN THE CONTRACT DOCUMENTS SO THAT THEMATTER MAY BE RESOLVED PRIOR TO SUBMISSION OF QUOTES.
4. EXISTING FACILITY INFORMATION HAS BEEN PROVIDED BY THE BUILDING OWNER. ANYDISCREPANCIES OR CONFLICTS BETWEEN THE EXISTING FIELD CONDITIONS AND THESECONTRACT DOCUMENTS ARE TO BE BROUGHT TO THE ATTENTION OF THE ENGINEER FORREVIEW PRIOR TO COMMENCEMENT OF CONSTRUCTION.
5. THE GENERAL CONTRACTOR SHALL NOTIFY THE ENGINEER, IN WRITING, OF ANY DEFICIENCIES INBASE BUILDING PRIOR TO THE COMMENCEMENT OF HIS WORK. ANY UNREPORTEDDEFICIENCIES WILL BECOME THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO CORRECT.
6. ALL WORK ON THIS PROJECT SHALL BE INSTALLED IN ACCORDANCE WITH, AND SHALL CONFORMTO THE REQUIREMENTS OF ALL CODES AND REGULATIONS OF ALL GOVERNMENTAL AUTHORITIESOR AGENCIES HAVING JURISDICTION. SUCH CODES AND REGULATIONS SHALL HAVEPRECEDENCE OVER THAT WHICH IS INDICATED ON THE CONSTRUCTION DOCUMENTS UNLESSTHAT SHOWN ON THE CONSTRUCTION DOCUMENTS IS MORE STRINGENT. IN CASES OFDISCREPANCIES, OMISSIONS, CHANGES IN THE CODES OR CODE INTERPRETATIONS BY CODEOFFICIALS WHICH CAUSE A CHANGE IN THE WORK, NOTIFY THE ENGINEER PRIOR TOPROCEEDING WITH THAT PORTION OF THE WORK AFFECTED BY THE CHANGE. CONTRACTORSHALL OBTAIN ALL NECESSARY PERMITS. CONTRACTOR SHALL PLAN AND COORDINATE ALLREQUIRED INSPECTIONS.
7. IN THE EVENT OF CONFLICT BETWEEN DATA SHOWN ON THE DRAWINGS AND INFORMATION INTHE SPECIFICATIONS, THE MOST STRINGENT SHALL GOVERN. DIMENSIONS NOTED ON THEDRAWINGS SHALL TAKE PRECEDENCE OVER SCALED DIMENSIONS. DETAIL DRAWINGS TAKEPRECEDENCE OVER DRAWINGS ON A SMALLER SCALE. SHOULD THE CONTRACTOR AT ANY TIMEDISCOVER AN ERROR IN A DRAWING OR SPECIFICATION OR A DISCREPANCY OR VARIATIONBETWEEN DIMENSIONS OR OTHER INFORMATION, HE SHALL NOT PROCEED WITH THE WORKAFFECTED UNTIL CLARIFICATION HAS BEEN MADE BY THE ENGINEER.
8. BY SUBMISSION OF QUOTE, THE CONTRACTOR SHALL ACKNOWLEDGE ACCEPTANCE OF THECONTRACT DOCUMENTS AS AN ADEQUATE DEFINITION OF THE SCOPE OF WORK AND EXTRACOST CLAIMS BASED ON INADEQUACY OF CONTRACT DOCUMENTS WILL NOT BE CONSIDERED.
9. THE CONTRACT DRAWINGS ARE SCHEMATIC AND ARE INTENDED TO CONVEY A COMPLETE ANDFUNCTIONAL PROJECT. CONTRACT DRAWINGS DEPICT THE GENERAL LOCATION OF EQUIPMENT,WALLS, AND BUILDING COMPONENTS.
10. "FURNISH" MEANS SUPPLY ONLY FOR OTHERS TO PUT IN PLACE.
11. "PROVIDE" MEANS FURNISH AND INSTALL, COMPLETE AND IN PLACE.
12. "SIMILAR" MEANS COMPARABLE CHARACTERISTICS FOR CONDITIONS NOTED. CONTRACTOR TOVERIFY DIMENSIONS AND ORIENTATION.
13. "TYPICAL" MEANS IDENTICAL FOR CONDITIONS NOTED.
14. "PRIME CONTRACTOR" MEANS THE CONTRACTOR THAT IS LEADING THE PROJECT AND HOLDSTHE CONSTRUCTION CONTRACT FOR THE PROJECT.
15. "GENERAL CONTRACTOR" MEANS THE CONTRACTOR THAT HAS OVERALL RESPONSIBILITY FORTHE CONSTRUCTION COORDINATION OF THE PROJECT AND IS GENERALLY THE "PRIMECONTRACTOR".
16. WHEN A "GENERAL CONTRACTOR" IS NOT ENGAGED ON THE PROJECT, THE "PRIME CONTRACTOR"SHALL ASSUME AND EXECUTE THE DUTIES OF THE "GENERAL CONTRACTOR".
17. THE PRIME CONTRACTOR IS RESPONSIBLE FOR THE ACTIONS, ACTIVITIES, WORK, QUALITY, ANDSAFETY OF ALL OF THE SUB-CONTRACTORS WORKING FOR HIM ON THE PROJECT.
18. HORIZONTAL DIMENSIONS INDICATED ARE TO/FROM FINISHED FACE OF CONSTRUCTION, EXCEPTAS NOTED.
19. VERTICAL DIMENSIONS ARE FROM TOP OF FLOOR SLAB, EXCEPT WHERE NOTED TO BE FROMABOVE FINISHED FLOOR (AFF).
20. DIMENSIONS ARE NOT ADJUSTABLE WITHOUT APPROVAL OF ENGINEER UNLESS NOTED (±).
21. THE GENERAL CONTRACTOR SHALL VERIFY THAT ALL CONSTRUCTION DOCUMENTS ARE THELATEST ISSUE AND THAT ALL SUBCONTRACTORS HAVE COMPLETE SETS OF THE LATEST ISSUEOF THE CONSTRUCTION DOCUMENTS PRIOR TO COMMENCING WITH ANY PORTION OF THEWORK.
22. IMMEDIATELY PRIOR TO THE OWNERS OCCUPANCY OF ANY PHASE OF THE WORK, THE GENERALCONTRACTOR SHALL CLEAN ALL SURFACES OF DUST, DEBRIS, LOOSE CONSTRUCTIONMATERIALS AND EQUIPMENT AND LEAVE ALL FLOORS VACUUM CLEAN. REMAININGCONSTRUCTION MATERIALS AND EQUIPMENT. IF ANY, SHALL BE MOVED AND TEMPORARILYSECURED IN AN AREA AS DIRECTED BY THE OWNER.
23. PREPARE A COMPLETE AND THOROUGH PROJECT CONSTRUCTION SCHEDULE FOR THE PROJECT.PROJECT SCHEDULE SHALL INCLUDE ALL MAJOR AND CRITICAL ELEMENTS REQUIRED, AND SHALLDEPICT THE CRITICAL PATH FOR SUCCESSFUL COMPLETION OF THE PROJECT IN A TIME AGREEDUPON WITH THE PROJECT MANAGER, ENGINEER AND OWNER. COORDINATE THE CONSTRUCTIONSCHEDULE WITH SCHEDULE OF THE REMAINING TRADES TO PROVIDE A COMPLETE ANDTHOROUGH CONSTRUCTION PLAN.
24. GENERAL CONTRACTOR SHALL ORDER AND SCHEDULE DELIVERY OF MATERIALS IN AMPLE TIMETO AVOID DELAYS IN CONSTRUCTION. IF AN ITEM IS FOUND TO BE UNAVAILABLE,CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY TO ALLOW THE ENGINEER AREASONABLE AMOUNT OF TIME TO SELECT A SUITABLE SUBSTITUTE.
25. REFER TO PROJECT DRAWINGS FOR ANY SEQUENCE AND/OR PRE-DETERMINED PHASES OFCONSTRUCTION. SEQUENCE AND PHASE OF CONSTRUCTION WHEN DEFINED BY THE PROJECTMANAGER, WHETHER CONTAINED IN THESE CONSTRUCTION DOCUMENTS OR NOT, SHALL BEADHERED TO AS A REQUIREMENT OF THE PROJECT.
26. IF AT ANY TIME BEFORE COMMENCEMENT OF WORK, OR DURING PROGRESS THEREOF, THEGENERAL CONTRACTOR'S METHODS, EQUIPMENT, OR APPLIANCES ARE INEFFICIENT ORINAPPROPRIATE FOR SECURING QUALITY OF WORK OR RATE OF PROGRESS AS INTENDED BYTHE CONTRACT DOCUMENTS, THE OWNER MAY ORDER THE GENERAL CONTRACTOR TO IMPROVETHEIR QUALITY OR INCREASE THEIR EFFICIENCY TO MEET PROJECT REQUIREMENTS. THIS WILLNOT RELIEVE THE GENERAL CONTRACTOR OR HIS SURETIES FROM THEIR OBLIGATIONS TOSECURE QUALITY OF OF WORK AND RATE OR PROGRESS SPECIFIED IN THE CONTRACT ORAGREED UPON IN PROJECT MEETINGS.
27. THE OWNER'S DESIGNATED AGENT WILL EXERCISE SOLE AUTHORITY FOR DETERMINING THECONFORMANCE OF MATERIALS, EQUIPMENT, AND SYSTEMS WITH THE INTENT OF THE DESIGN.REVIEW AND ACCEPTANCE OF ALL ITEMS PROPOSED BY THE CONTRACTOR FOR INCORPORATIONINTO THIS WORK WILL BE BY THE ENGINEER. THIS FUNCTION WILL APPLY BOTH TO THECONTRACT AS INITIALLY SIGNED, AND TO THE CHANGES TO CONTRACT BY MODIFICATIONDURING THE PROGRESS OF WORK.
28. REFERENCE TO MAKES, BRANDS, MODELS, ETC. IS TO ESTABLISH TYPE AND QUALITY DESIRED.SUBSTITUTION OF ACCEPTABLE EQUALS WILL NOT BE PERMITTED UNLESS SPECIFICALLYAPPROVED BY THE ENGINEER.
29. GENERAL CONTRACTOR SHALL PROVIDE A FULL TIME PROJECT SUPERVISOR. SUPERVISORSHALL BE ON SITE AND COORDINATING THE WORK OF ALL OTHER TRADES WHENEVER WORK ISBEING PERFORMED FOR THIS PROJECT. SUPERVISOR SHALL FIELD ALL QUESTIONS ANDREQUESTS FROM THE OWNER AND SHALL INSURE THAT REQUIREMENTS OF THE OWNER AREMET IN A TIMELY MANNER.
30. COORDINATE THE LOCATION OF ALL NEW EQUIPMENT BEING INSTALLED. IF IN COORDINATIONWITH SPECIFIC EQUIPMENT BEING INSTALLED A CONNECTION REQUIRING ACCESS MOVES FROMTHE GENERAL LOCATION SHOWN, THE CONTRACTOR SHALL MOVE THAT REPRESENTATIVECONNECTION WITHOUT ADDITIONAL CHARGE OR COST TO THE CLIENT OR PROJECT.CONTRACTOR SHALL ENSURE THAT ACCESS TO CONNECTIONS AND ALL EQUIPMENT REQUIRINGINSPECTION OR SERVICE.
31. PRIME CONTRACTOR SHALL COORDINATE ALL WORK BETWEEN ALL OTHER TRADES. BECOMEFAMILIAR WITH AND FOLLOW MANUFACTURERS RECOMMEND INSTALLATION INSTRUCTIONS,REGARDLESS OF THE TRADE PROVIDING THE EQUIPMENT.
32. THESE PLANS ARE GENERALLY DIAGRAMMATIC. THE PRIME CONTRACTOR SHALL COORDINATETHE WORK OF THE DIFFERENT TRADES IN ORDER THAT INTERFERENCES BETWEEN MECHANICAL,PLUMBING, ELECTRICAL, ARCHITECTURAL, GENERAL, AND STRUCTURAL WORK ARE AVOIDED. INCASE AN UNAVOIDABLE INTERFERENCES DEVELOP, THE PROJECT MANAGER OR ENGINEER WILLDECIDE WHICH EQUIPMENT SHALL BE RELOCATED REGARDLESS OF WHICH WAS FIRST INSTALLEDAND ALL MODIFICATIONS WILL BE MADE WITHOUT ADDITIONAL EXPENSE TO OWNER.
33. PRIME CONTRACTOR, SUBCONTRACTORS AND MATERIAL SUPPLIERS SHALL BE RESPONSIBLEFOR INSPECTION OF JOB CONDITIONS AFFECTING THE INSTALLATION OF EACH ITEM THEY AREPROVIDING AND FOR TAKING ALL FIELD MEASUREMENTS PRIOR TO THE FABRICATION ORPURCHASE OF THAT ITEM TO ENSURE THAT THE ITEM CONCERNED WILL INTEGRATE PROPERLYWITH ALL ADJACENT MATERIALS AND WILL FIT ALL OTHER CONDITIONS AS THEY EXIST OR WILLEXIST IN THE FINISHED BUILDING. SLEEVES, ANCHORS AND OTHER ITEMS THAT MUST BEEMBEDDED IN OR THAT OTHERWISE AFFECT OTHER PORTIONS OF THE WORK SHALL BE LOCATEDAND SET WHILE SUCH PORTIONS OF THE WORK ARE IN PROGRESS.
34. ALL WORK PERFORMED BY THE CONTRACTORS SHALL BE INSTALLED IN A WORKMANLIKEMANNER IN STRICT ACCORDANCE WITH THE BEST RECOGNIZED PRACTICE IN THE FIELDCONCERNED. MANUFACTURED ITEMS/EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCEWITH THE MANUFACTURER'S PRINTED INSTRUCTIONS, DIRECTIONS, SPECIFICATIONS AND/ORWRITTEN RECOMMENDATIONS FOR AN INSTALLATION OF THE HIGHEST QUALITY. ALL WORKINGPARTS SHALL BE PROPERLY ADJUSTED AFTER INSTALLATION AND LEFT IN PERFECT WORKINGORDER. ITEMS IN ALL CASES SHALL BE INSTALLED PLUMB, TRUE AND IN PROPER RELATIONSHIPTO SURROUNDING MATERIALS.
35. NO WORK DEFECTIVE IN CONSTRUCTION OR QUALITY OR DEFICIENT IN ANY REQUIREMENTS OFTHE CONTRACT WILL BE ACCEPTABLE IN CONSEQUENCE OF OWNER'S OR ENGINEER'S FAILURETO DISCOVER OR TO POINT OUT DEFECTS OR DEFICIENCIES DURING CONSTRUCTION, NOR WILLPRESENCE OF INSPECTORS ON WORK RELIEVE CONTRACTOR FROM RESPONSIBILITY FORSECURING QUALITY AND PROGRESS OF WORK AS REQUIRED BY THE CONTRACT. DEFECTIVEWORK REVEALED WITHIN REQUIRED TIME GUARANTEES SHALL BE REPLACED BY WORKCONFORMING WITH INTENT OF CONTRACT. NO PAYMENT, WHETHER PARTIAL OR FINAL, SHALLBE CONSTRUED AS AN ACCEPTANCE OF DEFECTIVE WORK OR IMPROPER MATERIALS.
36. ALL CONTRACTORS SHALL WAIVE "COMMON PRACTICE" AND "COMMON USAGE" ASCONSTRUCTION CRITERIA WHEREVER DETAILS AND CONTRACT DOCUMENTS OR GOVERNINGCODES, ORDINANCES, ETC. REQUIRE GREATER QUANTITY OR BETTER QUALITY THAN COMMONPRACTICE OR COMMON USAGE WOULD REQUIRE.
37. WHERE WORK DEPICTED IN THE CONSTRUCTION DOCUMENTS EXCEEDS THE MINIMALREQUIREMENTS OF THE CURRENTLY ENFORCED CODE, THE MORE STRINGENT REQUIREMENTSOF THE CONTRACT DOCUMENTS SHALL BE INSTALLED. MINIMUM ADHERENCE TO THE CODE ANDPASSING CODE INSPECTIONS ARE NOT ACCEPTABLE REASONS TO DEVIATE FROM THEREQUIREMENTS OF THESE PROJECT DOCUMENTS.
38. LOCATE ALL EQUIPMENT WHICH MUST BE SERVICED, OPERATED OR MAINTAINED IN FULLY
REQUIREMENTS OF THESE PROJECT DOCUMENTS.
38. LOCATE ALL EQUIPMENT WHICH MUST BE SERVICED, OPERATED OR MAINTAINED IN FULLYACCESSIBLE POSITION. SUCH EQUIPMENT SHALL INCLUDE, BUT NOT BE LIMITED TO, VALVEOPERATORS, MOTORS, CONTROLLERS, JUNCTION BOXES, SPLICES, DISCONNECTS, ACCESSPANELS, ETC. IF REQUIRED FOR ACCESSIBILITY, FURNISH ACCESS DOORS FOR THIS PURPOSE.MINOR DEVIATIONS FROM DRAWINGS MAY BE MADE TO ALLOW FOR BETTER ACCESSIBILITY,AND ANY CHANGE FOR THAT PURPOSE SHALL BE SUBMITTED FOR APPROVAL.
39. GENERAL CONTRACTOR SHALL THOROUGHLY CLEAN THE WORK AREA DAILY. DISPOSE OF ALLDEBRIS AND ENSURE ALL SAFETY SYSTEMS ARE OPERATIONAL AT THE COMPLETION OF DAILYCONSTRUCTION. THIS INCLUDES FIRE DETECTION SYSTEMS, SPRINKLER SYSTEMS, SECURITYSYSTEMS, ALARMS, AND OTHER SUCH BUILDING SAFETY SYSTEMS.
40. ALL CONTRACTORS SHALL VERIFY ALL DIMENSIONS AND LOCATIONS FOR PROPER EQUIPMENTINSTALLATION PRIOR TO SUBMITTING EQUIPMENT SHOP DRAWINGS TO DESIGN PROFESSIONALSFOR APPROVAL.
41. ALL SYSTEMS SHALL BE CLEAN OF FOREIGN MATERIAL PRIOR TO BEING PLACED IN SERVICE ANDBEFORE OPERATIONAL TESTS ARE PERFORMED. EXISTING SYSTEMS TO REMAIN IN SERVICE ATTHE CONCLUSION OF CONSTRUCTION SHALL BE THOROUGHLY CLEANED OF FOREIGN MATERIALPRIOR TO BEING PLACED BACK IN SERVICE.
42. THE FINISHED WORK SHALL BE FIRM, WELL ANCHORED, IN TRUE ALIGNMENT, PLUMB, LEVEL,WITH SMOOTH, CLEAN, UNIFORM APPEARANCE WITHOUT WAVES, DISTORTIONS, HOLES,MARKS, CRACKS, STAINS OR DISCOLORATION. JOINTS SHALL BE CLOSE FITTING, NEAT ANDWELL SCRIBED. THE FINISH SHALL NOT PRESENT HAZARDOUS, UNSAFE CORNERS. ALL WORKSHALL HAVE THE PROVISION FOR EXPANSION, CONTRACTION AND SHRINKAGE AS NECESSARYTO PREVENT CRACKS, BUCKLING AND WARPING DUE TO TEMPERATURE AND HUMIDITYCONDITIONS.
43. CUT AND FIT COMPONENTS FOR ALTERATIONS OF EXISTING WORK AND INSTALLATION OF NEWWORK. PATCH DISTURBED AREAS TO MATCH ADJACENT MATERIALS AND FINISHES IN EVERYRESPECT.
44. PATCH AND REPAIR ALL FIRESTOP DAMAGED OR REMOVED DURING PERFORMANCE OF THEWORK. FIREPROOF NEW PENETRATIONS REQUIRED BY THE WORK.
45. COORDINATE AND PROVIDE BLOCKING/BACKING IN PARTITIONS BEHIND ALL WALL-MOUNTEDITEMS. ALL BLOCKING TO BE STEEL.
46. PROVIDE STEEL SLEEVES FOR ALL NEW AND REUSED PENETRATIONS. SLEEVES SHALL BEGROUTED INTO CONCRETE OR BLOCK STRUCTURE, WELDED INTO STEEL STRUCTURE, ANDPATCHED INTO GYPSUM WALLS. SLEEVES IN GYPSUM WALLS SHALL BE SECURED TO STRUCTUREWITHIN WALL AND SHALL NOT BE FLOATING .
47. MAKE ALL NECESSARY PROVISIONS FOR ITEMS TO BE FURNISHED OR INSTALLED BY TENANTOR OCCUPANT AT THE CONCLUSION OF CONSTRUCTION. PROVIDE PROTECTION FOR THESEPROVISIONS UNTIL COMPLETION OF THE PROJECT. GENERAL CONTRACTOR TO COORDINATEIDENTIFIED N.I.C. ITEMS WITH APPROPRIATE TRADES, TENANT'S AND/OR INDEPENDENTCONTRACTORS.
48. GENERAL CONTRACTOR SHALL REVIEW THE BASE BUILDING CONTRACT DOCUMENTS OREXISTING BASE BUILDING CONDITIONS AND SHALL COMPLY WITH ALL BASE BUILDINGREQUIREMENTS, OWNER REQUIREMENTS, AND DESIGN CRITERIA.
49. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING CONTRACT DOCUMENTS, FIELDCONDITIONS AND DIMENSIONS FOR ACCURACY AND CONFIRMING THAT WORK IS BUILDABLE ASSHOWN BEFORE PROCEEDING WITH CONSTRUCTION. CLARIFICATIONS REGARDING ANYCONFLICTS SHALL BE ACHIEVED PRIOR TO RELATED WORK BEING STARTED.
50. GENERAL CONTRACTOR SHALL VERIFY THAT NO CONFLICTS EXIST IN LOCATIONS OF ANY ANDALL MECHANICAL, TELEPHONE, ELECTRICAL, PLUMBING AND SPRINKLER EQUIPMENT (TO INCLUDEALL PIPING, DUCTWORK AND CONDUIT) AND THAT ALL REQUIRED CLEARANCES FORINSTALLATION AND MAINTENANCE OF ABOVE LISTED EQUIPMENT ARE PROVIDED. ELEMENTS TOBE EXPOSED OR CONCEALED SHALL BE DETERMINED AND REVIEWED WITH ENGINEER PRIOR TOCONSTRUCTION PROCEEDING.
51. GENERAL CONTRACTOR AND SUBCONTRACTORS SHALL COORDINATE THE LAYOUT AND EXACTLOCATION OF ALL PARTITIONS, DOORS, ELECTRICAL/TELEPHONE/DATA OUTLETS, LIGHTSWITCHES AND ACCESS PANELS IN THE FIELD BEFORE PROCEEDING WITH CONSTRUCTION.
52. GENERAL CONTRACTOR IS RESPONSIBLE FOR AND SHALL PROVIDE PROTECTION FOR ALLEXISTING BUILDING FINISHES INCLUDING ELEVATORS, LOBBIES AND CORRIDORS OUTSIDE THEAREA OF WORK BUT WHICH WILL BE USED BY THE CONTRACTORS DURING CONSTRUCTION.GENERAL CONTRACTOR SHALL RESTORE THESE AREAS TO PRE-CONSTRUCTION CONDITION ANDIS RESPONSIBLE TO REPAIR, AT THEIR COST, ANY DAMAGE TO THE BUILDING CREATED BY THEIRWORK.
53. GENERAL CONTRACTOR SHALL EXERCISE EXTREME CARE AND PRECAUTION DURINGCONSTRUCTION OF THE WORK TO MINIMIZE DISTURBANCES TO ADJACENT TENANTS,OCCUPANTS, PROPERTY, PUBLIC THOROUGHFARES, ETC. GENERAL CONTRACTOR SHALL TAKEPRECAUTIONS AND BE RESPONSIBLE FOR THE SAFETY OF ALL BUILDING OCCUPANTSTHROUGHOUT THE DURATION OF CONSTRUCTION.
54. CORING, DRILLIING OR OTHER SUCH WORK IN OR ADJACENT TO OCCUPIED AREAS SHALL BEPERFORMED AT OTHER THAN NORMAL WORKING HOURS FOR THE AFFECTED OCCUPANCYUNLESS OTHERWISE INDICATED. GENERAL CONTRACTOR SHALL DIRECTLY COORDINATE WITHBUILDING OWNER'S REPRESENTATIVE AND AFFECTED OCCUPANT(S).
55. NO CORE DRILLING SHALL BE PERFORMED AFTER 8:30 AM MONDAY THROUGH FRIDAY,WITHOUT PRIOR PERMISSION OF ADJACENT OCCUPANT(S). WITH REGARD TO CORE DRILLEDSLAB OPENINGS, A DRAWING SHOWING THE LOCATION AND SIZE FOR ALL OPENINGS SHALL BESUBMITTED TO THE BUILDING OWNER'S REPRESENTATIVE FOR REVIEW BY THE BUILDINGSTRUCTURAL ENGINEER. THE FOLLOWING PROCEDURE SHALL BE EFFECTED:
55.1. OPENINGS SHALL NOT BE CLOSER THAN 2'-0" FROM THE FACE OF ANY COLUMN.55.2. OPENINGS SHALL NOT BE PERMITTED EITHER HORIZONTALLY OR VERTICALLY THROUGH
BEAMS.55.3. OPENINGS SHALL NOT BE CORED UNTIL IT IS DETERMINED THAT THE REINFORCING OR
TENDONS WILL NOT BE DAMAGED.55.4. OPENINGS AND/OR DAMAGED AREAS SHALL THEN BE PATCHED WITH NON-SHRINK GROUT
IN THE AREAS SUBJECT TO MOISTURE SUCH AS RESTROOMS, PANTRIES, JANITORCLOSETS, GARAGES, ETC. THE NON- SHRINK GROUT SHALL BE PLACED AT THE LOWER HALFOF THE OPENING AND THE UPPER HALF OF THE OPENING, THEN FILLED WITH JOINT SEALERAS USED IN BASE BUILDING CONSTRUCTION.
55.5. FIRESTOPPING OF RATED ASSEMBLIES SHALL BE PERFORMED IN A MANNER CONSISTENTWITH RECOGNIZED METHODS AND DESIGN TESTS.
56. UTILITY OUTAGES SHALL BE SCHEDULED OUTSIDE NORMAL WORKING HOURS FOR THEAFFECTED OCCUPANCY UNLESS OTHERWISE INDICATED.
57. THE GENERAL CONTRACTOR SHALL TAKE ALL REASONABLE CONTROL AND PRECAUTION TOELIMINATE DUST, NOISE, ODOR NUISANCE, WATER PENETRATION AND THE LIKE TO THEPREMISES AND THE OCCUPANCY.
58. SOUND CAULK ALL ACOUSTICAL WALLS, TOP AND BOTTOM JOINTS, WITH APPROVEDACOUSTICAL CAULKING.
59. ONLY NEW ITEMS OF RECENT MANUFACTURE, OF STANDARD QUALITY, FREE FROM DEFECTS,WILL BE PERMITTED. REJECTED ITEMS SHALL BE REMOVED IMMEDIATELY FROM THE SITE ANDREPLACED WITH ITEMS OF THE QUALITY SPECIFIED. FAILURE TO REMOVE REJECTED MATERIALSAND EQUIPMENT SHALL NOT RELIEVE THE CONTRACTOR FROM THE RESPONSIBILITY FORQUALITY AND CHARACTER OF ITEMS USED NOR FROM ANY OTHER OBLIGATION IMPOSED ONHIM BY THE CONTRACT.
60. ATTACHMENTS, CONNECTIONS OR FASTENINGS OF ANY NATURE ARE TO BE PROPERLY ANDPERMANENTLY SECURED IN CONFORMANCE WITH BEST PRACTICES. THE CONTRACTOR ISRESPONSIBLE FOR IMPROVING THEM ACCORDINGLY AND TO THESE CONDITIONS. THEDRAWINGS SHOW ONLY GENERAL CONDITIONS TO ASSIST CONTRACTOR; THEY DO NOTILLUSTRATE NOR ARE THEY INTENDED TO SUGGEST EVERY SUCH DETAIL REQUIRED TO PERFORMTHE WORK.
61. UNLESS OTHERWISE SPECIFICALLY MENTIONED, ALL ANCHORS, BOLTS, SCREWS, FITTINGS,FILLER, HARDWARE, ACCESSORIES, TRIM AND OTHER PARTS REQUIRED FOR, OR INCONNECTION WITH, AN ITEM OR MATERIAL TO MAKE A COMPLETE, SERVICEABLE, FINISHED ANDFIRST QUALITY INSTALLATION SHALL BE FURNISHED AND INSTALLED AS PART OF THE ITEM ORMATERIAL, WHETHER CALLED FOR OR NOT.
62. UNLESS OTHERWISE SPECIFICALLY MENTIONED, ALL ITEMS AND PARTS THEREOF THAT ARE MADEOF STEEL, IRON OR OTHER FERROUS METAL THAT ARE NOT GALVANIZED, PLATED OROTHERWISE SPECIFIED TO BE FACTORY FINISHED, SHALL BE CLEANED AND PAINTED WITH ONECOAT OF BEST QUALITY RUST INHIBITIVE METALLIC PRIMER PRIOR TO APPLYING THE FINISHEDCOAT OF PAINT.
63. AFTER INSTALLATION, ALL EXPOSED METAL CONNECTIONS AND ABRASIONS SHALL BETOUCHED-UP WITH THE SAME MATERIAL AS THE SHOP COAT AND LEFT IN GOOD CONDITIONFOR FINAL FINISHING.
64. PROVIDE A MINIMUM OF TWO COATS OF FINAL FINISH PAINT ON ALL EXPOSED METAL, PRIMECOATED, AND CONCRETE COMPONENTS; COLOR TO BE COORDINATED WITH OWNER ANDENGINEER. CONTRACTOR SHALL APPLY AS MANY COATS OF PAINT AS NECESSARY TO PROVIDEA THOROUGH AND CONSISTENT FINISH.
65. ALL GALVANIZED COMPONENTS FIELD CUT TO FIT THE PROJECT REQUIREMENTS SHALL HAVE ALLEXPOSED METAL CLEANED AND PAINTED WITH A GALVANIC PAINT TO MATCH THE FINISH COAT.PROVIDE A MINIMUM OF TWO COATS OF PAINT.
66. CONTRACTOR SHALL PAINT ALL WELDS WITH ZINC RICH RUST INHIBITIVE PRIMER IMMEDIATELYFOLLOWING WELDING.
67. ALL THREADED ROD USED TO SUPPORT TRAPEZE, EQUIPMENT, STRUT, OR OTHER COMPONENTSWHERE THE THREADED END OF THE ROD IS EXPOSED SHALL BE TRIMMED TO WITHIN AN INCHOF THE SUPPORTED ITEM AND SHALL BE FINISHED OFF WITH AN ACORN NUT AND LOCK NUT.THREADED ROD INSTALLED FOR A SPECIAL PURPOSE WHEREBY THIS FINISHING METHOD WOULDNOT BE ACCEPTABLE SHALL BE COORDINATED WITH THE ENGINEER.
68. EQUIPMENT, CONDUIT, PIPING OR OTHER INSTALLED COMPONENTS MAY NOT BE SUPPORTEDFROM WOODEN STRUCTURES. PROVIDE CONDUIT, PIPING, DUCTWORK, AND EQUIPMENTSUPPORTS FROM STRUCTURAL STEEL, MASONRY WALLS, OR INDEPENDENT STRUCTURALSUPPORTS FROM FLOOR. PROVIDE SUPPORTS AT CODE OR MANUFACTURER REQUIREDINTERVALS OR AS SPECIFIED, WHICHEVER IS MORE STRINGENT.
69. FOR ALL FINISHED SPACES, NO SURFACE MOUNTED RACEWAY, BOXES, CONDUIT, PIPING,DUCTWORK, OR ACCESSORIES SHALL BE PERMITTED WITHOUT WRITTEN APPROVAL.
70. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY PROTECTION OF THEFACILITY THROUGHOUT CONSTRUCTION. THIS INCLUDES PROTECTION OF ENVIRONMENTALSYSTEMS, SEPARATION OF CONSTRUCTION AREA FROM OCCUPIED SPACES, AND OVERSEEINGEXPOSED ELECTRICAL COMPONENTS. EXPOSED ELECTRICAL COMPONENTS MUST BE PROPERLYIDENTIFIED AND PROTECTED WITH OSHA & UL APPROVED PROTECTIVE COVERINGS. GENERALCONTRACTOR SHALL PROVIDE SAFETY BARRIERS, CONES, WARNING NOTICES, AND OTHERPROTECTIVE BARRIERS TO SEPARATE THE CONSTRUCTION AREA FROM GENERAL PUBLIC AREAS.GENERAL CONTRACTOR SHALL PROVIDE ALL CONSTRUCTION WARNING SAFETY SIGNS FOR THEGENERAL PUBLIC. SIGNAGE SHALL BE POSTED AT ALL LOCATIONS WHERE CONSTRUCTIONAREAS COMMUNICATE WITH GENERAL PUBLIC AREAS.
71. ALL PENETRATIONS OF WALLS, PARTITIONS, CHASES, SHAFTS, FLOORS AND ROOFS SHALL BECOMPLETELY SEALED. PENETRATIONS THROUGH FIRE-RATED WALLS AND FLOORS SHALL BESEALED TO PROVIDE A RATING RATING EQUAL TO OR GREATER THAN THAT OF THE WALL ORFLOOR PENETRATED.
72. CONTRACTOR SHALL VERIFY ALL VOLTAGE AND POWER REQUIREMENTS AND COORDINATE WITH
FLOOR PENETRATED.
72. CONTRACTOR SHALL VERIFY ALL VOLTAGE AND POWER REQUIREMENTS AND COORDINATE WITHELECTRICAL CONTRACTOR.
73. ALL ITEMS AND PARTS THEREOF THAT ARE MADE OF STEEL, IRON OR OTHER FERROUS METALTHAT ARE NOT GALVANIZED, PLATED OR OTHERWISE SPECIFIED TO BE FACTORY FINISHED,SHALL BE CLEANED AND PAINTED WITH ONE COAT OF BEST QUALITY RUST INHIBITIVE METALLICPRIMER. AFTER INSTALLATION, ALL EXPOSED METAL CONNECTIONS AND ABRASIONS SHALL BETOUCHED-UP WITH THE SAME MATERIAL AS THE PRIMED COAT AND LEFT IN GOOD CONDITIONFOR FINAL FINISHING.
74. PROVIDE A MINIMUM OF TWO COATS OF FINAL FINISH PAINT ON ALL EXPOSED METAL ANDCONCRETE COMPONENTS; COLOR TO BE AS SPECIFIED. CONTRACTOR SHALL APPLY AS MANYCOATS OF PAINT AS NECESSARY TO PROVIDE A THOROUGH AND CONSISTENT FINISH.
75. ALL GALVANIZED COMPONENTS FIELD CUT TO FIT SHALL HAVE ALL EXPOSED METAL CLEANEDAND PAINTED WITH A GALVANIC PAINT TO MATCH THE GALVANIZED FINISH. PROVIDE A MINIMUMOF TWO COATS OF PAINT.
76. ALL THREADED ROD USED TO SUPPORT TRAPEZE, EQUIPMENT, STRUT, OR OTHER COMPONENTSWHERE THE THREADED END OF THE ROD IS EXPOSED SHALL BE TRIMMED TO WITHIN AN INCHOF THE SUPPORTED ITEM AND SHALL BE FINISHED OFF WITH AN ACORN NUT AND LOCK NUT.THREADED ROD INSTALLED FOR A SPECIAL PURPOSE WHEREBY THIS FINISHING METHOD WOULDNOT BE ACCEPTABLE SHALL BE COORDINATED WITH THE ENGINEER.
77. CONTRACTOR TO FIELD VERIFY AND ADJUST LAYOUT ACCORDINGLY.
78. CONTRACTOR, AT HIS OWN EXPENSE, SHALL REPAIR OR REPLACE ANY EXISTING MATERIAL OREQUIPMENT DAMAGED DURING CONSTRUCTION. REPAIR OR REPLACEMENT SHALL BE AT THEDISCRETION OF THE ENGINEER AND OWNER AND SHALL NOT BE NEGOTIABLE. IF IN THEASSESSMENT OF THE ENGINEER AND OWNER, THE ITEM DAMAGED SHOULD BE REPLACED IN ITSENTIRETY, THE CONTRACTOR SHALL DO SO AT HIS EXPENSE AND TO THE SPECIFICATIONREQUIREMENTS SET FORTH BY THE ENGINEER.
79. VERIFY ALL VOLTAGE AND POWER REQUIREMENTS AND COORDINATE WITH MECHANICALCONTRACTOR. ADJUST BREAKER SIZES, FUSE SIZES, AMPACITY, POLES, VOLTAGE, ETC. TOMATCH EQUIPMENT BEING FURNISHED.
80. WHERE NEW CIRCUITS ARE FED FROM EXISTING PANELS, WIRE NEW CIRCUITS TO EXISTING FREECIRCUITS OR SPACES. PROVIDE NEW CIRCUIT BREAKER FOR ALL NEW CIRCUITS REPLACINGEXISTING BREAKERS; TURN OVER REMOVED BREAKERS TO OWNER. CIRCUIT BREAKER SHALLMATCH EXISTING BREAKERS IN MANUFACTURER, STYLE, TYPE AND INTERRUPTING RATING.
81. CIRCUITS AS SHOWN ARE REPRESENTATIVE ONLY, ELECTRICAL CONTRACTOR SHALL FIELDCOORDINATE ALL NEW CIRCUITS TO OPTIMIZE PANEL SPACES USED.
82. TERMINATE ALL CONDUIT ENDING IN CEILING 12" AFC WITH BUSHINGS TO PROTECT WIRES FROMCHAFING.
83. CONTRACTOR SHALL PROVIDE PULL STRINGS IN ALL CONDUIT INSTALLED FOR OTHER TRADES.
84. CONTRACTOR SHALL PROVIDE ALL NEW WIRING FROM CEILING ABOVE UNLESS OTHERWISENOTED.
85. ALL WIRING ABOVE CEILING SHALL BE IN CONDUIT.
86. TAG ALL ELECTRICAL PANELS, DISCONNECTS, AND ELECTRIC METERS. TAGS SHALL BEENGRAVED DUAL COLOR PLASTIC LABELS (LAMICOID) WITH WHITE LETTERING OVER A BLACKBACKGROUND. LETTER HEIGHT OF FIRST LINE OF LABEL SHALL BE 1" HIGH, REMAINING LINES OFLABEL SHALL BE MINIMUM 3/4" HIGH. LABEL SHALL BE FASTENED TO PANEL FACE WITH RIVETS,ONE AT EACH CORNER.
87. ADJUST FUSE SIZES IN ALL FUSED DISCONNECTS TO SIZE AS SPECIFIED BY MANUFACTURER OFEQUIPMENT.
88. FOR ALL FINISHED SPACES, NO SURFACE MOUNTED RACEWAY, BOXES, CONDUIT, ORACCESSORIES SHALL BE PERMITTED WITHOUT WRITTEN APPROVAL.
89. MARK, IDENTIFY, AND COLOR CODE ALL CONDUIT, AC OR MC CABLE, AND STRUCTURED CABLEINSTALLED FOR THIS PROJECT IN ACCORDANCE WITH SPECIFICATIONS.
90. MOTOR CONNECTIONS TO BE MADE WITH MAXIMUM 2'-0" LIQUID TIGHT/FLEX, SEAL TIGHT.
91. REFER TO SPECIFICATIONS FOR ALL MATERIAL, COMPONENTS, DEVICES AND ACCESSORIESREQUIRED FOR THE PROJECT.
92. TAG ALL RECEPTACLES AND SWITCHES WITH 1/2" HIGH "P-TOUCH" STYLE LABELS INDICATING THECIRCUIT SERVING THE DEVICE. REFER TO DETAIL.
93. ALL WIRE SIZES ARE BASED ON COPPER, UNLESS OTHERWISE NOTED.
1. THESE PROJECT DOCUMENTS IN THE FORM OF PLANS AND SPECIFICATIONS ARE INTENDED TOSHOW THE GENERAL SCOPE OF THE DEMOLITION FOR THE PROJECT. THESE DOCUMENTS DONOT AND ARE NOT INTENDED TO IDENTIFY EVERY PARTICULAR ELEMENT WHICH IS TO BEDEMOLISHED RATHER, THEY IDENTIFY THE GENERAL SCOPE OF THE DEMOLITION, THE AFFECTEDAREAS OF WORK, AND THEREBY DIRECTS THE CONTRACTOR TO DEMOLISH ALL ELEMENTSEFFECTED OR ABANDONED AS A RESULT OF THIS DEMOLITION ACTIVITY, WHETHER SHOWN,IDENTIFIED, OR NOT. THE GENERAL CONTRACTOR SHALL COORDINATE THE DEMOLITIONPERFORMED BY ALL OTHER TRADES. WHERE THE GENERAL CONTRACTOR IS UNCERTAIN IF ANITEM IS SCHEDULED TO BE DEMOLISHED, OR THE ENTIRE SCOPE OF THE DEMOLITION; THECONTRACTOR SHALL CONSULT WITH THE PROJECT MANAGER AND ENGINEER FOR DIRECTIONPRIOR TO COMMENCING WITH DEMOLITION.
2. EQUIPMENT BEING DEMOLISHED SHALL BE DEMOLISHED IN ITS ENTIRETY. THIS INCLUDES ALLUTILITY CONNECTIONS: GAS, ELECTRIC, WATER, FIRE ALARM, SPRINKLER, AND ANY OTHER UTILITYCONNECTION. GENERAL CONTRACTOR SHALL ENSURE THAT ALL DEMOLISHED UTILITIES AREDEMOLISHED COMPLETELY BACK TO THEIR SOURCE. ABANDONED PIPING, CONDUIT, OR OTHERITEMS SHALL BE REMOVED.
3. GENERAL CONTRACTOR SHALL CUT OFF BELOW THE FINISHED FLOOR ALL PIPE, CONDUIT, ORSTRUCTURAL SUPPORTS EMBEDDED IN CONCRETE. GENERAL CONTRACTOR SHALL PATCH FLOORWITH NON-SHRINKING GROUT OR EPOXY.
4. GENERAL CONTRACTOR SHALL HAVE ALL COMPUTER BASED EQUIPMENT REPROGRAMMED TOREFLECT DEMOLISHED COMPONENTS. FIRE ALARM AND SECURITY SYSTEMS SHALL BEREPROGRAMMED ON THE DAY THE COMPONENTS ARE DEMOLISHED TO PREVENT NUISANCETRIPS OR ALARMS.
5. GENERAL CONTRACTOR SHALL ENSURE THAT THE ELECTRICAL CONTRACTOR SAFES OFF ALLCIRCUITS ABANDONED AS PART OF DEMOLITION. CIRCUITS SHALL BE MADE SAFE DURING THEDEMOLITION PROCESS THROUGH UTILIZING LOCK-OUT AND TAG-OUT SAFETY PROCEDURES.PROVIDE OSHA APPROVED SAFETY COVERS OVER ALL EXPOSED LIVE PARTS.
6. GENERAL CONTRACTOR SHALL ENSURE THAT THE MECHANICAL AND PLUMBING CONTRACTORSSAFE OFF ALL GAS, HYDRAULIC, HYDRONIC, SANITARY, SPRINKLER, AND WATER LINES AS PARTOF DEMOLITION.
7. GENERAL CONTRACTOR SHALL SEAL AND PROTECT ALL BUILDING PENETRATIONS INCLUDINGROOF OPENINGS AS PART OF DEMOLITION. ALL OPENINGS SHALL BE SEALED WATER TIGHT.
8. ALL PENETRATIONS CREATED OR LEFT BEHIND IN INTERIOR WALLS, CEILINGS, OR FLOORS AS ARESULT OF DEMOLITION SHALL BE COMPLETELY FIRE STOPPED BY APPROVED SPECIFIEDMETHODS. PROJECT MANAGER AND ENGINEER SHALL APPROVE ALL FIRE STOPPING METHODSPRIOR TO THEIR EXECUTION AND THE CONTRACTOR SHALL PROVIDE A FIRE STOPPING METHODSSUBMITTAL FOR APPROVAL. WHERE APPLICABLE, CONTRACTOR SHALL FOLLOW BUILDINGSTANDARD FIRE STOPPING METHODS.
9. ALL EXISTING ELECTRICAL CIRCUITS INTERRUPTED AS A RESULT OF DEMOLITION THAT ARE TOREMAIN SHALL BE IMMEDIATELY RESTORED TO COMPLETE OPERATING CONDITION.
10. CRITICAL UTILITIES THAT ARE TO OR MAY BE INTERRUPTED AS PART OF THE DEMOLITIONPROCESS SHALL BE FIELD IDENTIFIED BY THE CONTRACTOR AND APPROVAL SOUGHT PRIOR TOTHEIR INTERRUPTION. COORDINATE WITH THE PROJECT MANAGER AND THE OWNER ALLPOTENTIAL ELECTRICAL DISRUPTIONS WHICH MAY AFFECT THE OPERATION OF THE FACILITYDURING CONSTRUCTION.
11. CONTRACTOR SHALL PREPARE A WRITTEN M.O.P. (METHOD OF PROCEDURE) FOR THEINTERRUPTION AND RESTORATION OF ACTIVE UTILITIES DURING THE DEMOLITION PROCESS. MOPSHALL INCLUDE IDENTIFICATION OF EFFECTED SYSTEMS, BACK OUT PLAN, DURATION OFDISRUPTION, AND ALTERNATE METHOD OF SERVING THE AFFECTED SYSTEMS.
13. CONTRACTOR SHALL PREPARE A WRITTEN M.O.P. (METHOD OF PROCEDURE) FOR ALL REQUIREDUTILITY OUTAGES REQUIRED FOR THE PROJECT. MOP SHALL INCLUDE IDENTIFICATION OFEFFECTED AREAS, BACK OUT PLAN, DURATION OF DISRUPTION, AND ALTERNATE METHOD OFSERVING THE AFFECTED SYSTEMS.
14. GENERAL CONTRACTOR SHALL COORDINATE THE PROVISION OF TEMPORARY POWER ANDLIGHTING FOR ALL AREAS OF WORK AS REQUIRED TO MAINTAIN SAFE WORK CONDITIONS ANDAS REQUIRED BY ALL OTHER TRADES PERFORMING WORK ON THE PROJECT.
15. GENERAL CONTRACTOR SHALL PROPERLY DISPOSE OF ALL DEBRIS, EQUIPMENT, DEVICES,MATERIALS, AND MISCELLANEOUS ACCESSORIES DEMOLISHED AS PART OF THE PROJECT.
16. THIS PROJECT HAS A SPECIFIC DISPOSAL PLAN, THE CONTRACTOR SHALL FOLLOW ALL ASPECTSOF THE PLAN AS PART OF THIS PROJECT. GENERAL CONTRACTOR SHALL SEPARATE METALDEBRIS FROM GENERAL CONSTRUCTION DEBRIS. METAL DEBRIS IS TO BE TRANSPORTED TO THEAREA DESIGNATED BY THE OWNER; THE OWNER SHALL RETAIN ALL SCRAP METAL DEBRIS. THISINCLUDES ELECTRICAL WIRE AND CABLE, PIPING, EQUIPMENT, APPLIANCES, OR OTHER METALITEMS DEMOLISHED AS PART OF THE PROJECT. METAL INCLUDES: COPPER, ALUMINUM, ANDSTEEL (STAINLESS AND BLACK).
17. GENERAL CONTRACTOR SHALL PROVIDE ALL REQUIRED PAPERWORK FOR TRACKING THEDISPOSAL OF HAZARDOUS MATERIALS DEMOLISHED AS PART OF THIS PROJECT. THIS INCLUDESTHE PROPER DISPOSAL OF BALLASTS, LIGHT TUBES, OIL FILLED TRANSFORMERS ANDTRANSFORMER OIL, AND ALL OTHER ITEMS THAT MAY BE SO CLASSIFIED.
18. ELECTRICAL MOTORS DEMOLISHED AS PART OF THIS PROJECT SHALL BE TURNED OVER TO THEOWNER.
19. REPAIR ALL ADJACENT CONSTRUCTION AND FINISHED DAMAGED AS A RESULT OF THEDEMOLITION. THIS INCLUDES PATCHING WALLS, SEALING OPENINGS (EXTERIOR AND INTERIOR),REPLACING CEILING TILES, PAINTING TO MATCH, AND ALL OTHER REPAIRS NECESSARY TO LEAVETHE SPACE IN PRISTINE CONDITION.
20. EQUIPMENT IDENTIFIED TO BE REUSED SHALL BE MAINTAINED IN SERVICEABLE CONDITION ANDSHALL BE KEPT IN A SAFE PLACE FROM THE TIME IT IS REMOVED TO THE TIME IT ISRE-INSTALLED. CLEAN, TUNE, CALIBRATE, REPAIR, AND OTHERWISE SERVICE EXISTINGEQUIPMENT PRIOR TO ITS RE-INSTALLATION.
21. GENERAL CONTRACTOR SHALL MAINTAIN CLEAR ACCESS TO ALL ELECTRICAL SYSTEMSTHROUGHOUT DURATION OF DEMOLITION.
22. COORDINATE ELECTRICAL DEMOLITION WITH ALL OTHER TRADES. ELECTRICAL WIRINGABANDONED AS A RESULT OF THE DEMOLITION OF WALL, CEILINGS, AND OTHER ELEMENTSSHALL BE IMMEDIATELY DEMOLISHED. ELECTRICAL WIRING ABANDONED AS A RESULT OF THEDEMOLITION OF MECHANICAL EQUIPMENT OR SYSTEMS SHALL BE IMMEDIATELY DEMOLISHED.
23. DEMOLITION OF WIRING INCLUDES AS A MINIMUM THE COMPLETE DISCONNECTION OF THEAFFECTED EQUIPMENT OR DEVICES, REMOVAL OF ALL CONDUIT & WIRING FROM THATEQUIPMENT OR DEVICE BACK TO ITS SOURCE PANEL, AND VACATING THE WIRING FROM THEELECTRICAL CIRCUIT BREAKER. THE PANEL SCHEDULE IN THE SOURCE PANEL SHALL BE UPDATEDTO REFLECT A "SPARE" BREAKER WHERE THE BREAKER FORMERLY SERVED THE EQUIPMENT ORDEVICE.
24. DEMOLISH ALL WIRE, CONDUIT, AND APPARATUS ASSOCIATED WITH EQUIPMENT BEINGREMOVED. FIELD VERIFY AND IDENTIFY ALL CIRCUIT ARRANGEMENTS PRIOR TO DEMOLITION.
25. ALL CABLE, CONDUIT, CONDUCTORS, BOXES, AND MISCELLANEOUS ACCESSORIES FOUNDHANGING OR LOOSE AS THE RESULT OF OR AS REVEALED BY PROJECT DEMOLITION SHALL BERE-SECURED TO THE BUILDING STRUCTURE REGARDLESS OF WHETHER THE CONDITION FOUNDWAS A DIRECT RESULT OF THE PROJECT DEMOLITION OR AN EXISTING CONDITION.
26. ALL PENETRATIONS CREATED OR LEFT BEHIND AS A RESULT OF DEMOLITION SHALL BECOMPLETELY FIRE STOPPED BY APPROVED SPECIFIED METHODS. PROJECT ARCHITECT ANDENGINEER SHALL APPROVE ALL FIRE STOPPING METHODS PRIOR TO THEIR EXECUTION AND THECONTRACTOR SHALL PROVIDE A FIRE STOPPING METHODS SUBMITTAL FOR APPROVAL.
27. ALL EXISTING CIRCUITS INTERRUPTED AS A RESULT OF DEMOLITION THAT ARE TO REMAIN SHALLBE IMMEDIATELY RESTORED TO COMPLETE OPERATING CONDITION.
28. CRITICAL CIRCUITS THAT ARE TO OR MAY BE INTERRUPTED AS PART OF THE DEMOLITIONPROCESS SHALL BE FIELD IDENTIFIED BY THE CONTRACTOR AND APPROVAL SOUGHT PRIOR TOTHEIR INTERRUPTION. COORDINATE WITH THE PROJECT MANAGER AND THE OWNER ALLPOTENTIAL ELECTRICAL DISRUPTIONS WHICH MAY AFFECT THE OPERATION OF THEIR FACILITYDURING CONSTRUCTION.
29. PROVIDE TEMPORARY POWER AND LIGHTING FOR ALL AREAS OF WORK AS REQUIRED TOMAINTAIN SAFE WORK CONDITIONS AND AS REQUIRED BY ALL OTHER TRADES PERFORMINGWORK ON THE PROJECT.
30. PROVIDE TEMPORARY WIRING AND CONNECTION FOR ALL ELECTRICAL CIRCUITS TO MAINTAINEXISTING EQUIPMENT IN COMPLETE OPERATION FOR THE DURATION OF THE CONSTRUCTION ORUNTIL THE PERMANENT ELECTRICAL CONNECTIONS FOR EQUIPMENT ARE INSTALLED.
31. PROPERLY DISPOSE OF ALL ELECTRICAL EQUIPMENT, DEVICES, MATERIALS, AND MISCELLANEOUSACCESSORIES DEMOLISHED AS PART OF THE PROJECT. IF THE PROJECT HAS A SPECIFICDISPOSAL PLAN, THE CONTRACTOR SHALL FOLLOW ALL ASPECTS OF THE PLAN AS PART OF THISPROJECT.
32. PROVIDE BLANK STEEL COVER PLATES FOR ALL ELECTRICAL BOXES FREED AS PART OFDEMOLITION BUT WHICH CANNOT BE REMOVED. COORDINATE COLOR AND FINISH WITHARCHITECT.
33. REPAIR ALL ADJACENT CONSTRUCTION AND FINISHED DAMAGED AS A RESULT OF THEELECTRICAL DEMOLITION. THIS INCLUDES PATCHING WALLS, SEALING OPENINGS (EXTERIOR ANDINTERIOR), REPLACING CEILING TILES, PAINTING TO MATCH, AND ALL OTHER REPAIRS NECESSARYTO LEAVE THE SPACE IN PRISTINE CONDITION.
34. EQUIPMENT IDENTIFIED TO BE REUSED SHALL BE MAINTAINED IN SERVICEABLE CONDITION ANDSHALL BE KEPT IN A SAFE PLACE FROM THE TIME IT IS REMOVED TO THE TIME IT ISRE-INSTALLED. CLEAN, TUNE, CALIBRATE, REPAIR, AND OTHERWISE SERVICE EXISTINGEQUIPMENT PRIOR TO ITS RE-INSTALLATION.
35. MAINTAIN CLEAR ACCESS TO ALL ELECTRICAL SYSTEMS THROUGHOUT DURATION OFDEMOLITION.
36. CLEAN AND SERVICE ALL EXISTING ELECTRICAL EQUIPMENT AFFECTED OR TOUCHED AS A RESULTOF DEMOLITION. CLEAN DEBRIS FROM EXISTING (AND NEW) ELECTRICAL PANELS, NEATENELECTRICAL WIRING IN EXISTING PANELS AND DEVICES, IDENTIFY WIRING FIELD VERIFIED AS ARESULT OF DEMOLITION (USE BRADY TAGS), TORQUE TO MANUFACTURES SPECIFICATIONS ALLLUGS AND BREAKER CONNECTIONS. REPLACE FAILED CIRCUIT BREAKERS WITH NEW. ALLELECTRICAL COMPONENTS INCLUDING PANELS, DISCONNECTS, SPLICES, AND OTHER ELECTRICALELEMENTS SHALL BE SERVICES.
37. COORDINATE MECHANICAL DEMOLITION WITH ALL OTHER TRADES. MECHANICAL PIPING &DUCTWORK EXPOSED OR ABANDONED AS A RESULT OF THE DEMOLITION OF WALL, CEILINGS,AND OTHER ELEMENTS SHALL BE IMMEDIATELY RE-ROUTED OR DEMOLISHED AS DICTATED BYTHE PROJECT DOCUMENTS OR PROJECT NEED. PIPING AND DUCTWORK ABANDONED AS ARESULT OF THE DEMOLITION OF MECHANICAL EQUIPMENT OR SYSTEMS SHALL BE IMMEDIATELYDEMOLISHED.
38. DEMOLITION OF PIPING INCLUDES AS A MINIMUM THE COMPLETE DISCONNECTION OF THEAFFECTED EQUIPMENT OR DEVICES, REMOVAL OF ALL PIPING & ACCESSORIES FROM THATEQUIPMENT OR DEVICE BACK TO ITS MAIN PIPING SOURCE AND COMPLETE CAPPING OF THEREMAINING PIPING THROUGH APPROVED METHODS. THIS INCLUDES THE RESTORATION OF ALLPIPE INSULATION DISTURBED OR AFFECTED BY THE DEMOLITION.
39. AS SHOWN THE DEMOLITION DRAWINGS ARE FOR INFORMATIONAL PURPOSES AND AREINTENDED TO ILLUSTRATE THE CURRENT CONFIGURATION OF THE MECHANICAL SYSTEMS IN THEFACILITY. PIPING IS TO BE DEMOLISHED ONLY TO THE EXTENT NECESSARY TO FACILITATE THEINSTALLATION OF NEW EQUIPMENT.
DANIEL B. GROVER, PE
THE STATE OF NEW JERSEYLICENSED
PROFESSIONAL ENGINEER24GE44239
The Great Meadows Design Group, LLCA Professional Engineering Company
24 Far View RoadGreat Meadows, New Jersey 07838
(908) 637-8233 Fax (908) 637-8234
www.TheGMDGroup.com
New Jersey Authorization Number: 24GA28095500
REVISIONS/ISSUES
MAY 3, 2017
17016
DBG
No. Revision/Issue Date
WARREN COUNTY VOCATIONALSCHOOL
SECURITY UPGRADE
TOWNSHIP OF WASHINGTONWARREN COUNTY, NEW JERSEY
GENERAL NOTES
GENERAL ANDDEMOLITION NOTES
G-2N.T.S.
- -RASDEMOLITION NOTES
VESTIBULE STORAGE
ELECTRICAL
ROOM
WOMENS
TOILET
MENS
TOILET
J.C.
TV
STUDIO
74
CLASSROOM
75
ELECTIRIC
ROOM
STAGE
THEATER
LOBBY
CLASSROOM
76
CLASSROOM
77
CLASSROOM
78
CLASSROOM
79
CLASSROOM
80
CLASSROOM
81
CLASSROOM
82
OFFICE
OFFICE
COMMUNITY
HEALTH
88
GRAPHIC ART /
COMMCERCIAL ART
87
SPRINKLER
CONTROL
ROOM
CLASSROOM
86
CHEMISTRY
85
LAW &
PUBLIC
SAFETY
84
STORAGE
CLASSROOM
91
J.C.
WOMENS
TOILET
MENS
TOILET
CHILD
DEVELOPMENT
83
PRE-K
HALLWAY
I
HALLWAY
L
HALLWAY
I
HALLWAY
L
HALLWAY
H
TW TW TW TW TW
TW
TW TW
TW
TW
TW
TW
TW
TW
DC
CR
DM
DC
DC
CR
DC
CR
DC
CR
1
ES
DC
ES ES
DM
DC
ES
DM
RM 66ARM 66A
DM
RM 66A
RM 66A
RM 91
(e)
DM
RM 91RM 91
(e)EXISTING COMPUTERRACK AND SECURITY COMPUTER
RM 91
2
DM
RM 91A
DM
(e)(e)
RM 91A
RM 91A
3
(2) (2)
(2)ES
(2)
(2)
(2)
4
4
4
4
(2)
25 (TYP.)
26
27
28 29
24 23
KEYED NOTES:
FLASHING BLUE "LOCKDOWN" INDICATOR LIGHT. CONTROLLED FROM NEWSECURITY SYSTEM.
INSTALL NEW 24 PORT PoE SWITCH IN EXISTING RACK FOR DOOR SECURITYSYSTEM.
VENDOR TO VERIFY AND CONFIRM THE BEST LOCATION FOR ALL WIRELESSACCESS POINTS TO PROVIDE PROPER BUILDING COVERAGE.
DOOR MODULE SHALL BE TIED TO PHONE SYSTEM TO RELEASE DOOR FROM KEYCODE FROM PHONES IN ADMINISTRATIVE OFFICES. COORDINATE WITH SCHOOL ITDEPARTMENT.
1
2
3
4
NOTES:
1. PROJECT REQUIREMENTS SHOWN ON SHEETS C-1, G-1 AND G-2 ARE THERESPONSIBILITY OF THIS AND ALL CONTRACTORS PROVIDING SERVICES FORTHIS PROJECT. CONTRACTOR SHALL COORDINATE THEM WITH ALL OTHERTRADES.
2. CONTRACTOR TO FURNISH AND INSTALL PLENUM RATED CAT6COMMUNICATION CABLES FROM EACH DOOR CONTROL MODULE TO SWITCH.TERMINATE DIRECTLY AT SWITCH.
3. ALL POWER REQUIRED SHALL BE PROVIDED BY THE OWNER.
4. CONTRACTOR SHALL PROVIDE ALL HARDWARE, INSTALLATION, AND WIRING ATEACH DOOR. INSTALL DOOR MODULE WIRING, TERMINATIONS, START-UP,AND PROGRAMMING. TYPICAL FOR ALL DOORS.
5. ALL DOOR CONTROL MODELS SHALL BE "POE" (POWER OVER ETHERNET) TYPE.CARD READER, DOOR CONTACTS, ELECTRIC STRIKES, MAGNETIC LOCKS ANDREQUEST TO EXIT DEVICES SHALL ALL BE POWERED THROUGH THE DOORCONTROL MODULE.
6. EXISTING BUILDING DOOR LOCK-SETS ARE MANUFACTURED BY "STANLEY/BEST". STANLEY/BEST IS THE BASIS OF DESIGN FOR ALL DOOR LOCK-SETS.
7. CONTRACTOR TO COORDINATE WITH OWNER'S INFORMATION TECHNOLOGYMANAGER THE CONNECTION OF NEW NETWORK SWITCHES TO THE EXISTINGBUILDING NETWORK INFRASTRUCTURE.
8. EXISTING HOST SOFTWARE IS VIDEO INSIGHT SOFTWARE. PROVIDENECESSARY HARDWARE AND COMPUTER INTERFACE TO INTEGRATE WITH THENEW STANLEY/BEST WI-Q LOCK-SETS.
9. COMPUTER WITH VIDEO INSIGHT SOFTWARE IS LOCATED IN ROOM #91.PROVIDE ALL PROGRAMMING, SET-UP, INTERFACE AND START UP OF DOORSYSTEM ON EXISTING SOFTWARE. PROVIDE ALL ACCESSORIES NEEDED TOPROPERLY INTERFACE VIDEO INSIGHT TO NEW DOOR MODULES ANDHARDWARE.
10. PROVIDE ALL NEW DOOR CONTROLLERS AND CARD READERS. REPLACEEXISTING WITH NEW AT ALL LOCATIONS.
11. REPLACE ALL EXISTING SECURITY COMPONENTS WITH NEW. TURN OVERDEMOLISHED COMPONENTS TO OWNER.
12. AT ALL MULTIPLE DOOR LOCATIONS, PROVIDE DOOR CONTACTS FOR EACHLEAF.
DANIEL B. GROVER, PE
THE STATE OF NEW JERSEYLICENSED
PROFESSIONAL ENGINEER24GE44239
The Great Meadows Design Group, LLCA Professional Engineering Company
24 Far View RoadGreat Meadows, New Jersey 07838
(908) 637-8233 Fax (908) 637-8234
www.TheGMDGroup.com
New Jersey Authorization Number: 24GA28095500
REVISIONS/ISSUES
MAY 3, 2017
17016
DBG
No. Revision/Issue Date
WARREN COUNTY VOCATIONALSCHOOL
SECURITY UPGRADE
TOWNSHIP OF WASHINGTONWARREN COUNTY, NEW JERSEY
PARTIAL FLOOR PLAN
PARTIAL FLOOR PLAN
E-1AS NOTED
- -RAS
COMPUTER
AIDED
DRAFTING
SHOWER
DRYING
TOIL.
TOIL.
STORAGE
INSTRUC.
GYMNASIUM
62
STORAGE OFFICE
SHOWER
STOR.
TOIL.
OFFICE
INSTRUC.VEST.
MECHANICAL / ELECTRICAL
J.C.
C
2
C
3
C
4
C
5
C
6
C
1
C
17
C
31
C
32
C
30
C
29
C
28
C
27
C
26
C
25
C
33
C
35
C
34
C
36
C
37
C
38
C
39
C
40
C
41
C
42
B
71
B
65
B
59
C
23
C
22
C
21
C
20
C
18
C
19
B
15
C
7
C
8
C
9
C
10
C
11
CAR WASH
LOCKER /
TOILET ROOM
LOCKER RM
ENGINEERING
LOCKER RM
TOIL.
CLASSROOM
WELDING
CAREERS
47
STORAGE
C.R.
AREA
OFFICE
OFFICE OFFICE OFFICE OFFICE GUIDANCE OFFICE
MAIN
OFFICE
MENWOMEN
CONF.
ROOM
STUDENT
SERVICES
STORAGELOCKER
TOILET AREA
OFFICE/
STORAGE
STORAGE
TOIL.
STORAGE
ELECTRICAL
DRYING
APPRETICESHIP
GED / ESL
OFFICE
CHIEF
SCHOOL
ADMIN
HALLWAY
A
STORAGE
NURSE
OFFICE
TOILETSTORAGE
FOOD
SERVICES
28
CLASSROOM
31
DATA
PROCESSING
LAB
30
STORAGE
TRANSFORMER
ROOM
27
SOCIAL
STUDIES
25
SOCIAL
STUDIES
24
CHEM.
LAB
22
MATH
21
ART
CLASSROOM
19
ART
SUPPLY
ELEC.
ROOM
20
STORAGE
PREP.
ROOM
CLASSROOM
18
GIRLS
LAV.
LIBRARY
9
WOMENS
FAC. LAV.
23
WORKROOM
13
TEACHERS
LOUNGE
14
MATH
CLASSROOM
12
BOYS
LAV.
CLASSROOM
11
ELEC
ROOM
7
HALLWAY
B
HALLWAY
A
HALLWAY
D
TOILET
STOR.
TOILET
CLOSET
LOBBY
CAFETERIA
HALLWAY
C
HALLWAY
C
ELECTRICAL
ROOM
MECHANICAL
ROOM
STORAGE
STORAGE H.C.
TOILET
FACULTY DINNING /
KNIGHTS CAFE
FOOD SERVICE
MENS
TOILET
WOMENS
TOILET
MENS
LOCKER
WOMENS
LOCKER
4746
CLASSROOM
44
CLASSROOM
41
HALLWAY
D
AUTO
SHOP
48
LOCKER /
TOILET ROOM
BUILDING
CONSTRUCTION
50
J.C.
OFFICE
CLASSROOM
52
HALLWAY
E
HALLWAY
G
BOYS
LOCKER ROOM
57
GIRLS
LOCKER ROOM
57
COSMOTOLOGY
63
CLASSROOM
64
CLASSROOM
66
LOCKER ROOMOFFICE
TOILET
CLASSROOM
66
ADMISSIONS
OFFICE
65
ELECT.
ROOM
TOIL.
ELECTRICAL
UV
UV
UV
UV
UVUVUVUVUVUVUV
UV
UV
UVUVUVUVUV
TW TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
TW
ELECTRONICS
1A
2A
2B
2C
3A
4A
1
1.1
2
3
4
5
6
66A
30A
DC
CR
1
DC
DC
CR
DC
DC
DC
DC
DC
DC
DC
DC
DC
CR
DC
CR
1
DC
CR
2
DC
CR
1
CR
DC
CR
2
CRCR
DC
ES
CRCR
DC
ESD
C
1
DC
CR
GATE OPERATOR
ES
ES
PAN
PAN
ES
ES
PAN
PAN
DC DC
DM
RM66A
RM 47
DM
RM 47
DM
RM 47
DM
RM 66A
(e)DM
RM 66A
ES
(e)DM
RM 66A
RM 66A
3
RM 66A
DM
RM 66A
EXISTING COMPUTERRACK
(e)
RM 7 DM
RM 7
DM
RM 7
RM 7
DM RM 7
DM
RM 7
(e) RM 7
4
EXISTING COMPUTERRACK
DM
RM 7
DM
RM 7
5
(e)
(e)
5
RM 7(e)
DMRM 7
DMRM 30A
(e)
(e)
DM
RM 30A
(e)
(e)
DM
RM 30A
PAN
PAN
DM
RM 30A
RM 30A
EXISTING COMPUTERRACK
3
DMRM 7
CR
CR
(e)
(2)
(2)
(2)
(2)
(2) (2)
(2)
CR
PAN
PAN
(2)
HANDICAPENTRANCE
HANDICAPENTRANCE
ELR
(2)(2)
ELR
ELR
ELR
ELR
ELR
ELR
ELR
(e)ES
DC
RM 47
FENCE
CARD-ACTIVATED GATE
17
22
6
21
20
14
13
1516
18
19
125
9
8
7
42
1110
5
6
3
4
(TYP.)
5
2
1
DC
DM
RM 47
(2)
23
DC
DM
RM 47
24
DC
DM
RM 47
(2)
25
DC
DM
RM 47
(2)
26
DC
DM
RM 47
25
EXISTING COMPUTERRACK
3
3
KEYED NOTES:
FLASHING BLUE "LOCKDOWN" INDICATOR LIGHT. CONTROLLED FROM NEWSECURITY SYSTEM.
EXISTING MOTOR OPERATED DOOR; HANDICAP ENTRANCE. CONTROL FROM NEWSECURITY SYSTEM. INTEGRATE EXISTING DOOR OPERATOR CONTROLS, MAGNETICLOCK RELEASE, AND EXISTING MANUAL PUSH BUTTON TO EXIT WITH NEWSECURITY DOOR CONTROLLER.
INSTALL NEW 24 PORT PoE SWITCH IN EXISTING RACK FOR DOOR SECURITYSYSTEM.
VENDOR TO VERIFY AND CONFIRM THE BEST LOCATION FOR ALL WIRELESSACCESS POINTS TO PROVIDE PROPER BUILDING COVERAGE.
PROVIDE STANLEY APEX 2200 SURFACE VERTICAL ROD EXIT DEVICES (LESSBOTTOM ROD) FOR EACH DOOR LEAF.
FUTURE GATE CONTROLS, PROVIDE (2) CARD READERS AS ATTIC STOCK. GATEOPERATOR N.I.C.
1
2
3
4
5
6
DANIEL B. GROVER, PE
THE STATE OF NEW JERSEYLICENSED
PROFESSIONAL ENGINEER24GE44239
The Great Meadows Design Group, LLCA Professional Engineering Company
24 Far View RoadGreat Meadows, New Jersey 07838
(908) 637-8233 Fax (908) 637-8234
www.TheGMDGroup.com
New Jersey Authorization Number: 24GA28095500
REVISIONS/ISSUES
MAY 3, 2017
17016
DBG
No. Revision/Issue Date
WARREN COUNTY VOCATIONALSCHOOL
SECURITY UPGRADE
TOWNSHIP OF WASHINGTONWARREN COUNTY, NEW JERSEY
PARTIAL FLOOR PLAN
PARTIAL FLOOR PLAN
E-2AS NOTED
- -RAS
DM J JUNCTION BOX ABOVE CEILINGFOR ALL CONNECTIONS
DOOR CONTROLLER
FLOOR
HINGE SIDE OF DOOR(TYPICAL)
CAT 6 TOPUNCHDOWN
DC
TYPICAL FOR DOORS5, 6, 7, 11, 13, 14, 21, 22
DM J JUNCTION BOX ABOVE CEILINGFOR ALL CONNECTIONS
DOOR CONTROLLER
FLOOR
HINGE SIDE OF DOOR(TYPICAL)
CAT 6 TOPUNCHDOWN
DC
PANESCR
TYPICAL FOR DOORS1, 2, 8, 9
NOTES:1. PROVIDE NEW ELECTRIC STRIKE, DOOR CONTACT,
DOOR MODULE AND CARD READER.
CEILING
DECK
FLOOR
PAN PAN
DC DC
DM JCAT 6 TOPUNCHDOWN
DOUBLE DOOR
JUNCTION BOX ABOVE CEILINGFOR ALL TERMINATIONS
NOTES:1. PROVIDE CONCEALED VERTICAL ROD EXIT DEVICE
WITH PANIC BAR AND ELECTRIC LATCH RETRACTIONFOR BOTH LEAFS OF DOOR.
2. PROVIDE ELECTRIC LATCH, CONTROLLER, POWERSUPPLY AND ALL REQUIRED SUPPORTING HARDWARE.
3. PROVIDE ELECTRIC POWER TRANSFER CONNECTORSFROM DOOR FRAME TO PANIC BAR.
4. PROVIDE NEW ELECTRIC LATCH RETRACTION, PANICBAR, DOOR CONTACTS, CARD READER ANDACCESSORIES.
7'-6"
DOOR CONTROLLER
ELRCR
ELRJ J
POWER CONNECTOR
TYPICAL FOR DOORS10, 12
CEILING
DECK
FLOOR
DC DC
DM JCAT 6 TOPUNCHDOWN
DOUBLE DOOR
JUNCTION BOX ABOVE CEILINGFOR ALL TERMINATIONS
7'-6"
DOOR CONTROLLER
CRPTE
MAG
ER
PAN
NOTES:1. SECURE LEAF WILL OPEN ONCE OPERATIONAL LEAF
OPENS.2. PROVIDE NEW MAG LOCK, DOOR CONTACTS, PUSH
TO EXIT, CARD READER, EMERGENCY RELEASE, DOORMODULE AND ACCESSORIES.
TYPICAL FOR DOOR27
CEILING
DECK
FLOOR
PAN PAN
DC DC
DM JCAT 6 TOPUNCHDOWN
DOUBLE DOOR
JUNCTION BOX ABOVE CEILINGFOR ALL TERMINATIONS
NOTES:1. PROVIDE CONCEALED VERTICAL ROD EXIT DEVICE
WITH PANIC BAR AND ELECTRIC LATCH RETRACTIONFOR BOTH LEAFS OF DOOR.
2. PROVIDE ELECTRIC LATCH, CONTROLLER, POWERSUPPLY AND ALL REQUIRED SUPPORTING HARDWARE.
3. PROVIDE ELECTRIC POWER TRANSFER CONNECTORSFROM DOOR FRAME TO PANIC BAR.
4. PROVIDE NEW ELECTRIC LATCH RETRACTION, PANICBAR, DOOR CONTACTS, CARD READER ANDACCESSORIES.
5. ELECTRIC DOOR RELEASE TO ACTIVATE DOOROPERATOR TO OPEN DOOR.
7'-6"
DOOR CONTROLLER
ELRCR
ELR
MOTOR
TYPICAL FOR DOORS3,4
PTEJ J
(2)
GENERAL DOOR DETAIL NOTES:(THESE GENERAL NOTES APPLY TO ALL DOOR DETAILS ON THIS DRAWING)
1. ALL SECURITY CONNECTIONS TO DOORS SHALL BE CONCEALED IN WALL.2. PROVIDE MINIMUM 3/4" FMC TO EACH CONNECTION LOCATION FOR DEVICES.3. COORDINATE WITH MILLWORK MANUFACTURER FOR OPENINGS REQUIRED FOR DOOR
CONTACTS, PANIC BAR, AND ACCESSORIES.4. PROVIDE ALL INTERCONNECTING WIRING BETWEEN CONTROLLERS, AND TO ALL DEVICES.5. CONTRACTOR SHALL FURNISH AND INSTALL ALL DEVICE WIRING AS REQUIRED BY
EQUIPMENT MANUFACTURER.6. WHEN PRE-APPROVED, ROUTE CONDUCTORS ON WALL SURFACES IN LEGRAND WIREMOLD
V500.7. ALL DOOR LOCKS TO RELEASE ON ACTIVATION OF FIRE ALARM. PROVIDE INTERFACE TO FIRE
ALARM SYSTEM.8. DOOR CONTROLLERS CANNOT BE INDIVIDUAL CONTROLLERS AT EACH DOOR.9. CONTRACTOR SHALL COORDINATE FIRE ALARM SYSTEM INTERFACE WITH SCHOOLS FIRE
ALARM VENDOR. CONTRACTOR SHALL RUN INTERCONNECTING WIRING TO LOCATION ASDIRECTED BY FIRE ALARM VENDOR. CONTRACTOR SHALL PROVIDE NECESSARY INTERFACEMODULES TO ENSURE COMPARABILITY WITH FIRE ALARM SYSTEM.
10. FIRE ALARM SYSTEM TERMINATIONS IN FIRE ALARM PANEL SHALL BE MADE BY SCHOOL FIREALARM VENDOR (N.I.C.).
CEILING
DECK
FLOOR
PAN PAN
DC DC
DM JCAT 6 TOPUNCHDOWN
DOUBLE DOOR
JUNCTION BOX ABOVE CEILINGFOR ALL TERMINATIONS
NOTES:1. SECURE LEAF WILL OPEN FROM THE INSIDE BY
DEPRESSING THE PANIC BAR BUT IS INACCESSIBLEFROM THE OUTSIDE.
2. PROVIDE NEW ELECTRIC STRIKE, DOOR CONTACTS,DOOR MODULE AND CARD READER.
7'-6"
DOOR CONTROLLER
ESCR
ACTIVE LEAFSECURE LEAF MULLION
TYPICAL FOR DOORS17, 19, 20, 24, 25, 26, 29
CEILING
DECK
FLOOR
PAN PAN
DC DC
DM JCAT 6 TOPUNCHDOWN
JUNCTION BOX ABOVE CEILINGFOR ALL TERMINATIONS
7'-6"
DOOR CONTROLLER
TYPICAL FOR DOORS15, 16, 18, 23, 28
FLOOR
HINGE SIDE OF DOOR(TYPICAL)
CRWIRELESS LOCKSET WITHINTEGRAL CARD READER
CEILING
DANIEL B. GROVER, PE
THE STATE OF NEW JERSEYLICENSED
PROFESSIONAL ENGINEER24GE44239
The Great Meadows Design Group, LLCA Professional Engineering Company
24 Far View RoadGreat Meadows, New Jersey 07838
(908) 637-8233 Fax (908) 637-8234
www.TheGMDGroup.com
New Jersey Authorization Number: 24GA28095500
REVISIONS/ISSUES
MAY 3, 2017
17016
DBG
No. Revision/Issue Date
WARREN COUNTY VOCATIONALSCHOOL
SECURITY UPGRADE
TOWNSHIP OF WASHINGTONWARREN COUNTY, NEW JERSEY
TOP/BOTTOM LATCH DOOR SET #5
SECURITY DETAILS
E-3AS NOTED
- -RAS
WIRELESS CLASSROOM AND RESTROOM LOCKSET
DOOR MONITORING SET #1 SINGLE DOOR CONTROL SET #3
HANDICAP DOOR SET #7UTILITY DOOR SET #6
CENTER MULLION DOOR CONTROL SET #4DOOR MONITORING SET #2