selecting current transformer

2
SELECTING CURRENT TRANSFORMER IEC Guidelines IEC 44-6 presents the requirements for CT transient performance in the form of a minimum saturation voltage as the following: Eal KsscKtd Rct Rb Isn where: Eal is the CT secondary excitation voltage, which corresponds to a magnetizing current that produces the maximum permissible error. Kssc is the ratio of fault current to nominal current. Ktd is the transient dimensioning factor. Rct is the CT secondary resistance. Rb is the CT burden. Isn is the nominal secondary current To avoid saturation, the CT shall develop adequate voltage such that V X > I f (R CT +R L +R B )- - - - - - - (1) where, I f = Fault current on CT secondary (Amps) R CT = CT Secondary resistance (Ohms) R L = CT Secondary total lead resistance (Ohms) and R B =CT secondary connected burden (Ohms

Upload: 322399mk7086

Post on 08-Nov-2015

4 views

Category:

Documents


1 download

DESCRIPTION

A worked example on how to select a CT for protection purposes

TRANSCRIPT

  • SELECTING CURRENT TRANSFORMER

    IEC Guidelines IEC 44-6 presents the requirements for CT transient

    performance in the form of a minimum saturation voltage as

    the following:

    Eal KsscKtd Rct Rb Isn where:

    Eal is the CT secondary excitation voltage, which

    corresponds to a magnetizing current that produces the

    maximum permissible error.

    Kssc is the ratio of fault current to nominal current.

    Ktd is the transient dimensioning factor.

    Rct is the CT secondary resistance.

    Rb is the CT burden.

    Isn is the nominal secondary current

    To avoid saturation, the CT shall develop adequate voltage such that

    VX

    > If (R

    CT+R

    L+R

    B)- - - - - - - (1)

    where,

    If = Fault current on CT secondary (Amps)

    RCT

    = CT Secondary resistance (Ohms)

    RL

    = CT Secondary total lead resistance (Ohms)

    and RB

    =CT secondary connected burden (Ohms

  • Example:

    What can be the maximum lead resistance for the application of a distance relay with the

    following data?

    Primary fault current =10kA (from system study)

    System X/R =15 (from system study)

    CT ratio = 1000/5A

    CT rating =C400 (CT existing)

    Design burden = 4 Ohms (as per standards for C400 CT)

    CT resistance = 0.25 Ohms (Data from manufacturer)

    Relay burden = Negligible (numerical relay)

    Calculations:

    Secondary fault current

    = 10000/ (1000/5)

    =50A

    Ni = 100/50 =2

    Nr = (RCT

    +4) / (RCT

    +RL+R

    B)

    = (0.25+4) / (0.25+ RL)

    = 4.25/ (0.25+ RL)