Fire Alarm System Salwico CS4000 User’s Guide

çConsilium

Page 2: Selwico CS4000 User manual

The contents of this document are subject to revision without notice due to continued progress in methodology, design and manufacturing. Consilium assumes no legal responsibility for any error or damage resulting from the usage of this document.

Edition 3, 08 1 E, May 2008. Document no. S-4-010.965 Part no: 465006

© 2005-2008, Consilium Fire & Gas AB

Consilium Marine AB

P.O. Box 8763 SE-402 76 GÖTEBORG SWEDEN Tel: +46-31-710 77 00, Fax: +46-31-710 78 00 E-mail: [email protected] Internet: www.consilium.se

Page 3: Selwico CS4000 User manual

User Guide Contents 1 Salwico CS4000

Contents About this manual .................................................................................................................... 3

Chapter 1: General description .............................................................................................. 4 Control panel MX4000........................................................................................................... 4

Description of keys and indicators ..................................................................................... 4 Repeater panel MN4000......................................................................................................... 8

Description of keys and indicators ..................................................................................... 8 Guide to the menu system .................................................................................................... 10

Choosing menu alternatives ............................................................................................. 10 Menu tree CS4000............................................................................................................ 11 Explanation of the different menu alternatives ................................................................ 13

Definition of terms ............................................................................................................... 19 CS4000 System data............................................................................................................. 20 CS4000 System : EN54 functions........................................................................................ 21

Optional functions with requirements .............................................................................. 21 Functions relating to other parts of the EN54 standard.................................................... 21 Ancillary functions not required by EN54 ....................................................................... 21

Chapter 2: Operations ........................................................................................................... 22 Access levels ........................................................................................................................ 22

Description of the access levels ....................................................................................... 23 Login .................................................................................................................................... 23 Pre-alarm .............................................................................................................................. 23 Fire alarm ............................................................................................................................. 24

When “Fire” is flashing.................................................................................................... 24 Information displayed ...................................................................................................... 24 Mute ................................................................................................................................. 24 Reset ................................................................................................................................. 25 Several alarms .................................................................................................................. 25 Type of fire alarms from conventional zones................................................................... 25

Fault indications ................................................................................................................... 26 When “Fault” is flashing .................................................................................................. 26 Information displayed ...................................................................................................... 26 Mute ................................................................................................................................. 26 Reset ................................................................................................................................. 27

Fault messages...................................................................................................................... 27 Disconnections ..................................................................................................................... 28

Disconnections available.................................................................................................. 28 Acknowledgement of a new disconnection...................................................................... 29 Disconnecting zones......................................................................................................... 29 Disconnecting addressable detectors................................................................................ 30 Disconnecting alarm devices (bells etc)........................................................................... 30 Alarm delay ...................................................................................................................... 31 Disconnecting external outputs (for example fans, fire doors etc) .................................. 31 Disconnection of alarm transfer output ............................................................................ 31

Reconnection of disconnected items .................................................................................... 31 Service menu (access level 4) .............................................................................................. 32

Page 4: Selwico CS4000 User manual

User Guide Contents 2 Salwico CS4000

Chapter 3: Installation........................................................................................................... 33 Electrical connection ............................................................................................................ 33

Description of CS4000 PCB’s.......................................................................................... 33 Connection ....................................................................................................................... 34

Testing.................................................................................................................................. 35 Test a fire-detecting zone ................................................................................................. 35 Reset test mode................................................................................................................. 35 Test the control unit display ............................................................................................. 35

Appendix A: Fault codes & Fuses......................................................................................... 36 Fault list................................................................................................................................ 36 Fuses..................................................................................................................................... 39

Fuse list ............................................................................................................................ 39 Fuse locations on base board, BB. ................................................................................... 39 Fuse locations on rectifier board, RB............................................................................... 39

Appendix B: Quick guide* .................................................................................................... 40 Fire alarm ......................................................................................................................... 40 Fault alarm........................................................................................................................ 40 Disconnections ................................................................................................................. 40 General operation ............................................................................................................. 40

Appendix C: Display analogue values of a loop unit........................................................... 41

Page 5: Selwico CS4000 User manual

User Guide About this manual 3 Salwico CS4000

About this manual This manual gives general information about the CS4000 fire alarm system and its control panel in chapter 1 General description. In chapter 2 Operation it is described how to operate the CS4000 fire alarm system. It also gives a brief instruction how to connect and test the CS4000 fire alarm system in chapter 3 Installation. For more detailed information, see the separate “CS4000 Installation manual”. In appendix A you will find detailed information about the fault codes that can appear and where the fuses are located. If nothing else, please read “Guide to the menu system” in chapter 1 and Appendix B “Quick guide” to get a basic understanding how to operate the system. In Appendix C you will find information about the analogue value that can be read out from each loop unit. This manual is valid for Base Board program versions from 1.0.32.

Page 6: Selwico CS4000 User manual

User Guide Chapter 1: General description 4 Salwico CS4000

Chapter 1: General description The CS4000 is a state of the art analogue addressable fire detection system designed to meet all major marine and industrial requirements. Special care has been taken to ergonomics and user friendliness with its logical self-instructing operator panel guiding the user to the various functions available. The CS4000 can be delivered with either analogue addressable or conventional detectors or a combination of both in the same system.

Control panel MX4000 The control panel is used to monitor and control all functions of the CS4000 fire alarm system. The CS4000 is a menu-operated system and instructions are given in the text display making it very easy to use.

0System Fault

Home Disc.

Test

Alarm Device

Power

Alarm Transfer

Alarm DelayZone/Unit

2

Warning

OK

Pre-Alarm

Menu

Reset

FAULT DISC.

NextMute

OK

ABC3

DEF' '1

5JKL

6MNOGHI

4

8TUV

9WXYZPQRS

7

F1

F2

F3

FIRE

Description of keys and indicators

1 2 3 4 5 6 7 8 9

10 11 12

13

14 15 16 17

18 19 20 21 22 23 24 25

Page 7: Selwico CS4000 User manual

User Guide Chapter 1: General description 5 Salwico CS4000

1. Fire alarm indicator

The fire alarm indication is flashing with red light to indicate that there is an un-muted fire alarm in the system. It turns into steady light when all fire alarms are muted.

2. Disconnection indicator This is a general indicator showing that there is at least one disconnected function in the system, for example a zone, detector, external control or alarm device.

3. Fault indicator

The fault indication is flashing with yellow light to indicate that there is an un-muted fault in the system. It turns into steady light when all fault alarms are muted.

4. Power indicator

Indicates with green steady light that the power supply to the control panel is OK.

5. Test indicator

Indicates with yellow steady light that there is at least one zone in test mode.

6. Alarm transfer indicator (only industrial application)

Indicates with yellow steady light that the output controlling the transmission of fire alarms to the fire brigade has been activated. The indication starts flashing if there is a fault detected on the alarm transfer output.

7. Alarm device indicator

Indicates with yellow steady light that an alarm device output (bells etc) is disconnected. Flashing light indicates that there is a fault on an alarm device output.

8. Alarm delay indicator Marine application: Indicates with yellow steady light that the alarm delay function is disconnected. Industrial application: Indicates with yellow steady light that the alarm transfer output is delayed.

9. Zone/Unit indicator Indicates with yellow steady light that a fire detector or zone is disconnected. Flashing yellow indicates that at least one fire detector or zone is in fault condition. Fault indication has priority over disconnection indication.

Page 8: Selwico CS4000 User manual

User Guide Chapter 1: General description 6 Salwico CS4000

10. System fault indicator

Flashes with yellow light to indicate an internal fault in the control panel or when there is a fault on the system communication of type “no poll”. See appendix A “Fault codes” for more information.

11. Warning indicator Warnings are indicated with yellow steady light.

12. Pre-alarm indicator The pre-alarm indication flashes with yellow light to indicate that there is an un-muted pre-alarm in the system. It turns into steady light when all pre-alarms are muted.

13. Custom keys and indicators

The three custom keys with yellow indicators are programmable to activate customer-specific functions or show customer specific menus. The functions of these buttons and indicators are programmed via the definition program.

14. Fields for custom text The function of each custom key can be described in these text fields using user-defined inserts in the panel slots.

15. Mute button This button is used to mute (acknowledge) and silence alarms.

16. More alarms Flashes with red light if there is more than one fire alarm in the system.

17. Next button Press Next button to scroll through the different alarms. The list always returns to the first fire alarm after 30 seconds if no buttons are pressed.

18. Menu shortcut button

This button gives direct access to the main menu, where all the functions of the CS4000 system can be accessed.

19. Home shortcut button This button gives direct access to the initial view.

20. Disconnections shortcut button This button gives direct access to the disconnections menu.

21. Alphanumerical display The blue alphanumerical display has a capacity of 14x40 characters.

Page 9: Selwico CS4000 User manual

User Guide Chapter 1: General description 7 Salwico CS4000

22. Numerical keypad

The numerical keypad is used to enter information into the system. The button erases one character at the time.

23 OK buttons The OK buttons are used to select a menu alternative or to accept a function. The OK buttons is also used to show details for a selected list entry. Both buttons have the same function.

24. Arrow keys The arrow keys are used to navigate in the menus and select different menu alternatives.

OK

Shows the previous item in the list. If the first item is displayed it will go to the last item.

Go to previous menu Select the chosen menu alternative. (or press OK)

Shows next item in the list. If the last item is displayed it will go to the first item.

25. Reset button This button is used to reset different alarms in the system.

Page 10: Selwico CS4000 User manual

User Guide Chapter 1: General description 8 Salwico CS4000

Repeater panel MN4000 The repeater panel is used to monitor functions in the CS4000 fire alarm system. It is possible to view and list fire alarm, faults and disconnections.

Description of keys and indicators

1. Fire alarm indicator

The fire alarm indication is flashing with red light to indicate that there is an un-muted fire alarm in the system. It turns into steady light when all fire alarms are muted from the main control panel.

2. Power indicator Indicates with green steady light that the power supply to the repeater panel is OK.

Power

Mute

FIRE

FaultTest Fire Disc.

Fault

Disconnection

Scroll

1

3. Fault indicator

The fault indication is flashing with yellow light to indicate that there is an un-muted fault in the system. It turns into steady light when all fault alarms are muted from the main control panel.

2 3 4

5 6 7 8

9 10 11

Page 11: Selwico CS4000 User manual

User Guide Chapter 1: General description 9 Salwico CS4000

4. Disconnection indicator

This is a general indicator showing that there is at least one disconnected function in the system, for example a zone, detector, external control or alarm device.

5. Test button Test of all indications and each segment in the alphanumerical display on the repeater panel.

6. Fire button Gives direct access to the fire alarm list.

7. Fault button Gives direct access to the fault list.

8. Disc. button Gives direct access to the disconnection list.

9. Alphanumerical display The blue alphanumerical display has a capacity of 14x40 characters.

10. Scroll buttons Used to scroll up and down in the different lists.

11. Mute buttons Mutes the local buzzer.

Page 12: Selwico CS4000 User manual

User Guide Chapter 1: General description 10 Salwico CS4000

Guide to the menu system The CS4000 is a menu-operated system. All functions in the system can be reached from the different menus.

Choosing menu alternatives Press Menu to enter the menu system. Navigate in the menu alternatives with the up and down arrows. Choose a menu alternative with the right arrow and go to previous menu with the left arrow. It is also possible to choose a menu alternative by entering the menu number (0 = menu 10). In the lower part of the alphanumerical display the different options available for each individual menu are shown. The numerical keypad is used to entering information, for example zone and detector number. The button erases the last alphanumeric entry.

OK

Show the previous item in the list. If the first item is displayed it will go to the last item.

Go to previous menu. Selects the chosen menu alternative.

Show next item in the list. If the last item is displayed it will go to the first item.

Page 13: Selwico CS4000 User manual

User Guide Chapter 1: General description 11 Salwico CS4000

Menu tree CS4000

Home 1 Fault Alarms

1 Fault List* 1 Mute 2 Reset

2 Warning List * 3 Reset All Faults

2 Fire Alarms 1 Fire List*

1 Mute 2 Reset

2 Pre-Alarm List* 3 Resound (restart bells) 4 Reset All Fire Alarms

3 Disconnections 1 New disconnection (access level 2B)

1 Zones 2 Detectors & Manual Call Points 3 External Controls

1 External Controls 1 General 2 Doors 3 Fire 4Fault 5 Ventilation 6 Indication

2 Alarm Transfer 4 Alarm Device (Bells etc.) 5 Alarm Delay

1 Disconnection (5 minutes) 2 Timer disconnection 3 Clock disconnection 4 Periodic disconnection

6 Test Mode 2 Disconnection list*

1 Reconnect 3 Periodic Disconnection list* 4 Old Disconnections 5 Remove all disconnections

4 Login 5 Settings

1 Set Dimmer 2 Set Time 3 Set Date 4 Test display 5 Alarm delay times (access level 3)

1 Alarm delay time 1 (mute) 2 Alarm delay time 2 (reset)

6 Keyboard beep 7 Cause Effect in test mode Continues on next page→

Page 14: Selwico CS4000 User manual

User Guide Chapter 1: General description 12 Salwico CS4000

6 Service menu (access level 4)

1 System Details 2 System Boards*

0 Disconnect system board 2 System board inputs 3 System board outputs

3 Display Units* 0 Disconnect panel board 2 Panel board inputs 3 Panel board outputs

4 Zones* 2 Loop units 0 Disconnect loop unit 2 Simulate fire alarm 3 Remove loop unit 4 Change supplementary text

5 Loops* 0 Disconnect logical loop 2 Loop units 0 Disconnect loop unit 2 Simulate fire alarm 3 Remove loop unit 3 Add logical loops 4 Scan for loops

6 Reload Configuration 1 Load entire configuration 2 Load supplementary texts only

7 Load config from Memory Stick 8 Upload config to Memory Stick 9 Save changes to configuration 10 Upload syslog to Memory Stick

7 History 1 Fire History List* 2 Fault History List* 3 Disconnection History List* 4 Common History List*

8 Maintenance 1 Lightly Contaminated Detectors 2 Heavily Contaminated Detectors

* All lists can be printed by pressing 1 the on the numerical keypad. It is also possible to monitor details about the list objects by pressing the OK button.

Page 15: Selwico CS4000 User manual

User Guide Chapter 1: General description 13 Salwico CS4000

Explanation of the different menu alternatives Home

Top-level start display showing “CS4000 FIRE ALARM SYSTEM” and the name of the installation (if defined).

1 Fault Alarms The menu from which fault- and warning messages are listed and handled.

1.1 Fault List Shows all present fault messages.

1.1.1 Mute Mute the fault alarm by pressing the Mute button on the control panel MN4000.

1.1.2 Reset Reset the fault alarm by pressing the Reset button on the control panel MN4000.

1.2 Warning List Shows all present warning messages, for instance a dirty detector or an open door on a central unit.

1.3 Reset All Faults Reset all present faults in the fault list (1.1).

2 Fire Alarms The menu from which fire- and pre-alarms are listed and handled. Also possibility to re-activate alarm devices that have been muted (re-sound).

2.1 Fire List Shows all present fire alarms.

2.1.1 Mute

Mute the fire alarm by pressing the Mute button on the control panel MN4000.

2.1.2 Reset Reset the fire alarm by pressing the Reset button on the control panel MN4000.

2.2 Pre-Alarm List

Shows all present pre-alarms.

Page 16: Selwico CS4000 User manual

User Guide Chapter 1: General description 14 Salwico CS4000

2.3 Resound (restart bells) If the alarm devices have been silenced by pressing Mute, this function will restart them if the fire alarm has not been reset.

2.4 Reset All Fire Alarms Resets all fire alarms in the fire list (2.1)

3 Disconnections The menu, from which disconnections of parts of the fire alarm system are added, removed or listed.

3.1 New disconnection (access level 2B) Adds new disconnections.

3.1.1 Zones Possibility to disconnect entire zones for a specified time period or permanent.

3.1.2 Detectors & Manual Call Points Possibility to disconnect individual detectors or manual call points for a specified time period or permanent.

3.1.3 External Controls Possibility to de-activate External Controls or Alarm Transfer.

3.1.3.1 External Controls Disconnects outputs (all or individual categories) to external controls. This means that an alarm condition will not cause activation of the selected category.

3.1.3.1.1 General Category including all external controls (doors, fire, fault, ventilation and indication)

3.1.3.1.2 Doors Category for external controls, Doors

3.1.3.1.3 Fire Category for external controls, Fire

3.1.3.1.4 Fault Category for external controls, Fault

3.1.3.1.5 Ventilation Category for external controls, Ventilation

3.1.3.1.6 Indication Category for external controls, Indication

Page 17: Selwico CS4000 User manual

User Guide Chapter 1: General description 15 Salwico CS4000

3.1.3.2 Alarm Transfer Disconnects the supervised output for alarm transfer, normally used in on-shore installations to alert the fire brigade in case of a fire alarm.

3.1.4 External Device (Bells etc.) Disconnects outputs for alarm devices, such as audible- (bells etc) and optical alarm devices.

3.1.5 Alarm Delay Disconnects the alarm delay function. Alarm delay is normally activated. Alarm delay is a programmable delay time between a fire is detected until the alarm device outputs are activated. See chapter 2: Disconnections under “Alarm delay” for more information.

3.1.6 Test Mode Possibility to set a zone into test mode. See chapter 3 Installation under “testing” for more details.

3.2 Disconnection list Shows all active disconnections in the system. A periodic disconnection (3.3) that is not active will not be shown in this list. Reconnection of a disconnected unit is made from this list. See chapter 2 Operations under “reconnection of disconnected items” for more details.

3.2.1 Reconnect Reconnect the disconnection by pressing the Reset button on the control panel MN4000.

3.3 Periodic Disconnection list Shows all periodic disconnections in the system. Removal of periodic disconnections is made from this list.

3.4 Old Disconnections A list showing the 150 latest, previously removed, disconnections. This list also gives the possibility to re-activate an old disconnection again. This function is very useful if the same disconnection is frequently needed during irregular time periods. Just mark the appropriate old disconnection in the list and press 0 to re-activate it.

3.5 Remove all disconnections Removes all active disconnections shown in the disconnection list (3.2). Does not remove periodic disconnections (3.3) permanently, just the active period of the periodic disconnection.

4 Login Login is made from this menu. Enter the personal access code. For further details see chapter 2 Operations under “login”.

Page 18: Selwico CS4000 User manual

User Guide Chapter 1: General description 16 Salwico CS4000

5 Settings Use this menu to adjust parameters in the system such as dimmer level on control panel, date and time and alarm delay time. It is also possible to make a lamp test for the control panel under “test display” (5.4).

5.1 Set Dimmer Use this menu to adjust the contrast level on the control panel display between 1-9.

5.2 Set Time Use this menu to set the system time. It is possible synchronize the CS4000 clock with the ship central time.

5.3 Set Date Use this menu to set the system date.

5.4 Test display From this menu it is possible to activate a lamp test to verify the correct function of the alphanumerical display and for all indications on the control panel.

5.5 Alarm delay time (access level 3) Use this menu to adjust the programmable alarm delay time between 1 to 10 minutes.

5.6 Keyboard beep Use this menu to turn the keyboard beep ON or OFF.

5.7 Cause Effect in test mode Use this menu to turn the Cause/Effect program ON or OFF during test mode. If set to ON, the outputs will be activated as normal during test mode.

6 Service menu (access level 4) Use this menu to list and view information about the system and its components. It is also possible to make disconnections of the listed units. The service menu is described in more detail in the separate manual CS4000 service manual.

6.1 System Details This menu gives information about the installed system such as name and reference number (if defined). It also lists when the system was last configured and by which program.

6.2 System Boards Use this menu to list and view information about the installed system PCB´s. It is possible to view all details about the boards such as installed detector loops, program versions installed, status of inputs and outputs and to print the listed information.

Page 19: Selwico CS4000 User manual

User Guide Chapter 1: General description 17 Salwico CS4000

6.3 Display Units Use this menu to list information about the installed control and repeater panels and how they are configured.

6.4 Zones This menu shows a list of all zones configured in the system. It is possible to list all loop units in a zone if it consists of addressable loop units. It is also possible to make disconnections of zones or loop units and to set a single fire detector in alarm condition.

6.5 Loops This menu shows a list of all the physical loops installed in the system. A loop can consist of conventional or addressable fire alarm detectors or other loop units. It is also possible to make disconnections of entire loops.

6.6 Reload Configuration Use this command when a new updated configuration file or supplementary text file has been downloaded to the CS4000 system.

6.6.1 Load entire configuration If a new configuration file is downloaded, the system will re-start and then use the new configuration file.

6.6.2 Load supplementary texts only The system will update the supplementary text files (no re-start needed).

6.7 Load config from Memory Stick Download a new configuration file from the Salwico Memory Stick .

6.8 Upload config to Memory Stick Copy the existing CS4000 configuration file to the Salwico Memory Stick .

6.9 Save changes to configuration Use this command to save all changes made to the system configuration from the control panel. Note: The changes are not permanently saved in the configuration file until this command is performed.

6.10 Upload syslog to Memory Stick Upload a system log with service information to the Salwico Memory Stick . This service log can then be sent to Consilium for further technical assistance.

7 History Use this menu to view previous events in the fire alarm system.

Page 20: Selwico CS4000 User manual

User Guide Chapter 1: General description 18 Salwico CS4000

7.1 Fire History List Shows a list of the 200 latest fire alarms in chronological order.

7.2 Fault History List Shows a list of the 200 latest fault alarms in chronological order.

7.3 Disconnection History List Shows a list of the 200 latest disconnections in chronological order.

7.4 Common History List Shows a common list of the 1000 latest pre alarms, fire alarms, fault alarms, disconnections, warnings and I/O:s in chronological order.

8 Maintenance Use this menu for monitoring detectors in need of maintenance.

8.1 Lightly Contaminated Detectors Shows a list of lightly contaminated detectors in the entire system.

8.2 Heavily Contaminated Detectors Shows a list of heavily contaminated detectors in the entire system.

Page 21: Selwico CS4000 User manual

User Guide Chapter 1: General description 19 Salwico CS4000

Definition of terms

External controls An output to activate external actions, for example release fire doors or stop ventilation.

Alarm device Alarm devices are outputs activated in case of fire, for example audible or optical alarms such as bells, sirens and flashlights.

Disconnection A disconnection of a system component such as a zone or a detector. Prevents fire alarms, fault alarms or control actions from that unit.

Panel board, PB This is the control panel with alphanumerical display. Alarm delay A delay before activating alarm device outputs when a fire is

detected. Normally set to 2 minutes (the delay is programmable).

Alarm transfer output Supervised output indicating that there is at least one fire alarm in system. Normally used to alert the fire brigade in onshore installations.

Zone board, ZB Zone board for connection of max 16 conventional detector loops This board can also be used as 16 input/outputs.

Loop board, LB3 Loop board for connection of 3 addressable detector loops. Base board, BB Base board is the centre of the central with basic in and

outputs. It controls the system communication etc. Relay board, RB Optional board with 8 programmable relay contacts. Power board, PB Power supply board. Warning A disturbance in the system not as dangerous as a fault

condition. This can for instance be a dirty detector or an open door to a central.

Fault condition A signal that is given by the control panel in the event of a fault in the system or on one of its components.

Loop A common name for the cable, detectors and manual call points that are connected with the fire alarm central.

Zone A group of addressable loop units or an entire conventional zone.

Loop unit Units located on the detector loop such as detectors, manual call points or short circuit isolators.

MCP Manual call point. An external fire alarm button. Creates a fire alarm when activated.

Pre-alarm A condition in which the detector senses a certain amount of danger, but the level of the detected state is not enough to cause a fire alarm.

Cause/Effect The Cause/Effect program defines how the in- and outputs of the system should react.

Page 22: Selwico CS4000 User manual

User Guide Chapter 1: General description 20 Salwico CS4000

CS4000 System data

Supply voltage (other supply voltage is optional) 230 VAC

Internal system voltage 27 VDC

Number of detectors on one central Max 512 (max according to EN54 regulations)

Number of detectors in one addressable detector loop Max 254

No. of detectors on a conventional loop. Max 50

No. of addressable detector loops on loop board, LB3. 3

No. of conventional detector sections per zone board, ZB 16

No. of Loop/ Zone Boards in one central Max 3

No. of output boards in one central Max 4

No. of control panels MX4000 / repeaters MN4000 in one central Max 4

No. of mini-repeaters MN3000 in one central Max 15 Incl. MX4000 / MN4000

No. of zones in a system 1-65535

Cable length of a detection circuit. See further “cable requirements” in CS4000 installation manual.

Max 2 000m unshielded cable

Min. loop cable requirements 2 x 0,3 mm2 unshielded

Communication parameters for the external system channel RS485, 19200 Baud, Odd parity, 8 data bits

Communication parameters for the detector loops FSK keying

Page 23: Selwico CS4000 User manual

User Guide Chapter 1: General description 21 Salwico CS4000

CS4000 System : EN54 functions

Optional functions with requirements The following optional functions with requirements are available in the CS4000 system:

Paragraph Function description 7.8 Output to alarm devices (Item C) 7.9 Output to fire alarm routing equipment (Item E) 7.10 Output to fire protection equipment (Item G) 7.11 Delays to outputs (Item C+E) 7.12 Co-incidence detection (Item C+E+G) 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition

The paragraphs above refer to EN54:2:1997/AC:1999.

Functions relating to other parts of the EN54 standard The system includes an integrated power supply that fulfils all mandatory functions of EN54:4.

Ancillary functions not required by EN54

• Earth failure CS4000 has capability to indicate earth failure individually per fire detection loop and power supply.

• Control panel, CU It is possible to mount the control unit separately from the central panel. See block diagram in “CS4000 Installation manual”, chapter 1.

Page 24: Selwico CS4000 User manual

User Guide Chapter 2: Operations 22 Salwico CS4000

Chapter 2: Operations

Access levels To prevent un-authorized operation of the system there are access levels to protect the different functions of the CS4000. The user has to login to the system or unlock the lock (mainly industrial applications) before any vital operations can be performed. Without access to an authorization code or a key the user can only view fire and fault alarms and mute the local buzzer. In industrial applications, access level 1 is the basic level. Open the lock to go to access level 2. The system automatically returns to access level 1when the lock is locked or after 30 minutes of inactivity. In marine applications, access level 2 is the basic level. These applications do not have a lock. The system automatically returns to access level 2 after 30 minutes of inactivity. There are five different access levels:

Access level Procedure to enter level Description of user

1 None, door is closed or lock is locked.

General public, safety personnel (not available for marine applications)

2 Open door or unlock the lock. Personnel trained and authorized to operate the system in case of fire or maintenance. Disconnections not possible.

2B Open door and enter access code for level 2B via menu/login.

Personnel trained and authorized to operate the system in case of fire or maintenance.

3 Open door and enter access code for level 3 via menu/login.

Personnel trained and authorized to make changes to the configured system.

4 Open door and enter access code for level 4 via menu/login.

Only authorized service personnel trained by Consilium.

Page 25: Selwico CS4000 User manual

User Guide Chapter 2: Operations 23 Salwico CS4000

Description of the access levels Access level 1 Only viewing of fire or fault alarms. Fire alarms have priority over fault alarms. Possibility to mute local buzzer. Access level 2 As level 1 + access to the menu system. List status. Reset and muting of alarms. Access level 2B As level 2 + make disconnections. Access level 3 As level 2B + possibility to make changes to the configured system. Access level 4 All functions available, including advanced service options.

Login Press Menu from level 1 or go to Menu/ 4 login/ 1 login and enter the four-digit access code for the desired access level. The system will acknowledge if the correct code is entered. Entering the system with the key gives direct access to level 2. The default access codes are: Level 2B 2222 Level 3 3333

Pre-alarm The CS4000 is equipped with the function Pre-alarm that will give an early alarm to a slow raise of the fire condition, for example a smouldering fire. The Pre-alarm level is lower than the ordinary fire alarm level. A pre-alarm will activate the local buzzer and the indication “Pre-alarm” will be lit on the control unit. The pre-alarm will also be added to the pre-alarm list found under: Menu/ 2 Fire Alarms/ 2 Pre-Alarm List. It is only possible to mute a pre-alarm, not reset. It will remain in the pre-alarm list until the fire condition is under or over (fire alarm) the level for pre-alarm. The pre-alarm will normally not activate any alarm devices or external outputs.

Page 26: Selwico CS4000 User manual

User Guide Chapter 2: Operations 24 Salwico CS4000

Fire alarm

When “Fire” is flashing

A fire alarm is detected in the system.

Information displayed The following information is displayed in the Control Panel:

0System Fault

Home Disc.

Test

Alarm Device

Power

Alarm Transfer

Alarm DelayZone/Unit

2

Warning

OK

Pre-Alarm

Menu

Reset

FIREFAULT DISC.

NextMute

OK

ABC3

DEF' '1

5JKL

6MNOGHI

4

8TUV

9WXYZPQRS

7

F1

F2

F3

FIRE ALARM 1(2) 15.53 1 FIRE ZONE 2 MCP 23 . Galley deck 4 . 2 FIRE ZONE 1 SMOKE 206 Café Panorama deck 14 _______________________________________________ RESET=Reset item, MUTE=Mute, OK=Details 0=Disconnect 1=Print item 2=Print all

• Number of alarm(s) • Zone in alarm • Type of unit in alarm • Address number of unit in alarm (only for addressable loop) • Supplementary text 1 (if defined) Press OK to view more details: • Time of alarm • Date of alarm • Supplementary text 2 about location of detector (if defined)

Mute The MUTE button has different function depending on the current access level. Access level 1 Pressing MUTE causes the internal buzzer to silence. Access level 2 or higher

Page 27: Selwico CS4000 User manual

User Guide Chapter 2: Operations 25 Salwico CS4000

Pressing MUTE causes the internal buzzer and all external alarms to silence and mutes the fire alarm indication. When the alarm is muted the fire indication stops flashing and turn over to steady light. Press OK for more details.

Reset Press RESET to reset the fire alarm. Alarms cannot be reset if the fire condition remains.

Several alarms If there is more than one fire alarm in the system, the red LED indicators above the NEXT button are activated. The first and last fire alarms are always displayed in the control panel. Scroll through the different fire alarms with the NEXT button or UP/DOWN arrows. Reset and mute as above.

Type of fire alarms from conventional zones The CS4000 will display whether a detector or a manual call point generates the fire alarm. If two or more detectors are activated in the same zone, the fire alarm will be presented as: manual call point/multiple detectors.

Page 28: Selwico CS4000 User manual

User Guide Chapter 2: Operations 26 Salwico CS4000

Fault indications

When “Fault” is flashing

0System Fault

Home Disc.

Test

Alarm Device

Power

Alarm Transfer

Alarm DelayZone/Unit

2

Warning

OK

Pre-Alarm

Menu

Reset

FIREFAULT DISC.

NextMute

OK

ABC3

DEF' '1

5JKL

6MNOGHI

4

8TUV

9WXYZPQRS

7

F1

F2

F3

FAULT ALARM 1(1) 18.53 _______________________________________________ 1 LOOP ANALOGUE 3 CABLE BREAK POSITIVE XXXXXXXXXXXXXXXf. Loop 3 on LB3 2XXXXXXXXXXXXM . _______________________________________________ RESET=Reset current entry, MUTE=Mute all OK D il 1 P i i 2 P i ll

A fault is detected in the system.

Information displayed The following information is displayed in the control unit:

• Number of fault(s) (i.e. how many faults are detected) • Type of fault • Identification of the faulty unit • Supplementary text for the faulty unit (if defined)

Press OK for more details:

• Time when fault occurred • Date when fault occurred • Supplementary text about location of fault (if defined)

Mute Press MUTE to silence internal buzzer and mute all faults in list. Press OK for more details.

Page 29: Selwico CS4000 User manual

User Guide Chapter 2: Operations 27 Salwico CS4000

Reset All faults in the system are shown in the fault list. Reset a fault:

1. Go to the fault list under: Menu/ 1 Fault Alarms/ 1 Fault List 2. Choose the fault in the fault list and then press RESET to reset

the fault alarm. If the cause of the fault alarm remains the alarm cannot be reset. Check the problem and deal with it. Then try to reset the fault again.

Reset all faults: 1. Go to: Menu/ 1 Fault Alarms/ 3 Reset All Faults 2. Press OK

Fault messages

If a fault occurs in the system it will be displayed at the control panel with information about which part of the system that is faulty and also a short description of the fault.

See “Appendix A: Fault codes & Fuses” for a list of all fault messages.

Page 30: Selwico CS4000 User manual

User Guide Chapter 2: Operations 28 Salwico CS4000

Disconnections It is possible to disconnect different parts of the system, such as: zones, detectors, manual call points, section units, alarm devices, external control devices and loops. All disconnections are placed in a disconnection list. The yellow indication DISC. is lit on the control unit when the first disconnection is defined in the system and remains lit until all disconnections are reconnected. To be able to make a disconnection you must enter access level 2B or higher. WARNING! When a fire detector or zone is disconnected the fire alarm system will not be able to detect any occurring fire in that area. It is therefore important that disconnections are minimized in terms of quantity of disconnected units and duration of time. For example if dual detectors heat/smoke are installed it is possible to disconnect only the smoke detection part of the detector and keep the heat detecting part active or vice versa.

Disconnections available There are four different disconnections available: Permanent disconnection

The disconnection is permanent until it is manually reconnected. Note: It is possible to limit the disconnection time by defining a maximal disconnection time in the configuration program. Timer disconnection

Disconnection is instant and lasts for the time period entered (hh:mm). Maximum disconnection time is 23h 59m. Clock disconnection

Enter reconnection time. Disconnection is instant and the reconnection will take place next time the entered time occurs. Maximum disconnection time is 23h 59m. Periodic disconnection

A disconnection for a certain time period during certain days of the week. Example: Disconnect zone 1 each Tuesday and Friday between 7.00 – 17.00.

Page 31: Selwico CS4000 User manual

User Guide Chapter 2: Operations 29 Salwico CS4000

Acknowledgement of a new disconnection After entering a new disconnection correctly, an acknowledgement is presented on the control panel. The new disconnection is also added in the disconnection list under: Menu/ 3 Disconnections/ 2 Disconnection list

Disconnecting zones (access level 2B or higher)

Disconnections are made under: Menu/ 3 Disconnections/ 1 New disconnection To disconnect a conventional zone, follow the basic system below:

Step 1 Choose Zone

Step 2 Choose disconnection type

Step 3 Enter time

Zone number Permanent Timer→ X Clock→ X

To disconnect an addressable zone, follow the basic system below:

Step 1 Choose Zone

Step 2 Choose detector type

Step 3 Choose disconnection type

Step 4 Enter time

Zone number Smoke Permanent All Timer→ X Heat Clock→ X Flame Periodic→ X Manual Call Points

Example: You want to disconnect zone 3 each Monday and Tuesday between 06.00-18.30.

1. Enter the disconnections menu either by pressing the shortcut button Disc. or press Menu and choose 3 Disconnections by pressing 3 and then press OK. (Be sure to have access level 2B or higher)

2. Choose 1 New disconnection 3. Choose 1 Disconnect Zone 4. Enter the zone number 3, then press OK 5. For addressable loops: Choose 2 All Detectors (manual call

points will remain active), then press OK 6. Choose 4 Periodic disconnection

Page 32: Selwico CS4000 User manual

User Guide Chapter 2: Operations 30 Salwico CS4000

7. Enter disconnection time 06001830, then press OK. 8. Disable all weekdays except Monday and Tuesday by pressing

the number for each weekday (i.e. 34567), then press OK Note: Periodic disconnection is only for addressable zones.

Disconnecting addressable detectors (access level 2B or higher) Disconnecting individual detectors is only possible on addressable loops. Disconnections of detectors are made under*: Menu/ 3 Disconnections/ 1 New disconnection/ 2 Detectors & Manual Call Points To disconnect an addressable detector, follow the basic system below:

Step 1 Choose zone

Step 2 Choose detector type

Step 3 Choose detector address (or interval)

Step 4 Choose disconnection type

Step 5 Enter time

Zone number

Smoke Address number(s) Permanent

All Timer→ X Heat Clock→ X Flame Periodic→ X Manual Call

Point

*It is also possible to disconnect detectors from the Fire List.

Disconnecting alarm devices (bells etc) (Access level 2B or higher) Disconnections of alarm devices is done under: Menu/ 3 Disconnections/ 1 New disconn./ 4 External Alarm/ 1 Alarm Device (Bells etc.)

Page 33: Selwico CS4000 User manual

User Guide Chapter 2: Operations 31 Salwico CS4000

Alarm delay (Access level 2B or higher) Alarm delay function is normally activated, and will delay the activation of alarm devices in case of an alarm. The delay time is programmable and normally set to two minutes. The alarm delay function may be disconnected under: Menu/ 3 Disconnections/ 1 New disconn./ 5 Alarm Delay Setting delay time is done under: Menu/ 5 Settings/ 5 Alarm Delay Times/ 1 Alarm Delay Time 1 (mute)

Disconnecting external outputs (for example fans, fire doors etc)

(Access level 2B or higher) 1. Select: Menu/ 3 Disconnections/ 1 New disconn./ 3 External

Controls/ 1 External Controls 2. Select an output category to be disconnected

(general = all categories). 3. Press OK.

Disconnection of alarm transfer output (Access level 2B or higher) Disconnection of the alarm transfer (fire brigade) output is done under: Menu/ 3 Disconnections/ 1 New disconn./ 3 External Controls/ 2 Alarm Transfer

Reconnection of disconnected items All disconnections in the system are shown in the disconnection list. Any reconnection is made from this list. 1. Go to Menu/ 3 Disconnections/ 2 Disconnection list. 2. Choose the disconnection you want to reconnect. 3. Press Reset button

Page 34: Selwico CS4000 User manual

User Guide Chapter 2: Operations 32 Salwico CS4000

Service menu (access level 4)

The Service menu is used for configuration of the system in the commissioning phase, as well as for troubleshooting and small updates when the system is in operation. The menu has functions for downloading and uploading information from/to the Salwico Memory Stick. The service menu screen displays a list of the 10 service menu alternatives, described on the following pages. The alternatives are reached by pressing the corresponding number on the numerical keypad, or by selecting the desired alternative with the arrow buttons and pressing the OK button. Service menu screen

Please see separate manual “CS4000 Service manual” for detailed information about the service menu.

SERVICE 12 36 1 System Details > 2 System Boards > 3 Display Units > 4 Zones > 5 Loops > 6 Reload Configuration > 7 Load config from Memory Stick > 8 Upload config from Memory Stick > 9 Save changes to configuration > 10 Upload syslog to Memory Stick > _______________________________________________ Select a menu with 0-9 (or arrows + OK)

Page 35: Selwico CS4000 User manual

User Guide Chapter 3: Installation 33 Salwico CS4000

Chapter 3: Installation

Electrical connection This chapter will give some brief information about installation. For more information, please refer to “CS4000 installation manual”.

Description of CS4000 PCB’s The CS4000 system is based on the following standard PCB’s: Panel Board, PB

This board, together with an alphanumerical display, forms the control panel. Base Board, BB

Base board with the basic in and outputs, system communication etc. Loop Board, LB3

Connection board for up to 3 addressable analogue detector loops Zone board, ZB

Connection board for up to 16 conventional detector zones. This board can also be used as 16 input/outputs. Output Board, OB

Optional board with 8 programmable relay contacts. Rectifier Board, RB

Power supply board. USB expansion board

Optional board (piggyback on base board) with USB and serial communication possibilities. Ethernet board

Optional board (piggyback on base board) with Ethernet communication possibilities. IPLC board

Optional connection board for 1 addressable detector loop via Ethernet interface. See datasheet for respectively board for full information.

Page 36: Selwico CS4000 User manual

User Guide Chapter 3: Installation 34 Salwico CS4000

Connection Since all CS4000 systems are customer designed no standard exists for how the different PCB’s are to be connected in the system. However, in the figure below you will find an example with one board of each type showing the connection terminals.

Page 37: Selwico CS4000 User manual

User Guide Chapter 3: Installation 35 Salwico CS4000

Testing After installation of the fire alarm system the different parts of the system shall be tested to assure correct function. The CS4000 has a special test mode, which makes the testing easier. When a zone is in test mode it will:

• Not activate any external alarm devices or controls in case of a fire (this function can be turned off).

• The alarm level is lowered to give quick response to test gas. • Detectors and manual call points in the zone will blink. • Each tested detector and manual call point will indicate

activation with a red LED. • The units in alarm are automatically reset when the heat or

smoke concentration is under the alarm level or if the manual call point is reset.

Fire alarms from zones not in test mode will be handled normally by the system. Note: The tested zone will automatically return to normal operation after two hours.

Test a fire-detecting zone Put the zone into test mode under: Menu/3 Disconnections/1 New disconn./ 5 Test Mode Enter the zone number and confirm with OK button The indications DISC., Test and Zone/Unit will be lit to confirm the test mode. It is now safe to test each detector, manual call point etc in this fire zone during two hours. Use suitable testing equipment. All alarms will be listed under: Menu/7 History/1 Fire History List

Reset test mode After testing it is important to return the tested zone into normal condition again. Make sure that there is no detectors or manual call points still in alarm before leaving test mode. The zones in test mode are listed in the disconnection list, found under: Menu/3 Disconnections /2 Disconnection list. Choose the zone in the disconnection list and then press RESET.

Test the control unit display It is possible to test the alphanumerical display, all indications on the control panel and the local buzzer with the function Test display, found under: Menu/5 Settings/4 Test display.

Page 38: Selwico CS4000 User manual

User Guide Appendix A: Fault codes & Fuses 36 Salwico CS4000

Appendix A: Fault codes & Fuses

Fault list Listed below are all fault codes, their causes and how an operator with some knowledge of the system can solve the problem.

Fault code Cause Remedy Wrong type of loop unit Exchange to the correct loop unit Two loop units have the same address

Check the units

Hardware fault Exchange the unit A fuse is blown (a secondary fault appears)

Exchange the fuse

128 NO ANSWER

Lost communication. The system has recognized a unit but lost contact with it due to some interference.

Cable break in a detector or system loop (a secondary fault appears)

Mend the cable

The detector has a faulty sensor element.

Exchange unit 129 SENSOR FAULT

The smoke detector is exposed to wind

Take care of wind problem

Try to clean the detector with a vacuum cleaner or by blowing high-pressure air on it. If this does not help, exchange the detector.

130

DIRTY SENSOR The detector has a dirty sensor element

Ion smoke detector: Exchange the detector Fewer loop units found than configured

Check the specification and re-define the system

Loop units not correctly installed

Connect the unit correctly

131 TOO FEW FOUND

Missing answer from a unit Check address (possible double address). Otherwise exchange the unit.

132 TOO MANY FOUND More loop units found than configured

Check the specification and re-define the system

133

IN1 CABLE BREAK There is a cable break on input 1

Mend the cable break

134

IN2 CABLE BREAK There is a cable break on input 2

Mend the cable break

135

EXT 24V FAIL External 24V power source missing.

The local power supply is defect.

136

FEEDBACK FAULT External load is missing. Check the cable and the external load.

137

POSITION FAULT A supervised unit (for example a door or damper) is in the wrong position.

Check for obstructions.

138

LOOP CABLE SHORT A short circuit in the detector loop cable.

Locate the short circuit and fix it.

139

LOOP CABLE A SHORT Short circuit on the A-side of a detector loop.

Locate the short circuit and fix it.

140

LOOP CABLE B SHORT Short circuit on the B-side of a detector loop

Locate the short circuit and fix it.

141

CABLE BREAK POSITIVE A cable break on the positive conductor has been detected.

Locate the cable break and mend it.

Page 39: Selwico CS4000 User manual

User Guide Appendix A: Fault codes & Fuses 37 Salwico CS4000

142

CABLE BREAK NEGATIVE A cable break on the negative conductor has been detected.

Locate the cable break and mend it.

Two units have the same address.

Check the loop unit addresses

Loop unit faulty. Exchange the unit.

143

COMMUNICATION ERROR The communication with a unit is deficient.

Interference Locate interference and deal with it. 144

WRONG TYPE OF UNIT The type of unit specified is different from the type found or configured.

Check the specification and change definition or the unit.

Unit faulty Exchange the unit 145

UNKNOWN TYPE OF UNIT The type of unit specified is unknown to the system.

Wrong type of detector has been installed

Install the correct type and restart the loop.

146

TIMER STUCK The timer has been activated too long.

Check the unit.

148

DOUBLE ADDRESS Two units sharing the same address

Change one of the addresses.

149

CABLE SHORT Short circuit on cable. Locate the short circuit and fix it.

150

VALVE CLOSED The valve is closed. Open the valve

151

CONFIGURED NOT PRESENT

Unit is configured but not present.

Add the unit or change the system configuration.

152

PRESENT NOT CONFIGURED

Unit is present but not configured.

Remove the unit or change the system configuration.

153

HIGH CURRENT ON LOOP There is high current in the loop cable.

Check if there is to many units connected to the loop. Compare with the loop limitations.

154

LOOP POWER LOSS The loop voltage is missing. Exchange the loop board.

155

EARTH FAULT POSITIVE Too low impedance on positive conductor.

Locate the earth fault and fix it.

156

EARTH FAULT NEGATIVE Too low impedance on negative conductor.

Locate the earth fault and fix it.

157

FUSE FAULT A fuse is defective. Replace the fuse.

158

BATTERY FUSE FAULT A battery fuse has blown or a cable break.

Replace fuse or mend the cable.

159

CABLE BREAK A cable break has been detected.

Mend the cable.

160

CABLE OVERLOAD Too high current on an output.

Check external loads.

161

POWER FAULT The main power supply is lost.

Check the main power supply.

162

EMERGENCY POWER FAULT

Emergency power is lost. Check the emergency power supply.

163

BATTERY FAULT A bad battery is detected. Charge the battery. If the fault remains then replace the battery.

164

CHARGING LOSS The battery charger is unable to charge the battery.

Replace the battery charger.

165

EXTERNAL FAULT External equipment has indicated fault.

Check the external equipment.

166

EARTH DETECTION FAULT

Unable to detect earth fault. Replace the earth fault circuit.

167

CHECKSUM EEP Incorrect EPROM checksum.

Contact our service department.

Page 40: Selwico CS4000 User manual

User Guide Appendix A: Fault codes & Fuses 38 Salwico CS4000

168

RESTARTED Something has restarted. If it happens repeatedly, contact our service department.

169

TOO LONG BOOT Exceeded the maximal allowed boot time.

If it happens repeatedly, contact our service department.

170

EXTERNAL LOAD ON LINE There is a too high external load on a conventional zone.

Locate the load and deal with it.

171

EXTERNAL SOURCE ON LINE

Feeding voltage detected on a conventional zone.

Locate the source and remove it.

172

LOW POWER SUPPLY IN1 Low voltage on the primary 24VDC power supply to the internal PCB’S.

Check the power supply.

173

LOW POWER SUPPLY IN2 Low voltage on the secondary 24VDC power supply to the internal PCB’S.

Check the power supply.

174

LOW POWER SUPPLY LOCAL

Too low voltage on the 3.3V/5V feeding to the internal circuit boards.

Contact our service department.

175

LOW POWER SUPPLY Too low incoming 24VDC supply to the internal circuit boards.

Check the power supply

The configuration file is corrupt.

Check the configuration file and re-configure the system.

176

SYSTEM CONF FAULT

An error has occurred during downloading of the configuration file.

Re-configure the system. If the fault remains, contact our service dept.

177

LOW PRESSURE External equipment indicates low pressure.

Check the pressure on the supervised unit.

178

ACTUATOR 1 Missing feedback from actuator 1

Check cables to actuator 1. If the cables are OK, change the actuator.

179

ACTUATOR 2 Missing feedback from actuator 2.

Check cables to actuator 2. If the cables are OK, change the actuator.

180 MAINS POWER The main power supply is lost

Check the main power supply

181 INTERNAL FAULT Internal system fault Contact our service department 209

WRONG TYPE OF UNIT DEFINED

The type of unit found is different from the type configured.

Change the unit or the system configuration.

210 ERROR IN CAUSE&EFFECT DEFINITIONS

Fault detected in the configuration.

Check the configuration.

255 ILLEGAL Internal system error. Contact our service department.

Page 41: Selwico CS4000 User manual

User Guide Appendix A: Fault codes & Fuses 39 Salwico CS4000

Fuses If a fuse is defective in the system a fault will be displayed at the control units. Locate and replace the fuse with the information below.

Fuse list Location Fuse Fuse rating

Base board F1: Alarm bell output 1 AT Base board F2: Alarm bell output 1 AT Base board F3: Alarm bell output 1 AT Base board F4: Alarm bell output 1 AT Rectifier board F3: To transformer 3.15 AF Rectifier board F4: To transformer 3.15 AF Rectifier board F5: To external 230VAC 3.15 AF Rectifier board F6: To external 230VAC 3.15 AF Rectifier board F8: Battery 4 AF Rectifier board F9: Battery 4 AF Rectifier board F10: From transformer 6.3 AF Rectifier board F11: From transformer 6.3 AF

Fuse type: 5x20 mm

Fuse locations on base board, BB.

Fuse locations on rectifier board, RB.

Page 42: Selwico CS4000 User manual

User Guide Appendix B: Quick guide* 40 Salwico CS4000

0System Fault

Home Disc.

Test

Alarm Device

Power

Alarm Transfer

Alarm DelayZone/Unit

2

Warning

OK

Pre-Alarm

Menu

Reset

FAULT DISC.

NextMute

OK

ABC3

DEF' '1

5JKL

6MNOGHI

4

8TUV

9WXYZPQRS

7

F1

F2

F3

FIRE

Mute

Reset

Mute

Appendix B: Quick guide*

Menu

Reset

Fire alarm Accept a fire alarm & silence buzzer: Press Reset a fire alarm: Press

Disc.

Fault alarm Accept a fault alarm & silence buzzer: Press

Disc.

Disc.

Reset

Reset a fault: 1. Press 2. Select: Fault alarms→Fault list 3. Select actual fault and press

Disconnections Disconnect a zone 1. Press 2. Select: New disconnection (access level 2B)

3. Select zone. Press OK to confirm. 4. Select type of detector. Press OK to confirm. 5. Select type of disconnection. Press OK to confirm.

The Disc. indication is illuminated.

Disconnect detector/manual call point 1. Press 2. Select: New disconnection (access level 2B) 3. Select: Detectors & manual call points 4. Enter type, zone and address of detector(s) 5. Choose disconnection type. Press OK to confirm.

The Disc. indication is illuminated.

Reconnect item 1. Press 2. Select: Disconnection list 3. Select disconnection and press

General operation The arrow keys are used to navigate in the menus and select different menu alternatives.

OK

Shows the previous item in the list. If the first item is displayed it will go to the last

Go to previous i

Select the chosen menu alternative.

Shows next item in the list. If the last item is displayed it will go to the first

Local service contact: Company: Tel: E-mail: *A copy of this page may be placed at the fire alarm control panel

Page 43: Selwico CS4000 User manual

User Guide Appendix C: Display analogue values of a loop unit 41 Salwico CS4000

Appendix C: Display analogue values of a loop unit

The analogue value of a loop unit can be displayed on the panel board. This information can be useful to see the condition of a loop unit.

To get a list of loop units go to: Menu/ 6 Service menu/ 4 Zones Choose a zone and confirm with 2 Loop unit. Choose a loop unit and confirm with OK button. The analogue values of a selected loop unit are now read and shown on the display.

The analogue values depend on the type of loop unit and the status of the detector. Use the table below to determine the status of each unit. Analogue values for detectors and manual call points

Loop Unit Channel Analogue values

Name ID No Type Normal* Alarm Fault

NS-AOS NS-AOS-IS

226 0

1

Smoke

Heat

60-100 >(Normal + 60) <5 or not responding to

test

NS-AOHS NS-AOHS-IS

194 (CS3000 type) else 234

0

1

Smoke

Heat

60-100

90-100 (21-23°C)

> (Normal + 60),

temp. dependent

<5 or not responding to

test

NS-AIS 225 0 Smoke 50-100 > (Normal +75) <5 or not responding to

test

NS-AIHS 195 (CS3000 type) else 233

0 Smoke 50-100 > (Normal + 75),

temp. dependent

<5 or not responding to

test

NS-AUV 194 (CS3000 type) else 232

0 UV 5-23 131 <3

NS-AH/CS 230 0 Heat 90-100 (21-23°C)

222 (87C) <5

NS-AH/A1S 228 0 Heat 90-100 (21-23°C)

179 (56C) <5

IA-130 2 0

1

Smoke

Heat

20-87

90 ± 5% at 25°C

165

178

6

6

* The normal value depends on the environment. The system indicates on the display when there is a

fault on a detector.

Page 44: Selwico CS4000 User manual

User Guide Appendix C: Display analogue values of a loop unit 42 Salwico CS4000

NS-ACP, NS-ACWP

227 0 Callp. 36± 5% at 25°C

180 9

LK-2/-2K 64 0 Callp. 127 ± 5% at 25°C

150 6

OA-120 15 0

2

Smoke

Sub.L

20-100

>15

170 6

OA-130 16 0

1

2

Smoke

Heat

Sub.L

20-100

90 ± 5% at 25°C

>15

170

178

6

6

RDJ-2 8 0 Smoke 21 - 45 96 4

RDJ-2T 10 0

1

Smoke

Heat

21 - 45

90 ± 5% at 25°C

96

178

4

6

RDO-2 14 0 Smoke 40 ± 10 102 6

SID-38 4 0 Smoke 10 - 41 85 6

SID-38T 6 0 1

Smoke Heat

10 - 41 90 ± 5% at 25°C

85 178

6 6

TDT-2 18 1 Heat 90 ± 5% at 25°C

178 6

TDT-2/RoR 19 1 Heat 90 ± 5% at 25°C

(223) 6

TDT-2K 20 1 Heat 90 ± 5% at 25°C

178 6

TDT-2K/RoR 21 1 Heat 90 ± 5% at 25°C

(223) 6

TDT-2/80° 26 1 Heat 90 ± 5% at 25°C

213 6

TDT-2/RoR,57° 27 1 Heat 90 ± 5% at 25°C

(178) 6

TDT-2K/80° 28 1 Heat 90 ± 5% at 25°C

213 6

TDT-2K/RoR,57°

29 1 Heat 90 ± 5% at 25°C

(178) 6

If you want to connect a unit that you can not find in this table, please contact our service department.

NB! The value within brackets indicates the maximum alarm level for rate of rise detectors. The detector may generate a fire alarm before it reaches the maximum alarm level if the temperature rise is to fast. The fire alarm condition is generated by signal processed data.

Page 45: Selwico CS4000 User manual

User Guide Appendix C: Display analogue values of a loop unit 43 Salwico CS4000 Address units type AE

Address units make conventional digital detectors and other digital signals addressable and compatible with the CS4000 system. The type of connected device is set with the ID switch, see table below.

Analogue values for address unit type AE

Address unit Channel Analogue values

Name ID No. Normal Alarm Fault

Heat detector 127 2 15 - 32 -/84 6

Intrinsically safe detectors, using AE-2K/I and ES-2K in combination

99 2 15 - 32 -/84 6

Sprinkler, carbon dioxide 125 2 15 - 32 -/84 6

Sprinkler, foam 121 2 15 - 32 -/84 6

Sprinkler, halon 107 2 15 - 32 -/84 6

Sprinkler, water 126 2 15 - 32 -/84 6

UV flame detector 119 2 15 - 32 -/84 6

Optical smoke detector 111 2 15 - 32 84 6

Fire alarm from central 114 2 15 - 32 84 6

Manual call point 116 2 15 - 32 84 6

Heat detector , constant voltage on sub-loop

118 - - - -

Door indicating unit 117 - - - -

IR flame detector 123 2 15 - 32 84 6

Analogue values for address unit type NS-AIN

Address unit Type of Analogue values

Name ID NS-AIN Normal Alarm Fault

Sprinkler 1 AIN2 32 - 96 > 96 0 - 32

Intrinsically safe unit 2 AIN1 32 - 96 > 96 0 - 32

Detector 3 AIN1 32 - 96 > 96 0 - 32

Conventional detectors 4 AIN2 32 - 96 > 96 0 - 32

Intrinsically safe unit (industry)

5 AIN1 32 - 96 > 96 0 - 32

Detector (industry) 6 AIN1 32 - 96 > 96 0 - 32

Sprinkler & valve 7 AIN2 32 - 96 > 96 0 - 32

Indication 8 AIN2 32 - 96 > 96 0 - 32

Page 46: Selwico CS4000 User manual

User Guide Appendix C: Display analogue values of a loop unit 44 Salwico CS4000 Analogue values for other loop units

Loop Unit Channel Analogue values

Name ID No Function Normal Activated

KS-2/-2K 240 0 Short circuit 0 26

UR-2K 233 0 Timer 0 85

UR-2KN 232 0 1

Timer Key

0 0

85 85