service report island sky english
TRANSCRIPT
-
8/3/2019 Service Report Island Sky English
1/8
Service Report
Service at: Istanbul and Samsun / TurkeyCustomer:Period: Oct 8 to 13, 2008Alternator: DIDBN 131 I/10 Number: 8103336 C003
Scope of work: Assembly and start-up of DG I
The passenger vessel ".." in the port of Istanbul on 09/10/2008.
-
8/3/2019 Service Report Island Sky English
2/8
We found the alternator in the following condition on the October 9,2008:
The stator was fixed to the foundation with the pins in place. The rotorwas coupled to the drive machine; the bearing and the end shield were
mounted.
Since there was no grease on board and the bearing has not yet beengreased, the bearing end cover and the grease slinger had to be
removed.
-
8/3/2019 Service Report Island Sky English
3/8
An insulation test was performed on the stator winding, and all powerand control cables on the stator and rotor sides were connected.
When doing so, we found one of the auxiliary terminal boards to bebroken.
-
8/3/2019 Service Report Island Sky English
4/8
The board was fixed temporarily using a cable tie.
We routed and fixed all cables in the alternator and connected both thevoltage regulator and the resistor integrated into the excitation.
-
8/3/2019 Service Report Island Sky English
5/8
In the meantime, we installed the PT100 for the bearing temperaturemonitoring in the alternator and integrated a temperature alarm circuit
into the existing alarm control. Furthermore, we installed two resetbuttons with signal lamps in the engine control room and the control
system in the engine room, in addition to the existing alarm control. Weset the warning threshold to 75 C.
-
8/3/2019 Service Report Island Sky English
6/8
When the grease arrived on Friday afternoon, we greased the bearingand tried to assemble the alternator completely. However, since we didnot have enough time due to the delay for obtaining of the grease, we
discussed the problem with the port agent who then organised a flight to
Samsun for Saturday.
The alternator was assembled completely on Sunday. We rotated themachine by hand prior to the first start, and three visible damage points
were found on the exciter system. They had evidently been caused whenthe end shield was mounted during the assembly of the alternator.
Insulation tests and resistance measurements were performed for thewinding; no abnormal conditions were found.
The points mentioned above were coated with insulation paint.
-
8/3/2019 Service Report Island Sky English
7/8
The start-up was performed as follows:Dry run in the excited state for approx. 20 minutes.
The bearing temperatures increased to 26 C. The machine was stoppedand operated with excitation at 60Hz.
I1/K1: 16VDCI2/K2: 141VDCUH1/UH2: 95VACUH1/UH3: 186VACWH1/WH2: 99VACU-V-W: 3x 440VAC
The alternator was operated in this state for a longer period until thecrew was able to rectify a problem with the motor control.
Subsequently, the alternator was synchronised with alternator DG II andsubjected to load. Since different currents could be measured at thesame load, the no-load voltage was adjusted on alternator DG II. It
differed from the voltage measured on alternator DG I by 3V. A loosecontact was detected on the setpoint potentiometer of DG II. A jumper
was installed on the voltage regulator between "s" and "t", and thevoltage was adjusted on the regulator. The next dry runs in parallel
operation were completely properly; each alternator was loaded with alittle over 300kW at approx. 500A.
We shifted the entire load to alternator DG I, opened the drive-end cover
of DG II and measured the bearing temperature. This measurementyielded a temperature of 60 C.
DG I was operated at a load of more than 600kW for 2 hours, and thetemperature was measured cyclically. The last measurement yielded a
bearing temperature of 40 C.I1/K1: 24.7VDCI2/K2: 144VDC
UH1/UH2: 99VACUH1/UH3: 196VAC
WH1/WH2: 102.5VACU-V-W: 3x 441VAC
Since non-one on board could find the PT100 monitoring unit which wassupplied a few years ago after damage to the bearing of DG II, no
temperature monitoring could be installed for DG II. We gave instructionsto the chief electrician on how to set up such a monitoring unit and how
to integrate it into the existing system. A circuit diagram was created andhanded over as a PDF file, and is also attached to this report. The
following components must be sent to the Island Sky:1 pc. PT100 tripping device2 pcs. relays with 2 changeover contacts
-
8/3/2019 Service Report Island Sky English
8/8
We gave one PT100 to the chief electrician and showed him where andhow to install it.
The defective setpoint potentiometer of DG II must be replaced. After thereplacement, the jumper between "s" and "t" on the voltage regulator
must be removed again, and the voltage must be set accordingly.
There is an option to bring the actual temperature with the 0 10Voltsignal of the PT100 tripping device to the engine control room. It would
make sense to install a measure instrument like this to give the crew thechance to react as soon as possible if there is a problem on the
bearings.
Best regards
Daniel Patzek, service engineer.Oliver Wanka, service engineer.