“Setting Standards for the Industry”
2010 PRODUCT CATALOG
● DENVER FOAM® OPEN CELL POLYURETHANE BACKER ROD
● MILE HIGH FOAM® CLOSED CELL POLYETHYLENE BACKER ROD
● ULTRA BLOCK® FIRE STOPPING SYSTEMS
Backer Rod Mfg. Inc. 4244 N. Broadway ● Denver, CO 80216
Toll Free 800-595-2950 ● Telephone 303-308-0363 ● Fax 303-308-0393 www.backerrod.com
Backer Rod Mfg. Inc.
Backer Rod Manufacturing – one of the largest manufacturers ofbacker rod materials in the world. We are experts in the specialtycaulking field, providing backing for elastomeric and other appliedsealants to the worldwide construction market. No other companymanufactures and supplies backer rod products that are able towithstand temperature variations from -60°F to over 2000°F.
We serve customers in the construction industry with specificapplications in expansion/construction joints to include:
• highway construction and maintenance• log homes• parking decks• buildings requiring structural fireproofing
fire rated for 1,2,3 and 4 hours construction (ASTME 119)• seismic movement (ASTME 1399)
Backer Rod offers three distinct products for use in constructionjoints: Denver Foam®, Mile High Foam®, and Ultra Block®. Thetype of backer rod used is governed by the type of sealant used, plusenvironmental, seismic and temperature requirements. Backer RodManufacturing is proud to market our products through authorizeddistributors and select OEM customers around the world.
Backer Rod Mfg. Inc. Reply to: 4244 N. Broadway Denver, CO 80216 2929 Walker Drive P.O. Box 8005 Green Bay, WI 54308-9229 Phone 303-308-0363 Fax 303-308-0393 Phone 920-406-4000 Fax 920-406-4040
GENERAL CERTIFICATE OF COMPLIANCE
DESCRIPTION: BACKER ROD MFG. INC. SEALANT BACKING PRODUCTS Denver foam Mile High Foam Ultra Block THESE PRODUCTS ARE TESTED TO ONE OR MORE OF THE FOLLOWING STANDARDS:
DENVER FOAM® MILE HIGH FOAM® ULTRA BLOCK® • ASTM D 1622 • ASTM D 1622 • UL 2079 • ASTM D 1623 • ASTM C 1016 P. B • ASTM E 814 • ASTM C 1016 • ASTM C 1253 • ASTM E 84 • ASTM D 5249 - 95 • ASTM D 5249 • ASTM E 1399 • ASTM D 3574 • ASTM D 1623 • ASTM E 119 • ASTM C 1330 type O • ASTM C 1330 type C • ASTM C 719 • NFPA 251 • NFPA 255
No asbestos, PCB’s, or lead are used or contained in these products.
Bill Bergel February 10, 2009 ___________________________ _________________ Sales and Marketing Manager Date
The majority of construction incommercial building today is
done by use of large building panelsof various types, connected by ahigh performance elastometric seal-ant material to form a waterproofseal. These panels consist of eitherprecast concrete, prestressed con-crete, or curtain wall which is pre-dominately glass and metal. Anycombination of these three typesalso is commonplace in modernconstruction.
It is vitally important that theconnecting link, the sealant, joiningall these panels be of top quality,capable of performing satisfactorilyfor a great many years. without thisperformance, water tightness soon islost, resulting in long, costly mod-ifications and repairs.
Many factors must be consideredin designing a commercial buildingwhich will give many years of trou-ble free service. These include jointdesign, selection of sealant, surfacepreparation of joints just prior tocaulking and, finally, selection ofthe proper backer rod (againstwhich sealant is placed). The rightdecisions in these important areas,plus proper installation of the prod-ucts, ensures desired results.
The backer rod evolves
Evolution of the backer rod from thefirst use of caulking to the present
Hidden, but essentialA technical reviewof backer rodsby J.F. Gibb
At left, the result of outgassingby a closed cell backer rod. Therod has been removed, and thepanels and sealant bead sawedin cross-section to showcavities caused by the bubbles.This is an unsatisfactory seal.Below, the sample at left seenfrom the side. A cured sealantbead applied above a closed cellbacker rod was ruptured whentrapped gases escaped from therod.
John F. Gibb invented and developedthe production equipment used to makeopen cell backer rods, and holds U.S.and foreign patents on this machinery.He is a member of the ASTM C-24 JointSealant Committee, and is GeneralManager/part owner of Backer Rod Mfg.& Supply Co., Denver.
40 THE CONSTRUCTION SPECIFIER/MARCH ’80
state of the art covers use of manydifferent types of materials. Theyrange from sand in horizontal joints,through wood, fiber board, jute,rope, and twisted paper. About 17years ago, a product evolved whichconsisted of an extruded plastic rod.
This new backer rod was a closedcell, flexible foam material. At first,it was made from polyethylene plas-tic. Now it consists of polyethyleneand polypropylene, both nearlyidentical in appearance and per-formance. This new rod is manufac-tured by plastic extrusion: A gas isinjected into the material, creatingplastic foam. The result might bedescribed best as being somewhatsimilar to a tube inflated underslight pressure as gas is trappedwithin its cellular structure. Thisrod proved to be far superior to whathad been used previously in thetrade, but was not without its prob-lems.
Problems — and solutionsOne of the more serious problemswas outgassing. When these closedcells and their outer skin somehowbecome ruptured, trapped gasesslowly escape to the atmosphere. If ahigh proportion of these cells be-come ruptured or deflated (so tospeak), much of the rigidity of therod is lost. The rod also loses muchof its ability to regain its originalround shape once it has been de-formed.
The problem of outgassing as-sociated with these new flexible foambacker rods resulted in sealantmanufacturers insisting on furtherresearch, in the attempt to find asuitable material that would elimi-nate this problem — without creat-
ing even more serious ones.For many years, in limited appli-
cations only, polyurethane foammaterials had been used success-fully. This promoted further de-velopment of this material, to de-termine its suitability for use inbacker rods in the caulking busi-ness.
Most early applications em-ployed a backing material cut intoshort strips (square or rectangular incross-section). The material exhi-bited a wide range of physical prop-erties, because much of it had beencut from scrap material used by thefurniture business. The type ofpolyurethane used in that industry isrequired to have a very high de-gree of resilency, and to retain thisproperty through severe usage. Thissame property is necessary in ex-pansion joint backer rod. Therefore,it proved to be an ideal material forbacker rod use.
About six years ago, a round,open cell, flexible polyurethanebacker rod was introduced. Theproduct was made from specialformulations of these flexiblefoams, producing a more uniformmaterial. (As noted, uniformity waslacking in previous urethane backerrod produced from scrap.)
Open vs. closed cell
There are some interseting (and im-portant) differences between openand closed cell backer rods.
Both open cell and closed cell areinert to all common and more pre-dominately used sealant materials onthe market today. Both have ex-cellent chemical resistance.
Both, too, are classified as non-
staining. This means they containno materials that would bleed outslowly and seep into the sidewalls(substrate), later to reappear as dis-coloration on the surface (some dis-tance away). This is a particularlyimportant point, if marble or othermasonry materials are used.
The open cell rod is more flexiblethan its counterpart closed cell. Theopen cell must depend on its chem-ical and physical make up to attainrigidity, while closed cell rigidity isthe result of gases trapped in itsinterior (as explained earlier).
Rarely in commercial buildingconstruction do expansion jointwidths conform exactly to design.For instance, a one-half inch jointfrequently will vary from as little asone-quarter inch or less to as muchas three-quarter inch (or more). It isvirtually impossible to manufactureor to erect large building panelseconomically to such precise di-mensions that joints between suchpanels stay within close tolerances.A backer rod to be packed betweenthese panels must be flexibleenough for easy insertion.
Manufacturers of closed cellbacker rods recommend that theproduct not be compressed morethan 25 percent of its diameter. Con-sequently, the applicator mustchange sizes frequently, usingclosed cell in commonplace, vary-ing width joints, and open cell rod ifhe is to exceed the 25 percent max-imum compression limit.
Open cell backer rod must becompressed at least 25 percent; itdoes not hurt these rods to be com-pressed as much as 75 percent oftheir diameter. This allows theapplicator to use fewer sizes in vary-
THE CONSTRUCTION SPECIFIER/MARCH ’80 41
ing width joints. Many times, onesize will work the full length of thejoint (which might not be the casewhen using closed cell rod).
Three primary purposesA backer rod has three primary pur-poses. First, it forms a base againstwhich sealant is applied. (It there-fore determines the thickness of thesealant bead.) Also, it forces un-cured sealant out laterally undertooling pressure, resulting in 100percent contact of sealant tosidewall (substrate). These are thebond lines. Finally, backer rodsdictate the cross-sectional config-uration of the sealant bead.
Flexibility of the two backer rodmaterials plays an important part intooling the newly applied sealantbeads. A backer rod, although im-portant in an expansion joint, issecondary to the primary prod-uct—the sealant. The desired endresult is a satisfactory seal thatmeets or exceeds specifications.
The more rigid closed cell backer
rod is able to withstand a heavierpressure. The greater flexibility ofthe open cell rod requires thecaulker to use lighter toolingpressure, to minimize spring back.(It is not a difficult technique tomaster, for open cell backer rod hasbeen used successfully for 20 yearsor more.)
Tooling the hour glassTooling is done with a variety of in-struments. Most incorporate asemi-flexible blade, like a spatula. Itis the tooling operation that givesthe cross-sectional shape to thenewly applied sealant bead. Thisshape is referred to as an “hourglass” configuration.
The hour glass shape is impor-tant. It results in a maximum bond-ing surface on the sidewalls, and athinner section midway between.This means the adhesive bond to thesidewalls will be of sufficientstrength to eliminate failure causedby repeated elongations and con-tractions of the sealant material. Insimple terms, the strength of the
bond to the sidewalls forces ellasticmovement of the sealant. Elasticityof the sealant comes into play by al-lowing stretching and contractionat the thinnest point, avoiding ex-cessive stress at the bonds to thesidewall. Choosing the correctbacker rod obviously plays an im-portant part.
If a backer rod is placed incor-rectly (too deeply) or so it doesn’tforce an hour glass cross section,cohesive or adhesive failure be-comes a distinct possibility.
Proper cross sectionsFigures 1 and 2 show the dif-ferences between the proper crosssection of a newly applied sealantbead, and an incorrect one. Figure 2is incorrect because the ratio ofthickness of the sealant bead at thebond line to that at the midwaypoint is too small. Movement of thejoint sidewalls will put undue stresson the bond lines. The high cohe-sive strength of the overly thicksealant bead will make it very dif-ficult or impossible for the sealant toelongate. The bonds may fail even-tually because of this; they will notif they have the correct ratio de-picted in Figure 1.
This problem can be com-pounded if an incorrect back-up isused in cases where three-sidedadhesion occurs. In these cases, asealant cures while adhered to bothsidewalls, and to the backer rod.When the back-up rod is composedof a rigid, unyielding material,problems can arise.
Closed cell backer rods, being anolefin-type plastic material, are wellknown for their anti-stick prop-erties. Usually, any inital adhesionto these back-ups break downquickly, and the sealant comes free.
This was thought to be the casewith open cell rods as well, sincethe weak open cell surface structurealso shears away from the sealantbead. In cases where it does not,however, the flexibility of the opencell rod allows it to move with thesealant bead (with absolutely no illeffects) for the life of the sealant.
This has been demonstrated both
42 THE CONSTRUCTION SPECIFIER/MARCH ’80
in laboratory tests of 10,000 cycles(excess of 25 years) and in over 20years of actual use in the field. Prob-lems do arise when a rigid back-up isused: the sealant bonds to ittenaciously. When the joint moves,the sealant doesn’t—and failurelikely will occur.
Closed cell rods tend to take a setwhen compressed for extendedperiods of time. This is not the casefor open cell rods. It is a basic re-quirement of these open cell foamsin the furniture and padding indus-try that they not take a set. On occa-sion, closed cell rods have beenknown to move back into a jointunder gunning pressure, if the rodfirst was placed in the joint too far.(This permits too thick a sealantbead, risking bond failure.)
Open cell rods have a high coeffi-cient of friction, and do not slideeasily over most surfaces. This re-sults in a good grip to sidewalls, anda resistance to movement undergunning presuure. Open cell rod canmove, however, if it is not com-
pressed the recommended 25 per-cent in joint packing.
Moisture AbsorptionOne of the myths that existed foryears about open cell backer rod wasits alleged moisture absorption.Many felt its open cell structuremade it perform as a sponge. Opencell foam will absorb some water,but under most situations it does notretain it for long. Twenty-four hourtotal submersion tests indicate 50percent absorption is about average.(This, of course, is not encounteredin the field, but whatever watermight be absorbed in actual practicestill is not retained long.) Closed cellrod, on the other hand, is virtu-ally non-absorbent; therefore, noproblem.
This open cell feature has provento be an important asset, because anescape route for gases always isreadily available. Should somemoisture become trapped betweenthe sidewalls and the backer rod, thearea usually is much slower to dry
out than is that part of the joint notcovered by the backer rod—and ex-posed to the air. (See Figure 3 andFigure 4.) The portion to be caulked,however, is dry enough to be sealed.
When this moisture problem oc-curs and the wetness begins toevaporate, vapor pressure is built upbetween the backer rod and thesidewalls. In the case of the open cellrod, when these vapors take thecourse of least resistance they gothrough the backer rod to escape. Asfor closed cell, being impervious,the only escape route is through thenewly applied sealant bead. Whenthis occurs, the sealant bead blis-ters. Channels can developthroughout it; at times, the bond linefails or is seriously weakened.
Another important plus for opencell rod which became obvious in theapplication of air cured sealants(silicones) was the fact that a cure isinitiated from both sides. Thisspeeds up the cure substantially(highly desirable with slow-curingsealants). This faster cure to a largeextent eliminates precure adhesive orcohesive failure problems.
Two-sided curing is impossiblewith closed cell rod material, there-fore air curing sealants remain in anuncured or semi-cured state for alonger period of time. (See Figure 5and Figure 6.)
OutgassingBubbling of newly applied or semi-cured sealant beads is referred to asoutgassing. The results are similarto those caused by trapped mois-ture. This is a common problemwhen using closed cell rod. Formany years, it was suspected thisbubbling in newly applied sealantbeads was caused by the sealant.However, more precise observationshowed it to be from closed cellbacker rod.
It was explained earlier thatclosed cell backer rod containstrapped gases within its surface skinand inside its closed cells. Also, itwas pointed out that if this skinand/or some of these cells becomeruptured, the gas begins to seep out.The impervious nature of the closedcell backer rod prevents escaping
THE CONSTRUCTION SPECIFIER/MARCH ’80 43
gases from going any place otherthan through the newly appliedsealant beads.
This seepage bubbles in the seal-ant, that, at times, can extend fromthe vent hole in the backer rodcompletely through the sealant bead,to its outer surface. This causes aleak in the seal. Most outgassing andbubbling isn’t quite this severe.Usually, these gas bubbles staywithin the sealant bead, though
they do detract from appearance,and weaken the sealant bead. (SeeFigure 7.)
Backer rod ruptureRupture of closed cell backer rod canoccur in several ways. Roughmasonry surfaces often (and easily)cut open the surface skin and under-lying cells, allowing enclosed gasesto escape. Rupture also can becaused by equipment used to pack
the backer rod into the joints. Asmentioned earlier, closed cell rodshould not be compressed over 25percent of its diameter. Variation injoint width is so predominant thatover-compression occurs often; thistoo can cause rupture of the skin andunderlying cells.
Over-compression in packing thejoint requires heavier pressure inuse of the packing tool, which in-troduces more chance of rupture ofthe skin and underlying cells, at thepoint of contact of the tool. Themore over-compression, the morepoints of contact, therefore the morechance of rupture. Should the jointbe in a rough masonry wall, theproblem is compounded. The roughsurfaces also will tear open thebacker rod when it is subjected tosuch over-compression.
This problem can be com-pounded further if heat is involved,and rapid expansion of the buildingpanels occurs. The more rapid clo-sure of the joints (and expansion ofthe gases) due to heat forces gasesinto the uncured sealant faster, onlyadding to the troubles.
Another cause of outgassing withclosed cell rod is sharp bends.Again, the surface skin and underly-ing cells can be ruptured. It is betterto break closed cell backer rod atsharp turns than to bend it. Thebreak provides an avenue of escapefor these gases, away from the seal-ant bead.
One proposed partial solution tothis outgassing problem was to packthe joint well in advance of (days be-fore) the caulking operation. How-ever, this would increase labor costssubstantially. The closed cell rodwould take a permanant set, par-tially releasing its grip to thesidewalls. This would risk move-ment during caulking (what’s more,it was found closed cell rod stillgassed, even after a year in a joint).
Outgassing is one problem thatdoes not exist with open cell rod. Thelack of an outer skin (or closedcells) totally eliminates any possi-bility of this occurring. In fact, pre-vention of outgassing was the pri-mary reason open cell backer rodwas developed.
44 THE CONSTRUCTION SPECIFIER/MARCH ’80
Other consequences of heatClosed cell backer rod is a thermo-plastic olefin material. This charac-teristic limits its usage if highertemperatures are encountered. (Themaximum allowable temperaturerecommended by manufacturers is160°F.) Open cell backer rod is athermosetting plastic material withmuch higher heat resistance. It hasbeen used successfully for limitedperiods under hot-applied sealantmaterial (up to 500°F), with no ill ef-fects.
The effects of elevated tempera-tures on successful application of asatisfactory sealant bead are of vitalimportance. New construction inhot climates reportedly will en-counter temperatures of nearly300°F for some materials. A backerrod material installed under suchconditions must be able to with-stand these temperatures withouthaving a detrimental effect onapplied sealants. The possibility ofbacker rod outgassing or shrinkingbrought about by contact with hotsurfaces should be considered care-fully.
Both closed cell and open cell ma-terials have good cold temperaturecharacteristics under normal caulk-ing environments. However, in ex-tremely cold temperatures the opencell has a definite edge, remainingflexible at minus 60°F.
A minor role?
The backer rod in an expansion jointappears to play somewhat of aminor role. After the sealant has at-tained a full cure, the rod serves nofurther purpose other than, perhaps,offering some insulating propertiesin the expansion joints.
Although the role backer rodsplay may seem minor, it is impor-tant that architects, specificationwriters, caulking contractors andbuilding owners ensure that seals inexpansion joints perform well, anddo not become the prematurelyweak link in the structure.
It is in making possible that im-portant seal that the backer rod per-forms its hidden, but essentialtask.
THE CONSTRUCTION SPECIFIER/MARCH ’80 45
From top to bottom: (1) Atypical rough masonry jointwhich will be sealed with acaulking material, after abacker rod has been packedbetween the panels. (2) Anopen cell backer rod beingpacked into an expansionjoint prior to caulking. (3) Aproperly caulked joint inrough masonry, using anopen cell backer rod (notethe absence of bubbles in thecured sealant bed).
Manufactured under U.S. and foreign Patents and Applications
DENVER FOAM® is a ROUND, LABOR-SAVING, continuous-length, compressible open-cell polyurethanefoam used primarily as a “NON-GASSING” backer rod in caulking and sealant applications, such asexpansion joints.
TIME PROVEN APPLICATION: Open-cell polyurethane foam, in various shapes and densities, hasbeen used successfully for many years in the caulking and sealant trade without adverse effect.
1. Note that DENVER FOAM® is dispensed from core - - 2. Note ease of application from scaffold. Small bales will“binder-twine” type bale enables workman to secure sit flat and can be lashed easily. Bales can be steppedto scaffold without dispensing problems. over easily.
ADVANTAGES:
1. LABOR SAVING: DENVER FOAM® can be installed rapidly with any type toolWITHOUT REGARD FOR SURFACE DAMAGE. Since round, compressible DENVERFOAM® can be installed in continuous form IN JOINT WIDTHS OF LARGE VARIA-TION without the necessity of changing backer rods sizes excessively, DENVERFOAM® can be installed TWO OR THREE TIMES FASTER than conventional closed-cell polyethylene or rectangular shaped backer rod materials.
2. “NON-GASSING”: DENVER FOAM® is open-cell polyurethane foam, and, being vir-tually “gas-free”, can be installed rapidly without regard to surface damage, therebyeliminating potential sealant failures and expensive repairs due to “gassing” action ex-perienced by damaged closed-cell polyethylene backer rod materials.
3. “BINDER-TWINE” PACKAGING: DENVER FOAM® is packaged in continuouslength bales in preshrunk, transparent polyethylene in such a manner that DENVERFOAM® is dispensed from the center of the bale. Several bales are packed in a masterbag of extra-strength polyethylene, and tied with a removable and reusable plastic tie.Each diameter is designated by a different color label, and premarked at nominal 100foot intervals. (NOTE: See explanation next page for master-compressed FREIGHT-SAVING shipping bales, and also pre-packed MINI-BAGS for small requirements.)
D7
DE
NV
ER
FO
AM
®
19
92
SE
AL
AN
T B
AC
KE
R-R
OD
ADVANTAGES (continued):
4. COMPETITIVE: DENVER FOAM® is competitively priced, throughout the World, with most backerrod materials
5. SEALANT ADHESION TO BOTH OPEN-CELL AND CLOSED-CELL BACKER ROD: Unbiased thirdparty laboratory tests and extensive field experience show that sealant materials usually adhere toboth open-cell polyurethane backer rod and closed-cell polyethylene backer rod. Performance ofboth type backer rod materials was found to be similar in that the behavior of the sealants wasessentially the same with each back-up. Sealants subjected to dynamic movement will not beadversely affected by adhesion to DENVER FOAM® due to the low surface strength and shearingcapabilities of the backer rod.
6. NON-STAINING: DENVER FOAM® is white to beige in color, odorless, and non-staining.
7. INERT: DENVER FOAM® is physically and chemically compatible with virtually every sealant.
8. COMPRESSIBLE: 25% nominal at 1 to 11⁄2 p.s.i. (70 to 100 gms./sq.cm) with an approximate densityof 4# to 6# per cubic foot (64Kg to 96 Kg per cubic meter).
9. FLEXIBILITY: DENVER FOAM® has been found to handle much easier than closed-cell polyethyl-ene due to it’s greater flexibility, resulting in faster application and usage, without size change, in awider range of joint width.
10. LESS INVENTORY INVESTMENT: Because each size of DENVER FOAM® can be used in such awide range of joint widths, the amount of dollar investment to carry a full inventory is greatly reduced.
11. LESS STORAGE SPACE REQUIREMENT: Due to compression packaging of DENVER FOAM®,considerably less storage space is required to carry an adequate inventory.
12. EASE OF JOB CLEAN-UP: Since DENVER FOAM® is packaged in easily-disposable polyethylenebags, the problem of container disposal is reduced to a minimum.
13. EASE OF SHIPMENT: Since DENVER FOAM® is packaged in compact, compressed, light-weightmaster bags, ease of hauling sufficient material to the job in a minimum of space is greatly facilitated.Also, emergency shipments of a substantial amount of backer rod can be made very easily by UnitedParcel Service or other small package carriers.
14 WIDE TEMPERATURE RANGE: DENVER FOAM® has been used successfully at temperatures of-70°F. (-57°C.) up to intermittent temperatures of 500°F. (260°C.). It has been determined by an in-dependent testing laboratory that DENVER FOAM® subjected to 300°F. (149°C.) for six weeks willstart to deteriorate, but since hot-pour sealants cool quite rapidly, DENVER FOAM® IS AN EXCELL-ENT HOT-POUR SEALANT BACKER ROD.
ADVANTAGES (continued):
15. NON-WICKING: DENVER FOAM® does not wick water, and is non-hygroscopic. DENVER FOAM®
does not absorb water readily under field conditions. If wetted during a rainstorm, the DENVERFOAM® is usually dry enough to caulk when the sidewalls of the joint are dry enough to apply thesealant. It is recommended that DENVER FOAM® should be reasonably clean, relatively dry, andfree of contamination at the time of caulking application.
16. FREIGHT SAVING ADVANTAGE: Since DENVER FOAM® is a highly resilient open-cell polyure-thane foam, it can be compressed substantially to increase the density (weight per cubic foot ormeter) enough to take advantage of the lowest available freight rate, thereby offering MAXIMUMFREIGHT SAVINGS without damaging the product.
The above picture clearly shows the two-stage compression packaging.
The Back Row contains 10 full sized Master Bags approximately 17" x 31" (43 cm x 79 cm) weighing about16 pounds (7.3 Kg.) each. The middle row contains 10 Master Bags semi-compressed and contained in areinforced paper sleeve of about one-half the original size. The compressed bale in the foreground contains10 semi-compressed sleeves further compressed to a size of approximately 18" x 21" x 36" (46 cm x 53 cmx 91 cm) having a total weight of approximately 175 pounds (79 Kg.), and a resultant density ofapproximately 22 pounds per cubic foot (357 Kg. per cubic meter). Upon releasing the restrainingpackaging, the DENVER FOAM® rapidly returns to it’s original size without any detrimental effect to thematerial. EXTREME CAUTION SHOULD BE USED WHEN CUTTING STEEL RETAINING BANDS.
NOTE: The compressed bale in the foreground may contain all the same diameter, or mixed diameters ofMaster Bags including Master Bags of MINI-BAGS as indicated on back page.
1. PRODUCT NAME
DENVER FOAM®
2. MANUFACTURER
Backer Rod Mfg. Inc.4244 N. BroadwayDenver, CO 80216Phone: (800) 595-2950
(303) 308-0363Fax: (303) 308-0393Web: www.backerrod.com
3. PRODUCT DESCRIPTION
Basic Use: DENVER FOAM® is abacker rod used as a backing forelastomeric and other applied caulk-ing sealants. DENVER FOAM® con-trols the depth and amount ofsealant required.
DENVER FOAM® also forms thecorrect hour glass shape of sealant.
Specific Uses: For use inexpansion/construction joints inconcrete and precast concrete walls,floors, partitions, bridge construc-tion, parking decks, curtain walls,glazing, log home construction,highway construction, and pave-ment maintenance.
Both hot and cold installationscan be installed with DENVERFOAM® backer rod.
Physical Properties:
• Density: 1.7 pcf. ASTM D-1622• Tensile: 25 psi. ASTM D-1623• Moisture Absorption: .024% by
volume. ASTM C-509• Out Gassing: None• Temperature Service Range: -60°F
to +500°F. ASTM D-5249-95• Auto Ignition: 700-800°F• Elongation: 90% ASTM D-3574• Air Flow: 90%. ASTM D-3574• Compression Set: less than 5%
(after 80% compression for 30days). ASTM D-3574
5. INSTALLATION
DENVER FOAM® should beinstalled in expansion/constructionjoints free from all contaminants,loose materials, and dry and freefrom frost. Install under 25% com-pression to offer a good toolingbase. Systems can be installed with-out the fear of out-gassing associat-ed with polyethylene.
DA
TATECH
Backer Rod Mfg. Inc.
Backer Rod Mfg. Inc. January 2009
GLAZING EXPANSION JOINTS LOG CONSTRUCTION
GLASS
SEALANT
SEALANT
SEALANT
DENVERFOAM® DENVER
FOAM®DENVERFOAM®
Open cell DENVER FOAM® hasan advantage allowing air to reachboth sides of sealant offering afaster and more uniform cure. Thisis especially true for one part non-sag sealants. DENVER FOAM® canalso be used in floor joints with self-leveling sealants or in traffic areaswhere additional support isrequired.
Limitations: Whatever restric-tion the sealant manufacturer placeson their product, the same will applyto DENVER FOAM®.
Composition and Materials:
DENVER FOAM® is continuouslengths of flexible, round, fabricatedopen cell polyurethane. Yellow incolor and available in a wide rangeof diameters.
Packaging: Both mini bags andmaster bags are compressed intosuper bundles for economical ship-ping and storage. Each individualsize is color coded for identification.
4. TECHNICAL DATA
DENVER FOAM® is chemicallyinert and will resist oil, gasoline andmost solvents. Material is odorlessand will not stain. The open cell con-struction eliminates the out-gassingand cold flow problem associatedwith closed cell polyethylene backerrods. Plus sealant has benefits of atwo-sided cure.
6. AVAILABILITY AND COST
DENVER FOAM® is marketednationally and internationally by ourdistributors. For name, address, andtelephone number of your nearestdistributor please contact us at:
Backer Rod Mfg. Inc.
4244 N BroadwayDenver, CO 80216Phone: (800) 595-2950Phone: (303) 308-0363Fax: (303) 308-0393Web: www.backerrod.com
DENVER FOAM® is available inother sizes, shapes, and colors.Please contact Backer Rod Mfg. Inc.for availability on custom madeitems.
7. WARRANTY
Unless otherwise agreed to inwriting, product is sold without war-ranty. In no case will Backer RodMfg. Inc. be liable for incidental orconsequential damages on anyproduct.
8. MAINTENANCE
No maintenance is needed.
9. TECHNICAL SERVICES
Contact Backer Rod Mfg. Inc.for technical guidance or specialproject engineering designs anddrawings.
DENVER FOAM® PACKAGING INFORMATION
Backer Rod Mfg. Inc.4244 N BroadwayDenver, CO 80216Phone: (800) 595-2950Phone: (303) 308-0363Fax: (303) 308-0393Web: www.backerrod.com
Backer Rod Mfg. Inc. January 2009
ColorCode Diameter Ft/per
Mini BagFt/per
Master BagFt/per
Super Bundle
Clear
Red
Orange
Green
Yellow
Blue
3/8" (10mm)
5/8" (16mm)
7/8" (22mm)
11/8" (29mm)
11/2" (38mm)
2" (51mm)
200' (61m)
100' (30m)
100' (30m)
75' (23m)
40' (12m)
25' (7.6m)
3,600' (1097m)
2,000' (608m)
1,050' (319m)
600' (182m)
350' (106m)
200' (61m)
36,000' (10972m)
20,000' (6090m)
10,500' (3,192m)
6,000' (1,824m)
3,500' (1,064m)
2,000' (608m)
Material Safety Data Sheet
May be used to comply with
OSHA�s Hazard Communication Standard,
29 CFR 1910.1200. Standard must be
consulted for specific requirements.
U.S. Department of LaborOccupational Safety and Health Administration
(Non-Mandatory Form)
Form Approved
OMB No. 1218-0072
IDENTITY (As Used on Label and List)
DENVER FOAM
Note: Blank spaces are not permitted. If any item isnot applicable, or no information is available, thespace must be marked to indicate that.
Section I
Manufacturer�s Name
BACKER ROD MFG., INC.
Address (Number, Street, City, State and ZIP Code)
4244 No. BROADWAY
DENVER, COLORADO
80216
Emergency Phone Number
920-406-4000
Telephone Number for Information
1-800-595-2950
Date Prepared
August 12, 2002
Signature of Preparer (optional)
Section II � Hazard Ingredients/Identity Information
Hazardous Components (Specified ChemicalIdentity; Common Name(s)
OSHAPEL
ACGIHTLV
Other LimitsRecommended % (optional)
DOES NOT APPLY (DNA)
NO HAZARDOUS INGREDIENTS
THIS IS THE SAME FOAM USED IN BEDDING, FURNITURE, AUTOMOBILESEATS, CARPET PADDING & WINTER CLOTHING
�POLYURETHANE FOAM� (FLEXIBLE)
Section III � Physical/Chemical Characteristics
Boiling Point
Vapor Pressure (mm Hg.)
Vapor Density (AIR = 1)
Solubility in Water
NO
Specific Gravity (H2O = 1)
Melting Point
Evaporation Rate(Butyl Acetate = 1)
SOLID
DNA
DNA
.038
DNA
DNA
Appearance and Odor
ROUND DIA/IN COILS (LITE YELLOW, OR BLACK) SOLID MATERIAL NOVAPORS OR ODOR
Section IV � Fire and Explosion Hazard Data
Flash Point (Method Used) 600 � 650 F Flammable Limits N/A LEL UEL
Extinguishing Media
H2O � CO2 OR DRY CHEMICAL EXTINGUISHERS
Special Fire Fighting Procedures
DRENCHING OR SOAKING WITH WATER, FIRE FIGHTINGPERSONNEL SHOULD USE FULL MASK & SELF CONTAINEDBREATHING APPARATUS
Unusual Fire and Explosion Hazards
NONE
(Reproduce locally) OSHA 174, Sept. 1985
Section V � Reactivity Data
Stability
HazardousPolymerization
Unstable
Stable
May Occur
Will NotOccur
Conditions to Avoid
NONE
DO NOT STORE NEAR OPEN FLAMES
Conditions to Avoid
NONE DNA
DIA
X
Incompatibility (Materials to Avoid) PRODUCT DEGRADED BY STRONG ALKALI ORACID & SWOLLEN BY SOLVENTS
Hazardous Decomposition or Byproducts
NONE AT TEMPERATURE PRODUCT IS USED
Section VI � Health Hazard Data
Route(s) of Entry:
Health Hazards (Acute and Chronic)
NONE DNA
Signs and Symptoms of Exposure
DNA
Medical ConditionsGenerally Aggravated by Exposure DNA
Emergency and First Aid Procedures
Inhalation? DNA Skin? DNA Ingestion? DNA
Carcinogenicity: NTP?
NONEIARC Monographs?
NONEOSHA Regulated?
NONE
Section VII � Precautions for Safe Handling and Use
Steps to B Taken in Case Material is Released or Spilled
DNA SOLID PRODUCT
Waste Disposal Method
DNA
Precautions to Be Taken in Handling and Storing
KEEP AWAY FROM OPEN FLAME
Other Precautions
NONE
Section VIII � Control Measures
Respiratory Protection (Specify Type) SOLID MATERIAL NO VAPORS
Protective Gloves NONE NEEDED
Other Protective Clothing or Equipment
NONE
Work/Hygienic Practices
NONE
Eye Protection NONE NEEDED
Ventilation Local Exhaust NONE NEEDED
Mechanical (General) NONE
Special DNA
Other DNA
Page 2 * U.S.G.P.O.: 1986 - 491 - 529/45775
DENVER FOAM®Engineering & Technical Bulletin
Open Cell Polyurethane Backer Rod
HOT POUR TESTED TO + 500°F Date: October 25, 2004
Manufacturer - Backer Rod Mfg. Inc., 4244 N. Broadway, Denver, CO 80216
Trade Name - DENVER FOAM®
Prescribed Tests - ASTM D 5249 – 95U.S. Dept. of Commerce National Institute of Standards
Description - Denver Foam® is a backer rod serving as a backing for elastomeric,hot applied and other applied caulking sealants. Denver Foam®
controls the depth and amount of sealant required.
Specific Uses - For use in expansion/construction joints in concrete and pre-castconcrete walls, floors, partitions bridge construction, parking decks,curtain walls, glazing, log home construction, highway construction,and pavement maintenance.
Recommendation - WIDE TEMPERATURE RANGE: Denver Foam® can be usedsuccessfully at temperatures of -70° (-57°C) up to intermittenttemperatures of 500°F (260°C). Denver Foam® is an excellent hotpour sealant backer rod. Tested under ASTM 5249-95 at +500°F,Denver Foam® showed no signs of deterioration and actuallyexpanded in the joint. Cross linked (hot type) backer rods shrink andbreak down at approximately 180°F.
Denver Foam® is chemically inert and will resist oil, gasoline, jet fueland most solvents. Material is odorless and will not stain. The opencell construction eliminates the out-gassing problems associated withclosed cell cross linked (hot type) backer rods. Denver Foam® is100% non out-gassing.
Easy installation: Denver Foam® can be compressed as much as 80%of its original diameter. This allows the applicator to use fewer sizesin varying and/or twisting joint widths.
“Setting Standards for the Industry”
Backer Rod Mfg. Inc.4244 N. Broadway • Denver, CO 80216
800 595 2950 • 303 308 0363 • Fax 303 308 0393
www.backerrod.com
1. PRODUCT NAME
MILE HIGH FOAM®
2. MANUFACTURER
Backer Rod Mfg. Inc.4244 N. BroadwayDenver, CO 80216Phone: (800) 595-2950
(303) 308-0363Fax: (303) 308-0393Web: www.backerrod.com
3. PRODUCT DESCRIPTION
Basic Use: MILE HIGH FOAM®
is a backer rod used as a backing forelastometric and other appliedsealants. MILE HIGH FOAM® con-trols the depth of sealant required.
Specific Uses: MILE HIGHFOAM® is a soft, resilient, polyethyl-ene backer rod used as a backupmaterial for construction joints andapplications that require sealants.MILE HIGH FOAM® performs as adepth control for most known coldapplied sealants. Sealants will notadhere to MILE HIGH FOAM®; nobond breaker is required.
Composition and Materials:
MILE HIGH FOAM® is a round,black, resilient, extruded closed cellpolyethylene backer rod with awater resistant outer skin. It is com-patible with most known coldapplied sealants such as urethane,silicone, acrylic, butyl, polysulfides,latex, and chinking sealants.
Specific Uses Include:
• Expansion joints• Highway joints• Glazing• Log home chinking• Parking Decks• Curtain Walls• Coping joints• Isolation joints• Temporary joint seal
Limitations: MILE HIGHFOAM® should be installed with aroller or blunt, flat-sided tool. Pleasefollow sealant manufacturer specifi-cations for recommended sealantwidth and depth ratio. For bestresults, do not puncture, fold oroverly stretch the product. MILEHIGH FOAM® is made with a water-resistant outer skin. Where moistureresistance is important, care shouldbe taken not to puncture this outersurface skin.
Packaging: MILE HIGH FOAM®
is available in a wide variety ofdiameters in 3 carton sizes:Mini Carton 18" x 18" x 13"Standard Carton 18" x 18" x 30"Super Carton 131⁄2" x 131⁄2" x 73"All cartons are UPS-able. For quanti-ty per carton and rod size per joint,see charts on reverse side.
4. TECHNICAL DATA
MILE HIGH FOAM® is chemi-cally inert and will resist gasoline,oil, and most solvents. Product willnot stain or adhere to sealants.
Physical Properties:
Density: 1.25-2lbs./cu. ft.
Moisture Absorption: Less than1% by volume
Temperature Range: -40°F to200°F
5. INSTALLATION
Joint or opening must be freeof all contaminants, loose materials,dry and free of frost. Select correctrod size for joint width. With a bluntinstrument or roller, seat rod todepth recommended by sealantmanufacturer.
DA
TATECH
Backer Rod Mfg. Inc.
Backer Rod Mfg. Inc. January 2009
GLAZING EXPANSION JOINTS LOG CONSTRUCTION
GLASS
MLE HIGH FOAM® MLE HIGH FOAM®
MLE HIGHFOAM®
SEALANT
SEALANT
SEALANT
6. AVAILABILITY AND COST
MILE HIGH FOAM® is marketednationally and internationally by ourdistributors. For name, address, andtelephone number of your nearestdistributor please contact us at:
Backer Rod Mfg. Inc.
4244 N BroadwayDenver, CO 80216Phone: (800) 595-2950Phone: (303) 308-0363Fax: (303) 308-0393Web: www.backerrod.com
MILE HIGH FOAM® is availablein other sizes, shapes, and colors.Please contact Backer Rod Mfg. Inc.for availability on custom madeitems.
7. WARRANTY
Unless otherwise agreed to inwriting, product is sold without war-ranty. In no case will Backer RodMfg. Inc. be liable for incidental orconsequential damages on anyproduct.
8. MAINTENANCE
No maintenance is needed.
9. TECHNICAL SERVICES
Contact Backer Rod Mfg. Inc.for technical guidance or specialproject engineering designs anddrawings.
MILE HIGH FOAM® – PACKAGING
MILE HIGH FOAM® – JOINT WIDTH TO ROD SIZE
Rod Size Mini Carton18" x 18" x 13"
Standard Carton18" x 18" x 30"
Super Carton131⁄2" x 131⁄2" x 73"
1⁄4"
3⁄8"
1/2"
5/8"
3/4"
7/8"
1"
1-1/4"
1-1⁄2"
2"
2-1/2"
3"
4"
3⁄16"
1⁄4"
3⁄8"
1/2"
5/8"
3/4"
1⁄4"
3⁄8"
1⁄2"
5/8"
3/4"
1"
1"
1-1/8"
1-5/8"
2"
2-1/2"
3 1/2"
1-1⁄4"
1-1/2"
2"
2-1/2"
3"
4"
2500 LF/Ctn
1400
800
550
400
6400 LF/Ctn
3600
2500
1550
1100
850
550
400
MFG’D in 6' lengths
420 LF 70 pcs
252 LF 42 pcs
156 LF 26 pcs
102 LF 17 pcs
54 LF 9 pcs
Joint Width Rod Diameter Joint Width Rod Diameter
Backer Rod Mfg. Inc.4244 N BroadwayDenver, CO 80216Phone: (800) 595-2950Phone: (303) 308-0363Fax: (303) 308-0393Web: www.backerrod.com
Backer Rod Mfg. Inc. January 2009
Material Safety Data Sheet
May be used to comply with
OSHA�s Hazard Communication Standard,
29 CFR 1910.1200. Standard must be
consulted for specific requirements.
U.S. Department of LaborOccupational Safety and Health Administration
(Non-Mandatory Form)
Form Approved
OMB No. 1218-0072
IDENTITY (As Used on Label and List)
MILE HIGH FOAMNote: Blank spaces are not permitted. If any item isnot applicable, or no information is available, thespace must be marked to indicate that.
Section I
Manufacturer�s Name
BACKER ROD MFG., INC.
Address (Number, Street, City, State and ZIP Code)
4244 No. BROADWAY
DENVER, COLORADO
80216
Emergency Phone Number
920-406-4000
Telephone Number for Information
1-800-595-2950
Date Prepared
August 12, 2002
Signature of Preparer (optional)
Section II � Hazard Ingredients/Identity Information
Hazardous Components (Specified ChemicalIdentity; Common Name(s)
OSHAPEL
ACGIHTLV
Other LimitsRecommended % (optional)
DOES NOT APPLY (DNA) NO HAZARDOUS INGREDIENTS
�POLYURETHANE FOAM� (FLEXIBLE)
NOT HAZARDOUS AS DEFINED IN 29 CFR 1910.1200 (OCCUPATIONAL SAFETY
AND HEALTH STANDARDS FOR GENERAL INDUTRY 29 CODE OF FEDERAL
REGULATIONS, SECTION 1910, PART 1200)
Section III � Physical/Chemical Characteristics
Boiling Point
DNA
Vapor Pressure (mm Hg.)
DNA
Vapor Density (AIR = 1)
DNA (SOLID MATERIAL)
Solubility in Water
Specific Gravity (H2O = 1)
ASTM D 792
Melting Point ASTM D 1525VICAT SOFTENING POINT
Evaporation Rate(Butyl Acetate = 1) DNA
DNA
DNA
DNA
2LBS/CUFT
196°F
DNA
NOT WATER SOLUBLE
Appearance and Odor
ROUND DIA./IN COILS OR SIX FOOT PIECES, BLACK IN COLOR,SOLID MATERIAL, NO VAPORS
Section IV � Fire and Explosion Hazard Data
Flash Point (Method Used)
341 F ASTM D 1929Flammable Limits
AUTO IGNITION343°F
LEL
DNAUEL
DNA
Extinguishing Media
WATER SPRAY, DRY CHEMICAL, FOAM OF CARBONDIOXIDE
Special Fire Fighting Procedures
WATER SPRAY FROM FOGGING NOZZLE IS RECOMMENDED
Unusual Fire and Explosion Hazards
(Reproduce locally) OSHA 174, Sept. 1985
Section V � Reactivity Data
Stability
HazardousPolymerization
Unstable
Stable
YES
May Occur
Will NotOccur
Conditions to Avoid
SOFTENED BY HYDROCARBONS ANDCHLORINATED HYDROCARBONS
AVOID OPEN FLAMES
Conditions to Avoid
ATTACKED BY OXIDIZING AGENTS SUCH ASNITRIC ORPERCHLORIC ACID AND FREE HALOGENS
X
XX
Incompatibility (Materials to Avoid)ZYLENE
Hazardous Decomposition or Byproducts
CARBON, CARBON MONOXIDE, CARBON DIOXIDE VAPORS MAY BEPRODUCED BY THERMAL DECOMPOSITION
Section VI � Health Hazard Data
Route(s) of Entry:
Health Hazards (Acute and Chronic)
Signs and Symptoms of Exposure
NO APPLICABLE INFORMATION FOUND
Inhalation? DNA Skin? DNA Ingestion? DNA
Carcinogenicity: NONE NTP? NO IARC Monographs? NO OSHA Regulated? NO
MAY BURN AT OR ABOVE FLASH POINT, AIRBORNE DUST MAYEXPLODE IF IGNITED. SEE NATIONAL FIRE PROTECTION BULLETIN 654
NO APPLICABLE INFORMATION FOUND
Section VII � Precautions for Safe Handling and Use
Steps to Be Taken in Case Material is Released or Spilled
PRACTICE GOOD HOUSEKEEPING. RECOIL PRODUCT ON SPOOLS.
Waste Disposal Method
THIS MATERIAL IS NOT A RCA HAZARDOUS WASTE. DISPOSE OF IN
ACCORDANCE WITH STATE AND LOCAL REGULATIONS (RCA: RESOURCECONSERVATION ACT 1976)
Precautions to Be Taken in Handling and Storing
AVOID OPEN FLAME OR IGNITION CONDITIONS
Other Precautions
NO APPLICABLE INFORMATION FOUND
Section VIII � Control Measures
Respiratory Protection (Specify Type) DNA
Protective Gloves DNA
Other Protective Clothing or Equipment NONE REQUIRED
Work/Hygienic Practices NO APPLICABLE INFORMATION FOUND
Eye Protection DNA
Ventilation Local Exhaust XX
Mechanical (General) NONE
Special DNA
Other DNA
Page 2 * U.S.G.P.O.: 1986 - 491 - 529/45775
Medical Conditions
Generally Aggravated by Exposure NO APPLICABLE INFORMATION FOUND
Emergency and First Aid Procedures NO APPLICABLE INFORMATION FOUND
Backer Rod Mfg. Inc.Reply to: ❑ 4244 N. Broadway • Denver, CO 80216
Phone 303-308-0363 • Fax 303-308-0393
HIDDEN DANGER
There exists today many high occupancy buildings which claim to meet fire codesthat actually may have some very serious �Hidden Dangers.� These hidden dangers are inthe expansion/construction joints. The fire stopping material used in these joints are almostalways covered over with some type of sealant.
The expansion/construction joints do exactly as the name infers, they open andclose as a result of temperature changes. These changes occur generally once a day.Warmer temperatures close the joint and cooler temperatures open them. To have aneffective joint packing material it must be capable of moving within the joint, and remainin place.
There are three well-known fire blocking backup materials used in expansion/construction joints. Ceramic fibers, mineral wool and Ultra Block®. All three are capableof blocking fires in fire rated joints when they are installed with standard constructionsealants. However, only when they are initially installed.
To be an effective fire blocking joint packing material the product must remain inand completely seal the entire joint for a great number of years.
The structural or movement testing of Ultra Block® was done by HauserLaboratories in Boulder, Colorado. The results were impressive. The test was run on a±50% joint movement. The tests were run on all three products: ceramic fiber, mineralwool and Ultra Block®. Both the ceramic fiber and the mineral wool failed in less than 600cycles or 1.6 years. Ultra Block® tested for 28,000 cycles without failure, which represents76 years of service. There was no physical change in the Ultra Block® at the end of thetest. When mineral wool and ceramic fibers are subjected to cycling at a ±50%, they fail.When the joint closes the joint packing compresses, when the joint opens mineral wool andceramic fibers do not recover. The ceramic fiber and the mineral wool actually fell out ofthe test apparatus. The Ultra Block® retained its resiliency and looked exactly the same asit did before it was tested.
Unfortunately, in the past, on a number of occasions, the packing materials used inperimeter joints, had already fallen out of the joint when there happened to be a fire. Inmany instances human lives were lost. The �HIDDEN DANGER� was exposed.
Ultra Block® would not have let this happen, as it would have still had the jointsealed from fire. Do not let this �HIDDEN DANGER� cost more lives.
1. PRODUCT NAME
ULTRA BLOCK®
Mechanical Expansion and Construction Joint fire stopping System: 2-Hour, 3-Hour,
4-Hour Fire Rated
2. MANUFACTURER
Backer Rod Mfg. Inc.4244 N. BroadwayDenver, CO 80216Phone: (800) 595-2950
(303) 308-0363Fax: (303) 308-0393Web: www.backerrod.com
3. PRODUCT DESCRIPTION
ULTRA BLOCK® is a pre-engi-neered, patented, flexible textilefiberglass roll material with a fiber-glass matt facing, containingapproximately 30% by weight unex-panded vermiculite.
Specific Uses: ULTRA BLOCK®,when used together with anapproved sealant, provides a 2-Hour, 3-Hour, or 4-Hour fire ratedjoint system as designated bydesign configuration, which is capa-ble of withstanding ± 50% expan-sion and contraction. Most sealantmanufacturers in the United Stateshave tested one or more of theirsealants in a UL® classified ULTRABLOCK® system ranging in joint sizefrom 1⁄2" up to 7". Approved sealantmanufacturers include:
• Dow Corning• General Electric• Tremco Vulkem• C R Lawrence• Lymtal• Pecora• Quaker• Sika• Sonneborn• Specified Technologies Inc• Nelson
4. Benefits
Resiliency: To be an effectivefire blocking joint packing system, aproduct must remain highly resilientand must completely fill the movingjoint for a great number of years. Inmost packed and caulked joints,examination of the resiliency of theforming material is difficult to check,as the material is covered up withsealant. Many joint packing materi-als, such as mineral wood andceramic fiber, are not designed tohandle joint movement and may fallout or slump in the joint when sub-jected to continuous joint expansionand contraction. Under fire situa-tions, the fire blocking materialmust be in the same condition aswhen it was installed, meaning thatthe material must completely fill thevoid in order to block a fire. ULTRABLOCK® has a unique patented,hinged design and composition thatremains highly resilient under themost extreme conditions.
Structurally Rested: The struc-tural testing of ULTRA BLOCK® wasperformed by Hauser Laboratories.The test was run on a ± 50% jointmovement. Mineral wool andceramic fiber joint packing materialswere also tested. The joints werepacked in the fully open positionand were under the 25% joint sidecompression. The test ran continu-ously until either failure occurred orthe test was terminated. Failure ofboth the mineral wool and ceramicfiber materials occurred in under600 cycles, or 1.6 years. The ULTRABLOCK® successfully performed forover 28,000 cycles without failure orloss of resiliency, representing 76years of service at one cycle perday!
Fire Stopping: ULTRA BLOCK®
has been proven to withstand thetest of time in joint expansion andcontraction. The ULTRA BLOCK®
system also has a very unique fea-ture not present in either mineralwool or ceramic fiber material.ULTRA BLOCK® contains vermicu-lite, which expands when exposedto heat. As the vermiculite expandsit produces thousands of reflectiveshields that reflect heat back awayfrom the expansion joint. Whenexposed to fire on the caulked anduncaulked side there is no passageof destructive heat to the sealantbead on the opposite side.
ULTRA BLOCK® is a fire block-ing material in the fire rated jointsthat will be in place if and whenneeded. It is the only fire rated jointsystem today, which gives this pro-tection using standard constructionsealants! In addition, it does notrequire metal cover plates as somesystems do.
Composition and Materials: AllULTRA BLOCK® systems are manu-factured in accordance with projectrequirements. ULTRA BLOCK® ismanufactured in various widths andthicknesses, depending on the jointwidth, and sold in rolls.
DA
TATECH
Backer Rod Mfg. Inc.
Backer Rod Mfg. Inc. January 2009
5. EASY INSTALLATION
ULTRA BLOCK® requires nocutting, fitting, or fabrication.Simply open the bag, unwind theroll, fold in half with the matt sidefacing outward, compress and slideit in the joint to required depth.Apply sealant per manufacturersinstructions.
When joining ends of rolls, cuteach end at a 45° angle, alternatingcuts so that the folded over ULTRABLOCK® forms an interlocking v-shape. (See drawing below.)
SPLICING
6. TECHNICAL INFORMATION
All ULTRA BLOCK® systemsare covered with a nominal sealant(see list of manufacturers). Systemdesigns can range from 1-Hour, 2-Hour, 3-Hour or 4-Hour fire ratingsand joint widths from 1⁄2" up to 7"wide.
ULTRA BLOCK® systems allowthe mechanical expansion/construc-tion joint to function and fulfill thepurpose it was designed for, MOVE-MENT.
Testing of ULTRA BLOCK® foruse in expansion/construction jointswas conducted at UnderwritersLaboratories®, Northbrook, Illinois.Tests were performed to the full-scale, 180 sf surface area, and eachjoint tested was 12 ft. long. Our test-ing also included the hose streamportion. The full scale testing earnedus classifications by UL® for use inhorizontal and vertical joints pluscompliance with all major codes inthe United States.
Seismic testing of ULTRABLOCK® systems was performed bythe University of California-SanDiego. The seismic ”earthquake“simulation test was a joint projectbetween the US and Japan. ULTRABLOCK® performed perfectly underthe most severe conditions.
Specific Compliance: ULTRABLOCK® Systems comply withand/or have been tested under thefollowing standards and buildingcodes:
• UBC – Uniform Building Code• BOCA – Building Officials and
Code Administrators Interna-tional
• SBCCI – Southern BuildingCode Congress International
• City of Los Angeles BuildingCode
• UL 2079 – UL Standard forSafety Tests for Fire Resistanceof Building Joint Systems
• UL 263-92 – UL Standard forSafety Fire Tests of BuildingConstruction and Materials
• UL 1479 – UL Standard forSafety Fire Test of ThroughPenetration Firestops
• UL 723 – UL Standard forSafety Test for Surface BurningCharacteristics of BuildingMaterials
• ASTM E119 – Method for FireTests of Building Constructionand Materials
• ASTM E814 – Methods of FireTests of Through PenetrationFire Stops
• ASTM E84 – Test Method forSurface Burning Character-istics of Building Materials
• ASTM E136 – Test Method forBehavior of Materials in aVertical Tube Furnace at 750°C
• ASTM E90 – Test Method forLaboratory Measurement ofAirborne Sound TransmissionLoss of Building Partitions
• ASTM E1399 – Test Method ofCyclic Movement and Measur-ing the Minimum and Maxi-mum Joint Widths of Architec-tural Joint System
• ASTM C719 – Test Method forAdhesion and Cohesion ofElastometric Joint SealantsUnder Cyclic Movement
• ASTM C920 – Specification forElastometric Joint Sealants
• NFPA 251 – Fire Test of BuildingConstruction Materials
• NFPA 255 – Burning Characterof Building Materials
7. WARRANTY
Unless otherwise agreed to inwriting, product is sold without war-ranty.
SIZING CHART
PACKAGING INFORMATION
JOINTWIDTH*
ULTRABLOCK®
THICKNESS
ULTRA BLOCK®
WIDTH2-HOUR
FIRE RATING
CONFIGURATION
ULTRA BLOCK®
WIDTH3-HOUR
FIRE RATING
CONFIGURATION
ULTRA BLOCK®
WIDTH4-HOUR
FIRE RATING
CONFIGURATION
1⁄2"3⁄4"1"
1-1⁄2"
3⁄8"1⁄2"3⁄4"1"
3⁄8"1⁄2"3⁄4"1"
70 LF60 LF40 LF30 LF
12601080
700600400300
630540360270
420360240180
280240160120
21018012090
NO. 16"6"6"6"
NO. 18"8"8"8"
NO. 112"12"12"12"
NO. 2*2"2"
3-1⁄2"3-1⁄2"
NO. 2*4"4"4"4"
NO. 2*6"6"6"6"
*Configuration NO. 2 requires ULTRA BLOCK® on both sides of joint opening. The above table representsthe requirement for only one side of the joint opening. Please call us for information regarding joint widthsof 2" or greater.
ULTRABLOCK®
THICKNESS*
2"WIDE
LFPERBAG
3-1⁄2"WIDE
LFPERBAG
4"WIDE
LFPERBAG
6"WIDE
LFPERBAG
8"WIDE
LFPERBAG
12"WIDE
LFPERBAG
ROLLLENGTH
*Please call us for packaging information on sizes over 1" thick.
Knauf Fiber Glass GmbH
MATERIAL SAFETY DATA SHEETHealth Hazard 1
Fire Hazard 0
Physical Hazard 0
Personal Protection B
HMIS RATING NFPA RATING
001
←
SECTION I - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION
SECTION II - COMPOSITION/INFORMATION ON INGREDIENTS
SECTION III - HAZARDS IDENTIFICATION
Product: Ultrablock Fire Proof Insulation MSDA Number: 1011
Trade Designations: Backer rod insulation material
Manufacturer: Knauf Fiber Glass GmbH Date Issued: August 1, 2003
Address: One Knauf Drive Product Stewardship Support Line: 317-398-4434, X8102
Shelbyville, IN 46176-1496 24 hr Emergency (Chemtrec) Phone: 800-424-9300
Chemical Name CAS Number % TLV PEL
Fibrous Glass (Textile) 65997-17-3 60-70 10 mg/m3 (PNOC) 15 mg/m3 (PNOR)
Phenol formaldehyde resin (cured) 68585-23-9 16-20 None None
Vermiculite Ore 01318-00-9 25-30 10 mg/m3 (PNOC) 15 mg/m3 (PNOR)
Black Mat Facing NA 1-2 None None
Key: TLV = ACGIH, 8 hr. time weighted average (TWA); PEL = OSHA permissible exposure limit.
PNOC = Particulates Not Otherwise Classified (ACGIH - Inhalable)
PNOR = Particulates Not Otherwise Regulated (OSHA - Total dust)
Emergency Overview: Airborne particulate which may be created during cutting is considered nuisance dust whichshould be minimized through the use of good work practices and adequate ventilation. Acrid smoke may be generatedin a fire. Exposure to high temperatures may release airborne concentrations of thermal decomposition productssuch as carbon monoxide, especially in enclosed or poorly ventilated areas.
HMIS Rating: Health: 1 Fire: 0 Reactivity: 0 Protection: B
Primary Routes of Entry: Via particulate to the lungs and respiratory system and airborne fibers to the skin and eyes.
Primary Target Organs: Lungs, respiratory system, skin and eyes.
Potential Health Effects:
Inhalation: Irritating to the mucous membranes and respiratory tract.
Skin Contact: Irritation and redness due to excessive exposure.
Eye Contact: A mechanical irritant which can cause moderate to severe eye irritation.
Ingestion: Non-hazardous when ingested. Potentially a mild irritant to the GI tract if excessive quantity is
ingested.
Medical Conditions Aggravated by Exposure: Pre-existing chronic upper respiratory and lung diseases such as,
but not limited to, bronchitis, emphysema, and asthma. Skin disease such as dermatitis.
Carcinogenicity: This product is manufactured using textile grade glass filaments which are classified by IARC as
group 3 (Unclassifiable as to carcinogenicity to humans). It is not classified by NTP or OSHA.
Issued: August 1, 2003 Page 1 of 4
2Trade Name: Knauf Ultrablock Fire Proof Insulation MSDS Number: 1011
SECTION IV - FIRST AID MEASURES
Inhalation: Remove to fresh air. Drink water to clear throat and blow nose to evacuate dust. If coughing and irritationdevelop, call a physician.
Eye Contact: Flush with large amounts of water until irritation subsides, as least 15 minutes. See a physician ifirritation persists.
Skin Contact: Normal good personal hygiene practices. Wash with mild soap and warm water after each exposure.
Ingestion: Emergency procedures not normally required. May be a temporary irritant to the GI system.
SECTION V - FIREFIGHTING MEASURES
NFPA Rating: Health: 1 Fire: 0 Reactivity: 0 Other: 0
Extinguishing Method: Use water, foam, dry chemical or carbon dioxide.
Special Firefighting Procedures: Wear self-contained breathing apparatus and protective clothing. Dense smoke maylimit visibility in enclosed areas.
Fire or Explosion Hazards: Product is not highly flammable however, in a major fire product will be consumedcausing dense acrid smoke.
SECTION VI - ACCIDENTAL RELEASE MEASURES
Clean-up Procedures: Pick up or shovel material into waste container taking care to minimize dust and fibergeneration. Vacuum clean-up is preferred. If sweeping is required use a dust suppressant.
Personal Precautions: If dusty conditions exist, wear a face mask approved for use with dusts such as 3M 8210, N95or equivalent.
Environmental Precautions: This product is not regulated under RCRA Hazardous Waste Regulations. May bedisposed in landfill. Comply with federal, state and local regulations.
SECTION VII - HANDLING AND STORAGE
Storage Requirements: Store in dry area. Keep area clean. Vacuum clean dust. Use a dust suppressant if sweeping isnecessary.
Special Sensitivity or Incompatibility: Hydrofluoric acid will react with and dissolve glass.
Handling Precautions: Assure proper respiratory protection if dust potential exceeds PEL/TLV.
SECTION VIII - EXPOSURE CONTROLS/PERSONAL PROTECTION
Engineering Controls: Maintain sufficient mechanical or natural ventilation to assure fiber concentrations remainbelow PEL/TLV. Use local exhaust if necessary. Power equipment should be equipped with properly designed dustcollection devices.
Respiratory Protection: When over PEL/TLV wear an approved face mask such as 3M 8210, N95 or equivalent, toprevent against inhalable glass wool fibers. Concentrations of fibers that exceed the recommendations of the maskmanufacturer will need a higher level of respiratory protection, such as a half mask respirator with appropriate dustfilters.
Issued: August 1, 2003 Page 2 of 4
3Trade Name: Knauf Ultrablock Fire Proof Insulation MSDS Number: 1011
Eye Protection: Wear safety glasses with side shields, goggles or face shield when handling, installing or fabricatingto protect eyes against dust and fibers.
Skin Protection (clothing): Long-sleeved, loose fitting clothes and head covering are recommended. Wash workclothes separately from other clothing, towels and linens to prevent fiber migration. Rinse washer thoroughly.
SECTION IX - PHYSICAL AND CHEMICAL PROPERTIES
Physical Form: Yellow fibrous product, slight phenol formaldehyde odor.
Melting Point: >1300°F Specific Gravity: Variable
Solubility in Water: Insoluble Pure/Mixture: Mixture
SECTION X - REACTIVITY
Stability: This is a stable, non-reactive product.
Hazardous Decomposition Products: Thermal decomposition of the resin may include carbon dioxide, carbonmonoxide, formaldehyde, carbon particulate and traces of hydrogen cyanide.
SECTION XII - DISPOSAL CONSIDERATIONS
Waste Disposal Method: This product is not regulated under RCRA Hazardous Waste Regulations. May be disposedin landfill. If unsure, contact the local office of the USEPA, your local public health department or the local landfillregulators.
SECTION XIII - TRANSPORTATION INFORMATION
US DOT Shipping Name: Not regulated DOT Label: None UN/NA Number: None
SECTION XI - TOXICOLOGICAL/ECOLOGICAL INFORMATION
LD50: N/Av LC50: N/Av
Toxicological Hazards: This product is manufactured with textile grade glass filaments which are classified by IARCas group 3 (Unclassifiable as to carcinogenicity to humans). It is not classified by NTP or OSHA.
Ecological Hazards: No data exists for this product.
Teratogenicity, Multagenicity, other Reproductive Effects: None known
SECTION XIV - REGULATORY INFORMATION
OSHA Status: This product is considered hazardous under OSHA criteria.
TSCA/CEPA Status: All components of this product are included in the TSCA and CEPA Chemical Inventories.
CERCLA Reportable Quantity: N/Ap
Issued: August 1, 2003 Page 3 of 4
SARA Title III:
Section 302 Extremely Hazardous: This product contains no extremely hazardous substances as defined andlisted in section #302.
Section 311/312 Hazard Categories: Irritation and redness due to excessive exposure.
Section 313 Toxic Chemicals: This product does not contain substances which are reportable under Section 313.
California Safe Drinking Water and Toxic Enforcement Act (Prop. 65): Not regulated.
Canada (WHMIS): This product is not controlled under Canadian WHMIS regulations.
4Trade Name: Knauf Ultrablock Fire Proof Insulation MSDS Number: 1011
SECTION XV - APPROVALS
Reason for Issue: New MSDS Revision: New Approval Date: August 1, 2003
Prepared by: CCG, Inc. Supersedes Date: None
SECTION XVI - DISCLAIMER
As of the date of this document, the foregoing information is believed to be accurate and is provided in good faith tocomply with applicable federal and state laws. However, no warranty or representation of law or fact, with respect tosuch information, is intended or given.
Issued: August 1, 2003 Page 4 of 4
ULTRA BLOCK®
SYSTEMSEngineering & Technical Bulletin
File No. Ultra Block Configuration Designs
“Setting Standards For The Industry”
Backer Rod Mfg. Inc.
ALL WE NEED ARE THE ABC’S OF YOUR PROJECTAND WE WILL FURNISH YOU OUR DRAWING
ASTM E119 Fire Tested by Underwriters Laboratories - All Horizontal & Vertical Joints.ASTM E1399 Movement Tested by Hauser Research - 50% movement - 28,000openings and closing.Seismic Tested-Drift Tested by University of California San Diego for U.S. Governmenton a National Science Foundation project.
Configuration # 1
“A” = Joint Width“B” = Concrete Thichness“C” = Hourly Fire Rating
of StructureConfiguration # 2
Configuration # 3
4244 N. Broadway • Denver, CO 802161-800-595-2950 • 303-308-0363 • Fax 303-308-0393
Backer Rod Mfg. Inc.4244 N. Broadway • Denver, CO 80216 • Toll Free 1-800-595-2950 • Phone 303-308-0363 • Fax 303-308-0393
Page I
CODE COMPLIANCE U.S.A.“ULTRA BLOCK®”, THANKS TO YOU, HAS FULFILLED OUR CONSTRUCTIONINDUSTRY’S NEEDS FOR A
2 HOUR _______ 3 HOUR _______ 4 HOUR _______
FIRE RATED, MOVEMENT CERTIFIED MECHANICAL, EXPANSION, CONSTRUCTIONJOINT SYSTEM.
“A” FIRE TESTEDUNDERWRITERS LABORATORIES, NORTH BROOK, ILLINOIS, FILE #R-13729,FULL SCALE FIRE TEST 14' X 17', 180 SQ. FT. FIRE SLAB. JOINT LENGTHSWERE 12 LF. ALL TESTING INCLUDED THE HOSE STREAM TEST. THANKS TOUNDERWRITERS LABORATORIES’ GUIDANCE, THE FULL SCALE TESTINGGAVE US TOTAL COMPLIANCE WITH ASTM E 119, NFPA 251, UL-263 FOR ALLEXPANSION JOINT DESIGNS.
“B” STRUCTURAL TESTEDHAUSER RESEARCH, BOULDER, COLORADO, LISTED IN THE BUILDINGSTANDARDS DIRECTORY (ICBO EVALUATION SERVICE INC.) NUMBER TL-140 AS A STRUCTURAL TEST AGENCY, NONE OF THE FIRE TEST AGENCIESHAD ESTABLISHED THEMSELVES IN THE STRUCTURAL-MOVEMENTFIELD. HAUSER TESTED OUR ULTRA BLOCK® SYSTEMS AT A MOVEMENTOF ±50% FOR A MINIMUM OF 10,000 OPENINGS AND CLOSINGS. HAUSERRAN OUR LAST TEST TO 28,775 CYCLES.
THIS IS NOW ASTM 1399.
ULTRA BLOCK® WAS THE FIRST, AND CONTINUES TO BE THE ONLY,PRODUCT WITH ENGINEERED MOVEMENT CAPABILITIES DESIGNED INPRODUCT.
THE FIRE TESTING PER ASTM E 119 AND STRUCTURAL TESTING TO ASTM E1399 VERIFIES OUR:
CODE COMPLIANCE U.S.A.BOCA _____ SBCCI _____ UBC _____ U.S. CORPS OF ENGS. ______
✓ ✓ ✓
✓ ✓ ✓ ✓
Page II
“C” MATERIAL SAFETY DATA SHEETULTRA BLOCK® MSDS LISTS PRODUCT AS NON-CARCINOGENIC
#1 NOT LISTED (NTP)#2 NOT CLASSIFIABLE (IARC)#3 NOT REGULATED (OSHA)
“D” THE ELASTOMERIC SEALANTS TESTED IN ULTRA BLOCK® SYSTEMSARE AN IMPORTANT PART OF OUR DESIGN. ASTM C-920 ESTABLISHES THEELASTICITY OF THE SEALANT. THE SEALANT MANUFACTURER DICTATESTHE TYPE SEALANT YOU USE (LATEX, URETHANE, SILICONE), AND THESELECTION YOU CHOOSE BASED ON JOINT DESIGN AND LOCATION.
EVERY MAJOR SEALANT MANUFACTURER IN THE UNITED STATES HASTESTED ONE OR MORE OF THEIR SEALANTS IN A UL CLASSIFIED ULTRABLOCK® SYSTEM. ALPHABETICAL LISTING FOLLOWS:
CARLISLE COATINGS & WATER PECORAC.R. LAURENCE CO., INC. SIKADOW CORNING SONNEBORNGENRAL ELECTRIC SPECIFIED TECHNOLOGIES, INC.LYMTAL INT. ISO-FLEX TREMCO VULKEMNELSON
THE SEALANT’S MOST IMPORTANT FUNCTION DOES NOT OCCUR UNTIL AFIRE. AT THAT TIME IT BECOMES THE SMOKE AND TOXIC FUME BARRIER.
“E” SEISMIC TESTINGSIKA CORPORATION LISTED THEIR SIKALEX 15-LM SEALANT IN AN ULTRABLOCK® DESIGN IN A ICBO EVALUATION REPORT. WHEN THE UNIVERSITY OFCALIFORNIA, SAN DIEGO RECEIVED A CONTRACT FROM U.S. GOVERNMENTAND JAPAN ON A MASONRY RESEARCH PROJECT NAMED TCCMAR SIKA’SULTRA BLOCK® EXPANSION JOINT DESIGN WAS SPECIFIED. THE ULTRABLOCK® DESIGN WITH SIKAFLEX 15-LM BASED ON ICBO REPORT WASSPECIFIED AND WORKED SO WELL ON THEIR 2-STORY STRUCTURE THAT WEWERE SPECIFIED AND TESTED IN THE PROJECT’S 5-STORY STRUCTURE. THEPROJECT WAS DESIGNED TO EVALUATE THE PERFORMANCE OF EXPANSIONJOINTS BETWEEN SHEAR WALLS.
BACKER ROD MFG. HAS CONTINUED ITS TESTING WITH COMPANIES LIKECONSTRUCTION RESEARCH LAB, MIAMI, FLORIDA IN THEIR HURRICANE TEST.WE CONTINUE TO OFFER, AT NO CHARGE, ENGINEERING SERVICES ANDDESIGN FOR PROJECTS WHERE SPECIAL OR CUSTOM DESIGNS ARE NEEDED.
THE STAFF AT BACKER ROD MFG. LOOKS FORWARD TO THE OPPORTUNITY TO WORKWITH YOU ON YOUR FUTURE PROJECTS.
ULTRA BLOCK®
SYSTEMSEngineering & Technical Bulletin
U.S.A. CODE COMPLIANCE FIRE/STRUCTURAL/SEISMIC
Manufacturer - Backer Rod Mfg. Inc., 4244 N. Broadway, Denver CO 80216
Trade Name - ULTRA BLOCK® (U.S. Patent 4,756,945)
Product - Fire stop filler systems for mechanical expansion/construction joints, bothhorizontal and vertical.
Pertinent Code -
Prescribed Tests - ASTM E 119 - Structural Fire Test (14'x17' full scale test panel)ASTM E 1399 - Movement - 10,000 openings & closings (at ±50%)
Laboratories - Underwriters Laboratories Inc.Hauser Research LaboratoriesUniversity of California -San Diego
Test Report(s) - Fire Test - Underwriters Laboratories Inc.Master File R-13729 (ASTM E 119) 2-hour, 3-hour, 4-hour fire rating in jointsup to 7" wide on one of these configurations (UL 263 - NFPA 251):
Structural Test - Hauser Research Inc.Accelerated fatigue test 90-1326 ASTM E 1399, 50% movement capability.
Seismic Test - University of California - San DiegoTCCMAR masonry research (no ASTM to date).
Description - ULTRA BLOCK® is a heat expandable fire stopping material. Product is a 3 lb.density textile fiberglass blanket containing 32% by weight unexpandedvermiculite. All systems are designed to serve as the fire protection in allhorizontal and vertical mechanical, expansion/construction joints. ULTRABLOCK®’s resiliency under compression allows expansion joints to move andcompensate for the ongoing everyday expansion and contraction whileremaining in place to perform to its fire rated design function, if and whenneeded.
Recommendation - ULTRA BLOCK® is to be installed in fire rated structures. Joint must be cleanand dry. Sealant selection is based on joint location and must have adhesionand cohesion capabilities to contain the smoke and toxic fumes created byfire. Manufacturer will furnish (at no charge) system design drawings forcontractor to present to Code authority.
“Setting Standards For The Industry”
Backer Rod Mfg. Inc.4244 N. Broadway • Denver, CO 80216
1-800-595-2950 • 303-308-0363 • Fax 303-308-0393
INSTALLATION INSTRUCTIONS
ULTRA BLOCK(R)
IMPORTANT! READ THE FOLLOWINGCAREFULLY BEFORE PROCEEDING
1. Select the ULTRA BLOCK(R) bag containing the proper width and thickness for the joints tobe packed and caulked.
2. Remove roll of ULTRA BLOCK(R) from the package. The end of each roll is glued slightly toprevent unwinding during transit. Pull this glued end loose and the ULTRA BLOCK(R) is ready forinstallation.
3. Referring to the installation diagrams, make sure the printed side of the ULTRA BLOCK(R) isagainst the surface to be packed. The groove in the ULTRA BLOCK(R) is to be positioned directlyover the center of the expansion joint. This is shown in the diagram in Step 1 of Configurations 1-2and assures proper folding so both edges of the ULTRA BLOCK(R) match to give the propercaulking surface. This is shown in Step 3 of Configurations 1 and 2.
Should the groove not be exactly in the middle of the expansion joint when it is insertedresulting in an uneven edge match up, the ULTRA BLOCK(R) can be easily pulled out andreinserted properly.
4. Multi-Layer Designs
Follow installation as outlined above. However, “Multi-Layer” Designs are seated under handcompression. Align pad edges, finish closing, compress and seat. Make sure pad surfaces on side tobe caulked are smooth. Flat faced wood trowel may be used to seat ULTRA BLOCK(R) to caulkingdepth.
In cases where wider ULTRA BLOCK(R) is used it may be necessary during packing of thejoint to put some tension on the ULTRA BLOCK(R) to remove any folds that may develop. Thistension need not be much but sufficient to eliminate such folds.
Splicing of two pieces of ULTRA BLOCK(R) together in an expansion joint is easilyaccomplished by cutting material in flat position. Using 45 degree angles and overlapping as shown,assures a tight fit with no voids or gaps.
Over for drawings . . . .
INSTALLATION PROCEDURES FOR ULTRA BLOCK® SYSTEMCONFIGURATIONS 1 AND 2
GROOVE
ULTRA BLOCK®
PRINTED SIDE PRINTED SIDE
EXPANSION JOINTBUILDING PANELS
ULTRA BLOCK®
GROOVE
BUILDING PANELSEXPANSION JOINT
ULTRA BLOCK®
GROOVE
INSERTING TOOL
PRINTED SIDEULTRA BLOCK®
ULTRA BLOCK®PRINTED SIDE
INSERTING TOOL
SEALANT
ULTRABLOCK®
ULTRA BLOCK®
SEALANT
ULTRA BLOCK®
INSERTING TOOL
PRINTED SIDE
SEALANT
PROPER FOLDING OF MULTI-LAYER ULTRA BLOCK®
ULTRA BLOCK®
EXPANSION JOINTS
BLDG. PANELSPROPER SPLICING
FOLDED (SIDE VIEW)INSTALLED
FLAT
BOARD OF
BUILDING AND SAFETY COMMISSIONERS
___
MARSHA L. BROWN PRESIDENT
VAN AMBATIELOS VICE-PRESIDENT
VICTOR H. CUEVAS HELENA JUBANY
ELENORE A. WILLIAMS ___
CITY OF LOS ANGELES CALIFORNIA
ANTONIO R. VILLARAIGOSA
MAYOR
DEPARTMENT OF BUILDING AND SAFETY 201 NORTH FIGUEROA STREET
LOS ANGELES, CA 90012 ____
ANDREW A. ADELMAN, P.E.
GENERAL MANAGER
RAYMOND CHAN EXECUTIVE OFFICER
____
RR 25037 Page 1 of 2
LADBS G-5 (Rev.6/08) AN EQUAL EMPLOYMENT OPPORTUNITY - AFFIRMATIVE ACTION EMPLOYER
Backer Rod Manufacturing, Inc. RESEARCH REPORT: RR 25037 4244 North Broadway (CSI #07920) Denver, Colorado 80216
Expires: June 1, 2010 Attn: Bill Bergel Issued Date: June 1, 2009 (800) 595-2950 Code: 2008 LABC GENERAL APPROVAL - Backer Rod Manufacturing, Inc., Two-Hour to Four-Hour Fire-Resistive Joint Sealing Systems for Walls and Floors DETAILS The joint sealing system consists of Ultra-Block® backer material used in conjunction with sealant material. Ultra block consists of textile glass fibers, impregnated with un-expanded vermiculite used as a fire blocking backer material in construction joints. The approval is subject to the following conditions:
1. Joints located in exterior locations (i.e., subject to the weather) shall use sealants specified in this report which are approved by a separate research report for weather protection (see RR 24637 and RR 24950 for Dow Corning 795 and General Electric Co. Silpruf, respectively).
2. Installation of the joint sealing systems shall be in accordance with the attached details
and the manufacturer's instructions. Copies of the design details and the installation instructions along with this research report shall be available at each job site.
3. The minimum thickness of the concrete floor or wall shall comply with Table 207.1 (2)
and 207.1 (3), respectively, of the 2008 Los Angeles City Building Code for the required fire-resistive rating.
4. Components of the system shall be delivered to the job site in sealed containers bearing
Underwriters Laboratories, Incorporated labels.
Backer Rod Manufacturing, Inc. RE: Two-Hour to Four-Hour Fire-Resistive Joint Sealing Systems
RR 25037 Page 2 of 2
5. Block walls utilizing this joint sealing system shall be fully grouted.
6. All assemblies in this report shall be limited to construction joints to accommodate
thermal movement only. DISCUSSION The approval is based upon fire tests conducted in accordance with UBC Standard No. 7-1 (ASTM E119). Addressee to whom this Research Report is issued is responsible for providing copies of it, complete with any attachments indicated, to architects, engineers and builders using items approved herein in design or construction which must be approved by Department of Building and Safety Engineers and Inspectors. This general approval of an equivalent alternate to the Code is only valid where an engineer and/or inspector of this Department has determined that all conditions of this approval have been met in the project in which it is to be used. YEUAN CHOU, Chief Engineering Research Section 201 N. Figueroa St., Room 880 Los Angeles, CA 90012 Phone - 213-202-9812 Fax - 213-202-9942 BG:elcm RR25037/MSWord2003 R05/21/09 1A1/1A2/1C1/1C2/6A4/703
Attachments: 37 Sheets of Design Details.
ULTRA BLOCK®
SYSTEMSEngineering & Technical Bulletin
File: FLAT THICKNESS Joint Width: (up to) 1/2"
“Setting Standards For The Industry”
Backer Rod Mfg. Inc.4244 N. Broadway • Denver, CO 80216
1-800-595-2950 • 303-308-0363 • Fax 303-308-0393
ULTRA BLOCK®
SYSTEMSEngineering & Technical Bulletin
File: FLAT THICKNESS Joint Width: (up to) 3/4"
“Setting Standards For The Industry”
Backer Rod Mfg. Inc.4244 N. Broadway • Denver, CO 80216
1-800-595-2950 • 303-308-0363 • Fax 303-308-0393
ULTRA BLOCK®
SYSTEMSEngineering & Technical Bulletin
File: FLAT THICKNESS Joint Width: (up to) 1"
“Setting Standards For The Industry”
Backer Rod Mfg. Inc.4244 N. Broadway • Denver, CO 80216
1-800-595-2950 • 303-308-0363 • Fax 303-308-0393
ULTRA BLOCK®
SYSTEMSEngineering & Technical Bulletin
File: FLAT THICKNESS Joint Width: (up to) 1-1/2"
“Setting Standards For The Industry”
Backer Rod Mfg. Inc.4244 N. Broadway • Denver, CO 80216
1-800-595-2950 • 303-308-0363 • Fax 303-308-0393
ULTRA BLOCK SYSTEMS
File: BUILT UP CONFIGURATIONS FOR JOINT WIDTHS 2 INCHES AND GREATER
2 Hour Built Up Assemblies
Joint Configuration A B C 2.0 1 3/8" x 9" 1.375 9 3.5 2.5 1 7/8" x 10" 1.875 10 3.5 3.0 2 3/8" x 10" 2.375 10 3.5 4.0 3 3/8" x 11" 3.375 11 3.5 4.5 3 1/2" x 13" 3.5 13 4 5.0 4 3/8" x 13" 4.375 13 4 5.5 4 3/8" x 14" 4.375 14 4 6.0 4 1/2" x 14" 4.5 14 4 7.0 5 3/8" x 15" 5.375 15 4
3 Hour Built Up Assemblies Joint Configuration A B C
2.0 1 7/8" x 10" 1.875 10 4 2.0 2 1/2" x 10" 2.5 10 4 2.5 2 3/8" x 11" 2.375 11 4 3.0 2 1/2" x 11" 2.5 11 4 4.0 3 3/8" x 14" 3.375 14 5 4.5 3 3/8" x 15" 3.375 15 5 5.0 4 3/8" x 15" 4.375 15 5 5.5 4 3/8" x 16" 4.375 16 5 6.0 5 3/8" x 16" 5.375 16 5 6.5 5 3/8" x 17" 5.375 17 5 7.0 5 1/2" x 17" 5.5 17 5
4 Hour Built Up Assemblies Joint Configuration A B C
2.0 1 3/8" x 14" 1.375 14 6 2.5 1 7/8" x 15" 1.875 15 6 3.0 2 3/8" x 15" 2.375 15 6 4.0 3 3/8" x 16" 3.375 16 6
Engineering & Technical Bulletin
®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
Click on the UL system number to be directed to the design detail
UL SYSTEM DESIGN MATRIX
2 HOUR SYSTEMS Joint Width Sealant Floors Walls Head of Wall Floor to Wall
DOW CORNING 790, 795 FF-S-0009 WW-S-0013 HW-S-0077 FW-S-0016 DOW CORNING NS PSS FF-D-0031 WW-D-0034
GE PENSIL 100, 300 FF-S-0013 WW-S-0017 HW-S-0075 FW-S-0014 DYNATROL II, AC-20FTR, 864 FF-S-0006 WW-S-0010 HW-S-0072 FW-S-0011
ISO-FLEX 880GB, 881, 830 FF-S-0008 WW-S-0012 HW-S-0073 FW-S-0012 RHODIA FR-71 FF-S-0012 WW-S-0016
SIKA 2CNS, 15LM FF-S-0007 WW-S-0011 HW-S-0076 FW-S-0015
0.75"
CRL M64 FF-S-0026 WW-S-0031 DYNAFLEX, DYNATRED FF-S-0017 WW-S-0021 2.0"
SONOLASTIC NP2 FF-S-0016 WW-S-0020 HW-S-0065 GE PENSIL 300 FF-S-1009 WW-S-1010 HW-S-1014 FW-S-1018
ISO-FLEX 880 PREMOLD FF-S-1006 WW-S-1007 4.0" EGS NELSON CLK FF-S-1032 WW-S-1034 HW-S-1013 FW-S-1017
7.0" PECORA AC-20 FTR FF-S-2002 WW-S-2008 PENETRATION PECORA AC-20 FTR C-AJ-1093
3 HOUR SYSTEMS Joint Width Sealant Floors Walls Head of Wall Floor to Wall
2.0" ISO-FLEX 880GB, 881, 830 FF-S-0018 WW-S-0022 HW-S-0074 FW-S-0013 3.0" PECORA DYNATROL II FF-S-1007 WW-S-1008
4 HOUR SYSTEMS Joint Width Sealant Floors Walls Head of Wall Floor to Wall
GE PENSIL 300 FF-S-0020 WW-S-0023 HW-S-0070 FW-S-0009 2.0" SIKA 2CNS FF-S-0024 WW-S-0027 HW-S-0071 FW-S-0010
PECORA AC-20 FTR FF-S-1010 WW-S-1012 SONOLASTIC NP2 FF-S-1013 WW-S-1016 HW-S-1012 4.0" EGS NELSON CLK FF-S-1036
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-D-0031
August 01, 2002 Assembly Rating – 2 Hr
Nominal Joint Width – ¾ In. Class II Movement Capabilities – 25% Compression or Extension
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
2. Joint System – Max width of the joint (at time of installation of the joint system) is ¾ in. The joint
system is designed to accommodate a max 25 percent compression or extension from its installed width. The joint system shall consist of the following:
A. Forming Material* - A nom 6 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. For joint openings up to ½ in. in width, the forming material shall be a min of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. Forming material to be recessed from top surface of floor as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with top surface of the floor.
DOW CORNING CORP – DOW CORNING NS PARKING STRUCTURE SEALANT
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0006
August 29, 1995 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum
Configuration No. 1 1 2B 2A
Configuration No. 2
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following: A. Forming Material* - For joint openings up to ½ in. in width, the forming material shall be a min
of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. In Configuration No. 1, a nom 6 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from top surface of floor as required to accommodate the required thickness of fill material. In Configuration No. 2, a nom 2 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from each surface of the floor as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - In Configuration No. 1, min ½ in. thickness of fill material
applied within the joint, flush with the top surface of the floor. PECORA CORP – DYNATROL II or 864 SILICONE
Fill, Void or Cavity Material* - In Configuration No. 2, min ½ in. thickness of fill material applied within the joint, flush with each surface of the floor.
PECORA CORP – DYNATROL II or AC-20 FTR
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0007
August 11, 1995 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum
Configuration No. 1 1 2B 2A
Configuration No. 2
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150) pcf structural concrete.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following: A. Forming Material* - For joint openings up to ½ in. in width, the forming material shall be a min
of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. In Configuration No. 1, a nom 6 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from top surface of floor as required to accommodate the required thickness of fill material. In Configuration No. 2, a nom 2 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from each surface of the floor as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - In Configuration No. 1, min ½ in. thickness of fill material
applied within the joint, flush with the top surface of the floor. SIKA CORPORATION – SIKAFLEX 2CNS or 15LM
Fill, Void or Cavity Material* - In Configuration No. 2, min ½ in. thickness of fill material applied within the joint, flush with each surface of the floor.
SIKA CORPORATION – SIKAFLEX 2CNS
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0008
June 17, 1997 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following:
A. Forming Material* - A nom 6 in. width of forming material shall be folded in half and firmly
packed into joint opening as a permanent form. The thickness of the forming material is dependant upon the width of the joint. For joint openings up to ½ in. in width, the forming material shall be a min of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. Forming material to be recessed from top surface of floor as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with top surface of floor.
LYMTAL INTERNATIONAL INC – ISO-Flex 880-GB, ISO-Flex 881 and ISO-Flex 830
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0009
March 22, 1996 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following:
A. Forming Material* - A nom 6 in. width of forming material shall be folded in half and firmly
packed into joint opening as a permanent form. The thickness of the forming material is dependant upon the width of the joint. For joint openings up to ½ in. in width, the forming material shall be a min of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. Forming material shall be recessed from top surface of floor as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with top surface of floor.
DOW CORNING CORP – DOW CORNING 790 or 795
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0012
September 14, 2001 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following:
A. Forming Material* - For joint openings up to ½ in. in width, the forming material shall be a
min of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. A nom 2 in. width of forming material shall be folded in half and firmly packed into joint opening as a permanent form. Forming material to be recessed from each surface of floor as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with each surface of floor.
RHODIA SILICONES – FR-71
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0013
November 18, 2008 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum
1 2B 2A
1. Floor Assembly – Min 4 ½ in. (114 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
2. Joint System – Max width of the joint is ¾ in. (19 mm). The joint system shall consist of the
following:
A. Forming Material* - A nom 6 in. (152 mm) width of forming material shall be folded in half and firmly packed into joint opening as a permanent form. The thickness of the forming material is dependant upon the width of the joint. For joint openings up to ½ in. (13 mm) in width, the forming material shall be a min of 3/8 in. (10 mm) thick. For joint openings up to ¾ in. (19 mm) in width, the forming materials shall be a min of 1/2 in. (13 mm) thick. Forming material to be recessed from top surface of floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with top surface of floor.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 100, PENSIL 300 or PENSIL 300 S/L SEALANTS SPECIFIED TECHNOLOGIES INC – PENSIL 300, PENSIL 300 S/L, SPECSEAL SERIES SIL300 or SPECSEAL SERIES SIL300SL SEALANTS
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0016
April 15, 2009 Assembly Rating – 2 Hr
Joint Width – 2 In. Maximum
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
2. Joint System – Max width of the joint is 2 in. The joint system shall consist of the following:
A. Forming Material* - A nom 9 in. width of forming material shall be folded in half and firmly
packed into joint opening as a permanent form. Forming material to be recessed from top surface of floor as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with top surface of floor.
BASF CONSTRUCTION CHEMICAL LLC – SONOLASTIC NP 2
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0017
August 11, 1995 Assembly Rating – 2 Hr
Joint Width – 2 In. Maximum
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
2. Joint System – Max width of the joint is 2 in. The joint system shall consist of the following:
A. Forming Material* - A nom 9 in. width of forming material shall be folded in half and firmly
packed into joint opening as a permanent form. Forming material to be recessed from top surface of floor as required to accommodate the required thickness of fill material. See manufacturers installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Prior to the installation of the caulk material into the joint the interior surfaces of the concrete slab shall be treated with the primer as specified below. The primer shall be applied in accordance with the installation instructions accompanying the primer. Min ½ in. thickness of fill material applied within the joint, flush with top surface of floor.
PECORA CORP – DYNAFLEX (installed in conjunction with Pecora Primer P-200, Parts A and B) or DYNATRED (installed in conjunction with Pecora Primer P-75)
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0026
April 25, 1997 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum
Configuration No. 1 1 2B 2A
Configuration No. 2
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following: A. Forming Material* - For joint openings up to ½ in. in width, the forming material shall be a min
of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. In Configuration No. 1, a nom 6 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from top surface of floor as required to accommodate the required thickness of fill material. In Configuration No. 2, a nom 2 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from each surface of the floor as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - In Configuration No. 1, min ½ in. thickness of fill material
applied within the joint, flush with the top surface of the floor. In Configuration 2, min ½ in. thickness of fill material applied within the joint, flush with each surface of the floor.
C R LAURENCE – CRL M64
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-1006
June 17, 1997 Assembly Rating – 2 Hr
Joint Width – 4 In. Maximum
1 2C 2D
2B
5 1/
4" M
IN
1. Floor Assembly – Reinforced lightweight or normal weight (100-150 pcf) structural concrete
having a min thickness of 5-1/4 in. at stepped-edges receiving Fill, Void or Cavity Material (Item 2C).
2. Joint System – Max width of the joint is 4 in. The joint system shall consist of the following:
A. Fill, Void or Cavity Material* - (Not Shown) – Prior to the installation of the Forming Material (Item 2B), a nom 1/2 in. bead of caulk is applied along the edges of the joint, 2 in. below the top surface of floor.
RECTORSEAL – METACAULK 950 B. Forming Material* - A nom 14 in. width of forming material shall be folded in half and firmly
packed into opening as a permanent form. Forming material to be recessed 1-1/4 in. from top surface of floor. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK® C. Fill, Void or Cavity Material* - Prior to the installation of the premold into the joint, the
stepped-surface of the concrete wall shall be treated with 2 component LymTal International, Inc. Primer 10 in accordance with the installation instructions accompanying the primer. Premold, max 12 in. wide min 3/4 in. deep, centered in the joint, such that it is spaced 1/2 in. from each stepped edge of concrete floor. When installed, the premold shall be flush with the top surface of the floor.
LYMTAL INTERNATIONAL INC – ISO-FLEX 880 PREMOLD D. Fill, Void or Cavity Material* - Min 3/4 in. thickness of fill material applied within the joint,
flush with top surface of floor. LYMTAL INTERNATIONAL INC – ISO-FLEX 980 Nosing
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-1009
November 18, 2008 Assembly Rating – 2 Hr
Joint Width – 4 In. Maximum
1 2B 2A
1. Floor Assembly – Min 4 ½ in. (114 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
2. Joint System – Max width of the joint is 4 in. (102 mm). The joint system shall consist of the
following: A. Forming Material* - Max 11 in. (279 mm) width of forming material shall be folded in half and
packed into joint opening as a permanent form. Forming material to be recessed from top surface of the floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with top surface of the floor.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 or PENSIL 300 S/L SEALANTS SPECIFIED TECHNOLOGIES INC – PENSIL 300, PENSIL 300 S/L, SPECSEAL SERIES SIL300 or SPECSEAL SERIES SIL300SL SEALANTS
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-1032
March 31, 2005 Assembly Rating – 2 Hr
Joint Width – 4 In. Maximum
1 2B 2A
1. Floor Assembly – Min 4 ½ in. (114 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
2. Joint System – Max width of the joint is 4 in. (102 mm) The joint system shall consist of the
following:
A. Forming Material* - Min 11 in. (279 mm) width of forming material shall be folded in half, compressed min 40 percent in thickness and friction fitted into opening as a permanent form. Forming material to be recessed from top surface of floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material*- Sealant - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with top surface of floor.
EGS NELSON FIRESTOP – CLK S/L (Self Leveling) Caulk or CLK N/S (Non-Sag) Caulk
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-2002 August 29, 1995
Assembly Rating – 2 Hr Joint Width – 7 In. Maximum
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
2. Joint System – Max width of the joint is 7 in. The joint system shall consist of the following:
A. Forming Material* - A nom 15 in. width of forming material shall be folded in half and firmly
packed into joint opening as a permanent form. Forming material to be recessed from top surface of floor as required to accommodate the required thickness of fill material. See Manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with top surface of floor.
PECORA CORP – AC-20 FTR
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-D-0034
January 07, 2009 Assembly Rating – 2 Hr
Nominal Joint Width – ¾ In. Class II Movement Capabilities – 25% Compression or Extension
(Limited to Fire Exposure on Interior Face Only)
1 2B 2A
1. Wall Assembly – Min 4-1/2 in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Joint System – Max width of the joint (at time of installation of the joint system) is 3/4 in. The joint
system is designed to accommodate a max 25 percent compression or extension from its installed width. The joint system shall consist of the following:
A. Forming Material* - For joint openings up to ½ in. in width, the forming material shall be a min of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. A nom 6 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with exterior face of wall.
DOW CORNING CORP – DOW CORNING NS PARKING STRUCTURE SEALANT
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0010
August 29, 1995 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum (Configuration No. 1 Limited to Fire Exposure on Interior Face Only)
Configuration No. 1
1 2B 2A
Configuration No. 2
1 2B 2A
1. Wall Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturers.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following: A. Forming Material* - For joint openings up to ½ in. in width, the forming material shall be a min
of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. In Configuration No. 1, a nom 6 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material. In Configuration No. 2, a nom 2 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from each surface of the wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - In Configuration No. 1, min ½ in. thickness of fill material
applied within the joint, flush with exterior face of wall. PECORA CORP – DYNATROL II or 864 SILICONE
B1. Fill, Void or Cavity Materials* - In Configuration No. 2, min ½ in. thickness of fill material applied within the joint, flush with each surface of the wall.
PECORA CORP – DYNATROL II or AC-20 FTR
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0011
July 29, 1995 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum (Configuration No. 1 Limited to Fire Exposure on Interior Face Only)
Configuration No. 1
1 2B 2A
Configuration No. 2
1 2B 2A
1. Wall Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150) pcf structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturers.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following: A. Forming Material* - For joint openings up to ½ in. in width, the forming material shall be a min
of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. In Configuration No. 1, a nom 6 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material. In Configuration No. 2, a nom 2 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from each surface of the wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - In Configuration No. 1, min ½ in. thickness of fill material
applied within the joint, flush with exterior face of wall. SIKA CORPORATION - SIKAFLEX 2CNS or 15LM
B1. Fill, Void or Cavity Material* - In Configuration No. 2, min ½ in. thickness of fill material applied within the joint, flush with each surface of the wall.
SIKA CORPORATION - SIKAFLEX 2CNS
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0012
July 02, 1997 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum (Limited to Fire Exposure on Interior Surface Only)
1 2B 2A
1. Wall Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturers.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following:
A. Forming Material* - A nom 6 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. The thickness of the forming material is dependant upon the width of the joint. For joint openings up to ½ in. in width, the forming material shall be a min of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. Forming material to be recessed from exterior surface of wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint,
flush with exterior face of wall. LYMTAL INTERNATIONAL INC – ISO-FLEX 880-GB, ISO-FLEX 881 and ISO-FLEX 830
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0013
July 29, 1995 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum (Limited to Fire Exposure on Interior Surface Only)
1 2B 2A
1. Wall Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturers.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following:
A. Forming Material* - For joint openings up to ½ in. in width, the forming material shall be a min of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. A nom 6 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with exterior face of wall.
DOW CORNING CORP – DOW CORNING 790 or 795
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0016
September 14, 2001 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum
1 2B 2A
1. Wall Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturer’s.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following:
A. Forming Material* - For joint openings up to ½ in. in width, the forming material shall be a
min of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. A nom 2 in. width of forming material shall be folded in half and firmly packed into joint opening as a permanent form. Forming material to be recessed from each surface of wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with each surface of wall.
RHODIA SILICONES – FR-71
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0017
November 19, 2008 Assembly Rating – 2 Hr
(Limited to Fire Exposure on Interior Surface Only) Joint Width – ¾ In. Max
1 2B 2A
1. Wall Assembly – Min 4 ½ in. (114 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturers.
2. Joint System – Max width of the joint is ¾ in. (19mm). The joint system shall consist of the following:
A. Forming Material* - A nom 6 in. (152 mm) width of forming material shall be folded in half
and packed into opening as a permanent form. The thickness of the forming material is dependant upon the width of the joint. For joint openings up to ½ in. (13 mm) in width, the forming material shall be a min of 3/8 in. (10 mm) thick. For joint openings up to ¾ in. (19 mm) in width, the forming materials shall be a min of 1/2 in. (13 mm) thick. Forming material to be recessed from exterior surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with exterior face of wall.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 100 or PENSIL 300
SPECIFIED TECHNOLOGIES INC – PENSIL 100, PENSIL 300 or SPECSEAL SERIES SIL300 SEALANTS
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0020
April 15, 2009 Assembly Rating – 2 Hr
Joint Width – 2 In. Maximum (Limited to Fire Exposure on Interior Face Only)
1 2B 2A
1. Wall Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturers.
2. Joint System – Max width of the joint is 2 in. The joint system shall consist of the following:
A. Forming Material* - A nom 9 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint,
flush with exterior face of wall. BASF CONSTRUCTION CHEMICAL LLC – SONOLASTIC NP 2
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0021
July 29, 1995 Assembly Rating – 2 Hr
Joint Width – 2 In. Maximum (Limited to Fire Exposure on Interior Face Only)
1 2B 2A
1. Wall Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturers.
2. Joint System – Max width of the joint is 2 in. The joint system shall consist of the following:
A. Forming Material* - A nom 9 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Prior to the installation of the caulk material into the joint the interior surfaces of the concrete slab shall be treated with primer as specified below. The primer shall be applied in accordance with the installation instructions accompanying the primer. Min ½ in. thickness of fill material applied within the joint, flush with exterior face of wall.
PECORA CORP – DYNAFLEX (installed in conjunction with Pecora Primer P-200, Parts A and B) or DYNATRED (installed in conjunction with Pecora Primer P-75).
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0031
April 25, 1997 Assembly Rating – 2 Hr
Joint Width – ¾ In. Maximum
Configuration No. 1 1 2B 2A
Configuration No. 2
1 2B 2A
1. Wall Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturers.
2. Joint System – Max width of the joint is ¾ in. The joint system shall consist of the following: A. Forming Material* - For joint openings up to ½ in. in width, the forming material shall be a min
of 3/8 in. thick. For joint openings up to ¾ in. in width, the forming materials shall be a min of 1/2 in. thick. In Configuration No. 1, a nom 6 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material. In Configuration No. 2, a nom 2 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from each surface of the wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - In Configuration No. 1, min ½ in. thickness of fill material
applied within the joint, flush with exterior face of wall. In Configuration No. 2, min ½ in. thickness of fill material applied within the joint, flush with each surface of wall.
C R LAURENCE CO INC – CRL M64
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-1007
July 03, 1997 Assembly Rating – 2 Hr
Joint Width – 4 In. Maximum (Limited to Fire Exposure on Interior Surface Only)
1 2C 2D
2B
5 1/
4" M
IN
1. Wall Assembly – Reinforced lightweight or normal weight (100-150 pcf) structural concrete having
a min thickness of 5 1/4 in. at stepped-edges receiving Fill, Void or Cavity Material (Item 2C). Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Joint System – Max width of the joint is 4 in. The joint system shall consist of the following:
A. Fill, Void or Cavity Material* - (Not Shown) – Prior to the installation of the Forming Material (Item 2B), a nom 1/2 in. bead of caulk is applied along the edges of the joint, 2 in. from exterior surface of the wall.
B. Forming Material* - A nom 14 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed 1-1/4 in. from exterior surface of wall. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK® C. Fill, Void or Cavity Material* - Prior to the installation of the premold into the joint, the
stepped-surface of the concrete wall shall be treated with 2 component LymTal International, Inc. Primer 10 in accordance with the installation instructions accompanying the primer. Premold, max 12 in. wide min 3/4 in. deep, centered in the joint, such that it is spaced 1/2 in. from each stepped edge of concrete wall. When installed, the premold shall be flush with the exterior surface of the wall.
LYMTAL INTERNATIONAL INC – ISO-FLEX 880 PREMOLD D. Fill, Void or Cavity Material* - Min 3/4 in. thickness of fill material applied within the joint,
flush with exterior surface of wall. LYMTAL INTERNATIONAL INC – ISO-FLEX 980 Nosing
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-1009 November 19, 2008
Assembly Rating – 2 Hr Joint Width – 4 In. Maximum
(Limited to Fire Exposure on Interior Surface Only)
1 2B 2A
Interior Face
1. Wall Assembly – Min 4 ½ in. (114 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Joint System – Max width of the joint is 4 in. (102 mm) The joint system shall consist of the
following:
A. Forming Material* - Max 11 in. (279 mm) width of forming material shall be folded in half and packed into opening as a permanent form. Forming material to be recessed from exterior surface of wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with exterior surface of wall.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 SPECIFIED TECHNOLOGIES INC – PENSIL 300 or SPECSEAL SERIES SIL300 SEALANTS
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-1010 November 19, 2008
Assembly Rating – 2 Hr Joint Width – 4 In. Maximum
1 2B 2A
2B
1. Wall Assembly – Min 4 ½ in. (114 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Joint System – Max width of the joint is 4 in. (102 mm) The joint system shall consist of the
following:
A. Forming Material* - Max 11 in. (279 mm) width of forming material shall be folded in half and packed into opening as a permanent form. Forming material to be recessed from exterior surface of wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with each surface of wall.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 SEALANT SPECIFIED TECHNOLOGIES INC – PENSIL 300 SEALANT or SPECSEAL SERIES SIL300 SEALANTS
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-1034 April 12, 2005
Assembly Rating – 2 Hr Joint Width – 4 In. Maximum
1 2B 2A
1. Wall Assembly – Min 5 in. (127 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Joint System – Max width of the joint is 4 in. (102 mm). The joint system shall consist of the
following:
A. Forming Material* - Nom 11 in. (279 mm) wide by 3-3/8 in. (86 mm) thick blanket folded in half and compressed min 40 percent in thickness. Forming material installed into opening as a permanent form and to be recessed from each surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within
the joint, flush with each surface of wall. EGS NELSON FIRESTOP – CLK N/S (Non-Sag) Caulk
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-2008 August 17, 1995
Assembly Rating – 2 Hr Joint Width – 7 In. Maximum
(Limited to Fire Exposure on Interior Face Only)
1 2B 2A
1. Wall Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Joint System – Max width of the joint is 7 in. The joint system shall consist of the following:
A. Forming Material* - A nom 15 in. width of forming material shall be folded in half and firmly
packed into joint opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material. See Manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with exterior face of wall.
PECORA CORP – AC-20 FTR
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-0065 April 15, 2009
Assembly Rating – 2 Hr Joint Width – 2 In. Maximum
1
2
3B
3A
3B
1. Wall Assembly – Min 5 in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural
concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Floor Assembly – Min 4-1/2 in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
3. Joint System – Max width of the joint is 2 in. The joint system shall consist of the following:
A. Forming Material* - A nom 9 in. width of forming material shall be folded in half and firmly
packed into joint opening as a permanent form. Forming material to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with both surfaces of wall.
BASF CONSTRUCTION CHEMICAL LLC – SONOLASTIC NP2
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-0072
September 23, 2005 Assembly Rating – 2 Hr
Joint Width – 3/4 In. (19 mm) Maximum
1
3B
3A
2
3B
1. Floor Assembly – Min 4-1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
2. Wall Assembly – Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
3. Joint System – Max separation between bottom of floor and top of wall is 3/4 in. (19 mm) The joint system shall consist of the following:
A. Forming Material* - A nom 6 in. (152 mm) width of forming material shall be folded in half,
compressed min 25 percent and firmly packed into joint opening as a permanent form. Forming material to be recessed from each surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with each surface of wall.
PECORA CORP – DYNATROL II or AC-20 FTR
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-0073
September 23, 2005 Assembly Rating – 2 Hr
Joint Width – 3/4 In. (19 mm) Maximum
1
3B
3A
2
3B
1. Floor Assembly – Min 4-1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
2. Wall Assembly – Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
3. Joint System – Max separation between bottom of floor and top of wall is 3/4 in. (19 mm) The joint system shall consist of the following:
A. Forming Material* - A nom 6 in. (152 mm) width of forming material shall be folded in half,
compressed min 25 percent and firmly packed into joint opening as a permanent form. Forming material to be recessed from each surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with each surface of wall.
LYMTAL INTERNATIONAL INC – ISO-FLEX 880-GB, ISO-FLEX 881 and ISO-FLEX 830
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-0075
November 19, 2008 Assembly Rating – 2 Hr
Joint Width – 3/4 In. (19 mm) Maximum
1
3B
3A
2
3B
1. Floor Assembly – Min 4-1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100
– 150 pcf or 1600-2400 kg/m³) structural concrete. 2. Wall Assembly – Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
3. Joint System – Max separation between bottom of floor and top of wall is 3/4 in. (19 mm) The joint system shall consist of the following:
A. Forming Material* - A nom 6 in. (152 mm) width of forming material shall be folded in half,
compressed min 25 percent and firmly packed into joint opening as a permanent form. Forming material to be recessed from each surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with each surface of wall.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 SEALANT SPECIFIED TECHNOLOGIES INC – PENSIL 300 SEALANT or SPECSEAL SERIES SIL300 SEALANT
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-0076
September 23, 2005 Assembly Rating – 2 Hr
Joint Width – 3/4 In. (19 mm) Maximum
1
3B
3A
2
3B
1. Floor Assembly – Min 4-1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
2. Wall Assembly – Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
3. Joint System – Max separation between bottom of floor and top of wall is 3/4 in. (19 mm) The joint system shall consist of the following:
A. Forming Material* - A nom 6 in. (152 mm) width of forming material shall be folded in half,
compressed min 25 percent and firmly packed into joint opening as a permanent form. Forming material to be recessed from each surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with each surface of wall.
SIKA CORPORATION – SIKAFLEX 2CNS or 15LM
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-0077
September 23, 2005 Assembly Rating – 2 Hr
Joint Width – 3/4 In. (19 mm) Maximum
1
3B
3A
2
3B
1. Floor Assembly – Min 4-1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
2. Wall Assembly – Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
3. Joint System – Max separation between bottom of floor and top of wall is 3/4 in. (19 mm) The joint system shall consist of the following:
A. Forming Material* - A nom 6 in. (152 mm) width of forming material shall be folded in half,
compressed min 25 percent and firmly packed into joint opening as a permanent form. Forming material to be recessed from each surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with each surface of wall.
DOW CORNING CORP – 790 or 795 SEALANT
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-1013
April 12, 2005 Assembly Rating – 2 Hr
Joint Width – 4 In. Maximum
1
3B
3A
2
3B
1. Floor Assembly – Min 4-1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 –
150 pcf or 1600-2400 kg/m³) structural concrete. 2. Wall Assembly – Min 5 in. (127 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or
1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
3. Joint System – Max separation between bottom of floor and top of wall is 4 in. (102 mm). The joint system shall consist of the following:
A. Forming Material* - A nom 11 in. (279 mm) wide by 3-3/8 in. (86 mm) thick blanket folded in
half and compressed min 40 percent in thickness. Forming material installed into opening as a permanent form and to be recessed from each surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with each surface of wall.
EGS NELSON FIRESTOP – CLK N/S (Non-Sag) CAULK
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-1014
November 19, 2008 Assembly Rating – 2 Hr
Joint Width – 4 In. (102 mm) Maximum
1
3B
3A
2
3B
1. Floor Assembly – Min 4-1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 –
150 pcf or 1600-2400 kg/m³) structural concrete. 2. Wall Assembly – Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
3. Joint System – Max separation between bottom of floor and top of wall is 4 in. (102 mm). The joint system shall consist of the following:
A. Forming Material* - Min 11 in. (279 mm) width of forming material, folded in half and
compressed min 40 percent into opening as a permanent form. Forming Material to be recessed from each surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with each surface of wall.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 SEALANT SPECIFIED TECHNOLOGIES INC – PENSIL 300 SEALANT or SPECSEAL SERIES SIL300 SEALANT
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FW-S-0011
September 23, 2005 Assembly Rating – 2 Hr
Joint Width – 3/4 In. (19 mm) Maximum
2 3B3A 1
1. Wall Assembly – Min 4 1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
2. Floor Assembly – Min 4 1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
3. Joint System – Max separation between edge of floor and face of wall is ¾ in. (19 mm). The joint system shall consist of the following:
A. Forming Material* - Min 6 in. (152 mm) width of forming material shall be folded in half,
compressed min 25 percent in thickness and firmly packed into joint opening as a permanent form. Forming material to be recessed from top surface of floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with top surface of floor.
PECORA CORP – DYNATROL II or AC-20 FTR
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FW-S-0012
September 23, 2005 Assembly Rating – 2 Hr
Joint Width – 3/4 In. (19 mm) Maximum
2 3B3A 1
1. Wall Assembly – Min 4 1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
2. Floor Assembly – Min 4 1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
3. Joint System – Max separation between edge of floor and face of wall is ¾ in. (19 mm). The joint system shall consist of the following:
A. Forming Material* - Min 6 in. (152 mm) width of forming material shall be folded in half,
compressed min 25 percent in thickness and firmly packed into joint opening as a permanent form. Forming material to be recessed from top surface of floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with top surface of floor.
LYMTAL INTERNATIONAL INC – ISO-FLEX 880-GB, ISO-FLEX 881 and ISO-FLEX 830
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FW-S-0014
November 19, 2008 Assembly Rating – 2 Hr
Joint Width – 3/4 In. (19 mm) Maximum
2 3B3A 1
1. Wall Assembly – Min 4 1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
2. Floor Assembly – Min 4 1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
3. Joint System – Max separation between edge of floor and face of wall is ¾ in. (19 mm). The joint system shall consist of the following:
A. Forming Material* - Min 6 in. (152 mm) width of forming material shall be folded in half,
compressed min 25 percent in thickness and firmly packed into joint opening as a permanent form. Forming material to be recessed from top surface of floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with top surface of floor.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 or PENSIL 300 S/L SEALANT SPECIFIED TECHNOLOGIES INC – PENSIL 300, PENSIL 300 S/L, SPECSEAL SERIES SIL300 or SPECSEAL SERIES SIL300SL SEALANTS
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory
Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FW-S-0015
September 23, 2005 Assembly Rating – 2 Hr
Joint Width – 3/4 In. (19 mm) Maximum
2 3B3A 1
1. Wall Assembly – Min 4 1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
2. Floor Assembly – Min 4 1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
3. Joint System – Max separation between edge of floor and face of wall is ¾ in. (19 mm). The joint system shall consist of the following:
A. Forming Material* - Min 6 in. (152 mm) width of forming material shall be folded in half,
compressed min 25 percent in thickness and firmly packed into joint opening as a permanent form. Forming material to be recessed from top surface of floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with top surface of floor.
SIKA CORPORATION – SIKAFLEX 2CNS or 15LM
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FW-S-0016
September 23, 2005 Assembly Rating – 2 Hr
Joint Width – 3/4 In. (19 mm) Maximum
2 3B3A 1
1. Wall Assembly – Min 4 1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
2. Floor Assembly – Min 4 1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
3. Joint System – Max separation between edge of floor and face of wall is ¾ in. (19 mm). The joint system shall consist of the following:
A. Forming Material* - Min 6 in. (152 mm) width of forming material shall be folded in half,
compressed min 25 percent in thickness and firmly packed into joint opening as a permanent form. Forming material to be recessed from top surface of floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with top surface of floor.
DOW CORNING CORP – 790 or 795 SEALANT
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FW-S-1017
March 31, 2005 Assembly Rating – 2 Hr
Joint Width – 4 In. Maximum
2 3B3A 1
1. Wall Assembly – Min 4 1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
2. Floor Assembly – Min 4 1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
3. Joint System – Max separation between edge of floor and face of wall is 4 in. (101 mm). The joint system shall consist of the following:
A. Forming Material* - Min 11 in. (279 mm) width of forming material shall be folded in half,
compressed min 40 percent in thickness and friction fitted into joint opening as a permanent form. Forming material to be recessed from top surface of floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with top surface of floor.
EGS NELSON FIRESTOP – CLK S/L (Self Leveling) CAULK or CLK N/S (Non-Sag) CAULK
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FW-S-1018
November 19, 2008 Assembly Rating – 2 Hr
Joint Width – 4 In. (102 mm) Maximum
2 3B3A 1
1. Wall Assembly – Min 4 1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
2. Floor Assembly – Min 4 1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
3. Joint System – Max separation between edge of floor and face of wall is 4 in. (102 mm). The joint system shall consist of the following:
A. Forming Material* - Min 11 in. (279 mm) width of forming material shall be folded in half,
compressed min 40 percent in thickness and friction fitted into joint opening as a permanent form. Forming material to be recessed from top surface of floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with top surface of floor.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 or PENSIL 300 S/L SEALANTS SPECIFIED TECHNOLOGIES INC – PENSIL 300, PENSIL 300 S/L, SPECSEAL SERIES SIL300 or SPECSEAL SERIES SIL300SL SEALANTS
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. C-AJ-1093 February 04, 1994
(Formerly System No. 492) F Rating – 2 Hr
T Rating – 0 and 1/4 Hr (See Item 2)
2
3B
3B 3A
1
A
A
3B
3A
2
SECTION A-A
1. Floor or Wall Assembly – Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL classified Concrete Blocks*. Max diam of opening is 8 in. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants – One metallic pipe, conduit or tubing to be centered within the firestop system.
Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The annular space between pipe, conduit or tubing and periphery of opening shall be min 7/8 in. to max 3-7/8 in. The “T” rating is dependant upon the type of penetrating item used. The “T” rating is 0 h if copper tubing is used. The “T” rating is 1/4 h if steel pipe, steel conduit or electrical metallic tubing is used. The following types and sizes of metallic pipes, conduit or tubing may be used.
A. Steel Pipe – Nom 6 in. diam (or smaller) Schedule 40 (or heavier) steel pipe. B. Conduit – Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. C. Copper Tubing – Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
3. Firestop System – The firestop system shall consist of the following:
A. Forming Material* - Blanket Material – Min 1/2 in. thick, min 3-1/2 in. wide, firmly wrapped around the penetrating item. Forming material to be recessed from both surfaces of floor and from both surfaces of wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG INC – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Caulk – Min 1/2 in. thickness of fill material applied within the annulus, flush with both surfaces of floor or wall. Additional fill material to be installed such that a min 1/2 in. crown is formed around the penetrating item.
PECORA CORP – AC-20 FTR * Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0018
June 17, 1997 Assembly Rating – 3 Hr
Joint Width – 2 In. Maximum
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
2. Joint System – Max width of the joint is 2 in. The joint system shall consist of the following:
A. Forming Material* - A nom 10 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from top surface of floor as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Prior to the installation of the caulk material into the joint, the interior surfaces of the concrete slab shall be treated with 2 component LymTal International, Inc. Primer 10 in accordance with the installation instructions accompanying the primer. Min 3/8 in. thickness of fill material applied within the joint, flush with top surface of floor.
LYMTAL INTERNATIONAL INC – ISO-FLEX 880-GB, ISO-FLEX 881 and ISO-FLEX 830
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-1007 August 11, 1995
Assembly Rating – 3 Hr Joint Width – 3 In. Maximum
1 2B 2A
1. Floor Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete.
2. Joint System – Max width of the joint is 3 in. The joint system shall consist of the following:
A. Forming Material* - A nom 11 in. width of forming material shall be folded in half and firmly
packed into joint opening as a permanent form. Forming material to be recessed from top surface of floor as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Prior to the installation of the caulk material into the joint, interior surfaces of the concrete slab shall be treated with Pecora Primer P-75 in accordance with the installation instructions accompanying the primer. Min ½ in. thickness of fill material applied within the joint, flush with top surface of floor.
PECORA CORP – DYNATROL II
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0022
June 17, 1997 Assembly Rating – 3 Hr
Joint Width – 2 In. Maximum
(Limited to Fire Exposure on Interior Surface Only)
1 2B 2A
1. Wall Assembly – Min 4 ½ in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturers.
2. Joint System – Max width of the joint is 2 in. The joint system shall consist of the following:
A. Forming Material* - A nom 10 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material. See manufacturers installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Prior to the installation of the caulk material into the joint, the interior surfaces of the exterior surface of the wall shall be treated with 2 component LymTal International, Inc. Primer 10 in accordance with the installation instructions accompanying the primer. Min 3/8 in. thickness of fill material applied within the joint, flush with exterior surface of wall.
LYMTAL INTERNATIONAL INC – ISO-FLEX 880-GB, ISO-FLEX 881 and ISO-FLEX 830
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-1008
July 29, 1995 Assembly Rating – 3 Hr
Joint Width – 3 In. Maximum (Limited to Fire Exposure on Interior Face Only)
1 2B 2A
1. Wall Assembly – Min 4-1/2 in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Joint System – Max width of the joint is 3 in. The joint system shall consist of the following:
A. Forming Material* - A nom 11 in. width of forming material shall be folded in half and firmly
packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - Prior to the installation of the caulk material into the joint, the
interior surfaces of the exterior side of the wall shall be treated with Pecora Primer P-75 in accordance with the installation instructions accompanying the primer. Min ½ in. thickness of fill material applied within the joint, flush with exterior face of wall.
PECORA CORP – DYNATROL II
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-0074
September 23, 2005 Assembly Rating – 3 Hr
Joint Width – 2 In. (51 mm) Maximum
1
3B 3B
3A
2
1. Floor Assembly – Min 4-1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
2. Wall Assembly – Min 5-3/4 in. (146 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
3. Joint System – Max separation between bottom of floor and top of wall is 2 in. (51 mm). The joint system shall consist of the following:
A. Forming Material* - Min 10 in. (254 mm) width of forming material, folded in half and
compressed min 60 percent into opening as a permanent form. Forming Material to be recessed from each surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Prior to the installation of the caulk material into the joint, the concrete surfaces shall be treated with 2 component LymTal International, Inc. Primer 10 in accordance with the installation instructions accompanying the primer. Min 3/8 in. (10 mm) thickness of fill material applied within the joint, flush with both surfaces of wall.
LYMTAL INTERNATIONAL INC – ISO-FLEX 880-GB, ISO-FLEX 881 and ISO-FLEX 830
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FW-S-0013
September 23, 2005 Assembly Rating – 3 Hr
Joint Width – 2 In. (51 mm) Maximum
12 3B
3A
1. Wall Assembly – Min 4 1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of ant UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
2. Floor Assembly – Min 4 1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
3. Joint System – Max separation between edge of floor and face of wall is 2 in. (51 mm). The joint system shall consist of the following:
A. Forming Material* - Min 10 in. (254 mm) width of forming material shall be folded in half,
compressed min 60 percent in thickness and firmly packed into joint opening as a permanent form. Forming material to be recessed from top surface of floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Prior to the installation of the fill material into the joint, the concrete surfaces shall be treated with 2 component LymTal International, Inc. Primer 10 in accordance with the installation instructions accompanying the primer. Min 3/8 in. (10 mm) thickness of fill material applied within the joint, flush with top surface of floor.
LYMTAL INTERNATIONAL INC – ISO-FLEX 880-GB, ISO-FLEX 881 and ISO-FLEX 830
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0020
November 18, 2008 Assembly Rating – 4 Hr
Joint Width – 2 In. Maximum
1 2B 2A
1. Floor Assembly – Min 5-3/4 in. (146 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. 2. Joint System – Max width of the joint is 2 in. (51 mm). The joint system shall consist of the
following: A. Forming Material* - Max 12 in. (305 mm) width of forming material shall be folded in half
and packed into joint opening as a permanent form. Forming material to be recessed from top surface of the floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with top surface of the floor.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 or PENSIL 300 S/L SEALANTS SPECIFIED TECHNOLOGIES INC – PENSIL 300, PENSIL 300 S/L, SPECSEAL SERIES SIL300 or SPECSEAL SERIES SIL300SL SEALANTS
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-0024
October 29, 1997 Assembly Rating – 4 Hr
Joint Width – 2 In. Maximum
1 2B 2A
1. Floor Assembly – Min 8 in. thick reinforced lightweight or normal weight (100 – 150 pcf)
structural concrete. 2. Joint System – Max width of the joint is 2 in. The joint system shall consist of the following:
A. Forming Material* - A nom 14 in. width of forming material shall be folded in half and firmly
packed into joint opening as a permanent form. Forming material to be recessed from top surface of the floor to accommodate the required thickness of fill material. See Manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. thickness of fill material applied within the joint, flush with top surface of the floor.
SIKA CORPORATION – SIKAFLEX 2CNS
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-1010
August 29, 1995 Assembly Rating – 4 Hr
Joint Width – 4 In. Maximum
1 2B 2A
1. Floor Assembly – Min 6 in. thick reinforced lightweight or normal weight (100 – 150 pcf)
structural concrete. 2. Joint System – Max width of the joint is 4 in. The joint system shall consist of the following:
A. Forming Material* - A nom 16 in. width of forming material shall be folded in half and firmly
packed into joint opening as a permanent form. Forming material to be recessed from top surface of the floor to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. thickness of fill material applied within the joint, flush with top surface of the floor.
PECORA CORP – AC-20 FTR
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-1013
April 15, 2009 Assembly Rating – 4 Hr
Joint Width – 4 In. Maximum
1 2B 2A
1. Floor Assembly – Min 6 in. thick reinforced lightweight or normal weight (100 – 150 pcf)
structural concrete. 2. Joint System – Max width of the joint is 4 in. The joint system shall consist of the following:
A. Forming Material* - A nom 16 in. width of forming material shall be folded in half and firmly
packed into joint opening as a permanent form. Forming material to be recessed from top surface of the floor to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. thickness of fill material applied within the joint, flush with top surface of the floor.
BASF CONSTRUCTION CHEMICAL LLC – SONOLASTIC NP1 or NP2
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FF-S-1036
April 15, 2009 Assembly Rating – 4 Hr
Joint Width – 4 In. Maximum
1 2B 2A
1. Floor Assembly – Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete.
2. Joint System – Max width of the joint is 4 in. (102 mm) The joint system shall consist of the
following:
A. Forming Material* - A nom 16 in. (406 mm) width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from top surface of floor as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with top surface of floor.
EGS NELSON FIRESTOP – CLK S/L (Self Leveling) Caulk or CLK N/S (Non-Sag) Caulk
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0023 November 19, 2008
Assembly Rating – 4 Hr Joint Width – 2 In. Maximum
(Limited to Fire Exposure on Interior Surface Only)
1 2B 2A
1. Wall Assembly – Min 5-3/4 in. (146 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Joint System – Max width of the joint is 2 in. (51 mm) The joint system shall consist of the
following:
A. Forming Material* - Max 12 in. (305 mm) width of forming material shall be folded in half and packed into opening as a permanent form. Forming material to be recessed from exterior surface of wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with exterior surface of wall.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 SPECIFIED TECHNOLOGIES INC – PENSIL 300 or SPECSEAL SERIES SIL300 SEALANTS
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0027 August 17, 1995
Assembly Rating – 4 Hr Joint Width – 2 In. Maximum
(Configuration No. 1 Limited to Fire Exposure on Interior Surface Only)
Configuration No. 1 1 2B 2A
Configuration No. 2
1 2B 2A
2B
1. Wall Assembly – Min 8 in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Joint System – Max width of the joint is 2 in. The joint system shall consist of the following:
A. Forming Material* - In configuration No. 1, a nom 14 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material. In configuration No. 2, a nom 14 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from each surface of wall as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - In configuration No. 1, min ½ in. thickness of fill material applied within the joint, flush with exterior surface of wall. In configuration No. 2, min ½ in. thickness of fill material applied within the joint, flush with each surface of wall.
SIKA CORPORATION – SIKAFLEX 2CNS * Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory
Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-0029 November 19, 2008
Assembly Rating – 4 Hr Joint Width – 2 In. Maximum
1 2B 2A
2B
1. Wall Assembly – Min 5-3/4 in. (146 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Joint System – Max width of the joint is 2 in. (51 mm) The joint system shall consist of the
following:
A. Forming Material* - Max 12 in. (305 mm) width of forming material shall be folded in half and packed into opening as a permanent form. Forming material to be recessed from exterior surface of wall as required to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. (13 mm) thickness of fill material applied within the joint, flush with exterior surface of wall.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 SPECIFIED TECHNOLOGIES INC – PENSIL 300 or SPECSEAL SERIES SIL300 SEALANTS
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-1012 September 08, 1995
Assembly Rating – 4 Hr Joint Width – 4 In. Maximum
(Configuration No. 1 Limited to Fire Exposure on Interior Face Only)
Configuration No. 1 1 2B 2A
Configuration No. 2
1 2B 2A
2B
1. Wall Assembly – In Configuration No. 1, min 6 in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. In Configuration No. 2, min 7 in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturers.
2. Joint System – Max width of the joint is 4 in. The joint system shall consist of the following: A. Forming Material* - In Configuration No. 1, a nom 16 in. width of forming material shall be
folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material. In Configuration No. 2, a nom 16 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from each surface of wall as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - In Configuration No. 1, min ½ in. thickness of fill material
applied within the joint, flush with exterior face of wall. In Configuration No. 2, min ½ in. thickness of fill material applied within the joint, flush with each surface of wall.
PECORA CORPORATION – AC-20 FTR
* Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. WW-S-1016 April 15, 2009
Assembly Rating – 4 Hr Joint Width – 4 In. Maximum
(Configuration No. 1 Limited to Fire Exposure on Interior Face Only) CONFIGURATION NO. 1 1 2B 2A
CONFIGURATION NO. 2 1 2B 2A
2B
1. Wall Assembly – Min 6 in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of Manufacturers.
2. Joint System – Max width of the joint is 4 in. The joint system shall consist of the following: A. Forming Material* - In Configuration No. 1, a nom 16 in. width of forming material shall be
folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from exterior face of wall as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material. In Configuration No. 2, a nom 16 in. width of forming material shall be folded in half and firmly packed into opening as a permanent form. Forming material to be recessed from each surface of wall as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK® B. Fill, Void or Cavity Material* - In Configuration No. 1, min ½ in. thickness of fill material
applied within the joint, flush with exterior face of wall. In Configuration No. 2, min ½ in. thickness of fill material applied within the joint, flush with each surface of wall.
BASF CONSTRUCTION CHEMICAL LLC – SONOLASTIC NP 1 or NP2 * Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-0070
November 19, 2008 Assembly Rating – 4 Hr
Joint Width – 2 In. (51 mm) Maximum
1
3B 3B
3A
2
1. Floor Assembly – Min 5-3/4 in. (146 mm) thick steel-reinforced lightweight or normal weight (100 –
150 pcf or 1600-2400 kg/m³) structural concrete. 2. Wall Assembly – Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or
1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
3. Joint System – Max separation between bottom of floor and top of wall is 2 in. (51 mm). The joint system shall consist of the following:
A. Forming Material* - Min 12 in. (305 mm) width of forming material, folded in half and
compressed min 27 percent into opening as a permanent form. Forming Material to be recessed from each surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with each surface of wall.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 SEALANT SPECIFIED TECHNOLOGIES INC – PENSIL 300 SEALANT or SPECSEAL SERIES SIL300 SEALANT
*Bearing the UL Classification Mark This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory
Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-0071
September 23, 2005 Assembly Rating – 4 Hr
Joint Width – 2 In. (51 mm) Maximum
1
3B 3B
3A
2
1. Floor Assembly – Min 5-3/4 in. (146 mm) thick steel-reinforced lightweight or normal weight (100 –
150 pcf or 1600-2400 kg/m³) structural concrete. 2. Wall Assembly – Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100 – 150 pcf or
1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
3. Joint System – Max separation between bottom of floor and top of wall is 2 in. (51 mm). The joint system shall consist of the following:
A. Forming Material* - Min 12 in. (305 mm) width of forming material, folded in half and
compressed min 27 percent into opening as a permanent form. Forming Material to be recessed from each surface of wall to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with each surface of wall.
SIKA CORPORATION – SIKAFLEX 2CNS
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. HW-S-1012
April 15, 2009 Assembly Rating – 4 Hr
Joint Width – 4 In. Maximum
1
3B
3B
3A
2
1. Floor Assembly – Min 6 in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural
concrete. 2. Wall Assembly – Min 6 in. thick reinforced lightweight or normal weight (100 – 150 pcf) structural
concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers
3. Joint System – Max width of the joint is 4 in. The joint system shall consist of the following:
A. Forming Material* - A nom 16 in. width of forming material shall be folded in half and firmly packed into joint opening as a permanent form. Forming material to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material. See manufacturer’s installation instructions for size and configuration of forming material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min ½ in. thickness of fill material applied within the joint, flush with both surfaces of wall.
BASF CONSTRUCTION CHEMICAL LLC – SONOLASTIC NP1 or NP2
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FW-S-0009
November 18, 2008 Assembly Rating – 4 Hr
Joint Width – 2 In. (51 mm) Maximum
12 3B
3A
1. Wall Assembly – Min 5-3/4 in. (146 mm) thick reinforced lightweight or normal weight (100 – 150
pcf or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Floor Assembly – Min 5-3/4 in. (146 mm) thick steel-reinforced lightweight or normal weight (100
– 150 pcf or 1600-2400 kg/m³) structural concrete. 3. Joint System – Max separation between edge of floor and face of wall is 2 in. (51 mm). The joint
system shall consist of the following: A. Forming Material* - Max 12 in. (305 mm) width of forming material shall be folded in half,
compressed min 27 percent and installed into joint opening as a permanent form. Forming material to be recessed from top surface of the floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with top surface of the floor.
MOMENTIVE PERFORMANCE MATERIALS – PENSIL 300 or PENSIL 300 S/L SEALANTS SPECIFIED TECHNOLOGIES INC – PENSIL 300, PENSIL 300 S/L, SPECSEAL SERIES SIL300 or SPECSEAL SERIES SIL300SL SEALANTS
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®
Backer Rod Mfg. Inc. www.backerrod.com
Customer Service (800) 595 2950
UL System No. FW-S-0010
September 23, 2005 Assembly Rating – 4 Hr
Joint Width – 2 In. (51 mm) Maximum
12 3B
3A
1. Wall Assembly – Min 8 in. (203 mm) thick reinforced lightweight or normal weight (100 – 150 pcf
or 1600-2400 kg/m³) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CATZ) category in the Fire Resistance Directory for names of manufacturers.
2. Floor Assembly – Min 8 in. (203 mm) thick steel-reinforced lightweight or normal weight (100 –
150 pcf or 1600-2400 kg/m³) structural concrete. 3. Joint System – Max separation between edge of floor and face of wall is 2 in. (51 mm). The joint
system shall consist of the following: A. Forming Material* - Min 14 in. (356 mm) width of forming material shall be folded in half,
compressed min 27 percent and installed into joint opening as a permanent form. Forming material to be recessed from top surface of the floor to accommodate the required thickness of fill material.
BACKER ROD MFG. INC. – ULTRA BLOCK®
B. Fill, Void or Cavity Material* - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with top surface of the floor.
SIKA CORPROATION – SIKAFLEX 2CNS
*Bearing the UL Classification Mark
This material was extracted and drawn by Backer Rod Mfg. Inc. from the 2009 UL Fire Resistance Directory Copyright © 2009 Underwriters Laboratories Inc.®