  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    1/17

    Sheath over-voltagesin cross-bondedunderground transmission lines

    Antoine NAUD (RTE)

    Gatan GUTIERREZ (RTE)Wilfried FRELIN (EDF R&D)

    Minh NGUYEN TUAN (EDF R&D)

    EMTP User Group Meeting Paris, June 21st 2013

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    2/17

    Content

    Introduction

    Case study: modelling of a 90 kV cross-bonded link with EMTP-RV

    Switching surge

    Lightning stroke

    Conclusion & perspectives

    2 - Sheath over-voltages in cross-bonded underground transmission lines

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    3/17

    Introduction

    For long UGL, sectionalised cross-bonding is common practice.

    Until recently, SVL were installed at each cross-bonding point.

    Terminations

    Sectionalizing joints Earthing joints

    3 - Sheath over-voltages in cross-bonded underground transmission lines

    The availability of reliable tools for transient studies allows the optimization ofthe design of cross-bonded links.

    Major section

    Minor section = Surge voltage limiter (SVL)

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    4/17

    Transients affecting UGL

    UGL between substations: switching surges

    SUBSTATION A SUBSTATION B

    4 - Sheath over-voltages in cross-bonded underground transmission lines

    Siphon: lightning strokes

    OHL OHL

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    5/17

    Case study

    Cables: 3 x single-core 1200 mm Al90 kV

    Cross-bonded, 2 major sections

    ,

    grounded neutral

    5 - Sheath over-voltages in cross-bonded underground transmission lines

    Withstandlevels

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    6/17

    Modelling with EMTP-RV

    Underground cables: FDQ model

    Overhead lines: FD model

    Towers: CP model, with 10 groundingSurge arresters: non-linear elements

    Bonding leads: lumped inductances

    6 - Sheath over-voltages in cross-bonded underground transmission lines

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    7/17

    Modelling with EMTP-RV

    Circuit-breakers: ideal switches

    Voltage transformers: RL circuit model

    R1 X1 R2 X2

    ZcRfL

    Lightning: current source, Cigr wave shape

    7 - Sheath over-voltages in cross-bonded underground transmission lines

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    8/17

    Switching surges

    8 - Sheath over-voltages in cross-bonded underground transmission lines

    280 290 300 310 320 330 340 350 360 370 380-1.5

    -1

    -0.5

    0

    0.5

    1

    1.5x 10

    5

    t (ms)

    y

    PLOT

    gauche_a1@vn@1

    source_gauche/VwZ1a@vb@1

    Network voltage

    Cableconductorpotential

    Re-closing

    Over-voltages reache 1.7 p.u. at theentrance of the UGL.

    Re-closing occurs on discharged cables,thanks to voltages transformers.

    Neither phase SA nor SVL becomeconductive.

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    9/17

    Switching surges - Results

    Over-voltages applied to cable sheaths

    and screen interruptions are far belowtheir withstand levels.

    This is also true in the worst case of re-closing of a charged cable on voltage ofopposite polarity.

    This is also true when performing a sensitivity analysis on re-closing time,length of minor sections, length of bonding leads, earthing resistances, cablecross-section, number of major sections.

    9 - Sheath over-voltages in cross-bonded underground transmission lines

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    10/17

    Lightning stroke

    Median lightning stroke: 31 kA, probability 50 %

    Severe lightning stroke: 150 kA, probability 0.05 %

    Stroke on the UGL/OHL tower, which is the most severe configuration.

    10 - Sheath over-voltages in cross-bonded underground transmission lines

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    11/17

    Median lightning stroke

    !

    Phase SA do not conduct.

    SVL of 1st major section conduct.

    With SVL, sheath over-voltages are excessive close to the UGL/OHLtransition.

    Without SVL, sheath over-voltages at cross-bonding points are impossible toassess.

    With/wihout SVL, screen interruption over-voltages are acceptable.

    11 - Sheath over-voltages in cross-bonded underground transmission lines

    Max screen to local earth over-voltages Max screen interruption over-voltages

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    12/17

    Severe lightning stroke

    ! !

    12 - Sheath over-voltages in cross-bonded underground transmission lines

    Some phase SA conduct.

    SVL of both major sections conduct.Sheath over-voltages are excessive.

    Screen interruption over-voltages are excessive.

    Max screen to local earth over-voltages Max screen interruption over-voltages

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    13/17

    Influence of striking location

    12

    3

    !

    13 - Sheath over-voltages in cross-bonded underground transmission lines

    Screen interruption over-voltages areacceptable, even for a severe stroke, ifthe striking location is the 2nd tower orbeyond.

    Sheath over-voltages are acceptable ifthe striking location is the 2nd tower orbeyond. This is not true for a severestroke.

    Max screen to local earth over-voltages

    (median lightning strokes)

    Max screen interruption over-voltages(median lightning strokes)

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    14/17

    Influence of skywires

    -

    !

    14 - Sheath over-voltages in cross-bonded underground transmission lines

    For a median stroke, sheath over-voltages are excessive, whereas screeninterruption over-voltages remainacceptable.

    For a severe stroke, both sheath andscreen interruption over-voltages areexcessive.

    Max screen interruption over-voltages(severe lightning strokes)

    !

    (severe lightning strokes)

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    15/17

    Probability of lightning strokes

    Max lightning current for material

    1st tower Mid-span 2nd tower

    Oversheath

    Screeninterruption u

    lativedistributionfunction(%)

    Lightning current

    (kA)

    Probability

    according to Cigr TB 63

    For screen interruptions: the probability of destructive strokes is low.

    For oversheaths: the probability of destructive strokes on the 2nd tower is low.

    15 - Sheath over-voltages in cross-bonded underground transmission lines

    Lightning current (kA)

    C

    um

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    16/17

    Conclusion & perspectives

    Switching surges are not likely to cause excessive over-voltages, even without SVL.

    Median lightning strokes (50 % probability) are not harmful if beyond the 2nd tower.

    In case of strokes of very large magnitudes (0.05 % probability), excessive over-voltagesoccur.

    Moreover, in case of a lightning stroke:

    SVL do not significantly reduce screen interruption over-voltages.

    Sheath over-voltages are excessive close to the UGL/OHL transition.

    Further studies should be carried out to decide whether higher withstand levels of screeninterruptions should be asked for, while suppressing the SVL.

    Tests on the field will be performed in order to validate the computations.

    These issues should be considered for other voltage levels, such as 225 kV.

    16 - Sheath over-voltages in cross-bonded underground transmission lines

  • 8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF

    17/17

    Thank you

    for your attention.

    EMTP User Group Meeting Paris, June 21st 2013