Sheath over-voltagesin cross-bondedunderground transmission lines
Antoine NAUD (RTE)
Gatan GUTIERREZ (RTE)Wilfried FRELIN (EDF R&D)
Minh NGUYEN TUAN (EDF R&D)
EMTP User Group Meeting Paris, June 21st 2013
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
2/17
Content
Introduction
Case study: modelling of a 90 kV cross-bonded link with EMTP-RV
Switching surge
Lightning stroke
Conclusion & perspectives
2 - Sheath over-voltages in cross-bonded underground transmission lines
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
3/17
Introduction
For long UGL, sectionalised cross-bonding is common practice.
Until recently, SVL were installed at each cross-bonding point.
Terminations
Sectionalizing joints Earthing joints
3 - Sheath over-voltages in cross-bonded underground transmission lines
The availability of reliable tools for transient studies allows the optimization ofthe design of cross-bonded links.
Major section
Minor section = Surge voltage limiter (SVL)
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
4/17
Transients affecting UGL
UGL between substations: switching surges
SUBSTATION A SUBSTATION B
4 - Sheath over-voltages in cross-bonded underground transmission lines
Siphon: lightning strokes
OHL OHL
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
5/17
Case study
Cables: 3 x single-core 1200 mm Al90 kV
Cross-bonded, 2 major sections
,
grounded neutral
5 - Sheath over-voltages in cross-bonded underground transmission lines
Withstandlevels
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
6/17
Modelling with EMTP-RV
Underground cables: FDQ model
Overhead lines: FD model
Towers: CP model, with 10 groundingSurge arresters: non-linear elements
Bonding leads: lumped inductances
6 - Sheath over-voltages in cross-bonded underground transmission lines
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
7/17
Modelling with EMTP-RV
Circuit-breakers: ideal switches
Voltage transformers: RL circuit model
R1 X1 R2 X2
ZcRfL
Lightning: current source, Cigr wave shape
7 - Sheath over-voltages in cross-bonded underground transmission lines
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
8/17
Switching surges
8 - Sheath over-voltages in cross-bonded underground transmission lines
280 290 300 310 320 330 340 350 360 370 380-1.5
-1
-0.5
0
0.5
1
1.5x 10
5
t (ms)
y
PLOT
gauche_a1@vn@1
source_gauche/VwZ1a@vb@1
Network voltage
Cableconductorpotential
Re-closing
Over-voltages reache 1.7 p.u. at theentrance of the UGL.
Re-closing occurs on discharged cables,thanks to voltages transformers.
Neither phase SA nor SVL becomeconductive.
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
9/17
Switching surges - Results
Over-voltages applied to cable sheaths
and screen interruptions are far belowtheir withstand levels.
This is also true in the worst case of re-closing of a charged cable on voltage ofopposite polarity.
This is also true when performing a sensitivity analysis on re-closing time,length of minor sections, length of bonding leads, earthing resistances, cablecross-section, number of major sections.
9 - Sheath over-voltages in cross-bonded underground transmission lines
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
10/17
Lightning stroke
Median lightning stroke: 31 kA, probability 50 %
Severe lightning stroke: 150 kA, probability 0.05 %
Stroke on the UGL/OHL tower, which is the most severe configuration.
10 - Sheath over-voltages in cross-bonded underground transmission lines
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
11/17
Median lightning stroke
!
Phase SA do not conduct.
SVL of 1st major section conduct.
With SVL, sheath over-voltages are excessive close to the UGL/OHLtransition.
Without SVL, sheath over-voltages at cross-bonding points are impossible toassess.
With/wihout SVL, screen interruption over-voltages are acceptable.
11 - Sheath over-voltages in cross-bonded underground transmission lines
Max screen to local earth over-voltages Max screen interruption over-voltages
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
12/17
Severe lightning stroke
! !
12 - Sheath over-voltages in cross-bonded underground transmission lines
Some phase SA conduct.
SVL of both major sections conduct.Sheath over-voltages are excessive.
Screen interruption over-voltages are excessive.
Max screen to local earth over-voltages Max screen interruption over-voltages
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
13/17
Influence of striking location
12
3
!
13 - Sheath over-voltages in cross-bonded underground transmission lines
Screen interruption over-voltages areacceptable, even for a severe stroke, ifthe striking location is the 2nd tower orbeyond.
Sheath over-voltages are acceptable ifthe striking location is the 2nd tower orbeyond. This is not true for a severestroke.
Max screen to local earth over-voltages
(median lightning strokes)
Max screen interruption over-voltages(median lightning strokes)
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
14/17
Influence of skywires
-
!
14 - Sheath over-voltages in cross-bonded underground transmission lines
For a median stroke, sheath over-voltages are excessive, whereas screeninterruption over-voltages remainacceptable.
For a severe stroke, both sheath andscreen interruption over-voltages areexcessive.
Max screen interruption over-voltages(severe lightning strokes)
!
(severe lightning strokes)
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
15/17
Probability of lightning strokes
Max lightning current for material
1st tower Mid-span 2nd tower
Oversheath
Screeninterruption u
lativedistributionfunction(%)
Lightning current
(kA)
Probability
according to Cigr TB 63
For screen interruptions: the probability of destructive strokes is low.
For oversheaths: the probability of destructive strokes on the 2nd tower is low.
15 - Sheath over-voltages in cross-bonded underground transmission lines
Lightning current (kA)
C
um
-
8/9/2019 Sheath Over-Voltages Minh NGUYEN TUAN RTE EDF
16/17
Conclusion & perspectives
Switching surges are not likely to cause excessive over-voltages, even without SVL.
Median lightning strokes (50 % probability) are not harmful if beyond the 2nd tower.
In case of strokes of very large magnitudes (0.05 % probability), excessive over-voltagesoccur.
Moreover, in case of a lightning stroke:
SVL do not significantly reduce screen interruption over-voltages.
Sheath over-voltages are excessive close to the UGL/OHL transition.
Further studies should be carried out to decide whether higher withstand levels of screeninterruptions should be asked for, while suppressing the SVL.
Tests on the field will be performed in order to validate the computations.
These issues should be considered for other voltage levels, such as 225 kV.