This document is downloaded from DR‑NTU (https://dr.ntu.edu.sg) Nanyang Technological University, Singapore. Short‑Circuit Calculation in Distribution Networks with Distributed Induction Generators Zhou, Niancheng; Ye, Fan; Wang, Qianggang; Lou, Xiaoxuan; Zhang, Yuxiang 2016 Zhou, N., Ye, F., Wang, Q., Lou, X., & Zhang, Y. (2016). Short‑Circuit Calculation in Distribution Networks with Distributed Induction Generators. Energies, 9(4), 277‑. https://hdl.handle.net/10356/81497 https://doi.org/10.3390/en9040277 © 2016 by the authors; licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC‑BY) license (http://creativecommons.org/licenses/by/4.0/). Downloaded on 22 Mar 2022 02:25:43 SGT

Upload: others

Post on 22-Mar-2022

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Short‑Circuit Calculation in Distribution Networks with

This document is downloaded from DR‑NTU (https://dr.ntu.edu.sg)Nanyang Technological University, Singapore.

Short‑Circuit Calculation in Distribution Networkswith Distributed Induction Generators

Zhou, Niancheng; Ye, Fan; Wang, Qianggang; Lou, Xiaoxuan; Zhang, Yuxiang

2016

Zhou, N., Ye, F., Wang, Q., Lou, X., & Zhang, Y. (2016). Short‑Circuit Calculation inDistribution Networks with Distributed Induction Generators. Energies, 9(4), 277‑.

https://hdl.handle.net/10356/81497

https://doi.org/10.3390/en9040277

© 2016 by the authors; licensee MDPI, Basel, Switzerland. This article is an open accessarticle distributed under the terms and conditions of the Creative Commons Attribution(CC‑BY) license (http://creativecommons.org/licenses/by/4.0/).

Downloaded on 22 Mar 2022 02:25:43 SGT

Page 2: Short‑Circuit Calculation in Distribution Networks with

energies

Article

Short-Circuit Calculation in Distribution Networkswith Distributed Induction GeneratorsNiancheng Zhou 1, Fan Ye 1,*, Qianggang Wang 1,2, Xiaoxuan Lou 1,3 and Yuxiang Zhang 2

1 State Key Laboratory of Power Transmission Equipment & System Security and New Technology,Chongqing University, Chongqing 400044, China; [email protected] (N.Z.);[email protected] (Q.W.); [email protected] (X.L.)

2 School of Electricaland Electronic Engineering, Nanyang Technological University, Singapore 639798,Singapore; [email protected]

3 Department of Electrical Engineering, University of Wisconsin-Milwaukee, Milwaukee, WI 53211, USA* Correspondence: [email protected]; Tel.: +86-136-1768-5854; Fax: +86-23-6511-2739

Academic Editor: João P. S. CatalãoReceived: 19 January 2016; Accepted: 31 March 2016; Published: 9 April 2016

Abstract: This paper presents an improved current source equivalent model method to determine theshort-circuit current of a distribution system with multiple fixed-speed and variable-speed inductiongenerators (IGs). The correlation coefficients of flux components between stator and rotor under theunsymmetrical fault are analyzed using the positive and negative sequence steady-state equivalentcircuits of an IG. The terminal voltage and current responses of fixed-speed and variable-speedIGs with and without the rotor slip changes under different penetration levels are compared toinvestigate the coupling relation between the short-circuit currents of IGs and the nodal voltages inthe distribution network. Then the transient equivalent potential of an IG at the grid fault instant isderived. Sequence components of the short-circuit current in the network can be determined using theproposed technique. The correctness of the proposed method is verified using dynamic simulation.

Keywords: short circuit calculation; induction generator; symmetrical components; rotor slip;steady-state equivalent circuit; distribution network

1. Introduction

The increased penetration of renewable power has resulted in more distributed generators(DGs) embedded in distribution networks. The integration of large-scale DGs into the distributionnetwork changes the distribution of power flow and short-circuit currents, and leads the short-circuitcurrent contribution of the DGs to affect the power system protection and reclosing [1]. DGs includesynchronous generators, induction generators (IGs), and other power sources with electronic interfaces;of these types, the squirrel-cage IG has received increased attention in distribution networks becauseof its low cost, small size, and low maintenance requirements [2]. When short-circuit faults occur,IGs are unable to maintain their terminal voltage without an external excitation current, becausethey have different short-circuit current characteristics compared with synchronous generators [3].IG technology is based on the relatively mature induction motor (IM), and the difference is that theIG tends to excessively accelerate instead of the IM stalling that occurs during faults. Short-circuitcalculation of the IM usually uses the voltage source equivalent method [4]. The similar method usedfor IG cannot calculate the short-circuit currents accurately during the fault process, because it doesnot consider the electromagnetic transient characteristics of IGs [5,6]. Therefore, understanding thedynamic characteristics and short-circuit current calculation of IGs under different fault conditions isessential. This work aims to study the short-circuit calculation of a multi-IG distribution network.

Surge current in the stator windings of IGs is driven mainly by the stator transient DC fluxlinkage. At the same time, the extra transient AC component of the stator current is produced by

Energies 2016, 9, 277; doi:10.3390/en9040277 www.mdpi.com/journal/energies

Page 3: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 2 of 21

the rotor flux linkage when a short-circuit fault occurs in the distribution network. The short-circuitbehavior of IGs has been extensively investigated using dynamic simulation software [7–9], physicalexperiments [10] and real-time simulation tools [11]. With the assumption of a fixed rotor speedduring fault, an approximate formula based on the generator state equations at dq0 coordinationhas been derived for three-phase short-circuit current calculation in [12]. Owing to the short-currentcontribution of the healthy phases during an unsymmetrical faults, the short-circuit characteristicsof IGs under symmetrical and unsymmetrical faults are different from one other. For unsymmetricalvoltage sags, the analytic expressions of transient stator voltage and current and transient rotor voltageand current have been derived in [13–15]. The above studies are limited to the mathematical andtime-domain transient studies. Although the short-circuit current of a distribution network withIGs can be determined by using simulation software, but a very long computation time is required.Additionally, the physical transient process of IGs during a fault cannot be explained theoretically.The implicit simulation is usually adopted for the numerical stability and errors and it is difficult toobtain the analytical relationship between the short-circuit current of IGs and their parameters. A moreaccurate sequence network circuit representation of IG is derived for the short-circuit calculationson the basis of the sequence network in [16]. The transient reactance and short-circuit current of asingle fixed-speed IG is studied, however the work cannot calculate the trend of short-circuit currentchanging with time and the short-circuit current of multiple fixed-speed and variable-speed IGs. Thosestudies are not suitable for fault analysis in a distribution network with multiple IGs because of withoutconsidering the coupling between the short-circuit current of IGs and the distribution network.

The fundamental frequency components of the current and voltage in a power system for the firstfew cycles after a fault are the primary focus of protection engineers. The sequence component methodis usually adopted to calculate the short-circuit current because of the smaller computational burdenand problem size compared with those of other methods [17]. The present work analyzes the transientbehavior of fixed-speed and variable-speed IGs when an unsymmetrical fault occurs in the distributionnetwork and the sequence components current source models of fixed-speed and variable-speed IGsconsidering the rotor slip change during a fault is established. The terminal voltage and short-circuitcurrent responses of IGs under different integrated capacity, with and without considering slip changeare investigated. Then an analytical method to calculate the shortcircuit currents of a multi-IG systembased on the current source model of IG and the parameters of the distribution network is thenproposed. The technique is a significant improvement of the one in [16] and can significantly reducecomputational burden. The method is verified using the simulation software PSCAD/EMTDC whereIGs are presented by the fifth-order differential model. The errors between analytical and simulationresults are analyzed.

2. Sequence Component Current Model of Induction Generators (IGs)

2.1. Stator and Rotor Flux of IGs during Grid Faults

All parameters in this paper are per unit. The stator short-circuit current of the IG is determinedby the stator and rotor fluxes when an unsymmetrical fault occurs. The stator and rotor fluxes of IGare not affected by the zero-sequence component of the voltage [13], whereas the forced sinusoidalcomponent is driven only by the positive and negative sequence components of the IG terminal voltage.With the motor convention, the stator voltage equation of the IG under an unsymmetrical fault using aspace vector can be written as:

usptq “ u1sptq ` u2sptq “.

U1sejωst `.

U2se´jωst “ Rsri1sptq ` i2sptqs `ddtrψ1sptq `ψ2sptqs (1)

where u1s(t) and u2s(t) are the positive and negative voltage space vectors, i1s(t) and i2s(t) are thepositive and negative current space vectors, Rs is the stator resistance, ψ1s(t) and ψ2s(t) are the positiveand negative fluxes after faults,

.U1s and

.U2s are the sequence component phasors of the stator voltage,

Page 4: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 3 of 21

andωs is the synchronous electric angular velocity. When the stator resistance is disregarded, the forcedcomponents of the stator flux can be expressed as ψ1s(t) =

.U1sejωstjωs and ψ2s(t) = ´

.U2se´jωstjωs

by solving Equation (1). According to the flux linkage conservation, the post-fault stator flux alsocontains a DC component. Assuming the normal operation voltage us(t) =

.Usejωst, then the stator

post-fault flux linkage ψs(t) of IG can be given as:

ψsptq “

.U1sjωs

ejωst ´

.U2s

jωse´jωst ` r

.Us

jωs´ p

.U1sjωs

´

.U2s

jωsqse´tTs (2)

where Ts = (Ls ´ Lm2/Lr)/Rs is the stator time constant, Lm is the excitation inductance, Ls = Lls + Lm,

Lr = Llr + Lm, and Lls and Llr are the leakage inductances of stator and rotor. The post-fault forcedflux components in the stator are the steady-state response, and the positive and negative forcedcomponents in the rotor can be derived through the steady-state equivalent circuits in Figure 1. Therelationship between the rotor current

.I1r,

.I2r and the stator current

.I1s,

.I2s can be expressed as follows:

.I1r “

´jωsLm.I1s

Rrs` jωsLr,

.I2r “

jωsLm.I2s

Rrp2´ sq ´ jωsLr(3)

Energies 2016, 9, 277 3 of 20

positive and negative fluxes after faults, U1s and 2sU are the sequence component phasors of the

stator voltage, and ωs is the synchronous electric angular velocity. When the stator resistance is

disregarded, the forced components of the stator flux can be expressed as ψ1s(t) = sj t

sU e j

1s and

ψ2s(t) = sj t

sU e j

2s by solving Equation (1). According to the flux linkage conservation, the

post-fault stator flux also contains a DC component. Assuming the normal operation voltage us(t) = sj t

sU e , then the stator post-fault flux linkage ψs(t) of IG can be given as:

/( ) [ ( )]s s sj t j t t T1s 2s s 1s 2s

s s s s s

U U U U Ut e e e

j j j j j

ψs (2)

where Ts = (Ls − Lm2/Lr)/Rs is the stator time constant, Lm is the excitation inductance, Ls = Lls + Lm, Lr =

Llr + Lm, and Lls and Llr are the leakage inductances of stator and rotor. The post-fault forced flux

components in the stator are the steady-state response, and the positive and negative forced

components in the rotor can be derived through the steady-state equivalent circuits in Figure 1.

The relationship between the rotor current 1rI ,

2rI and the stator current 1sI ,

2sI can be

expressed as follows:

, (2 )

s m 1s s m 2s

1r 2r

r s r r s r

j L I j L II I

R s j L R s j L

(3)

Rs jωsLls jωsLlr

jωsLm rR

s

1rI 1sI

1sU

Rs -jωsLls -jωsLlr

-jωsLm 2

rR

s

2rI 2sI

2sU

(a) (b)

Figure 1. Positive and negative sequence steady-state equivalent circuits of an IG: (a) Positive

sequence circuit, (b) Negative sequence circuit.

where Rr is the rotor resistance, the rotor slip s = (ωs − ωr)/ωs, and ωr is the rotor angular velocity.

Combining ψs(t) = Lsis(t) + Lmir(t) and ψr(t) = Lmis(t) + Lrir(t), the post-fault forced components in the

rotor can be calculated as follows:

2

2

( )( ) ( ) ( )

( )

(2 ) ( )( ) ( ) ( )

(2 ) ( )

m r 1s

1r 1rs 1s

s r s s r m

m r 2s

2r 2rs 2s

s r s s r m

L R s tt s t

L R s j L L L

L R s tt s t

L R s j L L L

ψψ ψ

ψψ ψ

(4)

With a 3MW IG (the parameters are given in [18]) as an example, Figure 2 illustrates the

amplitude and phase characteristics of the positive and negative sequence correlation coefficients

η1rs and η2rs in Equation (4) between the stator and rotor flux. The amplitude of η1rs is near 1.0 when

the rotor slip is small in the normal operation [2]. When the slip drops to −0.1 during the fault, the

amplitude of η1rs will decrease by 90%, as shown in Figure 2. This decrease indicates that a small slip

change has a significant influence on the positive sequence forced rotor flux in the rotor. Therefore

the slip change should be taken into consideration in the rotor flux calculation.

The negative sequence flux component in rotor windings induced by the stator negative

sequence forced flux can be neglected, because η2rs is near zero under the different rotor slips for a

fixed-speed IG in Figure 2a. However, there are still negative sequence short-circuit currents of IGs

caused by the grid negative sequence voltages, especially, the negative sequence current of a

variable-speed IG is mainly influenced by the control structures and objectives in its machine side

and line side converters [19]. The rotor resistance of a variable-speed IG will increase significantly

Figure 1. Positive and negative sequence steady-state equivalent circuits of an IG: (a) Positive sequencecircuit, (b) Negative sequence circuit.

where Rr is the rotor resistance, the rotor slip s = (ωs ´ωr)/ωs, andωr is the rotor angular velocity.Combining ψs(t) = Lsis(t) + Lmir(t) and ψr(t) = Lmis(t) + Lrir(t), the post-fault forced components in therotor can be calculated as follows:

ψ1rptq “LmRrs¨ψ1sptq

LsRrs`jωspLs Lr´L2mq“ η1rspsqψ1sptq

ψ2rptq “LmRrp2´sq¨ψ2sptq

LsRrp2´sq´jωspLs Lr´L2mq“ η2rspsqψ2sptq

(4)

With a 3MW IG (the parameters are given in [18]) as an example, Figure 2 illustrates the amplitudeand phase characteristics of the positive and negative sequence correlation coefficients η1rs and η2rs inEquation (4) between the stator and rotor flux. The amplitude of η1rs is near 1.0 when the rotor slipis small in the normal operation [2]. When the slip drops to ´0.1 during the fault, the amplitude ofη1rs will decrease by 90%, as shown in Figure 2. This decrease indicates that a small slip change has asignificant influence on the positive sequence forced rotor flux in the rotor. Therefore the slip changeshould be taken into consideration in the rotor flux calculation.

The negative sequence flux component in rotor windings induced by the stator negative sequenceforced flux can be neglected, because η2rs is near zero under the different rotor slips for a fixed-speed IGin Figure 2a. However, there are still negative sequence short-circuit currents of IGs caused by the gridnegative sequence voltages, especially, the negative sequence current of a variable-speed IG is mainlyinfluenced by the control structures and objectives in its machine side and line side converters [19].The rotor resistance of a variable-speed IG will increase significantly after its crowbar protection

Page 5: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 4 of 21

activation during grid faults and the magnitude of η2rs will stay in the range of 0.2–0.3 pu underdifferent rotor slips, as shown in Figure 2b. In this figure, the rotor resistance rises to 25 times that ofthe fixed-speed IG, and so a non-ignorable flux component in the rotor windings of a variable-speedIG can be generated by the negative sequence component of the stator flux. Besides the couplingdifferences of flux forced components between fixed-speed and variable-speed IGs, the decay timeconstant of the rotor flux DC component, Tr = (Lr ´ Lm

2/Ls)/Rr, will also be changed by increase inrotor resistance of variable-speed IGs during a grid fault.

Energies 2016, 9, 277 4 of 20

after its crowbar protection activation during grid faults and the magnitude of η2rs will stay in the

range of 0.2–0.3 pu under different rotor slips, as shown in Figure 2b. In this figure, the rotor

resistance rises to 25 times that of the fixed-speed IG, and so a non-ignorable flux component in the

rotor windings of a variable-speed IG can be generated by the negative sequence component of the

stator flux. Besides the coupling differences of flux forced components between fixed-speed and

variable-speed IGs, the decay time constant of the rotor flux DC component, Tr = (Lr − Lm2/Ls)/Rr, will

also be changed by increase in rotor resistance of variable-speed IGs during a grid fault.

(a)

(b)

Figure 2. Positive and negative sequencecorrelation coefficients between stator and rotor flux:

(a) a fixed-speed IG, (b) a variable-speed IG.

The stator flux ψs(t) has both the positive and negative sequence forced components ψ1s(t) and

ψ2s(t) and the DC component ψdcs(t) in Equation (2). The reverse rotation flux with the rotor speed

will be generated in the rotor windings because of ψdcs(t) cutting the rotor windings. The stator flux

DC component is difficult to analyze in the stator reference frame, but it can be discussed in the

rotor side by the frequency transformation [2]. The equivalent circuit in the rotor reference frame

for the stator flux DC component is shown in Figure 3, where dcsI and

dcrI are the DC components

of the stator and rotor currents, and dcsU is a virtual voltage caused by the stator flux DC

component. With the relationship of the stator current dcsI and the rotor current

dcrI in Figure 3,

the rotor flux component ψdcr(t) caused by the stator flux DC component ψdcs(t) can be obtained as:

0

90

80

70

60

50

40

30

20

10

- 0. 1 - 0. 08 - 0. 06 - 0. 04 - 0. 02 0

Ph

ase

deg 2rs

1rs

s

M

0.8

0.7

0.6

0.5

0.4

0.3

0.2

0.1

0-0.1 -0. 08 -0. 06 -0. 04 -0. 02 0

ag

nit

ud

e/p

u 2rs

1rs

0.9

s

/

-0.2 -0.2 -0.1 0 0.1 0.2 0.3

-80

-60

-40

-20

0

20

40

60

80

0.9

0.8

0.7

0.6

0.5

0.4

0.3

0.2

0.1

0

Mag

nit

ud

e/p

u

-0.1 0 0.1 0.2 0.3

s s

Ph

ase

deg2rs

1rs

2rs

1rs

/

Figure 2. Positive and negative sequencecorrelation coefficients between stator and rotor flux: (a) afixed-speed IG, (b) a variable-speed IG.

The stator flux ψs(t) has both the positive and negative sequence forced components ψ1s(t) andψ2s(t) and the DC component ψdcs(t) in Equation (2). The reverse rotation flux with the rotor speedwill be generated in the rotor windings because of ψdcs(t) cutting the rotor windings. The stator fluxDC component is difficult to analyze in the stator reference frame, but it can be discussed in the rotorside by the frequency transformation [2]. The equivalent circuit in the rotor reference frame for thestator flux DC component is shown in Figure 3, where

.Idcs and

.Idcr are the DC components of the stator

and rotor currents, and.

Udcs is a virtual voltage caused by the stator flux DC component. With the

Page 6: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 5 of 21

relationship of the stator current.Idcs and the rotor current

.Idcr in Figure 3, the rotor flux component

ψdcr(t) caused by the stator flux DC component ψdcs(t) can be obtained as:

ψdcrptq “LmRr ¨ψdcsptq

LsRr ´ jωsp1´ sqpLsLr ´ L2mq“ ηdcrspsqψdcsptq (5)

Energies 2016, 9, 277 5 of 20

2

( )( ) ( ) ( )

j (1 )( )

m r dcs

dcrs dcs

s r s s r m

L R tt s t

L R s L L L

ψψψdcr (5)

Rs -jωrLls -jωrLlr

-jωrLm

dcrI dcsI

dcsU Rr

Figure 3. An equivalent circuit for stator flux DC component in the rotor reference frame.

The amplitude and phase characteristics of the DC component correlation coefficient ηdcrs in

Equation (5) between the stator and rotor fluxes are shown in Figure 4. The reverse rotation flux

component ψdcr(t) in the rotor windings of a fixed-speed IG is approximately zero because of its

small rotor resistance. Meanwhile, the amplitude changing range of ηdcrs for a variable-speed IG is

from 0.4 pu to 0.6 pu as the rotor slips increase. The rotor flux of variable-speed IG will also appear

as a significant reverse rotation component in the rotor flux.

-0.2 -0.1 0 0.1 0.2 0.30

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

-0.2 -0.1 0 0.1 0.2 0.30

10

20

30

40

50

60

70

80

90

Fixed-speed IG

Variable-speed IG

s

Mag

nit

ud

e/p

u

Fixed-speed IG

Variable-speed IG

s

Ph

ase

deg

/

Figure 4. DC component correlation coefficient between stator and rotor flux.

2.2. Sequence Component Current Model of Fixed-Speed IGs

Assuming the initial slip of a fixed-speed IG is s0 before the short-circuit fault occurrs, the rotor

flux linkage ψr(t) of the fixed-speed IG in the stator reference frame is derived as in Equation (6)

according to the flux linkage conservation:

/1s( ) ( ) ( )s r rj t t T j t1s s

1rs 1rs 0

s s

U U Ut s e s e e

j j

ψr (6)

where Tr = (Lr − Lm2/Ls)/Rr is the rotor time constant. With Equations (2) and (6) substituted into is(t) =

(Lrψs − Lmψr)/(LsLr − Lm2), the general expression for the post-fault stator short-circuit current of a

fixed-speed IG can be given as:

/

2

s

/2s

2 2

1( ) [ ( )] ( )

[ ( )]

s r r

s s

j t t T j t1s s 1s

s r m 1rs m 1rs 0

ss r m

j t t Ts 1s 2sr r

s s s ss r m s r m

U U Ut L L s e L s e e

j jL L L

U U U UL Le e

j j j jL L L L L L

i

(7)

Figure 3. An equivalent circuit for stator flux DC component in the rotor reference frame.

The amplitude and phase characteristics of the DC component correlation coefficient ηdcrs inEquation (5) between the stator and rotor fluxes are shown in Figure 4. The reverse rotation fluxcomponent ψdcr(t) in the rotor windings of a fixed-speed IG is approximately zero because of its smallrotor resistance. Meanwhile, the amplitude changing range of ηdcrs for a variable-speed IG is from0.4 pu to 0.6 pu as the rotor slips increase. The rotor flux of variable-speed IG will also appear as asignificant reverse rotation component in the rotor flux.

Energies 2016, 9, 277 5 of 20

2

( )( ) ( ) ( )

j (1 )( )

m r dcs

dcrs dcs

s r s s r m

L R tt s t

L R s L L L

ψψψdcr (5)

Rs -jωrLls -jωrLlr

-jωrLm

dcrI dcsI

dcsU Rr

Figure 3. An equivalent circuit for stator flux DC component in the rotor reference frame.

The amplitude and phase characteristics of the DC component correlation coefficient ηdcrs in

Equation (5) between the stator and rotor fluxes are shown in Figure 4. The reverse rotation flux

component ψdcr(t) in the rotor windings of a fixed-speed IG is approximately zero because of its

small rotor resistance. Meanwhile, the amplitude changing range of ηdcrs for a variable-speed IG is

from 0.4 pu to 0.6 pu as the rotor slips increase. The rotor flux of variable-speed IG will also appear

as a significant reverse rotation component in the rotor flux.

-0.2 -0.1 0 0.1 0.2 0.30

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

-0.2 -0.1 0 0.1 0.2 0.30

10

20

30

40

50

60

70

80

90

Fixed-speed IG

Variable-speed IG

s

Mag

nit

ud

e/p

u

Fixed-speed IG

Variable-speed IG

s

Ph

ase

deg

/

Figure 4. DC component correlation coefficient between stator and rotor flux.

2.2. Sequence Component Current Model of Fixed-Speed IGs

Assuming the initial slip of a fixed-speed IG is s0 before the short-circuit fault occurrs, the rotor

flux linkage ψr(t) of the fixed-speed IG in the stator reference frame is derived as in Equation (6)

according to the flux linkage conservation:

/1s( ) ( ) ( )s r rj t t T j t1s s

1rs 1rs 0

s s

U U Ut s e s e e

j j

ψr (6)

where Tr = (Lr − Lm2/Ls)/Rr is the rotor time constant. With Equations (2) and (6) substituted into is(t) =

(Lrψs − Lmψr)/(LsLr − Lm2), the general expression for the post-fault stator short-circuit current of a

fixed-speed IG can be given as:

/

2

s

/2s

2 2

1( ) [ ( )] ( )

[ ( )]

s r r

s s

j t t T j t1s s 1s

s r m 1rs m 1rs 0

ss r m

j t t Ts 1s 2sr r

s s s ss r m s r m

U U Ut L L s e L s e e

j jL L L

U U U UL Le e

j j j jL L L L L L

i

(7)

Figure 4. DC component correlation coefficient between stator and rotor flux.

2.2. Sequence Component Current Model of Fixed-Speed IGs

Assuming the initial slip of a fixed-speed IG is s0 before the short-circuit fault occurrs, the rotorflux linkage ψr(t) of the fixed-speed IG in the stator reference frame is derived as in Equation (6)according to the flux linkage conservation:

ψrptq “ η1rspsq

.U1sjωs

ejωst ` η1rsps0q

.Us ´

.U1s

jωse´tTr ejωrt (6)

Page 7: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 6 of 21

where Tr = (Lr ´ Lm2/Ls)/Rr is the rotor time constant. With Equations (2) and (6) substituted into

is(t) = (Lrψs ´ Lmψr)/(LsLr ´ Lm2), the general expression for the post-fault stator short-circuit current

of a fixed-speed IG can be given as:

isptq “ 1Ls Lr´L2

m

"

rLr ´ Lmη1rspsqs.

U1sjωs

ejωst ´ Lmη1rsps0q¨.

Us´.

U1sjωs

e´tTr ejωrt*

`Lr

Ls Lr´L2m

.U2s´jωs

e´jωst ` LrLs Lr´L2

mr

.Usjωs

´ p

.U1sjωs

´

.U2sjωsqse´tTs

(7)

The short-circuit current of the fixed-speed IG is composed of three components. The firstcomponent is the steady periodic component, which includes both positive and negative components.The second component decays exponentially with the time constant Tr and rotates withωr in the statorreference frame because of the natural rotor flux. The third component is the DC component decayingexponentially with the time constant Ts because of the natural stator flux. Given that the neutralpoint of a distribution network is commonly not grounded or grounded by arc-suppression coil, thezero sequence is not considered here. When a short-circuit fault occurs in distribution networks withmultiple IGs, the short-circuit currents of IGs inject into the distribution network in the form of avariable current source based on symmetrical components, and the DC component is not within thesymmetrical network.

The change law of the short-circuit current with time and the relation between the current andterminal voltage sequence components of IG can be determined by Equation (7). With a terminalthree-phase short circuit, the rotor speed after 10 cycles is less than 1.10 when a rated torque isgiven [20]. Thus the AC component of the short-circuit current rotating with ωr can be considereda synchronous frequency component. Assuming the slips of m sets of fixed-speed IGs are si (i = 1,2,. . . ,m), the positive and negative sequence phasors of the short-circuit current for the ith fixed-speedIG can be derived as in Equations (8) and (9):

.I1si “

1LsiLri ´ L2

mi

#

rLri ´ Lmiη1rsipsiqs

.U1sijωs

´Lmiη1rsipsi0q

.Usi ´

.U1si

jωse´tTri

+

(8)

.I2si “

Lri

LsiLri ´ L2mi

.U2si´jωs

(9)

2.3. Sequence Component Current Model of Variable-Speed IGs

Besides considering the effect of positive sequence forced component ψ1s(t) in the stator flux,the post-fault rotor flux of the variable-speed IG has to include the flux components produced bythe negative sequence forced component ψ2s(t) and the DC component ψdcs(t). According to the fluxlinkage conservation before and after a short-circuit fault occurs, the post-fault rotor flux ψr(t) of thevariable-speed IG in the stator reference frame can be given as:

#

ψrptq “ η1rspsq.

U1sjωs

ejωst ´ η2rspsq.

U2sjωs

e´jωst ` ηdcrspsqr.

Usjωs

´ p

.U1sjωs

´

.U2sjωsqse´tTs `ψr0e´tTr ejωr t

ψr0 “ η1rsps0q.

Us´.

U1sjωs

` η2rsps0q.

U2sjωs

´ ηdcrsps0qr.

Usjωs

´ p

.U1sjωs

´

.U2sjωsqs

(10)

The stator current can be obtained as is(t) = (Lrψs ´ Lmψr)/(LsLr ´ Lm2) through the relationships

among the flux and current in the stator and rotor windings. Combined with the formulas of ψs(t) andψr(t), the short-circuit current of a variable-speed IG can be written as:

isptq “ 1Ls Lr´L2

m

"

rLr ´ Lmη1rspsqs.

U1sjωs

ejωst ´ Lmψr0e´tTr ejωrt*

`Lr´Lmη2rspsq

Ls Lr´L2m

.U2s´jωs

e´jωst `Lr´Lmηdcrspsq

Ls Lr´L2m

r

.Usjωs

´ p

.U1sjωs

´

.U2sjωsqse´tTs

(11)

Page 8: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 7 of 21

The positive sequence steady component of the short-circuit current of variable-speed IG is thesame as that of fixed-speed IG, but the positive sequence steady component, transient decay ACcomponent rotoring with ωr, and DC component are different from those in Equation (7) becauseof the nonignorable flux correlation coefficients η2rs and ηdcrs In consideration of the AC componentrotoring withωr as a synchronous frequency component, the positive and negative sequence phasorsof the short-circuit current for the ith variable-speed IG can be derived as follows:

.I1si “

1Lsi Lri´L2

mi

"

rLri ´ Lmiη1rsipsiqs

.U1sijωs

´ Lmi

η1rsipsi0q

.Usi´

.U1si

jωs`η2rsipsi0q

.U2sijωs

´ηdcrsipsi0q

ˆ .Usijωs

´

.U1sijωs

`

.U2sijωs

˙

e´tTri

*

(12)

.I2si “

Lri ´ Lmiη2rsipsiq

LsiLri ´ L2mi

.U2si´jωs

(13)

According to the interaction among the stator short-circuit current, network equation and rotormovement equation, the terminal voltage and slip can be updated iteratively in each data windowduring the fault. The calculation process is similar with that of the simulation software. The IGs arerepresented by the analytical expressions including Equations (8), (9), (12) and (13) in the proposedmethod, while the simulation software adopts the fifth-order differential-algebraic equations asthe model of IGs. Then the time series for the positive and negative sequence components of theshort-circuit current can be determined based on the dynamic phasor and analytical expression duringthe fault process from sub-transient to steady-state.

3. Coupling Relationship between Short-Circuit Current of IGs and the Distribution Network

When the integrated capacity of IGs is small, the terminal voltages of IGs will drop to a steady-statevalue as soon as the fault occurs in a distribution network [13–15]. However, the terminal voltageswill be significantly changed by their own short-circuit current injections in a distribution networkwith high permeability of IGs. In this case, the coupling between short-circuit currents of IGs anddistribution network have to be considered. A distribution network with a short-circuit capacityof 240 MW is analyzed, and the short-circuit ratio (SCR) [21] between IG and network is 80. Thedynamic simulation and calculation results of a fixed-speed IG with a three-phase short-circuit fault atthe end of the feeder downstream are shown in Figure 5, where ε is the relative error of the calculationresults. By setting the impedance of the downstream feeder equal to the short-circuit impedance ofthe network, the voltage dip magnitude at the generator terminals during a fault can be fixed to aproportion p = 0.5 (the voltage changes from

.Us to p

.Us, where p is the proportion of the post-fault

voltage versus the pre-fault voltage), the rotor speed increases in a linear manner with a slope of(p2 ´ 1)Tm/(2H), where Tm = ´1.0 is the mechanical torque and H = 5.04 s is the inertia constant.

Energies 2016, 9, 277 7 of 20

2

( )ri i

smi

L L s UI

jL L L

m i 2rsi 2si2si

si ri

(13)

According to the interaction among the stator short-circuit current, network equation and rotor

movement equation, the terminal voltage and slip can be updated iteratively in each data window

during the fault. The calculation process is similar with that of the simulation software. The IGs are

represented by the analytical expressions including Equations (8), (9), (12) and (13) in the proposed

method, while the simulation software adopts the fifth-order differential-algebraic equations as the

model of IGs. Then the time series for the positive and negative sequence components of the

short-circuit current can be determined based on the dynamic phasor and analytical expression

during the fault process from sub-transient to steady-state.

3. Coupling Relationship between Short-Circuit Current of IGs and the Distribution Network

When the integrated capacity of IGs is small, the terminal voltages of IGs will drop to a

steady-state value as soon as the fault occurs in a distribution network [13–15]. However, the

terminal voltages will be significantly changed by their own short-circuit current injections in a

distribution network with high permeability of IGs. In this case, the coupling between short-circuit

currents of IGs and distribution network have to be considered. A distribution network with a

short-circuit capacity of 240 MW is analyzed, and the short-circuit ratio (SCR) [21] between IG and

network is 80. The dynamic simulation and calculation results of a fixed-speed IG with a

three-phase short-circuit fault at the end of the feeder downstream are shown in Figure 5, where ε is

the relative error of the calculation results. By setting the impedance of the downstream feeder equal

to the short-circuit impedance of the network, the voltage dip magnitude at the generator terminals

during a fault can be fixed to a proportion p = 0.5 (the voltage changes from sU to

spU , where p is

the proportion of the post-fault voltage versus the pre-fault voltage), the rotor speed increases in a

linear manner with a slope of (p2 − 1)Tm/(2H), where Tm = −1.0 is the mechanical torque and H = 5.04 s

is the inertia constant.

sI 1

/pu

0 .6

80 .

1 .0

1 .2

1 .4

1 .6

Variable slip

Initial slip

Zero slip

Simulation

1 .05 1 .1 1 .15 1 .20 .95 1 .0t / s

/%

t / s0 .95 1 .0 1 .05 1 .1 1 .15 1 .2

- 50

- 40

- 30

- 20

- 10

0

10

20

- 60

Figure 5. Positive and negative sequence correlation coefficients between stator and rotor flux of a

fixed-speed IG.

The short-circuit current can be calculated by substituting the pre-fault and post-fault terminal

voltages and slip variation of IGs into Equation (8). The calculation results under the variable slip

and fixed slip (including both the initial slip s0 = −0.0051 pu and zero slip) are shown in Figure 5. The

calculation error of fixed slip increases with time. The calculation accuracy with initial slip is above

that of zero slip, although its relative error can be over 10%. The comparison results show that the

calculation results with variable slip is much closer to the simulation results.

When a phase B to phase C fault occurs at the end of the feeder downstream, the sequence

components of the terminal voltage are 3 / 21s sU p U and / 22s sU p U , and the rotor speed

increases with the slope of (5p2/2 − 1)Tm/(2H), where Tm = −0.5. Figure 6 shows the sequence

Figure 5. Positive and negative sequence correlation coefficients between stator and rotor flux of afixed-speed IG.

Page 9: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 8 of 21

The short-circuit current can be calculated by substituting the pre-fault and post-fault terminalvoltages and slip variation of IGs into Equation (8). The calculation results under the variable slip andfixed slip (including both the initial slip s0 = ´0.0051 pu and zero slip) are shown in Figure 5. Thecalculation error of fixed slip increases with time. The calculation accuracy with initial slip is abovethat of zero slip, although its relative error can be over 10%. The comparison results show that thecalculation results with variable slip is much closer to the simulation results.

When a phase B to phase C fault occurs at the end of the feeder downstream, the sequencecomponents of the terminal voltage are

.U1s “ 3p2

.Us and

.U2s “ p2

.Us, and the rotor speed increases

with the slope of (5p2/2 ´ 1)Tm/(2H), where Tm = ´0.5. Figure 6 shows the sequence components ofthe short-circuit of fixed-speed and variable-speed IGs in the case of two-phase fault. The positive andnegative sequence components of short-circuit current of IG are extracted by a sequence filter based onthe second-order generalized integrators [22]. The output of filter is the instantaneous waveform ofpositive and negative sequence current, and then the RMS value of instantaneous waveform can becomputed through a RMS block.The negative sequence component I2s of fixed-speed IG reaches itssteady-state value directly and doesn’t change with the slip in Figure 6a, while I2s of variable-speed IGdecreases with the increase of fault duration because of the rising rotor speed in Figure 6b.

Energies 2016, 9, 277 8 of 20

components of the short-circuit of fixed-speed and variable-speed IGs in the case of two-phase fault.

The positive and negative sequence components of short-circuit current of IG are extracted by a

sequence filter based on the second-order generalized integrators [22]. The output of filter is the

instantaneous waveform of positive and negative sequence current, and then the RMS value of

instantaneous waveform can be computed through a RMS block.The negative sequence component

I2s of fixed-speed IG reaches its steady-state value directly and doesn’t change with the slip in Figure

6a, while I2s of variable-speed IG decreases with the increase of fault duration because of the rising

rotor speed in Figure 6b.

(a)

(b)

Figure 6. Two-phase short-circuit current with and without rotor slip change: (a) a fixed-speed IG,

(b) a variable-speed IG.

The steady-state short-circuit currents of variable-speed IGs in Figure 6b are less than that of

fixed-speed IGs because of the offsetting effect from the short-circuit currents caused by the positive

and negative sequence forced fluxes in rotor windings, which are markedly influenced by the rotor

resistance and the rotor speed. For the steady-state short-circuit currents, the signs of η1rs and η2rs

are minus in Equations (12) and (13) where the change of η1rs with rotor slip becomes slow and the

magnitude of η2rs stays in the range of 0.2–0.3 pu due to the rising of rotor resistance of

variable-speed IGs. The calculation results of fixed initialand zero slips can not match the real trend

of I2s of variable-speed IG during a grid fault. Although the calculation error with a fixed initial slip

(s0 = −0.0023 pu) is slightly reduced because of the smaller rotor slip differences compared to that of

zero slip, the errors are still larger than that with a variable slip in both cases of fixed-speed and

variable-speed IGs.

0.95 1 1.05 1.1 1.15 1.2

0.75

0.8

0.4

0.55

0.5

0.6

0.45

0.65

0.7

I 1s/

pu

Variable slip

Initial slip

Zero slip

Simulation

t/s

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

0.95 1 1.05 1.1 1.15 1.2

I 2s/

pu

t/s

0.95 1 1.05 1.1 1.15 1.20.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

0.95 1 1.05 1.1 1.15 1.20

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

Simulation

Variable slip

Initial slip

Zero slip

Simulation

Variable slip

Initial slip

Zero slip

I 1

s/p

u

t/s t/s

I 2s/

pu

Figure 6. Two-phase short-circuit current with and without rotor slip change: (a) a fixed-speed IG,(b) a variable-speed IG.

The steady-state short-circuit currents of variable-speed IGs in Figure 6b are less than that offixed-speed IGs because of the offsetting effect from the short-circuit currents caused by the positive

Page 10: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 9 of 21

and negative sequence forced fluxes in rotor windings, which are markedly influenced by the rotorresistance and the rotor speed. For the steady-state short-circuit currents, the signs of η1rs andη2rs are minus in Equations (12) and (13) where the change of η1rs with rotor slip becomes slowand the magnitude of η2rs stays in the range of 0.2–0.3 pu due to the rising of rotor resistance ofvariable-speed IGs. The calculation results of fixed initialand zero slips can not match the real trendof I2s of variable-speed IG during a grid fault. Although the calculation error with a fixed initial slip(s0 = ´0.0023 pu) is slightly reduced because of the smaller rotor slip differences compared to thatof zero slip, the errors are still larger than that with a variable slip in both cases of fixed-speed andvariable-speed IGs.

Figure 7 shows the terminal voltage and short-circuit current response of fixed-speed IGs with athree-phase fault at the end of feeder downstream when an IG, four IGs, and eight IGs are integratedinto a distribution network with a short-circuit capacity of 240 MW separately. Furthermore, the peakvalues I1sp of the short-circuit current of fixed-speedand variable-speed IGs under different SCRs areshown in the figure. A large difference is observed between the calculation results of fixed-speed IGsusing Equation (8) without considering the transient variation of terminal voltage and the simulationresults with a small SCR. According to the variation of I1sp with SCR, it is unnecessary to considerthe effect of the short-circuit current of IGs on their terminal voltage when SCR ě 20 for fixed-speedIGs and SCR ě 40 for variable-speed IGs. However, the current of IGs is determined by both thetransient characteristics of the IG generator and the power system network equations when SCR < 20for fixed-speed IGs and SCR < 40 for variable-speed IGs.

Energies 2016, 9, 277 9 of 20

Figure 7 shows the terminal voltage and short-circuit current response of fixed-speed IGs with a

three-phase fault at the end of feeder downstream when an IG, four IGs, and eight IGs are integrated

into a distribution network with a short-circuit capacity of 240 MW separately. Furthermore, the

peak values I1sp of the short-circuit current of fixed-speedand variable-speed IGs under different

SCRs are shown in the figure. A large difference is observed between the calculation results of

fixed-speed IGs using Equation (8) without considering the transient variation of terminal voltage

and the simulation results with a small SCR. According to the variation of I1sp with SCR, it is

unnecessary to consider the effect of the short-circuit current of IGs on their terminal voltage when

SCR ≥ 20 for fixed-speed IGs and SCR ≥ 40 for variable-speed IGs. However, the current of IGs is

determined by both the transient characteristics of the IG generator and the power system network

equations when SCR < 20 for fixed-speed IGs and SCR < 40 for variable-speed IGs.

I 1s/

pu

I 1sp

/pu

U1s

/pu

SCR

1.1

1.2

1.5

1.6

1.4

1.3

1

0.5

0.6

0.9

1

0.8

0.7

0.41 1.05 1.1 1.21.15 1 1.05 1.1 1.21.15

t/s t/s

CalculationSCR=80SCR=20SCR=10

Fixed-speed IG Fixed-speed IG

SCR=80SCR=20SCR=10

0 20 40 60 800.8

1

1.2

1.4

1.6

1.8

1.9

Variable-speed IG

Fixed-speed IG

Figure 7. Short-circuit current and terminal voltage of IGs with different penetration levels.

When a short-circuit fault occurs at a distribution network, the surge current in the stator

winding is driven mainly by the stator transient DC flux linkage. At the same time, the transient AC

component of the stator current is produced by the rotor flux linkage. The injection of short-circuit

current changes the distribution of nodal voltages in the distribution network, and the terminal

voltage of IGs changes with the decaying current, and then affects the short-circuit current in reverse.

Therefore, besides the slip change, the interaction of the injection current of IGs and the network

equations for short-circuit calculation of a multi-IG system must be thoroughly considered.

The coupling relation between the short-circuit current of IG and the distribution network is

shown in Figure 8, where only the current source model of IG (at bus i) is given. Bus 1 is the main

source node of distribution network, sE , Z1s and Z2s are the voltages (i.e., the positive and negative

sequence of the main source), 1fU , 2fU , 1fI , and 2fI are the sequence components of voltage and

current at the fault bus f. When a fault occurs at bus f, the initial short-circuit current can be

determined by the initial conditions, and then the voltage can be updated in the next step by

substituting the current into network equations. Meanwhile, the electromagnetic power is calculated

to update the slip.

Figure 7. Short-circuit current and terminal voltage of IGs with different penetration levels.

When a short-circuit fault occurs at a distribution network, the surge current in the stator windingis driven mainly by the stator transient DC flux linkage. At the same time, the transient AC componentof the stator current is produced by the rotor flux linkage. The injection of short-circuit current changesthe distribution of nodal voltages in the distribution network, and the terminal voltage of IGs changeswith the decaying current, and then affects the short-circuit current in reverse. Therefore, besides theslip change, the interaction of the injection current of IGs and the network equations for short-circuitcalculation of a multi-IG system must be thoroughly considered.

The coupling relation between the short-circuit current of IG and the distribution network isshown in Figure 8, where only the current source model of IG (at bus i) is given. Bus 1 is the mainsource node of distribution network,

.Es, Z1s and Z2s are the voltages (i.e., the positive and negative

sequence of the main source),.

U1 f ,.

U2 f ,.I1 f , and

.I2 f are the sequence components of voltage and

current at the fault bus f. When a fault occurs at bus f, the initial short-circuit current can be determined

Page 11: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 10 of 21

by the initial conditions, and then the voltage can be updated in the next step by substituting thecurrent into network equations. Meanwhile, the electromagnetic power is calculated to update the slip.Energies 2016, 9, 277 10 of 20

+

-

Z1s

1i +

-+

-

Z2s

1i

f

N1

N2

Eq. (8)

or (12)

Eq. (9)

or (13)

sE

1fI

1fU1siU

+

-2siU+

-

f

2fI

2fU

1siI

2siI

1siU

1siI

2siU

2siI

Power

Calculation

Slip

Recursion

2si 2si, U I

1si 1si, U I

Pei

sri

Figure 8. Schematic diagram of coupling relation between short-circuit current of IGs and

distribution network.

The terminal voltage and slip can be considered constant in the step because the iterative step is

very small. At the initial time of fault, the initial value of short-circuit current of IGs can be obtained

according to the unchanged transient potentialof IGs at the fault moment, and their terminal

voltages during the first iterative step can also be determined by combining the network equations

and the short-circuit current injection of IGs. Then the voltages of the last iterative step can be

substituted into Equations (8) and (9) for a fixed-speed IG, as well as Equations (12) and (13) for a

variable-speed IG, to achieve the short-circuit currents of IGs at the next iterative step. The positive

sequence currents of fixed-speed and variable-speed IGs exponentially decayin terms of the rotor

time constant in Equations (8) and (12), whereas the negative sequence current of variable-speed IG

changes only with the rotor slip in Equation (13). The terminal voltages and rotor slips can be

calculated at this iterative step and used to determine the short-circuit currents of IGs by the

equations at the next iterative step. The method to determine the sequence components of

short-circuit current using the current source model of IGs will be given in the next section.

4. Short-Circuit Calculation of the Multi-IG Network

4.1. Initial Value Calculation for Short-Circuit CurrentSequence Components of IGs

Substituting ψs(t)/dt and dψr(t)/dt, which are determined by the stator and rotor voltage

equations, into the differential of is = [Lrψs(t) − Lmψr(t)]/(LsLr − Lm2) as:

2 ( ) ( ) ( )( ) ( ) [ ( ) ( )]s r m s s m mr

s s s r r r r

r r r

L L L d t d t L Ld tt R t j t R t

L dt dt L dt L

i ψ ψu i ψ i (14)

Equation (14) can be modified using ir(t) = [Lsψr(t) − Lmψs(t)]/(LsLr − Lm2).The expression of us(t)

can be then written as:

2

2 2

( )( ) ( ) [( ) ( ) ( )]s r m s m r s r m

s s s r r s

r r s r m s r m

L L L d t L R L R Lt R t j t t

L dt L L L L L L L

iu i ψ ψ (15)

The fluxes ψs(t) and ψr(t) remain unchanged at the moment the fault occurs. Thus, the third part

of Equation (15) can be defined as the transient equivalent potential of IG. Assume there are m sets of

IGs in the distribution network, and the integrated buses of IGs are from bus 2 to bus m + 1. The

transient equivalent potential of the ith IG can be described as follows:

2

s ( )1si i s

L L LE U Z I U R j I

L

si ri m isi si si si si

ri

(16)

Figure 8. Schematic diagram of coupling relation between short-circuit current of IGs anddistribution network.

The terminal voltage and slip can be considered constant in the step because the iterative step isvery small. At the initial time of fault, the initial value of short-circuit current of IGs can be obtainedaccording to the unchanged transient potentialof IGs at the fault moment, and their terminal voltagesduring the first iterative step can also be determined by combining the network equations and theshort-circuit current injection of IGs. Then the voltages of the last iterative step can be substituted intoEquations (8) and (9) for a fixed-speed IG, as well as Equations (12) and (13) for a variable-speed IG,to achieve the short-circuit currents of IGs at the next iterative step. The positive sequence currentsof fixed-speed and variable-speed IGs exponentially decayin terms of the rotor time constant inEquations (8) and (12), whereas the negative sequence current of variable-speed IG changes only withthe rotor slip in Equation (13). The terminal voltages and rotor slips can be calculated at this iterativestep and used to determine the short-circuit currents of IGs by the equations at the next iterative step.The method to determine the sequence components of short-circuit current using the current sourcemodel of IGs will be given in the next section.

4. Short-Circuit Calculation of the Multi-IG Network

4.1. Initial Value Calculation for Short-Circuit CurrentSequence Components of IGs

Substituting ψs(t)/dt and dψr(t)/dt, which are determined by the stator and rotor voltageequations, into the differential of is = [Lrψs(t) ´ Lmψr(t)]/(LsLr ´ Lm

2) as:

LsLr ´ L2m

Lr

disptqdt

“dψsptq

dt´

Lm

Lr

dψrptqdt

“ usptq ´ Rsisptq ´Lm

Lrrjωrψrptq ´ Rrirptqs (14)

Equation (14) can be modified using ir(t) = [Lsψr(t) ´ Lmψs(t)]/(LsLr ´ Lm2). The expression of

us(t) can be then written as:

usptq “ Rsisptq `LsLr ´ L2

mLr

disptqdt

`Lm

Lrrpjωr ´

RrLs

LsLr ´ L2mqψrptq `

RrLm

LsLr ´ L2m

ψsptqs (15)

The fluxes ψs(t) and ψr(t) remain unchanged at the moment the fault occurs. Thus, the third partof Equation (15) can be defined as the transient equivalent potential of IG. Assume there are m sets

Page 12: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 11 of 21

of IGs in the distribution network, and the integrated buses of IGs are from bus 2 to bus m + 1. Thetransient equivalent potential of the ith IG can be described as follows:

.E1

si “.

Usi ´ Z11si.Isi “

.Usi ´ pRsi ` jωs

LsiLri ´ L2mi

Lriq

.Isi (16)

where Z11si is the positive transient impedance of the ith IG. Given that the three phase quantitiesform a balanced system during normal operation, the pre-fault voltage and current can be calculatedusing the Newton-Raphson method, then the transient equivalent potential can be determined. Withthe iteration step for short-circuit calculation defined as ∆t = T/2 (T = 0.02s), the initial value of theshort-circuit current can be determined by the unchanged transient potential at the first step. Addingthe positive and negative impedances Z11si “ Z12si of IGs into the original positive and negative matrixZ1 and Z2 of the network to form the node-impedance matrixes Z1

1 and Z21 of n ˆ n order. The normal

operation voltage of each node:

.Up0q“ Z11

.Ip0q“ Z11r

.I1,

.Ip0q2 , ¨ ¨ ¨ ,

.Ip0qm`1, 0, ¨ ¨ ¨ , 0s

T(17)

where.I1 “

.EsZ1s and

.Ip0qi “

.E1

siZ11si are the equivalent current of the main source and the Nortoncircuit of the ith IG respectively. The normal voltages of each node are equal to the pre-fault voltagesof each node in the network because the transient equivalent potential of IGs remains unchanged atthe first step. Taking a phase B to phase C fault at bus f for an example, the sequence components ofthe short-circuit current at the fault bus at the first iterative step can be calculated as:

.Ip1q1 f “ ´

.Ip1q2 f “

.Up1qf

Z11 f f ` Z12 f f ` z f“

.Up0qf

Z11 f f ` Z12 f f ` z f(18)

The voltage phasors of each node in the positive and negative sequence fault component networkscan be derived as Equation (19) using the superposition principle in fault analysis:

∆.

Up1q1 “ rZ111 f , ¨ ¨ ¨ , Z11i f ¨ ¨ ¨ , Z11n f s

Tp´

.Ip1q1 f q

∆.

Up1q2 “ rZ121 f , ¨ ¨ ¨ , Z12i f ¨ ¨ ¨ , Z12n f s

Tp´

.Ip1q2 f q

(19)

The post-fault voltage phasors are.

U1p1q1 “

.Up1q` ∆

.Up1q1 and

.U1p1q2 “ ∆

.Up1q2 , and the initial values

of the positive and negative sequence short-circuit current at the first step are given as:

.Ip1q1si p0q “

.U1p1q1i ´

.E1

siZ11si

,.Ip1q2si p0q “

.U1p1q2i

Z12si(20)

Given that the sequence components of the terminal voltage and the slip are unchanged at eachstep, the positive sequence component of the short-circuit current decays exponentially with the timeconstant Tr, while the negative component is unchanged according to Equations (8), (9), (12), and (13),The RMS of the negative sequence current in the first ∆t is rIp1q2si srms “ Ip1q2si p∆tq “ Ip1q2si p0q. The RMS ofthe positive sequence short-circuit current at the end of the first step can be derived by substituting.

U1p1q1i and si

(1) = si0 into Equations (8) and (12). The positive sequence component of the short-circuitcurrent at the first step is given as:

Ip1q1si ptq “rIp1q1si p∆tq´Ip1q1si p0qe

´∆tTri sIp1q1si p∆tq

Ip1q1si p∆tqp1´e´∆tTri q`rIp1q1si p0q´Ip1q1si p∆tqse´tTri

1´e´∆tTri“ Ap1qi Ip1q1si p∆tq ` Bp1qi rIp1q1si p0q ´ Ip1q1si p∆tqse´tTri (21)

Page 13: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 12 of 21

The first point of RMS values cannot reflect the maximum value of instantaneous waveform insimulation because the RMS computation has a time lag, while the calculation results of RMS currentsare widely used to identify the rating of electrical equipment, the selection of fuses and the settingof protective devices. The RMS of the positive sequence short-circuit current at the first step can bederived as follows: (the process is presentedin detail in Appendix A)

rIp1q1si srms “

g

f

f

f

e

rAp1qi Ip1q1si p∆tqs2`

TriT Bp1qi rIp1q1si p0q ´ Ip1q1si p∆tqs

!

4Ap1qi Ip1q1si p∆tq¨

r1´ e´Tp2Triqs ` Bp1qi rIp1q1si p0q ´ Ip1q1si p∆tqsp1´ e´TTriq

) (22)

4.2. Short-Circuit CurrentSequence Components of IGs during Grid Faults

When a fault occurs in the network with multiple IGs, the short-circuit currents of IGs inject intothe sequence network in the form of a dynamic current source based on its terminal voltage. Theinstantaneous electromagnetic power of IGs is made up of DC and double frequency components if theterminal voltage and current of the IGs contain both positive and negative components. The averageof the double-frequency component in a half cycle is zero, and so the average of the electromagneticpower at step k ´ 1 can be derived as Equation (23) by the terminal voltage and short-circuit current ofthe ith IG:

Ppk´1qei “ U1pk´1q

1i rIpk´1q1si srmscosϕpk´1q

1i `U1pk´1q2i rIpk´1q

2si srmscosϕpk´1q2i (23)

where ϕ1i(k´1) is the positive power factor angle

.U1pk´1q1i leading r

.Ipk´1q1si p∆tq `

.Ipk´1q1si p0qs/2, and

ϕ 2i(k´1) is the negative sequence power factor angle

.U1pk´1q2i leading

.Ipk´1q2si p0q. Solving the rotor

motion equation of IGs with the rectangular integral method can derive the slip of the ith IG atstep k as:

spkqi “ spk´1qi ´

∆t2Hi

rPpk´1q

ei

1´ spk´1qi

´ Tmis (24)

According to the currents.Ipk´1q1si p∆ tq and

.Ipk´1q2si p∆tq of IGi at the end of step k ´ 1, the node

voltage of the normal network at step k can be updated iteratively as:

.Upkq1 “ Z1

.Ipk´1q1si p∆tq “ Z1r

.I1,

.Ipk´1q1si p∆tq, ¨ ¨ ¨ ,

.Ipk´1q1spm`1qp∆tq, 0, ¨ ¨ ¨ , 0s

T

.Upkq2 “ Z2

.Ipk´1q2si p∆tq “ Z2r0,

.Ipk´1q2si p∆tq, ¨ ¨ ¨ ,

.Ipk´1q2spm`1qp∆tq, 0, ¨ ¨ ¨ , 0s

T (25)

The multiple IGs are equivalent to the current sources, and Z1 and Z2 are the original impedancematrixes of the distribution network. Owing to the negative short-circuit current of IGs injecting intothe network, the voltage at the fault node f in the normal network contains a negative sequence voltagecomponent. The sequence components of the short-circuit current at fault node f under a differentfault type can be derived using the boundary conditions at the fault node and the composite sequencenetwork with negative sequence voltage.

Taking a phase B to phase C fault through the impedance zf at the fault node f as an example, asshown in Figure 9, the sequence components of the short-circuit current at fault node f at step k can beexpressed as:

.Ipkq1 f “ ´

.Ipkq2 f “

.Upkq1 f ´

.Upkq2 f

Z1 f f ` Z2 f f ` z f(26)

The post-fault voltage phasors of each node in the positive and negative sequence fault componentnetwork at step k are as follows:

Page 14: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 13 of 21

∆.

Upkq1 “ rZ11 f , ¨ ¨ ¨ , Z1i f ¨ ¨ ¨ , Z1n f s

Tp´

.Ipkq1 f q

∆.

Upkq2 “ rZ21 f , ¨ ¨ ¨ , Z2i f ¨ ¨ ¨ , Z2n f s

Tp´

.Ipkq2 f q

(27)

The positive and negative sequence components of node voltages in the distribution network at

step k can be calculated as.

U1pkq1 “

.Upkq1 ` ∆

.Upkq1 and

.U1pkq2 “

.Upkq2 ` ∆

.Upkq2 by combining Equations (25)

and (27). Subsequently, the sequence components of the short-circuit current at step k can be obtained

using.

U1pkq1i , si

(k), and.

U1pkq2i .

Energies 2016, 9, 277 12 of 20

4.2. Short-Circuit CurrentSequence Components of IGs during Grid Faults

When a fault occurs in the network with multiple IGs, the short-circuit currents of IGs inject

into the sequence network in the form of a dynamic current source based on its terminal voltage. The

instantaneous electromagnetic power of IGs is made up of DC and double frequency components if

the terminal voltage and current of the IGs contain both positive and negative components. The

average of the double-frequency component in a half cycle is zero, and so the average of the

electromagnetic power at step k − 1 can be derived as Equation (23) by the terminal voltage and

short-circuit current of the ith IG:

( 1) ( 1) ( 1) ( 1) ( 1) ( 1) ( 1)

e 1 1s 1 2 2s 2[ ] cos [ ] cosk k k k k k k

i i i rms i i i rms iP U I U I (23)

where ϕ1i(k−1) is the positive power factor angle ( 1)

1

k

iU leading ( 1) ( 1)

1s 1s[ ( ) (0)]k k

i iI t I /2, and ϕ 2i(k−1) is

the negative sequence power factor angle ( 1)

2

k

iU leading ( 1)

2s (0)k

iI . Solving the rotor motion

equation of IGs with the rectangular integral method can derive the slip of the ith IG at step k as:

( 1)

( ) ( 1) e

m( 1)[ ]

2 1

k

k k i

i i ik

i i

Pts s T

H s

(24)

According to the currents ( 1)

1s ( )k

iI t and ( 1)

2s ( )k

iI t of IGi at the end of step k − 1, the node

voltage of the normal network at step k can be updated iteratively as:

( ) ( 1) ( 1) ( 1)

1 1 1s 1 1 1s 1s( 1)

( ) ( 1) ( 1) ( 1)

2 2 2s 2 2s 2s( 1)

( ) [ , ( ), , ( ),0, ,0]

( ) [0, ( ), , ( ),0, ,0]

k k k k T

i i m

k k k k T

i i m

t I I t I t

t I t I t

U Ζ I Ζ

U Ζ I Ζ (25)

The multiple IGs are equivalent to the current sources, and Z1 and Z2 are the original impedance

matrixes of the distribution network. Owing to the negative short-circuit current of IGs injecting into

the network, the voltage at the fault node f in the normal network contains a negative sequence

voltage component. The sequence components of the short-circuit current at fault node f under a

different fault type can be derived using the boundary conditions at the fault node and the

composite sequence network with negative sequence voltage.

Taking a phase B to phase C fault through the impedance zf at the fault node f as an example, as

shown in Figure 9, the sequence components of the short-circuit current at fault node f at step k can

be expressed as:

( ) ( )

1 2( ) ( )

1 2

1 2

k k

f fk k

f f

ff ff f

U UI I

Z Z z

(26)

The post-fault voltage phasors of each node in the positive and negative sequence fault

component network at step k are as follows:

( ) ( )

1 11 1 1 1

( ) ( )

2 21 2 2 2

[ , , , ] ( )

[ , , , ] ( )

k T k

f if nf f

k T k

f if nf f

Z Z Z I

Z Z Z I

U

U (27)

The positive and negative sequence components of node voltages in the distribution network at

step k can be calculated as ( ) ( ) ( )

1 1 1

k k k U U U and ( ) ( ) ( )

2 2 2

k k k U U U by combining Equations (25)

and (27). Subsequently, the sequence components of the short-circuit current at step k can be

obtained using ( )

1

k

iU , si(k),and ( )

2

k

iU .

Z1ff

zf

+

-( )

1

k

fU

Z2ff

+

-( )

2

k

fU

( )

1

k

fI ( )

2

k

fI2

zf

2

Figure 9. Composite sequence network of two-phase short-circuit with negative sequence voltage. Figure 9. Composite sequence network of two-phase short-circuit with negative sequence voltage.

4.3. Procedure of Short-Circuit Calculation

When a fault occurs at node f, the procedure for the short-circuit calculation of the distributionnetwork is summarized as follows:

Step 1: Form the original matrixes Z1 and Z2 of the pre-fault network without IGs, determine thepre-fault voltage

.Usi and stator current

.Isi of each IG according to the mechanical torque during normal

operation, and solve Equation (16) to obtain.E1

si.

Step 2: Add Z11si and Z12si to Z1 and Z2 to form the matrixes Z11 and Z2

1, obtain.

Up1q

by Equation (17)

and.

Up1q“

.Up0q

, and then determine.Ip1q1 f and

.Ip1q2 f according to the fault node and type.

Step 3: Solve Equation (19) to obtain ∆.

Up1q1 and ∆

.Up2q2 , determine

.U1p1q1 and

.U1p2q2 , and solve

Equation (20) to obtain.Ip1q1si p0q and

.Ip1q2si p0q.

Step 4: Solve Equation (8) for a fixed-speed IG, Equation (12) for a variable-speed IG with.

U1p1q1i and

si(1) to obtain

.Ip1q1si p∆ tq, determine the RMS of the positive and negative sequence components rIp1q1si srms

and rIp1q2si srms, set.

U1pk´1q1i =

.U1p1q1i ,

.U1pk´1q2i =

.U1p1q2i ,

.Ipk´1q1si =

.Ip1q1si and

.Ipk´1q2si =

.Ip1q2si , and then go to Step 5.

Step 5: Solve Equation (24) by calculating of Ppk´1qei using Equation (23) to obtain the slip vector s(k).

Step 6: Solve Equation (25) with Z1 and Z2 to obtain the voltage.

Upkq1 and

.Upkq2 of the normal network,

calculate.Ipkq1 f and

.Ipkq2 f , substitute them into Equation (27) to obtain ∆

.Upkq1 and ∆

.Upkq2 of the fault

component network, and determine the voltages.

U1pkq1 and

.U1pkq2 of each IG.

Step 7: Solve Equations (8) and (9) for a fixed-speed IG, Equations (12) and (13) for a variable-speed

IG with.

U1pkq1 , s(k) and

.U1pkq2 to obtain

.Ipkq1si p∆ tq and

.Ipkq2si p∆tq, substitute

.Ipkq1si p0q =

.Ipk´1q1si p∆tq and

.Ipkq1si p∆tq

into (22) to obtain rIpkq1si srms, and rIpkq2si srms =.Ipkq2si p∆tq.

Step 8: If k ď N (N = 20), set k = k + 1 and go to Step 5; otherwise, stop the iteration and output theRMS of sequence components of the short-circuit current of each IG.

5. Simulation Studies

The proposed method is applied to two 50 Hz distribution networks. The short-circuit currentsfor different fault locations are calculated. The results obtained from the proposed method are

Page 15: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 14 of 21

verified by the simulation using PSCAD/EMTDC. In the simulation, the model of the fixed-speedand variable-speed IGs is described by the stator and rotor voltage equations in the d-q axes referenceframe, which rotates at a synchronous speed, as well as the rotor swing and the converter controlequations. The 10 kV system with four 3 MW, 0.69 kV IGs is shown in Figure 10. The test systemparameters are shown in Appendix B.

Energies 2016, 9, 277 13 of 20

4.3. Procedure of Short-Circuit Calculation

When a fault occurs at node f, the procedure for the short-circuit calculation of the distribution

network is summarized as follows:

Step 1: Form the original matrixes Z1 and Z2 of the pre-fault network without IGs, determine the

pre-fault voltage siU and stator current

siI of each IG according to the mechanical torque during

normal operation, and solve Equation (16) to obtain siE .

Step 2: Add 1siZ and 2siZ to Z1 and Z2 to form the matrixes Z1′ and Z2′, obtain (1)

U by Equation (17)

and (1) (0)U U , and then determine (1)

1 fI and (1)

2 fI according to the fault node and type.

Step 3: Solve Equation (19) to obtain (1)

1U and (2)

2U , determine (1)

1U and (2)

2U , and solve

Equation (20) to obtain (1)

1s (0)iI and (1)

2s (0)iI .

Step 4: Solve Equation (8) for a fixed-speed IG, Equation (12) for a variable-speed IG with (1)

1iU and

si(1) to obtain (1)

1s ( )iI t , determine the RMS of the positive and negative sequence components (1)

1s[ ]i rmsI

and (1)

2s[ ]i rmsI , set ( 1)

1

k

iU = (1)

1iU , ( 1)

2

k

iU = (1)

2iU , ( 1)

1s

k

iI = (1)

1siI and ( 1)

2s

k

iI = (1)

2siI , and then go to Step 5.

Step 5: Solve Equation (24) by calculating of ( 1)

e

k

iP using Equation (23) to obtain the slip vector s(k).

Step 6: Solve Equation (25) with Z1 and Z2 to obtain the voltage ( )

1

kU and ( )

2

kU of the normal

network, calculate ( )

1

k

fI and ( )

2

k

fI , substitute them into Equation (27) to obtain ( )

1

kU and ( )

2

kU of

the fault component network, and determine the voltages ( )

1

kU and ( )

2

kU of each IG.

Step 7: Solve Equations (8) and (9) for a fixed-speed IG, Equations (12) and (13) for a variable-speed

IG with ( )

1

kU , s(k) and ( )

2

kU to obtain ( )

1s ( )k

iI t and ( )

2s ( )k

iI t , substitute ( )

1s (0)k

iI = ( 1)

1s ( )k

iI t and ( )

1s ( )k

iI t into (22) to obtain ( )

1s[ ]k

i rmsI , and ( )

2s[ ]k

i rmsI = ( )

2s ( )k

iI t .

Step8: If k ≤ N (N = 20), set k = k + 1 and go to Step 5; otherwise, stop the iteration and output the RMS

of sequence components of the short-circuit current of each IG.

5. Simulation Studies

The proposed method is applied to two 50 Hz distribution networks. The short-circuit currents

for different fault locations are calculated. The results obtained from the proposed method are

verified by the simulation using PSCAD/EMTDC. In the simulation, the model of the fixed-speed

and variable-speed IGs is described by the stator and rotor voltage equations in the d-q axes

reference frame, which rotates at a synchronous speed, as well as the rotor swing and the converter

control equations. The 10 kV system with four 3 MW, 0.69 kV IGs is shown in Figure 10. The test

system parameters are shown in Appendix B.

SubL2

10kV

240MVA

L3

IG1

3 4 6

T1

IG2

T2

PL1+jQL1 PL2+jQL2

ZLC1 ZLC2

PL5+jQL5

L4

IG3

T3

PL3+jQL3

ZLC3

2

L5IG4

PL4+jQL4

ZLC4

5

L1

1

Figure 10. Four-IG test system.

5.1. Three-Phase Short Circuit of Fixed-Speed IGs

When four IGs in Figure 10 are fixed-speed IGs, the short-circuit currents and slips of IG1 to IG4

when a three phase fault occurs at node 4 are shown in Figure 11, where the mechanical torques of

IGs are Tm2 = Tm3 = Tm4 = −1.0. The short-circuit currents rise to the peak value after the fault that

Figure 10. Four-IG test system.

5.1. Three-Phase Short Circuit of Fixed-Speed IGs

When four IGs in Figure 10 are fixed-speed IGs, the short-circuit currents and slips of IG1 to IG4when a three phase fault occurs at node 4 are shown in Figure 11, where the mechanical torques of IGsare Tm2 = Tm3 = Tm4 = ´1.0. The short-circuit currents rise to the peak value after the fault that occurrsat t = 1.0s, and then transition to the steady state with the change of terminal voltages and slips. Thesimulation results are clearly accordant with the calculated results using the analytical method.

Energies 2016, 9, 277 14 of 20

occurrs at t = 1.0s, and then transition to the steady state with the change of terminal voltages and slips.

The simulation results are clearly accordant with the calculated results using the analytical method.

I 1s/

pu

0

0.5

1

1.5

2

2.5

3

1 1.05 1.1 1.15 1.2 1 1.05 1.1 1.15 1.2

-0.04

-0.035

-0.03

-0.025

-0.02

-0.015

-0.01

-0.005

0

s/pu

t/s t/s

Simulation

Analytical

IG1

IG1

IG2

IG2

IG3

IG3

IG4

IG4

Figure 11. Short-circuit currents and rotor slips of fixed-speed IGs when three-phase short-circuit

occurs at bus 4.

Figure 11 shows that the peak value I1sp occurs at the second point of calculated results because

I1s is the RMS short-circuit current for a half cycle. The peak value I1sp and steady-state value I1ss can

be given both by simulation and calculation, as shown in Table 1, where the short-circuit current

value of the 10th cycle is selected as the steady-state value. The proposed method has a relative error

within ±6%. The voltages of IG3, IG2, IG1, and IG4 increase in turn while their currents decrease in

turn because of the increasing electrical distance from IG to the fault node. Given that the voltage

drop of IG4 at the adjacent feeder is the smallest, the peak value and steady-state value of IG4 are

near each other.

Table 1. Short-circuit currents of fixed-speed IGs when three-phase short circuit occurs at bus 4.

Induction Generators IG1 IG2 IG3 IG4

Analytical I1sp (pu) 1.642 2.079 2.605 1.317

I1sp Simulation I1sp (pu) 1.745 2.187 2.716 1.369

Relative error (%) −5.90 −4.93 −4.09 −3.80

Analytical I1ss (pu) 1.426 1.363 1.297 1.308

I1ss Simulation I1ss (pu) 1.434 1.414 1.321 1.361

Relative error (%) −0.56 −3.61 −1.82 −3.89

Figure 12 shows the calculation and simulation results of the short-circuit current with the

variable mechanical torque of one IG and a 0.1 change step under the assumption that the

mechanical torques of the other three IGs remain unchanged. The simulated and calculated results

with the proposed method are basically similar in the figure. The short-circuit currents calculated

with zero mechanical torque are the same as the results with zero slips, which do not depend on the

torque. The errors of the short-circuit currents with zero slips to the currents with different torques

are shown in Figure 13. The relative errors of the peak and steady state value increase with the

increase of −Tm.

Figure 11. Short-circuit currents and rotor slips of fixed-speed IGs when three-phase short-circuitoccurs at bus 4.

Figure 11 shows that the peak value I1sp occurs at the second point of calculated results becauseI1s is the RMS short-circuit current for a half cycle. The peak value I1sp and steady-state value I1sscan be given both by simulation and calculation, as shown in Table 1, where the short-circuit currentvalue of the 10th cycle is selected as the steady-state value. The proposed method has a relative errorwithin ˘6%. The voltages of IG3, IG2, IG1, and IG4 increase in turn while their currents decrease inturn because of the increasing electrical distance from IG to the fault node. Given that the voltagedrop of IG4 at the adjacent feeder is the smallest, the peak value and steady-state value of IG4 are neareach other.

Page 16: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 15 of 21

Table 1. Short-circuit currents of fixed-speed IGs when three-phase short circuit occurs at bus 4.

Induction Generators IG1 IG2 IG3 IG4

Analytical I1sp (pu) 1.642 2.079 2.605 1.317I1sp Simulation I1sp (pu) 1.745 2.187 2.716 1.369

Relative error (%) ´5.90 ´4.93 ´4.09 ´3.80

Analytical I1ss (pu) 1.426 1.363 1.297 1.308I1ss Simulation I1ss (pu) 1.434 1.414 1.321 1.361

Relative error (%) ´0.56 ´3.61 ´1.82 ´3.89

Figure 12 shows the calculation and simulation results of the short-circuit current with the variablemechanical torque of one IG and a 0.1 change step under the assumption that the mechanical torquesof the other three IGs remain unchanged. The simulated and calculated results with the proposedmethod are basically similar in the figure. The short-circuit currents calculated with zero mechanicaltorque are the same as the results with zero slips, which do not depend on the torque. The errors of theshort-circuit currents with zero slips to the currents with different torques are shown in Figure 13. Therelative errors of the peak and steady state value increase with the increase of ´Tm.Energies 2016, 9, 277 15 of 20

-1 -0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 01

1.2

1.4

1.6

1.8

2

2.2

2.4

2.6

2.8

3

0.5

0.6

I 1sp

/pu

I 1ss

/pu

0.7

0.8

0.9

1.0

1.1

1.2

1.3

1.4

1.5

-1 -0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 0

Tm/ pu Tm/ pu

Simulation

Analytical

IG1

IG1

IG2

IG2

IG3

IG3

IG4

IG4

Figure 12. Three-phase short-circuit current of fixed-speed IGs when the torque is varying.

-140

I 1ss

/%

-1 -0.9 -0.8 -0.7 -0.6 -0.5 -0.3 -0.2-0.4 -0.1

-120

-100

-80

-60

-40

-20

0

20

Tm/pu 0

I 1sp

/%

1.2

-1-25

Tm/pu -0.9 -0.8 -0.7 -0.6 -0.5 -0.3 -0.2-0.4 -0.1 0

-20

-15

-10

-5

10

0

5Simulation

Analytical

IG1

IG1

IG2

IG2

IG3

IG3

IG4

IG4

Figure 13. Relative errors of three-phase short-circuit currents of fixed-speed IGs with zero slips.

Figure 13 shows that the larger the electrical distances from IG to the fault node, the more

significant the rotor speed changes affect the short-circuit currents, and the smaller the peak and

steady-state values calculated with zero slip. Even when taking the variation of terminal voltages is

taken into account, the error of the short-circuit current may still exceed ±10% when constant speed

sequence models are adopted in the iterative calculation. Such an effect may be due to the effect of

slip variation on the positive sequence component of the short-circuit current. The errors of the peak

value are mainly caused by different initial slips, whereas the errors of the steady-state value are

decided by slip variations. Hence, the errors of steady-state values with zero slips are considerably

bigger than the errors of peak values.

5.2. Two-Phase Short Circuit of Fixed-Speed IGs

The positive and negative sequence components of the short-circuit current of fixed-speed IGs

with a phase B to phase C fault at node 6 are shown in Figure 14, where the mechanical torques of

IGs are Tm1 = Tm2 = Tm3 = Tm4 = −0.5. The simulated and calculated results of the peak and steady-state

value shown in Table 2 are almost same. Owing to the half-cycle lag of the real maximum value of

I1s has a half cycle lag compared with that of I2s in the instantaneous current waveforms, the peak

values of I1s and I2s are the third and second points in the calculation results respectively.

Figure 12. Three-phase short-circuit current of fixed-speed IGs when the torque is varying.

Figure 13 shows that the larger the electrical distances from IG to the fault node, the moresignificant the rotor speed changes affect the short-circuit currents, and the smaller the peak andsteady-state values calculated with zero slip. Even when taking the variation of terminal voltages istaken into account, the error of the short-circuit current may still exceed ˘10% when constant speedsequence models are adopted in the iterative calculation. Such an effect may be due to the effect of slipvariation on the positive sequence component of the short-circuit current. The errors of the peak valueare mainly caused by different initial slips, whereas the errors of the steady-state value are decided byslip variations. Hence, the errors of steady-state values with zero slips are considerably bigger thanthe errors of peak values.

Page 17: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 16 of 21

Energies 2016, 9, 277 15 of 20

-1 -0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 01

1.2

1.4

1.6

1.8

2

2.2

2.4

2.6

2.8

3

0.5

0.6

I 1sp

/pu

I 1ss

/pu

0.7

0.8

0.9

1.0

1.1

1.2

1.3

1.4

1.5

-1 -0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 0

Tm/ pu Tm/ pu

Simulation

Analytical

IG1

IG1

IG2

IG2

IG3

IG3

IG4

IG4

Figure 12. Three-phase short-circuit current of fixed-speed IGs when the torque is varying.

-140

I 1ss

/%

-1 -0.9 -0.8 -0.7 -0.6 -0.5 -0.3 -0.2-0.4 -0.1

-120

-100

-80

-60

-40

-20

0

20

Tm/pu 0

I 1sp

/%

1.2

-1-25

Tm/pu -0.9 -0.8 -0.7 -0.6 -0.5 -0.3 -0.2-0.4 -0.1 0

-20

-15

-10

-5

10

0

5Simulation

Analytical

IG1

IG1

IG2

IG2

IG3

IG3

IG4

IG4

Figure 13. Relative errors of three-phase short-circuit currents of fixed-speed IGs with zero slips.

Figure 13 shows that the larger the electrical distances from IG to the fault node, the more

significant the rotor speed changes affect the short-circuit currents, and the smaller the peak and

steady-state values calculated with zero slip. Even when taking the variation of terminal voltages is

taken into account, the error of the short-circuit current may still exceed ±10% when constant speed

sequence models are adopted in the iterative calculation. Such an effect may be due to the effect of

slip variation on the positive sequence component of the short-circuit current. The errors of the peak

value are mainly caused by different initial slips, whereas the errors of the steady-state value are

decided by slip variations. Hence, the errors of steady-state values with zero slips are considerably

bigger than the errors of peak values.

5.2. Two-Phase Short Circuit of Fixed-Speed IGs

The positive and negative sequence components of the short-circuit current of fixed-speed IGs

with a phase B to phase C fault at node 6 are shown in Figure 14, where the mechanical torques of

IGs are Tm1 = Tm2 = Tm3 = Tm4 = −0.5. The simulated and calculated results of the peak and steady-state

value shown in Table 2 are almost same. Owing to the half-cycle lag of the real maximum value of

I1s has a half cycle lag compared with that of I2s in the instantaneous current waveforms, the peak

values of I1s and I2s are the third and second points in the calculation results respectively.

Figure 13. Relative errors of three-phase short-circuit currents of fixed-speed IGs with zero slips.

5.2. Two-Phase Short Circuit of Fixed-Speed IGs

The positive and negative sequence components of the short-circuit current of fixed-speed IGswith a phase B to phase C fault at node 6 are shown in Figure 14, where the mechanical torques of IGsare Tm1 = Tm2 = Tm3 = Tm4 = ´0.5. The simulated and calculated results of the peak and steady-statevalue shown in Table 2 are almost same. Owing to the half-cycle lag of the real maximum value of I1shas a half cycle lag compared with that of I2s in the instantaneous current waveforms, the peak valuesof I1s and I2s are the third and second points in the calculation results respectively.Energies 2016, 9, 277 16 of 20

10.4 0

0.20.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

1.05 1.1 1.15 1.2 1 1.05 1.1 1.15 1.2

0.4

0.6

0.8

1.0

1.2

1.4

1.5

I 1s/

pu

t/s

t/s

Simulation

Analytical

IG1

IG1

IG2

IG2

IG3

IG3

IG4

IG4

I 2s/

pu

Figure 14. Short-circuit current sequence components of fixed-speed IGs when two-phase short

circuit occurs at bus 6.

Table 2. Short-circuit currents of fixed-speed IGs when two-phase short-circuit occurs at bus 6.

Induction Generators IG1 IG2 IG3 IG4

Analytical I1sp (pu) 0.727 0.911 1.116 0.582

I1sp Simulation I1sp (pu) 0.765 0.947 1.151 0.587

Relative error (%) −4.97 −3.80 −3.04 −0.85

Analytical I1ss (pu) 0.645 0.712 0.789 0.573

I1ss Simulation I1ss (pu) 0.644 0.712 0.789 0.575

Relative error (%) 0.16 0 0 −0.35

Analytical I2sp (pu) 0.813 1.042 1.283 0.55

I2sp Simulation I2sp (pu) 0.822 1.052 1.292 0.552

Relative error (%) −1.09 −0.95 −0.70 −0.36

Analytical I2ss (pu) 0.790 1.012 1.244 0.537

I2ss Simulation I2ss (pu) 0.793 1.021 1.248 0.538

Relative error (%) −0.38 −0.88 −0.32 −0.19

Similar with the three-phase short circuit, the difference between the steady-state and peak

values of the positive and negative sequence components for IG4 is at the minimum with a

two-phase fault occurring at node 6. The negative sequence components of short-circuit currents are

determined only by the negative sequence terminal voltage, whereas the positive components of

short-circuit currents depend upon the rotor flux attenuation associated with the slip and terminal

voltage. Thus, the attenuation degrees of the negative sequence short-circuit currents of IG1, IG2,

and IG3 are less than the degrees of their positive sequence components.

Figure 15 shows the relative errors of the proposed method with a two-phase fault at different

nodes in the distribution network. With the slip variation, the coupling relation between terminal

voltages, and the sequence networks during the fault considered, the absolute values of the relative

errors for the steady-state value are observed to be less than the absolute value of the relative errors

for the peak value. The relative errors of the proposed method for short-circuit calculation are

within ±5%.

Figure 14. Short-circuit current sequence components of fixed-speed IGs when two-phase short circuitoccurs at bus 6.

Similar with the three-phase short circuit, the difference between the steady-state and peak valuesof the positive and negative sequence components for IG4 is at the minimum with a two-phase faultoccurring at node 6. The negative sequence components of short-circuit currents are determinedonly by the negative sequence terminal voltage, whereas the positive components of short-circuitcurrents depend upon the rotor flux attenuation associated with the slip and terminal voltage. Thus,the attenuation degrees of the negative sequence short-circuit currents of IG1, IG2, and IG3 are lessthan the degrees of their positive sequence components.

Page 18: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 17 of 21

Table 2. Short-circuit currents of fixed-speed IGs when two-phase short-circuit occurs at bus 6.

Induction Generators IG1 IG2 IG3 IG4

Analytical I1sp (pu) 0.727 0.911 1.116 0.582I1sp Simulation I1sp (pu) 0.765 0.947 1.151 0.587

Relative error (%) ´4.97 ´3.80 ´3.04 ´0.85

Analytical I1ss (pu) 0.645 0.712 0.789 0.573I1ss Simulation I1ss (pu) 0.644 0.712 0.789 0.575

Relative error (%) 0.16 0 0 ´0.35

Analytical I2sp (pu) 0.813 1.042 1.283 0.55I2sp Simulation I2sp (pu) 0.822 1.052 1.292 0.552

Relative error (%) ´1.09 ´0.95 ´0.70 ´0.36

Analytical I2ss (pu) 0.790 1.012 1.244 0.537I2ss Simulation I2ss (pu) 0.793 1.021 1.248 0.538

Relative error (%) ´0.38 ´0.88 ´0.32 ´0.19

Figure 15 shows the relative errors of the proposed method with a two-phase fault at differentnodes in the distribution network. With the slip variation, the coupling relation between terminalvoltages, and the sequence networks during the fault considered, the absolute values of the relativeerrors for the steady-state value are observed to be less than the absolute value of the relative errors forthe peak value. The relative errors of the proposed method for short-circuit calculation are within ˘5%.Energies 2016, 9, 277 17 of 20

(a) (b)

Figure 15. Relative errors of short-circuit currents of fixed-speed IGs when two-phase short circuit

occurs: (a) Positive sequence component, (b) Negative sequence component.

5.3. Two-Phase Short Circuit of Variable-Speed IGs

Figure 16 shows the positive and negative sequence components of the short-circuit current of

variable-speed IGs with a phase B to phase C fault at node 6 when four IGs in the test system are

variable-speed IGs. The short-circuit currents of the four variable-speed IGs decay rapidly after

rising to the peak value, and the descent rate of the negative components are slower than that of the

positive components. The calculated results of the short-circuit currents by the analytical method

are basically consistent with the dynamic simulation results in Table 3.

10

0.1

1.05 1.1 1.15 1.2 1 1.05 1.1 1.15 1.2

0.2

0.3

0.4

0.5

0.6

0.7

0.8

I 1s/

pu

t/s

t/s

I 2s/

pu

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

1.2

1.3 Simulation

Analytical

IG1

IG1

IG2

IG2

IG3

IG3

IG4

IG4

0.9

Figure 16. Short-circuit current sequence components of variable-speed IGs when two-phase short

circuit occurs at bus 6.

Table 3. Short circuit currents of variable-speed IGs when two-phase short circuit occurs at bus 6.

Induction Generators IG1 IG2 IG3 IG4

Analytical I1sp (pu) 0.856 1.093 1.196 0.715

I1sp Simulation I1sp (pu) 0.937 1.104 1.308 0.765

Relative error (%) −8.62 −1.03 −0.81 −6.53

Analytical I1ss (pu) 0.418 0.444 0.489 0.395

I1ss Simulation I1ss (pu) 0.412 0.439 0.485 0.396

Relative error (%) 1.37 1.09 0.86 −0.21

Analytical I2sp (pu) 0.436 0.596 0.746 0.278

I2sp Simulation I2sp (pu) 0.456 0.634 0.806 0.307

Relative error (%) −4.39 −5.99 −7.44 −9.45

Analytical I2ss (pu) 0.159 0.185 0.219 0.102

I2ss Simulation I2ss (pu) 0.158 0.183 0.208 0.103

Relative error (%) 0.36 1.22 5.29 −0.65

The relative errors of the proposed method for variable-speed IGs are shown in Figure 17. The

interactive process of the short-circuit current of variable-speed IGs with the distribution network is

1 2 3 4 5 612

34

012345

1 2 3 4 5 612

34

012345

I 1sp ||

/%

IGs

Fault Buses

I 1ss ||

/%

IGs

Fault Buses

1 2 3 4 5 612

34

0

0.5

1

1.5

2

1 2 3 4 5 612

34

0

0.5

1

1.5

2

I 2sp ||

/%

IGs Fault Buses

I 2ss ||

/%

IGs Fault Buses

Figure 15. Relative errors of short-circuit currents of fixed-speed IGs when two-phase short circuitoccurs: (a) Positive sequence component, (b) Negative sequence component.

5.3. Two-Phase Short Circuit of Variable-Speed IGs

Figure 16 shows the positive and negative sequence components of the short-circuit current ofvariable-speed IGs with a phase B to phase C fault at node 6 when four IGs in the test system arevariable-speed IGs. The short-circuit currents of the four variable-speed IGs decay rapidly after risingto the peak value, and the descent rate of the negative components are slower than that of the positivecomponents. The calculated results of the short-circuit currents by the analytical method are basicallyconsistent with the dynamic simulation results in Table 3.

Page 19: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 18 of 21

Energies 2016, 9, 277 17 of 20

(a) (b)

Figure 15. Relative errors of short-circuit currents of fixed-speed IGs when two-phase short circuit

occurs: (a) Positive sequence component, (b) Negative sequence component.

5.3. Two-Phase Short Circuit of Variable-Speed IGs

Figure 16 shows the positive and negative sequence components of the short-circuit current of

variable-speed IGs with a phase B to phase C fault at node 6 when four IGs in the test system are

variable-speed IGs. The short-circuit currents of the four variable-speed IGs decay rapidly after

rising to the peak value, and the descent rate of the negative components are slower than that of the

positive components. The calculated results of the short-circuit currents by the analytical method

are basically consistent with the dynamic simulation results in Table 3.

10

0.1

1.05 1.1 1.15 1.2 1 1.05 1.1 1.15 1.2

0.2

0.3

0.4

0.5

0.6

0.7

0.8

I 1s/

pu

t/s

t/s

I 2s/

pu

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

1.2

1.3 Simulation

Analytical

IG1

IG1

IG2

IG2

IG3

IG3

IG4

IG4

0.9

Figure 16. Short-circuit current sequence components of variable-speed IGs when two-phase short

circuit occurs at bus 6.

Table 3. Short circuit currents of variable-speed IGs when two-phase short circuit occurs at bus 6.

Induction Generators IG1 IG2 IG3 IG4

Analytical I1sp (pu) 0.856 1.093 1.196 0.715

I1sp Simulation I1sp (pu) 0.937 1.104 1.308 0.765

Relative error (%) −8.62 −1.03 −0.81 −6.53

Analytical I1ss (pu) 0.418 0.444 0.489 0.395

I1ss Simulation I1ss (pu) 0.412 0.439 0.485 0.396

Relative error (%) 1.37 1.09 0.86 −0.21

Analytical I2sp (pu) 0.436 0.596 0.746 0.278

I2sp Simulation I2sp (pu) 0.456 0.634 0.806 0.307

Relative error (%) −4.39 −5.99 −7.44 −9.45

Analytical I2ss (pu) 0.159 0.185 0.219 0.102

I2ss Simulation I2ss (pu) 0.158 0.183 0.208 0.103

Relative error (%) 0.36 1.22 5.29 −0.65

The relative errors of the proposed method for variable-speed IGs are shown in Figure 17. The

interactive process of the short-circuit current of variable-speed IGs with the distribution network is

1 2 3 4 5 612

34

012345

1 2 3 4 5 612

34

012345

I 1sp ||

/%

IGs

Fault Buses

I 1ss ||

/%

IGs

Fault Buses

1 2 3 4 5 612

34

0

0.5

1

1.5

2

1 2 3 4 5 612

34

0

0.5

1

1.5

2

I 2sp ||

/%

IGs Fault Buses

I 2ss ||

/%

IGs Fault Buses

Figure 16. Short-circuit current sequence components of variable-speed IGs when two-phase shortcircuit occurs at bus 6.

Table 3. Short circuit currents of variable-speed IGs when two-phase short circuit occurs at bus 6.

Induction Generators IG1 IG2 IG3 IG4

Analytical I1sp (pu) 0.856 1.093 1.196 0.715I1sp Simulation I1sp (pu) 0.937 1.104 1.308 0.765

Relative error (%) ´8.62 ´1.03 ´0.81 ´6.53

Analytical I1ss (pu) 0.418 0.444 0.489 0.395I1ss Simulation I1ss (pu) 0.412 0.439 0.485 0.396

Relative error (%) 1.37 1.09 0.86 ´0.21

Analytical I2sp (pu) 0.436 0.596 0.746 0.278I2sp Simulation I2sp (pu) 0.456 0.634 0.806 0.307

Relative error (%) ´4.39 ´5.99 ´7.44 ´9.45

Analytical I2ss (pu) 0.159 0.185 0.219 0.102I2ss Simulation I2ss (pu) 0.158 0.183 0.208 0.103

Relative error (%) 0.36 1.22 5.29 ´0.65

The relative errors of the proposed method for variable-speed IGs are shown in Figure 17. Theinteractive process of the short-circuit current of variable-speed IGs with the distribution network issimplified by ignoring the delaying influence of the crowbar activation and the dynamic responsesof the converter and its controller, factors that lead to relatively large calculation errors of thevariable-speed IGs. According to the test results of variable-speed IGs, the maximum relative error ofthe method ranges from 10% to 15%.

Energies 2016, 9, 277 18 of 20

simplified by ignoring the delaying influence of the crowbar activation and the dynamic responses

of the converter and its controller, factors that lead to relatively large calculation errors of the

variable-speed IGs. According to the test results of variable-speed IGs, the maximum relative error

of the method ranges from 10% to 15%.

(a) (b)

Figure 17. Relative errors of short-circuit currents of variable-speed IGs when two-phase short circuit

occurs: (a) Positive sequence component, (b) Negative sequence component.

6. Conclusions

This paper proposes an improved analytical method to calculate the sequence components of

the short-circuit currents of multi-IG systems. The short-circuit calculation problem is formulated

based on the transient response, slip variation of fixed-speed and variable-speed IGs, and

parameters of distribution network, and is solved using the iteration technique. The results show

that the coupling relationship among the short-circuit currents, slip variations and terminal voltages

should be considered for the short-circuit calculation of IGs when the SCR is small. The proposed

method is verified using dynamic simulation. Comparisons show that the analytical results are very

close to the simulation results. Therefore, the proposed technique is an effective tool to determine the

short-circuit currents of multi fixed-speed and variable-speed IGs, which are very useful for the fault

analysis and protection of distribution networks. However, the simulation software requires

additional computational burden and time to find the short-circuit currents. The analytical method

can likewise provide more information to better understand the transient responses of IGs during

grid faults and the related effects of IG and network parameters. Accordingly, an improved

protection system for the distribution network can be designed.

Acknowledgments: This work was supported by the National Natural Science Foundation of China (51577018).

Author Contributions: Niancheng Zhou and Fan Ye proposed the idea of short-circuit current calculation for induction

generators. Fan Ye was in charge of deriving the equations. Qianggang Wang built the simulation model and

analyzed the data.Yuxiang Zhang checked the language. All authors were involved in preparing the manuscript.

Conflicts of Interest: The authors declare no conflict of interest.

Appendix A

The amplitude of positive sequence short circuit currentin step k decays exponentially

according to Equation (21) can be written as:

r

( 1)

( ) ( ) ( ) ( ) ( )

1s 1s 1s 1s

2( ) 2 ( ) [ (0) ( )] cos( ) i

k t t

Tk k k k k

i i i i i i

ti t A I t B I I t e

T

(A1)

where the t = T/2 (T = 0.02 s). The RMS value i1s(t) is given as:

r

r

2 ( 1)( ) 2

1s rms 1s( 1)

/( ) ( ) 2 ( ) ( ) ( ) ( ) ( )/2 1s 1s 1s 1s 2

2 /( ) ( ) ( ) 201s 1s

2[ ] [ ( )]

[ ( )] 2 ( )[ (0) ( )]22 cos (2 / )

[ ( (0) ( ))]

i

i

T k tk

i ik t

t Tk k k k k k kT i i i i i i i

t Tk k k

i i i

I i t dtT

A I t A B I t I I t et T dt

T B I I t e

(A2)

12

34

561

23

4

0

5

10

12

34

561

23

4

0

5

10

I 1sp ||

/%

IGs Fault Buses

I 1ss ||

/%

IGs Fault Buses

12

34

561

23

4

0

5

10

12

34

561

23

4

0

5

10

I 2sp ||

/%

IGs

Fault Buses

I 2ss ||

/%

IGs Fault Buses

Figure 17. Relative errors of short-circuit currents of variable-speed IGs when two-phase short circuitoccurs: (a) Positive sequence component, (b) Negative sequence component.

Page 20: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 19 of 21

6. Conclusions

This paper proposes an improved analytical method to calculate the sequence components ofthe short-circuit currents of multi-IG systems. The short-circuit calculation problem is formulatedbased on the transient response, slip variation of fixed-speed and variable-speed IGs, and parametersof distribution network, and is solved using the iteration technique. The results show that thecoupling relationship among the short-circuit currents, slip variations and terminal voltages shouldbe considered for the short-circuit calculation of IGs when the SCR is small. The proposed methodis verified using dynamic simulation. Comparisons show that the analytical results are very closeto the simulation results. Therefore, the proposed technique is an effective tool to determine theshort-circuit currents of multi fixed-speed and variable-speed IGs, which are very useful for the faultanalysis and protection of distribution networks. However, the simulation software requires additionalcomputational burden and time to find the short-circuit currents. The analytical method can likewiseprovide more information to better understand the transient responses of IGs during grid faults andthe related effects of IG and network parameters. Accordingly, an improved protection system for thedistribution network can be designed.

Acknowledgments: This work was supported by the National Natural Science Foundation of China (51577018).

Author Contributions: Niancheng Zhou and Fan Ye proposed the idea of short-circuit current calculation forinduction generators. Fan Ye was in charge of deriving the equations. Qianggang Wang built the simulationmodel and analyzed the data.Yuxiang Zhang checked the language. All authors were involved in preparingthe manuscript.

Conflicts of Interest: The authors declare no conflict of interest.

Appendix A

The amplitude of positive sequence short circuit currentin step k decays exponentially accordingto Equation (21) can be written as:

i1siptq “?

2"

Apkqi Ipkq1si p∆tq ` Bpkqi rIpkq1si p0q ´ Ipkq1si p∆tqsepk´1q∆t´t

Tri

*

cosp2πtTq (A1)

where the ∆t = T/2 (T = 0.02 s). The RMS value i1s(t) is given as:

rIpkq1si srms “

c

2TşT2`pk´1q∆tpk´1q∆t ri1siptqs

2dt

g

f

f

f

e

2TşT2

0 2

$

&

%

rApkqi Ipkq1si p∆tqs2` 2Apkqi Bpkqi Ipkq1si p∆tqrIpkq1si p0q ´ Ipkq1si p∆tqse´tTri

`rBpkqi pIpkq1si p0q ´ Ipkq1si p∆tqqs2e´2tTri

,

.

-

cos2p2πtTqdt(A2)

The first part F1 of Equation (A2) as:

F1 “2T

ż T2

02rApkqi Ipkq1si p∆tqs

2cos2p2πtTqdt “ rApkqi Ipkq1si p∆tqs

2(A3)

The second part F2 of Equation (A2) can be given as:

F2 “2Tr T2

0 4Apkqi Bpkqi Ipkq1si p∆tqrIpkq1si p0q ´ Ipkq1si p∆tqse´tTri cos2p2πtTqdt

“8Tri

T Apkqi Bpkqi Ipkq1si p∆tqrIpkq1si p0q ´ Ipkq1si p∆tqs"

pT2`8π2T2riqre

Tp2Triq´1spT2`16π2T2

riqeTp2Triq

*

«4Tri

T Apkqi Bpkqi Ipkq1si p∆tqrIpkq1si p0q ´ Ipkq1si p∆tqsr1´ e´Tp2Triqs

(A4)

The third part F3 of Equation (A2) can be given as:

Page 21: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 20 of 21

F3 “ 2Tr T2

0 2rBpkqi pIpkq1si p0q ´ Ipkq1si p∆tqqs2e´2tTri cos2p2πtTqdt

“2Tri

T rBpkqi pIpkq1si p0q ´ Ipkq1si p∆tqqs

2rpT2`2π2T2

riqpeTTri´1q

pT2`4π2T2r qeTTri

s

«TriT rB

pkqi pIpkq1si p0q ´ Ipkq1si p∆tqqs

2p1´ e´TTriq

(A5)

Substituting Equations (A3), (A4) and (A5) into Equation (A2), The RMS value of the half waveshort circuit current can be derived as:

rIpkq1si srms “?

F1 ` F2 ` F3

c

rApkqi Ipkq1si p∆tqs2`

TriT Bpkqi rIpkq1si p0q´ Ipkq1si p∆tqs

!

4Apkqi Ipkq1si p∆tqr1´ e´Tp2Triqs ` Bpkqi rIpkq1si p0q´ Ipkq1si p∆tqsp1´ e´TTri q

) (A6)

Appendix B

The voltage level of four IGs system is 10 kV and the local load of all induction generators arealso set to zero.

(1) The IG parameters:

(a) Rated power = 3 MW, Rated AC voltage = 0.69 kV;(b) Rs = 0.004843 p.u., Xls = 0.1248 p.u.;(c) Rr = 0.004347 p.u., Xlr = 0.1791 p.u.;(d) Xm = 6.77 p.u., H = 5.04 s;(e) Capacitor rated voltage = 0.69 kV, Rated power = 0.75 Mvar for a fixed-speed IG;(f) Rated DC voltage = 1.5 kV, Crowbarresistance = 0.1043 p.u. for a variable-speed IG.

(2) Transformer T1, T2, T3 and T4 have the same parameters:

(a) Rated capacity = 3.5 MVA;(b) VI/VII (Yn/∆) = 0.69/10.5 kV;(c) XT = 0.06 p.u., RT = 0.02 p.u..

(3) The length of lines and impedance of per km are:

(a) L1 = L2 = L3 = L4 = 0.5 km, L5 = 3.5 km;(b) ZL = j0.300 Ω/km.

(4) The parameters of substation:

(a) Rated Voltage = 10 kV, Es = 1.05 p.u.;(b) Short circuit level = 240 MVA, X/R = 10.

References

1. Nimpitiwan, N.; Heydt, G.T.; Ayyanar, R.; Suryanarayana, S. Fault current contribution fromsynchronousmachine and inverter based distributed generators. IEEE Trans. Power Deliv. 2007, 22, 634–641.[CrossRef]

2. Akhmatov, V. Induction Generators for Wind Power; Multi Science: Essex, UK, 2007.3. Freitas, W.; Vieira, J.C.M.; Morelato, A.; da Silva, L.C.P.; da Costa, V.F.; Lemos, F.A.B. Comparative

analysis between synchronous and induction machines for distributed generation applications.IEEE Trans. Power Syst. 2006, 21, 301–311. [CrossRef]

4. Huening, W.C. Calculating short-circuit currents with contributions from induction motors. IEEE Trans.Ind. Appl. 1982, IA-18, 85–92. [CrossRef]

Page 22: Short‑Circuit Calculation in Distribution Networks with

Energies 2016, 9, 277 21 of 21

5. Morren, J.; de Haan, S.W.H. Short-circuit current of wind turbines with doubly fed induction generator.IEEE Trans. Energy Convers. 1991, 22, 174–180. [CrossRef]

6. Boutsika, T.N.; Papathanassiou, S.A. Short-circuit calculations in networks with distributed generation.Electr. Power Syst. Res. 2008, 78, 1181–1191. [CrossRef]

7. Sulawa, T.; Zabar, Z.; Czarkowski, D.; TenAmi, Y.; Birenbaum, L.; Lee, S. Evaluation of a 3-φ boltedshort-circuit on distribution networks having induction generators at customer sites. IEEE Trans. Power Deliv.2007, 22, 1965–1971. [CrossRef]

8. Trudnowski, D.J.; Gentile, A.; Khan, J.M.; Petritz, E.M. Fixed speed wind-generator and wind-park modelingfor transient stability studies. IEEE Trans. Power Syst. 2004, 19, 1911–1917. [CrossRef]

9. Causebrook, A.; Atkinson, D.J.; Jack, A.G. Fault ride-through of large wind farms using series dynamicbraking resistors. IEEE Trans. Power Syst. 2007, 22, 966–975. [CrossRef]

10. Pannell, G.; Atkinson, D.J.; Zahawi, B. Analytical study of grid-fault response of wind turbine doubly fedinduction generator. IEEE Trans. Energy Convers. 2010, 25, 1081–1091. [CrossRef]

11. Ouhrouche, M. Transient analysis of a grid connected wind driven induction generator using a real-timesimulation platform. Renew. Energy 2009, 34, 801–806. [CrossRef]

12. Vicatos, M.S.; Tegopoulos, J.A. Transient state analysis of a doubly-fed induction generator under threephase short circuit. IEEE Trans. Energy Convers. 1991, 6, 62–68. [CrossRef]

13. Lopez, J.; Gubia, E.; Sanchis, P.; Roboam, X.; Marroyo, L. Wind turbines based on doubly fed inductiongenerator under asymmetrical voltage dips. IEEE Trans. Energy Convers. 2008, 23, 321–330. [CrossRef]

14. Sulla, F.; Svensson, J.; Samuelsson, O. Symmetrical and unsymmetrical short-circuit current of squirrel-cageand doubly-fed induction generators. Electr. Power Syst. Res. 2011, 81, 1610–1618. [CrossRef]

15. Mohseni, M.; Islam, S.M.; Masoum, M.A.S. Impacts of symmetrical and asymmetrical voltage sags onDFIG-based wind turbines considering phase-angle jump, voltage recovery, and sag parameters. IEEE Trans.Power Electron. 2011, 26, 1587–1598. [CrossRef]

16. Howard, D.F.; Habetler, T.G.; Harley, R.G. Improved sequence network model of wind turbine generatorsfor short-circuit studies. IEEE Trans. Energy Convers. 2012, 27, 968–977. [CrossRef]

17. Anderson, P.M. Analysis of Faulted Power Systems; Institute of Electrical and Electronics Engineers (IEEE):Piscataway, NJ, USA, 1995.

18. Li, H.; Zhao, B.; Yang, C.; Chen, H.W.; Chen, Z. Analysis and estimation of transient stability for agrid-connected wind turbine with induction generator. Renew. Energy 2011, 36, 1469–1476. [CrossRef]

19. El-Naggar, A.; Erlich, I. Analysis of fault current contribution of doubly-fed induction generator windturbines under unbalanced grid faults. Renew. Energy 2016, 91, 137–146. [CrossRef]

20. Grilo, A.P.; Mota, A.A.; Mota, L.T.; Freitas, W. An analytical method for analysis of large-disturbance stabilityof induction generators. IEEE Trans. Power Syst. 2007, 22, 1861–1869. [CrossRef]

21. Sun, T.; Chen, Z.; Blaabjerg, F. Flicker study on variable speed wind turbines with doubly fed inductiongenerators. IEEE Trans. Energy Convers. 2005, 20, 896–905. [CrossRef]

22. Rodriguez, P.; Timbus, A.V.; Teodorescu, R.; Liserre, M.; Blaabjerg, F. Flexible active power control ofdistributed power generation systems during grid faults. IEEE Trans. Ind. Electron. 2007, 54, 2583–2592.[CrossRef]

© 2016 by the authors; licensee MDPI, Basel, Switzerland. This article is an open accessarticle distributed under the terms and conditions of the Creative Commons Attribution(CC-BY) license (http://creativecommons.org/licenses/by/4.0/).