siemens - distance protection power swing

Upload: jose-alberto-rodriguez

Post on 14-Apr-2018

249 views

Category:

Documents


3 download

TRANSCRIPT

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    1/12

    Siemens AG 2006

    Distance Protection Power Swing

    Power Transmission

    and Distribution

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    2/12

    Page 2 Symmetrical Components

    Siemens AG 2006

    Power Transmission and Distribution

    Power swing:

    Voltage diagram

    LZS1 LZL LZS2

    E2 = E'2E1UA UB

    U'B

    U'A

    'L L

    ' E'1

    E1 E2ZS1 ZS2ZL

    UA UB

    Two Machine Problem

    If the angle becomes too large, the system stability can be lost

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    3/12

    Page 3 Symmetrical Components

    Siemens AG 2006

    Power Transmission and Distribution

    Power swing locus and relay characteristic

    in the impedance diagram

    E1 = E2

    E1 > E2

    E1 < E2

    X

    R

    ZS2

    B

    ZL

    A

    ZS1

    ZLoad

    '

    load point

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    4/12

    Page 4 Symmetrical Components

    Siemens AG 2006

    Power Transmission and Distribution

    Dynamic system stability, equal area criterion

    ZS1

    U1

    E1

    U2

    E2ZS2

    ZL

    ZL

    D PTP = sinE1 E2

    XT

    1

    D

    2

    D

    3

    D

    A

    C

    1

    3

    2

    1

    2

    30

    4

    5

    6

    0 1 20 90 180

    PT

    P

    B

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    5/12Page 5 Symmetrical Components

    Siemens AG 2006

    Power Transmission and Distribution

    56

    1

    34

    X

    RZload

    ZS1

    ZS1

    ZL

    2

    2

    0

    0

    Power swing locus in the impedance plane

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    6/12Page 6 Symmetrical Components

    Siemens AG 2006

    Power Transmission and Distribution

    Power swing detection: Classic Method

    (Not used in 7SA52 and 7SA6)

    Classic power swing detection

    is restricted to slow swings

    The setting ofZ may not be too large

    to avoid load encroachment (typ. 5 )

    During fast swings the time available(t) for detection of impedance vector

    in the power swing zone is too short.Z

    t = time for transition of Z from outer to inner zone

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    7/12Page 7 Symmetrical Components

    Siemens AG 2006

    Power Transmission and Distribution

    Advanced Power swing blocking techniques

    (7SA513, 7SA522, 7SA6)Novel space vector based principle

    Self-setting

    Small Z (1 Ohm at In=5 A)

    Blocking up to high slip frequencies (7 Hz)

    Recognition of all fault types during swing

    Remains effective during single pole ARCopen time (3-phase set-up)

    dZ/dt measurement

    Calculation of swing centre

    and plausibility check

    (+90O<

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    8/12Page 8 Symmetrical Components

    Siemens AG 2006

    Power Transmission and Distribution

    Power Swing detection: New method

    dR

    dX

    (k-n)

    (k-n)

    dR(k)dX(k)

    Power swingX

    R

    Fault entry

    Faultimpedance

    Load

    impedance

    Transition from load to fault is fast

    Power swing transition is slow

    Continuos monitoring of the impedance trajectory

    Monitoring of trajectory continuity

    Monitoring of trajectory velocity

    Evaluation of trajectory ellipse

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    9/12Page 9 Symmetrical Components

    Siemens AG 2006

    Power Transmission and Distribution

    Example:

    i/kA

    t/ms500

    u/kV

    t/ms500

    200

    -3

    6

    3

    R

    A ZA a Zl b ZB B

    ~ ~ ~ ~ ~

    Evaluation of the power swing process

    Power swing

    locus(EA>EB)

    -90O

    180O

    0O

    90OXm

    Slip

    frequency

    EBEARelay

    Relay

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    10/12

    Page 10 Symmetrical Components

    Siemens AG 2006

    Power Transmission and Distribution

    Novel power swing detection provides secure

    operation with swing frequencies of up to 7 Hz

    t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6

    iL1/A

    -4

    -2

    0

    t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6

    iL2/A

    -2

    0

    t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6

    iL3/A

    -2

    0

    2

    t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6

    uL1/V

    -50

    0

    t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6

    uL2/V

    -50

    0

    50

    t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6

    uL3/V

    -50

    0

    50

    t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6

    DisTRIP3p Z1Bmf

    Relay TRIP

    Relay PICKUP

    Dis. reverse

    Dis. forward

    Dis.T.SEND>DisTel Rec.Ch1

    Power Swing

    Example:400 kV400 kmfPS 2 Hz3-pole fault

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    11/12

    Page 11 Symmetrical Components

    Siemens AG 2006

    Power Transmission and Distribution

    Fault detection during power swing

    I1

    I2

    V1

    Trip

    The Power swing passes through

    the trip characteristic several times.

    Single phase fault is detected andcleared.

  • 7/29/2019 SIEMENS - Distance Protection Power Swing

    12/12

    Page 12 Symmetrical Components

    Siemens AG 2006

    Power Transmission and Distribution

    Three phase fault during Power Swing

    Three phase fault during power swing

    is detected and cleared

    Fault inception while swing is inside

    trip characteristic

    I1

    V1

    V2

    V3

    Trip