siemens - distance protection power swing
TRANSCRIPT
-
7/29/2019 SIEMENS - Distance Protection Power Swing
1/12
Siemens AG 2006
Distance Protection Power Swing
Power Transmission
and Distribution
-
7/29/2019 SIEMENS - Distance Protection Power Swing
2/12
Page 2 Symmetrical Components
Siemens AG 2006
Power Transmission and Distribution
Power swing:
Voltage diagram
LZS1 LZL LZS2
E2 = E'2E1UA UB
U'B
U'A
'L L
' E'1
E1 E2ZS1 ZS2ZL
UA UB
Two Machine Problem
If the angle becomes too large, the system stability can be lost
-
7/29/2019 SIEMENS - Distance Protection Power Swing
3/12
Page 3 Symmetrical Components
Siemens AG 2006
Power Transmission and Distribution
Power swing locus and relay characteristic
in the impedance diagram
E1 = E2
E1 > E2
E1 < E2
X
R
ZS2
B
ZL
A
ZS1
ZLoad
'
load point
-
7/29/2019 SIEMENS - Distance Protection Power Swing
4/12
Page 4 Symmetrical Components
Siemens AG 2006
Power Transmission and Distribution
Dynamic system stability, equal area criterion
ZS1
U1
E1
U2
E2ZS2
ZL
ZL
D PTP = sinE1 E2
XT
1
D
2
D
3
D
A
C
1
3
2
1
2
30
4
5
6
0 1 20 90 180
PT
P
B
-
7/29/2019 SIEMENS - Distance Protection Power Swing
5/12Page 5 Symmetrical Components
Siemens AG 2006
Power Transmission and Distribution
56
1
34
X
RZload
ZS1
ZS1
ZL
2
2
0
0
Power swing locus in the impedance plane
-
7/29/2019 SIEMENS - Distance Protection Power Swing
6/12Page 6 Symmetrical Components
Siemens AG 2006
Power Transmission and Distribution
Power swing detection: Classic Method
(Not used in 7SA52 and 7SA6)
Classic power swing detection
is restricted to slow swings
The setting ofZ may not be too large
to avoid load encroachment (typ. 5 )
During fast swings the time available(t) for detection of impedance vector
in the power swing zone is too short.Z
t = time for transition of Z from outer to inner zone
-
7/29/2019 SIEMENS - Distance Protection Power Swing
7/12Page 7 Symmetrical Components
Siemens AG 2006
Power Transmission and Distribution
Advanced Power swing blocking techniques
(7SA513, 7SA522, 7SA6)Novel space vector based principle
Self-setting
Small Z (1 Ohm at In=5 A)
Blocking up to high slip frequencies (7 Hz)
Recognition of all fault types during swing
Remains effective during single pole ARCopen time (3-phase set-up)
dZ/dt measurement
Calculation of swing centre
and plausibility check
(+90O<
-
7/29/2019 SIEMENS - Distance Protection Power Swing
8/12Page 8 Symmetrical Components
Siemens AG 2006
Power Transmission and Distribution
Power Swing detection: New method
dR
dX
(k-n)
(k-n)
dR(k)dX(k)
Power swingX
R
Fault entry
Faultimpedance
Load
impedance
Transition from load to fault is fast
Power swing transition is slow
Continuos monitoring of the impedance trajectory
Monitoring of trajectory continuity
Monitoring of trajectory velocity
Evaluation of trajectory ellipse
-
7/29/2019 SIEMENS - Distance Protection Power Swing
9/12Page 9 Symmetrical Components
Siemens AG 2006
Power Transmission and Distribution
Example:
i/kA
t/ms500
u/kV
t/ms500
200
-3
6
3
R
A ZA a Zl b ZB B
~ ~ ~ ~ ~
Evaluation of the power swing process
Power swing
locus(EA>EB)
-90O
180O
0O
90OXm
Slip
frequency
EBEARelay
Relay
-
7/29/2019 SIEMENS - Distance Protection Power Swing
10/12
Page 10 Symmetrical Components
Siemens AG 2006
Power Transmission and Distribution
Novel power swing detection provides secure
operation with swing frequencies of up to 7 Hz
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6
iL1/A
-4
-2
0
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6
iL2/A
-2
0
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6
iL3/A
-2
0
2
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6
uL1/V
-50
0
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6
uL2/V
-50
0
50
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6
uL3/V
-50
0
50
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6
DisTRIP3p Z1Bmf
Relay TRIP
Relay PICKUP
Dis. reverse
Dis. forward
Dis.T.SEND>DisTel Rec.Ch1
Power Swing
Example:400 kV400 kmfPS 2 Hz3-pole fault
-
7/29/2019 SIEMENS - Distance Protection Power Swing
11/12
Page 11 Symmetrical Components
Siemens AG 2006
Power Transmission and Distribution
Fault detection during power swing
I1
I2
V1
Trip
The Power swing passes through
the trip characteristic several times.
Single phase fault is detected andcleared.
-
7/29/2019 SIEMENS - Distance Protection Power Swing
12/12
Page 12 Symmetrical Components
Siemens AG 2006
Power Transmission and Distribution
Three phase fault during Power Swing
Three phase fault during power swing
is detected and cleared
Fault inception while swing is inside
trip characteristic
I1
V1
V2
V3
Trip