Page 1 of 4 Low Voltage Circuit Breaker Test Report Rev. 14, 12-14 Job Number 27261 Date 12/16/14 Job Information Customer Rubicon Minerals Test Information Test Location Gainesville, TX Temperature (°F) 73 (°C) 22 Test Condition As Left Product Condition Reconditioned Humidity (%) 33 Circuit Breaker Information Manufacturer Westinghouse Model DS-420 Mechanism Model # N/A Rated Maximum Voltage 600 V Continuous Amp Rating 2000 A Type Air Charge 120VAC Close 120VAC Trip 120VAC Serial Number 27261-001 Wiring Diag. # 2a 6a Operator Manual/Electric Mount Draw Out Trip Unit Information Manufacturer Westinghouse Type Static/Solid State Model Amptector I A LSI Curve Number 2 C. T. Rating 2000 Rating Plug N/A Serial Number N/A Primary Fuses N/A Pickup Settings Band Long Time 1.0 4 Short Time 4 .5 Instant 4 N/A Ground Fault N/A N/A Control Voltage X N/A Y 120VAC UV N/A Comments: N/A .5 Band 4 Quality Control Signature

Upload: others

Post on 11-Mar-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Job Information

Customer Rubicon Minerals

Test Information

Test Location Gainesville, TX

Temperature (°F) 73 (°C) 22

Test Condition As Left

Product Condition ReconditionedHumidity (%) 33

Circuit Breaker Information

Manufacturer Westinghouse

Model DS-420

Mechanism Model # N/A

Rated Maximum Voltage 600 V

Continuous Amp Rating 2000 A

Type Air

Charge 120VAC

Close 120VAC

Trip 120VAC

Serial Number 27261-001

Wiring Diag. # 2a 6a

Operator Manual/Electric

Mount Draw Out

Trip Unit Information

Manufacturer Westinghouse

Type Static/Solid State

Model Amptector I A LSI

Curve Number 2

C. T. Rating 2000

Rating Plug N/A

Serial Number N/A

Primary Fuses N/A

PickupSettings Band

Long Time 1.0 4

Short Time 4 .5

Instant 4 N/A

Ground Fault N/A N/A

Control Voltage

X N/A

Y 120VAC

UV N/A

Comments:

N/A

.5

Band

4

Quality Control Signature

Page 2 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Results Summary

Customer Rubicon Minerals

Manufacturer Westinghouse

Model DS-420 Serial Number 27261-001

Mechanical Inspection Pass

Electrical Inspection Pass

Inspections

Visual Inspection Pass

Remarks/Recommendations

Tests Remarks/Recommendations

High Current Test Pass

Insulation Test Pass

Contact Resistance Test Pass

Min. Close and Trip Test Pass

Megger Control WiringP

Mechanical InterlocksP

Name PlateP

Blown Fuse IndicatorN/A

4th Wire GroundN/A

Anti-Pump FunctionP

Test StickerP

Indicating StickersP

Auxiliary SwitchesP

Operation CounterN/A

DocumentsY

Power Factor AttachedN/A

TTA AttachedN/A

Operation Counter ReadingN/A

Comments:

Tester Initials gd

P=Pass

F=Fail

Y=Yes

N=No

N/A=Not Applicable

I=Incomplete

Additional Tests, Inspections, and Documentation

Page 3 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

High Current Test Data

FunctionPercent

Pickup

Current

(Amps)Curve Specs.

Phase A

(Seconds)

Phase B

(Seconds)

Phase C

(Seconds)

Long Time 300 6000 11-18 11.1 11.0 11.1 Pass/Fail: Pass

Short Time 150 12000 .35-.50 .463 .462 .461 Tester Initials: cm

Instantaneous 100 8000 +/- 10% Amps7990 Amps7980 Amps8000

Ground Fault N/A N/A N/A N/A N/A N/A

Comments:

Insulation Resistance Test

Comments:

Test

Voltage

Isolated

Bushing/s1

Open

2

Open

3

Open

4

Open

5

Open

6

Open

A Phase

Closed

B Phase

Closed

C Phase

Closed

1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass

Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd

Contact Resistance Test

Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass

N/A 24 25 24 Tester Initials: gd

In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest

value recorded (ANSI/NETA MTS-2011 7.5.1.1).

Comments:

Minimum Close/Trip Voltage Test

Required Value Tested Value

Minimum Close Voltage 104VAC 90 Pass/Fail: Pass

Mininum Trip Voltage 104VAC 85 Tester Initials: gd

Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).

Comments:

Page 4 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Equipment

Manufacturer Model Serial Number Calibration Expires Used For

AVO/ETI PS-9160R 11412 03/03/15 High Current

AVO/ETI PS-9160R 11412 03/03/15 High Current

Fluke 1520 92470030 03/03/15 Insulation Resistance

Biddle 247001 49017 03/03/15 Contact Resistance

CBS Big Gray 148990 03/03/15 Min Trip/Close

Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level

Page 1 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Job Information

Customer Rubicon Minerals

Test Information

Test Location Gainesville, TX

Temperature (°F) 73 (°C) 22

Test Condition As Left

Product Condition ReconditionedHumidity (%) 33

Circuit Breaker Information

Manufacturer Westinghouse

Model DS-420

Mechanism Model # N/A

Rated Maximum Voltage 600 V

Continuous Amp Rating 2000 A

Type Air

Charge 120VAC

Close 120VAC

Trip 120VAC

Serial Number 27261-002

Wiring Diag. # 2a 6a

Operator Manual/Electric

Mount Draw Out

Trip Unit Information

Manufacturer Westinghouse

Type Static/Solid State

Model Amptector I A LSI

Curve Number 2

C. T. Rating 2000

Rating Plug N/A

Serial Number N/A

Primary Fuses N/A

PickupSettings Band

Long Time 1.0 4

Short Time 4 .5

Instant 4 N/A

Ground Fault N/A N/A

Control Voltage

X N/A

Y 120VAC

UV N/A

Comments:

N/A

.5

Band

4

Quality Control Signature

Page 2 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Results Summary

Customer Rubicon Minerals

Manufacturer Westinghouse

Model DS-420 Serial Number 27261-002

Mechanical Inspection Pass

Electrical Inspection Pass

Inspections

Visual Inspection Pass

Remarks/Recommendations

Tests Remarks/Recommendations

High Current Test Pass

Insulation Test Pass

Contact Resistance Test Pass

Min. Close and Trip Test Pass

Megger Control WiringP

Mechanical InterlocksP

Name PlateP

Blown Fuse IndicatorN/A

4th Wire GroundN/A

Anti-Pump FunctionP

Test StickerP

Indicating StickersP

Auxiliary SwitchesP

Operation CounterN/A

DocumentsY

Power Factor AttachedN/A

TTA AttachedN/A

Operation Counter ReadingN/A

Comments:

Tester Initials gd

P=Pass

F=Fail

Y=Yes

N=No

N/A=Not Applicable

I=Incomplete

Additional Tests, Inspections, and Documentation

Page 3 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

High Current Test Data

FunctionPercent

Pickup

Current

(Amps)Curve Specs.

Phase A

(Seconds)

Phase B

(Seconds)

Phase C

(Seconds)

Long Time 300 6000 11-18 14.4 13.4 14.4 Pass/Fail: Pass

Short Time 150 12000 .35-.50 .461 .480 .482 Tester Initials: cm

Instantaneous 100 8000 +/- 10% Amps8710 Amps8480 Amps8370

Ground Fault N/A N/A N/A N/A N/A N/A

Comments:

Insulation Resistance Test

Comments:

Test

Voltage

Isolated

Bushing/s1

Open

2

Open

3

Open

4

Open

5

Open

6

Open

A Phase

Closed

B Phase

Closed

C Phase

Closed

1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass

Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd

Contact Resistance Test

Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass

N/A 25 26 26 Tester Initials: gd

In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest

value recorded (ANSI/NETA MTS-2011 7.5.1.1).

Comments:

Minimum Close/Trip Voltage Test

Required Value Tested Value

Minimum Close Voltage 104VAC 100 Pass/Fail: Pass

Mininum Trip Voltage 104VAC 85 Tester Initials: gd

Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).

Comments:

Page 4 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Equipment

Manufacturer Model Serial Number Calibration Expires Used For

AVO/ETI PS-9160R 11412 03/03/15 High Current

AVO/ETI PS-9160R 11412 03/03/15 High Current

Fluke 1520 92470030 03/03/15 Insulation Resistance

Biddle 247001 49017 03/03/15 Contact Resistance

CBS Big Gray 148990 03/03/15 Min Trip/Close

Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level

Page 1 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Job Information

Customer Rubicon Minerals

Test Information

Test Location Gainesville, TX

Temperature (°F) 73 (°C) 22

Test Condition As Left

Product Condition ReconditionedHumidity (%) 33

Circuit Breaker Information

Manufacturer Westinghouse

Model DS-420

Mechanism Model # N/A

Rated Maximum Voltage 600 V

Continuous Amp Rating 2000 A

Type Air

Charge 120VAC

Close 120VAC

Trip 120VAC

Serial Number 27261-003

Wiring Diag. # 2a 6a

Operator Manual/Electric

Mount Draw Out

Trip Unit Information

Manufacturer Westinghouse

Type Static/Solid State

Model Amptector I A LSI

Curve Number 2

C. T. Rating 2000

Rating Plug N/A

Serial Number N/A

Primary Fuses N/A

PickupSettings Band

Long Time 1.0 4

Short Time 4 .5

Instant 4 N/A

Ground Fault N/A N/A

Control Voltage

X N/A

Y 120VAC

UV N/A

Comments:

N/A

.5

Band

4

Quality Control Signature

Page 2 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Results Summary

Customer Rubicon Minerals

Manufacturer Westinghouse

Model DS-420 Serial Number 27261-003

Mechanical Inspection Pass

Electrical Inspection Pass

Inspections

Visual Inspection Pass

Remarks/Recommendations

Tests Remarks/Recommendations

High Current Test Pass

Insulation Test Pass

Contact Resistance Test Pass

Min. Close and Trip Test Pass

Megger Control WiringP

Mechanical InterlocksP

Name PlateP

Blown Fuse IndicatorN/A

4th Wire GroundN/A

Anti-Pump FunctionP

Test StickerP

Indicating StickersP

Auxiliary SwitchesP

Operation CounterN/A

DocumentsY

Power Factor AttachedN/A

TTA AttachedN/A

Operation Counter ReadingN/A

Comments:

Tester Initials gd

P=Pass

F=Fail

Y=Yes

N=No

N/A=Not Applicable

I=Incomplete

Additional Tests, Inspections, and Documentation

Page 3 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

High Current Test Data

FunctionPercent

Pickup

Current

(Amps)Curve Specs.

Phase A

(Seconds)

Phase B

(Seconds)

Phase C

(Seconds)

Long Time 300 6000 11-18 12.4 11.3 11.9 Pass/Fail: Pass

Short Time 150 12000 .35-.50 .450 .451 .463 Tester Initials: cm

Instantaneous 100 8000 +/- 10% Amps7580 Amps7540 Amps8710

Ground Fault N/A N/A N/A N/A N/A N/A

Comments:

Insulation Resistance Test

Comments:

Test

Voltage

Isolated

Bushing/s1

Open

2

Open

3

Open

4

Open

5

Open

6

Open

A Phase

Closed

B Phase

Closed

C Phase

Closed

1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass

Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd

Contact Resistance Test

Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass

N/A 24 25 25 Tester Initials: gd

In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest

value recorded (ANSI/NETA MTS-2011 7.5.1.1).

Comments:

Minimum Close/Trip Voltage Test

Required Value Tested Value

Minimum Close Voltage 104VAC 95 Pass/Fail: Pass

Mininum Trip Voltage 104VAC 85 Tester Initials: gd

Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).

Comments:

Page 4 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Equipment

Manufacturer Model Serial Number Calibration Expires Used For

AVO/ETI PS-9160R 11412 03/03/15 High Current

AVO/ETI PS-9160R 11412 03/03/15 High Current

Fluke 1520 92470030 03/03/15 Insulation Resistance

Biddle 247001 49017 03/03/15 Contact Resistance

CBS Big Gray 148990 03/03/15 Min Trip/Close

Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level

Page 1 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Job Information

Customer Rubicon Minerals

Test Information

Test Location Gainesville, TX

Temperature (°F) 73 (°C) 22

Test Condition As Left

Product Condition ReconditionedHumidity (%) 33

Circuit Breaker Information

Manufacturer Westinghouse

Model DS-416

Mechanism Model # N/A

Rated Maximum Voltage 600 V

Continuous Amp Rating 1600 A

Type Air

Charge 120VAC

Close 120VAC

Trip 120VAC

Serial Number 27261-004

Wiring Diag. # 2a 6a

Operator Manual/Electric

Mount Draw Out

Trip Unit Information

Manufacturer Westinghouse

Type Static/Solid State

Model Amptector I A LSI

Curve Number 2

C. T. Rating 1200

Rating Plug N/A

Serial Number N/A

Primary Fuses N/A

PickupSettings Band

Long Time 1.0 4

Short Time 4 .5

Instant 4 N/A

Ground Fault N/A N/A

Control Voltage

X N/A

Y 120VAC

UV N/A

Comments:

N/A

.5

Band

4

Quality Control Signature

Page 2 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Results Summary

Customer Rubicon Minerals

Manufacturer Westinghouse

Model DS-416 Serial Number 27261-004

Mechanical Inspection Pass

Electrical Inspection Pass

Inspections

Visual Inspection Pass

Remarks/Recommendations

Tests Remarks/Recommendations

High Current Test Pass

Insulation Test Pass

Contact Resistance Test Pass

Min. Close and Trip Test Pass

Megger Control WiringP

Mechanical InterlocksP

Name PlateP

Blown Fuse IndicatorN/A

4th Wire GroundN/A

Anti-Pump FunctionP

Test StickerP

Indicating StickersP

Auxiliary SwitchesP

Operation CounterN/A

DocumentsY

Power Factor AttachedN/A

TTA AttachedN/A

Operation Counter ReadingN/A

Comments:

Tester Initials gd

P=Pass

F=Fail

Y=Yes

N=No

N/A=Not Applicable

I=Incomplete

Additional Tests, Inspections, and Documentation

Page 3 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

High Current Test Data

FunctionPercent

Pickup

Current

(Amps)Curve Specs.

Phase A

(Seconds)

Phase B

(Seconds)

Phase C

(Seconds)

Long Time 300 3600 11-18 12.2 12.0 12.1 Pass/Fail: Pass

Short Time 150 7200 .35-.50 .486 .471 .499 Tester Initials: gd

Instantaneous 100 4800 +/- 10% Amps5137 Amps4838 Amps4736

Ground Fault N/A N/A N/A N/A N/A N/A

Comments:

Insulation Resistance Test

Comments:

Test

Voltage

Isolated

Bushing/s1

Open

2

Open

3

Open

4

Open

5

Open

6

Open

A Phase

Closed

B Phase

Closed

C Phase

Closed

1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass

Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd

Contact Resistance Test

Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass

N/A 30 30 31 Tester Initials: gd

In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest

value recorded (ANSI/NETA MTS-2011 7.5.1.1).

Comments:

Minimum Close/Trip Voltage Test

Required Value Tested Value

Minimum Close Voltage 104VAC 95 Pass/Fail: Pass

Mininum Trip Voltage 104VAC 85 Tester Initials: gd

Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).

Comments:

Page 4 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Equipment

Manufacturer Model Serial Number Calibration Expires Used For

AVO/ETI PS-9160R 11412 03/03/15 High Current

AVO/ETI PS-9160R 11412 03/03/15 High Current

Fluke 1520 92470030 03/03/15 Insulation Resistance

Biddle 247001 49017 03/03/15 Contact Resistance

CBS Big Gray 148990 03/03/15 Min Trip/Close

Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level

Page 1 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Job Information

Customer Rubicon Minerals

Test Information

Test Location Gainesville, TX

Temperature (°F) 73 (°C) 22

Test Condition As Left

Product Condition ReconditionedHumidity (%) 33

Circuit Breaker Information

Manufacturer Westinghouse

Model DS-416

Mechanism Model # N/A

Rated Maximum Voltage 600 V

Continuous Amp Rating 1600 A

Type Air

Charge 120VAC

Close 120VAC

Trip 120VAC

Serial Number 27261-005

Wiring Diag. # 2a 6a

Operator Manual/Electric

Mount Draw Out

Trip Unit Information

Manufacturer Westinghouse

Type Static/Solid State

Model Amptector I A LSI

Curve Number 2

C. T. Rating 1200

Rating Plug N/A

Serial Number N/A

Primary Fuses N/A

PickupSettings Band

Long Time 1.0 4

Short Time 4 .5

Instant 4 N/A

Ground Fault N/A N/A

Control Voltage

X N/A

Y 120VAC

UV N/A

Comments:

N/A

.5

Band

4

Quality Control Signature

Page 2 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Results Summary

Customer Rubicon Minerals

Manufacturer Westinghouse

Model DS-416 Serial Number 27261-005

Mechanical Inspection Pass

Electrical Inspection Pass

Inspections

Visual Inspection Pass

Remarks/Recommendations

Tests Remarks/Recommendations

High Current Test Pass

Insulation Test Pass

Contact Resistance Test Pass

Min. Close and Trip Test Pass

Megger Control WiringP

Mechanical InterlocksP

Name PlateP

Blown Fuse IndicatorN/A

4th Wire GroundN/A

Anti-Pump FunctionP

Test StickerP

Indicating StickersP

Auxiliary SwitchesP

Operation CounterN/A

DocumentsY

Power Factor AttachedN/A

TTA AttachedN/A

Operation Counter ReadingN/A

Comments:

Tester Initials gd

P=Pass

F=Fail

Y=Yes

N=No

N/A=Not Applicable

I=Incomplete

Additional Tests, Inspections, and Documentation

Page 3 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

High Current Test Data

FunctionPercent

Pickup

Current

(Amps)Curve Specs.

Phase A

(Seconds)

Phase B

(Seconds)

Phase C

(Seconds)

Long Time 300 3600 11-18 11.8 11.4 11.2 Pass/Fail: Pass

Short Time 150 7200 .35-.50 .480 .494 .475 Tester Initials: gd

Instantaneous 100 4800 +/- 10% Amps4615 Amps4610 Amps4636

Ground Fault N/A N/A N/A N/A N/A N/A

Comments:

Insulation Resistance Test

Comments:

Test

Voltage

Isolated

Bushing/s1

Open

2

Open

3

Open

4

Open

5

Open

6

Open

A Phase

Closed

B Phase

Closed

C Phase

Closed

1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass

Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd

Contact Resistance Test

Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass

N/A 33 32 31 Tester Initials: gd

In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest

value recorded (ANSI/NETA MTS-2011 7.5.1.1).

Comments:

Minimum Close/Trip Voltage Test

Required Value Tested Value

Minimum Close Voltage 104VAC 95 Pass/Fail: Pass

Mininum Trip Voltage 104VAC 85 Tester Initials: gd

Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).

Comments:

Page 4 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Equipment

Manufacturer Model Serial Number Calibration Expires Used For

AVO/ETI PS-9160R 11412 03/03/15 High Current

AVO/ETI PS-9160R 11412 03/03/15 High Current

Fluke 1520 92470030 03/03/15 Insulation Resistance

Biddle 247001 49017 03/03/15 Contact Resistance

CBS Big Gray 148990 03/03/15 Min Trip/Close

Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level

Page 1 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Job Information

Customer Rubicon Minerals

Test Information

Test Location Gainesville, TX

Temperature (°F) 73 (°C) 22

Test Condition As Left

Product Condition ReconditionedHumidity (%) 33

Circuit Breaker Information

Manufacturer Westinghouse

Model DS-416

Mechanism Model # N/A

Rated Maximum Voltage 600 V

Continuous Amp Rating 1600 A

Type Air

Charge 120VAC

Close 120VAC

Trip 120VAC

Serial Number 27261-006

Wiring Diag. # 2a 6a

Operator Manual/Electric

Mount Draw Out

Trip Unit Information

Manufacturer Westinghouse

Type Static/Solid State

Model Amptector I A LSI

Curve Number 2

C. T. Rating 1200

Rating Plug N/A

Serial Number N/A

Primary Fuses N/A

PickupSettings Band

Long Time 1.0 4

Short Time 4 .5

Instant 4 N/A

Ground Fault N/A N/A

Control Voltage

X N/A

Y 120VAC

UV N/A

Comments:

N/A

.5

Band

4

Quality Control Signature

Page 2 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Results Summary

Customer Rubicon Minerals

Manufacturer Westinghouse

Model DS-416 Serial Number 27261-006

Mechanical Inspection Pass

Electrical Inspection Pass

Inspections

Visual Inspection Pass

Remarks/Recommendations

Tests Remarks/Recommendations

High Current Test Pass

Insulation Test Pass

Contact Resistance Test Pass

Min. Close and Trip Test Pass

Megger Control WiringP

Mechanical InterlocksP

Name PlateP

Blown Fuse IndicatorN/A

4th Wire GroundN/A

Anti-Pump FunctionP

Test StickerP

Indicating StickersP

Auxiliary SwitchesP

Operation CounterN/A

DocumentsY

Power Factor AttachedN/A

TTA AttachedN/A

Operation Counter ReadingN/A

Comments:

Tester Initials gd

P=Pass

F=Fail

Y=Yes

N=No

N/A=Not Applicable

I=Incomplete

Additional Tests, Inspections, and Documentation

Page 3 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

High Current Test Data

FunctionPercent

Pickup

Current

(Amps)Curve Specs.

Phase A

(Seconds)

Phase B

(Seconds)

Phase C

(Seconds)

Long Time 300 3600 11-18 13.3 13.4 13.6 Pass/Fail: Pass

Short Time 150 7200 .35-.50 .490 .497 .482 Tester Initials: gd

Instantaneous 100 4800 +/- 10% Amps4810 Amps4910 Amps4859

Ground Fault N/A N/A N/A N/A N/A N/A

Comments:

Insulation Resistance Test

Comments:

Test

Voltage

Isolated

Bushing/s1

Open

2

Open

3

Open

4

Open

5

Open

6

Open

A Phase

Closed

B Phase

Closed

C Phase

Closed

1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass

Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd

Contact Resistance Test

Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass

N/A 31 29 30 Tester Initials: gd

In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest

value recorded (ANSI/NETA MTS-2011 7.5.1.1).

Comments:

Minimum Close/Trip Voltage Test

Required Value Tested Value

Minimum Close Voltage 104VAC 95 Pass/Fail: Pass

Mininum Trip Voltage 104VAC 85 Tester Initials: gd

Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).

Comments:

Page 4 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Equipment

Manufacturer Model Serial Number Calibration Expires Used For

AVO/ETI PS-9160R 11412 03/03/15 High Current

AVO/ETI PS-9160R 11412 03/03/15 High Current

Fluke 1520 92470030 03/03/15 Insulation Resistance

Biddle 247001 49017 03/03/15 Contact Resistance

CBS Big Gray 148990 03/03/15 Min Trip/Close

Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level

Page 1 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Job Information

Customer Rubicon Minerals

Test Information

Test Location Gainesville, TX

Temperature (°F) 73 (°C) 22

Test Condition As Left

Product Condition ReconditionedHumidity (%) 33

Circuit Breaker Information

Manufacturer Westinghouse

Model DS-416

Mechanism Model # N/A

Rated Maximum Voltage 600 V

Continuous Amp Rating 1600 A

Type Air

Charge 120VAC

Close 120VAC

Trip 120VAC

Serial Number 27261-007

Wiring Diag. # 2a 6a

Operator Manual/Electric

Mount Draw Out

Trip Unit Information

Manufacturer Westinghouse

Type Static/Solid State

Model Amptector I A LSI

Curve Number 2

C. T. Rating 1200

Rating Plug N/A

Serial Number N/A

Primary Fuses N/A

PickupSettings Band

Long Time 1.0 4

Short Time 4 .5

Instant 4 N/A

Ground Fault N/A N/A

Control Voltage

X N/A

Y 120VAC

UV N/A

Comments:

N/A

.5

Band

4

Quality Control Signature

Page 2 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Results Summary

Customer Rubicon Minerals

Manufacturer Westinghouse

Model DS-416 Serial Number 27261-007

Mechanical Inspection Pass

Electrical Inspection Pass

Inspections

Visual Inspection Pass

Remarks/Recommendations

Tests Remarks/Recommendations

High Current Test Pass

Insulation Test Pass

Contact Resistance Test Pass

Min. Close and Trip Test Pass

Megger Control WiringP

Mechanical InterlocksP

Name PlateP

Blown Fuse IndicatorN/A

4th Wire GroundN/A

Anti-Pump FunctionP

Test StickerP

Indicating StickersP

Auxiliary SwitchesP

Operation CounterN/A

DocumentsY

Power Factor AttachedN/A

TTA AttachedN/A

Operation Counter ReadingN/A

Comments:

Tester Initials gd

P=Pass

F=Fail

Y=Yes

N=No

N/A=Not Applicable

I=Incomplete

Additional Tests, Inspections, and Documentation

Page 3 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

High Current Test Data

FunctionPercent

Pickup

Current

(Amps)Curve Specs.

Phase A

(Seconds)

Phase B

(Seconds)

Phase C

(Seconds)

Long Time 300 3600 11-18 12.7 12.4 12.5 Pass/Fail: Pass

Short Time 150 7200 .35-.50 .474 .467 .493 Tester Initials: gd

Instantaneous 100 4800 +/- 10% Amps4812 Amps4725 Amps4635

Ground Fault N/A N/A N/A N/A N/A N/A

Comments:

Insulation Resistance Test

Comments:

Test

Voltage

Isolated

Bushing/s1

Open

2

Open

3

Open

4

Open

5

Open

6

Open

A Phase

Closed

B Phase

Closed

C Phase

Closed

1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass

Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd

Contact Resistance Test

Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass

N/A 30 29 29 Tester Initials: gd

In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest

value recorded (ANSI/NETA MTS-2011 7.5.1.1).

Comments:

Minimum Close/Trip Voltage Test

Required Value Tested Value

Minimum Close Voltage 104VAC 100 Pass/Fail: Pass

Mininum Trip Voltage 104VAC 85 Tester Initials: gd

Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).

Comments:

Page 4 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Equipment

Manufacturer Model Serial Number Calibration Expires Used For

AVO/ETI PS-9160R 11412 03/03/15 High Current

AVO/ETI PS-9160R 11412 03/03/15 High Current

Fluke 1520 92470030 03/03/15 Insulation Resistance

Biddle 247001 49017 03/03/15 Contact Resistance

CBS Big Gray 148990 03/03/15 Min Trip/Close

Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level

Page 1 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Job Information

Customer Rubicon Minerals

Test Information

Test Location Gainesville, TX

Temperature (°F) 73 (°C) 22

Test Condition As Left

Product Condition ReconditionedHumidity (%) 33

Circuit Breaker Information

Manufacturer Westinghouse

Model DS-416

Mechanism Model # N/A

Rated Maximum Voltage 600 V

Continuous Amp Rating 1600 A

Type Air

Charge 120VAC

Close 120VAC

Trip 120VAC

Serial Number 27261-008

Wiring Diag. # 2a 6a

Operator Manual/Electric

Mount Draw Out

Trip Unit Information

Manufacturer Westinghouse

Type Static/Solid State

Model Amptector I A LSI

Curve Number 2

C. T. Rating 1200

Rating Plug N/A

Serial Number N/A

Primary Fuses N/A

PickupSettings Band

Long Time 1.0 4

Short Time 4 .5

Instant 4 N/A

Ground Fault N/A N/A

Control Voltage

X N/A

Y 120VAC

UV N/A

Comments:

N/A

.5

Band

4

Quality Control Signature

Page 2 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Results Summary

Customer Rubicon Minerals

Manufacturer Westinghouse

Model DS-416 Serial Number 27261-008

Mechanical Inspection Pass

Electrical Inspection Pass

Inspections

Visual Inspection Pass

Remarks/Recommendations

Tests Remarks/Recommendations

High Current Test Pass

Insulation Test Pass

Contact Resistance Test Pass

Min. Close and Trip Test Pass

Megger Control WiringP

Mechanical InterlocksP

Name PlateP

Blown Fuse IndicatorN/A

4th Wire GroundN/A

Anti-Pump FunctionP

Test StickerP

Indicating StickersP

Auxiliary SwitchesP

Operation CounterN/A

DocumentsY

Power Factor AttachedN/A

TTA AttachedN/A

Operation Counter ReadingN/A

Comments:

Tester Initials gd

P=Pass

F=Fail

Y=Yes

N=No

N/A=Not Applicable

I=Incomplete

Additional Tests, Inspections, and Documentation

Page 3 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

High Current Test Data

FunctionPercent

Pickup

Current

(Amps)Curve Specs.

Phase A

(Seconds)

Phase B

(Seconds)

Phase C

(Seconds)

Long Time 300 3600 11-18 12.5 12.1 12.8 Pass/Fail: Pass

Short Time 150 7200 .35-.50 .488 .489 .485 Tester Initials: gd

Instantaneous 100 4800 +/- 10% Amps4612 Amps4547 Amps4531

Ground Fault N/A N/A N/A N/A N/A N/A

Comments:

Insulation Resistance Test

Comments:

Test

Voltage

Isolated

Bushing/s1

Open

2

Open

3

Open

4

Open

5

Open

6

Open

A Phase

Closed

B Phase

Closed

C Phase

Closed

1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass

Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd

Contact Resistance Test

Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass

N/A 32 37 33 Tester Initials: gd

In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest

value recorded (ANSI/NETA MTS-2011 7.5.1.1).

Comments:

Minimum Close/Trip Voltage Test

Required Value Tested Value

Minimum Close Voltage 104VAC 90 Pass/Fail: Pass

Mininum Trip Voltage 104VAC 85 Tester Initials: gd

Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).

Comments:

Page 4 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Equipment

Manufacturer Model Serial Number Calibration Expires Used For

AVO/ETI PS-9160R 11412 03/03/15 High Current

AVO/ETI PS-9160R 11412 03/03/15 High Current

Fluke 1520 92470030 03/03/15 Insulation Resistance

Biddle 247001 49017 03/03/15 Contact Resistance

CBS Big Gray 148990 03/03/15 Min Trip/Close

Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level

Page 1 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Job Information

Customer Rubicon Minerals

Test Information

Test Location Gainesville, TX

Temperature (°F) 73 (°C) 22

Test Condition As Left

Product Condition ReconditionedHumidity (%) 33

Circuit Breaker Information

Manufacturer Westinghouse

Model DS-416

Mechanism Model # N/A

Rated Maximum Voltage 600 V

Continuous Amp Rating 1600 A

Type Air

Charge 120VAC

Close 120VAC

Trip 120VAC

Serial Number 27261-009

Wiring Diag. # 2a 6a

Operator Manual/Electric

Mount Draw Out

Trip Unit Information

Manufacturer Westinghouse

Type Static/Solid State

Model Amptector I A LSI

Curve Number 2

C. T. Rating 1200

Rating Plug N/A

Serial Number N/A

Primary Fuses N/A

PickupSettings Band

Long Time 1.0 4

Short Time 4 .5

Instant 4 N/A

Ground Fault N/A N/A

Control Voltage

X N/A

Y 120VAC

UV N/A

Comments:

N/A

.5

Band

4

Quality Control Signature

Page 2 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Results Summary

Customer Rubicon Minerals

Manufacturer Westinghouse

Model DS-416 Serial Number 27261-009

Mechanical Inspection Pass

Electrical Inspection Pass

Inspections

Visual Inspection Pass

Remarks/Recommendations

Tests Remarks/Recommendations

High Current Test Pass

Insulation Test Pass

Contact Resistance Test Pass

Min. Close and Trip Test Pass

Megger Control WiringP

Mechanical InterlocksP

Name PlateP

Blown Fuse IndicatorN/A

4th Wire GroundN/A

Anti-Pump FunctionP

Test StickerP

Indicating StickersP

Auxiliary SwitchesP

Operation CounterN/A

DocumentsY

Power Factor AttachedN/A

TTA AttachedN/A

Operation Counter ReadingN/A

Comments:

Tester Initials gd

P=Pass

F=Fail

Y=Yes

N=No

N/A=Not Applicable

I=Incomplete

Additional Tests, Inspections, and Documentation

Page 3 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

High Current Test Data

FunctionPercent

Pickup

Current

(Amps)Curve Specs.

Phase A

(Seconds)

Phase B

(Seconds)

Phase C

(Seconds)

Long Time 300 3600 11-18 11.2 11.2 11.3 Pass/Fail: Pass

Short Time 150 7200 .35-.50 .499 .490 .498 Tester Initials: gd

Instantaneous 100 4800 +/- 10% Amps4812 Amps4760 Amps4750

Ground Fault N/A N/A N/A N/A N/A N/A

Comments:

Insulation Resistance Test

Comments:

Test

Voltage

Isolated

Bushing/s1

Open

2

Open

3

Open

4

Open

5

Open

6

Open

A Phase

Closed

B Phase

Closed

C Phase

Closed

1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass

Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd

Contact Resistance Test

Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass

N/A 34 35 32 Tester Initials: gd

In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest

value recorded (ANSI/NETA MTS-2011 7.5.1.1).

Comments:

Minimum Close/Trip Voltage Test

Required Value Tested Value

Minimum Close Voltage 104VAC 90 Pass/Fail: Pass

Mininum Trip Voltage 104VAC 85 Tester Initials: gd

Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).

Comments:

Page 4 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Equipment

Manufacturer Model Serial Number Calibration Expires Used For

AVO/ETI PS-9160R 11412 03/03/15 High Current

AVO/ETI PS-9160R 11412 03/03/15 High Current

Fluke 1520 92470030 03/03/15 Insulation Resistance

Biddle 247001 49017 03/03/15 Contact Resistance

CBS Big Gray 148990 03/03/15 Min Trip/Close

Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level

Page 1 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Job Information

Customer Rubicon Minerals

Test Information

Test Location Gainesville, TX

Temperature (°F) 73 (°C) 22

Test Condition As Left

Product Condition ReconditionedHumidity (%) 33

Circuit Breaker Information

Manufacturer Westinghouse

Model DS-416

Mechanism Model # N/A

Rated Maximum Voltage 600 V

Continuous Amp Rating 1600 A

Type Air

Charge 120VAC

Close 120VAC

Trip 120VAC

Serial Number 27261-010

Wiring Diag. # 2a 6a

Operator Manual/Electric

Mount Draw Out

Trip Unit Information

Manufacturer Westinghouse

Type Static/Solid State

Model Amptector I A LSI

Curve Number 2

C. T. Rating 1200

Rating Plug N/A

Serial Number N/A

Primary Fuses N/A

PickupSettings Band

Long Time 1.0 4

Short Time 4 .5

Instant 4 N/A

Ground Fault N/A N/A

Control Voltage

X N/A

Y 120VAC

UV N/A

Comments:

N/A

.5

Band

4

Quality Control Signature

Page 2 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Results Summary

Customer Rubicon Minerals

Manufacturer Westinghouse

Model DS-416 Serial Number 27261-010

Mechanical Inspection Pass

Electrical Inspection Pass

Inspections

Visual Inspection Pass

Remarks/Recommendations

Tests Remarks/Recommendations

High Current Test Pass

Insulation Test Pass

Contact Resistance Test Pass

Min. Close and Trip Test Pass

Megger Control WiringP

Mechanical InterlocksP

Name PlateP

Blown Fuse IndicatorN/A

4th Wire GroundN/A

Anti-Pump FunctionP

Test StickerP

Indicating StickersP

Auxiliary SwitchesP

Operation CounterN/A

DocumentsY

Power Factor AttachedN/A

TTA AttachedN/A

Operation Counter ReadingN/A

Comments:

Tester Initials gd

P=Pass

F=Fail

Y=Yes

N=No

N/A=Not Applicable

I=Incomplete

Additional Tests, Inspections, and Documentation

Page 3 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

High Current Test Data

FunctionPercent

Pickup

Current

(Amps)Curve Specs.

Phase A

(Seconds)

Phase B

(Seconds)

Phase C

(Seconds)

Long Time 300 3600 11-18 12.5 13.2 13.4 Pass/Fail: Pass

Short Time 150 7200 .35-.50 .48 .467 .471 Tester Initials: gd

Instantaneous 100 4800 +/- 10% Amps4788 Amps4712 Amps4675

Ground Fault N/A N/A N/A N/A N/A N/A

Comments:

Insulation Resistance Test

Comments:

Test

Voltage

Isolated

Bushing/s1

Open

2

Open

3

Open

4

Open

5

Open

6

Open

A Phase

Closed

B Phase

Closed

C Phase

Closed

1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass

Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd

Contact Resistance Test

Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass

N/A 35 33 35 Tester Initials: gd

In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest

value recorded (ANSI/NETA MTS-2011 7.5.1.1).

Comments:

Minimum Close/Trip Voltage Test

Required Value Tested Value

Minimum Close Voltage 104VAC 90 Pass/Fail: Pass

Mininum Trip Voltage 104VAC 85 Tester Initials: gd

Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).

Comments:

Page 4 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Equipment

Manufacturer Model Serial Number Calibration Expires Used For

AVO/ETI PS-9160R 11412 03/03/15 High Current

AVO/ETI PS-9160R 11412 03/03/15 High Current

Fluke 1520 92470030 03/03/15 Insulation Resistance

Biddle 247001 49017 03/03/15 Contact Resistance

CBS Big Gray 148990 03/03/15 Min Trip/Close

Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level

Page 1 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Job Information

Customer Rubicon Minerals

Test Information

Test Location Gainesville, TX

Temperature (°F) 73 (°C) 22

Test Condition As Left

Product Condition ReconditionedHumidity (%) 33

Circuit Breaker Information

Manufacturer Westinghouse

Model DS-416

Mechanism Model # N/A

Rated Maximum Voltage 600 V

Continuous Amp Rating 1600 A

Type Air

Charge 120VAC

Close 120VAC

Trip 120VAC

Serial Number 27261-011

Wiring Diag. # 2a 6a

Operator Manual/Electric

Mount Draw Out

Trip Unit Information

Manufacturer Westinghouse

Type Static/Solid State

Model Amptector I A LSI

Curve Number 2

C. T. Rating 1200

Rating Plug N/A

Serial Number N/A

Primary Fuses N/A

PickupSettings Band

Long Time 1.0 4

Short Time 4 .5

Instant 4 N/A

Ground Fault N/A N/A

Control Voltage

X N/A

Y 120VAC

UV N/A

Comments:

N/A

.5

Band

4

Quality Control Signature

Page 2 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Results Summary

Customer Rubicon Minerals

Manufacturer Westinghouse

Model DS-416 Serial Number 27261-011

Mechanical Inspection Pass

Electrical Inspection Pass

Inspections

Visual Inspection Pass

Remarks/Recommendations

Tests Remarks/Recommendations

High Current Test Pass

Insulation Test Pass

Contact Resistance Test Pass

Min. Close and Trip Test Pass

Megger Control WiringP

Mechanical InterlocksP

Name PlateP

Blown Fuse IndicatorN/A

4th Wire GroundN/A

Anti-Pump FunctionP

Test StickerP

Indicating StickersP

Auxiliary SwitchesP

Operation CounterN/A

DocumentsY

Power Factor AttachedN/A

TTA AttachedN/A

Operation Counter ReadingN/A

Comments:

Tester Initials gd

P=Pass

F=Fail

Y=Yes

N=No

N/A=Not Applicable

I=Incomplete

Additional Tests, Inspections, and Documentation

Page 3 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

High Current Test Data

FunctionPercent

Pickup

Current

(Amps)Curve Specs.

Phase A

(Seconds)

Phase B

(Seconds)

Phase C

(Seconds)

Long Time 300 3600 11-18 13.3 13.6 13.6 Pass/Fail: Pass

Short Time 150 7200 .35-.50 .498 .499 .500 Tester Initials: gd

Instantaneous 100 4800 +/- 10% Amps4610 Amps4810 Amps4615

Ground Fault N/A N/A N/A N/A N/A N/A

Comments:

Insulation Resistance Test

Comments:

Test

Voltage

Isolated

Bushing/s1

Open

2

Open

3

Open

4

Open

5

Open

6

Open

A Phase

Closed

B Phase

Closed

C Phase

Closed

1K (K) Megohms 2 2 2 2 2 2 2 2 2 Pass/Fail: Pass

Temp. Adjusted (20°C) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Tester Initials: gd

Contact Resistance Test

Manufacturer Spec (µΩ) Phase A (µΩ) Phase B (µΩ) Phase C (µΩ) Pass/Fail: Pass

N/A 36 32 37 Tester Initials: gd

In the absence of manufacturer recommendations investigate values which deviate by more than 50 percent from the lowest

value recorded (ANSI/NETA MTS-2011 7.5.1.1).

Comments:

Minimum Close/Trip Voltage Test

Required Value Tested Value

Minimum Close Voltage 104VAC 95 Pass/Fail: Pass

Mininum Trip Voltage 104VAC 85 Tester Initials: gd

Minimum close and trip values may not be higher than the published minimum values (ANSI/NETA MTS-2011 Table 100.20.1).

Comments:

Page 4 of 4

Low Voltage Circuit Breaker Test Report Rev. 14, 12-14

Job Number 27261 Date 12/16/14

Test Equipment

Manufacturer Model Serial Number Calibration Expires Used For

AVO/ETI PS-9160R 11412 03/03/15 High Current

AVO/ETI PS-9160R 11412 03/03/15 High Current

Fluke 1520 92470030 03/03/15 Insulation Resistance

Biddle 247001 49017 03/03/15 Contact Resistance

CBS Big Gray 148990 03/03/15 Min Trip/Close

Haefely DIAS Type 730 081 683 - 011 N/A Basic Impulse Level

! " # $ % ! & ' % ( )* + * , - . / 0 1 2 3 4 5 6 1 4 7 8 9 1 : : 7, ; < , - * = * * = - <> 7 8 ? 1 4 5 @ 3 / 8 7 1 4 A 3 3 .A 8 / 4 1 ? B *C , D D 9 * D D D 6E 6 1 4 * D D D - C F 1 = 5 6 . A G 6 8 8 * D D 6 1 3 4 * D - * D D * D -E 6 1 4 * D D D F 6 8 7 H H D G 6 8 8I A . B - - * D D < C F 1 = 5 6 . A G 6 8 8I A . B * - * D D < C F 1 = 5 6 . A G 6 8 8I A . B H - * D D < C F 1 = 5 6 . A G 6 8 8I A . B < - * D D < C F 1 = 5 6 . A G 6 8 8

< D D < D - < D D < D D 4 J 6 4 J 6 4 J 6 4 J 6 4 J 6 K D C F K D K D C - + ; C ; 4 J 6 4 J 6 4 J 6

L M

N O M M

P

* C F H * D D F D D D H + D D 4 J 6I A . B - - * D D 6 - D 6 - * K - * K - H *I A . B * - * D D 6 - D 6 - * D - * * - * ;I A . B H - * D D 6 - D 6 - * < - * - - - ;I A . B < - * D D 6 - D 6 - - H - - ; - * D

4 J 6

? Q

R S S T U V W X Y Z [ \ ] U ^ W [ V _ ` S [ a b ` W U c ` ^ ^ Z ` S S d e _ f \ [ U V f g _ U b W [ g [ _ ` W [ f ^ [ V ` h ` [ S ` a S U [ ^ W i U X ^ j [ ^ U U b [ ^ j k U \ ` b W ] U ^ W lm f b ] V n o p q r m s t q s u W i b f Z j i n o p q r m s t q v w

x y z | ~ z z ~ ~ ~ ~ ~ ¡ ¢ £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « § ¦ ¬ ­ ® ¯ ¡ ° ¥ ­ £ ¤ ¥ ¦ ¥ ± ± ± ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ³ µ ¶ § ² ­ · ª ª ¥ § ¸ ³ ³ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ³ µ ¶ § ² ­ · ª ª ¥ § ¥ § © ± µ ¶ § ² ­ · ª ª ¥ ¬ · ¡ ¤ £ £ ± ¹ ¡ º £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¦ ¹ » ¼ ´ ¹ ³ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ± ¡ º £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¦ ¹ » ¼ ´ ¹ ³ ³ ± µ ¶ § ² ­ · ª ª ¥ § ¸ µ ¶ § ² ­ · ª ª ¥ ³ © ½ § ¾ ± ± £ µ ¶ § ² ­ · ª ª ¥ ¹ ³ ¹ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ¹ ¾ ¡ ª « ¿ § ¥ ¯ ¨ ¢ ³ ¹ ¡ ¢ £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¾ À ¡ ¢ £ ¤ ¥ ¦ ¥ © ¶ Á ½ £ ´ ¬ ¦ ¹ ± ¡ ¢ £ ¤ ¥ ¦ ¥ © ¶ Á ½ £ ´ ¬ ¦ ¹ ± § ² ² ± ± µ ¶ § ² ­ · ª ª ¥ © ½ § ¾ ¹ § ² ¥ ¡ § ¨ ¥ ª ¥ § ¥ ª ¡ ¿ À ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ¹ ¹ ³ ³ µ ¶ § ² ­ · ª ª ¥ ¯ ¨ ¢ ¹ ¹ µ ¶ § ² ­ · ª ª ¥ ¯ ¨ ¢ ¹ ¬ ­ ® ¯ ¡ ° ¥ ­ £ ¤ ¥ ¦ ¥ ­ Â § ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ Á ¼ ± ± ¡ º £ ¤ ¥ ¦ ¥ ­ Â ¯ ± © ¾ Ã ² · ¬ ­ ¥ Ã ² · ¶ ­ ¥ ¡ ² ¬ £ ¦ ¹ § ¥ § ² ² ± ± Á Á ± µ ¶ ¾ Ã º « ­ ¥ Ã « ­ ¥ ­ ¿ ° ¤ ³ ± ¬ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ¶ Ä Å ±

! " # $ % ! & ' % ( )* + * , - . / 0 1 2 3 4 5 6 1 4 7 8 9 1 : : 7, ; < , - * = * * = - <> 7 8 ? 1 4 5 @ 3 / 8 7 1 4 A 3 3 .A 8 / 4 1 ? B *C , D D 9 * D D D 6E 6 1 4 * D D D - C F 1 = 5 6 . A G 6 8 8 * D D 6 1 3 4 * D - * D D * D -E 6 1 4 * D D D F 6 8 7 H H D G 6 8 8I A . B - - * D D < C F 1 = 5 6 . A G 6 8 8I A . B * - * D D < C F 1 = 5 6 . A G 6 8 8I A . B H - * D D < C F 1 = 5 6 . A G 6 8 8I A . B < - * D D < C F 1 = 5 6 . A G 6 8 8

< D D < D - < D D < D D 4 J 6 4 J 6 4 J 6 4 J 6 4 J 6 K D C F K D K D C - + ; C ; 4 J 6 4 J 6 4 J 6

L M

N O M M

P

* C F H * D D F D D D H + D D 4 J 6I A . B - - * D D 6 - D 6 - * K - * K - H *I A . B * - * D D 6 - D 6 - * D - * * - * ;I A . B H - * D D 6 - D 6 - * < - * - - - ;I A . B < - * D D 6 - D 6 - - H - - ; - * D

4 J 6

? Q

R S S T U V W X Y Z [ \ ] U ^ W [ V _ ` S [ a b ` W U c ` ^ ^ Z ` S S d e _ f \ [ U V f g _ U b W [ g [ _ ` W [ f ^ [ V ` h ` [ S ` a S U [ ^ W i U X ^ j [ ^ U U b [ ^ j k U \ ` b W ] U ^ W lm f b ] V n o p q r m s t q s u W i b f Z j i n o p q r m s t q v w

x y z | ~ z z ~ ~ ~ ~ ~ ¡ ¢ £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « § ¦ ¬ ­ ® ¯ ¡ ° ¥ ­ £ ¤ ¥ ¦ ¥ ± ± ± ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ³ µ ¶ § ² ­ · ª ª ¥ § ¸ ³ ³ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ³ µ ¶ § ² ­ · ª ª ¥ § ¥ § © ± µ ¶ § ² ­ · ª ª ¥ ¬ · ¡ ¤ £ £ ± ¹ ¡ º £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¦ ¹ » ¼ ´ ¹ ³ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ´ ´ ´ ± ¡ º £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¦ ¹ » ¼ ´ ¹ ³ ³ ± µ ¶ § ² ­ · ª ª ¥ § ¸ µ ¶ § ² ­ · ª ª ¥ ³ © ½ § ¾ ± ± £ µ ¶ § ² ­ · ª ª ¥ ¹ ³ ¹ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ¹ ¾ ¡ ª « ¿ § ¥ ¯ ¨ ¢ ³ ¹ ¡ ¢ £ ¤ ¥ ¦ ¥ § ¨ ¥ © ª « ¾ À ¡ ¢ £ ¤ ¥ ¦ ¥ © ¶ Á ½ £ ´ ¬ ¦ ¹ ± ¡ ¢ £ ¤ ¥ ¦ ¥ © ¶ Á ½ £ ´ ¬ ¦ ¹ ± § ² ² ± ± µ ¶ § ² ­ · ª ª ¥ © ½ § ¾ ¹ § ² ¥ ¡ § ¨ ¥ ª ¥ § ¥ ª ¡ ¿ À ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ¹ ¹ ³ ³ µ ¶ § ² ­ · ª ª ¥ ¯ ¨ ¢ ¹ ¹ µ ¶ § ² ­ · ª ª ¥ ¯ ¨ ¢ ¹ ¬ ­ ® ¯ ¡ ° ¥ ­ £ ¤ ¥ ¦ ¥ ­ Â § ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ Á ¼ ± ± ¡ º £ ¤ ¥ ¦ ¥ ­ Â ¯ ± © ¾ Ã ² · ¬ ­ ¥ Ã ² · ¶ ­ ¥ ¡ ² ¬ £ ¦ ¹ § ¥ § ² ² ± ± Á Á ± µ ¶ ¾ Ã º « ­ ¥ Ã « ­ ¥ ­ ¿ ° ¤ ³ ± ¬ ² ¥ ¡ § ¨ ¥ ª ¥ ¯ ¨ ¢ ³ ¶ Ä Å ±

P.O. BOX 1098 1315 COLUMBINE ST.

GAINESVILLE, TX 76240

P.O. BOX 1098 1315 COLUMBINE ST.

GAINESVILLE, TX 76240

P.O. BOX 1098 1315 COLUMBINE ST.

GAINESVILLE, TX 76240

P.O. BOX 1098 1315 COLUMBINE ST.

GAINESVILLE, TX 76240

P.O. BOX 1098 1315 COLUMBINE ST.

GAINESVILLE, TX 76240

P.O. BOX 1098 1315 COLUMBINE ST.

GAINESVILLE, TX 76240