SIGNALIZATION SYSTEM LIGHT COLUMNS EX SEMAPHORES LIGHT PANEL light panel for mounting in Engine Control Room (ECR) from 2 up to 8 symbols lamp test incorporated audio signalization (buzzer) incorporated power supply 24V,DC flush mounting (bulkhead on special request) our range of light columns (semaphores) also include versions for dangerous area where different number of symbols, sirens and/or flashing lights can be chosen SIGNALIZATION SYSTEM is applied on board ships and particularly within the area of engine room, where requirements for several alarms signalization by visual and/or audible means exist. The SIGNALIZATION SYSTEM has been developed having in mind the basic idea of unifying all the alarms signalization within one common system. THE NEW GENERATION OF LIGHT COLUMNS use LE diodes instead of incandescent lamps. SIGNALIZATION SYSTEM meets requirements of IMO, ISO, SBG and all major classif ication societies. WE ARE AT YOUR DISPOSAL to deliver each part of the system separately, to meet any modification and special requirement, to perform complete engineering. siren ITES-M-..., 1 input,32 different tones (for detailed information see separate leaflet) lamp test push button (or lamp test / DMA reset push button, on request) power indicator self adhesive symbols possible to change in "last minute" wide range of two-inputs programmable sirens series ITES (for detailed information see separate leaflet) flashing light ITFL Ex-proof connection boxes ITES-110Ex or ITES-115Ex sirens' loudspeakers Ex-proof light symbols Ex-proof flashing lights power indicator internal buzzer lamp and buzzer test symbol fields DMA reset button can be mounted 01 · SIGNALIZATION ENGINEERING FOR ELECTRONIC EQUIPMENT AND SYSTEMS light columns (semaphores) for bulkhead mounting in engine room spaces up to 12 symbols with or without flashing lights with or without sirens / loudspeakers power supply 230V,AC or 110V,AC or 24V,DC protection IP 54 bulkhead mounting LE diodes instead of incandescent lamps can be used

Upload: nguyentram

Post on 16-Sep-2018

269 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SIGNALIZATION SYSTEM - INELTEH 01 Signalization System.pdf · SIGNALIZATION SYSTEM LIGHT COLUMNS EX SEMAPHORES LIGHT PANEL • light panel for mounting in Engine Control Room (ECR)

SIGNALIZATION SYSTEM

LIGHT COLUMNS

EX SEMAPHORES

LIGHT PANEL• light panel for mounting in Engine Control Room

(ECR)• from 2 up to 8 symbols• lamp test incorporated• audio signalization (buzzer) incorporated• power supply 24V,DC• f lush mounting (bulkhead on special request)

• our range of light columns (semaphores) also include versions for dangerous area where different number of symbols, sirens and/or f lashing lights can be chosen

SIGNALIZATION SYSTEM is applied on board ships and particularly within the area of engine room, where requirements for several alarms signalization by visual and/or audible means exist. The SIGNALIZATION SYSTEM has been developed having in mind the basic idea of unifying all the alarms signalization within one common system.

THE NEW GENERATION OF LIGHT COLUMNS use LE diodes instead of incandescent lamps.

SIGNALIZATION SYSTEM meets requirements of IMO, ISO, SBG and all major classif ication societies.

WE ARE AT YOUR DISPOSAL to deliver each part of the system separately, to meet any modification and special requirement, to perform complete engineering.

siren ITES-M-...,1 input,32 different tones(for detailed informationsee separate leaflet)

lamp test push button(or lamp test / DMA resetpush button, on request)

power indicator

self adhesive symbols possible to change in "last minute"

wide range oftwo-inputs programmable sirens series ITES (for detailed information see separate leaflet)

f lashing light ITFL

Ex-proof connection boxes

ITES-110Ex orITES-115Ex sirens'loudspeakers

Ex-proof light symbols

Ex-proof f lashing lights

power indicator

internal buzzer

lamp and buzzer test

symbol f ields

DMA reset buttoncan be mounted

01 · SIGNALIZATION

ENGINEERING FOR ELECTRONIC EQUIPMENT AND SYSTEMS

• light columns (semaphores) for bulkhead mounting in engine room spaces

• up to 12 symbols• with or without f lashing lights• with or without sirens /

loudspeakers• power supply 230V,AC or

110V,AC or 24V,DC• protection IP 54• bulkhead mounting

LE diodes instead ofincandescent lampscan be used

Page 2: SIGNALIZATION SYSTEM - INELTEH 01 Signalization System.pdf · SIGNALIZATION SYSTEM LIGHT COLUMNS EX SEMAPHORES LIGHT PANEL • light panel for mounting in Engine Control Room (ECR)

AUDIBLE SIGNALIZATION (for detailed information see separate leaflet)

SIGNALLING UNITS

ELECTRONICMULTITONESIREN ITES-M-...with one input32 different tones

PROGRAMMABLEELECTRONIC MULTITONESIRENS ITES-...wide range of two-inputsprogrammable sirens

CONTROL UNIT ITCU• signal processing• double supply possibility (main

and emergency) with automatic change-over

• comprise electronic units of sirens (if exist)

• bulkhead mounting or mounting within console

ALARM INPUTS:• General Alarm• Fire Alarm• CO release alarm or 2

FOAM• Machinery alarm• DMA• Telephone call alarm• Telegraph alarm• Bilge alarm

ALARM OUTPUTS:• to semaphores• to flashing lights• to sirens

FLASHING LIGHTS

STANDARD FLASHING LIGHT ITFL

• Power supply / consumption: 12V,DC / 0.8A; 24V,DC / 0.5A; 110V,AC / 0.2A; 230V,AC / 0.1A• Approx. 60 flashes per minute• Temperature range -20°C/+55°C• Flashing energy 6J• IP protection IP 54• Weight approx. 0.27 kg• Colours: red, amber, blue, green, white, green-white• Steel support can be delivered (on request)

EX-PROOF FLASHING LIGHT

• Type: 6161 or CWB-ATEX or XB9• Explosion protection: EEx de IIC T5/T6 (EEx d IIC T5/T6 for XB9)• Power supply: 230V,AC• Consumption: 80mA (60mA for XB9)• Flashing power 5J• Primary fuse 0.20AT• Protection IP 66• Weight approx.1.6 kg• Colours: red, amber, blue, green

XB9

6161or

CWB-ATEX

• various signalling units for different alarm purposes

• different visual and audio alarms to suit your needs

ENGINEERING FOR ELECTRONIC EQUIPMENT AND SYSTEMS

Page 3: SIGNALIZATION SYSTEM - INELTEH 01 Signalization System.pdf · SIGNALIZATION SYSTEM LIGHT COLUMNS EX SEMAPHORES LIGHT PANEL • light panel for mounting in Engine Control Room (ECR)

ENGINE ROOM ALARM INDICATION SYSTEM BLOCK DIAGRAM (EXAMPLE)

6 pcs ofITS-07-ER-230-3FL-2S

Light columns

ITES-110-3siren's

electronicmodule

Symbols (7+1common),audio signal to loudspeakers (4)and light panel supply (2)

1 pcs ofITS-07-CRLight panel

TEST POWERON

CO2CO2

LOUDSP.110dB

ITES-M-230SIREN

RED AMBER

GREEN-WHITE

TEST POWERON

CO2CO2

LOUDSP.110dB

ITES-M-230SIREN

RED AMBER

GREEN-WHITE

TYPE ITS-07-CR-

INELTEHCroatia

CO 2

TEST

POWER ON

2 pcs of

N.O

. vol

tage

free

inpu

t co

ntac

ts

Junction box(Yard supply)10 10

1010

10

Light column supply (2),flashing lights supply (6)

and ITES-M-230 siren (2)

1 pcs ofITCU-7, 230V AC

Control unit

GENERAL

CO2

FIRE

MACHINERY

DMA

TELEPHONE

TELEGRAPH

IMO CODE 1A, 800 HZ

IMO CODE 2, 1000 HZ

IMO CODE 2, 800 HZ

CO2

IMO CODE 3A

IMO CODE 3A

IMO CODE 3A

IMO CODE 3A

GENERAL

CO2

FIRE

MACHINERY

DMA

TELEPHONE

TELEGRAPH

AUDIOPRIORITY: 1. CO2 2. FIRE 3. GENERAL 4. OTHERS

LIGHT COLUMN DIMENSIONS

TEST POWERON

200180

226148 70

35A

C (

only

for

11 a

nd 1

2 sy

mbo

ls)

B10

0

177 max 105

EARTHBOLT

HINGES

440

FIXINGHOLES O8

142

FL.LIGHT FL.LIGHTFL.LIGHT

ITES-M-xxxSIREN

ITES SIREN'SLOUDSPEAKER

TEST POWERON

200180

226148 70

35A

B10

0

105

EARTHBOLT

HINGES

440

FIXINGHOLES O8

142

FL.LIGHT FL.LIGHT

ITES-M-xxxSIREN

ITES SIREN'S LOUDSP.

286 max

FL.LIGHT

If ITES siren 115 or 120 dBis used, loudspeaker ismounted on the top

230V,AC POWER SUPPLY

POWER FAILUREALARM OUTPUT

(VOLTAGE-FREE C.O. CONTACT)

PRINCIPLE OF OPERATION

C (

only

for

11 a

nd 1

2 sy

mbo

ls)

01 · SIGNALIZATION

Page 4: SIGNALIZATION SYSTEM - INELTEH 01 Signalization System.pdf · SIGNALIZATION SYSTEM LIGHT COLUMNS EX SEMAPHORES LIGHT PANEL • light panel for mounting in Engine Control Room (ECR)

335

335

535

535

635

735

835

935

1035

1135

A (mm)

3

4

5

6

7

8

9

10

11

12

Number of symbols

470

470

670

670

770

870

970

1070

1170

1270

B (mm)

-

-

-

-

-

-

-

-

517.5

567.5

C (mm)

All dimensions are in mm.

35

50

1035

260

O70 280

340

O7

M20x1.56-13mm

Ø5.

5

120°

12.

50

88

1814

0

Ø112

EX-PROOF FLASHING LIGHTS

6161 or CWB-ATEX XB9

STANDARDFLASHING LIGHTS

ITFL

FLASHING LIGHTS DIMENSIONS

LIGHT COLUMNS DIMENSIONS

LIGHT COLUMNS and LIGHT PANEL ORDERING INFORMATION

ITS - 06 - ER - 230 - x - 3FL - 2SInelteh's semaphores

Number of symbol fields

Power supply 230V,AC / 110V,AC / 24V,DC

ER - LIGHT COLUMN, bulkhead mounting (engine room)CR - LIGHT PANEL, flush mounting (engine control room)

* Lamp test and power indication are not incorporated for 230V AC.

Flashing lights

Number of sirens/loudspeakers (1 or 2)Siren type should be specify separately

Number of flashing lights

8074

M3

72

180

174

172 CONSOLE

CUT-OUT

DEPTH IS 55 mm 6

6

TYPE

INELTEH

POWER ONCroatia

T E S T

CO 2

FLASHING LIGHT ITFL ORDERING INFORMATION

ITFL - 230 - RInelteh's flashing light

ColourR(red), A(amber), G(green), B(blue), W(white/clear), GW(green-white)Power supply 230V,AC / 110V,AC / 24V,DC / 12V,DC

LIGHT PANEL DIMENSIONS

330

60

1035

248

O80

35O7

M20x1.56-13mm

Ljubljanska cesta 7, HR-51000 Rijeka / Croatia / tel. ++385 51 274 536 / fax 712 122 / [email protected] / www.inelteh.hr

** If light column supply is 230V AC, light bulbs or LE diodes operate on 24V DC over incorporated rectif ier 230/24V. Lamp test and power indication for each light column are incorporated.

Empty - incandescent bulbs, operate on 24V DC**A - incandescent bulbs, operate on 230V AC*

L - LE diodes, operate on 24V DC**