    SwitchgearType SIMOSEC up to 24 kV,Air-Insulated, Extendable

    Medium-VoltageSwitchgear

    Catalog HA 41.212003

    Supersedes:

    Catalog HA 41.21 . 2002

  • 7/26/2019 Simosec En

    2/44

    2 SiemensHA41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Contents Application

    Page

    Application, Requirements

    Typical uses, features 2 and 3

    Technical Data

    Electrical data, pressure values,temperature 4 and 5

    Switchgear installation 6

    Shipping data 7

    Product Range

    Product range overview, equipmentfeatures 8 and 9

    Panels 10 to 15

    Design

    Panel design 16 and 17

    Components

    3AH vacuum circuit-breakers 18 to 20

    Three-position switches 21

    Busbars, HV HRC fuse assembly 22 and 23

    Operating mechanisms 24

    Indicating and measuring equipment 25

    Interlocking systems and locking devices 26

    Transformers 27 to 29

    Cable connection 30 and 31

    Low-voltage equipment 32

    Dimensions

    Panels 33 to 39

    Floor openings, fixing points 40

    Standards

    Standards, specifications, guidelines 41 to 43

    Notes

    43

    Siemens AG 2003

    Example4-panel transfer switchgear withintegrated low-voltage niche

    R-HA41-082eps

    R-HA41-055eps

    Utilities transfer substationfor industrial plants

    Typical uses

  • 7/26/2019 Simosec En

    3/44

    SiemensHA 41.21 2003 3

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Application, Requirements

    Reliability

    Type and routine-testedStandardized and manu-

    factured using numericallycontrolled machines

    Quality management systemaccording to DIN EN ISO 9001

    More than 350,000 switchgearcomponents in operationworldwide for many years

    No cross-insulation betweenphases

    Personal safety

    All switching operations can

    be performed with closedpanel front

    Metal-enclosed, cubicle-typeor metal-clad switchgear

    HV HRC fuses and cable seal-ing ends are only accessiblewhen the outgoing feeders areearthed

    Logical mechanical interlocking

    Capacitive voltage detectionsystem for verification of safeisolation from supply

    Earthing of outgoing feedersby means of make-proof

    earthing switches

    Security of operation

    Components, e.g. operatingmechanisms, three-positionswitches, vacuum circuit-breakers proven for years

    Metal-clad panels (metal com-partmentalization betweenbusbar and switching deviceand between switching deviceand cable connection compart-ment)

    Cubicle-type panels with

    metal compartmentalizationbetween switching device andbusbar compartment

    Three-position switch metal-enclosed with gas-insulatedswitching functions

    Welded sealed-for-lifeswitchgear vessel

    No cross-insulation betweenphases

    With welded-in bushings forcable connection, busbar andoperating mechanism

    Switch operating mechanismsoutside switchgear vessel

    Maintenance-free operatingmechanism parts (IEC 60 694/VDE 0670 Part 1000 *)

    SIMOSEC switchgear is afactory-assembled, type-

    tested, three-phase, metal-enclosed, metal-clad indoorswitchgear according toIEC 60 298 / VDE 0670,Part 6 for single busbars.

    Typical uses

    SIMOSEC switchgear isused for power distribution indistribution systems withfeeder currents up to 1250 A.

    Modular space-saving designallows use in

    Substations, customer trans-

    fer substations, distributionsubstations and switchingsubstations of power supplyand public utilities

    Public buildings, such ashigh-rise buildings, railwaystations, hospitals

    Industrial plants

    Typical examples

    Wind power stations

    High-rise buildings

    Airports

    Underground railway stations

    Sewage treatment plants

    Port facilities

    Traction power supplysystems

    Automobile industry

    Petroleum industry

    Chemical industry

    Unit-type heating powerstations

    Textile, paper andfood industry

    Emergency power supplyinstallations

    Modular design

    Individual panels, for freecombination and extension

    Option: low-voltage compart-ments can be supplied intwo overall heights

    Technical features

    Air-insulated indoorswitchgear

    Gas-insulated, maintenance-free switching functions forthe three-position switch

    Three-pole primary enclosure

    Phases arranged one behindthe other

    No cross-insulation betweenphases

    Busbar system at top

    Air-insulated busbar and cableconnection system

    Three-position switch, metal-enclosed, with air-insulatedprimary terminals and gas-insulated switching functions

    Vacuum circuit-breaker 3AH5,metal-enclosed, up to 630 A,fixed-mounted in gas-insulatedswitchgear vessel

    Vacuum circuit-breaker 3AH6,air-insulated, up to 1250 A,easy to withdraw after loose-ning the fixing bolts

    Hermetically-sealed bywelding, stainless-steelswitchgear vessel,

    For switching devices With welded-in bushings

    (for electrical connections andmechanical components)

    With insulating gas SF6

    Cubicle-type or metal-cladpanel design

    Pressure relief To the rear and upwards Separately for each

    compartment

    Air-insulated cable connectionsystem for conventional cablesealing ends

    Three-phase current trans-former, factory-assembled onthe feeder bushings

    Integrated low-voltage niche(standard) for installationof, e.g.

    Terminals, MCBs, push-buttons

    Protection devices

    Option: Top-mounted low-voltage compartment

    Option: Panel heating forsevere ambient conditions,e.g. condensation

    Mechanical switch positionindications integrated in

    mimic diagram

    Switchgear interlockingsystem with logicalmechanical interlocks

    Reavailability

    Three-position switch discon-nector with gas-insulated,maintenance-free quenchingprinciple

    Metal compartmentalizationbetween busbar compart-ment, switching devices andcable connection compart-

    mentSeparate pressure relief for

    each compartment

    Cable testing without theneed to isolate the busbar

    Mounting location of three-phase current transformer forselective disconnection ofcircuit-breaker feeders

    Cost-efficiency

    Extremely low life-cycle costsand extremely high availabilitythroughout the entire product

    service life cycle as a result of:Three-position switch with

    gas-insulated quenchingprinciple

    3AH vacuum circuit-breaker

    Minimum space requirement

    Easy switchgear extension

    Standard protection relays,e.g. multifunction protectionSIPROTEC 4

    Electrical features

    Rated voltages up to 24 kV

    Rated short-time withstandcurrent up to 25 kA

    Rated normal current offeeders

    Up to 630 A, e.g. forring-main, metering andcircuit-breaker panels

    Up to 1250 A, forcircuit-breaker and bussectionalizer panels

    Rated normal current ofbusbar up to 1250 A

    * Standards see page 41

    Features

  • 7/26/2019 Simosec En

    4/44

    4 SiemensHA41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Electrical data of panels, pressure values, temperature

    1) The rated normal currents apply to ambient tempera-tures of 40 C. The 24-hour-mean value is max. 35 C(according to IEC 60 694 / VDE 0670 Part 1000)

    2) Pressure values for SF6-insulated vessels

    * Type designationof the vacuumcircuit-breaker

    Common details on electrical data, filling pressure and temperature

    Rated insulation level Rated voltageUr kV 7.2 12 15 17.5 24

    Rated short-dur. power-freq. withstand voltageUd kV 20 28 35 38 50

    Rated lightning impulse withstand voltageUp kV 60 75 95 95 125

    Rated frequencyfr 50/60 Hz

    Rated normal currentIr1)of busbar

    Standard 630 A

    Option 1250 A

    Rated short-timewithstand currentIk

    for switchgear withtk= 1 s up to kA 20 25 20 25 16 20 25 16 20 25 16 20

    for switchgear withtk= 3 s up to kA 20 20 20 20 20

    Rated peak withstand currentIp up to kA 50 63 50 63 40 50 63 40 50 63 40 50

    Rated filling pressurepre2) for insulation 1500 hPa (absolute) at 20 C

    Minimum operating pressurepme2) for insulation 1300 hPa (absolute) at 20 C

    Ambient temperatureT for panels without secondary equipment 25 C to +55 C

    for panels with secondary equipment 5 C to +55 C

    Ring-main panel type RK and cable connection panel type K

    Rated normal currentIr1

    ) for feeder and transfer, panel type RK 400, 630 Afor feeder, panel type K 400, 630 A

    for feeder, panel type K1 400, 630, 1250 A

    Rated short-circuit making currentIma up to kA 50 63 50 63 40 50 63 40 50 63 40 50

    Transformer panel type TR

    Rated normal currentIr1) for feeder3) 200 A

    Rated peak withstand currentIp 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50

    Rated short-circuit making currentIma 3) up to kA 25 25 25 25 25 25 25 25 25 25 25 25

    Reference dimension e for HV HRC fuse links mm 2924) 292 442 442 442

    Circuit-breaker panel type LS

    Rated normal currentIr1) f. panel type LS1 and LS1-U 3AH5 * 630 Af. panel type LS11 andLS11-U 3AH6 * 630 Af. panel type LS31,LS32 and LS31-U 3AH6* 1250 A

    Rated short-circuit making currentIma up to kA 50 63 50 63 40 50 63 40 50 63 40 50

    Rated short-circuit breaking currentIsc for 3AH vacuum circuit-breaker up to kA 20 25 20 25 16 20 25 16 20 25 16 20

    Busbar earthing panel type SE

    Rated short-circuit making currentIma up to kA 50 63 50 63 40 50 63 40 50 63 40 50

    Busbar voltage metering panels type ME3 and type ME31-F

    Rated peak withstand currentIp 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50

    Rated short-circuit making currentIma 3) up to kA 25 25 25 25 25 25 25 25 25 25 25 25

    Reference dim. e in panel type ME31-F for HV HRC fuse links 292 mm

    Billing metering panels type ME1

    Rated normal currentIr1) for transfer, panel types ME1 and ME1-H 630 A, 1250 A

    for feeder as cable-connection panel type ME1-K 630 A, 1250 Afor busbar connection, panel type ME1-S 630 A, 1250 A

    for bus riser panel type HF 630 A, 1250 A

    Bus sectionalizer panels type LT

    Rated normal currentIr1) for panel types LT10 and HF, with 3AH5 * 630 Afor panel type LT1, with 3AH5 *: On request 630 Afor panel types LT11 and HF, with 3AH6 * 630 Afor panel types LT2 and LT22 630 A

    for panel types LT31 and HF, with 3AH6 * 1250 ARated short-circuit making currentIma up to kA 50 63 50 63 40 50 63 40 50 63 40 50

    Rated short-circuit breaking currentIsc for 3AH vacuum circuit-breaker up to kA 20 25 20 25 16 20 25 16 20 25 16 20

    Electrical service life for 3AH vacuum circuit-breaker:

    at rated normal currentIr1) 10,000 operating cycles

    at rated short-time breaking currentIsc 50 breaking operations, 35 breaking operations on3AH6 *with 25 kA

    for feeder for transfer with

    3) For panel types TR and ME31-F depending on the max.cut-off current of the HV HRC fuse link

    4) With reference dimension e = 192 mm, an extension tube(100 mm long) is additionally required for fuse mounting 292 mm

    Technical Data

  • 7/26/2019 Simosec En

    5/44

    SiemensHA 41.21 2003 5

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    1) Depending on the HV HRCfuse links

    2) Depending on the cut-offcurrent of the HV HRC fuse

    * Higher values of electrical data available on request

    **Indications in parenthesis acc. to previous standards

    Electrical data*of the switching devices

    Technical Data

    Make-proof earth-ing function ofthe three-positionswitch-disconnector

    Make-proofearthing functionin panels LS11,LS31, LS32

    Earthing functionof the three-positiondisconnector

    Three-position switch-disconnector

    Rated voltage Ur kV 7.2 12 15 17.5 24Rated insulationlevel

    Rated short-duration power-frequency withstand volt. Ud kV 20 28 36 38 50

    Rated lightning impulse withstand voltage Uw kV 60 75 95 95 125

    Rated frequency fr Hz 50/60 50/60 50/60 50/60 50/60

    Rated normalcurrent for

    ring-main feeders Ir A 400, 630 400, 630 400, 630 400, 630 400, 630

    transformer feeders1) Ir A 200 200 200 200 200

    Rated short-timewithstand current

    for switchgear withtk(ttk)**= 1 s Ik(Ith)** up to kA 25 25 25 25 20

    for switchgear withtk(ttk)**= 3 s Ik(Ith)** kA 20 20 20 20 20

    Rated peak withstand current Ip up to kA 63 63 63 63 50

    Rated short-circuitmaking current for

    transformer feeders2) Ima kA 25 25 25 25 25

    ring-main feeders Ima up to kA 63 63 63 63 50

    Switching capacity of general-purpose switches (class E3) according to IEC 60 265-1 / VDE 0670 Part 301 (Standards see page 41)

    Test duty 1 Rated mainly active for 100 switching operations I1 A 630 630 630 630 630

    load breaking current for 20 switching operations I1 A 31.5 31.5 31.5 31.5 31.5

    Test duty 2a Rated closed-loop breaking current I2a A 630 630 630 630 630

    Test duty 3 Rated transformer breaking current I3 A 40 40 40 40 40

    Test duty 4a Rated cable-charging breaking current I4a(IC orI6)** A 68 68 68 68 68

    Test duty 4b Rated line-charging breaking current I4b A 68 68 68 68 68

    Test duty 5 Rated short-circuit making current Ima up to kA 63 63 63 63 50

    Test duty 6a Rated earth-fault breaking current I6a(Ie)** A 60 60 60 60 60

    Test duty 6b Rated cable-charging breaking current and line- I6b A

    charging breaking current under earth-fault conditions (HJ3 vICL)**35 35 35 35 35

    Cable-charging breaking current under IL +HJ3 vICL Aearth-fault conditions with superimposed load current

    630+50 630+50 630+50 630+50 630+50

    Switching capacity of switch-disconnector/fuse combination(Standards see page 41)

    Rated transfer current I4 A 1150 1150 830 830 830

    Earthing switch

    Rated voltage Ur kV 7.2 12 15 17.5 24

    Rated short-circuit making current Ima up to kA 63 63 63 63 50

    Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20

    Rated short-circuit making current Ima up to kA 63 63 63 63 50

    Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20

    Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20

    3AH5 and 3AH6 vacuum circuit-breakersRated voltage Ur kV 7.2 12 15 17.5 24

    Rated insulationlevel

    Rated short-duration power-frequency withstand volt. Ud kV 20 28 36 38 50

    Rated lightning impulse withstand voltage Up kV 60 75 95 95 125

    Rated frequency fr Hz 50/60 50/60 50/60 50/60 50/60

    Rated normal current of feeders for 3AH5 Ir A 400, 630 400, 630 400, 630 400, 630 400, 630

    for 3AH6 Ir A 630, 1250 630, 1250 630, 1250 630, 1250 630,1250

    Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20

    Rated short-circuit duration tk (tth)** s 3 3 3 3 3

    Rated peak withstand current Ip up to kA 63 63 63 63 50

    Rated short-circuit breaking current Isc up to kA 25 25 25 25 20

    Rated short-circuit making current Ima up to kA 63 63 63 63 50

    Electrical service life at rated normal current 10,000 operating cycles

    HA41-29aeps

  • 7/26/2019 Simosec En

    6/44

    6 SiemensHA41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Technical Data

    Switchgear installation

    Room planning

    Switchgear installation

    Wall-standing arrangement Single row Double row (for face-to-face

    arrangement)

    Room dimensions

    See opposite dimensiondrawings

    Door dimensions

    The door dimensionsdepend on the Number of panels in a

    transport unit Design with or withoutlow-voltage compartment

    Switchgear fastening

    For floor openings andfixing points of the switch-gear, see page 40

    Foundations: Steel structure Steel-reinforced concrete

    Panel dimensions

    See pages 34 to 39

    Weight

    The weight of a panel dependson the extent to which it isequipped (e.g. with motoroperating mechanism, voltagetransformer). For details,please refer to page 7.

    1 Relief opening

    2 Direction of pressure relief

    3 Pressure relief of switchgear

    4 Room height

    5 Individual panel depth

    6 Panel depth including end wall

    7 Control aisle

    8 Option: Floor cover

    9 Cable

    10 Foundation

    11 Height of cable basement corresponding to

    cable bending radius

    12 Wall distance

    13 Side wall distance

    14 Installation flush with rear wall

    15 Panel width

    16 End wall

    17 Depth of pressure relief duct

    18 Option: For free-standing arrangementpressure relief duct for each panelfor rated short-time withstand currentIk w 20 kA

    19 Option: Front cover

    20 Option: Low-voltage compartment

    21 Option: High end wall

    Room planning

    Plan view Plan view

    Wall-standing arrangement(side view) Free-standing arrangement(side view)

    Cable basement Cable basement

    Switchgear room Switchgear room

    * Switchgear height 2100 mm if height oflow-voltage compartment 350 mm;switchgear height 2300 mm if height oflow-voltage compartment 550 mm

    ** Depending on bending radius of cable

  • 7/26/2019 Simosec En

    7/44

    SiemensHA 41.21 2003 7

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Transport unitsfor shipping(plan view)

    1) Thenet weightdepends on theextent to which it is equipped(e.g. current transformers, motoroperating mechanisms) and istherefore given as mean value

    * Low-voltage compartment,350 mm high, weight approx.60 kg depending on thepanel type and on the extentto which it is equipped

    With individual panel

    With combinations of differentindividual panels

    1 T1 = Depth of individual panel

    2 Individual paneldimension B1 x T1

    3 Transport unit,dimension B2 x T2

    4 B3 = Overall width ofcombination of differentindividual panels

    5 B2 = Width of thetransport unit

    **Packingweight

    Shipping data

    2)Sum of thenet weightsofindividual panels

    Individual panelor combinations

    thereof for standard switchgear(without pressure relief duct)

    Paneltype

    Panel or panelcombination

    Transport unit (including packing)for standard panels (without pressure relief duct)

    WidthB1mm

    Netweight1)approx. kgwith- / withoutLVC*/LVC*

    Width

    B2m

    Height

    m

    with- / withoutLVC*/LVC*

    DepthT2m

    Volume

    m3

    with- / withoutLVC*/LVC*

    Grossweightapprox. kg

    with- / withoutLVC*/LVC*

    Transport of individual panels

    Ring-main panel RKRK1

    375500

    190 / 250210 / 270

    0.70.7

    1.9 / 2.3 1.40 1.86 / 2.251.86 / 2.25

    250 / 310270 / 330

    Ring-mainpanelforpanelcombinations RK-U 375 260 / 320 0.7 1.86 / 2.25 320 / 380

    Cable panel K, K-EK1, K1-E

    375500

    190 / 250190 / 250

    0.70.7

    1.86 / 2.251.86 / 2.25

    250 / 310250 / 310

    Transformer panel TRTR1

    375500

    210 / 270230 / 290

    0.70.7

    1.86 / 2.251.86 / 2.25

    270 / 330290 / 350

    Circuit-breaker panel 630 A LS1

    LS11

    750

    750

    340 / 400

    340 / 400

    1.08

    1.08

    2.87 / 3.48

    2.87 / 3.48

    410 / 460

    410 / 460

    Circuit-breaker panel 1250 A

    For connection of max. 2 cables For connection of 3 cables

    LS31LS32

    750875

    400 / 460460 / 520

    1.081.08

    2.87 / 3.482.87 / 3.48

    470 / 520530 / 580

    Bus sectionalizer panel 1250 A LT31 750 450 / 510 1.08 2.87 / 3.48 520 / 570

    Bus sectionalizer panel 630 Awith vacuum circuit-breaker

    LT10LT11

    750750

    320 / 380320 / 380

    1.081.08

    2.87 / 3.482.87 / 3.48

    390 / 440390 / 440

    Bus sectionalizer panel with1 three-position switch-disconnector

    LT2LT2-W

    750750

    250 / 310310 / 370

    1.081.08

    2.87 / 3.482.87 / 3.48

    320 / 370380 / 430

    Bus sectionalizer panel with2 three-position switch-disconnectors

    LT22LT22-W

    750750

    290 / 350350 / 410

    1.081.08

    2.87 / 3.482.87 / 3.48

    360 / 410420 / 470

    Billing metering panel ME1....ME1-H

    750750

    270 / 330330 / 390

    1.081.08

    2.87 / 3.482.87 / 3.48

    340 / 390400 / 450

    Busbarvoltage metering panel

    ME3ME31-F

    375500

    210 / 270270 / 330

    0.70.7

    1.86 / 2.251.86 / 2.25

    270 / 330330 / 390

    Bus riser without transformers

    panel with transformers

    HF 375 170 / 230 0.7 1.86 / 2.25 230 / 290

    HF 375 260 / 320 0.7 1.86 / 2.25 320 / 380

    Busbarearthing panel

    SE1SE2

    375500

    190 / 250270 / 330

    0.70.7

    1.86 / 2.251.86 / 2.25

    250 / 310330 / 390

    For individual panel Panelwidthmm

    Additionalweightapprox. kg

    Pressure relief ductfor free-standing arrangementof switchgear

    375 30

    500 40

    750 60

    875 70

    Transport of combinations of different individual panels

    Transport unit: Standard: As individual panels arranged

    side by side and not screwed together

    Option: As multi-panel transport unit,panels screwed together

    Overall width B3

    w 875 mm

    B2

    1.08 1.9 / 2.3

    T2

    1.40 2.87 / 3.48 2)+ 70 **

    w 1125 mm 1.20 1.9 / 2.3 1.40 3.19 / 3.86 2

    )+ 80 **w 1500 mm 1.70 1.9 / 2.3 1.40 4.52 / 5.47 2)+ 100 **

    w 2000 mm 2.33 1.9 / 2.3 1.40 6.20 / 7.50 2)+ 120 **

    Packing, transport(examples)

    Packing Version For supply Transport

    Panels mounted on wooden floorand covered with PE protection sheeting

    Open In Europe Rail, truck

    In container Overseas Ship + truck

    Technical Data

  • 7/26/2019 Simosec En

    8/44

    8 SiemensHA41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Product range overview

    1) Metal-clad

    2) With additional make-proof earthing switch

    3) Type designation of vacuum circuit-breaker

    4) With 1 three-position switch-disconnector

    5) With 2 three-position switch-disconnectors

    6) With voltage transformer for busbar metering

    Product Range

    Paneltype

    Panelwidth

    RKRK1

    375 mm500 mm

    RK-U 375 mm

    TRTR1

    375 mm500 mm

    KK1

    375 mm500 mm

    K-EK1-E

    375 mm500 mm

    LS1 750 mm

    LS1-U 750 mm

    LS11 750 mm

    LS11-U 750 mm

    LS31LS32

    750 mm875 mm

    LS31-U 750 mm

    LT10 750 mm

    LT11 750 mm

    LT31 750 mm

    LT2LT2-W

    750 mm750 mm

    LT22LT22-W

    750 mm750 mm

    ME1ME1-S

    750 mm750 mm

    ME1-KME1-KS

    750 mm750 mm

    ME1-H 750 mm

    ME3ME31-F

    375 mm500 mm

    SE1 375 mm

    SE2 500 mm

    HF 375 mm

    Panel designation

    Ring-mainpanel1)

    asfeeder

    astransfer

    Transformerpanel1)

    asfeeder

    Cable panel asfeeder

    Cable panel1)2) asfeeder

    Circuit-breaker panel 630 A1)with 3AH53)

    asfeeder

    astransfer

    Circuit-breaker panel 630 Awith 3AH63)

    asfeeder

    astransfer

    Circuit-breaker panel 1250 Awith 3AH63)

    asfeeder

    astransfer

    Bussectionalizer panel630 A 1)with 3AH53), for panel type HF

    Bus sectionalizer panel 630 Awith 3AH63), for panel type HF

    Bus sectionalizer panel 1250 Awith 3AH63), for panel type HF

    Bus sectionalizer panel630 A 1) 4)

    5)

    Billing meteringpanel

    Standard

    asend panel

    Billing metering panelfor additional current transformer

    Busbar voltage meteringpanel1)

    Busbar earthingpanel1)

    6)

    Bus riser panel

    Standard panels

    Ring-main paneltype RK

    Circuit-breaker paneltype LS1

    Transformer paneltype TR

    Circuit-breaker paneltype LS11

    Cable paneltype K

    Billing metering paneltype ME1

    R-HA41-073eps

    R-HA41-076eps

    R-HA41-074eps

    R-HA41-077eps

    R-HA41-075e

    ps

    R-HA41-078e

    ps

    Column No.

  • 7/26/2019 Simosec En

    9/44

    SiemensHA 41.21 2003 9

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Basic equipment

    Additional equipment (option),further additionalequipment on request

    Not available

    Product Range

    Equipment features

    1) Three-position switch as three-position switch-disconnector

    2) Three-position switch as three-position disconnector in paneltypes LS31, LS31-U, LS32 and LT31

    3) Type designation of the vacuum circuit-breaker

    4) In special cases, deeper floor cover required

    Manua

    lope

    rating

    mec

    hanis

    mfort

    hree-p

    ositio

    nswi

    tch

    Interloc

    kfor

    cable

    com

    partm

    entc

    over

    Cable

    com

    partm

    entc

    over

    locke

    dinp

    lace

    C-rai

    lasc

    able

    bracke

    t

    Low-

    volta

    genic

    heas

    term

    inalc

    ompa

    rtmen

    t

    Relea

    seas

    shun

    trele

    ase

    Mec

    hanic

    alrea

    dy-fo

    r-serv

    iceind

    icator

    forthr

    ee-po

    sition

    switc

    h

    Signa

    llings

    witch

    (1NO)

    forrem

    oteele

    ctrica

    l

    ready

    -for-s

    ervice

    indica

    tionf

    orthr

    ee-po

    sition

    switc

    h

    Aux.

    switc

    h(2N

    O+

    1NC

    forC

    LOSE

    D/EA

    RTHE

    Dan

    d2NO

    for

    OPE

    N)fo

    rthr

    ee-po

    sition

    switc

    hand

    mak

    e-proo

    feart

    hings

    witch

    Moto

    rope

    rating

    mecha

    nism

    forthr

    ee-po

    sition

    switc

    h1)

    2)

    Localre

    mote

    switc

    hfor

    mot

    orop

    erat.m

    ech.

    ofthree

    -posit

    ionswi

    tch1)

    2)

    Interl

    ocki

    ncirc

    uit-br

    eake

    rpan

    elbetw

    een

    three

    -posit

    ionsw

    itch

    1)2)a

    nd3A

    H...v

    acuu

    mcir

    cuit-b

    reake

    r

    Locking

    devic

    efor

    switc

    hpos

    ition

    CLOS

    EDo

    f3AH

    6vacuu

    m

    circu

    it-brea

    kerw

    ithearth

    edthr

    ee-po

    sition

    switc

    h

    De-ea

    rthing

    lock-o

    utfor

    mak

    e-proo

    feart

    hings

    witch

    Inspe

    ction

    wind

    owin

    theconn

    ectio

    n/cab

    lecom

    partm

    entc

    over

    Low-

    volta

    gecom

    partm

    ento

    rshu

    tter

    Closin

    gloc

    k-out

    fort

    hree

    -posit

    ionsw

    itch

    Moto

    rope

    rating

    mecha

    nism

    forva

    cuum

    circu

    it-bre

    aker

    Relea

    seas

    c.t.-ope

    rated

    relea

    sein

    3AH

    3)

    Locking

    devic

    efor

    three

    -posit

    ionsw

    itch

    Short-c

    ircuit

    orearth

    -fault

    indica

    tor

    Sec

    ondary

    equip

    men

    t

    Floo

    rcov

    er4)

    Pan

    elhe

    ating

    Mou

    ntedc

    able

    clam

    ps

    6)

    6)

    RK

    RK1

    RK-U

    TR

    TR1

    K

    K1

    K-E

    K1-E

    LS1

    LS1-U

    5)

    LS11

    LS11-U

    5)

    LS31LS32

    LS31-U

    LT10

    LT11

    LT31

    LT2

    LT2-W

    LT22

    LT22-W

    ME1ME1-S

    ME1-KME1-KS

    ME1-H

    ME3ME31-F

    SE1

    SE2

    HF

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Panel type

    5) Not to be applied for versions with separate feeder earthing switch inpanel types LS11, LS31 and LS32

    6) Inspection window is a standard equipment in panel types LS11, LS31and LS32 for versions with separate earthing switch

    7) Option (on request): Closing lock-out possible for panels LT11 or LT31in combination with the adjacent panel type HF

    7)

    7)

    7)

  • 7/26/2019 Simosec En

    10/44

    10 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Ring-main panels

    Type RK-U375 mm wide

    Ring-main panels

    as feeder panels

    either:Version withtransformers

    HA41-2390beps

    Type RK375 mm wide

    Type RK1500 mm wide

    Type LT10750 mm wide

    Type RK1500 mm wide

    Ring-main panel

    as transfer panel for attachmentto panel types ME1... or ME1-H

    * On requestup to 12 kV

    or:Version withconnectionfittings

    For other panel combinations

    Capacitivevoltage detectionsystem

    Voltage transformere.g. 4MR, 1-pole,cast-resin insulated

    Cable (notincluded in thescope of supply)

    2nd cable (notincluded in thescope of supply)

    Surgearrester

    Block-typecurrent transformer4MA,cast-resin insulated

    Cable-typecurrent transformere.g. 4MC703 . . .

    Three-phasecurrent transformer4MC63 . . .

    P1 and P2are terminaldesignationsof the currenttransformer

    Type RK-U375 mm wide

    With3AH5vacuumcircuit-breaker,fixed-mounted

    With3AH6vacuumcircuit-breaker,with-drawable

    Bus sectionalizer panel type LT10 withring-main transfer panel type RK-U

    Type RK-U375 mm wide

    Type LT11750 mm wideBus sectionalizer panel type LT11 withring-main transfer panel type RK-U(non-interchangeable arrangement)

    3AH5 vacuumcircuit-breaker

    Three-positionswitch-disconnector

    3AH6 vacuumcircuit-breaker

    Standard:transferto theright

    Option:transferto theleft

    The ring-main transferpanel RK-U can beattached on the left orright of the bus section-alizer panel LT10

    Product Range

  • 7/26/2019 Simosec En

    11/44

    SiemensHA 41.21 2003 11

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Transformer panels

    as feeder panels

    Cable panels

    as feeder panels, 630 A

    Transformer and cable panels

    Type K375 mm wideType TR375 mm wide

    Type TR1500 mm wide

    Cable panels

    as feeder panels withmake-proof earthing switch

    Type K-E375 mm wide

    Type K1500 mm wide

    Type K1-E500 mm wide

    * On request

    up to 12 kV** Current

    transformerlocated partlyunderneaththe panel

    either:Version withtransformers

    or:Version withconnectionfittings

    either:Version withtransformers

    or:Version withconnectionfittings

    HV HRC fuse

    Capacitivevoltage detectionsystem

    Make-proofearthing switch

    Earthingswitch

    Three-positionswitch-disconnector

    Fixedearthing point

    Cable-typecurrent transformer,e.g. 4MC703 . . .

    Block-type

    current transformer4MA,cast-resin insulated

    Three-phasecurrent transformer4MC63 . . .

    Voltage transformere.g. 4MR, 1-pole,cast-resin insulated

    Cable (notincluded in thescope of supply)

    2nd cable (notincluded in thescope of supply)

    Surgearrester HA

    41-2390beps

    Type K1500 mm wide

    Type K1-E500 mm wide

    as feeder panels630 A and 1250 A

    Product Range

  • 7/26/2019 Simosec En

    12/44

    12 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Circuit-breaker panels

    Circuit-breaker panels 630 A

    as feeder panels

    as transfer panels for attachmentto panel types ME1... or ME1-H

    Type LS1750 mm wide

    Type LS1-U750 mm wide

    Footnotes for the left and right columns:

    * On request

    ** Standard: Feeder earthingvia the 3AH6 vacuum circuit-breaker

    with interlocks (without earthing switch)BMounting position of the current

    transformer with terminal P1 at the top only

    P1 and P2 are terminal designationsof the current transformer

    With 3AH5 vacuum circuit-breaker,fixed-mounted

    Voltage transformere.g. 4MR, 1-pole,cast-resin insulated

    Cable (notincluded in thescope of supply)

    Addit. cables (not

    included in thescope of supply)

    Surgearrester

    Three-phasecurrent transformer4MC63 . . .

    Capacitivevoltage detectionsystem

    Fixedearthing point HA

    41-2390beps

    Type LS31750 mm wide

    With 3AH6vacuum circuit-breaker,withdrawable

    Type LS11750 mm wide

    With 3AH5vacuum circuit-breaker, fixed-mounted

    With 3AH6vacuum circuit-breaker, withdrawable

    Type LS11-U750 mm wide

    as transfer panel for attachmentto panel types ME1... or ME1-H

    With 3AH6vacuum circuit-breaker, withdrawable

    Type LS31-U750 mm wide

    Standard:transferto theright

    Option:transferto theleft

    Transferpossibleonly tothe right

    3AH5 vacuumcircuit-breaker

    Three-positionswitch-disconnector

    Three-positiondisconnector

    3AH6 vacuumcircuit-breaker

    Cable-typecurrent transformere.g. 4MC703 . . .

    Block-typecurrent transformer4MA,cast-resin insulated

    Make-proofearthing switch

    Transferpossibleonly tothe right

    Circuit-breaker panels 1250 A

    as feeder panels

    forconnectionof max.2 cables

    With 3AH6vacuum circuit-breaker, withdrawable

    forconnectionof max.3 cables(4 cables *)

    With 3AH6vacuum circuit-breaker,withdrawable

    Type LS32875 mm wide

    Product Range

  • 7/26/2019 Simosec En

    13/44

    SiemensHA 41.21 2003 13

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Bus sectionalizer panels 630 A

    in combination with bus riser panel

    Type HF375 mm Type LT10750 mm wide

    Type HF375 mm wide

    Type LT10750 mm wide

    Type HF375 mm wide

    Type LT11750 mm wide

    Type LT2750 mm wide

    Bus sectionalizer panels 630 A

    with 1 three-position switch-disconnector

    Type LT2-W750 mm wide

    with 2 three-position switch-disconnectors

    Type LT22750 mm wide

    Type LT22-W750 mm wide

    Paneltype

    HF

    attached

    on

    the

    right

    Bus sectionalizer panels

    3AH5 vacuumcircuit-breaker

    Three-positionswitch-disconnector

    3AH6 vacuumcircuit-breaker

    Three-positiondisconnector

    Voltage transformer

    e.g. 4MR, 1-pole,cast-resin insulated

    Block-typecurrent transformer4MA,cast-resin insulated

    Three-phasecurrent transformer4MC63 . . .

    Capacitivevoltage detectionsystem

    Fixedearthing point HA

    41-2390beps

    With3AH5vacuumcircuit-breaker,

    fixed-mounted

    corresponds to type RK-Uwith type HF

    Type HF375 mm wide

    Type LT31750 mm wide

    corresponds to type RK-Uwith type RK-U

    corresponds to type RK-Uwith type RK-U

    corresponds to type RK-Uwith type HF

    With3AH5vacuumcircuit-breaker,

    fixed-mounted

    With3AH6vacuumcircuit-breaker

    with-drawable

    Bus sectionalizer panel 1250 Ain combination with bus riser panel

    Paneltype

    HF

    attached

    on

    the

    left

    Paneltype

    HF

    can

    only

    be

    attached

    on

    the

    right

    Pan

    eltype

    HF

    can

    only

    be

    attached

    on

    the

    right

    P1 and P2are terminaldesignationsof the currenttransformer

    With3AH6vacuumcircuit-breaker

    with-drawable

    Product Range

  • 7/26/2019 Simosec En

    14/44

    14 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Billing metering panels

    Billing metering panels

    630 A and 1250 AStandard

    Type ME1750 mm wide Standard **:Transfer to the right Type ME1-S750 mm wide

    Billing metering panels

    630 A and 1250 Afor busbar connection

    Type ME1750 mm wide

    Type ME1-S750 mm wide

    Type ME1750 mm wide

    Type ME1-S750 mm wide

    Type ME1750 mm wide

    Type ME1-S750 mm wide

    Type ME1-H750 mm wide

    Type ME1-H750 mm wide

    Billing metering panels

    630 A and 1250 Afor additional current transformer

    HA41-2390beps

    Capacitivevoltage detectionsystem

    On request:Voltage transformer,e.g. 4MR,cast-resin insulatedwith HV HRC fuse

    Block-typecurrent transformer4MA,cast-resin insulated

    Fixedearthing point

    Fixed earthingpoint forbusbar earthing

    Standard **:Transfer to the right

    Standard **:Transfer to the right

    Standard **:Transfer to the right

    Standard **:Transfer to the right

    Standard **:Transfer to the right

    Standard **:Transfer to the right

    Standard **:Transfer to the right

    Standard **:Transfer to the right

    Standard **:Transfer to the right

    Standard **:Transfer to the right

    Type ME1-H750 mm wide

    Type ME1-H750 mm wide

    Standard **:Transfer to the right

    * On request

    ** Option:Transferto the left

    Voltage transformer,e.g. 4MR,1- or 2-pole,cast-resin insulated

    Transformerterminalsinterchanged

    Transformerterminalsinterchanged

    Transformerterminalsinterchanged

    Transformerterminalsinterchanged

    Transformerterminalsinterchanged

    Scheme 1 Scheme 1 Scheme 1

    Scheme 2 Scheme 2 Scheme 2

    Scheme 3 Scheme 3 Scheme 3

    Scheme 4 Scheme 4 Scheme 4

    Transformerterminalsinterchanged

    P1 and P2are terminaldesignationsof the currenttransformer

    Product Range

  • 7/26/2019 Simosec En

    15/44

    SiemensHA 41.21 2003 15

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Make-proofearthing switch

    Three-positionswitch-disconnector

    HA41-2390beps

    Capacitivevoltage detectionsystem

    Fixedearthing point

    Voltage transformer,e.g. 4MR,1- or 2-pole,cast-resin insulated

    Billing metering panels, busbar voltage metering panels,busbar earthing panels and bus riser panels

    HV HRC fuse

    * On requestup to 12 kV

    ** Connectionfor 3 cablespossible

    B Option:Transferto the left

    BB For

    attachmentto left orrightring-mainpanelstype RK-U

    Billing metering panels

    630 A and 1250 A**for cable connection

    Type ME1-K750 mm wide StandardB

    ):Transfer to the right Type ME1-KS750 mm wide

    Billing metering panels

    630 A and 1250 A**for busbar connection

    Type ME1-K750 mm wide

    Type ME1-KS750 mm wide

    Type ME1-K750 mm wide

    Type ME1-KS750 mm wide

    Type ME1-K750 mm wide

    Type ME1-KS750 mm wide

    Type ME31-F500 mm wide

    Type ME3375 mm wide

    Busbar voltage

    metering panels

    Standard B):Transfer to the right

    StandardB):Transfer to the right

    Standard B):Transfer to the right

    Type SE1375 mm wide

    Type SE2500 mm wide

    Bus riser panels

    630 A and 1250 A

    Type HFBB

    )375 mm wide

    Transformerterminalsinterchanged

    Transformerterminalsinterchanged

    Type HF BB)375 mm wide

    Type HF BB)375 mm wide

    Busbarearthing panels

    Type HF BB)375 mm wide

    Earthing switch

    Make-proofearthing switch

    Transformerterminalsinterchanged

    Transformerterminalsinterchanged

    Scheme 1 Scheme 1 Scheme 1

    Scheme 2 Scheme 2 Scheme 2

    Scheme 3 Scheme 3 Scheme 3

    Scheme 4 Scheme 4 Scheme 4

    P1 and P2are terminaldesignationsof the currenttransformer

    as right or leftend panel

    as right or leftend panel

    as right or leftend panel

    as right or leftend panel

    Voltage transformer,e.g. 4MR,1-polecast-resin insulated

    Block-typecurrent transformer4MA,cast-resin insulated

    Product Range

  • 7/26/2019 Simosec En

    16/44

    16 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Panel design(examples)

    Ring-main panel as feeder Transformer panel as feeder

    Billing metering panel Legend for pages 14 and 15

    1 Option: Low-voltage compartment

    2 Niche for optional low-voltage equipment,cover can be unscrewed

    3 Option: CAPDIS voltage detection system

    4 Option: Short-circuit/earth-fault indicator

    5 Option: Ready-for-service indicatorfor switching device

    6 Switch position indication for load-breakfunction CLOSED OPEN

    7 Switch position indication for earthingfunction OPEN EARTHED

    8 Feeder designation label9 Mimic diagram

    10 Option: Sockets for capacitive voltage detection system(depending on arrangement)

    11 Option: Momentary-contact rotary control switchCLOSED OPEN for motor operating mechanismwith local-remote switchfor three-position switch-disconnector

    12 Option: Locking device for three-positionswitch-disconnector

    13 Pressure relief device for switching device

    14 Manual operation for the mechanism ofthe earthing function

    15 Manual operation for the mechanism ofthe load-break function

    16 Rating and type plate

    17Gas-insulated vessel for switching device

    18 Interlocking of the cable compartment cover

    19Bushing-type insulator for busbar

    20 Bushing-type insulator for feeder

    Type RK Type TR

    Type ME1

    Section Section

    Section

    Design

  • 7/26/2019 Simosec En

    17/44

  • 7/26/2019 Simosec En

    18/44

    18 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Common features

    Circuit-breakers withvacuum interrupters

    Stored-energy spring-operated mechanism for10,000 operating cycles

    Maintenance-free for in-door installation accordingto IEC 60694 / VDE 0670Part1000, subsequentlyIEC 62 271-1*

    Individual secondaryequipment

    Switching duties andoperating mechanisms

    The switching duties of thevacuum circuit-breaker aredependent, among otherfactors, on its type of oper-ating mechanism. Threeoperating mechanismversions are available:

    Motor operating stored-energy mechanism

    For auto-reclosure (K), For synchronization and

    rapid load transfer (U)

    Manual operating stored-energy mechanism

    For auto-reclosure (K)Manual spring-operated

    mechanism(= spring CLOSED,stored-energy OPEN)

    Not for auto-reclosure (K) For normal closing and For storage of one

    opening

    Trip-free mechanism

    The vacuum circuit-breakers are fitted with atrip-free mechanismaccording to IEC 60 056

    and VDE 0670.

    3AH5 and 3AH6 vacuum circuit-breakers

    3AH5 vacuum circuit-breaker

    Metal-enclosed

    Up to 630 A

    Pole parts with vacuuminterrupters fixed-mountedin hermetically welded,gas-filled switchgear vessel

    System-conforming usewith three-position switchin gas-insulated switchgearvessel

    Operating mechanismarranged outside theswitchgear vessel and

    behind the control boardAir-insulated primary

    terminals

    Installation in metal-cladpanels

    Feeder panels type LS1,panel width 750 mm

    Transfer panels type LS1-U,panel width 750 mm

    Bus sectionalizer panelstype LT10 (for adjacent busriser panel type HF),panel width 750 mm

    3AH6 vacuum circuit-breaker

    Withdrawable1) lateral-mechanism circuit-breaker,air-insulated

    Up to 1250 A

    Circuit-breaker polesarranged one behind theother

    Operating mechanism inseparate box behind lowerpanel cover

    Logical mechanical inter-

    locking between 3AH6vacuum circuit-breaker andthree-position switch

    Installation in: Feeder panel type LS11,

    panel width 750 mm Transfer panel type LS11-U,

    panel width 750 mm Bus sectionalizer panels

    type LT11 and LT31 (foradjacent bus riser paneltype HF), panel width750 mm

    Feeder panel type LS31(for connection of

    max. 2 cables),panel width 750 mm Feeder panel type LS32

    (for connection of 3 cables;4 cables on request),panel width 875 mm

    3AH5vacuum circuit-breaker(operating mechanism box open)

    Abbreviations for switchingduties and applications:

    U = Synchronization andrapid load transfer(make timew 90 ms)

    K =Auto-reclosure

    R-HA41-066eps

    1

    2

    3

    4

    5

    * Standards see page 41

    1) Withdrawable after looseningthe respective contactconnections and fixing bolts

    7 Operating mechanism box with controlelements

    8 Circuit-breaker poles with vacuuminterrupters

    9 Truck

    1 Operating mechanism box

    2 Bushing-type insulator for busbar

    3 Switchgear vessel, gas-filled, with3AH5 vacuum circuit-breaker andthree-position switch-disconnector

    R-HA41-068eps 9

    8

    7

    3AH6vacuum circuit-breaker

    6

    Components

    4 Spring-operated mechanism ofthree-position switch-disconnector

    5 Bushing-type insulator for feeder

    6 Location for three-phase currenttransformer (option)

    10 Locking device for the3AH6 vacuum circuit-breakerin switch position CLOSEDwith earthed three-position switchin switch position EARTHED

    11 Logical mechanical interlocking(standard when earthing the

    feeder with closed vacuumcircuit-breaker) in panel types:

    630 A: LS11, LS11-U and LT11 1250 A: LS31, LS31-U, LS32

    and LT31For further details, please referalso to Catalog HG 11.113AH Vacuum Circuit-Breakers

    11

    10

  • 7/26/2019 Simosec En

    19/44

    SiemensHA 41.21 2003 19

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    3AH5 and 3AH6 vacuum circuit-breakers

    Operating mechanismelements of the3AH6 vacuum circuit-breaker

    Operating mechanism elements

    1 Gear

    2 Coupling on gear for operationwith hand crank

    For closing with manualspring-operated mechanism

    For charging the closing springwith stored-energy mechanism

    3 Closing spring

    4 Motor (M1 *)

    5 Closingspring charged indicator

    6 Circuit-breaker OPEN

    7 Circuit-breaker CLOSED8 Operating rod

    Operating mechanismfunctions

    Motor operating mechanism1)(M1 *)

    In the case of the motor operat-ing mechanism, the closingspring is charged by means ofa motor and latched in thecharged position (the springcharged indication is visible).Closing is effected either bymeans of an ON pushbutton ora closing solenoid. The closingspring is recharged automati-cally (for auto-reclosure).

    Manual operating stored-energy mechanism

    The closing spring is chargedby means of the supplied handcrank until latching of theclosing latch is indicated(= spring charged indication).

    Subsequently the vacuumcircuit-breaker can be closedeither manually or electrically.The closing spring can be re-charged manually. The possibil-ity to close is thus stored oncemore (for auto-reclosure).

    Manual spring-operatedmechanism(= spring CLOSED,stored-energy OPEN)

    The closing spring of the vacuumcircuit-breaker is charged bymeans of the supplied handcrank until the vacuum circuit-breaker closes. Subsequentlyeither manual or electrical open-ing is possible.

    Vacuum circuit-breakers withspring-operated mechanism arenot suitable for auto-reclosure.

    1) Motor rating at24 V to 220 V DC: 350 W110 V and 220 V AC: 400 VA

    2) With closing solenoid

    * Equipment code

    Abbreviations:

    O = OPEN operation

    CO = CLOSE operation with subse-quent OPEN operation at theshortest internal close-open timeof the vacuum circuit-breaker

    t = Dead time 0.3 s

    t = Dead time 3 min

    Operating mechanism

    elements of the3AH5 vacuum circuit-breaker

    6

    4

    3

    1

    R-HA4

    1-080eps

    2

    8

    7

    R-HA41-069eps

    2

    1

    3

    47

    8

    6

    Differences between the vacuum circuit-breakers depending on the operating mechanism version

    Operatingmechanism version

    Motor operatingstored-energy mechanism

    Manual operatingstored-energy mechanism

    Manual spring-operatedmechanism

    Typical uses Utility substationsand industrial plants

    Classic transfer substationsand substations withoutauxiliary voltage supply

    Simple utility substations(circuit-breaker astransformer switch)

    Mechanismfunction

    Stored-energy CLOSED,stored-energy OPEN

    Stored-energy CLOSED,stored-energy OPEN

    Spring CLOSED,stored-energy OPEN

    Mechanismoperation

    With motor1), manual(emergency) operationat the panel includinganti-pumping

    With handcrank

    With handcrank

    Closing thevacuumcircuit-breaker

    Electrically2) ormechanically at the panelwith pushbutton

    Mechanically at the panelwith pushbutton, option:electrically2)

    Mechanically at the panelwith hand crank(charging process)

    Closing solenoid,e.g. for remoteelectrical closing

    Always provided, withelectrical signalclosing spring charged

    Option Without

    Rated switchingsequence

    O-t-CO orO-t-CO-t-CO

    O-t-CO O or CO

    Auto-reclosure (K)

    Suitable (multipleauto-reclosure possible)

    Suitable (only with closingsolenoid)

    For further details, please refer also toCatalog HG 11.11 3AH VacuumCircuit-Breakers

    5

    5

    Components

  • 7/26/2019 Simosec En

    20/44

    20 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Secondary equipment of the 3AH5 and 3AH6 vacuum circuit-breakers

    The scope of the secondaryequipment of the 3AH vacu-

    um circuit-breaker dependson the type of applicationand offers a wide range ofvariations, thus allowingeven the highest require-ments to be satisfied.

    Closening solenoid

    Type 3AY15 10 (Y9 *)

    For electrical closing

    Shunt releases

    Types: Standard: 3AY15 10 (Y1 *)

    Option: 3AX11 01 (Y2 *),with energy store

    Tripping by protection re-lay or electrical operation

    Current transformer-operated release

    Type 3AX11 04 (Y6 *) fortripping pulseW 0.1 Ws inconjunction with suitableprotection systems, e.g.7SJ4 protection relay,SEG relay (other designson request)

    Used where no externalauxiliary voltage is avail-able, tripping by protec-tion relay

    Undervoltage release

    Type 3AX11 03 (Y7 *)

    Comprising: Energy store and

    unlatching mechanism Electromagnetic system,

    to which voltage is perma-nently applied in theCLOSED position of thevacuum circuit-breaker;tripping is initiated whenthis voltage drops

    Connection to voltagetransformer possible

    Position switch

    Type 3SE4 (S4 *)

    For signalling closingspring charged

    Only in conjunctionwithstored-energymechanisms

    Secondary equipment of the 3AH6vacuum circuit-breaker(typical example)

    Anti-pumping(standard)(mechanical and electrical)

    Function: If CLOSE andOPENcommands are ap-plied simultaneouslyandcontinuously to thevacuumcircuit-breaker, this revertsto itsOPENposition afterclosing.The circuit-breakerremains in this positionuntilthe OPENcommand is eli-minated and a new CLOSEcommandis given.Thuscontinuous closingandope-ning (=pumping) is avoided.

    Breaker tripping signal

    (standard)For electrical signalling

    (as pulse > 10 ms), e.g. toremote control systems,in the case of automatictripping (e.g. protection)

    Via NO contact (S6 *)and cut-out switch (S7 *)

    Varistor module

    As overvoltage protectionfor protection devices inconjunction with inductivedevices in the vacuumcircuit-breaker (limiting toapprox. 500 V)

    Recommended for auxil-iary voltagesW 60 V DC

    Auxiliary switch

    Type 3SV9 (S1 *)

    Standard: 6NO+6NC,of which 2NO+2NC+2 changeover contactsare free1)

    Option:12NO+12NC,ofwhich 7NO+4NC+2 change-overcontactsare free 1)

    Mechanical interlocking

    Dependent on the typeof operating mechanism:

    Spring-operatedmechanism or

    Stored-energy mechanism

    Option:Switchgear interlockingwith the three-positionswitch-disconnector

    For further details concer-ning interlocking functions,refer to page 26.

    For further details, please refer also toCatalog HG 11.11 3AH Vacuum Circuit-Breakers

    1) For utilizationby thecustomer

    Abbreviations:NO = normally-open contactNC = normally-closed contact

    * Equipmentcode

    Basic equipment

    1 Auxiliary switch 6NO+6NC (S1*),option: 12NO+12NC

    2 1st release (Y1 *)

    Additional equipment

    3 Position switch (S4 *)

    4 Closing solenoid (Y9*)

    5 Operating cycle counter

    6 2nd release

    (e.g. Y2 *, Y6* and Y7 *)

    7 Mechanical interlockingwith interrogationof the three-positionswitch-disconnector

    1

    1

    2

    5

    6

    2

    7

    4

    3

    5

    R-HA41-080eps

    4

    3

    R-HA41-046eps

    Components

    Secondary equipment of the 3AH5vacuum circuit-breaker(typical example)

  • 7/26/2019 Simosec En

    21/44

    SiemensHA 41.21 2003 21

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Three-position switches as three-position switch-disconnectors or disconnectors

    Common features

    Metal-enclosedLocated in a

    gas-insulatedswitchgear vessel

    Switch positions:CLOSED-OPEN-EARTHED

    No cross insulationbetween phases

    Three-position switchwith air-insulatedprimary connectionsfor busbar and feeder

    Operation via a

    gas-tight welded-inbushing in the front ofthe switchgear vessel

    Mode of operation

    The switch shaft with themoving contact piecesrotates inside the cham-ber containing the fixedcontact pieces.

    Compression vanes,which rotate in conjunc-tion with the switchshaft, divide the arcingchamber into two sub-

    chambers each of whichchanges in conjunctionwith the rotation.

    During the switchingmovement, the compres-sion vanes generate apressure difference be-tween the subchambers.The SF6gas flowsthrough a nozzle, causesa directional blow-out ofthe breaking arc andquenches it rapidly.

    Interlocking is not neces-sary as the CLOSED

    and EARTHED func-tions cannot be imple-mented simultaneously.

    1 Bushing-type insulator for busbar

    2 Switchgear vessel for gas insulation

    3 Three-position switch-disconnector

    4 Bushing-type insulator for feeder

    5 Spring-operated mechanism with detachable lever

    6 Mounting location for three-phase current transformer (option)

    Detachable lever mechanism

    with three-position switch-disconnector

    Three-positionswitch-disconnector630 A

    R-HA41-057eps

    1

    2

    3

    4

    7 Operating lever, plugged inserted

    Three-positionswitch-disconnector 630 A

    Up to 630 A

    With gas-insulated,maintenance-free quench-ing principle

    Operating mechanism

    Spring-operated mechanismwith detachable lever

    Manual operation with theaid of a detachable lever

    Options: Mechanical ready-for-

    service indication

    Auxiliary switch Motor operating mecha-nism for switch-disconnector

    Locking device

    Spring-operated/stored-energy mechanism fortransformer panel types TR,TR1 and ME31-F

    Interlocks

    Opening of lower panelcover or cable compartmentcover only in EARTHEDposition

    Option: Logical mechanical

    interlocking of three-positionswitch-disconnector withvacuum circuit-breaker

    Three-positiondisconnector 1250 A

    Up to 1250 A, for paneltypes LS31, LS31-U, LS32and LT31

    Metal-enclosed

    Operating mechanism

    Spring-operated mechanismwith detachable lever

    Manual operation with theaid of a detachable lever

    Options: Mechanical ready-for-

    service indication Auxiliary switch Motor operating mecha-

    nism for disconnector Locking device

    Interlocks

    Opening of lower panelcover or cable compartmentcover only in EARTHEDposition

    Logical mechanicalinterlocking with vacuumcircuit-breaker

    Switch positions:

    EARTHED

    OPEN

    CLOSED

    5

    6

    Switching functions of thethree-position switch-disconnector630 A

    Switching and disconnecting underload

    Switching function as general purposeswitch-disconnector (class E3 and M1)according to

    IEC 60 265-1

    VDE 0670 Part 301 IEC 62 271-102 VDE 0670 Part 2/ EN 60 129

    Make-proof earthing function

    Switching functions of thethree-position disconnector1250 A

    Disconnecting

    Switching functions according to IEC 62 271-102 VDE 0670 Part 2/ EN 60 129

    Earthing function

    For panel types LS31, LS31-U,LS32 and LT31

    Note: Standards see page 41

    asthree-positionswitch-disconnector630 A

    asthree-positiondisconnector1250 A

    Components

  • 7/26/2019 Simosec En

    22/44

    22 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Busbars, HV HRC fuse assembly

    Busbar compartment extending over 3 panels(example)Side view

    R-HA41-061eps

    Busbars

    Safe-to-touch due tometallic enclosure

    Metal-clad busbarcompartment

    Three-pole design,bolted from panel topanel

    Easy switchgearextension

    Made of copper: Fl E-Cu forw 630 A Rd E-Cu for > 630 A to

    1250 A

    For > 12 kV:

    With insulated busbar

    HV HRC fuse assembly

    For transformer paneltypes TR and TR1

    For busbar voltage meter-ing panel type ME31-F

    HV HRC fuse linksacc. to DIN 43 625 (maindimensions) with strikerpin; version mediumacc. to IEC 60 282/VDE 0670 Part 4 *

    As short-circuit protec-tion before transformers

    With selectivity (depend-ing on correct selection)to upstream and down-

    stream connectedequipment Single-pole insulation

    Requirements acc. toIEC 60 420 * fulfilled bycombination of HV HRCfuse and three-positionswitch-disconnector

    Fuse replacement possi-ble only when feeder isearthed

    Option: Shunt release onoperating mechanism ofthree-position switch-disconnector

    Option: Tripped indica-tion of three-positionswitch-disconnector intransformer feeder (trans-former switch) for remoteelectrical indication withone normally-open con-tact (1NO)

    HV HRC fuse tripped

    Following the tripping of anHV HRC fuse link, the me-chanism for charging thespring must be set to theOPEN position

    Subsequently, earthing canbe implemented by meansof the three-positionswitch-disconnector ande.g. the fuse can bereplaced.

    Replacement of HV HRCfuse links

    Isolating and earthing ofthe transformer feeder

    Subsequent manualreplacement of theHV HRC fuse link

    2

    3

    1

    1 Busbar

    2 Insulating cap (e.g.forUr> 17.5 kV) onbusbar

    3 Bushing-typeinsulator for busbar

    Busbars

    HV HRC fuse assembly

    6

    4

    5

    8

    R-HA41-052eps 4 Insulating sleeve

    5 HV HRC fuse(not included in thescope of supply)

    6 Earthing switch (ratedshort-circuit makingcurrentIma= 4 kA)for cable connection

    7 Cover for boltedcable lug connection(e.g. for rated voltageUr= 24 kV)

    8 Cable sealing end(not included in thescope of supply)

    HV HRC fuses in transformer panel type TRSide view

    7

    R-HA41-071eps

    Control board of a transformer feeder

    CLOSED indi-cation, manual ormotor operation

    Indication HVHRC fuse trippedor shuntrelease tripped

    OPEN indication

    * Standards see page 41

    Components

  • 7/26/2019 Simosec En

    23/44

    SiemensHA 41.21 2003 23

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Allocation of HV HRC fuses and transformers

    The table opposite shows therecommended 3GD HV HRC

    fuse links (electrical data validfor ambient temperatures of upto 40oC) for the fuse protec-tion of transformers

    Recommendation

    The three-position switch-disconnector in the trans-former feeder (transformerswitch) was combined withSiemens HV HRC fuse linksof type 3GD and tested inaccordance with IEC 60 420 *

    Standards

    HV HRC fuse links withstriker pin, medium versionaccording to

    IEC 60 282 *

    VDE 0670 Parts 4 and 402

    DIN 43 625 main dimensions

    Ratedsystem

    voltage

    kV

    Transformer

    RatingSN

    kVA

    Relativeimpedancevoltageuk

    %

    RatedcurrentI1

    A

    Rated normal current of the HV HRCfuse link at ambient temperature of 40 OC

    Lowest Highestvalue value

    A A

    6 to 7.2 5075

    100

    444

    4.87.29.6

    161620

    161625

    125160200

    444

    12.015.419.2

    253240

    253240

    250315400

    444

    24.030.338.4

    505063

    5063

    100

    500630

    44

    48.061.0

    6380

    100100

    10 to 12 5075

    100

    44

    4

    2.94.3

    5.8

    1010

    16

    1010

    16

    125160200

    444

    7.29.3

    11.5

    162025

    162025

    250315400

    444

    14.518.323.1

    253240

    324050

    500630800

    445 to 6

    29.036.446.2

    506363

    638080

    10001250

    5 to 65 to 6

    58.072.3

    80100

    100100

    13.8 5075

    100

    444

    2.13.24.2

    61010

    61010

    125160200

    444

    5.36.78.4

    161616

    161620

    250315400

    444

    10.513.216.8

    202532

    253232

    500630800

    445 to 6

    21.026.433.5

    405050

    505050

    10001250

    5 to 65 to 6

    41.952.4

    6380

    6380

    15 to 17.5 5075

    100

    444

    1.92.93.9

    61010

    61010

    125160200

    444

    4.86.27.7

    101616

    101620

    250

    315400

    4

    44

    9.7

    12.215.5

    20

    2532

    25

    2532

    500630800

    445 to 6

    19.324.330.9

    324050

    405050

    10001250

    5 to 65 to 6

    38.548.2

    6363

    6380

    20 to 24 5075

    100

    444

    1.52.22.9

    66

    10

    66

    10

    125160200

    444

    3.64.75.8

    101016

    101016

    250315400

    444

    7.39.2

    11.6

    162020

    162025

    500

    630800

    4

    45 to 6

    14.5

    18.223.1

    25

    3232

    32

    4032

    100012501600

    5 to 65 to 65 to 6

    29.036.046.5

    405063

    405080

    2000 5 to 6 57.8 80 80* Standards see page 41

    Components

  • 7/26/2019 Simosec En

    24/44

    24 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Manual operatingmechanism

    Standard:As detachable levermechanism

    Option: Design accordingto VDEW recommenda-tion Association ofGerman Power Stations VDEW e.V.

    Spring-operated mecha-nism

    For ring-main paneltypes RK and RK1

    For all three-positionswitches (except in panel

    types TR and TR1)Spring-operated-/stored-

    energy mechanismFor transformer paneltypes TR and TR1 as wellas for busbar voltage me-tering panel type ME31-F

    The three-position switch isoperated via a rocker withmetal bellows which isgas-tight and welded at theswitchgear vessel.

    Motor operatingmechanism(option)

    The manual operating me-chanisms can be equippedwith motor operating mecha-nisms both for the three-position switch-disconnectorand for the three-positiondisconnector.

    Operating voltages for motoroperating mechanisms: 24, 48, 60, 110, 220 V DC 50/60 Hz 110 and 230 V AC

    Electrical operation:

    Standard: Remote opera-tion (applied to terminal)

    Option: Local operationby momentary-contactrotary control switch

    Shunt release(option)

    Spring-operated/stored-en-ergy mechanisms can beequipped with a shunt re-lease. Remote electrical trip-ping of the three-positionswitch-disconnector is possi-ble via the magnetic coilof the shunt release, e.g.transformer overtemperaturetripping.

    To avoid thermal overloadingof the shunt release in theevent of a continuous signalthat may be applied, theshunt release is switched offvia an auxiliary switch whichis mechanically coupled withthe three-position switch-disconnector.

    Auxiliary switch(option)

    Each operating mechanismof the three-position switch-disconnector can be option-ally equipped with an auxil-iary switch for the switchposition indication: 1NO + 1NC for

    CLOSED/EARTH 2NO for OPEN

    Separate earthing switch: 2NO and 1NC for

    EARTH 2NO for OPEN

    Operating mechanisms for three-position switches

    Operating mechanisms(examples)

    Detachable lever mechanismas spring-operated mechanismfor ring-main feeders

    R-HA41-079eps

    1 Terminal strip locatedin the low-voltageniche (optionally inthe low-voltagecompartment)

    2 M.c.b. (option)in the low-voltageniche

    3 Local-remote switch(option)

    4 Actuation for themotor operatingmechanism of thethree-position

    switch-disconnector5 Auxiliary contactors

    of the motor operatingmechanism for lockingthe motor

    6 Auxiliary switch

    7 Switch positionindicator for thethree-positionswitch-disconnector

    8 Locking device(standard for motoroperating mechanism)

    9 Operating mechanismfor the three-positionswitch-disconnectorcoupled with the motor

    operating mechanism10 Shunt release (option)

    11 Motor operatingmechanism

    R-HA41-070eps

    Abbreviations:

    NO = normally-open contactNC = normally-closed contact

    Rated insulationvoltage250 V AC/DC

    Insulation groupC to VDE 0110

    Continuous current10 A

    Making capacity50 A

    Technical data of the auxiliary switch

    Breaking capacity

    AC operation at40 Hz to 60 Hz

    Operating Normalvoltage current

    V A

    DC operation

    Operating Normal currentvoltage resistive inductive:

    T=20 msV A A

    up to 230 10 24 10 10

    48 10 9

    60 9 7

    110 5 4

    220 2.5 2

    Rated switching capacity

    Operating mechanism parts intransformer feeder

    6

    8

    7

    9

    10

    11

    5

    4

    3

    2

    1

    Components

  • 7/26/2019 Simosec En

    25/44

    SiemensHA 41.21 2003 25

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Short-circuit/earth-faultindicator (option)

    The ring-main feeders canbe equipped with a 3-phaseshort-circuit or earth-faultindicator:

    Optical signal when a pre-selected pickup value isexceeded

    With ring-type sensors

    Display panel, withdraw-able housing, dependingon the type

    Short-circuit pickup values:e.g. 400, 600, 800 or

    1000 AOption: Remote electricalindication via contact (1NO +1NC contact, passing con-tact), applied to terminal

    Ready-for-service indicator(option for three-positionswitch)

    Self-monitoring; easy toread

    Independent of tempera-ture and pressure varia-tions

    Independent of site altitude

    Only responds to changesin gas density

    Option: Alarm switch1NO contact

    Mode of operation

    For the ready-for-service indi-cator, a gas-tight measuringbox is installed on the insideof the switchgear vessel.

    A coupling magnet, whichis fitted to the bottom endof the measuring box, trans-mits its position to an outsidearmature through the stain-less steel switchgear vessel.This armature moves theready-for-service indicator ofthe switchgear.

    While changes in the gasdensity during the loss ofgas, which are decisive forthe insulating capacity, aredisplayed, temperature-dependent changes in thegas pressure are not. Thegas in the measuring box hasthe same temperature asthat in the switchgear.

    The temperature effect iscompensated via the samepressure change in both gasvolumes.

    Verification of safeisolation from supply

    Voltage detection systems

    For voltage detectionaccording to IEC 61 243-5 /VDE 0682 Part 415 with:

    Standard: HR system

    Option: LRM system

    Option: LRM system asCAPDIS-S1 or CAPDIS-S2

    Features of theHR/LRM system

    Voltage indicator

    HR system (standard) or LRM system (option)

    Verification of safe isolationfrom supply phase byphase through insertion ineach socket pair

    For continuous operation

    Safe-to-touch

    Measuring system andvoltage indicator can betested

    Voltage indicator flashesif high voltage is present

    Fixed-mounted capacitive

    voltage divider in bushings

    Features of CAPDIS-S1, -S2

    Maintenance-free

    Without auxiliary power

    Self-checking

    Option: With remoteindication of the voltagestate (auxiliary powerrequired for CAPDIS-S2)

    Mounting of voltagedetection systems

    Standard:In all ring-main andcircuit-breaker feeders

    Option:In transformer feeders

    Verification of correct ter-minal-phase connections

    Verification of correctterminal-phase connec-tions possible by means ofa phase comparison testunit (can be ordered sepa-rately)

    Safe-to-touch handling of

    the phase comparison testunit by inserting it into thecapacitive taps (socketpairs) of the switchgear

    Indicating and measuring equipment

    Indicating and measuring equipment(examples)

    Voltage indicator, HR system(standard)

    R-HA40-088

    eps

    R-HA40-032eps

    Short-circuit indicator ALPHA M(example)

    6 Measuring box

    7 Magnetic coupling

    8 Red indication:not ready for service

    9 Green indication:ready for service

    Principle of operation of gas monitoringwith ready-for-service indicator

    Stainless-steel vesselfilled with SF6gas,gauge pressure500 hPa at 20 C

    Ready-for-serviceindicator

    Reset:manual

    For phase indicationsL1, L2 and L3

    Mounting locations inthe control board for

    1 Short-circuit / earth-fault indicator (option)

    2 Ready-for-serviceindicator (option)

    3 Voltage indicator, HRsystem, plugged-in(standard)

    R-HA41-072beps

    Control board of a ring-main panel

    (example)

    3

    1

    2

    Components

  • 7/26/2019 Simosec En

    26/44

    26 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Interlocking systems and locking devices

    Interlocking of connectioncompartment

    Ring-main andcircuit-breaker panel

    Access to the cable con-nection compartment(e.g. for cable testing) isonly possible providedthat the feeder is isolatedand earthed (three-posi-tion switch-disconnectorin EARTHED position)

    Option: Closing lock-outThis prevents the three-position switch-disconnec-tor from being switchedfrom OPEN toCLOSED position,when the cable compart-ment cover is removed

    Transformer panel

    Access to the cable con-nection compartment andto the HV HRC fuse com-partment (e.g. for replace-ment of HV HRC fuselinks) is only possible pro-vided that the feeder isisolated and earthed(three-position switch-

    disconnector inEARTHED position)

    Option: De-earthinglock-outThis prevents thethree-position switch-disconnector from beingswitched from positionEARTHED to OPEN.

    Switchgear interlocking

    Dependent on the va-cuum circuit-breaker oper-ating mechanism with

    Spring-operated or

    Stored-energy mechanism

    Option: Switchgear-sidemechanical interlockingwith three-positionswitch-disconnector

    Vacuum circuit-breakercannot be closed whenthree-position switch-disconnector is in theOPEN position:

    Spring-operated mecha-nism: Hand crank openingis blocked

    Stored-energy mechanismwith closing solenoid3AY15 10: Pushbutton(S12) operated by mecha-nical interlock preventscontinuous command toclosing solenoid

    Interlocking in circuit-breaker panel types LS1,

    LS1-U and LT10 (with 3AH5fixed-mounted vacuumcircuit-breaker)

    Option: Logical mechanicalinterlocking with three-po-sition switch-disconnector

    Earthing of feeder viathree-position switch-disconnector inEARTHED position

    Interlocking in circuit-breaker panels (with 3AH6removable vacuum circuit-breaker)

    Option: For 630 A paneltypes LS11, LS11-U andLT11: Logical mechanicalinterlocking with three-po-sition switch-disconnector

    Standard: For 1250 Apanel types LS31, LS31-U,LS32 and LT31: Logicalmechanical interlockingwith three-positiondisconnector

    Logical mechan. interlock-ing of cable compartmentcover: Opening of cable

    compartment cover onlypossible provided that thefeeder is earthed

    Feeder earthing

    Standard: Earthing byswitching of vacuumcircuit-breaker 3AH61) inposition CLOSED andof three-position switch2)in position EARTHED

    Option: For circuit-breakerpanel types LS11, LS31and LS32: Earthing bymeans of an additional

    make-proof earthingswitch at the feeder withinspection window in thecable compartment cover

    Locking devices

    The three-position switch-disconnector can be lockedon the operating mechanismside in any position (option).

    1) With additional locking device optionally with signallingswitch for securing theCLOSED position of the

    vacuum circuit-breaker forfeeder EARTHED

    2) Three-position switch as Switch-disconnector in panel

    types LS11, LS11-U and LT11 Disconnector in panel types

    LS31, LS31-U, LS32 and LT31

    Interlocking systems

    Locking device(option)

    R-HA41-064ceps

    R-HA41-081eps

    Interlocking for cable compartment cover

    Removed cable compartment coverwith earthed bus sectionalizer panel

    Locking device of the detachable lever mechanisme.g. for padlock

    Components

  • 7/26/2019 Simosec En

    27/44

    SiemensHA 41.21 2003 27

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    4MC63 three-phase current transformers for panel types LS ... and LT ...

    Application

    For circuit-breaker panelstype LS ...

    For bus sectionalizer panelstype LT ...

    Option: For ring-main panelstype RK ...

    Features

    According to IEC 60 044-1/VDE 0414 Part 1

    Designed as a three-polering-core currenttransformer

    Free of dielectrically

    stressed cast-resin parts(due to design)

    Insulation class E

    Inductive type

    Climate-independent

    Secondary connection bymeans of a terminal stripinside the panel

    Installation

    Arranged outside the switch-gear vessel on the bushings

    Factory-assembled

    Other designs(option)

    Three-phase current transfor-mers for protection equipmentbased on c.t. operation:

    7SJ4 protection relay asdefinite-time overcurrentprotection

    Definite-time overcurrentprotection relay,make SEG, type WIP 1

    Technical data 4MC63 53 three-phase current transformer

    forIN

  • 7/26/2019 Simosec En

    28/44

    28 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    4MC70 33, 4MC70 31 cable-type current transformers and 4MC70 32 bus-type current transformers

    4MC70 33 cable-type current transformerson the cable at the panel connection

    Application

    For circuit-breaker panelstype LS ...

    For ring-main panelstype RK ...

    For transformer panelstype TR ...

    Features

    According to IEC 60 044-1/VDE 0414 Part 1

    Designed as a single-polering-core current transformer

    Only for shielded cables

    Climate-independent

    Free of dielectricallystressed cast-resin parts(due to design)

    Insulation class E

    Inductive type

    Secondary connection bymeans of a terminal stripinside the panel

    Installation

    4MC70 33 cable-type currenttransformer and 4MC70 32bus-typecurrent transformer

    for panel typeLS ...4MC70 31 cable-type current

    transformer: e.g. for paneltypes RK ..., K ... and TR ...

    Arranged on the cable atthe panel connection

    Transformers mounted on asupporting plate at ourfactory; final assembly onthe cables on site

    * Depending on the core data** Available installation height

    inside panel types RK or RK1:Approx. 285 mm, depending onmake, type and cross-section ofsealing end

    Other values available on request

    R-HA41-049aeps

    R-HA41-025eps 4MC70 31 cable-type

    current transformer

    R-HA41-024eps

    H

    H

    4MC70 33 cable-typecurrent transformer,4 different overall heights

    R-HA41-027eps

    4MC70 32bus-typecurrent transformer

    Technical data 4MC70 33 cable-typecurrent transformer

    4MC70 31 cable-typecurrent transformer

    4MC70 32 bus-typecurrent transformer

    Primary data

    Max. equipment operatingvoltage Um

    0.72 kV 0.72 kV 0.72 kV

    Rated currentIN A 30 A to 600 A 50 A to 600 A 200 A to 600 A

    Rated short-durationpower-frequencywithstand voltage(winding test)

    3 kV 3 kV 3 kV

    Rated thermal short-timewithstand currentIth

    25 kA 25 kA 25 kA

    Rated continuous thermalcurrentID

    max. 1.2 xIN max. 1.2 xIN max. 1.2 xIN

    Transient overloadcurrent

    1.5 xID/ 1 h or2 xID/ 0.5 h

    1.5 xID/ 1 h or2 xID/ 0.5 h

    1.5 xID/ 1 h or2 xID/ 0.5 h

    Rated peak withstandcurrentIdyn

    unlimited unlimited unlimited

    Secondary data

    Rated current 1 A (option: 5 A) 1 A (option: 5 A) 1 A (option: 5 A)

    Meas-uringcore

    Class 0.2 0.5 1 1 0.2 0.5 1

    Overcurrent factor FS10 (option: FS5) FS5 (option: FS10) FS10 (option: FS5)

    Rating 2.5 VA to 10 VA 2.5 VA to 10 VA 2.5 VA to 10 VA

    Pro-tectioncore

    Class 10 P 5 P 10 P 5 P (on request)

    Overcurrent factor 10 10 10 10

    Rating 2.5 VA to 10 VA 2.5 VA to 15 VA

    Option: Secondary tap 1 : 2(e.g. 150 A 300 A)

    1 : 2 1 : 2(e.g. 150 A 300 A)

    Dimensions

    Overall height H ** mm 50* 100* 170*285* 89 80 * 150 *

    Outside diameter 145 mm 85 mm x 114 mm 125 mm

    Inside diameter 55 mm 40 mm 55 mm

    For cable diameter 50 mm 36 mm 50 mm

    Components

  • 7/26/2019 Simosec En

    29/44

    SiemensHA 41.21 2003 29

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    4MA7 block-type current transformers and 4MR voltage transformers

    4MR single-pole voltage transformer

    Primary data

    Max. equipment operatingvoltageUm(= 1.2 x UN)12 kV

    Rated voltageUNat max.rated short-durationpower-frequencywithstand voltageUd

    3.3/ 3kV at 10 kV3.6/ 3 kV at 10 kV

    4.8/ 3 kV at 20 kV5.0/ 3 kV at 20 kV6.0/ 3 kV at 20 kV6.6/ 3kV at 20 kV7.2/ 3 kV at 20 kV

    10.0/ 3 kV at 28 kV11.0/ 3kV at 28 kV

    Rated lightning impulsewithstand voltageUp

    75 kV

    Rated voltage factor(8 h)

    1.9 xUN

    Max. equipment operating

    voltageUm(= 1.2 xUN)

    24 kV

    Rated voltageUNat max.rated short-durationpower-frequencywithstand voltageUd

    13.8/ 3kV at 38 kV15.0/ 3 kV at 38 kV

    17.5/ 3 kV at 50 kV20.0/ 3 kV at 50 kV22.0/ 3 kV at 50 kV

    Rated lightning impulsewithstand voltage

    125 kV

    Rated voltage factor(8 h)

    1.9 xUN

    Secondary data

    Rated voltage 100/ 3V110/ 3 V120/ 3 V

    Rated voltage for auxiliary

    winding (option)

    100/3 V

    110/3 V120/3 V

    Rating 20 VA 50 VA 100 VA

    Class 0.2 0.5 1

    Other values available on request

    Application

    For billing metering panelstype ME1 ...

    For bus riser paneltype HF

    For mounting at thefeeder

    Features

    4MA7 current transformer

    According to IEC 60 044-1/VDE 0414 Part 1

    Dimensions according toDIN 42600 Part 8

    Designed as a single-poleindoor block-type currenttransformer

    Cast-resin insulated

    Insulation class E

    Secondary connection bymeans of screw-typeterminals

    4MR voltage transformer

    According to IEC 60 044-2/VDE 0414 Part 2

    Dimensions according toDIN 42600 Part 9 (small

    model)

    Designed as an indoorvoltage transformer:

    Type 4MR, single-pole Option: Type 4MR, two-pole

    Cast-resin insulated

    Insulation class E

    Secondary connection bymeans of screw-typeterminals

    Other values available on request

    R-HA41-060aeps

    4MA7 block-type currenttransformer,single-pole

    4MR14 voltagetransformer,single-pole

    4MR voltage transformer and4MA7 block-type current transformer installed inbilling metering panel type ME1

    R-HA41-029aeps

    R-HA41-030aeps

    Technical data

    4MA7 single-pole block-type current transformer

    Primary data

    Max. equipment operatingvoltageUm12 kV 24 kV

    Rated short-durationpower-frequencywithstand voltage

    38 kV 50 kV

    Rated lightning impulsewithstand voltage

    95 kV 125 kV

    Rated currentIN 25 A to 1250 A

    Rated thermal short-timewithstand currentIth

    up to 25 kA

    Rated continuous thermalcurrentID

    up to 1.2 xIN

    Rated peak withstandcurrentIdyn

    max. 2.5 x Ith

    Secondary data

    Rated current 1 A or 5 A

    Meas- Classuring Overcurrent factorcore

    Rating

    0.2 0.5 1

    FS5 or FS10

    10 VA to 15 VA

    Pro- Classtection Overcurrent factorcore

    Rating

    5 P or 10 P

    10

    5 VA or 15 VA

    Components

  • 7/26/2019 Simosec En

    30/44

    30 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Cable connection

    General features

    Connecting lugs for sealing endsarranged one behind the other

    Uniform cable connection heightfor the respective panel types

    Withcablebracket,e.g. type C40according toDIN EN50024

    Access to the cable connectioncompartment only if feeder hasbeen isolated and earthed

    Special features

    In ring-main panels In circuit-breaker panels In cable panels

    For thermoplastic-insulated cables

    For paper-insulated mass-impregnated cables withadapter systems

    For connection cross-sections up to 300 mm2

    Cable routing downwards

    In transformer panels:

    For thermoplastic-insulated cables

    For connection cross-sections up to 120 mm2:

    Cable lug max. 32 mm wide

    For rated normal currentsof 200 A

    For options see figures

    Cable cross-sections

    Note

    Cable sealing ends and cable clampsare not included in the scope of supply

    Cable connection(examples)

    Cable connection compartment with cablesealing ends (options: A, B, C1) and D1), see below)

    Ring-main panel type RKCable connection compartment as delivered

    L3 L2 L1 L1L2L3

    Transformer panel type TRCable connection compartment as delivered

    Cable connection compartment with cablesealing ends (option: A2), see below)

    L3L2L1

    R-HA41-050eps

    R-HA41-051eps

    R-HA41-053eps

    R-HA41-052eps

    R-H

    A41-055eps

    R-HA41-067eps

    L3L2L1

    Cable connection compartment with cablesealing ends (options: A, B, C and D, see below)

    Circuit-breaker panel type LS11Cable connection compartment as delivered

    Options A Mounted cable clamps 2)

    B Short-circuit / earth-fault indicator

    C Double cable connection

    D Suitable for connection of surge arresters3)

    5

    1

    4

    3

    7

    8

    14

    10 13

    12

    2

    6

    L1L2

    L3

    9

    11

    1) Only with ring-main panel type RK1

    2) Cable clamps with transformerpanels type TR ... partly mounted

    underneath the panel in the cablebasement

    3) Make Siemens, type 3EK7,other makes on request

    Panel type Connectable cablesxconnection cross-sections

    No. x mm2

    for rated voltage

    12 kV 17.5kV 24 kV

    K Standard

    on request

    1x300 1x300 1x300

    2x300

    K1 2x400 2x400 2x400

    RK, K-E 2x300 1x300 1x300

    RK1, K1-E 2x300 2x300 2x300

    LS1 2x300 2x300 2x300

    LS11,LS31 2x400 2x400 2x300

    LS32 Standard

    Option

    on request

    3x400 3x400 3x300

    4x300 4x300

    4x300

    ME1-K, ME1-KS 3x400 3x400 3x300

    Components

  • 7/26/2019 Simosec En

    31/44

    SiemensHA 41.21 2003 31

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    1) Transformer panel types TR ...: Lower edge of sealing end below panel Cable lugs of sealing ends up to 32 mm width Owing to the various sealing end lengths, some of

    the mounted cable clamps are underneath the panel

    2) Circuit-breaker panel types LS11, LS31 and LS32: Lower edge of sealing end below panel

    Selection data for various cable sealing ends

    1 As-delivered condition, preparedfor cable sealing endw 12 kV

    2 As-delivered condition, preparedfor cable sealing end > 12 kV, w 24 kV,additionally with insulating sleeve

    3 Phase L1:Make: Corning Cables (RXS)Type IAEM 20,240 mm2 (20 kV)

    4 Phase L2:Make: Tyco Electronics RaychemType EPKT 24 C / 1X,185 mm2 (24 kV),as shrink-on sealing end,for severe ambient conditions

    5 Phase L3:Make: PirelliType ELTI mb-1C-2h-C-T3,240 mm2 (24 kV)

    6 As-delivered condition, preparedfor cable sealing end

    7 Phase L1:Make: Corning Cables (RXS)Type IAEM 20,95 mm2 (20 kV)

    8 Phase L2:Make: Tyco Electronics RaychemType TFTI/5131,

    95 mm

    2

    (24 kV),as push-on sealing end

    9 Phase L3:Make: EuromoldType AIN, 95 mm2 (24 kV)

    10 As-delivered condition, preparedfor cable sealing endw 12 kV

    11 As-delivered condition, preparedfor cable sealing end > 12 kV, w 24 kV,additionally with insulating cap

    12Phase L1:Make: Corning Cables (RXS)Type IAES 20,240 mm2 (20 kV)

    13Phase L2:Make: PirelliType ELTI 1C-24-D-T3,240 mm2 (24 kV),as indoor sealing end,for severe ambient conditions

    14Phase L3:Make: EuromoldType AIN 20,240 mm2 (24 kV)

    Connection height **of cables above

    floor or abovelower edge of panel:

    Cable sealing ends

    (examples)

    Single-core thermoplastic-insulated cables for 12 kV to

  • 7/26/2019 Simosec En

    32/44

    32 SiemensHA 41.21 2003

    Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

    Low-voltage equipment

    Low-voltage niche(standard)

    Screwed-on cover as Cover (available mounting

    depth behind ofapprox. 184 mm)

    Frame cover, approx.46 mm deeper version(available mountingdepth behind ofapprox. 230 mm)

    For accommodation ofterminals and standardprotection devices, e.g.in circuit-breaker panelscombined with framecover for panels

    Type LS1: Protectionrelays (with max. 75 mmwide mounting frame),e.g. type 7SJ45, 7SJ46and 7SJ60,option: Protection relaymake SEG

    Type LS11: Protectionrelays (with max. 150 mmwide mounting frame),e.g. type 7SJ4..., 7SJ60and 7SJ61 (on requesttype 7SJ62), option: Pro-tection relay make SEG

    For bus wires and/or con-

    trol cables; niche open atthe side to the adjacentpanel

    Safe-to-touch, separatedfrom high-voltage part ofthe panel

    Degree of protectionIP 3X (standard)

    Low-voltagecompartment(option)

    Heights 350