sinking and sourcing concepts - buffalo state...

2
1-800-633-0405 e35-2 Appendix When choosing the type of input or output module for your system (or DL05/DL06/DL105 I/O type), it is very important to have a solid understanding of sinking and sourcing concepts. Use of these terms occurs frequently in discussion of input or output circuits. It is the goal of this section to make these concepts easy to understand, so you can make the right choice the first time when selecting the type of I/O points for your application. This section provides short definitions, followed by general example circuits. First you will notice that the diagrams on this page are associated with only DC circuits and not AC, because of the refer- ence to (+) and (-) polarities. Therefore, sinking and sourcing terminology applies only to DC input and output circuits. Input and output points that are sinking or sourcing can conduct current in one direc- tion only. This means it is possible to connect the external supply and field device to the I/O point, with current trying to flow in the wrong direction, and the circuit will not operate. However, the supply and field device can be connected every time based on an understanding of sourcing and sinking. The figure below depicts a sinking input. To properly connect the external supply, it must be connected so the input provides a path to supply common(-). So, start at the PLC input terminal, follow through the input sensing circuit, exit at the common terminal, and connect the supply (-) to the common terminal. By adding the switch between the supply (+) and the input, the circuit is completed. Current flows in the direction of the arrow when the switch is closed. By applying the circuit principles to the four possible combinations of input/output sinking/sourcing types, there are four circuits, as shown above. The common terminal is the terminal that serves as the common return path for all I/O points in the bank. Sink/source I/O circuits combine sinking and sourcing capabilities. This means that the I/O circuitry in the PLC will allow current to flow in either direction, as shown at the right. The common terminal connects to one polarity, and the I/O point connects to the other polarity (through the field device). This provides flexibility in making connections to your field power supply. Please note: • Wire all I/O points with a shared common as either sinking or sourcing. • Do not use an AC power supply on a DC sink/source I/O point. + -- Input S ens ing PLC Input Common (sinking) + -- Input S ens ing Load Sinking Input (IE C: pos itive logic) Sinking Output (IE C: negative logic) Sourcing Input (IE C: negative logic) Sourcing Output (IE C: pos itive logic) PLC Input Common + -- Output S witch PLC Output Common + -- Input S ens ing Load PLC Input Common + -- Output S witch PLC Output Common P NP NP N Sink/Source Input (IE C: pos ./neg. logic) Sink/Source Output (IE C: pos ./neg. logic) + -- Input S ens ing Load PLC Input Common Output S witch PLC Output Common + -- OR + -- + -- OR P NP /NP N Sinking and Sourcing Concepts Sinking = provides a path to supply common (-) Sourcing = provides a path to supply source (+) 24VDC + Output Sensor Common Input Optical Isolator Current Sourcing Configuration (NPN) Current Sinking Field Device DC Sourcing Input Module + NPN (Sinking) Field Device Example 24VDC + Output Sensor Common Input Optical Isolator Current Sinking Configuration (PNP) Current Sourcing Field Device DC Sinking Input Module + PNP (Sourcing) Field Device Example Field device examples - 3 wire connections Volume 13

Upload: truongtu

Post on 17-Apr-2018

222 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Sinking and Sourcing Concepts - Buffalo State Collegetech2.buffalostate.edu/classes/plc/projects/DL05/sinksource.pdf · Sinking and Sourcing Concepts Sinking = provides a path to

1 - 8 0 0 - 6 3 3 - 0 4 0 5e35-2 Appendix

When choosing the type of input or outputmodule for your system (orDL05/DL06/DL105 I/O type), it is veryimportant to have a solid understanding ofsinking and sourcing concepts. Use ofthese terms occurs frequently in discussionof input or output circuits. It is the goal ofthis section to make these concepts easy tounderstand, so you can make the rightchoice the first time when selecting the typeof I/O points for your application. Thissection provides short definitions, followedby general example circuits.

First you will notice that the diagrams onthis page are associated with only DCcircuits and not AC, because of the refer-ence to (+) and (-) polarities. Therefore,sinking and sourcing terminology appliesonly to DC input and output circuits. Inputand output points that are sinking orsourcing can conduct current in one direc-tion only. This means it is possible toconnect the external supply and fielddevice to the I/O point, with current tryingto flow in the wrong direction, and thecircuit will not operate. However, thesupply and field device can be connectedevery time based on an understanding ofsourcing and sinking.

The figure below depicts a sinking input.To properly connect the external supply, itmust be connected so the input provides apath to supply common(-). So, start at thePLC input terminal, follow through theinput sensing circuit, exit at the commonterminal, and connect the supply (-) to thecommon terminal. By adding the switchbetween the supply (+) and the input, thecircuit is completed. Current flows in thedirection of the arrow when the switch isclosed.

By applying the circuit principles to the fourpossible combinations of input/outputsinking/sourcing types, there are fourcircuits, as shown above. The commonterminal is the terminal that serves as thecommon return path for all I/O points inthe bank.

Sink/source I/O circuits combine sinkingand sourcing capabilities. This means thatthe I/O circuitry in the PLC will allowcurrent to flow in either direction, as shownat the right. The common terminalconnects to one polarity, and the I/O pointconnects to the other polarity (through thefield device). This provides flexibility inmaking connections to your field powersupply. Please note:

• Wire all I/O points with a shared common as either sinking or sourcing.

• Do not use an AC power supply on a DC sink/source I/O point.

+

--

InputSensing

PLCInput

Common

(s inking)

+

--

InputSensing

Load

S inking Input(IE C: pos itive logic)

S inking Output(IE C: negative logic)

S ourcing Input(IE C: negative logic)

S ourcing Output(IE C: pos itive logic)

PLC

Input

Common

+

--

OutputSwitch

PLC

Output

Common

+

--

InputSensing

LoadPLC

Input

Common

+

--

OutputSwitch

PLC

Output

Common

PNP

NPN

S ink/S ource Input(IE C: pos ./neg. logic)

S ink/S ource Output(IE C: pos ./neg. logic)

+

--InputSensing

Load

PLC

Input

Common

OutputSwitch

PLC

Output

Common

+

--OR

+

-- +

--ORPNP/NPN

Sinking and Sourcing ConceptsSinking = provides a path to supply common (-)

Sourcing = provides a path to supply source (+)

24VDC

+

Output Sensor

Common

Input

OpticalIsolator

Current SourcingConfiguration

(NPN) Current SinkingField Device

DC Sourcing Input Module+ –

NPN (Sinking)Field Device Example

24VDC

+

Output Sensor

Common

Input

OpticalIsolator

Current SinkingConfiguration

(PNP) Current SourcingField Device

DC Sinking Input Module+ –

PNP (Sourcing)Field Device Example

Field device examples - 3 wire connections

Volume 13

Page 2: Sinking and Sourcing Concepts - Buffalo State Collegetech2.buffalostate.edu/classes/plc/projects/DL05/sinksource.pdf · Sinking and Sourcing Concepts Sinking = provides a path to

w w w . a u t o m a t i o n d i r e c t . c o m Appendix e35-3

CompanyInformation

SystemsOverview

ProgrammableControllers

Field I/O

Software

C-more & other HMI

Drives

SoftStarters

Motors &Gearbox

Steppers/Servos

Motor Controls

ProximitySensors

Photo Sensors

Limit Switches

Encoders

CurrentSensors

PressureSensors

TemperatureSensors

Pushbuttons/Lights

Process

Relays/Timers

Comm.

TerminalBlocks & Wiring

Power

CircuitProtection

Enclosures

Tools

Pneumatics

Appendix

ProductIndex

Part #Index

Volume 13

Sinking and Sourcing ConceptsCommon terminals and how to use themIn order for a PLC I/O circuit to operate,current must enter at one terminal andexit at another. This means at least twoterminals are associated with every I/Opoint. In the figure at the right, the inputor output terminal is the main path for thecurrent. One additional terminal mustprovide the return path to the powersupply. Together, the main path and thereturn path create a loop, or a completecircuit for current to flow.

If there was unlimited space and budgetfor I/O terminals, then every I/O pointcould have two dedicated terminals.However, providing this level of flexibilityis not practical or even necessary for mostapplications. So, most input or outputpoints on PLCs are in groups that sharethe return path (called commons). Thefigure at the right shows a group (orbank) of four input points that share acommon return path. In this way, the fourinputs require only five terminals insteadof eight.

NOTE: Assuming all input circuits have a similarresistance, the current at the common terminal isfour times greater than the current at any one of theinputs. This effect is especially important to note foroutput circuits, where the current through a commonterminal can reach several amperes. You will needto decide whether to fuse each output point individu-ally, or to put a fuse in the common terminal path.

Wiring labels and how to interpret themDL205, DL305, DL405 - Most DL205,DL305 and DL405 input and outputmodules group their I/O points intobanks that share a common return path.The best indication of I/O commongrouping is on the wiring label, such asthe one shown at the right. The miniatureschematic shows two circuit banks witheight input points in each. The commonterminals are labeled “CA” and “CB,”respectively.

In the wiring label example, the positiveterminal of a DC supply connects to thecommon terminals. Some of the symbolsyou will see on wiring labels and theirmeanings are shown at the right.

DL05/DL06/DL105 — Most DL05, DL06and DL105 input and output circuits are

grouped into banks that share a commonreturn path. The best indication of I/Ocommon grouping is on the wiring label.Sample DL05, DL06 and DL105 wiringlabels and their meanings are shownbelow.

+

--

I/OCircuit

PLC

(I/O Point)

Return Path

FieldDevice

Main Path

+

--

InputSensing

Input 4

Common

Input 3

Input 2

Input 1

I/O Common Grouping Bar (DL105)

Two banks of four inputs and one bank of two (DL105)

Two banks of four inputs and two banks of three outputs (DL05)

Input Bank (DL05)

0123

4567

ATB

12--24VDC

D4--16ND2

0123

4567

B

INPUT

CA0

4

15

26

37

CB

40

51

62

73

10.2-- 26.4VDC4-- 12mA

L

AC supply

AC or DC supply

Input S witch

Output Load

DC supply+--

DL405 inputmodule shown