SISTEM SCADA DAN TELEKOMUNIKASIJENJANG DIKLAT I
Aulia Mahdi, ST, SE – PT.PLN (Persero) Disjaya & Tangerang
PENGERTIAN SCADA
MENGAWASI MENGENDALIKAN
SCADA (SUPERVISORY CONTROL AND DATA ACQUISITION)
SISTEM YANG MENGAWASI MENGENDALIKANDAN
PERALATAN PROSES YANG TERSEBAR SECARA GEOGRAFIS
TUJUAN DAN FUNGSI SCADATUJUAN
FUNGSI
1. WAKTU PEMULIHAN GANGGUAN
1. TELE CONTROL
2. TELE SIGNAL
3. TELE METERING
2. KWh PADAM
3. PEMANTAUAN JARINGAN 20 kV
4. OPTIMASI PEMBEBANAN
TELE CONTROL
TELE CONTROL / REMOTE CONTROL (RC) DO (DIGITAL OUTPUT)
OPEN / CLOSE CB / LBS AO (ANALOG OUTPUT)
NAIKKAN / TURUNKAN TAP CHANGER
TELE SIGNAL
TELE SIGNAL (TS) / DIGITAL INPUT (DI) TSS (TELE SIGNAL DOUBLE)
STATUS CB CLOSE / OPEN TSD (TELE SIGNAL SINGLE)
POSISI LOCAL / REMOTEOPT / HFDDCF / SF
TELE METERING
TELE METERING (TM) / ANALOG INPUT (AI) ARUS (A) TEGANGAN (kV) DAYA (MW, MX)
DISPATCHER
TIMUR BARAT
DIFUSERKOMPUTER MASTER
RADIO
MICROVAX 4106
LAN BRIDGE
MASTER STATION
REPEATER
MODEM
RADIO
KABEL KONTROL
FIBER OPTIK
MEDIA KOMUNIKASI
REMOTE TERMINAL UNIT(RTU)
MODEM
RTU
PLATINE
RECTIFIER
BATTERY
KUBICEL
RADIO
IED
KONFIGURASI SCADA
MASTER STATION (1) Komputer Server Front End Processor Man Machine Interface (MMI) Komputer Database server Komputer Engineering Swicth atau Hub LAN Radio Master Recorder GPS untuk referensi waktu DTS (Dispatcher Training Simulator) UPS (Uninterruptible Power Supply) Projector atau Mimic Panel Peripheral : Printer, logger Sofware Aplikasi SCADA Server & MMI
MASTER STATION (2)
FRONT END PROCESSOR
PENGAMBILAN DATA DARI RTU PENYIMPANAN DATA PENGIRIMAN DATA KE RTU PENGIRIMAN DATA KE HMI PENYESUAIAN WAKTU DIAGNOSA RTU
MAN MACHINE INTERFACE
MEMONITOR KONDISI SISTEM JARINGAN DISTRIBUSI
MENGONTROL SISTEM JARINGAN DISTRIBUSI
ENTRY/EDIT DATA NAVIGASI FUNGSI SCADA
REMOTE TERMINAL UNIT
FUNGSI RTU : KOMUNIKASI DENGAN MASTER KOMUNIKASI DENGAN IED I/O PROCESSING LOCAL DATA LOGGING MANAJEMEN DATABASE
MEDIA KOMUNIKASI
PILOT CABLE RADIO DATA FIBER OPTIC POWER LINE CARRIER (PLC)
CPU
RC
TS
MODEM
RangkaianProteksi
Box KK
BOX DS
MDF
Ke Pusat Kontrol
Box KK
RangkaianProteksi
cell
cell
Kabel
kontro
l
1-2 km
Gardu GH / CDS Gardu DS
KONFIGURASI KK ANTARA CDS DAN DSKONFIGURASI KK ANTARA CDS DAN DS
PILOT CABLE
RTURTUMD 15
RTU
RTU
RTU
RTU
RTU
DF01
RTU
RTUDF
01COMPUTERMAIN
STANDBYCOMPUTER
COMPUTERMAIN
STANDBYCOMPUTER
DF01
DF01
DF01
EAST
EAST
WEST
WEST
REPEATER
MDS 2100KEY POINT
RAN 19
MD 50
MD 50
MD 50
RADIO DATA KONFIGURASI RADIO KOMUNIKASI DATA
KONFIGURASI RADIO KOMUNIKASI DATA
FIBER OPTIC
OPGW (Optical Fiber Ground Wire) ADSS (All Dielectric Self Supporting) GWWOP (Ground Wire Wrap Optical
Fiber)
POWER LINE CARRIER (PLC)Keterangan : 1. Line Trap2. Capacitor3. Pengaman4. Line Matching Unit (LMU)5. Perangkat HF6. Remote Terminal7. Panel Kontrol8. Rele Kendali9. Telephone10.Recorder11.Rangkaian Proses12.Terminal Telemeter
SOFTWARE SCADATEL
OPERATING SYSTEM :
Unix, Windows, Linux SOFTWARE APLIKASI :
Sinaut Spectrum, Spider, Wonderware Distribution Management System (DMS)
SOFTWARE APLIKASI SCADA
KONTROL AKUISISI DATA MANAJEMEN EVENT & ALARM KALKULASI TREND & PENGARSIPAN INTERFACE
TM (AI)
RC (AO)
TM (AI)
TELE INFORMASI DATA
Digital Input (DI) Digital Output (DO) Analog Input (AI) Analog Output (AO)
TSD (DI)
TM (AI)
RC (DO)
TSD (DI)
kV
kV
STATUS C / O
CONTROL C / O
PMS STATUS C / O
Busbar 1
PMT
Trafo
CT
PT
Busbar 2
Tap Changer
kV, A, MW, MX
OC / GF ALARM TSS (DI)
SISTEM POWER SUPPLY
CATUDAYAACDC
KATEGORIKONTINYU : MASTER STATION, RTUCADANGAN : AC, PENERANGANNORMAL
RECTIFIERRECTIFIER
Tegangan Out
Arus Out
Mode Operasi
Proteksi
Alarm
Jumlah Battery
Tegangan Nominal
Kapasitas
Jenis Battery
: 53,2V/55,1V
Adj
: 5, 8, 10, 16,
25 A
: Boost,Float
: Batas Arus
: Indikasi SF
: 38 Cell
: 1,2 Volt
: 11, 20, 60
Ah
: NiCd