skm systems analysis oc motor

Upload: seanchan

Post on 01-Jun-2018

228 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/9/2019 SKM Systems Analysis OC Motor

    1/11

    Frequently Asked Questions | Application Guides | Power System Study Specs | Tech Support | PT

    Chosen by 39 of the top 40 Electrical Engineering Firms in the world.

    1-8

    HOME PRODUCTS SUPPORT DOWNLOADS TRAINING CONTACT CUSTOMER SER

    Overcurrent Coordination Setting Guidelines Motors

    The information presented in this application guide is for review, approval, interpretation and application by a registered professional en

    and liability resulting from the use and interpretation of this information.

    Reproduction of this material is permitted provided proper acknowledgement is given to SKM Systems Analysis Inc.

    Introduction

    The proper selection and coordination of protective devices is mandated in article 110.10 of the National Electrical Code. To fulfill this re

    s required. The electrical engineer is always responsible for this analysis. It is an unfortunate fact of life that many times the engineer w

    will not set the devices. Therefore, compromises are inevitable.

    There are three fundamental objectives to overcurrent coordination that engineers should keep in mind while selecting and setting prote

    The first objective is life safety. Life safety requirements are met if protective devices are rated to carry and interrupt maximum ava

    and interrupt maximum available fault currents. Life safety requirements are never compromised.

    The second objective is equipment protection. Protection requirements are met if overcurrent devices are set above load operating l

    curves. Feeder and transformer damage curves are defined in applicable equipment standards. Motor and generator damage curves (p

    normally provided in the vendor data submittal package. Based on system operating and equipment sizing practices equipment protecti

    The last objective is selectivity. Selectivity requirements are met if in response to a system fault or overload, the minimum area of t

    service. Again, based on system operating and equipment selection practices selectivity is not always possible.

    Purpose

    The purpose of this guide is to provide overcurrent protective device setting guidelines for motors to meet the objectives listed above.

    MV Motor Switchgear Feeder Unit

    Industry standard overcurrent protection schemes for MV induction and synchronous motors fed from switchgear circuit breakers include

    50/51). The 50/51 relay characteristics are plotted on a phase time-current curve (TCC) along with the motor starting and damage curve

    The purpose of the 50/51 relay is to allow the motor to start and run, and to protect the motor and cable from overloads and faults. To a

    above and to the right of the motor starting curve, and to the left and below the rotor, stator and cable damage curves, and the amp rat

    Suggested margins are listed below that have historically allowed for safe operation of the motor and cable while reducing instances of n

    Device Function Recommendations Comments

    CT Size 125-150% of FLA

    51 Pickup 115-125% of FLA Set below motor stator damage

    Set at or below cable ampaci

    51 Time Dial2-10 seconds above knee of

    motor curveSet below motor rotor damage c

    Set below cable damage curv

    http://www.skm.com/applicationguides17.html

    11 9/5/2013 1:56 PM

  • 8/9/2019 SKM Systems Analysis OC Motor

    2/11

    50 Pickup 200% of LRA Set below cable damage curv

    Cable damage curve must be abo

    maximum fault current at 0.1 se

    Fig. 1 MV motor switchgear feeder unit - one line

    http://www.skm.com/applicationguides17.html

    11 9/5/2013 1:56 PM

  • 8/9/2019 SKM Systems Analysis OC Motor

    3/11

    Fig. 2 MV motor switchgear feeder unit - phase TCC

    MV Motor Fused Starter Feeder Unit

    Industry standard overcurrent protection schemes for MV induction and synchronous motors fed from fused starters include an overcurre

    fuses (device 50). R rated fuses melt at 100 times the R rating and 20 seconds. Both the fuse and relay characteristics are plotted on a p

    damage curves, and the feeder damage curve.

    The purpose of the fuse-relay combination is to allow the motor to start and run, and to protect the motor and cable from overloads and

    combined curve must be above and to the right of the motor starting curve, and to the left and below the rotor, stator and cable damag

    Suggested margins are listed below that have historically allowed for safe operation of the motor and cable while reducing instances of n

    Device Function Recommendations Comments

    CT Size 125-150% of FLA

    51 Pickup 115-125% of FLA Set below motor stator damage

    Set at or below cable ampaci

    51 Time Dial2-10 seconds above knee of

    motor curve Set below motor rotor damage c

    Set below cable damage curv

    50 Fuse Size RRating > 1.1*LRA/100 Set below cable damage curv

    AMPRating > FLACable damage curve must be abo

    maximum fault current at 0.01 se

    Fig. 3 MV motor fused starter feeder unit - one line

    http://www.skm.com/applicationguides17.html

    11 9/5/2013 1:56 PM

  • 8/9/2019 SKM Systems Analysis OC Motor

    4/11

    Fig. 4 MV motor fused starter feeder unit - phase TCC

    LV Motor Circuit Breaker Feeder Unit

    Industry standard phase overcurrent functions purchased with circuit breakers serving LV motors include long time pickup, long time del

    PCBs, ICCBs, MCCBs and TMCBs. Short time pickup and short time delay functions are not used. The CB characteristics are plotted on a

    curve and safe stall point, and the feeder damage curve.

    The purpose of the CB is to allow the motor to start and run, and to protect the motor and cable from overloads and faults. To accomplis

    the right of the motor starting curve, and to the left and below the motor safe stall point, cable damage curve and amp rating. Note it is

    amp rating due to breaker tolerances.

    Suggested margins are listed below that have historically allowed for safe operation of the motor and cable while reducing instances of n

    Device Function Recommendations Comments

    LV CB LTPU 125% of FLA Set at or below cable ampaci

    LV CB Time Dial2-10 seconds above knee of

    motor curveSet below motor safe stall poi

    http://www.skm.com/applicationguides17.html

    11 9/5/2013 1:56 PM

  • 8/9/2019 SKM Systems Analysis OC Motor

    5/11

    LV CB INST 200% of LRA Set below cable damage curv

    Cable damage curve must be above

    defined by the maximum fault curre

    PCB instantaneous clear curv

    Fig. 5 LV motor circuit breaker feeder unit - one line

    http://www.skm.com/applicationguides17.html

    11 9/5/2013 1:56 PM

  • 8/9/2019 SKM Systems Analysis OC Motor

    6/11

    Fig. 6 LV motor power circuit breaker feeder unit - phase TCC

    LV Motor MCP Starter Feeder Unit

    Industry standard phase overcurrent protection is provided in MCP starter units by two discrete components, a thermal overload relay an

    s a circuit breaker with the thermal element removed. The overload and MCP characteristics are plotted on a phase TCC along with the

    the feeder damage curve.

    The purpose of the overload-MCP combination is to allow the motor to start and run, and to protect the motor and cable from overloads

    overload-MCP combined curve should be above and to the right of the motor starting curve, and to the left and below the motor safe sta

    rating. Note it is not always possible to be below the cable amp rating due to overload tolerances.

    Suggested margins are listed below that have historically allowed for safe operation of the motor and cable while reducing instances of n

    Device Function Recommendations Comments

    OL Pickup125% of FLA if SF > 1.15

    115% of FLA if SF = 1.00Set at or below cable ampaci

    OL Time Dial Fixed assume Class 20 Set below motor safe stall poi

    http://www.skm.com/applicationguides17.html

    11 9/5/2013 1:56 PM

  • 8/9/2019 SKM Systems Analysis OC Motor

    7/11

  • 8/9/2019 SKM Systems Analysis OC Motor

    8/11

    Fig. 8 LV motor MCP starter feeder unit - phase TCC

    LV Motor Fused Starter Feeder Unit

    Industry standard phase overcurrent protection is provided in fused starter units by two discrete components, a thermal overload relay a

    characteristics are plotted on a phase TCC along with the motor starting curve and safe stall point, and the feeder damage curve.

    The purpose of the overload-fuse combination is to allow the motor to start and run, and to protect the motor and cable from overloads

    overload-fuse combined curve should be above and to the right of the motor starting curve, and to the left and below the motor safe sta

    rating. Note it is not always possible to be below the cable amp rating due to overload tolerances.

    Suggested margins are listed below that have historically allowed for safe operation of the motor and cable while reducing instances of n

    Device Function Recommendations Comments

    OL Pickup125% of FLA if SF > 1.15

    115% of FLA if SF = 1.00Set at or below cable ampaci

    OL Time Dial Fixed assume Class 20 Set below motor safe stall poi

    Fuse Size 175% of FLA Set below cable damage curv

    http://www.skm.com/applicationguides17.html

    11 9/5/2013 1:56 PM

  • 8/9/2019 SKM Systems Analysis OC Motor

    9/11

    Cable damage curve must be above

    defined by the maximum fault curren

    seconds

    Fig. 9 LV motor fused starter feeder unit - one line

    http://www.skm.com/applicationguides17.html

    11 9/5/2013 1:56 PM

  • 8/9/2019 SKM Systems Analysis OC Motor

    10/11

    Fig. 10 LV motor fused starter feeder unit - phase TCC

    References

    Other Application Guides offered by SKM Systems Analysis at www.skm.com Electrical Transmission and Distribution Reference Book, ABB Power T&D Company, Raleigh, North Carolina, 1997

    Protective Relaying Theory and Applications, 2nd Edition, Marcel Dekker, New York, 2004

    The latest revision of:

    IEEE Std 242, IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems (IEEE Buff

    IEEE Std 620, IEEE Guide for the Presentation of Thermal Limit Curve for Squirrel Cage Induction Machines

    IEEE Std C37.96, IEEE Guide for AC Motor Protection

    NEMA MG-1, Motors and Generators

    back to Application guides

    http://www.skm.com/applicationguides17.html

    f 11 9/5/2013 1:56 PM

  • 8/9/2019 SKM Systems Analysis OC Motor

    11/11

    Home Products Support Downloads Training Contact Customer Service Career Opportun

    Copyright 2012. SKM Systems Analysis Inc. All rights reserved.

    http://www.skm.com/applicationguides17.html