SM6 trainingSM6 trainingfor Schneider Electric SEA for Schneider Electric SEA 20042004

Building a New Electric World

Page 2: SM6 Training Material 2004

2

SM6

MV Metal enclosed cubicle up to 24 kV

Aplication: Secondary distributionLow Isc level (<20kA/1s)

Type of cubicles:Switch and fuse switchCircuit Breaker (Incoming,Outgoing and Coupler) fixed and draw outDirect incomer or outgoerBusbar metering (CM, GBC-A/B)Other functional (interface VM6, Aux power,intermediate,etc)

Page 3: SM6 Training Material 2004

3

SM6MV Metal enclosed Switch cubicle up to 24 kV

Switch Cubicle:Load break switch ( IM)Off load switch (SM)Load break switch with CT (IMC)Fuse load break switch (QM)Fuse Off load swicth (CM, TM)

Max voltage : 24 kV Isc max (24kV) : max 20kA/1s (basic housing) Rating: 630A and 400A BIL : 125 kV earthing switch VPIS on cable side

Page 4: SM6 Training Material 2004

4

SM6MV Metal enclosed Switch cubicle up to 24 kV

Switch Cubicle:

Page 5: SM6 Training Material 2004

5

SM6MV Metal enclosed Switch cubicle up to 24 kV

Switch :Switch : rating current : 630A and 400 ASF6 with pressure : 0.4 bar relatif pressureSealed pressure systemEarthing switchSwitch disconnectorSafety membrane

Busbar :rating current : 630A and 1250 ARating voltage : 7.2kV, 12kV, 17.5kV, 24kV Insulated busbar Isc : 20kA/1s maxCover with field distributorsConnection in horizontal planeEasy for manintenance

Page 6: SM6 Training Material 2004

6

SM6MV Metal enclosed cubicle up to 24 kV

CB Cubicle:Fixed type (DM1A)Withdrawable type (DM1 W)Coupling type (DM2)Semi withdrawable type (DM1A +)

Max voltage : 24 kV Isc max (24kV) : max 20kA/1s (basic housing Rating: 630A and 1250A (I BC= 16kA(std), 20kA max) BIL : 125 kV earthing switch VPIS on cable side

Page 7: SM6 Training Material 2004

7

SM6MV Metal enclosed CB cubicle up to 24 kVCB Cubicle:

6. CT and VT

6

Page 8: SM6 Training Material 2004

8

SM6MV Metal enclosed CB cubicle up to 24 kV

CB :CB : rating current : 400A, 630A and 1250 ASF6 with pressure : 0.5 bar relatif pressure (no vacuum version at the moment until 2005 or beg 2006)Sealed for life, no pressure switchEarthing switchSwitch disconnectorSafety membrane

Switch disconnector & ES: Isolate the CB from main busbarEarthed the CB compartment

Main Busbar :Same as Switch cubucle

Page 9: SM6 Training Material 2004

9

SM6MV Metal enclosed CB cubicle up to 24 kV

CB : (630A - Isc 25kA/3s – for Singapore market)CB : rating current : 630A (using 1250A CB)LMK Type Tested Main Busbar 630A (using busbar 1250A to increase mech strength)Earthing switch 20 kASwitch disconnector using 1250A Incoming feeder without ES, outgoing feeder with ES Incoming CT with class X for Solkor relay

Metering Cubicle:CT with protection classVT with primary fuseDoor interlock with incoming feederCT for metering inside bottom pan

Page 10: SM6 Training Material 2004

10

SM6 General Characteristic:

Page 11: SM6 Training Material 2004

11

SM6 General Characteristic:

Page 12: SM6 Training Material 2004

12

SM6MV Metal enclosed Switch cubicle up to 24 kV

Switch cubicle:

Page 13: SM6 Training Material 2004

13

SM6MV Metal enclosed Switch cubicle up to 24 kV

Fuse Switch cubicle:

375/500 375/500375/500

750

Page 14: SM6 Training Material 2004

14

SM6MV Metal enclosed Switch cubicle up to 24 kV

CB cubicle:

Page 15: SM6 Training Material 2004

15

SM6MV Metal enclosed Switch cubicle up to 24 kV

CB cubicle:

Page 16: SM6 Training Material 2004

16

SM6MV Metal enclosed Switch cubicle up to 24 kV

ATS cubicle:NSM

Page 17: SM6 Training Material 2004

17

SM6MV Metal enclosed Switch cubicle up to 24 kV

Metering cubicle:

Page 18: SM6 Training Material 2004

18

SM6MV Metal enclosed Switch cubicle up to 24 kV

All functions cubicle:

Page 19: SM6 Training Material 2004

19

SM6MV Metal enclosed switch cubicle up to 24kVSwitch Operating mechanism :

Page 20: SM6 Training Material 2004

20

SM6MV Metal enclosed switch cubicle up to 24kVMotorized optional for switch unit :

Page 21: SM6 Training Material 2004

21

SM6MV Metal enclosed CB switch cubicle up to 24kVMotorized optional for switch unit :

Option:• operation counter• opening release: Shunt trip, mitop & under voltage• closing release: shunt trip• Mechanism charge indication: 1C

Aux contact of CB : 4NO + 4 NC

Page 22: SM6 Training Material 2004

22

SM6MV Metal enclosed CB cubicle up to 24kVLow Volatge compartment:

There are 2 LV compartment in SM6 cubicle:a. Front LV compartment (open with screw) (A)b. LV box compartment at the top of cubicle (with handle and key

lock) (B or C)

Page 23: SM6 Training Material 2004

23

SM6MV Metal enclosedSM6 cubicle up to 24kVCTs:CT for IMC cubicle:

CT for QMC cubicle:

Page 24: SM6 Training Material 2004

24

SM6MV Metal enclosedSM6 cubicle up to 24kVCTs:CT for CB cubicle: (DM1A,DM1W,DM1D,DM2, GBC-A,GBC-B)

Page 25: SM6 Training Material 2004

25

SM6MV Metal enclosedSM6 cubicle up to 24kVVTs:VT for cubicles: CM, DM1A,DM1W,DM2, DM1D, GBC-A,GBC-BVT: Phase to ground (wye-wye connection)Grounding and Ungrounding network system (VT selection)Up to 22kV/V3

Page 26: SM6 Training Material 2004

26

SM6MV Metal enclosedSM6 cubicle up to 24kVVTs:VT for cubicles: CM2, GBC-A,GBC-BVT: Phase to Phase (open delta connection)Up to 22kV/V3

Page 27: SM6 Training Material 2004

27

SM6MV Metal enclosedSM6 cubicle up to 24kVVTs:VT for cubicles: TMVT: Phase to Phase (Single phase transformer)Up to 22kV/V3Use for aux power supply 230VAC(max 2500VA/4000VA)

Page 28: SM6 Training Material 2004

28

SM6MV Metal enclosedSM6 cubicle up to 24kV

Surge Arrestor:Can be installed in cubicle: IM500, DM1A, DM1W,GAMSurge Arrestor in IM cubile to protect cable sideSurge Arrestor in GAM cubicle to protect busbar and cable sideSurge Arrestor in DM1A, DM1W cubicle to protect cable sideSurge arrestor 24kV – 10kA (Elina or ABB-MWK 24)

Page 29: SM6 Training Material 2004

29

SM6MV Metal enclosedSM6 cubicle up to 24kVTransformer Fuse Protection: (QM,QMC) Fuse must be selected as per table below Type of fuse: Fusarc(DIN size) and Solefuse(French Standard) In Cikarang : <=63A solefuse, >63A Fusarc Ambiant temperature max: 40 deg C

Page 30: SM6 Training Material 2004

30

SM6MV Metal enclosed SM6 cubicle up to 24kVProtection:Using Sepam 1000+ series (S20,T20,M20,B21,B22)

With external power supply (DC:24,48,110V or AC:230V)Using VIP relay integrated in DM1-S with 3 CR sensor current

No need external power supply.(internal power)Tripping release: mitop VIP 35 OCR (DT) + EFR (IT)VIP 300LL OCR(IT,VIT,EVIT)

Using SF set CB: VIP 200 or 201Dedicated for transformer protectionNo need external power supplyProtection against Over Current and Earth Fault

Using Statimax or Sepam 100LAUsing regular CT (I sec: 5A or 1 A)No need external power supplyProtection against Over Current(DT) and Earth Fault (DT)Tripping release : mitop

Page 31: SM6 Training Material 2004

31

SM6MV Metal enclosed SM6 cubicle up to 24kVProtection:

Page 32: SM6 Training Material 2004

32

SM6MV Metal enclosed SM6 cubicle up to 24kVSource Change Over : NSM Cubicle.Consist of 2 Incmoing switchMechanically interlock (as standard offer)No need VT to sensing the voltage (voltage sensor by using

capacitive voltage devider) Including DC power supply 24VDC (need aux supply 230VAC) Switch with motorized operation.Switch Rated current : 630A/switch 24kVChange over controller : RCV420 and RNS 11With Earthing switch (at both cable side)With neon indicator (at both side)Main busbar 630A or 1250A

Note: RCV 420 for Stand by power RNS 11 for Emergency power (Genset)

Page 33: SM6 Training Material 2004

33

SM6 NSM with RCV 420

Page 34: SM6 Training Material 2004

34

SM6 NSM with RNS 411

Page 35: SM6 Training Material 2004

35

SM6INTERLOCKING Interlocking is provided by key lock Comply with IEC recomendation 60298 and EDF spec HN 64-S-41 Built in padlocking fasilities (padlocks not supplied) For knock outs that may be used for key locks(supplied on request) for mechnism

locking functions.

Page 36: SM6 Training Material 2004

36

SM6INTERLOCKING

Page 37: SM6 Training Material 2004

37

SM6INTERLOCKING

Page 38: SM6 Training Material 2004

38

SM6Key Type Interlock:

Page 39: SM6 Training Material 2004

39

SM6Key Type Interlock:

Page 40: SM6 Training Material 2004

40

SM6Key Type Interlock:

Page 41: SM6 Training Material 2004

41

SM6MV Metal enclosed CB cubicle up to 24kVCable connection:Bottom entry (as standard)

Page 42: SM6 Training Material 2004

42

SM6MV Metal enclosed CB cubicle up to 24kVCable connection:Connection height: Switch and Fuse switch

Page 43: SM6 Training Material 2004

43

SM6MV Metal enclosed CB cubicle up to 24kVCable connection:Connection height: DM1 and GAM

Page 44: SM6 Training Material 2004

44

SM6MV Metal enclosed SM6 cubicle up to 24kVCable connection from above:(Incoming from top,outgoing from bottom)

TOP Incoming:Dry type and 1c cablesNo LV box in the unit.VPIS for incoming voltage monitor

Page 45: SM6 Training Material 2004

45

SM6MV Metal enclosed SM6 cubicle up to 24kVDimension and weight:

Page 46: SM6 Training Material 2004

46

SM6MV Metal enclosed SM6 cubicle up to 24kVApplication:

Page 47: SM6 Training Material 2004

47

SM6MV Metal enclosed SM6 cubicle up to 24kVApplication:Below schematic diagram is applicable if:

Power cable at incoming side still energized when open the Incoming CB door Metering CT and VT located in seperate cubicle with seal fasility

GBC-A(s) DM1-D GBM DM1-A DM1-A DM1-A

CB CB CB CB

Page 48: SM6 Training Material 2004

48

SM6 Semi withdrawable (alternative offer)

Using DM1-A cubicle Change CB control wiring from terminal to control plug (same as

withdrawable type) Easy to remove the CB during maintenance or repair No wrong connection for control CB after maintenance Save time for operating the CB Alternative offer instead of DM1-W Price + 3 % DM1-A control

plug in

bolt same as DM1-A

Page 49: SM6 Training Material 2004

49

SM6

THANK YOU FOR YOUR ATTENTION