Page 1: Smartpack New

June 2006

Page 2: Smartpack New

2

Eltek

Scaleable and flexible control module for the entire Eltek product range

Page 3: Smartpack New

3

Eltek

Small but powerfulSmall but powerful

44mm

109 mm

144 mm

< 300g

Page 4: Smartpack New

4

Eltek

”Traffic Light”LEDs

Front PanelStandardFront PanelStandard

2x16 character display

3 button Keypad

USB Port

CAN Bus IDDIP switches

Page 5: Smartpack New

5

Eltek

Rear PanelCAN BusRear PanelCAN Bus

CAN bus

Part No : 242100.110(RoHS compliant)

120 ohm term. required at each end

ID based serial bus communications

Max 8 Smartpack

Max 50 Rectifiers

Page 6: Smartpack New

6

Eltek

Rear PanelBattery MonitoringRear PanelBattery Monitoring

Battery Monitoring

Part No : 242100.110(RoHS compliant)

Con 4 : StandardCon 3 : Extended

• Symmetry measurement

• 8 strings mid point or2 strings 12V block

• Temp sense

Page 7: Smartpack New

7

Eltek

Rear PanelInternal SystemRear PanelInternal System

Internal System

Part No : 242100.110(RoHS compliant)

System measurements

Unit Power

2xLVD control (Latched)

Battery fuse fail

Page 8: Smartpack New

8

Eltek

Rear PanelAlarm I/ORear PanelAlarm I/O

Alarm I/O

Part No : 242100.110(RoHS compliant)

Con 1 (standard):-

2 + 2 relay input / output

Con 2 (extended):-

4 + 4 relay input / output

Page 9: Smartpack New

9

Eltek

RS-232 OptionRS-232 Option

RS-232 mounted

Part No : 242100.111(RoHS compliant)

•Enables connection of Standalone Webpower or modem

•Rear position : Replaces extended Battery symmetry card

Part No : 242100.112(RoHS compliant)

Page 10: Smartpack New

10

Eltek

1. Remove 4 chassis screws2. Remove top D-Sub fixings (CON 2 & 3).3. Lift top cover from the front.(Re-assemble in reverse order)

Opening the SmartpackOpening the Smartpack

Page 11: Smartpack New

11

Eltek

Rear PanelEmbedded WebpowerRear PanelEmbedded Webpower

Embedded

WebPower

Part No : 242100.113(RoHS compliant)

Ethernet interface of remote monitoring of SmartpackIs possible to “tunnel” Powersuite remotely also.

Page 12: Smartpack New

12

Eltek

FunctionalityFunctionality

Battery monitoring and testing

Temperature compensated charging

Battery lifetime indication

Alarm/event log (1000) with time and date

And much more ….

Page 13: Smartpack New

13

Eltek

ScalabilityScalability

Smartpack MasterSmartpack Slave n

System functionalityVoltage input 1

Symmetry inputs 8 (2x4x12V)

Current inputs 2

Temperature inputs 2

General purpose inputs 6

Load fuse input 1

Batt fuse input 2

Relay outputs 6

Contactor control 2+

System functionalityVoltage inputs 2

Symmetry inputs 16 (4x4x12V)

Current inputs 4

Temperature inputs 4

General purpose inputs 12

Load fuse input 2

Batt fuse input 4

Relay outputs 12

Contactor control 4+

System functionality with 8 modulesVoltage inputs 8

Symmetry inputs 64 (16x4x12V)

Current inputs 2x8

Temperature inputs 2x8

General purpose inputs 6x8

Load fuse input 1x8

Batt fuse input 2x8

Relay outputs 6x8

Contactor control 2+x8

Smartpack Slave 1

CAN/Power bus

Page 14: Smartpack New

14

Eltek

ConnectivityBatteryConnectivityBattery

CON3 & CON4 – Battery Connections

Temp SenseCable

Pin Function

1 Symmetry I/P 1

2 Symmetry I/P 2

3 Symmetry I/P 3

4 Symmetry I/P 4

5 Symmetry I/P 5

6 Symmetry I/P 6

7 Symmetry I/P 7

8 Symmetry I/P 8

9-10 Con 3 : Temp sense 2Con 4 : Temp sense 1

11 - 14 Con 3 – 2nd batt current, batt fuseCon 4 : Not used

Page 15: Smartpack New

15

Eltek

Symmetry measurement options

ConnectivitySymmetryConnectivitySymmetry

Page 16: Smartpack New

16

Eltek

ConnectivitySystemConnectivitySystem

CON5 – System ConnectionsPin Function

1 Positive Input

2 Negative Input

3 Batt Current +ve

4 Batt Current -ve

5 Batt Fuse +ve

6 Batt Fuse -ve

7 Load Fuse Fail

8 LVD1 Active

9 LVD1 Common

10 LVD2 Active

11 LVD2 CommonSystem Connection Card. Art 200625

Page 17: Smartpack New

17

Eltek

ConnectivitySystemConnectivitySystem

System card configuration

JP1-48v system = 1-2 +24v system = 2-3

JP2-48v system = ‘Neg’+24v system = ‘Pos’

Page 18: Smartpack New

18

Eltek

Connectivity Latched ContactorsConnectivity Latched Contactors

A latching contactor changes state only when a reversed pulse voltage is applied to the coil.

Protection Diode

Page 19: Smartpack New

19

Eltek

ConnectivityExternal Alarm I/OConnectivityExternal Alarm I/O

CON1 & CON2 – I/O Connections

Pin Function

1 - 2 Alarm input 1 ( + / -)

3 – 4 Alarm input 2 ( + / -)

5 - 7 Alarm output 1 ( NO /C / NC)

8 - 10 Alarm output 2 ( NO /C / NC)

1 - 2 Alarm input 3 ( + / -)

3 - 4 Alarm input 4 ( + / -)

5 - 6 Alarm input 5 ( + / -)

7 - 8 Alarm input 6 ( + / -)

9 - 11 Alarm output 3 ( NO /C / NC)

12 - 14 Alarm output 4 ( NO /C / NC)

15 - 17 Alarm output 5 ( NO /C / NC)

18 - 20 Alarm output 6 ( NO /C / NC)Alarm Output & Input Card

Art 105954

Page 20: Smartpack New

20

Eltek

Smartpack Extended Master Smartnode

CAN/Power bus Customer equipment

Convert PCOMM to Customer specific Protocol

Part no: 242100.200

Communicating with Smartpack on CAN bus

RS232 and RS485 serial interface as standard

SmartnodeSmartnode

Customer bus (RS 485)

Smartpack has only PCOMM protocol

Page 21: Smartpack New

21

Eltek

PowerSuitePowerSuite

Explorer oriented easy to use PC SW

USB gives simple access.

Wide functionality with clear graphic presentation.

Page 22: Smartpack New

22

Eltek

PowerSuitePowerSuite

Live Demo

Page 23: Smartpack New

29

Eltek

End of PresentationEnd of Presentation

Let’s us know if you found this presentation useful or would like more information.

Eltek values your feedback.

Thank you

[email protected]