Smoke ventilation in common areas of single stair residential

buildings

Some on-going issues and analysis Stewart Miles

International Fire Consultants

The study and results reported are part on-going, personal academic work, and do not necessarily represent the views of any organisation

1

Page 2: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke control in common areas

• Compartmentation is most important element

• Suppression may be significant

• Ventilation generally also required• Can assist means of escape

• Can assist fire service operations

2

Page 3: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke ventilation in single stair buildings

• To help protect stair enclosure• Limit smoke ingress before fire service arrival and during firefighting

• Where there are ‘extended’ corridor travel distances • Purge smoke that enters corridor prior to fire service arrival

• Reduce severity of conditions in corridor during firefighting

3

Page 4: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Current ventilation practice

• Natural ventilation from corridor; or

• Mechanical extract ventilation from corridor• Sometimes augmented with mechanical supply too

• Or sometimes open vents for inlet air

• Open vent at top of stair enclosure (with either of above)

• Air supply / pressurisation in stair enclosure not common

4

Page 5: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Some concerns

• Fire sizes considered are generally restricted to fuel-bed limited condition• i.e. contained fuel area and associated heat release rate

• But, can post-flashover fires actually be more severe?• (and take smoke ventilation system beyond designed capability?)

• Can too much depressurisation in the corridor lead to hazards that are not generally considered?• e.g. smoke drawn under door threshold

• Propensity for ‘backdraught’ conditions during firefighting?

5

Page 6: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Building geometry modelled

6

Page 7: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Apartment and common corridor

7

Page 8: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke ventilation methods analysed

• External wall AOV in corridor• (plus top of stair AOV)

8

Page 9: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke ventilation methods analysed

• Natural smoke shaft to corridor• (plus top of stair AOV)

9

Page 10: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke ventilation methods analysed

• Mechanical extract from corridor• (plus top of stair AOV)

10

Page 11: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke ventilation methods analysed

• Mechanical ‘push/pull’ in corridor• supply & extract in corridor

• (plus top of stair AOV)

11

Page 12: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke ventilation methods analysed

• Mechanical supply to stair• Fresh air into stair

• Pressure-relief damper

• (top of stair AOV omitted)

12

Page 13: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke ventilation methods analysed

• Mechanical supply to stair, plus either:

• External wall AOV in corridor, or

• Mechanical ‘push/pull’ in corridor

13

Page 14: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Post-flashover fire scenario

• Steady-state condition

• Fire distributed across whole floor

• Assume:• Hot gas layer at 800°C & emissivity ~1

• Fuel heat of gasification = 4 000 kJ kg-1

• (ranges from 1 000 to 5000 kJ kg-1 for most fuels)

• Heat of combustion = 20 000 kJ kg-1

• Then• Energy (heat) release rate associated with fuel pyrolysis = 375 kW m-2

• (would be higher if lower heat of gasification adopted)

14

Page 15: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Post-flashover fire scenario

• Fire spread across entire floor area in room of origin• 24m2 → 9 MW heat release

• (assuming all fuel combusts)

• Window/vent 3m by 1.4m• From empirical correlation ~7.5MW

heat release rate can be supported within room• (excess fuel can combust in flames

outside window)

15

Page 16: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Illustration of fire from CFD model

16

Page 17: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Illustration of fire from CFD model

17

Page 18: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Comparison with a real fire

• Flame and smoke dynamics similar to the CFD model

18

Page 19: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Illustration of fire from CFD model – apartment door open

19

Page 20: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Modelling using Fire Dynamics Simulator

• 10cm mesh throughout

• Eddy dissipation combustion• Heat combustion 20 000 kJ kg-1

• 10% soot yield

• ‘Finite volume’ ray-tracing radiation model• 100 rays

• Grey gas absorption sub-model

• 0.35 radiative fraction (from combustion process)

• HVAC sub-model• For mechanical supply & extract boundary conditions

20

Page 21: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Simulations (scenarios) at fire service intervention stage

• Steady (post-flashover) fire source

• Ventilation system running

• Apartment door open

• Stair door (on fire floor) open to 20° angle

• Stair bottom (entrance) door open

• Simulations conducted for two to three minutes or until quasi-steady state reached

21

Page 22: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Simulations (scenarios) prior to fire service arrival

• Steady (post-flashover) fire source

• Ventilation system running

• Apartment door closed• 3mm threshold gap modelled using FDS ‘leak vent’ capability

• Stair door (on fire floor) closed • Unless ‘pulled-open’ as part of ventilation operation

• Stair bottom (entrance) door open

• Simulations conducted for two to three minutes or until quasi-steady state reached

22

Page 23: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• No corridor ventilation

23

Page 24: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• ADB corridor AOV• ~1m2 aerodynamic free area

• (equivalent to 1.5m2 unobstructed rectangular opening)

24

Page 25: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• ADB natural smoke shaft

25

Page 26: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• Mechanical extract at 2 m3s-1

26

Page 27: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• Mechanical extract at 4 m3s-1

27

Page 28: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• Mechanical extract at 6 m3s-1

28

Page 29: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• Mechanical ‘push/pull’ at 2 m3s-1

29

Page 30: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• Stair supply at 2 m3s-1

• No vent in corridor

30

Page 31: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• Stair supply at 2 m3s-1

• Wall vent in corridor

31

Page 32: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• Stair supply at 4 m3s-1

• No vent in corridor

32

Page 33: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• Stair supply at 4 m3s-1

• Wall vent in corridor

33

Page 34: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• Mechanical ‘push/pull’ at 2 m3s-1

• Stair supply at 2 m3s-1

34

Page 35: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport at firefighting stage

• Mechanical ‘push/pull’ at 2 m3s-1

• Stair supply at 4 m3s-1

35

Page 36: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport prior to fire service arrival

• Mechanical ‘push/pull’ at 2 m3s-1

36

Page 37: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport prior to fire service arrival

• Low level mechanical extract • Air leakage into corridor

37

Page 38: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Smoke transport prior to fire service arrival

• Mechanical extract at 2 m3s-1

• ‘Reverse-hung’ stair door part-opening at ~10Pa

38

Page 39: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

To conclude

• Various issues relating to smoke ventilation in residential buildings warrants further investigation

• Impact of post-flashover apartment fires

• Potential for smoke and fie gases to be drawn into the corridor

• Possible benefit of supplying air mechanically into the stair is being missed

• For ‘extended corridors’ a combination of mechanical corridor smoke clearance (e.g. ‘push/pull’) and mechanical air supply into the stair may prove productive

• Work reported is very much ‘work in progress’ open for discussion

39

Page 40: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles

Thank you for your attention