soft-optimized system test of r410a, dr-55, r32, and dr-5a ... · soft-optimized system test of...

35
Soft - Optimized System Test of R410A , DR - 55 , R32 , and DR - 5A in a 4 - RT Unitary Rooftop Heat Pump Ken Schultz Principle Research Engineer La Crosse, WI

Upload: others

Post on 25-Sep-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump

Ken SchultzPrinciple Research Engineer

La Crosse, WI

Page 2: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

2Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Equipment Used

Precedent Rooftop Heat Pump

o48,500 Btu/hr @ 11.0 EERC

o44,000 Btu/hr @ 3.40 COPH

oAlliance scroll compressor‒ Emkarate RL32H POE oil

‒ TR200 P5K5 VFD installed

‒ Power measurements made upstream of VFD.

‒ η ~ 0.97 (varies little over range of speeds and loads encountered)

oFixed TXVs replaced w/adjustable TXVs of the same size

Replaced outdoor coil before testing began.

See supplementary slides at end of deck for more details.

oTested in Controlled Ambient Chambers

oWell instrumented

‒ Air-side & Refrigerant-side

Page 3: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

3Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Refrigerants Selected

name R32 R125 R1234yf

R410A 50% 50%

DR-55 67% 7% 26%

R32 100%

DR-5A 68.9% 31.1%

name GWP(AR4)

GWP(AR5)

R410A 2088 1924

DR-55 698 675

R32 675 677

DR-5A 466 466Refrigerant properties used are consistent with NIST REFPROP v9.1 with mixture interaction parameters supplied by DuPont (now Chemours).

Page 4: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

4Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Tests Conducted

Followed AHRI Standard 210/240 (2012) …

Additional tests in cooling mode

ooutdoor temperature sweep‒ 65F .. 125F in 10Fd inc’s

‒ 80F/67F ent indoor coil

‒ included in Report #56

ovary indoor conditions‒ 80/67, 75/63, 70/58.5

(DB/WB in F) (~50%RH)

‒ 82F outdoor (B condition)

‒ new data taken after Report #56 was submitted

o check for fractionation and leak/recharge behavior (new)

Page 5: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

5Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Test Procedure

Baseline tests w/R410A

oRefrigerant charge sweep at “A” conditions w/VFD @ 60 Hz‒ Maximum EER was near catalog charge of 9.0 lbm.

‒ Superheat at compressor suction was determined to be ~13Fd.

‒ Subcooling leaving condenser was determined to be ~15Fd.

Tests with alternative refrigerants

oRefrigerant charge sweep at “A” conditions w/VFD @ 60 Hz‒ Adjusted TXV to match R410A suction superheat.

‒ Selected refrigerant charge that maximized EER (and coincidentally

closely matched R410A subcooling).

oAdjusted VFD/compressor speed to match R410A capacity at “A” conditions.

Used the selected charge, TXV setting, and VFD frequency for all other test points (both cooling and heating).

Page 6: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

6Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results

Settings

Refrig# of runs

Charge (lbm)

TXV(turns)

VFD (Hz)

CAPwrt

R410AEER

wrt R410A

R410A 5 9.0 0 60 50,241 – 11.32 –DR-55 5 8.2 1 CW 60 50,213 0.1% 11.81 4.3%R32 4 7.25 3 CW 55 50,637 0.9% 11.98 5.8%DR-5A 1 8.2 3 CW 61 50,627 0.8% 11.84 4.6%CW is clockwise (in/closed), CAP is Capacity in BTU/hr, EER is in BTU/W·hr

Refrigerant charge, TXV position, and compressor speed selected for each refrigerant, along with the average capacity and EER obtained at the “A” point for each.

−9%

−19% −8%

+1.7%−9%

Page 7: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

7Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Repeatability

Capacity at “A” was repeatable within ±1%..±2%

Efficiency was repeatable within ±1%..±2%

Page 8: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

8Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

“A” conditions (95F ambient)

Capacities closely matched by selection

of VFD speed.

ave of 5 5 4 1 runs

Page 9: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

9Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

“A” conditions (95F ambient)

Alternatives gave higher efficiencies

by 4.5% to 6%.

ave of 5 5 4 1 runs

Page 10: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

10Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

“A” conditions (95F ambient)

Latent capacities follow total capacities.

Page 11: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

11Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

“A” conditions (95F ambient)

Compressor Discharge Temperature (CDT)

• DR-55 and DR-5A have modest ↑.

• R32 has larger ↑.

ave of 5 5 4 1 runs

See supplementary slides at end of deck for results at the B, C, and D conditions.

Page 12: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

12Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

Outdoor Temperature Sweep to High Ambient

o Sensitivity of capacity to Tamb is slightly lower for the alternatives than for R410A.

Page 13: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

13Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

Outdoor Temperature Sweep to High Ambient

oCompressor power is more sensitive to Tamb for R32 than for others. Compressor power is 4% to 5% lower than R410A for DR-55 and DR-5A over Tamb range.

Page 14: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

14Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

Outdoor Temperature Sweep to High Ambient

o Sensitivity of efficiency to Tamb is slightly lower for the alternatives than for R410A. R32 EER tailing off at high Tambbecause of increasing power draw.

Page 15: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

15Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

Outdoor Temperature Sweep to High Ambient (2)

oCompressor discharge temperatures

oR32 reached max CDT at Tamb ~ 120F

DR-55 & DR-5A:+6..+12Fd over R410A

R32:+20..+45Fd over R410A

Page 16: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

16Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Heating Mode

H1 – 47F/43F H3 – 17F/15F

Small reductions in heating mode capacity when match capacity at cooling “A” conditions.

Page 17: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

17Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Heating Mode

H1 – 47F/43F H3 – 17F/15F

Equal or small increases in heating mode efficiency when match capacity at cooling “A” conditions.

Page 18: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

18Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Heating Mode

H2 – 35F/33F Cyclic Defrost Test

o More variability between repeat runs –±10%.

o Significant differences between refrigerants.

‒ R32 performed exceptionally well – very short defrost periods.

‒ Based on other results, expect similar behavior for this condition as well.

o Outdoor coil temperature measurement (entrance to bottom circuit) not consistent between refrigerants.

See supplementary slides at end of deck for more details.

Not understood at this time – needs further study.

Page 19: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

19Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Leak/Recharge w/DR-55

oPulled refrig samples from subcooled liquid line while running.

o “Leaked” vapor from compressor discharge line while running.‒ ~2 lbm of refrigerant “leaked” each time. (8.2 lbm full charge)

‒ Subcooling ~ 14Fd..16Fd with “full” charge, ~ 2Fd..4Fd after each “leak”.

oCompositions measured after each “leak/recharge” cycle.

oCapacity drops 3% to 5% after “leaking” 2 lbm. Capacity returns to within 1% of starting point after recharge.

oEfficiency drops 0.5% to 2% after “leaking” 2 lbm. Efficiency returns to within 0.5% of starting point after recharge.

oCirculating composition matched composition charged to unit within ±0.5% ⇒ little fractionation while running.

‒ Circulating composition changed very little (<0.5%) over the course of four leak/recharge events (all while unit was running).

See supplementary slides at end of deck for more details.

Page 20: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

20Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Conclusions

Soft-optimized tests conducted on 4-RT RTU Heat Pump with R410A, DR-55, R32, and DR-5A.‒ Adjusted TXVs to match compressor suction superheat obtained

w/R410A.

‒ Selected charge to maximize EER @ “A” (essentially matching subcooling w/R410A.)

oMatched capacities @ “A” to R410A baseline by adjusting compressor speed.‒ DR-55 and DR-5A required no/little adjustment to compressor

displacement.

‒ R32 required an 8% reduction in compressor displacement to match heat exchanger capacities.

Page 21: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

21Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Conclusions (2)

All three alternatives performed similarly wrt capacities and efficiencies at the various rating points.

oCapacities were within −4% to +1% of R410A baseline (matching at “A”).

oEfficiencies ran −1% to +6% compared to R410A baseline (+4% to +6% at “A”).

oAll three alternatives were slightly less sensitive to variations in ambient temperature resulting in somewhat higher capacities and efficiencies at high ambient temperatures compared to R410A.

Page 22: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

22Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Conclusions (3)

Difference in compressor discharge temperatures.

oDR-55 and DR-5A produced CDTs only ~10Fd higher than R410A.

oR32’s CDTs ran ~20Fd higher than R410A at normal rating conditions and up to 40Fd hotter at 120F ambient temperature, reaching the maximum operating temperature.

Page 23: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

23Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

SUPPLEMENTARY MATERIAL

Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump

Page 24: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

24Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Equipment Used

Precedent Rooftop Heat Pump – WSC048E3

o AHRI Check-Test Unit

o 48,500 Btu/hr @ 11.0 EERC

o 44,000 Btu/hr @ 3.40 COPH

o Alliance scroll compressor, SXA044B2BPA

‒ 2.56 in³/rev = 311 ft³/min @ 60 Hz input → 3500 RPM

‒ Emkarate RL32H POE oil

‒ TR200 P5K5 VFD installed

‒ Power measurements made upstream of VFD.

‒ η ~ 0.97 (varies little over range of speeds and loads encountered)

o Fixed TXVs replaced w/adjustable TXVs of the same size

o Outdoor Coil

‒ 5/16" tube, 3 rows, 16 FPI

‒ 10.96 ft² face area

o Indoor Coil

‒ 5/16" tube, 4 rows, 16 FPI

‒ 7.71 ft² face area

Replaced outdoor coil before testing began.

Page 25: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

25Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Instrumentation

Refrigerant-side

o Pressures and temperatures (TCs) at entrance and exit of major components.

o Turbine flow meters upstream of TXVs.

o Temperatures at entrance and exit of individual circuits on indoor and outdoor coils.

Air-side

o Dry-bulb and wet-bulb temperature measurements (RTDs) via sampling system.

o Indoor air flow rate measured by flow nozzle

Cooling Mode Heating Mode

Page 26: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

26Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

“A” conditions (95F ambient)

Capacities matched by selection of VFD speed.

Latent capacities

follow total capacities.

Alternatives gave higher efficiencies by 4.5% to

6%.

• DR-55 and DR-5A have modest ↑.

• R32 has larger ↑.

ave of 5 5 4 1 runs

Page 27: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

27Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

“B” conditions (82F ambient, wet coil)

Capacities matched

w/selected VFD speeds.

Latent capacities

were down ~5%.

Alternatives gave higher efficiencies by 2.5% to

4%.

• DR-55 and DR-5A have modest ↑.

• R32 has larger ↑.

ave of 2 4 2 1 runs

Page 28: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

28Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

“C” conditions (82F ambient, dry coil)

Capacities matched

w/selected VFD speeds.

Alternatives gave higher efficiencies

by 2% to 6%.

Page 29: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

29Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

“D” conditions (82F ambient, dry coil, cyclic)

R4

10

AD

R-5

5R

32

DR

-5A

o DR-5A’s advantage might come from initial 30 seconds (during damper manipulation)?

o Repeatability of transient behavior?

o Good repeatability to steady-state “C” conditions.

‒ DR-5A going to overshoot capacity?

o Why the apparently different time constants?

Page 30: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

30Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Cooling Mode

Vary Air Temperature Entering Indoor Coil‒ Entering dry-bulb temperatures = 80F, 75F, 70F. – Tamb = 95F.

‒ Kept entering air relative humidity fixed at 50%rh.

Capacity and Efficiency:All refrigerants showed similar

sensitivity to return air condition.

Latent Capacity:R32 generated slightly lower latent capacities than R410A and DR-55.

Page 31: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

31Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Heating Mode

H1 – 47F/43F H3 – 17F/15F

Small reductions in heating mode capacity when match capacity at “A” conditions.

Equal or small increases in heating mode efficiency when match capacity at “A” conditions.

Elevation in CDTs over R410A are similar to cooling mode. Well within operating boun-daries when in heating mode.

Page 32: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

32Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Results – Heating Mode

H2 – 35F/33F Cyclic Defrost Test

o More variability encountered than for other conditions – up to ±10%.

o DR-55’s and R32’s higher capacity and COP are due to of shorter defrost intervals.

o Signal from outdoor coil temperature sensor to controller?

‒ Temperatures measured near sensor at mode change points are not consistent between refrigerants.

‒ OCT sensor signal to controller was not recorded.

‒ How does controller know which refrigerant is present??

o Would expect similar perfor-mance for all refrigerants if controller reacted consistently.

Page 33: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

33Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Fractionation & Leak/Recharge w/DR-55

o Pulled refrigerant samples from subcooled liquid line while running.

o “Leaked” refrigerant vapor from compressor discharge line while running.

‒ ~2 lbm of refrigerant “leaked” (collected into cylinders) each time. (8.2 lbm full charge)

‒ Subcooling ~ 14Fd..16Fd with “full” charge, ~ 2Fd..4Fd after each “leak”.

o Capacity drops 3% to 5% after “leaking” 2 lbm. Capacity returns to within 1% of starting point after recharge.

o Efficiency drops 0.5% to 2% after “leaking” 2 lbm. Efficiency returns to within 0.5% of starting point after recharge.

Have now leaked ~8# of the ~14# charged to

the unit.↓

Page 34: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

34Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Fractionation & Leak/Recharge w/DR-55

o Refrigerant samples were pulled from subcooled liquid line while running.

o “Leaks” occurred from compressor discharge line while running (collected into 1# cylinders).

Initial charge taken from “small” (15#)

cylinder.

Refills done from “large” (30#)

cylinder.

o Circulating composition closely matched composition charged to unit ⇒ little fractionation occurring within the unit while running.

o Circulating composition changed very little over the course of four leak/recharge events (all while unit was running).

“Leaks” collected here (added to

residual charge).

Page 35: Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A ... · Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A in a 4-RT Unitary Rooftop Heat Pump Conclusions (3) Difference

35Soft-Optimized System Test of R410A, DR-55, R32, and DR-5A

in a 4-RT Unitary Rooftop Heat Pump

Fractionation & Leak/Recharge w/DR-55

REFLEAK – Crude Simulation of Full Fractionation (eg, cylinder discharge/recharge)

DR-55 nominal

composition

R32 = 0.67

R125 = 0.07

R1234yf = 0.26

fractionationafter initial charge

fractionationafter 1st leak

fractionationafter 4th leak

DR-55 has ~2F condenser glide at “A” conditions.

6.5 pt drop in R32%.

6.5 pt incin R1234yf.