solutions for data centers...rack-top temperatures data center capacity increases measurement and...

47
Better Buildings Webinar Series We’ll be starting in just a few minutes…. Tell us… What topics are you interested in for future webinars? Please send your response to the webinar organizers via the question box. 1

Upload: others

Post on 17-Apr-2020

2 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Better Buildings Webinar Series

We’ll be starting in just a few minutes….

Tell us…

What topics are you interested in for future webinars?

Please send your response to the webinar organizers via the

question box.

1

Page 2: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Click To Edit Master Title StyleSolutions for Small- to

Medium-Sized Data

Centers – Air

Management

June 4, 2019

3:00 – 4:00 PM EST

Page 3: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Today’s Presenters

Name Organization

Steve Greenberg Lawrence Berkeley National Lab

John SasserSabey Data Centers

3

Page 4: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Steve Greenberg

Lawrence Berkeley National Lab

Page 5: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

The Early Days at LBNL

Fans were used to redirect air High-flow tiles reduced air pressure

It was cold, but hot spots were everywhere:

Page 6: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Problems:– By-pass air– Re-circulation air

Solution:– Air Management

Use hot and cold aisles Improve isolation of hot

and cold aisles– Reduce fan energy

– Improve air-conditioning efficiency

– Increase cooling capacity

Hot aisle/cold aisle configuration decreases mixing of intake and exhaust air, promoting efficiency.

Air Management

Page 7: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Supply cold air as close to the rack inlet as possible

Reduce mixing with ambient air and hot rack exhaust

Air moves from the front cold aisle to the rear hot aisle

Equip.

Rack

No Air

Mixing

No Air

Mixing

Cold Front

Aisle

Hot Rear

Aisle

Separating Cold from Hot Airflow

Page 8: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Reduce By-Pass and Recirculation Air

Bypass Air / Short-Circuiting Recirculation

Wastes fan energy as well as cooling energy and capacity

Increases inlet temperature to servers

Leakage

Page 9: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Too much supply airflow Misplaced perforated tiles Leaky cable penetrations Too-high tile exit velocity

Equip.

Rack

Bypass

Air

Bypass

Air

InletOutlet

Inlet Outlet

Bypass Air – Common Causes

Page 10: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Too little supply airflow Lack of blanking panels Gaps between racks Short equipment rows

Equip.

Rack

Recirculation

Air

Inlet Outlet

Inlet Outlet

Recirculation Air – Common Causes

Page 11: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Unsealed cable penetration (inside rack) Sealed cable penetration

Maintain seals of all potential leaks in the raised floor plenum

Maintaining Raised-Floor Seals

Page 12: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

top of rack

middle of rack

SynapSense™

SynapSense™

Any opening will degrade the separation of hot and cold air

Maintain blanking panels One 12" blanking panel

reduced temperature ~20°F

Equip.

Rack

Recirculation

Air

Managing Blanking Panels

Page 13: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Congested Floor & Ceiling Cavities

Empty Floor & Ceiling Cavities

Consider the Impact that Congestion Has on the Airflow

Patterns

Reduce Airflow Restrictions & Congestion

Page 14: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Balancing is required to optimize airflow

Rebalance with new IT or HVAC equipment

Place perforated floor tiles only in cold aisles

Under-floor pressure map with wireless sensors

Resolve Airflow Balancing

Page 15: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Too many permeable floor tiles

If airflow is optimized

under-floor pressure

rack-top temperatures

data center capacity increases

Measurement and visualization

assisted the tuning process

under-floor pressures

rack-top temperatures

SynapSense™

SynapSense™

Results: Tune Floor Tiles

Page 16: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

There are numerous references in ASHRAE. See for example V. Sorell et al; “Comparison of Overhead and Underfloor Air Delivery Systems in a Data Center Environment Using CFD Modeling”; ASHRAE Symposium Paper DE-05-11-5; 2005.

Elevation at a cold aisle looking at racks

Too hot

Just right

Too cold

Too hot

Hot air comes around the top and sides of servers

Cold air escapes through ends of aisles

Typical Temperature Profile with Under-floor Supply

Page 17: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Next step: Air Distribution Return-Air Plenum

Page 18: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Physical barriers enhance separate hot and cold airflow

Barrier placement must comply with fire codes

Curtains, doors, or lids have been used successfully

Open Semi-enclosed Enclosed

cold aisle cold aisle

Doors Lid

Enhanced Isolation Options

Page 19: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Adding Air Curtains for Hot/Cold Isolation

Page 20: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

95–105ºF vs. 60–70ºF (35–41ºC vs. 16–21ºC)

70–80ºF vs. 45–55ºF (21–27ºC vs. 7–13ºC)

Air Management: Separate Cold and Hot Air

Page 21: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

LBNL’s Cold Aisle Containment study achieved fan energy savings of ~75%

Cold Aisle Airflow Containment Example

Page 22: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Isolation significantly reduces

bypass air, which in turn allows

reduction of supply airflow

Fan speed can be reduced,

and fan power is proportional

to nearly the cube of the flow

Fan energy savings of 70%–

80% is possible with variable

air volume (VAV) fansWithout Enclosure With Enclosure Without Enclosure

Fan Energy Savings

Page 23: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Default recommended range = 64.4 - 80.6F

Provides guidance for operating above the default upper

limit

Default allowable range = 59.0 – 89.6F (Class A1)

Six classes with allowable ranges up to 113.0F

ASHRAE Thermal Guidelines

Page 24: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

LBNL Air Management Demonstration

Cold Aisle NW - PGE12813

40

45

50

55

60

65

70

75

80

85

90

6/13/2006 12:00 6/14/2006 0:00 6/14/2006 12:00 6/15/2006 0:00 6/15/2006 12:00 6/16/2006 0:00 6/16/2006 12:00

Time

Te

mp

era

ture

(d

eg

F)

Low

Med

High

Baseline Alternate 1

Setup

Setup

Alternate 2

Better airflow management permits warmer supply

temperatures!

ASHRAE

Recommended Range

Ranges during

demonstration

Page 25: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Hot and Cold Aisle Containment

Subzero Cold Aisle Containment

APC Hot Aisle Containment

(with in-row cooling)

Ceilume Heat Shrink Tiles

Page 26: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Energy intensive IT equipment needs good isolation of “cold” intake and “hot”

exhaust

Supply airflow can be reduced if no bypass occurs (assuming VFD fans)

Supply temperature can be raised if air is delivered without mixing

CRACs, chillers and economizers are more efficient with warmer return air

temperatures

Cooling and raised-floor capacity increase with air management

Isolating Hot and Cold Aisles Summary

Page 27: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Localized air cooling systems with hot and cold isolation can supplement or

replace under-floor systems

Examples

- Row-based cooling units

- Rack-mounted heat exchangers

Both options “pre-engineer” hot and cold isolation

Efficient Alternatives to Under-Floor Air Distribution

Page 28: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Example – Local In-Row Based Cooling

Page 29: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Rack-Mounted Heat Exchangers (“Rear Doors”)

Page 30: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Air management techniques:

Seal air leaks in floor (e.g., cable penetrations)

Prevent recirculation with blanking panels in racks and between racks

Manage floor tiles (e.g., no perforated tiles in hot aisle)

Improve isolation of hot and cold air (e.g., return air plenum, curtains, or complete isolation)

Impact of good isolation:

Supply airflow reduced

Fan savings up to 75%+

Supply air temperature can be raised

Chiller efficiency improves

Greater opportunity for economizer operation (“free” cooling)

Cooling and raised-floor capacity increases.

Air Management Review

Page 31: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Develop prescriptive air management “packages”

through computer modeling, targeting small data centers

Estimate energy savings

Look-up tables with existing and potential AM strategies

Availability December 2019 on datacenters.lbl.gov

Coming Attraction: Air Management Packages

Page 32: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Lawrence Berkeley National Laboratory

MS 90-3111

University of California

Berkeley, CA 94720

https://datacenters.lbl.gov/

Steve Greenberg, P.E.

[email protected]

(510) 486-6971

Contact Information

Page 33: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

John Sasser

Sabey Data Centers

Page 34: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Confidential – Please do not distribute

Air Management Solutions –

Sabey’s Experience

Better Buildings Webinar

Tuesday, June 4th, 2019

Page 35: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Sabey Data Centers – Who We Are

Intergate.Ashburn Intergate.Manhattan

1.2 Million SF 408,000 SF

1.1 Million SF900,000 SF

Intergate.Seattle Intergate.Columbia Intergate.Quincy438,000 SF

Page 36: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Solution 1: Migrate to Colocation

Modern colocation providers

• May operate with high efficiency (and reliability) - Not all Colos are the same- Dig in with questions on specific operational

approach (e.g. containment requirements) and actual efficiencies achieved

• Provide remote hands services - Racking-and-stacking equipment, - Cable management, - Blanking plate installation, - Containment

Page 37: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Efficiency Comparisons

• Latest Uptime Institute Survey – Average industry PUE = 1.67

• Sabey: - Most efficient data center average annual = 1.13- Portfolio weighted average annual = 1.32

• Sabey practices- Hot aisle containment required- Some form of economizer- Variable speed fans; fan speed controlled

based on differential pressure- On slab (no raised floor)- High efficiency UPS

Page 38: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Indirect Economizer Cooling

Page 39: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Solution 2: Improve Existing Data Center

• Hot aisle / cold aisle• Blanking plates• Network switches – supplemental ducting• Cable management• Containment• System controls• CRAH/CRAC/AHU ducting• Controls

Page 40: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Switch Airflow Management

• Vertiv Geist Switchair – example of a commercially available solution for managing airflow

• Even better – order switches with correct front to back airflow

Page 41: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Cable Management

Poorly dressed cables may partially block airflow from server fans, reducing their effectiveness

Page 42: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Hot Aisle vs

Cold Aisle Containment

Page 43: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Controls

• Return temperature control- Formerly default mode of CRAH/CRAC units- Old/discredited

• Precision temperature control

• Differential pressure control

• Better airflow management enables more efficient control strategies- Lowering fan energy use- Increasing use of economizer- Increasing efficiency of chiller plant

(if applicable)

Page 44: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Q&A

Page 45: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Better Buildings Webinar Series

45

STRAIGHT TALK: TALKING TO

MULTIFAMILY TENANTS ABOUT

UTILITY BENCHMARKING

Tuesday, October 1, 2019 | 3:00 - 4:00 PM ET

This webinar will identify strategies for obtaining

tenant consent to share their utility data; it will also

explore ways to engage multifamily residents about

the benefits of energy efficiency upgrades.

Page 47: Solutions for Data Centers...rack-top temperatures data center capacity increases Measurement and visualization ... Look-up tables with existing and potential AM strategies Availability

Additional Questions? Please Contact Us

[email protected]

Today’s

Presenters

Steve Greenberg

LBNL

[email protected]

John Sasser

Sabey Data Centers

[email protected]

DOE Program

Support

Ryan Livingston

Allegheny Science & Technology

[email protected]

Program Support

Kendall Sanderson

RE Tech Advisors

[email protected]

Megan Krest

RE Tech Advisors

[email protected]

Follow us on Twitter @BetterBldgsDOE

47