solvent machine cleaning - risk analysis 1/22 l.bardo - ph-cmx 04 december 2015

13
Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

Upload: daniella-knight

Post on 19-Jan-2018

215 views

Category:

Documents


0 download

DESCRIPTION

3/22 D ESCRIPTION Equipment & Location

TRANSCRIPT

Page 1: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

Solvent machine cleaning -

Risk analysis

1/22L.Bardo - PH-CMX 04 December 2015

Page 2: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

Content

1. Description

Equipment & Location

Vertrel XF

2. Continuous preventive and protective measures

3. Critical situations – Risk Analysis

2/22

Page 3: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

3/22

DESC

RIPT

ION

Equipment & Location

Page 4: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

4/22

DESC

RIPT

ION

VERTREL XF

Page 5: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

Technical measures

5/22

CON

TIN

UO

US

PREV

ENTI

VE A

ND

CORR

ECTI

VE M

EASU

RES - Adapt the ventilation

Cavern Volume = 2000 m3 air. Only fresh air pulsed : Flow rate= 10 000 m3/hour – (the air is warmed up)

+ “Brassage” = 30 000 m3/hour pulsing

= 40 000 m3/hour pulsing

Natural extraction through the pit Air renewed every 12 minutes – 5 renewal/hour

In case of emergency: Extraction (“désenfumage”) 20 000 m3/hour – test will be drawn up by Frederic Juban and he will also give an explanation on how to activate the system to CMS collaborators (To be completed: 16 5000, Antonio, Maf, Sandro,) -> to be planned

Install aerolic connection on the “ desenfumage” system to collect the vapours at the source-> to be done by EN-CV

If some areas seems not to be properly ventilated, extractors can be added –> extractors are ordered

Page 6: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

Technical measures

6/22

CON

TIN

UO

US

PREV

ENTI

VE A

ND

CORR

ECTI

VE M

EASU

RES

- Portable ODH always worn by personnel intervening in USC55 and UXC55 -> the ODH detector triggered in presence of VERTREL XF

- Move one of the two ODH sensors located under the cold box -> in discussion

- Retention tank under the condenser -> check if the CMS retention tank are big enough

- Retention tank included in the solvent machine -> retention > 1m3 once installed

- CO2 Fire extinguishers -> check that a sufficient amount of fire extinguisher are present on site.

- Obstructing plate -> Ordered

- Absorption kit already in USC55 level -2 S3 -> check if it is compatible with the product used

- Mobile shower -> to be ordered? + Retention for rinsing water

- Rinse eye already in USC55 level -2 S3 inside the absorption kit -> keep the absorption cabinet open

Page 7: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

Organisational measures

7/22

CON

TIN

UO

US

PREV

ENTI

VE A

ND

CORR

ECTI

VE M

EASU

RES

- Fire brigade will be informed about the intervention and the risks present (provide the product MSDS) -> organise a visit

- Access limited -> put barriers level-1 and level-2 with panel indicating the reason, duration, contact person

- Check if shifters will be present during nights and weekends. If no check with the Fire Brigade if they can patrol the area.

Page 8: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

Documentation

8/22

CON

TIN

UO

US

PREV

ENTI

VE A

ND

CORR

ECTI

VE M

EASU

RES

- MSDS close to the tank

- Tank identified with the name of the product and pictograms

- Instruction what to do in case of spill -> to be adapted

- Instruction what to do in case of projection -> already existing

Page 9: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

Training

9/22

CON

TIN

UO

US

PREV

ENTI

VE A

ND

CORR

ECTI

VE M

EASU

RES

- All persons intervening have followed the appropriate safety trainings and have the access to work in the USC55 cavern -> Email sent

- Specific training on site -> organise a Safety briefing for people intervening to get familiar with the premises and safety equipment and procedure

- Chemical awareness on SIR online will be followed by all people intervening

- List among the people intervening which one are First-aider -> list of people intervening

- List among the people intervening which one followed the fire extinguisher training courses -> list of people intervening

- At least 1 chemist will always be on site during working hours

Page 10: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

Scenarios

10/22

CRIT

ICAL

SIT

UATI

ON

S

1. Solvent Machine Leak in USC55 – level -2- S3

2. Solvent Machine transport in PM54 lift

3. Leak during the disconnection of the solvent Machine from the cold box

4. Small like of a pipe/equipment during the running

5. Power cut

Page 11: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015

Thank you for your attention

Page 12: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015
Page 13: Solvent machine cleaning - Risk analysis 1/22 L.Bardo - PH-CMX 04 December 2015