spaj140c electronic relays
TRANSCRIPT
-
8/2/2019 Spaj140c Electronic Relays
1/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94- 11. 1.
Multipurpose Relay for
Applications where non-directionalovercurrent and earth-fault protectionsare needed, e.g.- feeder protection- transformer protection- back-up protection
Application areas, e.g.- power utilities- industries- marine and offshore installations
RS 611 Ser.No.
n =
n =
SPAJ 140 C
Uaux
SPCJ 4D29
REGISTERS OPER.IND.
0 0 0 0 0
2
5
878E
I
( )I
( )oI
1I> START
I
80...265 V ac/dc
18...80 V dc
5A1A
1A 5A
fn = 50Hz
60Hz
SGR
SGB
SGF
SPCJ 4D29
TRIP
PROGRAM
RESET
STEP
L1 L2 L3 o IRF
3 >I
I>/In
879B
I
X
X
I I I I
1 IL1 /In2 IL2 /In
3 IL3 /In4 Imax (15 min)
5 t(I>)[%]
6 t(I>>)[%]
7 I0 /In
8 t(I0>)[%]
9 t(I0>>)[%]
2I> TRIP
3I>> START
4I>> TRIP
5I0> START
6I0> TRIP
7I0>> START
8I0>> TRIP
9 GBFP
t> [s]k
I>>/In
t>> [s]
I0>/In
t0> [s]k0
I0>>/In
t0>> [s]
-
8/2/2019 Spaj140c Electronic Relays
2/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94- 11. 2.
Protective Functions
Three-phase, low-set phase overcurrent protection with definite time orinverse definite minimum time (IDMT) characteristic
Three-phase, high-set phase overcurrent protection with instantaneous ordefinite time function
Low-set, non-directional earth-fault protection with definite time or
inverse definite minimum time (IDMT) characteristic
High-set, non-directional earth-fault protection with instantaneous ordefinite time function
Circuit-breaker failure protection
-
8/2/2019 Spaj140c Electronic Relays
3/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94- 11. 3.
Protective FunctionsTHREE PHASE DEFINITE TIMEOR INVERSE TIME LOW-SETOVERCURRENT PROTECTION
SERIAL COMMUNICATION PORT
TRIP
SIGNAL 1
SERIAL I/O
IL1
IL2
IL3
Io
BS
Blockingor reset
THREE PHASE INSTANTANEOUSOR DEFINITE TIME HIGH-SETOVERCURRENT PROTECTION
INSTANTANEOUS OR DEFINITETIME HIGH-SET EARTH-FAULTPROTECTION
REMOTE RESET, REMOTE SETTINGCONTROL OR BLOCKING INPUT FORTHE DIFFERENT CURRENT STAGES
SIGNAL 2
START 1
IRF
START 2
CIRCUIT BREAKER FAILUREPROTECTION
DEFINITE TIME OR INVERSE TIMELOW-SET EARTH-FAULTPROTECTION
51
50
51 N
51BF
50 N
Prot. functions
-
8/2/2019 Spaj140c Electronic Relays
4/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94- 11. 4.
Features
Wide and accurate numerical settings with perfect long-time stability
Possibility for two sets of relay settings
Local man-machine communication with push-buttons and a digital display
High immunity to electrical and electromagnetic interference
Rigid aluminium relay case with a degree of protection by enclosure to IP 54
Extensive data communication capability over built-in serial port
Enhanced system reliability and availability due to continuous
hardware and software self-supervision
-
8/2/2019 Spaj140c Electronic Relays
5/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94- 11. 5.
Versions of the Earth-fault Protection
Relay versions SPAJ 140 C SPAJ 141 C SPAJ 142 C
Measuring module SPCJ 4 D 29 SPCJ 4 D 24 SPCJ 4 D 29Rear module SPTK 4E1 SPTK 4E2 SPTK 4E2
Start current of I> stage, definite time 0.5 ... 5.0 x In
0.5 ... 5.0 x In
0.5 ... 5.0 x In
Start current of I> stage, inverse time 0.5 ... 2.5 x In
0.5 ... 2.5 x In
0.5 ... 2.5 x In
Start current of I>> stage 0.5 ... 40 x In
and 0.5 ... 40 x In
and 0.5 ... 40 x In
and
In
of earth-fault unit 1 A / 5 A 0.2 A / 1 A 0.2 A / 1 ASetting range of I
o> 0.1 ... 0.8 x I
n0.01 ... 0.25 x I
n0.1 ... 0.8 x I
n
Setting range of Io>> 0.1 ... 10.0 x I
n0.1 ... 10.0 x I
n0.1 ... 10.0 x I
n
Lowest primary setting of Io> 100 mA 2 mA 20 mA
Operation characteristic Definite time Definite time Definite time
IDMT - IDMT
-
8/2/2019 Spaj140c Electronic Relays
6/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94- 11. 6.
Block Diagram
6162
SPAJ 140 C
63 25 26 271 2 3 4 5 6 7 8 9
L1
L2
L3
70 71 72
0
65 66
+ (~)
- (~)
3I>
3I>>
Io>
Io>>
IRF
I/O
68 6977 78
IRF SIGNAL 2
-
+
TRIP
74 75
START 1
80 811011
SGB/1
SGB/2
SGB/3
SGB/4
SGB/6SGB/7
SGB/5
LATCHING
SIGNAL 1START 2
RESET
I-
I 0
++
+
B
+
C
+
F
+
E
+
D
+
A
U1
1 1
T2
T4
T6
T8
T1
T3
T5
T7
RC SETTINGS
SGB/8 SGF/40.1...1s
SGR2/8
SGR1/6
SGR1/8
SGR1/2
SGR1/4
U3TRIP
R
U2
U1T9
TS2SS3SS2SS1TS1
SPA-ZC_
Rx Tx
SERIALPORT
+ -
SGR2/6
SGR2/4
SGR2/2
1
SGR2/7
SGR2/5
SGR2/3
SGR2/1
1
SGR1/7
SGR1/5
SGR1/3
SGR1/1
1
SGR3/8
SGR3/7
SGR3/6
SGR3/5
SGR3/4
SGR3/3
SGR3/2
SGR3/1
~
EXTERNALCONTROL
Connections
1A5A1A
5A1A5A 1A5A
Uaux
SPCJ 4D29
-
8/2/2019 Spaj140c Electronic Relays
7/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94- 11. 7.
SGR
SGB
SGF
SPCJ 4D29
TRIP
PROGRAM
RESET
STEP
L1 L2 L3 o IRF
3 >I
> nI I/
ks>t [ ]
n>>I I/
s>>[ ]t
so >
ko
[ ]t
no>I I/
s>>ot [ ]
n>>o I/I
879B
I
I I I I
Indicators for readout of the measured phase currents,doubling as phase-fault indicators
Indicator for readout of the measured neutral current,doubling as earth-fault indicator
Indicator for signalling of internal relay faults
Digital display for readout of numerical parameters, i.e.settings, measured and recorded values including start andoperation indications, auto-diagnostic fault messages, etc.
Indicator showing that the main trip relay of the protectionrelay has operated
Readouts and Operation Indicators
-
8/2/2019 Spaj140c Electronic Relays
8/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94- 11. 8.
SGR
SGB
SGF
SPCJ 4D29
TRIP
PROGRAM
RESET
STEP
L1 L2 L3 o IRF
3 >I
> nI I/
ks>t [ ]
n>>I I/
s>>[ ]t
so >
ko
[ ]t
no>I I/
s>>ot [ ]
n>>o I/I
879B
I
I I I I
Push-button Operations
Use the RESET/STEP push-button to:- reset operation indicators
- step forward or backward in main menus or submenus- set adjustable parameter values when in the setting mode
Use the PROGRAM push-button to:- enter a submenu from the main menu
- enter the setting mode of an adjustable parameter- control the cursor in the setting mode or to control theselected output in the test mode
Use both push-buttons simultaneously to:- make a complete relay reset, i.e. erase recorded valuesand release latched output relays
- save a new setting value- carry out an output relay test
-
8/2/2019 Spaj140c Electronic Relays
9/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94- 11. 9.
Main Settings Second Settings
Two Setting Banks
Actual operate time t> ormultiplier k for stage I>
Actual start current I>>
Actual operate time t>>of stage I>>
Actual start current Io>
Actual operate time to>or multiplier ko
Actual start current Io>>
Actual operate time to>>
Operate time t> ormultiplier k
Start current ofstage I>>
Operate time t>>
Start current ofstage Io>
Operate time to> ormultiplier ko
Start current of
stage Io>>
Operate time to>>
Start current ofstage I>Actual start current I>
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
Operate time t> ormultiplier k
Start current ofstage I>>
Operate time t>>
Start current ofstage Io>
Operate time to> ormultiplier ko
Start current of
stage Io>>
Operate time to>>
Start current ofstage I>
Dualsetting
bank
s
-
8/2/2019 Spaj140c Electronic Relays
10/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 10.
SGR
SGB
SGF
SPCJ 4D29
TRIP
PROGRAM
RESET
STEP
L1 L2 L3 o IRF
3 >I
> nI I/
ks>t [ ]
n>>I I/
s>>[ ]t
so >
ko
[ ]t
no>I I/
s>>ot [ ]
n>>o I/I
879B
I
I I I I
Settings of the Overcurrent Unit
Low-set stage I>:
Start current I> at definite time 0.5 ... 5.0 x InStart current I> at inverse time 0.5 ... 2.5 x In*)
Operate time t> at definite time 0.05 ... 300 sTime multiplier k> at inverse time 0.05 ... 1.00
High-set stage I>>:
Start current I>> 0.5 ... 40 x In or infinite
Operate time t>> 0.04 ... 300 s
*) Any setting greater than 2.5 x In will be regarded as equal to 2.5 x In
-
8/2/2019 Spaj140c Electronic Relays
11/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 11.
SGR
SGB
SGF
SPCJ 4D29
TRIP
PROGRAM
RESET
STEP
L1 L2 L3 o IRF
3 >I
> nI I/
ks>t [ ]
n>>I I/
s>>[ ]t
so >
ko
[ ]t
no>I I/
s>>ot [ ]
n>>o I/I
879B
I
I I I I
Settings of the Earth-fault Unit
Low-set stage Io>:
Start current Io>, 0.1 ... 0.8 x In
Operate time to> for definite time 0.05...300 sTime multiplier k at inverse time 0.05...1.00
High-set stage Io>>:
Start current Io>> 0.1...10 x In or infinite
Operate time to>> 0.05...300 s
-
8/2/2019 Spaj140c Electronic Relays
12/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 12.
SGR
SGB
SGF
SPCJ 4D29
TRIP
PROGRAM
RESET
STEP
L1 L2 L3 o IRF
3 >I
> nI I/
ks>t [ ]
n>>I I/
s>>[ ]t
so >
ko
[ ]t
no>I I/
s>>ot [ ]
n>>o I/I
879B
I
I I I I
Switchgroup Settings
Switchgroups SGF1 and SGF2 for selection of operationcharacteristics and other functional parameters
Switchgroup SGB for routing of blocking signals and forselection of the latching function for the trip relay
Switchgroups SGR1, SGR2 and SGR3 for configuration ofthe output relays
-
8/2/2019 Spaj140c Electronic Relays
13/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 13.
Flexible Configuration of Output Signals
SGR3 / 6
SGR1 / 8
IL1
IL2
IL3
SGR3 / 1SGR1 / 1SGR3 / 2SGR2 / 1SGR2 / 2SGR1 / 2
SGR3 / 3SGR1 / 3
SGR3 / 4SGR2 / 3SGR2 / 4SGR1 / 4
SGR3 / 5SGR1 / 5
SGR2 / 5SGR2 / 6SGR1 / 6
SGR3 / 7SGR1 / 7SGR3 / 8
SGR2 / 7SGR2 / 8
I>
I>> t>>
t>, k
to>, koIo>
to>>Io>>
Io
BS
SGB / 1
SGB / 2
SGB / 3
SGB / 4
SGB / 5
SGB / 8REMOTE SETTINGS
RELAY RESET
1
SGB / 6RESET+PROGRAM
1
SGB / 7RESET+PROGRAM
1
1
1
SGF1 / 4
SS1
SS2
SPCJ 4D29
TS1
TS2
SS3
RESETTRIP
0.1...1s
A
B
C
D
FIRF
ESTART 1
START 2
SIGNAL 1
SIGNAL 2
TRIP
IRF
(AR2)
(AR1)
(AR3)SGF2 / 8
SGF2 / 7
SPTU ___R1SIGNAL DIAGRAM
Relay
Outputsignals
-
8/2/2019 Spaj140c Electronic Relays
14/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 14.
Settings of Switchgroup SGF 1
0.0
5...
300sD
ef.time
Extremelyinverse
Veryinverse
Normalinvers
e
Long-terminv
erse
RIcharacteris
tic
RXIDGcharac
teristic
Notinuse
Yes
No
Defaultprogramming
Setting
Main set
Second set
SGF1 1 Operation characteristic 0 1 0 1 0 1 0 1 0 x 1 =
2 of the low-set overcurrent 0 0 1 1 0 0 1 1 0 x 2 =3 stage (I>) 0 0 0 0 1 1 1 1 0 x 4 =4 Circuit breaker failure protection selected 1 0 0 x 8 =5 Energizing will double the I>> setting 1 0 0 x 16 =6 Operation characteristic 0 1 0 1 0 1 0 1 0 x 32 =7 of the low-set earth-fault 0 0 1 1 0 0 1 1 0 x 64 =
8 stage (Io>) 0 0 0 0 1 1 1 1 0 x 128 =Checksum =
(Default = 000)
PROGRAM
SGR
SGB
TRIP
SGF
SPCJ 4D29
-
8/2/2019 Spaj140c Electronic Relays
15/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 15.
Settings of Switchgroup SGF 2
Yes
No
Defaultprogramming
Setting
Main set
Second set
SGF2 1 Manual resetting of I> start indication 1 0 0 x 1 =
2 Manual resetting of I>> start indication 1 0 0 x 2 =3 Manual resetting of I
o> start indication 1 0 0 x 4 =
4 Manual resetting of Io>> start indication 1 0 0 x 8 =
5 I>> stage is blocked 1 0 0 x 16 =6 I
o>> stage is blocked 1 0 0 x 32 =
7 I>> start signal to autoreclose output AR1 1 0 0 x 64 =
8 Io> start signal to autoreclose output AR2 0 0 x 128 =Io>> start signal autoreclose output AR3 1
Checksum =(Default = 000)
PROGRAM
SGR
SGB
TRIP
SGF
SPCJ 4D29
-
8/2/2019 Spaj140c Electronic Relays
16/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 16.
Yes
No
Defaultprogramming
Setting
Settings of Switchgroup SGB
Main set
Second set
SGB 1 BS input = I> stage blocking 1 0 0 x 1 =
2 BS input = I>> stage blocking 1 0 0 x 2 =3 BS input = I
o> stage blocking 1 0 0 x 4 =
4 BS input = Io>> stage blocking 1 0 0 x 8 =
5 BS input or command V150 activates the second setting 1 0 0 x 16 =6 Overcurrent unit latches the relay A (signal TS2) 1 0 0 x 32 =7 Earth-fault unit latches the relay A (signal TS2) 1 0 0 x 64 =
8 BS input resets latched output relay and recorded values 1 0 0 x 128 =Checksum =
(Default = 000)
PROGRAM
SGR
SGB
TRIP
SGF
SPCJ 4D29
-
8/2/2019 Spaj140c Electronic Relays
17/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 17.
Settings of Switchgroup SGR 1
Yes
No
Defaultprogramming
Setting
Main set
Second set
SGR1 1 I> start signal routed to relay D (signal SS1) 1 0 1 x 1 =
2 I> start signal routed to relay A (signal TS2) 1 0 1 x 2 =3 I>> start signal routed to relay D (signal SS1) 1 0 0 x 4 =4 I>> start signal routed to relay A (signal TS2) 1 0 1 x 8 =5 I
o> start signal routed to relay D (signal SS1) 1 0 0 x 16 =
6 Io> start signal routed to relay A (signal TS2) 1 0 1 x 32 =
7 Io>> start signal routed to relay D (signal SS1) 1 0 0 x 64 =
8 Io>> start signal routed to relay A (signal TS2) 1 0 1 x 128 =Checksum =
(Default = 171)
PROGRAM
SGR
SGB
TRIP
SGF
SPCJ 4D29
-
8/2/2019 Spaj140c Electronic Relays
18/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 18.
Settings of Switchgroup SGR 2
Yes
No
Defaultprogramming
Setting
Main set
Second set
SGR2 1 I> operate signal routed to relay C (signal SS2) 1 0 1 x 1 =
2 I> operate signal routed to relay B (signal SS3) 1 0 0 x 2 =3 I>> operate signal routed to relay C (signal SS2) 1 0 1 x 4 =4 I>> operate signal routed to relay B (signal SS3) 1 0 0 x 8 =5 I
o> operate signal routed to relay C (signal SS2) 1 0 0 x 16 =
6 Io> operate signal routed to relay B (signal SS3) 1 0 1 x 32 =
7 Io>> operate signal routed to relay C (signal SS2) 1 0 0 x 64 =
8 Io>> operate signal routed to relay B (signal SS3) 1 0 1 x 128 =Checksum =
(Default = 165)
PROGRAM
SGR
SGB
TRIP
SGF
SPCJ 4D29
-
8/2/2019 Spaj140c Electronic Relays
19/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 19.
Settings of Switchgroup SGR 3
Yes
No
Defaultprogramming
Setting
Main set
Second set
SGR3 1 I> operate signal routed to relay E (signal TS1) 1 0 0 x 1 =
2 I> operate signal routed to relay E (signal TS1) 1 0 0 x 2 =3 I>> operate signal routed to relay E (signal TS1) 1 0 0 x 4 =4 I>> operate signal routed to relay E (signal TS1) 1 0 0 x 8 =5 I
o> operate signal routed to relay E (signal TS1) 1 0 0 x 16 =
6 Io> operate signal routed to relay E (signal TS1) 1 0 0 x 32 =
7 Io>> operate signal routed to relay E (signal TS1) 1 0 0 x 64 =
8 Io>> operate signal routed to relay E (signal TS1) 1 0 0 x 128 =Checksum =
(Default = 000)
PROGRAM
SGR
SGB
TRIP
SGF
SPCJ 4D29
-
8/2/2019 Spaj140c Electronic Relays
20/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 20.
Comprehensive Post-fault Analysis
The trip reason and phase conditions can be read on the front of the relay
The latest five values of the measured values are stored in the memory
The number of starts of all the protection stages available in the memory
1 2IL1
2 1 2
3 1 2
4 1 2tI>
5 1 2
6 1 2
7 1 2
8 1 2
1
Io
53
3
3
3
3
3
3
4
4
4
4
4
4
4
4
5
5
5
3
nI>
nI>>
nIo>
nIo>>
IL2
IL3
tI>>
tIo>
tIo>>
-
8/2/2019 Spaj140c Electronic Relays
21/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 21.
Missing protection or
nonselective operation
Relay availability
Without self-supervision
With self-supervision
-
8/2/2019 Spaj140c Electronic Relays
22/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 22.
Continuous Self-supervision
U ref
A
D
P
8 888
P
WD
-
8/2/2019 Spaj140c Electronic Relays
23/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 23.
Serial Communication Features
The following parameters can be accessed via serial communication overthe SPA bus:
- Actual measured values can be read
- Setting values for main and second sets and switchgroup settingscan be read and, if necessary, changed using a security password
- Status information of output relays etc. can be read and written withpassword
- Recorded fault parameters can be read and erased
- Spontaneous reporting of selected events to an event recorder or aprinter
-
8/2/2019 Spaj140c Electronic Relays
24/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 24.
Insulation tests
Dielectric test, inputs and outputsbetween themselves and to the relay frameas per IEC 255-5 2 kV
Impulse test, inputs and outputsbetween themselves and to the relay frame
as per IEC 255-5 5 kV , 1.2/50 s, 0.5 J
Insulation resistance, inputs and outputsbetween themselves and to the relay frame >100 Mohm, 500 Vdc
-
8/2/2019 Spaj140c Electronic Relays
25/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 25.
Disturbance tests
High frequency interference test,as per IEC 255-22-1,class III, 1 MHz, 400 bursts per sec
- common mode / differential mode 2.5 kV / 2.5 kV
Fast transient test as per IEC 255-22- 4, class IIIand IEC 801- 4, level IV
- power supply inputs 4 kV , 5/50 ns
- other inputs and outputs 2 kV , 5/50 nsElectrostatic discharge test as per IEC 255-22-2and IEC 801-2, class III, 150 pF
- air discharge / contact discharge 8 kV / 6 kV
Electromagnetic field test as per IEC 801-3, class III 10V/m,150 kHz1000 MHz
Magnetic field as per IEC 521 400 A/m
-
8/2/2019 Spaj140c Electronic Relays
26/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 26.
Mechanical tests
Seismic test as per ANSI/IEEE C37.98-1987- operating basis earth-quake tests (OBE) 0.55.25 g
- safe shutdown earth-quake tests (SSE) 0.57.5 g
Vibration test 213.2 Hz, 1.0 mm13.2100 Hz, 0.7 g
Shock/bump test as per IEC 255-21-2 20 g, 1000 bumps/direction
-
8/2/2019 Spaj140c Electronic Relays
27/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 27.
Environmental conditions
Corrosion test as per Battelle-test, class G3 20days
Specified ambient service temperature range -10...+55 C
Long term damp heat withstand according toIEC 68-2-3 < 95 % at 40 C for 56 days
Transport and storage temperature range -40...+70 C
Degree of protection by enclosure of the re-lay case as per IEC 529 when panel mounted IP 54
-
8/2/2019 Spaj140c Electronic Relays
28/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 28.
Dimensions and Panel Cut-out
Flush mounting
RAISING FRAMESPA-ZX 111SPA-ZX 112SPA-ZX 113
176136
96
74114154
a b
a b
PANEL
CUT-OUT
129 1
139
1
142
162
136
30
34
250
186
216
Semi-flush mounting
-
8/2/2019 Spaj140c Electronic Relays
29/29
ABB Network Control & Protection
Combined O/C and E/F Relay SPAJ 140 C
SPAJ 140 EN 94-11. 29.
Mounting Plates
Mounting in 19" cabinets Surface mounting
SPA-ZX 104 SPA-ZX 110482,6 0 (19")
101,6 7
177
0
(4U)
+0,4
+0,4
21,5
482,6 0 (19")
101,6 7
177
0
(4U)
+0,4
+0,4
21,5
SPA-ZX 106
263
6
115
292
312
10
115
158
6
98