sps module mts-p01 - bosch rexroth · conjunction with an mtc-p01 (nc controller). communication...
TRANSCRIPT
SPS ModuleMTS-P01.1
Configuration
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
mannesmannRexroth
engineering
IndramatRexroth
7=78)1���
About this Document SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
SPS Module MTS-P01.1
Configuration
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
• DOK-MTC200-TECHN*UNTERL-04M1-EN-P
• DOK-MTC200-TEC*DOC*4V3-04M1-EN-P
• Drawing number: 120-0400-B309-02
This document is used
• for configuring, installing, and commissioning the SPS modulesMTS-P01.1
Documentation identification ofprevious releases
Releasedate
Comment
DOK-CONTRL-MTS-P01.1**-PR02-EN-P 02.1999 First issue
INDRAMAT GmbH, 1999
Copying this document and giving it to others and the use orcommunication of the contents thereof without express authority areforbidden. Offenders are liable for the payment of damages. All rights arereserved in the event of the grant of a patent or the registration if a utilitymodel or design. (DIN 34-1)
All rights are reserved with respect to the content of this documentationand the availability of the product.
INDRAMAT GmbH • Bgm.-Dr.-Nebel-Str. 2 • D-97816 Lohr a. Main
Phone 09352/40-0 • Tx 689421 • Fax 09352/40-4885
Dept. ECS (RW)
This document is printed on paper bleached without chlorine.
Title
Type of document
Document code
Internal file reference
Purpose of the document
Configuration control
Copyright
Validity
Published by
Note
SPS Module MTS-P01.1 Contents I
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
Contents
1 The INDRAMAT SPS MTS-P01.1 1-11.1 Brief Description................................................................................................................................... 1-1
1.2 Communication .................................................................................................................................... 1-2
Computer communication ............................................................................................................. 1-2
Communication with the NC Controller ......................................................................................... 1-2
1.3 Address Selection ................................................................................................................................ 1-2
General.......................................................................................................................................... 1-2
DIP switch configuration table....................................................................................................... 1-3
1.4 SPS Inputs for the Machine Function Keys.......................................................................................... 1-3
1.5 Rechargeable Battery .......................................................................................................................... 1-4
1.6 Installation............................................................................................................................................ 1-4
1.7 Interface Pin Assignments ................................................................................................................... 1-5
1.8 Status Display and Fault Diagnosis ..................................................................................................... 1-5
Operating state display.................................................................................................................. 1-5
Error Indication.............................................................................................................................. 1-6
2 INTERBUS Master Interface 2-12.1 Brief Description of the IBM 2 Unit....................................................................................................... 2-1
2.2 Setting the I/O Address........................................................................................................................ 2-2
2.3 Interface Pin Assignments ................................................................................................................... 2-2
3 PROFIBUS-DP Interfaces 3-13.1 Brief description of the DPM01 and DPS01 Boards ............................................................................ 3-1
3.2 Setting the I/O Addresses .................................................................................................................... 3-2
3.3 Status and Diagnosis Indicators .......................................................................................................... 3-3
3.4 Specifications....................................................................................................................................... 3-3
3.5 Interface Pin Assignments ................................................................................................................... 3-4
4 Serial Interface 4-14.1 Brief Description................................................................................................................................... 4-1
4.2 Addresses and Interrupt Settings......................................................................................................... 4-2
Function Blocks............................................................................................................................. 4-2
4.3 Specifications....................................................................................................................................... 4-3
4.4 Interface Pin Assignments ................................................................................................................... 4-3
II Contents SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
5 I/O Module 5-15.1 Brief Description................................................................................................................................... 5-1
5.2 Setting the I/O Address........................................................................................................................ 5-1
5.3 Addressing the PEA 4/01 Board .......................................................................................................... 5-2
5.4 Specifications....................................................................................................................................... 5-2
5.5 Connector pin assignments of I/O connector....................................................................................... 5-2
6 Configurations 6-16.1 MTS-P01.1-**-B1-E1-NN-NN-FW ........................................................................................................ 6-1
6.2 MTS-P01.1-**-B1-S4-NN-NN-FW ........................................................................................................ 6-2
6.3 MTS-P01.1-**-B1-S4-E1-NN-FW......................................................................................................... 6-3
6.4 MTS-P01.1-**-P1-E1-NN-NN-FW ........................................................................................................ 6-4
7 Accessories 7-17.1 List of Connectors and Cable Sets ...................................................................................................... 7-1
8 Type Code 8-1
9 Figures 9-1
SPS Module MTS-P01.1 The INDRAMAT SPS MTS-P01.1 1-1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
1 The INDRAMAT SPS MTS-P01.1
1.1 Brief Description
The SPS module MTS-P01.1 is a powerful SPS controller in the ISA busplug-in module format. It can be installed in a BTV20/30 unit or in astandard industry PC.
The MTS-P01.1 module consists of a base unit (the SPS proper) andvarious PC104 plug-in modules. These plug-in modules can be, forexample, field bus interfaces, serial interfaces, or I/O modules.
The module can be configured as a master (stand-alone SPS) or as aslave SPS. The slave version of the MTS-P01 can only be used inconjunction with an MTC-P01 (NC controller).
Communication with remote I/O or operator input units takes place via theoptional plug-in field bus interfaces and/or serial interfaces. Theseoptional interfaces are made as PC104 modules. The following modulesare currently available:
• INTERBUS master interface
• PROFIBUS master interface
• PROFIBUS slave interface
• Serial interfaces (2 x RS232 and 2 x RS422)
Up to 4 PC104 modules can be used on an MTS-P01.1 unit.
Figure 1-1: MTS-P01.1 without additional interfaces
Addressingthe MTS-P01
SPS inputsfor machine
function keys/BTV20/30)
INDRAMAT Local bus(not with stand-alone SPS)
Battery PC104 bus PC ISA bus
1-2 The INDRAMAT SPS MTS-P01.1 SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
H1
X2
X1
8.
X5
H1 status display
X1 diagnostics connector
1 6
X5 watchdog: SPS Ready(stand-alone SPS only)
X2 serial interface DEVICE: 0 SERNR: 0
1
2
X5
SPS-READY
MTS-P01_Anschl.FH7
addresses usedin the SPS forprogramming
contact rating:Umax = 24VImax = 150 mA
Figure 1-2: Front view of the MTS-P01.1 unit
1.2 Communication
Computer communicationCommunication with the computer (CPU) is performed internally via thestandard ISA bus of the industry PC. The power supply of the MTS-P01.1module is also routed via this bus.
Communication with the NC ControllerCommunication between an SPS module and the NC module (MTC-P01.2) takes place via the INDRAMAT local bus. This is implemented viaa 50-way ribbon cable.
1.3 Address Selection
General
SPS module
ON
12
34
56
78
OP
EN
OFF e.g. 1st MTS-P (factory setting)
MTS-P01_Adress.FH7
Figure 1-3: Location of the address switch
The addresses must be selected before the MTS-P module is insertedinto a BTV20/30 unit or an industry PC. This is done on the DIP switchshown in Figure 1-3. However, the selected address is only valid for astand-alone SPS. When a slave SPS is employed, the DIP switches
SPS Module MTS-P01.1 The INDRAMAT SPS MTS-P01.1 1-3
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
must be set to OFF (Open). Use the following table when you employ oneor more stand-alone SPS module(s),.
DIP switch configuration table
MTS-P01.1 1 2 3 4 5 6 7 8 I/O address (hex)
1st (default) OFF OFF OFF OFF OFF OFF OFF OFF $31C
2nd (default) ON OFF OFF OFF OFF OFF OFF OFF $318
3rd (default) OFF ON OFF OFF OFF OFF OFF OFF $314
4th (default) ON ON OFF OFF OFF OFF OFF OFF $310
OFF OFF ON OFF OFF OFF OFF OFF $30C
ON OFF ON OFF OFF OFF OFF OFF $308
OFF ON ON OFF OFF OFF OFF OFF $304
ON ON ON OFF OFF OFF OFF OFF $300
OFF OFF OFF ON OFF OFF OFF OFF $21C
ON OFF OFF ON OFF OFF OFF OFF $218
OFF ON OFF ON OFF OFF OFF OFF $214
ON ON OFF ON OFF OFF OFF OFF $210
OFF OFF ON ON OFF OFF OFF OFF $20C
ON OFF ON ON OFF OFF OFF OFF $208
OFF ON ON ON OFF OFF OFF OFF $204
ON ON ON ON OFF OFF OFF OFF $200
Figure 1-4: DIP switch configuration of the MTS-P01.1 module
Note: In stand-alone and slave SPS, DIP switch 8 (boot lock) mustbe in position OFF (OPEN). Otherwise, the MTS-P01.1 willnot be operational.
1.4 SPS Inputs for the Machine Function Keys
The machine function keys are directly wired on the SPS module whenthe MTS-P01.1 unit is employed in an INDRAMAT industry PC of theBTV20 or BTV30 type. In the SPS they are addressed in the followingway:
Symbolic addressing first requires the symbolic identifier of the MFK_Rtype to be defined at the A#iMFK_R address in the declaration (exampleMKR).
Key Absolute addresses Symbolic addresses
R1 %,0.1481.0 MKR.R1
R2 %,0.1481.1 MKR.R2
.
.
.
.
.
.
.
.
.
R8 %,0.1481.7 MKR.R8
Figure 1-5: Addressing the right-hand machine function keys with BTV20/30
The BTV20 unit has additional machine function keys at the left-handside. These can be addressed as follows:
1-4 The INDRAMAT SPS MTS-P01.1 SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
Key Absolute addresses Symbolic addresses
L1 %,0.1480.0 MKL.L1
L2 %,0.1480.1 MKL.L2
.
.
.
.
.
.
.
.
.
L8 %,0.1480.7 MKL.L8
Figure 1-6: Addressing the left-hand machine function keys of BTV20
1.5 Rechargeable Battery
User-specific SPS data can be lost if an MTS-P01.1 module is not usedor stored for more than 6 months.
This affects the following data:
• SPS user program
• Retentive data
The rechargeable battery is recharged when an MTS-P01.1 module iscommissioned. A completely discharged battery requires the followingcharging times:
Charging time: 1 h -> approximately 100 h backup time
Charging time: 50 h -> approximately 5000 h backup time (fullbattery)
Under normal operating conditions, the service life of the rechargeablebattery is between 7 and 10 years. Continuous charging of therechargeable battery does not have a detrimental effect on the service life(continuous operation of the controller).
1.6 Installation
The MTS-P01.1 module is installed in a free ISA BUS slot. If possible, themodule should be secured to prevent it from getting loose due to vibrationor shocks. With the INDRAMAT BTV20/30 units, this is done by a cross-rail to which the modules are screwed and held down using the bracketprovided. The bracket is a part of the configured MTS-P01.1 module.
Before the MTS-P01.1 module can be installed in the PC, commissioningrequires some settings to be made that will be explained in the followingchapters.
Note: Depending on its configuration (i.e. additional PC104modules), an MTS-P01.1 module can occupy up to 5 slots in aPC (BTV20/30).
Affected data
Recharging the rechargeablebattery
SPS Module MTS-P01.1 The INDRAMAT SPS MTS-P01.1 1-5
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
1.7 Interface Pin Assignments
Pin Signal name Pin Signal name
1 DCD - Data Carrier Detect 2 RxD - Receive Data
3 TxD - Transmit Data 4 DTR - Data Terminal Ready
5 SGND - ground 6 DSR - Data Set Ready
7 RTS - Ready To Send 8 CTS - Clear To Send
9 RI - Ring Indicator
Figure 1-7: Connector pin assignments of the serial interface X2 (RS232 C)
Pin Signal name Pin Signal name
1 +5VDC 2 +5VDC
3 S0 4 S1
5 S2 6 S3
7 S4 8 S5
9 S6 10 S7
11 S8 12 S9
13 S10 14 S11
15 S12 16 S13
17 S14 18 S15
19 GND 20 GND
Figure 1-8: Connector pin assignments of the X3 connector (machine functionkeys)
1.8 Status Display and Fault Diagnosis
Operating state display
The 7-segment display H1 permits a diagnosis of the MTS-P01.1 moduleto be made. The following 1-digit error codes are used for indicating thediagnosis results.
Code Meaning
E Operational (SPS is running)
�� Power-on state (reset test)
)� Firmware in Flash EPROM invalid
-� Boot lock for firmware active
3� Local bus is not connected
Figure 1-9: Operating states of the MTS-P01.1
Note: Please notify Service immediately if any other 1-digit codewith a period is displayed.
1-6 The INDRAMAT SPS MTS-P01.1 SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
Error IndicationA 7-segment display that flashes in succession is used for displaying 3-digit error states. The shown error codes correspond to the system errormessages of the user MUI/GUI interface.
Code Meaning
��� Software version error
��� Self-test failed
��� Invalid SPS program
��� Maximum SPS cycle time exceeded
��� SPS operating voltage is low
��� Time-out 2 ms implementation
��� INTERBUS malfunction
��� INTERBUS memory overflow
��� INTERBUS configuration error
��� INTERBUS bus error
��� INTERBUS hardware/firmware error
��� INTERBUS I/O bus module error
��� INTERBUS not ready
��� INTERBUS general generation 4 error
Figure 1-10: Error codes of the MTS-P01.1 unit
SPS Module MTS-P01.1 INTERBUS Master Interface 2-1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
2 INTERBUS Master Interface
2.1 Brief Description of the IBM 2 Unit
X1
X8
X9
LK IBM 2
12345678
OFF
OFF ON
setting theI/O address
LK IBM2_Anschl.FH7
1 6
1 6
X60 INTERBUS interface (remote bus)
X64 INTERBUS diagnostics interface RS232 C
INTERBUSmodule
X60
X64
Figure 2-11: LK IBM 2
The IBM 2 board is a generation-4 INTERBUS master interface in thePC104 format. It is suitable for connecting devices, that range fromsimple sensors/actors up to intelligent field devices, via the INTERBUS.
The LK IBM2 unit has the following features:
• INTERBUS protocol (DIN E 19 258)
• up to 256 bus segments
2-2 INTERBUS Master Interface SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
• up to 16 device levels
• up to 512 devices per configuration
• up to 4096 inputs and 4096 outputs per configuration
• up to 32 INTERBUS loop devices per bus segment
• CMD G4 support
Configuration and parameter value assignment of the INTERBUS is donedirectly using the I/O configurator that is integrated in the SPSprogramming desktop.
In addition to the integrated INTERBUS diagnosis, the IBS CMD SWT G4(Phoenix-Contact) software can be used via the diagnosis interface.
Note: Configuring the INTERBUS via the IBS CMD SWT G4software is not possible.
2.2 Setting the I/O Address
In order to be able to address the IBM 2 board in a defined way, the S1DIP switch must be set as follows:
1 2 3 4 5 6 7 8 Address
OFF OFF ON OFF OFF ON OFF OFF 120h
Figure 2-12: Settings of the S1 DIP switch
2.3 Interface Pin Assignments
The following tables show the interface pin assignments:
Pin Signal name Pin Signal name
1 DCD - Data Carrier Detect 2 RxD - Receive Data
3 TxD - Transmit Data 4 DTR - Data Terminal Ready
5 SGND - ground 6 DSR - Data Set Ready
7 RTS - Ready To Send 8 CTS - Clear To Send
9 RI - Ring IndicatorFigure 2-13: Connector pin assignments of the INTERBUS diagnostics interface
X64 (RS232 C)
Pin Signal name Pin Signal name
1 DO 2 DI
3 GND - ground 4 NC
5 +5V 6 DO
7 DI 8 NC
9 RBST
Figure 2-14: Connector pin assignments of the INTERBUS interface X60 (remotebus)
SPS Module MTS-P01.1 PROFIBUS-DP Interfaces 3-1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
3 PROFIBUS-DP Interfaces
3.1 Brief description of the DPM01 and DPS01 BoardsA
13A
14A
15A
16A
17A
18A
19
1 100 101C A
0
LK DP_1_Anschl.FH7
PROFIBUS interface(master)
PROFIBUS diagnosticsinterface RS232 C(configuration interface)
PROFIBUS-DPmaster module
1 6
1 6SCL
DIAG
RUN
STA
RDY
ERR
LK DPM01 orLK DPS01
default setting ofI/O address $CA000
STA ERR RUN RDY
IRQ
15IR
Q 14
IRQ
12IR
Q 11
IRQ
10IR
Q 3
IRQ
4IR
Q 5
IRQ
6IR
Q 7
IRQ
9A 13A 14A 15A 16A 17A 18A 19
PROFIBUS-DPslave module
1 6
1 6SCL
DIAG
RUN
STA
RDY
ERR
PROFIBUS interface(slave)
PROFIBUS diagnosticsinterface RS232 C(configuration interfacee)
Figure 3-15: LK DPM01 and DPS01
The DPM01 (Master) and DPS01 (Slave) boards are intelligentPROFIBUS-DP interfaces in the PC104 format. They are used forhandling communication protocols between the SPS and remote I/O units.The integrated microprocessor enables the full data transfer to beperformed automatically, thus relieving the SPS from time-critical tasks.
An 8-kB dual-port memory (DPM) is used for exchanging the databetween the SPS and a DPM01 or DPS01 board. This is a memory that
3-2 PROFIBUS-DP Interfaces SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
can be accessed both by the SPS and by the microprocessor on aDPM01 or DPS01 board.
The PROFIBUS-DP master interface LK DPM01 permits up to 32PROFIBUS-DP device to be connected within a bus segment. If severalbus segments are interconnected via a repeater, up to 125 slaves can beserved in a maximum configuration. Each repeater reduces the maximumnumber of slaves within a segment. Being a passive device, the receiverdoes not have a device address assigned.
The DP slave can be provided with a maximum of 368 bytes I/O in theprocess image. A maximum of 244 Bytes thereof may be I or O. Each DPmaster possesses a maximum of 512 Bytes I/O in the process image.Depending on the selected baud rate, a maximum distance of 1200 m ispossible between the Profibus-DP devices. At a baud rate of 1.5 Mbits/s,the distance is reduced to 200 m, and at 12 Mbits/s to 100 m.
Note: To ensure proper functioning of the PROFIBUS interface, onlycables are allowed that comply with the PROFIBUSspecification RS485 (cable type A).
3.2 Setting the I/O Addresses
The bus address is selected via the jumpers of the J2 jumper array. Theaddress line is shown next to each plug-in jumper.
Depending on the expansion slot, the addresses must be set as follows(X = jumper inserted):
Slot Address A19 A18 A17 A16 A15 A14 A13
1 $CA000 X X X
2 $CC000 X X X
Figure 3-16: Setting the I/O Address
SPS Module MTS-P01.1 PROFIBUS-DP Interfaces 3-3
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
3.3 Status and Diagnosis Indicators
When a DPM01 or DPS01 board is switched on, it first executes a self-test. The two LEDs ERR and STA extinguish after the initialization phase(2 to 3 seconds). The yellow RDY LED lights up after the self-test hasbeen passed. If a malfunction has been detected, the RDY LED startsblinking and program execution is aborted. The other meanings of theindicators are shown in the following overview:
RDY yellow LED Ready
ON: DPM01 or DPS01 is operational
Blinks cyclically Bootstrap loader is active
Blinks unregularly Hardware and/or system fault
OFF: Hardware defect
RUN green LED RUN (communication)
ON: Communication is running
Blinks cyclically: Ready for communication
Blinks irregularly: Incorrect configuration
OFF: No communication
ERR red LED Error
ON: Error in communication interface
OFF: Communication interface OK
STA yellow LED Status
ON: Data exchange with slaves is active(master)
Data exchange with master is active (slave)
OFF: No data exchange
3.4 Specifications
Power supply
Operating voltage: +5VDC, ±5% / 650 mA
Interface data
Communication interface: PROFIBUS-DP, max 12 Mbits/s, floating
Diagnostics interface: RS 232C, 9600 bits/s
Operating conditions
Operating temperature: 0°C - +55°C
Storage temperature: -40°C - +85°C
Humidity: max. 75%, no condensation
3-4 PROFIBUS-DP Interfaces SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
3.5 Interface Pin Assignments
The following tables show the interface pin assignments:
PIN Signal name PIN Signal name
1 NC 2 RxD - Receive Data
3 TxD - Transmit Data 4 DTR - Data Terminal Ready
5 GND - signal ground 6 NC
7 RTS - Ready To Send 8 CTS - Clear To Send
9 NCFigure 3-17: Connector pin assignments of diagnostics interface RS 232C
(DIAG)
PIN Signal name PIN Signal name
1 RGND - reference potential 2 NC
3 RxD/TxD-P - transmit/receive 4 NC
5 DGND - reference potential 6 VP - power supply, plus
7 NC 8 RxD/TxD-N - transmit/receive
9 NCFigure 3-18: Connector pin assignments PROFIBUS interface (SCL)
SPS Module MTS-P01.1 Serial Interface 4-1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
4 Serial Interface
4.1 Brief Description
The SIO 04-B board can be used for providing the SPS user program withup to four general-purpose serial interface. The serial interfaces areinterrupt-controlled through the SPS firmware.
The transmit and receive data of each interface is provided in 256-bytebuffers. Using these buffers, the SPS user program communicatesindirectly with the interfaces via the function blocks provided.
RS232 Cmodule
X35 interface RS232 C DEVICE: 0 SERNR: 1
1 6
1 6
X40 interface RS422 DEVICE: 0 SERNR: 3
1 6
1 6
RS422module
X36 interface RS232 C DEVICE: 0 SERNR: 2
X41 interface RS422 DEVICE: 0 SERNR: 4
LK SIO04-B_Anschl.FH7
X36
X35
X41
X40
LK SIO 04-BRS 232 C
RS 232 C
RS 422
RS 422
Figure 4-19: LK SIO 04-B
4-2 Serial Interface SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
4.2 Addresses and Interrupt Settings
CH
0C
H1
CH
2C
H3
CH0
CH1
CH2
CH3
IRQ
2IR
Q3
IRQ
4IR
Q5
IRQ
6IR
Q7
IRQ
10IR
Q11
IRQ
12IR
Q14
IRQ
15N
ON
E
W5
W57
W63 W61 W62
W44
W58/59/60
LK SIO 04-B
RS 232 C
RS 232 C
RS 422
RS 422
X1
LK SIO04-B_Einstell.FH7
Figure 4-20: Jumper settings on the LK SIO 04-B module
Function Blocks
Name Comment
OPEN_COM Opens a serial interface
CLOSE_COM Closes a serial interface
RD_BYTE Read byte from receive buffer
WR_BYTE Write byte to transmit buffer
RD_STRING Read string from receive buffer
WR_STRING Write string to transmit bufferFigure 4-21: Function blocks for interface handling
The parameter value assignment of the blocks requires the COM datatype that gives a more detailed description of the serial interface (e. g.DEVICE, SERNR, BAUDRATE etc.). Please refer to the "SPS InstructionSet" document for a detailed description of the function blocks.
SPS Module MTS-P01.1 Serial Interface 4-3
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
4.3 Specifications
Power supply
Supply voltage: 4.5 - 5.5 VDC
Current consumption: max. 250 mA
Interface data
Input capacitance: max. 15 pF
Input leakage current: max. 5 µA
Output capacitance: min.150 pF
Output current (active 0 switching): min. 12 mA
Operating conditions
Operating temperature: 0°C - +70°C
Storage temperature: -40°C - +85°C
Humidity: max. 75%, no condensation
4.4 Interface Pin Assignments
The serial interfaces have the following pin assignments:
PIN Signal name PIN Signal name
1 DCD - Data Carrier Detect 2 RxD - Receive Data
3 TxD - Transmit Data 4 DTR - Data Terminal Ready
5 SGND - ground 6 DSR - Data Set Ready
7 RTS - Ready To Send 8 CTS - Clear To Send
9 RI - Ring Indicator
Figure 4-22: Connector pin assignments RS 232C X35,X36
PIN Signal name PIN Signal name
1 GND - Frame Ground 2 No Connection
3 TxD A - Transmit Data 4 RxD A - Receive Data
5 SGND - Signal ground 6 RxD B - Receive Data
7 RTS - Ready To Send 8 CTS - Clear To Send
9 TxD B - Transmit Data
Figure 4-23: Connector pin assignments RS422 X40,X41
SPS Module MTS-P01.1 I/O Module 5-1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
5 I/O Module
5.1 Brief Description
The PEA 4/01 board is an input/output board in the PC104 format. Itpossesses 16 inputs and 16 outputs with TTL level. Thus, it is suitable fora direct connection of the machine control keys (including keyswitch) ofthe BTV20 unit.
setting theI/O addresses
(e.g. slot 1)
LK PEA4_Adress.FH7
LK PEA 4/01X1
X9
X8
OP
EN
18
S1
12
34
56
78
OP
EN
OFFON
Figure 5-24: LK PEA 4/01
5.2 Setting the I/O Address
Depending on the PC104 slot (1-4 possible), the I/O addresses areselected at the DIP switch S1. Bits 1...5 are used for address selection.Bits 6 and 7 are without a function.
Note: Bit 8 must always be ON. The card cannot function properly ifthis is not the case.
PC104 slot S1.1 S1.2 S1.3 S1.4 S1.5 Output Input Output Enable
1 OFF OFF OFF OFF ON 02F0h 02F4h 02F9h
2 ON OFF OFF OFF ON 0300h 0304h 0309h
3 OFF ON OFF OFF ON 0310h 0314h 0319h
4 ON ON OFF OFF ON 0320h 0324h 0329h
Figure 5-25: Setting the DIP switch S1, bit 1 through bit 5
5-2 I/O Module SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
5.3 Addressing the PEA 4/01 Board
Machine function keys, lamps, keyswitch and indicators of the BTV20 unitare addressed by assigning one logical device number to the inputs andone to the outputs in the SPS I/O configurator.
The following addresses result, for example:
• 10 = Logical device number of the inputs
• 11 = Logical device number of the outputs
%I10.0.0 %I10.0.1 %I10.0.2 %I10.0.3 %I10.0.4 %I10.0.5 %I10.0.6
%I10.0.7 %I10.1.0 %I10.1.1 %I10.1.2 %I10.1.3 %I10.1.4 %I10.1.5
%Q11.1.7%Q11.1.6
%Q11.0.0
%Q11.0.7
%Q11.0.1
%Q11.1.0
%Q11.0.2
%Q11.1.1
%Q11.0.3
%Q11.1.2
%Q11.0.4
%Q11.1.3
%Q11.0.5
%Q11.1.4
%Q11.0.6
%Q11.1.5LK PEA4_MFK-Tast.FH7
%I10.1.6 %I10.1.7
Figure 5-26: Input and output addresses of the machine function keys in theBTV20 unit
5.4 Specifications
Supply voltage: 4.5 - 5.5VDC
Current consumption: max. 1A
Operating temperature: 0°C - 60°C
5.5 Connector pin assignments of I/O connector
Pin Function
X1.1 - X1.4 Supply voltage VCC
X1.5 - X1.20 Input (0....15)
X1.21 - X1.36 Output (0....15)
X1.37 - X1.40 GNDFigure 5-27: Connector pin assignments of X1
SPS Module MTS-P01.1 Configurations 6-1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
6 Configurations
6.1 MTS-P01.1-**-B1-E1-NN-NN-FW
X2
X1
X6X3
X8X9
SPS module
INTERBUSmodule
12X5
X10
H1
X2
X1
8.
X5
S1
I/O module
X60
X64
LK IBM 2
MTS-P01_B1-E1.FH7
140
09,5
110
122
280
17,5
17,5
1,5
13
LK PEA 4
PC/104 expansion slot
machine function keys
LK MTS 2
watchdog: SPS Ready(stand-alone SPS only)
SPSmodule
INTERBUSmodule
INDRAMAT local bus(with slave SPS only)
124
ribbon cable to theBTV20 front panel
(machine control keys)
Figure 6-28: Structure of the MTS-P01.1-**-B1-E1-NN-NN-FW configuration
6-2 Configurations SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
6.2 MTS-P01.1-**-B1-S4-NN-NN-FW
X2
X1
X6X3
X8X9
12X5
X10
S1
LK IBM 2
MTS-P01_B1-S4.FH7
H1
X2
X1
8.
X5
X60
X64
X41
X40
X36
X35
RS232module
watchdog: SPS ready(with stand-alone SPS only)
SPSmodule
INTERBUSmodule
RS422module
LK SIO 04-BCH0
CH1
CH2
CH3
140
09,5
110
122
280
17,5
17,5
1,5
13
PC/104 expansion slot
machine function keys
LK MTS 2
INDRAMAT local bus(with slave SPS only)
124
SPS module
INTERBUSmodule
RS 232 Cinterfaces
RS 422interfaces
Figure 6-29: Structure of the MTS-P01.1-**-B1-S4-NN-NN-FW configuration
SPS Module MTS-P01.1 Configurations 6-3
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
6.3 MTS-P01.1-**-B1-S4-E1-NN-FW
E/A module
X2
X1
X6X3
X8X9
12X5
X10
S1
LK IBM 2
H1
X2
X1
8.
X5
X60
X64
X41
X40
X36
X35
RS232module
watchdog: SPS eeady(with stand-alone SPS only)
SPSmodule
INTERBUSmodule
RS422module
MTS-P01_B1-S4-E1.FH7
LK SIO 04-BCH0
CH1
CH2
CH3
LK PEA 4
140
09,5
110
122
280
17,5
17,5
1,5
17,5
13
ribbon cable to theBTV20 front panel
(machine control keys)
PC/104 expansion slot
machine function keys
LK MTS 2
INDRAMAT local bus(with slave SPS only)
124
SPS module
INTERBUS-module
RS 232 Cinterfaces
RS 422interfaces
Figure 6-30: Structure of the MTS-P01.1-**-B1-S4-E1-NN-FW configuration
6-4 Configurations SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
6.4 MTS-P01.1-**-P1-E1-NN-NN-FW
X2
X1
X6X3
X8X9
12X5
X10
S1
H1
X2
X1
8.
X5
LK IBM 2
MTS-P01_P1-S4.FH7
X41
X40
X36
X35
1 6
1 6SCL
DIAG
RUN
STA
RDY
ERR
LK SIO 04-BCH0
CH1
CH2
CH3
140
09,5
110
122
280
17,5
17,5
1,5
13
PC/104 expansion slot
machine function keys
LK MTS 2
INDRAMAT local bus(with slave SPS only)
124
SPS module
PROFIBUS module
RS 232 Cinterfaces
RS 422interfaces
RS232module
watchdog: SPS ready(with stand-alone SPS only)
SPSmodule
PROFIBUSmodule
RS422module
Figure 6-31: Structure of the MTS-P01.1-**-P1-S4-NN-NN-FW configuration
SPS Module MTS-P01.1 Accessories 7-1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
7 Accessories
7.1 List of Connectors and Cable Sets
Order number Mating connector ofthe unit
INDRAMAT cable Cable end
IKB0005
MN: 278 141, 2m
MN: 278 144, 5m
MN: 278 142, 10m
MN: 278 143, 15m
(RS232, max. 15m)
INS526INS439
INK572
15-way/male9-way/female
IKB0012/000,0
MN: 281 715
(RS232, max. 15m)
INS439
INS588
INK572
9-way/female
15-way/male
IKS106/000,0
MN: 260 838
(RS232, max. 15m)
INS588
INK572
INS526
9-way/female9-way/female
IKS0056/000,0
MN: 255 968
(INTERBUS, max. 400m)
INK234
INS525 INS526
9-way/female9-way/male
INS0540/K01
MN: 279 538
INS0540/Profibus (male)
Profibus connector forbuilding cables with active
termination.
INS0541/K01
MN: 279 539
INS541/Profibus (male/female)
Profibus connector forbuilding cables with active
termination.
(mounting side-by-sidepossible)
Figure 7-32: MTS-P accessories
SPS Module MTS-P01.1 Type Code 8-1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
8 Type Code
Comment:Configuration 1 through 4B1 = INTERBUS master moduleE1 = INPUT/OUTPUT module for integrated
control panel (BTV20)NN = emptyP1 = PROFIBUS-DP master moduleP2 = PROFIBUS-DP slave moduleS4 = Serial interface module (2xRS232 + 2xRS422/485)
1
1. Product group1.1 MTS. . . . . . . . . . = MTS
2. Enclosure2.1 for industry PC . . . . . . . . . . = P
3. Series3.1 1 . . . . . . . . . . . . . . . . . . . . . . . = 01
4. Version4.1 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . = 1
5. Function type5.1 Master. . . . . . . . . . . . . . . . . . . . . . . . . . . . = M5.2 Slave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . = S
6. Main memory size6.1 1MB-RAM. . . . . . . . . . . . . . . . . . . . . . . . . . . . = 1
7. Configuration7.1 B1-E1-NN-NN7.2 B1-NN-NN-NN7.3 B1-S4-E1-NN7.4 B1-S4-NN-NN7.5 E1-NN-NN-NN7.6 NN-NN-NN-NN7.7 P1-E1-NN-NN7.8 P1-NN-NN-NN7.9 P1-S4-E1-NN7.10 P1-S4-NN-NN7.11 P1-P2-E1-NN7.12 P1-P2-NN-NN7.13 P1-P2-S4-E17.14 P1-P2-S4-NN
8. Firmware8.1 Code that firmware must be ordered as a separate subitem. . . = FW
1 2 3 4 6 7 8 9105 1 2 3 4 6 7 8 9
205 1 2 3 4 6 7 8 9
305
Example:
Brief textcolumn
1
Figure 8-33: Type code
SPS Module MTS-P01.1 Figures 9-1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
9 Figures
Figure 1-1: MTS-P01.1 without additional interfaces 1-1Figure 1-2: Front view of the MTS-P01.1 unit 1-2Figure 1-3: Location of the address switch 1-2Figure 1-4: DIP switch configuration of the MTS-P01.1 module 1-3Figure 1-5: Addressing the right-hand machine function keys with
BTV20/30 1-3Figure 1-6: Addressing the left-hand machine function keys of BTV20 1-4Figure 1-7: Connector pin assignments of the serial interface X2
(RS232 C) 1-5Figure 1-8: Connector pin assignments of the X3 connector (machine
function keys) 1-5Figure 1-9: Operating states of the MTS-P01.1 1-5Figure 1-10: Error codes of the MTS-P01.1 unit 1-6Figure 2-11: LK IBM 2 2-1Figure 2-12: Settings of the S1 DIP switch 2-2Figure 2-13: Connector pin assignments of the INTERBUS
diagnostics interface X64 (RS232 C) 2-2Figure 2-14: Connector pin assignments of the INTERBUS interface
X60 (remote bus) 2-2Figure 3-15: LK DPM01 and DPS01 3-1Figure 3-16: Setting the I/O Address 3-2Figure 3-17: Connector pin assignments of diagnostics interface
RS 232C (DIAG) 3-4Figure 3-18: Connector pin assignments PROFIBUS interface (SCL) 3-4Figure 4-19: LK SIO 04-B 4-1Figure 4-20: Jumper settings on the LK SIO 04-B module 4-2Figure 4-21: Function blocks for interface handling 4-2Figure 4-22: Connector pin assignments RS 232C X35,X36 4-3Figure 4-23: Connector pin assignments RS422 X40,X41 4-3Figure 5-24: LK PEA 4/01 5-1Figure 5-25: Setting the DIP switch S1, bit 1 through bit 5 5-1Figure 5-26: Input and output addresses of the machine function
keys in the BTV20 unit 5-2Figure 5-27: Connector pin assignments of X1 5-2Figure 6-28: Structure of the MTS-P01.1-**-B1-E1-NN-NN-FW
configuration 6-1Figure 6-29: Structure of the MTS-P01.1-**-B1-S4-NN-NN-FW
configuration 6-2Figure 6-30: Structure of the MTS-P01.1-**-B1-S4-E1-NN-FW
configuration 6-3Figure 6-31: Structure of the MTS-P01.1-**-P1-S4-NN-NN-FW
configuration 6-4Figure 7-32: MTS-P accessories 7-1Figure 8-33: Type code 8-1
SPS Module MTS-P01.1 Service Agencies
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
Sales & Service Facilities
Germany from abroad: don’t dial (0) after country code!
Vertriebsgebiet Mitte Germany Centre V/S Service
INDRAMAT GmbHBgm.-Dr.-Nebel-Str. 2D - 97816 Lohr am Main
Phone: +49 (0)9352/40-0Fax: +49 (0)9352/40-4885
Vertriebsgebiet Ost Germany East V/S Service
INDRAMAT GmbHBeckerstraße 31D - 09120 Chemnitz
Phone: +49 (0)371/35 55-0Fax: +49 (0)371/35 55-333
Vertriebsgebiet West Germany West V/S Service
INDRAMAT GmbHHarkortstraße 25D - 40849 Ratingen
Phone: +49 (0)2102/43 18-0Fax: +49 (0)2102/41 315
Vertriebsgebiet Nord Germany North V/S Service
INDRAMAT GmbHKieler Straße 212D - 22525 Hamburg
Phone: +49 (0)40/85 31 57-0Fax: +49 (0)40/85 31 57-15
Vertriebsgebiet Süd Germany South V/S Service
INDRAMAT GmbHRidlerstraße 75D-80339 München
Phone: +49 (0)89/540138-30Fax: +49 (0)89/540138-10
Gebiet Südwest Germany South-West V/S Service
INDRAMAT GmbHBöblinger Straße 25D-71229 Leonberg
Phone: +49 (0)7152/9 72-6Fax: +49 (0)7152/9 72-727
INDRAMAT Service-Hotline
INDRAMAT GmbHPhone: +49 (0)172/660 04 06
or
Phone: +49 (0)171/333 88 26
Service agencies in Germany
Service Agencies SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
Europe from abroad: don’t dial (0) after country code, dial 0 after country code!
Austria V/S Service
Mannesmann Rexroth Ges.m.b.H.Geschäftsbereich INDRAMATHägelingasse 3A - 1140 Wien
Phone: +43 (0)1/9852540-400Fax: +43 (0)1/9852540-93
Austria V/S Service
Mannesmann Rexroth G.m.b.H.Geschäftsbereich INDRAMATIndustriepark 18A - 4061 Pasching
Phone: +43 (0)7221/605-0Fax: +43 (0)7221/605-21
Belgium V/S Service
Mannesmann Rexroth N.V.-S.A.Geschäftsbereich INDRAMATIndustrielaan 8B-1740 Ternat
Phone: +32 (0)2/5823180Fax: +32 (0)2/5824310
Denmark V/S Service
BEC ASZinkvej 6DK-8900 Randers
Phone: +45 (0)87/11 90 60Fax: +45 (0)87/11 90 61
United KingdomV/S Service
Mannesmann Rexroth Ltd.INDRAMAT Division4 Esland Place, Love LaneGB - Cirencester, Glos GL7 1YG
Phone: +44 (0)1285/658671Fax: +44 (0)1285/654991
Finland V/S Service
Rexroth Mecman OYAnsatie 6SF-017 40 Vantaa
Phone: +358 (0)9/84 91 11Fax: +358 (0)9/84 91 13 60
France V/S Service
Mannesmann Rexroth S.A.Division INDRAMATParc des Barbanniers4, Place du VillageF-92632 Gennevilliers Cedex
Phone: +33 (0)141 47 54 30Fax: +33 (0)147 94 69 41Hotline: +33 (0)6 08 33 43 28
France V/S Service
Mannesmann Rexroth S.A.Division INDRAMAT270, Avenue de LardenneF - 31100 Toulouse
Phone: +33 (0)5 61 49 95 19Fax: +33 (0)5 61 31 00 41
France V/S Service
Mannesmann Rexroth S.A.Division INDRAMAT91, Bd. Irène Joliot-CurieF - 69634 Vénissieux - Cedex
Phone: +33 (0)4 78 78 53 65Fax: +33 (0)4 78 78 52 53
Italy V/S Service
Mannesmann Rexroth S.p.A.Divisione INDRAMATVia G. Di Vittoria, 1I - 20063 Cernusco S/N.MI
Phone: +39 02/92 36 52 70Fax: +39 02/92 36 55 12
Italy V/S Service
Mannesmann Rexroth S.p.A.Divisione INDRAMATVia Borgomanero, 11I - 10145 Torino
Phone: +39 011/7 71 22 30Fax: +39 011/7 71 01 90
Italy V/S Service
Mannesmann Rexroth S.p.A.Divisione INDRAMATVia del Progresso, 16 (Zona Ind.)I - 35020 Padova
Phone: +39 049/8 70 13 70Fax: +39 049/8 70 13 77
Italy V/S Service
Mannesmann Rexroth S.p.A.Divisione INDRAMATVia de Nicola, 12I - 80053 Castellamare di Stabbia NA
Phone: +39 081/8 72 30 37Fax: +39 081/8 72 30 18
Italy V/S Service
Mannesmann Rexroth S.p.A.Divisione INDRAMATViale Oriani, 38/AI - 40137 Bologna
Phone: +39 051/34 14 14Fax: +39 051/34 14 22
Netherlands V/S Service
Hydraudyne Hydrauliek B.V.Kruisbroeksestraat 1P.O. Box 32NL - 5281 RV Boxtel
Phone: +31 (0)411/65 19 51Fax: +31 (0)411/65 14 83e-mail: [email protected]
Netherlands V/S Service
Hydrocare B.V.Kruisbroeksestraat 1P.O. Box 32NL - 5281 RV Boxtel
Phone: +31 (0)411/65 19 51Fax: +31 (0)411/67 78 14
Poland V/S Service
Mannesmann Rexroth Sp.zo.o.Biuro Poznanul. Dabrowskiego 81/85PL – 60-529 Poznan
Phone: +48 061/847 67 99Fax: +48 061/847 64 02
Spain V/S Service
Mannesmann Rexroth S.A.Divisiòn INDRAMATCentro Industrial SantigaObradors s/nE-08130 Santa Perpetua de MogodaBarcelona
Phone: +34 937 47 94 00Fax: +34 937 47 94 01
Spain V/S Service
Goimendi S.A.División IndramatJolastokieta (Herrera)Apartado 11 37E - 20017 San Sebastian
Phone: +34 9 43/40 01 63Fax: +34 9 43/39 17 99
Sweden V/S Service
Rexroth Mecman Svenska ABINDRAMAT DivisionVaruvägen 7S - 125 81 Stockholm
Phone: +46 (0)8/727 92 00Fax: +46 (0)8/64 73 277
Switzerland - East V/S Service
Mannesmann Rexroth AGGeschäftsbereich INDRAMATGewerbestraße 3CH-8500 Frauenfeld
Phone: +41 (0)52/720 21 00Fax: +41 (0)52/720 21 11
Switzerland - West V/S Service
Mannesmann Rexroth SADépartement INDRAMATChemin de l`Ecole 6CH-1036 Sullens
Phone: +41 (0)21/731 43 77Fax: +41 (0)21/731 46 78
Russia V/S Service
Tschudnenko E.B.Arsenia 22RUS - 153000 IvanovoRußland
Phone: +7 093/223 96 33oder/or +7 093/223 95 48Fax: +7 093/223 46 01
Slowenia V/S Service
INDRAMAT elektromotorji d.o.o.Otoki 21SLO - 64 228 Zelezniki
Phone: +386 64/61 73 32Fax: +386 64/64 71 50
Turkey V/S Service
Mannesmann Rexroth Hidropar A..S.Fevzi Cakmak Cad No. 3TR - 34630 Sefaköy Istanbul
Phone: +90 212/541 60 70Fax: +90 212/599 34 07
European Service agencies (without Germany)
SPS Module MTS-P01.1 Service Agencies
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
Outside Europe from abroad: don’t dial (0) after country code!
Argentina V/S Service
Mannesmann Rexroth S.A.I.C.Division INDRAMATAcassusso 48 41/7RA - 1605 Munro (Buenos Aires)
Phone: +54 (0)1/756 01 40+54 (0)1/756 01 36
Argentina V/S Service
NAKASEAsesoramiento TecnicoCalle 49, No. 5764-66RA - 1653 Villa BalesterProvincia de Buenos Aires
Phone: +54 (0) 1/768 36 43Fax: +54 (0) 1/768 24 13e-mail: Fehler! Textmarke nichtdefiniert.net
Australia V/S Service
AIMS - Australian IndustrialMachinery Services Pty. Ltd.Unit 3/45 Horne STCampbellfield 3061AUS - Melbourne, VIC
Phone: +61 (0)3/93 59 02 28Fax: +61 (0)3/93 59 02 86
Brazil V/S Service
Mannesmann RexrothAutomação Ltda.Divisão INDRAMATRua Georg Rexroth, 609Vila Padre AnchietaBR - 09951-270 Diadema-SP[ Caixa Postal 377 ][ BR-09901-970 Diadema-SP ]
Phone: +55 (0)11/745 90 60+55 (0)11/745 90 70
Fax: +55 (0)11/745 90 50
Brazil V/S Service
Mannesmann RexrothAutomação Ltda.Divisão INDRAMATRua Umberto Pinheiro Vieira, 100Distrito IndustrialBR - 09220-390 Joinville - SC[ Caixa Postal 1273 ]
Tel./Fax: +55 (0)47/473 55 833Mobil: +55 (0)47 974 6645e-mail: [email protected]
Canada V/S Service
Basic Technologies CorporationBurlington Division3426 Mainway DriveBurlington, OntarioCanada L7M 1A8
Phone: +1 905/335 55 11Fax: +1 905/335-41 84
China V/S Service
Mannesmann Rexroth (China) Ldt.Shanghai Office - Room 206Shanghai Internat. Trade Centre2200 Yanan Xi LuPRC - Shanghai 200335
Phone: +86 21/62 75 53 33Fax: +86 21/62 75 56 66
China V/S Service
Mannesmann Rexroth (China) Ldt.Shanghai Parts & Service Center199 Wu Cao Road, Hua CaoMinhang DistrictPRC - Shanghai 201 103
Phone: +86 21/62 20 00 58Fax: +86 21/62 20 00 68
China V/S Service
Mannesmann Rexroth (China) Ldt.15/F China World Trade Center1, Jianguomenwai AvenuePRC - Beijing 100004
Phone: +86 10/65 05 03 80Fax: +86 10/65 05 03 79
China V/S Service
Mannesmann Rexroth (China) Ldt.A-5F., 123 Lian Shan StreetSha He Kou DistrictPRC - Dalian 116 023
Phone: +86 411/46 78 930Fax: +86 411/46 78 932
Hong KongV/S Service
Rexroth (China) Ldt.19 Cheung Shun Street1st Floor, Cheung Sha Wan,Kowloon, Hong Kong
Phone: +852 22 62 51 00Fax: +852 27 41 33 44
India V/S Service
Mannesmann Rexroth (India) Ltd.INDRAMAT DivisionPlot. 96, Phase IIIPeenya Industrial AreaIND - Bangalore - 560058
Phone: +91 (0)80/8 39 21 01Fax: +91 (0)80/8 39 43 45
India V/S Service
Mannesmann Rexroth (India) Ltd.INDRAMAT DivisionPlot. A-58, TTC Industrial AreaThane Turbhe Midc RoadMahape VillageIND - Navi Mumbai - 400 701
Phone: +91 (0)22/7 61 46 22Fax: +91 (0)22/7 68 15 31
Indonesia V/S Service
PT. Rexroth WijayakusumaJl. Raya Bekasi Km 21PulogadungRI - Jakarta Timur 13920
Phone: +62 21/4 61 04 87+62 21/4 61 04 88
Fax: +62 21/4 60 01 52
Japan V/S Service
Rexroth Automation Co., Ltd.INDRAMAT Division1F, I.R. BuildingNakamachidai 4-26-44Tsuzuki-ku, YOKOHAMA224-0041 Japan
Phone: +81 459/42-72 10Fax: +81 459/42-03 41
Japan V/S Service
Rexroth Automation Co., Ltd.INDRAMAT DivisionYutakagaoka 1810Meito-ku, NAGOYA465-0035 Japan
Phone: +81 (0)52/777 88 41+81 (0)52/777 88 53+81 (0)52/777 88 79
Fax: +81 (0)52/777 89 01
Mexico V/S Service
Rexroth Mexico S.A. de C.V.Calle Neptuno 72Unidad Ind. VallejoMEX - 07700 Mexico, D.F.
Phone: +52 5 754 17 11+52 5 754 36 84+52 5 754 12 60
Fax: +52 5 754 50 73+52 5 752 59 43
Korea V/S Service
Mannesmann Rexroth-Seki Co Ltd.1500-12 Da-Dae-DongROK - Saha-Ku, Pusan, 604-050
Phone: +82 (0)51/2 60 06 18Fax: +82 (0)51/2 60 06 19
Korea V/S Service
Seo Chang Corporation Ltd.Room 903, Jeail Building44-35 Yeouido-DongYeoungdeungpo-KuC.P.O.Box 97 56ROK - Seoul
Phone: +82 (0)2/7 80 82 08+82 (0)2/7 80 82 09
Fax: +82 (0)2/7 84 54 08
South Africa V/S Service
HYTEC Automation (Pty) Ltd.28 Banfield Road,Industria NorthRSA - Maraisburg 1700
Phone: +27 (0)11/673 20 80Fax: +27 (0)11/673 72 69
Taiwan V/S Service
Rexroth Uchida Co., Ltd.No.1, Tsu Chiang StreetTu Cheng Ind. EstateTaipei Hsien, Taiwan, R.O.C.
Phone: +886 2/2 68 13 47Fax: +886 2/2 68 53 88
Service agencies outside Europe
Service Agencies SPS Module MTS-P01.1
DOK-CONTRL-MTS-P01.1**-PR02-EN-P
Outside Europe / USA
USA V/S Service
Mannesmann Rexroth CorporationINDRAMAT Division5150 Prairie Stone ParkwayUSA -Hoffman Estates, IL 60192-3707
Phone: +1 847/6 45 36 00Fax: +1 847/6 45 62 01
USA V/S Service
Mannesmann Rexroth CorporationINDRAMAT DivisionCentral Region Technical CenterUSA - Auburn Hills, MI 48326
Phone: +1 248/3 93 33 30Fax: +1 248/3 93 29 06
USA V/S Service
Mannesmann Rexroth CorporationINDRAMAT DivisionSoutheastern Technical Center3625 Swiftwater Park DriveUSA - SuwaneeGeorgia 30174
Phone: +1 770/9 32 32 00+1 770/9 32 19 03
USA V/S Service
Mannesmann Rexroth CorporationINDRAMAT DivisionNortheastern Technical Center99 Rainbow RoadUSA - East Granby,Connecticut 06026
Phone: +1 860/8 44 83 77+1 860/8 44 85 95
USA V/S Service
Mannesmann Rexroth CorporationINDRAMAT DivisionCharlotte Regional Sales Office14001 South Lakes DriveUSA - Charlotte,North Carolina 28273
Phone: +1 704/5 83 97 62+1 704/5 83 14 86
Service agencies outside Europe / USA