HAZARD CATEGORIES AND SPECIAL SYMBOLS
Read these instructions carefully and look at the equipment to becomefamiliar with the device before trying to install, operate, service, or maintainit. The following special messages may appear throughout this bulletin or onthe equipment to warn of potential hazards or to call attention to informationthat clarifies or simplifies a procedure.
The addition of either symbol to a Danger or Warning safety labelindicates that an electrical hazard exists which will result in personal injury ifthe instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personalinjury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
Danger indicates an immediately hazardous situation which, if notavoided, will result in death or serious injury.
Warning indicates a potentially hazardous situation which, if notavoided, can result in death or serious injury.
Caution indicates a potentially hazardous situation which, if notavoided, can result in minor or moderate injury.
Caution, used without the safety alert symbol, indicates a potentiallyhazardous situation which, if not avoided, can result in propertydamage or improper operation.
NOTE: Provides additional information to clarify or simplify a procedure.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
3/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 3
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel. This document is not intended as an instructionmanual for untrained persons. No responsibility is assumed by Square D forany consequences arising out of the use of this manual.
Class B FCC Statement
This equipment has been tested and found to comply with the limits for aClass B digital device, pursuant to Part 15 of the FCC Rules. These limitsare designed to provide reasonable protection against harmful interferencein a residential installation. This equipment generates, uses, and can radiateradio frequency energy and, if not installed and used in accordance with theinstructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particularinstallation. If this equipment does cause harmful interference to radio ortelevision reception, which can be determined by turning the equipment offand on, the user is encouraged to try to correct the interference by one ormore of the following measures:
Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
4/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
4 2007 Schneider Electric. All Rights Reserved.
INTRODUCTION
This bulletin provides instructions for installing Square DClipsal
Eight-Channel DIN-Rail Dimmers, which are C-Bus-controlledoutput units suitable for use with incandescent lighting or compatiblelow-voltage lighting. These dimmer units automatically compensatefor voltage and frequency fluctuations and employ advancedphase-control techniques to reduce flicker and increase lamp life.
Each dimmer channel can independently control loads of2 A @ 120 V AC. As part of a channel group (channels 14 or 58),a channel also can carry loads up to 3 A @ 120 V AC, so long asthe load rating per channel group is no greater than 8 A.
At 12M wide (1M = 0.69 in. [17.5 mm]), the dimmers are designedfor mounting in suitable DIN-style enclosures, such as the Clipsal36M enclosure. Built-in RJ-45 connectors enable quick connectionto the C-Bus network and interconnection of units. The units can beconfigured by using Learn mode or the C-Bus Toolkit software.
These dimmer units can be ordered with an internal C-Bus networkpower supply. When connected to an external power source, unitsincorporating the C-Bus power supply (catalog numberSLC5508TD2A) can support a number of other C-Bus units by
providing up to 200 mA to the network.
The standard dimmer units (catalog number SLC5508TD2AP) donot provide power to the network, even when they are connected toan external electrical power source.
Before You Begin
Before installing an eight-channel DIN-rail dimmer, verify that yourorder is complete by comparing the contents of the package with theappropriate items in the table below. Also verify that the catalog
number on the box label matches your order.
Table 1: Contents of the Box
Part Number Description Quantity
SLC5508TD2A
SLC5508TD2AP
C-Bus Eight-Channel DIN-Rail Dimmer (110-120 V, 50-60 Hz), withC-Bus network power supply
C-Bus Eight-Channel DIN-Rail Dimmer (110-120 V, 50-60 Hz)
1
Included with each unit Rubber RJ-45 terminal plugs 3
Included with each unit C-Bus network cable, 15.7 in. (400 mm) 1
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
5/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 5
Features
Over-temperature shutdown of all channels at approximately158F (70C)
Soft load turn-on reduces mechanical stress on lamp filaments Linearized brightness control compensates for voltage
fluctuations
Non-volatile RAM holds programmed settings Maintains established dimming levels during changes in the
status of the C-Bus network, such as power outages, shorts, anddisconnects
Adjustable power-up delay of previously set dimming levels Remote inputs on multiple units can be connected in parallel for
a single master override control
Built-in RJ-45 connections enable configuration and networkcontrol of dimming levels
Front panel status indicator LEDs display the status of the unit,the C-Bus network connection, and the channels
Optional internal C-Bus power supply provides up to 200 mA toother C-Bus units on network
Built-in selectable C-Bus network burden and network clockgenerator for simple network installations
Easily configured by using the C-Bus Toolkit software or Learnmode
Groupings of four channels provide loading flexibility, with amaximum rating of 3 A per channel (8 A max. per channelgroup)
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
6/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
6 2007 Schneider Electric. All Rights Reserved.
COMPONENTS AND OPERATION
This section provides a detailed summary of the eight-channel DIN-rail dimmers capabilities.
Micro-Controller
The eight-channel DIN-rail dimmers micro-controller has a numberof specialized controls.
Soft Turn ON and OFF
Unlike conventional devices, where abrupt changes in brightnessoccur whenever a channel is switched ON or OFF, the
eight-channel DIN-rail dimmers micro-controller controls the rate ofbrightness change. This results in a soft brightness change that isreferred to as Soft Turn ON and Soft Turn OFF. This feature helpsto prolong the life of incandescent lamp filaments.
Linearized Brightness Control
In conventional phase-control dimmers, as the light is beingdimmed, the rate of change of power delivered to the load is notlinear. The result is a change in brightness that is more apparentwhen the brightness of the light is at lower settings. The micro-controller in the eight-channel DIN-rail dimmer uses an algorithm toensure that this change in brightness is uniform throughout thecontrol range.
Automatic Line-Frequency Adjustment
The eight-channel DIN-rail dimmer constantly tracks the power-source frequency. Whenever a frequency shift is detected, themicro-controller automatically adjusts the dimmer to ensuresynchronization. The DIN-rail dimmer will operate over a wide rangeof frequencies, provided that the drift rate is less than 3 Hz perminute or a step change of less than 0.1 Hz.
Flicker-Reduction Filter
Lighting flicker is reduced and lamp-life is increased by a filter thattracks the frequency of the incoming electricity and attenuates theharmonics of the fundamental frequency.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
7/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 7
Thermal Shutdown
An internal temperature sensor helps protect the unit fromoverheating by monitoring the units internal operating temperature.In the event there is an over-temperature condition, meaning thetemperature has exceeded approximately 158F (70C), allchannels will turn off (i.e., a thermal shutdown will occur). Hightemperatures are most likely to occur when the dimmer unit isoperating under heavy load conditions and there is insufficient airventilation.
In the event of a thermal shutdown, channel levels will beautomatically restored after the over-temperature condition hasbeen resolved and the unit has cooled.
Overrides
The eight-channel DIN-rail dimmer offers Local Override andRemote Override options (see figure DIN-Rail Dimmer OverrideOptions).
Figure 1: DIN-Rail Dimmer Override Options
KEY:
A. Local Override/Channel Control buttons
B. Remote Override/C-Bus connections
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Overrides cannot be locked down and must not be used as the method to turn offthe power before working on or inside the equipmentwhen overrides are used
the power can be restored without warning.
Turn off all electrical power supplying this equipment before working on or insidethe equipment.
Always use a properly rated voltage sensing device to confirm that power is off.Failure to follow these instructions will result in death or serious injury.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
8/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
8 2007 Schneider Electric. All Rights Reserved.
Local Override/Channel Control Buttons
Eight Local Override/Channel Control buttons on the front of the unit
provide a temporary way to change the state of each channel at theunit (this change is often referred to as "toggling" the channel or unit"locally"). Each button will light when its respective channel is ON.
By default, the Local Override buttons work opposite and inconjunction with C-Bus input units, with the most recent commandtaking precedence (see NOTE below). For example, if a keypadbutton is ON, pressing the Local Override button for that samechannel will turn OFF the keypad button and the channel. At thesame time, the Unit status indicator will start to flash. Flashing willcontinue until the Local Override has been turned off, either by
giving the same Local Override button a "Double Press" or bypressing a key on the affected input unit. See the table, "Operationof the Local Override Buttons," for an operational summary.
NOTE: By default, C-Bus commands will "override" changes to theoperating state that have been made by pressing the Local Overridebuttons. The C-Bus command override can be disabled by using theC-Bus Toolkit software. For more information about commandprecedence, see the section "Operating Mode Priorities."
Table 2: Operation of the Local Override Buttons
Type of Press on Local OverrideButton
Function
Short press Changes state of ("toggles") that channel/unit, e.g., from OFF toON
Double press (two short presses within 2seconds)
When a channel or unit is in Local Override mode, a doublepress on the Local Override button will return it to control by theC-Bus network
Long press (a press longer than 2seconds on any Local Override button)
When one or more channels or units are in Local Override mode,a long press will return them ALL to control by the C-Bus
network
Remote Overrides
The eight-channel DIN-rail dimmer has provisions for connectingtwo remote switches that provide Remote Override ON and OFFfunctions. The remote inputs are activated when the switchmechanism contact closes.
NOTE: External voltage sources are not required and MUST NOTbe connected to either of the dimmer's Remote Override inputs.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
9/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 9
Activation of a remote override input sets all dimmer channels eitherON or OFF accordingly. Remote OFF has priority if Remote ON andRemote OFF functions are activated simultaneously (see the table
Operating Mode Hierarchy).
The remote switches can be located up to 3280 ft (1000 m) from thedimmer unit. Multiple switches can be connected in parallel to thesame remote input, allowing remote control of the dimmer fromdifferent locations by using any type of cable (for wiring examples,see section Remote Override Connections). Similarly, a singleswitch can be used to remotely control up to 30 differentDIN-rail dimmers within the same C-Bus network.
NOTE: C-Bus is a balanced network, so C-Bus positive (+) must be
present at any point where C-Bus negative () is taken. Thereforeboth network conductors [C-Bus positive (+) and C-Busnegative ()] must be looped through all Remote Override inputswitches on the network.
Status Indicators
On the front of the eight-channel DIN-rail dimmer are two sets ofstatus indicators: the Unit and C-Bus status indicator LEDs and theeight illuminated Local Override (Channel Control) buttons (see
figure "Eight-Channel DIN-Rail Dimmer Status Indicators"). Unitshows the status of the individual unit C-Busshows the status of the C-Bus network at this unit Local Override/Channel buttonsshow the status of the
individual channels
Figure 2: Eight-Channel DIN-Rail Dimmer Status Indicators
KEY:
A. Unit
B. C-Bus
C. Local Override/Channel buttons
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
10/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
10 2007 Schneider Electric. All Rights Reserved.
NOTE: The Unit and C-Bus indicators do not function whenstandalone configuration is being performed on a dimmer unit that ispowered only by the C-Bus network.
Unit
The Unit status indicator LED shows the status of the individual unit.The LED displays a continuous green light (ON) when the unit isconnected to a properly operating C-Bus network and an electrical(AC) power source. When the LED flashes, it indicates that one ofthe four channels has been toggled (using a Local Override buttonor a Remote Override) into a state different from that set through theC-Bus network (for more information, see the section "Overrides").The LED displays no light when there is no electrical power or
standalone configuration is being performed on the unit.
Table 3: Unit Status Indicator Definitions
IndicatorStatus
Meaning
ON Normal operation
Flashing One or more channels has been overridden (Local Override button orRemote Override)
OFF No external electrical power source. Indicator does not function if theunit is powered only by C-Bus network, e.g., for configuration
C-Bus
The C-Bus status indicator LED shows the status of the C-Busnetwork at the unit. The LED displays a continuous green light (ON)when there is sufficient power and a valid C-Bus clock signal. TheLED flashes when the current load of a connected network is morethan the power supplies can support. The LED displays no lightwhen there is no C-Bus clock or standalone configuration is being
performed on the unit.Table 4: C-Bus Status Indicator Definitions
IndicatorStatus
Meaning
ON Power on and functional
Flashing Insufficient power to support network
OFF No external electrical power source. Indicator does not function ifthe unit is powered only by C-Bus network, e.g., for configuration
No C-Bus clock signal present
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
11/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 11
Local Override/Channel
A Local Override/Channel button will be illuminated when itschannel is ON. The section Local Override/Channel ControlButtons explains their uses.
Operating Mode Priorities
In the event a dimmer overheats, the network automatically turnsOFF loads on all channels.
In addition to the automated system controls, there are three waysto manually control loads that are connected to an eight-channelDIN-rail dimmer:
Press a button on a C-Bus input unit (e.g., a keypad button, atouch screen)
Activate (press) any of the Local Override buttons Use the Remote OverridesNOTE: By default, if any channel is in Local Override mode and aC-Bus command is received for that channel, the C-Bus commandstate will be imposed. This feature can be disabled in the C-BusToolkit software (see section Local Override Buttons).
The table "Operating Mode Hierarchy" outlines the differentoperating modes and their general precedence.
Table 5: Operating Mode Hierarchy
Mode Priority Function
Thermal shutdown 1 (Highest) All channels OFF
Remote OFF 2 Turns all channels OFF
Remote ON 3 Turns all channels ON
Local Override 4 Turns the affected channel or unit ON or OFF(opposite of the existing state)
C-Bus input unit(keypad, PIR, etc.)
4 Controls the channel and if there is a Local Overridein effect, the C-Bus command will be imposed
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
12/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
12 2007 Schneider Electric. All Rights Reserved.
Power-Up Load Status
All C-Bus units have onboard non-volatile memory that stores theoperating state of the unit in the event of a power outage. Whenpower is restored, the unit will carry out a diagnostic for about fiveseconds. The dimmer loads will remain OFF while the unit restoresthe channels to their previous states, according to the unitsrecovery settings. The load status will be displayed on the channels'status indicator LEDs.
Eight-Channel DIN-Rail Dimmer Compatibilities
The DIN-rail dimmers can dim the following types of lighting loads.
Resistive loads such as incandescent lighting and halogen110120 V lamps
Inductive loads such as iron-core transformers for low-voltagelighting
Loads compatible with phase control, such as low-voltagelighting with electronic transformers. The number of electronictransformer loads that can be connected to a channel dependson the transformer model that is used. Limit the capacitance to300 nF per output channel
Table 6: Compatibilities
Load Type Description
Incandescent lighting Incandescent lighting and halogen 110120 V lamps
Low-voltage lighting withiron-core transformers
Inductive loads such as iron-core transformers for low-voltage lighting
Low-voltage lighting withelectronic transformers
Electronic loads compatible with phase control, such aslow-voltage lighting with electronic transformers. Thenumber of electronic transformer loads that can be
connected to a channel depends on the transformermodel that is used. Limit the capacitance to 300 nF peroutput channel.
Standalone Configuration
The eight-channel DIN-Rail dimmer draws 18 mA from the C-Busnetwork when it is not connected to an external power source. This18 mA makes it possible to configure the unit without a connectionto an external power source.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
13/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 13
Requirements for configuring a unit without using an external powersource include connection to an operational C-Bus network that iscapable of supporting one or more extra C-Bus units (18 mA current
required per dimmer). For more information about configurationrequirements, see "Configuration" in the "Installation" section.
C-Bus System Clock
Eight-channel DIN-rail dimmers incorporate a software-selectableC-Bus System Clock, which synchronizes data communicationswaveforms on the C-Bus network. Typically the clock is disabled:Only one active clock is required for successful C-Bus networkcommunications, and a maximum of three C-Bus units per network
should have the clock circuitry enabled.If a system clock is required, it can be enabled through the C-BusToolkit software.
Network Burden
DIN-rail dimmers incorporate a software-selectable network burdenthat can be enabled in the event the network does not yet have aburden. One hardware or software network burden is required fornetwork termination and biasing, but only one network burden
should be installed per network. To determine if one must beinstalled for a network, consult the C-Bus Toolkit software.
To enable the software-selectable network burden, use the C-BusToolkit software to set the unit address to 001.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
14/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
14 2007 Schneider Electric. All Rights Reserved.
SAFETY PRECAUTIONS
This section contains important safety precautions that must befollowed before attempting to install or maintain electricalequipment. Carefully read and follow the safety precautions below.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
This equipment must be installed and serviced by qualifiedelectrical personnel.
Apply appropriate personal protective equipment (PPE) andfollow safe electrical work practices. See NFPA 70E.
Turn off all electrical power supplying this equipment beforeworking on or inside the equipment.
Always use a properly rated voltage sensing device to confirmthat power is off.
Replace all devices, doors, and covers before turning on powerto this equipment.
Failure to follow these instructions will result in death orserious injury.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
15/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 15
INSTALLATION
Follow the procedures in this section to mount the eight-channelDIN-rail dimmer units and to make electrical and C-Bus networkwiring connections.
Network Considerations
Determine the total network current load and verify that there will beadequate C-Bus power to support all the connected devices. Alsoverify that the amount of available power is no more than 2 A.Generally, one physical C-Bus network can have a maximum of 10DIN-rail units that incorporate a C-Bus power supply or 100
DIN-Rail units that do not. However, these limits will be affected bythe design of the network, including the specific number and typesof units on it.
The eight-channel DIN-rail dimmer units draw 18 mA from theC-Bus network when they do not have an external electrical powersource. When the units have external power, they draw no currentfrom the C-Bus network. Additionally, when connected to anexternal power source, dimmer units that incorporate a C-Busnetwork power supply can provide up to 200 mA to the C-Bus
network.Before an eight-channel DIN-rail dimmer can operate on the C-Busnetwork, the C-Bus Toolkit software must be used to assign aunique identification (unit address) and mode of operation on thenetwork. When the units are being installed as part of a large orcomplex network, it is most efficient to perform the basicconfiguration before the units are physically installed. However, theunits can be configured before or after physical installation.
Prerequisites
The following components are typically required to configure aneight-channel DIN-rail dimmer unit. (Specific items and productnumbers can vary according to the network and type of C-Bus unit.)
PC with the C-Bus Toolkit software installed Eight-channel DIN-rail dimmer unit being configured
(SLC5508TD2A, SLC5508TD2AP)
PCI (SLC5500PC)
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
16/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
16 2007 Schneider Electric. All Rights Reserved.
Identifying the C-Bus Units and Their Locations
The location of each C-Bus unit must be tracked. Two
recommended methods are given below, one for when the units areconfigured before installation (see section Labeling the C-BusUnits), the other for when the units are configured after installation(see section Recording Each Units Location).
Labeling the C-Bus Units
When C-Bus units are configured before physical installation, it isimportant to label them to indicate where they are to be placed. Onemethod for doing this would be to write each units address directlyon it.
NOTE: Verify that each configured unit has been marked to indicatewhere it should be placed in an enclosure or a building or site.
Recording Each Unit's Location
In order to track C-Bus units that will be configured after physicalinstallation, they must be identified and their location must berecorded at the time they are installed.
NOTE: If a unit has already been configured and assigned alocation on a site map, it is not necessary to make another record ofits location.
HAZARD OF UNEXPECTED OR IMPROPER SYSTEM BEHAVIOR
Properly record the physical location of each unit using the lift-and-peel label provided on the box and a site plan or location
log.
Retain location records and provide them to the person(s)responsible for configuring and commissioning the network.
Failure to follow these instructions can result in unexpected orimproper system behavior.
Before installing a unit, use the following guidelines to record itslocation. Recording each unit's location is required for configurationwith the C-Bus Toolkit software.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
17/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 17
Each unit is identified by a unique serial number found on the boxlabel (see the figure Box Label with Lift-and-Peel Section). Theserial number provides important information for recording a unit's
location.
Figure 3: Box Label with Lift-and-Peel Section
KEY:
A. Serial number
B. Bar code
C. Lift-and-peel section
The box label also has a bar code that can be read by an infraredscanner and used for a record of a specific units location. A lift-and-peel section of the box label duplicates the box labelsinformation (see Box Label with Lift-and-Peel Section diagram).
To record the location of a unit, remove the lift-and-peel sectionfrom the box label and attach it to a site plan or other document.The lift-and-peel section now provides a record of the physicallocation where that unit is installed. When installing multiple units ofone kind in an area or enclosure, such as six four-channel DINdimmers in an enclosure, verify that the document or site planindicates the relative position of each specific unit.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
18/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
18 2007 Schneider Electric. All Rights Reserved.
Mounting DIN-Rail Units onto the DIN Rail
The DIN-rail units are designed to be installed onto a standard1.38 in. (35 mm) DIN rail. To mount (i.e., attach) the dimmer unit,hook it onto the top of the DIN rail. Swing the bottom of the unitdown until it clicks into place.
Figure 4: Mounting the Unit onto the DIN Rail
KEY:
A. DIN railB. DIN-rail unit
1. Hook the unit onto the top of theDIN rail
2. Swing the bottom of the unit down3. Mounted unit
Removing DIN-Rail Units from the DIN Rail
Use a small flat-blade screwdriver to pull either the upper or lowerslide release out and disengage the unit from the DIN rail.
Figure 5: Removing the Unit from the DIN Rail
KEY:
A. DIN railB. Unit
1. Pull out the slide release2. Pull the unit away from the DIN rail3. Lift the unit away from the rail
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
19/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 19
Electrical Wiring Connections
Follow the safety precautions and guidelines for making electricalconnections that are given in this section.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all electrical power supplying this equipment beforeworking on or inside the equipment.
Always use a properly rated voltage sensing device to confirmthat power is off.
Replace all devices, doors, and covers before turning on powerto this equipment.
Failure to follow these instructions will result in death orserious injury.
SHORTING DIMMER OUTPUTS CAN RESULT IN EQUIPMENTDAMAGE
Turn off power before servicing this unit or a connected load. Do not short the dimmer outputs.Failure to follow these instructions can result in equipment
damage.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
20/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
20 2007 Schneider Electric. All Rights Reserved.
Wiring Guidelines
Follow the guidelines below when working with DIN-rail dimmers.The unit can handle up to eight channels of dimmed loadsconnected according to the guidelines below. Consider the totalcurrent consumption when designing the power feed and selectingthe cables. Also verify that the load supply has been protected by anappropriately rated circuit breaker.
Verify that the power supplying the system is turned OFF beforehandling electrical power conductors.
Each dimmer channel can independently control loads of2 A @ 120 V AC.
Additionally, the eight channels are split into two groups,channels 14 and channels 58.
Any channel in a group can carry loads up to 3 A @ 120 V AC,so long as the total load rating per channel group is no greaterthan 8 A.
Observe national and local electrical codes. Follow the wiring diagram shown in the figure "Electrical Wiring
Connections for the Eight-Channel DIN-Rail Dimmer.
Use copper wire only, one #12 or two #1416 AWG(3.1 mm1.3 mm). Verify the number and types of units that can be connected to
this network (see section Network Considerations).
Insert the rubber terminal plugs into any unused RJ-45 ports toprevent wire cuttings and other debris from entering the unit.
The recommended torque for tightening the line- andload-voltage terminal screws is 5 lb-inch (0.56 Nm). Do notexceed this torque.
Verify that electrical power conductors are separated from theC-Bus network cable and all other Class 2 conductors: Route thewiring to maintain a minimum separation or separate the wiresby barriers. Consult your electrical code for local requirements.
Verify that incoming electrical power lines are held in placeaccording to local regulations, for example, using cable ties toattach power lines to an enclosure.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
21/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 21
Use the same phase to wire the Control and Dimmer Outputcircuits of the unit. Power coming in to the Control and DimmerOutput circuits is not internally connected (see figure WiringConnections for the Eight-Channel DIN-Rail Dimmer).
Do not Meggertest C-Bus data cabling or terminals (seesection Megger
Testing Guidelines).
Figure 6: Wiring Connections for the Eight-Channel DIN-Rail Dimmer
KEY:
NOTE: Only use copper wire,one #12 or two #1416 AWG(3.1 mm1.3 mm)
Control circuit
A. GroundB. NeutralC. Line*
Dimmer Output circuit
D. Neutral Load (typical forOutput Channels 18)
E. Line*F. Load (typical for Output
Channels 18)G. To Neutral
*Power for the Control circuit and Dimmer Output circuit must be wired to the same phase.
Connecting the Dimmer to the C-Bus Network
The eight-channel DIN-rail dimmer unit is connected to the C-Busnetwork through one of the RJ-45 sockets (see the figureConnecting to the C-Bus Network). Use Category 5 unshieldedtwisted pair (UTP) data cable and an appropriately wired RJ-45connector to make the connection (see figure C-Bus WiringConnections and table C-Bus Cable Conductor Assignments).
NOTE: The C-Bus connection is polarity sensitive.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
22/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
22 2007 Schneider Electric. All Rights Reserved.
Figure 7: Connecting to the C-Bus Network
KEY:
A. C-Bus wiring connectionsB. RJ-45 connectors
C. RJ-45 pin outs
D. Rubber RJ-45 terminal plugfor any unused port
A Cat 5 UTP patch cord is included with the unit to facilitate easyinterconnection of units. Always verify that the network current loadand available power are within limits (see the section NetworkConsiderations) before adding units to the network.
Prevent wire clippings and other debris from entering the dimmerunit by inserting a rubber RJ-45 terminal plug into any unused ports.
Figure 8: C-Bus Wiring Connections
KEY:
A. C-Bus positive (+): blue + orange
B. C-Bus negative (-): blue-white + orange-white
C. Remote OFF: brown + brown-white
D. Remote ON: green + green-white
Table 7: C-Bus Cable Conductor Assignments
RJ Pin C-Bus Network Connection Color
1 Remote ON Green-White
2 Remote ON Green
3 C-Bus Neg () Orange-White
4 C-Bus Pos (+) Blue
5 C-Bus Neg () Blue-White
6 C-Bus Pos (+) Orange
7 Remote OFF Brown-White
8 Remote OFF Brown
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
23/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 23
Remote Override Connections
The C-Bus connectors have extra pairs of conductors (see thefigure C-Bus Wiring Connections and the table C-Bus CableConductor Assignments) that can be used to enable RemoteOverrides (ON/OFF) that will operate without using the C-Busnetwork, as is discussed in the section Remote Overrides. TheRemote Override connections are optional, but it is recommendedthat they be maintained for correct operation of these servicesacross the C-Bus network. The Remote Override (ON/OFF)services can be disabled by using the C-Bus Toolkit software.
NOTE: C-Bus is a balanced network, so C-Bus positive (+) must bepresent at any point where C-Bus negative () is taken. Therefore
both network conductors [C-Bus positive (+) and C-Bus negative()] must be looped through all Remote Override input switches onthe network.
The figure "Wiring for Remote Overrides" shows how one or moreswitches can be connected in parallel on any one network. Ifconnecting a Remote ON switch, use the green and greenwhiteconductors; if connecting a Remote OFF switch, use the brown andbrownwhite conductors. Remote Overrides are triggered byconnecting the relevant conductors to C-Bus negative (see the tableC-Bus Cable Conductor Assignments).
Figure 9: Wiring for Remote Overrides
KEY:
1. Remote ON connections2. Remote OFF connections
A. Remote OFF: Brown + Brown-WhiteB. C-Bus negative (): Orange-White + Blue-WhiteC. Remote ON: Green + Green-WhiteD. C-Bus positive (+): Orange + Blue
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
24/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
24 2007 Schneider Electric. All Rights Reserved.
MeggerTesting Guidelines
Do not Megger test C-Bus data cabling or terminals. Meggertesting of data cabling or terminals can degrade the performance ofthe C-Bus network.
It will not harm the C-Bus units if electrical power terminals only areMegger
tested. But because C-Bus units contain electronic
components, the Megger readings will not be correct. To obtainvalid readings, disconnect the power lines from the C-Bus units.
HAZARD OF C-BUS NETWORK PERFORMANCE DEGRADATION
Do not Megger test C-Bus data cabling or terminals as it can degrade theperformance of the C-Bus network.
Failure to follow this instruction will result in damage to the C-Bus network.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
25/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 25
STANDARDS
Table 8: U.S. and Canadian Product Safety Standards and U.S. FCC Regulations
Standards/Regulations Title
CSA C22.2 No. 14 Complies with cUL Standard for Industrial Control Equipment
UL508 Industrial Control Equipment
FCC Part 15 Complies with FCC Standards for Home or Office Use
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
26/28
Square D Clipsal Eight-Channel DIN-Rail Dimmers 63249-420-245A1Instruction Bulletin 01/2007
26 2007 Schneider Electric. All Rights Reserved.
SPECIFICATIONS
Table 9: Eight-Channel DIN-Rail Dimmer Specifications
Catalog Number SLC5508TD2A SLC5508TD2AP
Nominal Supply Voltageand Frequency
110-120 V AC, 10%, 5060 Hz
Nominal VoltageRequirements
Without an external power source, draws15-36 V DC @ 18 mA from the C-Busnetwork, enabling configuration.
With an external power source, supplies200 mA to the C-Bus network
Without an external power source,draws 15-36 V DC @ 18 mA from theC-Bus network, enabling configuration.
Never supplies power to the C-Busnetwork.
AC Input Impedance 50 kOhm @ 1 kHz 100 kOhm @ 1 kHz
Electrical Isolation 3.75 kV RMS from C-Bus to power source
Max. LoadRating/Channel
2 A per channel or max. 3 A @ 120 V AC so long as total load on the channel group(channels 14 or 58) is no greater than 8 A.*
Efficiency 98%
Dimmer Type Leading-edge phase control
Compatible Loads Suitable for incandescent, low-voltage lighting and electronic transformerscompatible with leading-edge dimmers
Max. Units/Network Based on the total network current load and available power.
Quiescent Power 10 W
Warm-Up Time 5 sec
Power-Up Delay 0 sec33 min, 30 sec, software selectable
Network Clock Software selectable
Network Burden Software selectable (Unit address 001 only)
C-Bus Connections Two RJ-45 connectors, CAT 5 UTP cable required
Remote OverrideConnection
RJ-45 connector. Remote switch input can be daisy-chained to the Max.Units/Network, with 3280 ft (1000 m) of cable (max.)
Power Terminals Accommodate copper wire only, 1612 AWG cable [two #1416 gauge(2 x 1.5 mm) or one #12 gauge (1 x 2.5 mm)]
Status Indicators Local Override button: Channel StatusUnit LED: Unit powerC-Bus LED: Power levels and presence of C-Bus clock
Mounting DIN rail, 12M wide
Operating Environment Temperature: 32F113F (0C45C)Humidity: 1095% RH
Dimensions 8.5 in. (L) x 3.62 in. (D) x 2.48 in. (H)[216 mm (L) x 92 mm (D) x 63 mm (H)]
Weight 23 oz (647 g)
*To allow flexibility of the loads used, channels 1-4 and 5-8 are grouped. The total load per group is 8 A, andthe maximum load per channel is 3 A.
NOTE: There are no user-serviceable parts in the Eight-ChannelDIN-Rail Dimmer.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
27/28
63249-420-245A1 Square D Clipsal Eight-Channel DIN-Rail Dimmers01/2007 Instruction Bulletin
2007 Schneider Electric. All Rights Reserved. 27
Load Ratings
Table 10: Load Ratings per Channel
Compatible Loads Load Rating/Channel**
Incandescent lighting (halogen 110-120 Vlamps)
3 A @ 120 V AC so long as total load on the channel group(channels 14 or 58) is no greater than 8 A.
Low-voltage lighting with iron-coretransformers
3 A @ 120 V AC so long as total load on the channel group(channels 14 or 58) is no greater than 8 A.
3 A @ 120 V AC so long as total load on the channel group(channels 14 or 58) is no greater than 8 A.
Low-voltage lighting with electronictransformers
**To allow flexibility of the loads, channels 1-4 and 5-8 are grouped. The total load per group is 8 A, and the
maximum load per channel is 3 A.
Dimensions
Figure 10: Dimensions of the Eight-Channel DIN-Rail Dimmer
SUPPORT AND SERVICE
Contact the Square D Customer Information Center for technicalsupport by phone at 1-888-Square D (1-888-778-2733) or e-mail [email protected].
Contact your local Square D service representative or Square D
Clipsalcertified installer for repairs or service to your network.
You may also find helpful information on our web site atwww.squaredlightingcontrol.com.
-
8/13/2019 SquareD Clipsal Eight Channel DIN Rail Dimmer_63249 420 245
28/28
Square D Clipsal Eight-Channel DIN-Rail DimmersInstruction Bulletin
Schneider Electric, USA295 Tech Park DriveLa Vergne, TN, 370861-888-SquareD (1-888-778-2733)www.squaredlightingcontrol.com
Electrical equipment should be installed, operated, serviced, andmaintained only by qualified personnel. No responsibility is assumed bySchneider Electric for any consequences arising out of the use of thismaterial.
Square D, , Clipsal, and C-Bus are trademarks or registered
trademarks of Schneider Electric and/or its affiliates in the United Statesand/or other countries.
2007 Schneider Electric All Rights Reserved