![Page 1: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/1.jpg)
© ABB Group July 6, 2011 | Slide 1
by NS Koh
ABB Pte. Ltd.
SS & IEC Requirements for MCB & RCCB
By NS Koh
![Page 2: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/2.jpg)
Since the withdrawal of SS 359 on 30th Jan 2004, International Standard IEC 60898 was adopted for MCB.
IEC 60898 : Circuit-breaker for overcurrent protection for household and similar installation
Scope : AC air-break circuit-breakers 50Hz or 60HzUn < 440VIn < 125AIcn < 25kA
Designed for use by uninstructed people and for not being maintained
SS & IEC Requirement for MCB & RCCBMCB
![Page 3: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/3.jpg)
Overcurrent protection
Overload protectionProtection of cables and wires aswell as system parts againstexcessive heating up duringoperating overload in a fault-freecircuit by delayed switch-off
Short-circuit protectionProtection of cables and wires aswell as system parts against theeffects of a dead short-circuitbetween conductors with adifferent potential by current-limiting switch-off
Protection of cables and wires in case of overcurrent
Thermal Tripping Magnetic Tripping
SS & IEC Requirement for MCB & RCCBMCB
![Page 4: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/4.jpg)
SS & IEC Requirement for MCB & RCCBMCB Tripping Characteristics
IEC 60898 Termal Release Trip time Electromagnetic Release Trip time
Type Non-trip Trip Hour Hold Trip sec
B 1.13 In > 1 3 In > 0.1
1.45 In < 1 5 In < 0.1
C 1.13 In > 1 5 In > 0.1
1.45 In < 1 10 In < 0.1
D 1.13 In > 1 10 In > 0.1
1.45 In < 1 20 In < 0.1
![Page 5: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/5.jpg)
SS & IEC Requirement for MCB & RCCBMCB Tripping Characteristics
![Page 6: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/6.jpg)
0.5 ms after short-circuit current is released
Miniature Circuit BreakersTripping of an MCB
0.5 ms
![Page 7: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/7.jpg)
1 ms after short-circuit current is released
Miniature Circuit BreakersTripping of an MCB
1 ms
![Page 8: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/8.jpg)
1.5 ms after short-circuit current is released
Miniature Circuit BreakersTripping of an MCB
1.5 ms
![Page 9: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/9.jpg)
2 ms after short-circuit current is released
Miniature Circuit BreakersTripping of an MCB
2 ms
![Page 10: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/10.jpg)
2.5 ms after short-circuit current is released
Miniature Circuit BreakersTripping of an MCB
2.5 ms
![Page 11: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/11.jpg)
3 ms after short-circuit current is released
Miniature Circuit BreakersTripping of an MCB
3 ms
![Page 12: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/12.jpg)
SS & IEC Requirement for MCB & RCCBMaximum disconnection times: TN-S System
3ms
![Page 13: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/13.jpg)
SS & IEC Requirement for MCB & RCCBRCCB
SS97 is a modified adoption of International Standard IEC 61008-1
SS97 & IEC 61008-1: Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs)
Scope : Functionally Dependent of or Independent on line voltage Un < 440VIn < 125A
Protect person against indirect contact and fire hazards due to earth persistent fault
![Page 14: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/14.jpg)
SS & IEC Requirement for MCB & RCCBRCCB
Major difference between SS97 and IEC 61008-1 is the tripping time:
General Type Max Break Times (s)
Standard Category 1 x I n 2 x I n 5 x I n 10 x I n, to 500A
IEC 61008 n < 30mA 0.3 0.15 0.04 0.04
SS 97 n< 30mA 0.1 0.1 0.04 0.04
![Page 15: SS & IEC Requirements for MCB & RCCB - ABB Ltd · SS & IEC Requirements for MCB & RCCB By NS Koh ... SS & IEC Requirement for MCB & RCCB MCB. Overcurrent protection Overload protection](https://reader031.vdocuments.net/reader031/viewer/2022013107/5b0e10ed7f8b9a8b038e96d8/html5/thumbnails/15.jpg)