stamford generators

8
STAMFORD AC GENERATORS FROM NEWAGE INTERNATIONAL BC162/182 164/184 BC162/182 164/184

Upload: erik82kuk

Post on 07-Apr-2015

2.822 views

Category:

Documents


18 download

DESCRIPTION

A manual about Generators.

TRANSCRIPT

Page 1: Stamford Generators

STAMFORD AC GENERATORS FROM

NEWAGE INTERNATIONAL

BC162/182 164/184

BC162/182 164/184

Page 2: Stamford Generators

• • •

SPECIAL FEATURES OF THE BC RANGE

Optional auxiliary winding system provides sustained short circuit capability.

Advanced automatic voltage regulator (AVR) control for

trouble-free operation under the most demanding conditions.

Easy paralleling with mains or other generators. Standard 2/3 pitch windings avoid excessive neutral currents.

Dynamically balanced rotors, with sealed-for-life ball bearings and single or two-bearing construction.

Simple installation and maintenance, with easy access to terminals, rotating diodes and coupling bolts.

Built to conform with all leading industrial standards.

STAMFORD Setting the standard in

AC generator technology

Newage International's long experience in generator manufacture, together with a most advanced design, production and testing facilities in the world, ensures that the STAMFORD range of brush less ac generators sets an international standard for ruggedness and reliability.

The full STAMFORD range covers ratings for 5kVA to 2,500kVA to meet the most demanding needs for industrial, marine, commercial, construction, mining or telecommunications, in fact most applications for prime or standby power generation.

STAMFORD BC generators provide a range of 2 pole ratings from 11 kVA to 37.5 kVA (50Hz) and 13.6 kVA to 47 kVA (60Hz). A range of 4 pole ratings from 7.5 kVA to 31.3 kVA (50Hz) and 8.9 kVA to 37.5 kVA (60Hz) is also available

Page 3: Stamford Generators

* SPECIFICATIONS AND OPTIONS STANDARDS BC16 and BC18 industrial generators meet the requirements of BS5000 Part 3, VDE0530, UTE5100, NEMA MG1-22, CEMA, IEC34-1, CSA22.2 and AS1359.

Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA.

Other standards and certifications can be considered on request.

• EXCITATION SYSTEMS SX460 & SA465 AVRs The SX460 AVR is available for use with both BC16 and BC18 generators. The SA465 AVR is available for use with the BC18 generator only.

With these self-excited systems the main stator provides power via the automatic voltage regulator (AVR) to the exciter stator. The high efficiency semiconductors of the AVR ensure positive build up from initial low levels of residual voltage.

The exciter rotor output is fed to the main rotor through a three phase full wave bridge rectifier. The rectifier is protected by a surge suppressor against surges caused, for example, by short circuit or out-of-phase parallelling.

The SA465 will support a range of electronic accessories, including a 'droop' Current Transformer (CT) to permit parallel operation with other ac generators. SA665 AVR (BC 184 only) The SA665 AVR is a new regulator designed to receive its power input from an auxiliary winding in the main

• stator to provide a sustained short circuit capability.

The AVR is capable of supporting a 'droop' current transformer (CT) to permit parallel operation with other ac generators.

variation. Voltage is adjusted using a trimmer on the AVR.

INSULATION IMPREGNATION The insulation system is Class 'H'.

All wound components are impregnated with materials and processes designed specifically to provide protection against the harsh environments encountered in generator applications. Resin based materials are selected and developed to provide the high build required for static windings and the high mechanical strength required for rotating components.

WINDINGS 3 ELECTHICAL PERFORMAME All generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th ...) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches, when in parallel with the mains. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion.

ELEPHIMF INTERFERENCE THE (as defined by BS4999 Part 40) is better than 2 0/0. TIF (as defined by ASA C50.12) is better than 50.

RADIO INTERFERENCE The absence of brushgear and the high quality AVR ensure low levels of interference with radio transmissions. Additional RFI suppression may be supplied if required.

ENCLOSURE IP23 (NEMA 1) is standard for all industrial and marine generators. Giving drip proof protection of 60° from the vertical.

Inlet air filters are available as an option on all generators, at reduced ratings (5%derate).

SHAFT & KEYS All generator rotors are dynamically balanced to better than BS6861: Part 1 Grade 2.5. for minimum vibration in operation. Two bearing generators are balanced with a half key.

ADAPTORS & COUPLINGS The BC generators are available in single and two bearing construction.

For the BC16 generators SAE 4, 5, and 6 adaptors, and SAE 6.5, 7.5, 8 and 10 disc couplings may be specified.

For the BC18 generator SAE 2, 3, 4 & 5 adaptors, and SAE 6.5, 7.5, 8, 10 and 11.5 disc couplings may be specified.

Note: If SAE 5 is used on the BC18 then it is necessary to derate the generator output by 5%.

QUALITY ASSURANCE Generators are manufactured using production procedures having a quality assurance level to BS5750 Part 2 (ISO 9002).

FURTHER REFERENCES SX 460 Technical Specification 5511 SA 465 Technical Specification 5541 SA 665 Technical Specification 5542

VOLTAGE REGULATION Stamford self excited AVRs are 2 phase average voltage sensed and will control the generator output voltage to within the following limits:

SX 460 p 1.5% SA 465 p 1.00/o SA 665 p 1.5%

from no load to full load including cold to hot variations for any power factor between 0.8 lagging and unity allowing for a 4 0/o engine speed

TERMINALS & TERMINAL BOX Standard generators are 3 phase reconnectable with 12 ends brought out to the terminals, which are mounted on a cover at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for customers' wiring and gland arrangements. It has removable panels for easy access.

Page 4: Stamford Generators

• •

BC 162 INDUSTRIAL RATINGS •

3 PHASE

Voltages

50Hz 3000 rpm

Class H Rise (125°) Class F Rise (105°C) Class H Rise (125°)

60 Hz 3600rpm

Class F Rise (105°C)

Series Star (Wye) 380 400 415 440 380 400 415 440 416 440 460 480 416 440 460 480

Parallel Star (Wye) 190 200 208 220 190 200 208 220 208 220 230 240 208 220 230 240

Series Delta 220 230 240 254 220 230 240 254 240 254 - 240 254 -

BC 162D kVA 12.5 12.5 12.5 12.0 11.5 11.5 11.5 11.0 14.7 15.6 15.6 15.6 13.6 14.4 14.4 14.4

kW 10.0 10.0 10.0 9.6 9.2 9.2 9.2 8.8 11.8 12.5 12.5 12.5 10.9 11.5 11.5 11.5

Eff% 72.4 73.3 74.0 75.0 72.9 73.7 74.3 75.1 71.1 71.9 72.8 73.5 71.5 72.3 73.0 73.7

kW Input 13.8 13.6 13.5 12.8 12.6 12.5 12.4 11.7 16.6 17.4 17.2 17.0 15.2 15.9 15.7 15.6

BC 162E kVA 15.0 15.0 15.0 14.5 13.8 13.8 13.8 13.3 17.8 18.8 18.8 18.8 16.3 17.3 17.3 17.3

kW 12.0 12.0 12.0 11.6 11.0 11.0 11.0 10.6 14.2 15.0 15.0 15.0 13.0 13.8 13.8 13.8

Eff% 76.3 77.0 77.5 78.2 76.6 77.3 77.7 78.3 75.1 75.8 76.5 77.0 75.4 76.1 76.6 77.1

kW Input 15.7 15.6 15.5 14.8 14.4 14.2 14.1 13.5 18.9 19.8 19.6 19.5 17.2 18.1 18.0 17.9

BC 162 F kVA 17.5 17.5 17.5 17.0 16.0 16.0 16.0 15.6 20.8 21.9 21.9 21.9 18.8 20.0 20.0 20.0

kW 14.0 14.0 14.0 13.6 12.8 12.8 12.8 12.5 16.6 17.5 17.5 17.5 15.0 16.0 16.0 16.0

Eff% 78.5 79.1 79.6 80.2 78.8 79.4 79.8 80.2 77.4 78.1 78.7 79.2 77.7 78.3 78.8 79.2

kW Input 17.8 17.7 17.6 16.9 16.2 16.1 16.0 15.6 21.4 22.4 22.2 22.1 19.3 20.4 20.3 20.2

BC 162 G kVA 25.0 25.0 25.0 24.0 23.0 23.0 23.0 22.0 29.6 31.3 31.3 31.3 27.0 28.6 28.6 28.6

kW 20.0 20.0 20.0 19.2 18.4 18.4 18.4 17.6 23.7 25.0 25.0 25.0 21.6 22.9 22.9 22.9

Eff% 80.7 81.4 81.9 82.6 81.1 81.8 82.1 82.7 80.0 80.6 81.2 81.7 80.4 80.9 81.5 81.9

kW Input 24.8 24.6 24.4 23.2 22.7 22.5 22.4 21.3 29.6 31.0 30.8 30.6 26.9 28.3 28.1 28.0

1 PHASE DEDICATED WINDINGS

Voltages

Series

Parallel

50 Hz 3000rpm

Class H Rise (125°) Class F Rise (105°C)

220 230 240 220 230 240

110 115 120 110 115 120

BC 162 D kVA 8.4 8.4 8.4 7.5 7.5 7.5

kW 6.7 6.7 6.7 6.0 6.0 6.0

Eff°/o 67.3 67.9 68.4 67.6 68.1 68.4

kW Input 10.0 9.9 9.8 8.9 8.8 8.8

BC 162 E kVA 10.0 10.0 10.0 9.0 9.0 9.0

kW 8.0 8.0 8.0 7.2 7.2 7.2

Eff% 71.2 71.7 72.0 71.3 71.7 71.9

kW Input 11.2 11.2 11.1 10.1 10.0 10.0

BC 162 F kVA 11.8 11.8 11.8 10.6 10.6 10.6

kW 9.4 9.4 9.4 8.5 8.5 8.5

Eff% 73.6 74.0 74.3 73.7 74.0 74.2

kW Input 12.8 12.8 12.7 11.5 11.5 11.4

BC 162 G kVA 16.8 16.8 16.8 15.0 15.0 15.0

kW 13.4 13.4 13.4 12.0 12.0 12.0

Eff°/o 76.7 77.1 77.4 76.9 77.2 77.5

kW Input 17.5 17.4 17.4 15.6 15.5 15.5

60 Hz 3600rpm

Class H Rise (125°)

220 230 240

110 115 120

Class F Rise (105°C)

220 230 240

110 115 120

10.0 10.0 10.0 9.0 9.0 9.0

8.0 8.0 8.0 7.2 7.2 7.2

64.5 65.3 66.0 64.8 65.5 66.1

12.4 12.2 12.1 11.1 11.0 10.9

12.4 12.4 12.4 11.0 11.0 11.0

9.9 9.9 9.9 8.8 8.8. 8.8

68.8 69.5 70.1 69.0 69.6 70.1

14.4 14.3 14.2 12.8 12.6 12.6

14.4 14.4 14.4 13.0 13.0 13.0

11.5 11.5 11.5 10.4 10.4 10.4

71.4 72.1 72.6 71.6 72.2 72.6

16.1 16.0 15.9 14.5 14.4 14.3

20.6 20.6 20.6 18.5 18.5 18.5

16.5 16.5 16.5 14.8 14.8 14.8

74.7 75.3 75.9 75.1 75.6 76.1

22.1 21.9 21.7 19.7 19.6 19.4

GENERAL NOTES Industrial ratings are based on 40°C ambient temperature and 1000m altitude.

3 phase units are reconnectable with 12 ends brought out to the terminals. Single phase ratings are available from reconnectable machines connected parallel zig-zag at 0.6 multiplier.

3 phase voltages listed are available from a single broad-range winding.

Other voltages will be considered on request.

Derate for air inlet filters 5%.

Page 5: Stamford Generators

• S •

BC 182 INDUSTRIAL RATINGS •

3 PHASE

Voltages

50 Hz 3000 rpm 60 Hz 3600rpm

Class H Rise (125°) Class F Rise (105°C) Class H Rise (125°C) Class F Rise (105°C)

Series Star (Wye) 380 400 415 440 380 400 415 440 416 440 460 480 416 440 460 480

Parallel Star (Wye) 190 200 208 220 190 200 208 220 208 220 230 240 208 220 230 240

Series Delta 220 230 240 254 220 230 240 254 240 254 - - 240 254 -

BC 182 H kVA 30.0 30.0 30.0 29.0 27.5 27.5 27.5 26.6 35.4 37.5 37.5 37.5 32.3 34.2 34.2 34.2

kW 24.0 24.0 24.0 23.2 22.0 22.0 22.0 21.3 28.3 30.0 30.0 30.0 25.8 27.4 27.4 27.4

Eff% 81.2 81.9 82.3 83.0 81.6 82.2 82.5 83.0 80.3 80.9 81.5 82.0 80.6 81.1 81.7 82.1

kW Input 29.5 29.3 29.2 28.0 27.0 26.8 26.7 25.6 35.3 37.1 36.8 36.6 32.1 33.7 33.5 33.3

BC 182 J kVA 35.0 35.0 35.0 34.0 32.0 32.0 32.0 31.0 41.3 43.8 43.8 43.8 38.0 40.0 40.0 40.0

kW 28.0 28.0 28.0 27.2 25.6 25.6 25.6 24.8 33.0 35.0 35.0 35.0 30.4 32.0 32.0 32.0

Eff% 82.3 83.0 83.4 84.0 82.7 83.2 83.6 84.1 81.5 82.1 82.6 83.1 81.8 82.3 82.8 83.2

kW Input 34.0 33.8 33.6 32.4 31.0 30.8 30.6 29.5 40.5 42.7 42.4 42.2 37.2 38.9 38.6 38.4

BC 182 K kVA 37.5 37.5 37.5 36.3 34.5 34.5 34.5 34.5 44.4 46.9 46.9 46.9 40.6 43.1 43.1 43.1

kW 30.0 30.0 30.0 29.0 27.6 27.6 27.6 27.6 35.5 37.5 37.5 37.5 32.5 34.5 34.5 34.5

Eff% 84.3 84.7 85.0 85.4 84.5 84.9 85.1 85.4 83.5 84.0 84.4 84.7 83.7 84.1 84.5 84.8

kW Input 35.6 35.4 35.3 34.0 32.7 32.5 32.4 32.3 42.5 44.7 44.5 44.3 38.8 41.0 40.8 40.7

1 PHASE DEDICATED WINDING

Voltages

50 Hz 3000rpm 60Hz 3600rpm

Class H Rise (125°) Class F Rise (105°C) Class H Rise (125°) Class F Rise (105°C)

Series 220 230 240 220 230 240 220 230 240 220 230 240

Parallel 110 115 120 110 115 120 110 115 120 110 115 120

BC 182 H kVA 20.0 20.0 20.0 18.0 18.0 18.0 24.8 24.8 24.8 22.3 22.3 22.3

kW 16.0 16.0 16.0 14.4 14.4 14.4 19.8 19.8 19.8 17.8 17.8 17.8

Eff% 77.2 77.6 77.9 77.3 77.6 77.9 75.0 75.6 76.2 75.2 75.8 76.3

kW Input 20.7 20.6 20.5 18.6 18.5 18.5 26.5 26.2 26.0 23.7 23.5 23.4

BC 182 J kVA 23.5 23.5 23.5 21.2 21.2 21.2 28.9 28.9 28.9 26.0 26.0 26.0

kW 18.8 18.8 18.8 17.0 17.0 17.0 23.1 23.1 23.1 20.8 20.8 20.8

Eff% 78.5 78.9 79.2 78.7 79.0 79.2 76.5 77.1 77.6 76.8 77.3 77.8

kW Input 24.0 23.8 23.7 21.6 21.5 21.4 30.2 30.0 29.8 27.1 26.9 26.7

BC 182 K kVA 25.0 25.0 25.0 22.5 22.5 22.5 31.0 31.0 31.0 28.0 28.0 28.0

kW 20.0 20.0 20.0 18.0 18.0 18.0 24.8 24.8 24.8 22.4 22.4 22.4

Eff% 80.4 80.6 80.8 80.4 80.5 80.6 78.8 79.2 76.6 78.9 79.3 79.6

kW Input 24.9 24.8 24.8 22.4 22.4 22.3 31.5 31.3 31.1 28.4 28.3 28.1

GENERAL NOTES Industrial ratings are based on 40°C ambient temperature and 1000m altitude.

3 phase units are reconnectable with 12 ends brought out to the terminals. Single phase ratings are available from reconnectable machines connected parallel zig-zag at 0.6 multiplier.

3 phase voltages listed are available from a single broad-range winding.

Other voltages will be considered on request.

Derate for air inlet filters 5 0/0.

With SAE 5 Adaptor derate output by 50/o.

Page 6: Stamford Generators

B 90

410 OVER SCREENS

400 T/BOX LID

333 OVER STATOR COVER

50 MIN AIR ENTRY

8.5 229

"A" OVERALL

105 I 105

242 6-HOLES 14 DIA

NOTE! ADAPTOR COVERS FOR SAE 2.3 8 5 ARE SOLID

BUT! FOR SAE4 ARE SCREENED WITH A FREE VENT AREA OF 202 S0 CM

SHAFT EXTENSION DETAIL 5CAI F = 2: 1

279 CRS

319

50 MIN 1 AIR ENTRY

65

'A" OVERALL

229

93

g r - 111111 I;

nun \ mum

\ 111=1111111111.

242

105 C .... ..SSPIGOT 1 3rnm THICK COUPLING DISC

D SECURING SCREWS TO BE TIGHTENED TO A TORQUE

OF 7,6 kgfrn (75 MA)

S

MLANGE

13 MAX

..1.- 0 I I

I 11111

1 X

4-- 6-HOLES 14 DIA

'AM'-HOLES "AP' DIA EQUI-SPACED ON

"AR" PCD 410 OVER SCREENS

400 T/BOX LID

333 OVER STATOR COVER

R-HOLES S DIA SPACED AS SHOWN

-r" PCD

279 CRS

319

23 65 6 SPIGOT

I 12 FLANGE

S

228

212

"Fr-HOLES "S" DIA EQUI-SPACED ON

"T" PCD

SINGLE BEARING

BC182/184 TWO BEARING

S

DIMENSIONS ' A B

BC182 H 481,5 197 BC182 J 481,5 197 BC182 K 521,5 237 BC184 E 431,5 147 BC184 F 521,5 237 BC184 G 521,5 237

DISC COUPLINGS S.A.E. No. AN AM AP AR V

7.5 30,16 8 8,7 222,2 241,2 8 61,9 6 10,3 244,5 263,4

10 53,98 8 10,3 295,3 314,2 11,5 39,68 8 10,3 333,4 352,3

FLANGE ADAPTORS SAE No. R S T U° W X C D

2 12 11 466,7 15 447,6 489 172 156 3 12 11 428,6 15 409,5 451 145 129 4 8 11 381,0 15 361,9 402 133 117 5 8 11 285 22,5 266,7 308 133 117

SHIPPING DETAILS Nett Weight kg Gross Weight kg Packing Case size cm

BC182 H 130 140 153

71 x 51 x 69 71 x51 x69 BC 182 J 143

BC182 K 159 169 71 x 51 x 69 BC184 E 131 133 71 x 51 x 69 9C184 F 154 156 71 x51 x69 BC184 G 170 172 71 x 51 x 69

DIMENSIONS A B

BC182 H 601,5 227 BC 82 J 601,5 227 BC182 K 641,5 267 BC184 E 551,5 177 BC184 F 641,5 267 BC184 G 641,5 267

FLANGE ADAPTORS S.A.E No R S T U° V W X

2 12 11 466,7 15 432 447,6 495 3 12 11 428,6 15 396 409,5 451 4 12 11 381,0 15 352 361,9 403 5 8 11 333,3 22,5 301 314,3 356

SHIPPING DETAILS Nett Weight kg Gross Weight kg

147 PackingCasesizecm

71 x 51 x 69 8C182 H 137 . BC182 J 150 160 71 x 51 x 69 BC182 K 166 176 71 x 51 x 69 BC184 E 131 141 71 x 51 x 69 BC184 F 154 164 71 x 51 x 69 BC184 G 170 180 71 x 51 x 69

i .° _ • __ II

1III

1,1 -12

mum f

Illustrations and weights are approximate only.

If in doubt please refer to factory for General Arrangement drawings.

Page 7: Stamford Generators

• S •

BC 184 INDUSTRIAL RATINGS

3 PHASE

Voltages 50Hz 1500 rpm 60 Hz 1800rpm

Class H Rise (125°) Class F Rise (105°C) Class H Rise (125°C) Class F Rise (105°C) Series Star (Wye) 380 400 415 440 380 400 415 440 416 440 460 480 600 416 440 460 480 600 Parallel Star (Wye) 190 200 208 220 190 200 208 220 208 220 230 240 300 208 220 230 240 300 Series Delta 220 230 240 254 220 230 240 254 240 254 266 277 346 240 254 266 277 346

BC184 E kVA 22.5 22.5 22.5 22.5 20.0 20.0 20.0 20.0 27.5 28.8 28.8 30.0 30.0 25.0 26.3 26.3 28.1 28.1

kW 18.0 18.0 18.0 18.0 16.0 16.0 16.0 16.0 22.0 23.0 23.0 24.0 24.0 20.0 21.0 21.0 22.5 22.5

Eff% 84.3 84.9 85.3 85.8 84.9 85.4 85.7 86.1 83.8 84.3 84.9 85.2 85.6 84.4 84.8 85.3 85.5 85.9

kW Input 21.4 21.2 21.1 21.0 18.8 18.7 18.7 18.6 26.2 27.1 27.1 28.2 28.0 23.7 24.8 24.3 26.3 26.2

BC184 F kVA 27.5 27.5 27.5 27.5 25.0 25.0 25.0 25.0 32.5 34.4 34.4 35.0 35.0 30.0 31.3 31.3 32.5 32.5

kW 22.0 22.0 22.0 22.0 20.0 20.0 20.0 20.0 26.0 27.5 27.5 28.0 28.0 24.0 25.0 25.0 26.0 26.0

Eff% 85.7 86.2 86.5 87.0 86.2 86.6 86.9 87.2 85.5 85.9 86.4 86.7 87.0 85.9 86.3 86.7 86.9 87.2

kW Input 25.7 25.5 25.4 25.3 23.1 23.1 23.0 22.9 30.4 32.0 31.9 32.3 32.2 27.9 29.0 28.9 29.9 28.8

BC184 G kVA 31.3 31.3 31.3 31.3 29.0 29.0 29.0 29.0 35.0 37.5 37.5 37.5 37.5 31.3 34.4 34.4 34.4 34.4

kW 25.0 25.0 25.0 25.0 23.2 23.2 23.2 23.2 28.0 30.0 30.0 30.0 30.0 25.0 27.5 27.5 27.5 27.5

Eff% 86.6 87.0 87.3 87.6 86.9 87.3 87.5 87.7 86.7 87.0 87.3 87.6 87.8 87.1 87.3 87.6 87.8 88.0

kW Input 28.9 28.8 28.7 28.6 26.7 26.6 26.5 26.4 32.3 34.5 34.4 34.2 34.2 28.8 31.5 31.4 31.3 34.5

1 PHASE DEDICATED WINDINGS

60 Hz 1800rpm Class H Rise (125°C) Class F Rise (105°C)

220

110 230

115

240

120 220

110

230

115

240

120

18.4 18.4 18.4 16.5 16.5 16.5

14.7 14.7 14.7 13.2 13.2 13.2

79.9 80.6 81.1 80.5 81.1 81.5

18.4 18.3 18.1 16.4 16.3 16.2

21.9 21.9 21.9 20.0 20.0 20.0

17.5 17.5 17.5 16.0 16.0 16.0

81.9 82.4 82.8 82.3 82.8 83.1

21.4 21.3 21.2 19.4 19.3 19.2

25.0 25.0 25.0 23.0 23.0 23.0

20.0 20.0 20.0 18.4 18.4 18.4

83.0 83.4 83.8 83.3 83.7 84.0

24.1 24.0 23.9 22.1 22.0 21.9

MARINE RATINGS GENERAL NOTES

Voltages Series

Parallel

50Hz 1500 rpm Class H Rise (125°) Class F Rise (105°C)

220 230 240 220 230 240

110 115 120 110 115 120

BC 184 E kVA 15.0 15.0 15.0 13.5 13.5 13.5

kW 12.0 12.0 12.0 10.8 10.8 10.8

Eff% 81.3 81.7 81.9 81.7 82.0 82.2

kW Input 14.8 14.7 14.6 13.2 13.2 13.1

BC 184 F kVA 18.5 18.5 18.5 16.8 16.8 16.8

kW 14.8 14.8 14.8 13.4 13.4 13.4

Eff% 82.7 83.0 83.3 83.1 83.3 83.4

kW Input 17.9 17.8 17.8 16.2 16.1 16.1

BC 184 G kVA 21.0 21.0 21.0 19.4 19.4 19.4

kW 16.8 16.8 16.8 15.5 15.5 15.5

Eff% 83.7 83.9 84.0 83.8 84.0 84.1

kW Input 20.1 20.0 20.0 18.5 18.5 18.5

Voltages Series Star (Wye)

Parallel Star (Wye)

Series Delta

50Hz 1500 rpm Class F Rise (90°)

380 400 415 440 190 200 208 220

220 230 240 254

60Hz 1800 rpm Class F Rise (90°C)

416 440 460 480

208 220 230 240

240 254 266 277

BCM184 E kVA 15.0 15.0 15.0 14.0 18.2 19.3 19.3 19.3

kW 12.0 12.0 12.0 11.2 14.6 15.4 15.4 15.4

Eff°/o 85.4 85.6 85.7 85.8 85.1 85.4 85.6 85.8

kW Input 14.1 14.0 14.0 13.1 17.1 18.1 18.0 18.0

BCM184 F kVA 20.0 20.0 20.0 19.0 23.0 24.4 24.4 24.4

kW 16.0 16.0 16.0 15.2 18.5 19.6 19.6 19.6

Eff% 86.9 87.1 87.2 87.2 86.8 87.0 87.2 87.3

kW Input 18.4 18.4 18.4 17.4 21.2 22.4 22.4 22.4

BCM184 G kVA 22.5 22.5 22.5 21.0 26.2 27.7 27.7 27.7

kW 18.0 18.0 18.0 16.8 21.0 22.2 22.2 22.2

Eff°/o 87.5 87.6 87.6 87.4 87.4 87.6 87.7 87.7

kW Input 20.6 20.5 20.5 19.2 24.0 25.3 25.3 25.3

Industrial ratings are based on 40°C ambient temperature and 1000m altitude.

Marine ratings are based on 50°C ambient temperature.

3 phase units are reconnectable with 12 ends brought out to the terminals. Single phase ratings are available from reconnectable machines connected parallel zig-zag at 0.58 multiplier.

3 phase voltages listed are available from a single broad-range winding except 600V 60 Hz which required a different winding. Other voltages will be considered on request.

Industrial generators are available with an auxiliary winding at a reduced output. Refer to factory for details.

Derate for air inlet filters 5%.

With SAE 5 Adaptor derate output by 5%.

Page 8: Stamford Generators

AC GENERATORS FROM NEWAGE INTERNATIONAL

STAMFORD

The Stamford range

• s •

First for performance First for dependability

Stamford AC generators rarely draw attention to themselves.

While they may be seen in all the worst places in the world the

fact remains that their performance and dependability are

unsurpassed. Years of experience in design and

manufacture sees to that. When help is needed, however, it is

readily available ... anywhere in the world. It starts with

specification and installation, with assistance and advice to

provide precisely the generator the job demands. It

continues through commissioning and into after-sales.

Newage service engineers are experienced professionals

with extensive training in electrical, electronic and

mechanical skills. They, in their turn, are supported by a

worldwide spares and service network. In fact, with field

support and service available in almost every country in the

world Newage International is .. . truly international.

Please note: Continuous development of our products ent'tles us to change specification details without notice. Therefore they must not be regarded as binding.

Sales Department, Newage International Limited, PO Box 17, Barnack Road, Stamford, Lincolnshire PE9 2NB, England

Telephone: 44 (0) 1780 484000 Fax: 44 (0) 1780 484100 Telex: 32268

Printed in England by Industrial Press BC/12/94/ED4