standard construction details - shorewood, illinois
TRANSCRIPT
VILLAGE OF SHOREWOOD
STANDARD CONSTRUCTION DETAILS
UPDATED APRIL 2017
\\CBBELSRVR1\cbbeldft\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\Index of Revisions - April 2017.xls
Village of Shorewood Construction StandardsChristopher B. Burke Engineering, Ltd.Last Updated: April 2017
Pavement, Curb and Gutter, Sidewalks
PVT-1 Roadway Cross Section (Major Arterial)Revised to allow for alternative pavement section using geogrid September 2014
PVT-2 Roadway Cross Section (Major Collector)Revised to allow for alternative pavement section using geogrid September 2014
PVT-3 Roadway Cross Section (Minor Collector)Revised to allow for alternative pavement section using geogrid September 2014
PVT-4 Roadway Cross Section (Local)Revised to allow for alternative pavement section using geogrid September 2014
PVT-5 Roadway Cross Section (Industrial) Revised to allow for alternative pavement section using September 2014PVT-6 Parking Lot Pavement Revised to allow for alternative pavement section using September 2014PVT-7 Right-In/Right-Out Driveway Entrance New detail June 2007PVT-8 Barrier Combination Concrete Curb & Gutter, Type B-6.12 No revisions made June 2007PVT-9 Mountable Combination Concrete Curb & Gutter, Type M-3.12 No revisions made June 2007PVT-10 Residential Driveway New detail June 2007PVT-11 Commercial Entrance New detail June 2007
PVT-12 SidewalkAdded ADA/PROWAG requirements and other general notes March 2017
PVT-13 Not UsedDeleted Handicap Sidewalk Ramp Detail (Reference IDOT Standards) March 2017
PVT-14 Bituminous Bicycle Path Pavement Revised to require use of geogrid September 2014PVT-15 Concentric Cul-De-Sac New detail June 2007PVT-16 Eccentric Cul-De-Sac New detail June 2007PVT-17 Butt Joint New detail June 2007PVT-18 Bituminous Pavement Patching New detail June 2007PVT-19 Open-Cutting Pavement Within the Public Right-of-Way New detail October 2009PVT-20 Pavement Crack Sealing New detail May 2011PVT-21 Typical Driveway Pinning New detail August 2011
Storm Sewer SystemSTM-1 Storm Sewer Installation No revisions made June 2007
STM-2 Storm Manhole Type ANew detail; created separate details for storm and sanitary manholes June 2007
STM-3 Catch Basin Type A Added note identifying structure wall thickness June 2007STM-4 Catch Basin Type C Added note identifying structure wall thickness June 2007STM-5 Inlet Deleted Plan View Detail June 2007STM-6 Casting Installation and Adjusting No revisions made June 2007STM-7 Subsurface Drain Tile & Sump Pump Connection New detail June 2007STM-8 Sump Discharge Service Line New detail June 2007STM-9 Detention Pond Restrictor Revised to non-clog design March 2017STM-10 Not Used Deleted pipe restrictor detail March 2017
Sanitary Sewer System
SAN-1 Sanitary Sewer InstallationAdded table for required pipe materials; added note for joint requirements for gravity sanitary sewer June 2007
SAN-2 Sanitary Sewer ManholeNew detail; created separate details for storm and sanitary manholes June 2007
SAN-3 Sanitary Manhole Frame & Cover New detail June 2007SAN-4 Sanitary Manhole Pipe Connection No revisions made June 2007SAN-5 Drop Connection No revisions made June 2007SAN-6 Non-Residential Sewer Service New detail June 2007SAN-7 Residential Sewer Service No revisions made June 2007
Water Distribution SystemWTR-1 Water Main Installation Revised testing requirements per Public Works direction June 2007WTR-2 Thrust Block Installations No revisions made June 2007WTR-3 Valve Vault New detail June 2007WTR-4 Pressure Connection Valve Vault Added reference to detail WTR-5 June 2007WTR-5 Valve Vault Frame and Cover New detail June 2007
WTR-6 Fire HydrantRevision to allowed manufacturers and new requirement for mechanical joint September 2014
WTR-7 Residential Water Service Revised to show b-box near ROW March 2017WTR-8 Water Sampling Station New detail June 2007
Electrical System
ELE-1 Ornamental Type Light PoleRevised catalog numbers to reflect new manufacturer codes and updated specifications March 2009
ELE-1A Pedestrian Scale (10') Ornamental Type Light Pole New Standard March 2009ELE-2 Pedestrian Scale Symmetrical Ornamental Type Light Pole New Standard March 2009
Revision DateDetail Name Standard Description of Revisions
\\CBBELSRVR1\cbbeldft\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\Index of Revisions - April 2017.xls
Revision DateDetail Name Standard Description of Revisions
ELE-3A Roadway Type Light PoleRevised catalog numbers to reflect new manufacturer codes and updated specifications April 2009
ELE-3B Roadway Type Light Pole with Pedestrian FixtureNew Standard; Revised catalog numbers to reflect new manufacturer codes and updated specifications April 2009
ELE-4 Concrete Light Pole Foundation Consoldated two old details into one July 2007ELE-5 Light Pole Handhole Wiring Diagram New detail July 2007ELE-6 Splicing Electrical Cables No revisions made July 2007ELE-7 Conduit Installation Consolidated old conduit and trench details July 2007ELE-8 Direct Connected Street Light Service Disconnect Miscellaneous minor revisions July 2007ELE-9 Com-Ed Overhead Connection for Lighting Controller Miscellaneous minor revisions July 2007ELE-10 Lighting Controller Revised for consistency with other detail revisions July 2007
Street SignsSGN-1 Sign Standards Revised Note #3A and 3E June 2007SGN-2 No Parking Sign No revisions made June 2007SGN-3 Residential Speed Limit Sign No revisions made June 2007SGN-4 Sprinkling Sign No revisions made June 2007SGN-5 5 Ton Weight Limit Sign No revisions made June 2007SGN-6 Sign Spacing for Typical Residential Subdivision Entrance New detail July 2007SGN-7 Signage for Future Street Connection New detail July 2007
Miscellaneous StandardsMSC-1 Permanent Monuments New detail June 2007MSC-2 Casing Pipe No revisions made June 2007MSC-3 Typical Service Laterals Revised per Village October 2016MSC-4 Handicap Stall New detail June 2007MSC-5 Not Used Deleted double striping detail March 2017
120' RIGHT OF WAY
PVT-1
R.O.W. LINER.O.W. LINE
GUTTER, TYPE B-6.24
CONCRETE CURB &
COMBINATION
MATERIALS, TYPE B
12" AGGREGATE SUBBASE GRANULAR
C/L
12"
(TYP.)
2'
33 12' 33 1
2'
10'
53' BACK TO BACK
5' '21
27 2'
'21
21 1'
N70
COURSE, MIX "D",
ASPHALT SURFACE
1 1/2" HOT-MIX.
FOOT (TYP.)
" PER21
SLOPE AT
PARKWAY
COURSE, IL-19, N70
12" HOT-MIX ASPHALT BINDER
*ALTERNATE PAVEMENT SECTION
GRANULAR MATERIALS, TYPE B
- 12" AGGREGATE SUBBASE
BINDER COURSE, IL-19, N70
- 10" HOT-MIX ASPHALT
SURFACE COURSE, MIX "D", N70
- 1 1/2" HOT-MIX. ASPHALT
ALLOWED BY THE VILLAGE ENGINEER:
TX5 GEOGRID (OR APPROVED EQUAL), AS
MAY BE USED, WITH THE USE OF TENSAR TRIAX
THE FOLLOWING ALTERNATE PAVEMENT SECTION
pvt-1 (arterial).dgn
48' 30"
FOOT (TYP.)
" PER41
THE VILLAGE ENGINEER.
AT 190 FOOT SPACING, UNLESS OTHERWISE DIRECTED BY
INSTALLED WITH AN OPPOSITE CONFIGURATION &
5. STANDARD ROADWAY TYPE LIGHT POLES SHALL BE
BY THE VILLAGE ENGINEER.
REDUCE AGGREGATE SUBBASE THICKNESS AS APPROVED
4. LIME MODIFICATION (OR EQUIVALENT) MAY BE USED TO
THE VILLAGE'S SUBDIVISION ORDINANCE.
MATERIALS SHALL BE DONE IN ACCORDANCE WITH
3. TESTING OF SUBGRADE AND ALL ROADWAY
SIX INCHES OF TOPSOIL.
2. PARKWAYS SHALL BE FINISHED WITH A MINIMUM OF
PSI AT 14 DAYS.
WITH A MINIMUM COMPRESSIVE STRENGTH OF 3,500
CONSTRUCTED WITH IDOT CLASS "SI" CONCRETE
1. ALL CURBS AND SIDEWALKS SHALL BE
NOTES:
DATE: SEPTEMBER 2014
MAJOR ARTERIAL
ROADWAY CROSS-SECTION
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
(SEE PVT-12)
SIDEWALK
(SEE PVT-14)
BIKEPATH
' 100' RIGHT OF WAY
(TYP.)
N70
COURSE, MIX "D",
ASPHALT SURFACE
1 1/2" HOT-MIX.
R.O.W. LINER.O.W. LINE
B-6.12 (SEE DETAIL)
CURB & GUTTER, TYPE
COMBINATION CONCRETE
MATERIALS, TYPE B
4" AGGREGATE SUBBASE GRANULAR
C/L
4"
1'
FOOT (TYP.)
" PER21
SLOPE AT
PARKWAY
FOOT (TYP.)
" PER41
26' 26'
18"45'
14' 10'
20'
48' BACK TO BACK
COURSE
" HOT-MIX ASPHALT BASE 21
8
PVT-2
5'
2'1'
BINDER COURSE, IL-19, N70
2 1/2" HOT-MIX ASPHALT
*ALTERNATE PAVEMENT SECTION
GRANULAR MATERIALS, TYPE B
- 8" AGGREGATE SUBBASE
COURSE
- 6" HOT-MIX ASPHALT BASE
BINDER COURSE, IL-19, N70
- 2 1/2" HOT-MIX ASPHALT
SURFACE COURSE, MIX "D", N70
- 1 1/2" HOT-MIX. ASPHALT
ALLOWED BY THE VILLAGE ENGINEER:
TX5 GEOGRID (OR APPROVED EQUAL), AS
MAY BE USED, WITH THE USE OF TENSAR TRIAX
THE FOLLOWING ALTERNATE PAVEMENT SECTION
BY THE VILLAGE ENGINEER.
& AT 125 FOOT SPACING, UNLESS OTHERWISE DIRECTED
INSTALLED WITH A SINGLE SIDED CONFIGURATION
5. STANDARD ROADWAY TYPE LIGHT POLES SHALL BE
APPROVED BY THE VILLAGE ENGINEER.
TO REDUCE AGGREGATE SUBBASE THICKNESS AS
4. LIME MODIFICATION (OR EQUIVALENT) MAY BE USED
SUBDIVISION ORDINANCE.
SHALL BE DONE IN ACCORDANCE WITH THE VILLAGE'S
3. TESTING OF SUBGRADE AND ALL ROADWAY MATERIALS
SIX INCHES OF TOPSOIL.
2. PARKWAYS SHALL BE FINISHED WITH A MINIMUM OF
COMPRESSIVE STRENGTH OF 3,500 PSI AT 14 DAYS.
WITH IDOT CLASS "SI" CONCRETE WITH A MINIMUM
1. ALL CURBS AND SIDEWALKS SHALL BE CONSTRUCTED
NOTES:
pvt-2 (major collector).dgn
DATE: SEPTEMBER 2014
MAJOR COLLECTOR
ROADWAY CROSS-SECTION
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
(SEE PVT-12)
SIDEWALK
(SEE PVT-14)
BIKEPATH
'
(TYP.)
N70
COURSE, MIX "D",
ASPHALT SURFACE
1 1/2" HOT-MIX.
R.O.W. LINER.O.W. LINE
B-6.12 (SEE DETAIL)
CURB & GUTTER, TYPE
COMBINATION CONCRETE
MATERIALS, TYPE B
4" AGGREGATE SUBBASE GRANULAR
C/L
4"
1'
FOOT (TYP.)
" PER21
SLOPE AT
PARKWAY
FOOT (TYP.)
" PER41
18"38'
10'
41' BACK TO BACK
PVT-3
80' RIGHT OF WAY
'2119 '2
119
5' '2113
'217 2'1'
BASE COURSE
" HOT-MIX ASPHALT 21
7
BINDER COURSE, IL-19, N70
2 1/2" HOT-MIX ASPHALT
*ALTERNATE PAVEMENT SECTION
GRANULAR MATERIALS, TYPE B
- 8" AGGREGATE SUBBASE
COURSE
- 5" HOT-MIX ASPHALT BASE
BINDER COURSE, IL-19, N70
- 2 1/2" HOT-MIX ASPHALT
SURFACE COURSE, MIX "D", N70
- 1 1/2" HOT-MIX. ASPHALT
ALLOWED BY THE VILLAGE ENGINEER:
TX5 GEOGRID (OR APPROVED EQUAL), AS
MAY BE USED, WITH THE USE OF TENSAR TRIAX
THE FOLLOWING ALTERNATE PAVEMENT SECTION
BY THE VILLAGE ENGINEER.
& AT 175 FOOT SPACING, UNLESS OTHERWISE DIRECTED
INSTALLED WITH A SINGLE SIDED CONFIGURATION
5. STANDARD ROADWAY TYPE LIGHT POLES SHALL BE
APPROVED BY THE VILLAGE ENGINEER.
TO REDUCE AGGREGATE SUBBASE THICKNESS AS
4. LIME MODIFICATION (OR EQUIVALENT) MAY BE USED
SUBDIVISION ORDINANCE.
SHALL BE DONE IN ACCORDANCE WITH THE VILLAGE'S
3. TESTING OF SUBGRADE AND ALL ROADWAY MATERIALS
SIX INCHES OF TOPSOIL.
2. PARKWAYS SHALL BE FINISHED WITH A MINIMUM OF
COMPRESSIVE STRENGTH OF 3,500 PSI AT 14 DAYS.
WITH IDOT CLASS "SI" CONCRETE WITH A MINIMUM
1. ALL CURBS AND SIDEWALKS SHALL BE CONSTRUCTED
NOTES:
pvt-3 (minor collector).dgn
DATE: SEPTEMBER 2014
MINOR COLLECTOR
ROADWAY CROSS-SECTION
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
(SEE PVT-12)
SIDEWALK
(SEE PVT-14)
BIKEPATH
66' RIGHT OF WAY
(TYP.)
R.O.W. LINER.O.W. LINE
14" PER
FOOT (TYP.)
IN ALL OTHER AREAS
(SEE DETAIL)
B-6.12,
CURB & GUTTER, TYPE
COMB. CONC.
AREAS, AND
RESIDENTIAL
(SEE DETAIL) IN
GUTTER, TYPE M-3.12,
CONCRETE CURB &
COMBINATION
1 12
SURFACE COURSE,
10" AGGREGATE BASE COURSE, TYPE B
C/L
1'
PRIME COAT, MC-30, AT 0.30
GAL./S.Y.
PARKWAY SLOPE
AT 12" PER
FOOT (TYP.)
PVT-4
12' 31' BACK TO BACK
28'11 1
2'
1'
17
18"5'
" HOT-MIX ASPHALT
4.5"
COURSE, IL-19, N50
3 1/2" HOT-MIX ASPHALT BINDER
MIX "D", N50
*ALTERNATE PAVEMENT SECTION
GRANULAR MATERIALS, TYPE B
- 8" AGGREGATE SUBBASE
BINDER COURSE, IL-19, N50
- 3" HOT-MIX ASPHALT
SURFACE COURSE, MIX "D", N50
- 1 1/2" HOT-MIX. ASPHALT
ALLOWED BY THE VILLAGE ENGINEER:
TX5 GEOGRID (OR APPROVED EQUAL), AS
MAY BE USED, WITH THE USE OF TENSAR TRIAX
THE FOLLOWING ALTERNATE PAVEMENT SECTION
PVT-4 (Local).dgn
OTHERWISE DIRECTED BY THE VILLAGE ENGINEER.
SIDED CONFIGURATION & AT 110 FOOT SPACING, UNLESS
POLES SHALL BE INSTALLED WITH A SINGLE
5. STANDARD SINGLE HEAD ORNAMENTAL TYPE LIGHT
APPROVED BY THE VILLAGE ENGINEER.
TO REDUCE AGGREGATE SUBBASE THICKNESS AS
4. LIME MODIFICATION (OR EQUIVALENT) MAY BE USED
THE VILLAGE'S SUBDIVISION ORDINANCE.
MATERIALS SHALL BE DONE IN ACCORDANCE WITH
3. TESTING OF SUBGRADE AND ALL ROADWAY
FOUR INCHES OF TOPSOIL.
2. PARKWAYS SHALL BE FINISHED WITH A MINIMUM OF
PSI AT 14 DAYS.
WITH A MINIMUM COMPRESSIVE STRENGTH OF 3,500
CONSTRUCTED WITH IDOT CLASS "SI" CONCRETE
1. ALL CURBS AND SIDEWALKS SHALL BE
NOTES:
DATE: SEPTEMBER 2014
LOCAL
ROADWAY CROSS-SECTION
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
SIDEWALK
(SEE PVT-12)
100' RIGHT OF WAY
PARKWAY
SLOPE AT
1/4" PER
FOOT
7" HOT MIX ASPHALT
BASE COURSE
R.O.W. LINER.O.W. LINE
4" CROWN
B 6.12 CURB &
GUTTER
6" CRUSHED AGGREGATE BASE
COURSE, TYPE B
C/L
4"
6"
2" HOT MIX ASPHALT
SURFACE COURSE,
MIX "D", N70
2 1/2" HOT MIX ASPHALT
BINDER COURSE, IL-19, N70
40' BACK TO BACK
37'24'
30'
5' 1.5'
1'
PVT-5
ALTERNATE PAVEMENT SECTION*
BY THE VILLAGE ENGINEER.
TO REDUCE AGGREGATE SUBBASE THICKNESS AS APPROVED
5. LIME MODIFICATION (OR EQUIVALENT) MAY BE USED
ORDINANCE.
DONE IN ACCORDANCE WITH THE VILLAGE'S SUBDIVISION
4. TESTING OF SUBGRADE AND ALL ROADWAY MATERIALS SHALL BE
OF TOPSOIL.
3. PARKWAYS SHALL BE FINISHED WITH A MINIMUM OF SIX INCHES
MINIMUM COMPRESSIVE STRENGTH OF 3500 PSI AT 14 DAYS.
2. ALL CURBS AND SIDEWALKS SHALL BE CONSTRUCTED WITH A
SUBMITTED FOR REVIEW AND APPROVAL
1. A CONCRETE PAVEMENT SECTION ALTERNATIVE MAY BE
NOTES:
TYPE B
- 8" CRUSHED AGGREGATE BASE COURSE,
- 5" HOT-MIX ASPHALT BASE COURSE
BINDER COURSE, IL-19, N70
- 2 1/2" HOT-MIX ASPHALT
SURFACE COURSE, MIX "D", N50
- 2" HOT-MIX. ASPHALT
ALLOWED BY THE VILLAGE ENGINEER:
TX5 GEOGRID (OR APPROVED EQUAL), AS
MAY BE USED, WITH THE USE OF TENSAR TRIAX
THE FOLLOWING ALTERNATE PAVEMENT SECTION
PVT-5 (Industrial).dgn
DATE: SEPTEMBER 2014
INDUSTRIAL
ROADWAY CROSS-SECTION
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
SIDEWALK
(SEE PVT-12)
GENERAL NOTES:
INTEGRAL CURB AND GUTTER SHALL NOT BE PERMITTED WITH RIGID OR COMPOSITE PAVEMENTS.
3.
2.
1.
TACK COAT
PRIME COAT
12" MIN.
ENGINEER
APPROVED BY SOILS
COMPACTED SUBGRADE
PROPERLY PREPARED AND
FOR VERIFYING REQUIRED PAVEMENT SECTION.
DIMENSIONS SHOWN ARE MINIMUM VALUES. SOIL ANALYSIS AND TRAFFIC COUNTS SHALL BE USED
THE FOLLOWING MATERIALS ARE ACCEPTABLE AS BASE COURSE ALTERNATIVES: BITUMINOUS BASE
COURSE AND P.C. CONCRETE.
SLOPE MIN. 1/4" PER FOOT
PVT-6
2-1/4" HOT MIX ASPHALT BINDER COURSE, IL-19, N50
APPROVED BY THE VILLAGE ENGINEER.
4. LIME MODIFICATION (OR EQUIVALENT) MAYBE USED TO REDUCE AGGREGATE BASE THICKNESS AS
*ALTERNATE PAVEMENT SECTION
1-1/2" HOT-MIX ASPHALT SURFACE COURSE, MIX "D", N50
AND GUTTER
B-6.12 COMBINATION CONCRETE CURB
10" COMPACTED AGGREGATE BASE, CA-6 (FOR AUTOMOBILE MOVEMENT)
14" COMPACTED AGGREGATE BASE, CA-6 (FOR TRUCK MOVEMENT)
- 10" COMPACTED AGGREGATE BASE, CA-6
BINDER COURSE, IL-19, N50
- 2-1/4" HOT-MIX ASPHALT
SURFACE COURSE, MIX "D", N70
- 1 1/2" HOT-MIX. ASPHALT
ENGINEER:
APPROVED EQUAL), AS ALLOWED BY THE VILLAGE
THE USE OF TENSAR TRIAX TX5 GEOGRID (OR
MAY BE USED FOR TRUCK MOVEMENT AREAS, WITH
THE FOLLOWING ALTERNATE PAVEMENT SECTION
PVT-6 (Parking Lot).dgn
DATE: SEPTEMBER 2014
PAVEMENT
TYPICAL PARKING LOT
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
PVT-7
...\PVT-7 (Right-in Right-out Driveway Entrance).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
RIGHT-IN RIGHT-OUT
DRIVEWAY ENTRANCE
DATE: JUNE 2007
PROPERTY LINE
EXISTING
EOP
VARIES
1’ MIN. RAD.
1’ MIN.
RAD.
14’
MIN
.14’MIN
.
50’ MIN. RAD.
35’ MIN.
RIGHT
TURN
ONLYSTOP
ONLY
DO NOT
ENTER
30"
30"
36"
36"
36"
36"
STANDARD
R5-1 SIGN
STANDARD
R1-1 SIGN
STANDARD
R3-2 SIGN
STANDARD
R3-2 SIGN
STANDARD
R3-5 SIGN
OR30"
30"
30"
24" 24"
30"
10’ MIN.
2’
50’M
IN.
RA
D.
R 2"
R 3"PITCH IN
SLOPE 3/4" PER FOOT
BITUMINOUS
SURFACE
4" CRUSHED AGGREGATE SUBBASE MATERIALS,
TYPE B
NOT TO SCALE
2- #5 DOWELS 2’ LONG
AT EXPANSION JOINTS
AND AT CONNECTIONS
BETWEEN NEW AND
EXISTING CURB AND
GUTTER
2- #4 BARS CONTINUOUS
THROUGHOUT CURB AND GUTTER
NOTES:
1. ALL CURB AND GUTTER SHALL BE CONSTRUCTED WITH IDOT CLASS SI
CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI AT 14 DAYS.
PROVIDE AND TEST 3 CYLINDERS FOR EACH DAY’S POUR, OR 50 CUBIC YARDS,
WHICHEVER IS LESS.
2. CONTRACTION JOINTS SHALL BE SAW-CUT AT 20’ INTERVALS AND CAULKED.
3. PREFORMED EXPANSION JOINTS, 3/4" THICK, SHALL BE PLACED FIVE FEET
EITHER SIDE OF STORM STRUCTURES IN CURB AND GUTTER, AT CURB RETURNS
AND AT POINTS OF CURVATURE, AT ALL CONNECTIONS BETWEEN NEW AND
EXISTING CURB AND GUTTER, AND AT 100’ INTERVALS ON TANGENTS.
4. CURB AND GUTTER AT STORM STRUCTURES SHALL BE BOXED-OUT AND
HAND-FORMED BETWEEN EXPANSION JOINTS. FORMS SHALL BE PLACED AND
INSPECTED BY VILLAGE PRIOR TO POURING CONCRETE. STRUCTURE FRAMES
SHALL BE PLACED AND ADJUSTED PRIOR TO THIS INSPECTION.
5. THE FOLLOWING SHALL BE STAMPED IN THE CURB AT THE INDICATED
LOCATIONS:
"W" FOR WATER SERVICES
"S" FOR SANITARY SEWER SERVICES
"ST" FOR STORM SEWER SERVICES
"CO" FOR STORM SEWER SERVICE LINE CLEAN-OUTS
TH
ICK
NE
SS
OF
PA
VE
ME
NT
ST
RU
CT
UR
E
6" (
CU
RB
HE
IGH
T)
12" GUTTER FLAG 1" 6"
1/4"
4" (
TY
P.)
6" 5"
1’
...\PVT\pvt-8 (b-6.12 curb).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
CONCRETE CURB & GUTTER
TYPE B-6.12
DATE: JUNE 2007
PVT-8
6. DOWELS AT EXPANSION JOINTS SHALL BE CENTERED ON THE
JOINT (DRILLED INTO EXISTING CURB AND GUTTER),
AND SHALL BE INSTALLED WITH GREASE CAPS ON ONE SIDE.
2- #4 BARS CONTINUOUS
THROUGHOUT CURB & GUTTER
1/4
"
R 4"
R 3"PITCH IN
SLOPE 3/4" PER FOOT
BITUMINOUS
SURFACE
NOT TO SCALE
2- #5
DOWELS 2’ LONG AT
EXPANSION JOINTS AND AT
CONNECTIONS BETWEEN NEW
AND EXISTING CURB AND
GUTTER
9 1/2"
TH
ICK
NE
SS
OF
PA
VE
ME
NT
ST
RU
CT
UR
E
4" (
TY
P.)
1’
2-3/4"
8 1/4"
6" 5"
4" CRUSHED AGGREGATE SUBBASE MATERIALS, TYPE B
...\PVT\pvt-9 (m-3.12 curb).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
CONCRETE CURB & GUTTER
TYPE M-3.12
DATE: JUNE 2007
PVT-9
NOTES:
1. ALL CURB AND GUTTER SHALL BE CONSTRUCTED WITH IDOT CLASS SI
CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI AT
14 DAYS. PROVIDE AND TEST 3 CYLINDERS FOR EACH DAY’S POUR, OR
50 CUBIC YARDS, WHICHEVER IS LESS.
2. CONTRACTION JOINTS SHALL BE SAW-CUT AT 20’ INTERVALS AND
CAULKED.
3. PREFORMED EXPANSION JOINTS, 3/4" THICK, SHALL BE PLACED FIVE
FEET EITHER SIDE OF STORM STRUCTURES IN CURB AND GUTTER, AT
CURB RETURNS AND AT POINTS OF CURVATURE, AT ALL CONNECTIONS
BETWEEN NEW AND EXISTING CURB AND GUTTER, AND AT 100’
INTERVALS ON TANGENTS.
4. CURB AND GUTTER AT STORM STRUCTURES SHALL BE BOXED-OUT
AND HAND-FORMED BETWEEN EXPANSION JOINTS. FORMS SHALL BE IN
PLACE AND INSPECTED BY VILLAGE PRIOR TO POURING CONCRETE.
STRUCTURE FRAMES SHALL BE PLACED AND ADJUSTED PRIOR TO THIS
INSPECTION.
5. THE FOLLOWING SHALL BE STAMPED IN THE CURB AT THE INDICATED
LOCATIONS:
"W" FOR WATER SERVICES
"S" FOR SANITARY SEWER SERVICES
"ST" FOR STORM SEWER SERVICES
"CO" FOR STORM SEWER SERVICE LINE CLEAN-OUTS
6. DOWELS AT EXPANSION JOINTS SHALL BE CENTERED ON THE JOINT
(DRILLED INTO EXISTING CURB AND GUTTER), AND SHALL BE INSTALLED
WITH GREASE CAPS ON ONE SIDE.
1’
DEPRESSED COMBINATION
CONCRETE CURB &
GUTTER
8" P.C.C
PAVEMENT
(3500 P.S.I. MIN)
5" CA-6
STONE BASE
5’
1% MIN - 8% MAX
2%
MAX
R.O.W. LINE
34" PREFORMED
EXISTING
ROADWAY
EXPANSION JOINT
5’
1’
20’ RAD.
MINIMUM
45%%176
B-6.12
CURB AND
GUTTER
SIDEWALK
CONTRACTION
JOINT (TYP.)
PL
ONE WAY
16’ MIN - 20’ MAX
TWO WAY
24’ MIN - 36’ MAX
34" PREFORMED
12" PREFORMEDEXPANSION JOINT(TYP)
EXPANSION JOINT
WITH (2) 1-1/4" EPOXY
COATED DOWEL BARS
WITH GREASE CAPS
(TYP)
5’
DEPRESSED CURB & GUTTER
EXISTING, PROPOSED, OR SAWCUT
EXISTING CURB
AND GUTTER
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
COMMERCIAL
ENTRANCE
DATE: JUNE 2007
PVT-11
NOTES:
1. ALL CONCRETE SHALL BE IDOT CLASS "SI" CONCRETE WITH A MINIMUM
COMPRESSIVE STRENGTH OF 3,500 PSI AT 14 DAYS.
2. THE SUBGRADE SHALL BE STABLE AND MECHANICALLY COMPACTED.
3. ALL AGGREGATE SUBBASE SHALL BE MECHANICALLY COMPACTED.
4. CONCRETE AND BASE THICKNESS OF SIDEWALK THRU DRIVEWAY SHALL
MATCH THAT OF DRIVEWAY.
5. WELDED WIRE FABRIC (6"X6") OR WIRE MESH SHALL BE INSTALLED IN
DRIVEWAYS AND IN SIDEWALKS THROUGH DRIVEWAYS AT 2" ABOVE BOTTOM
SLAB.
...\PVT-11 (Nonresidential Driveway).dgn
5'
4"
FROM EDGES OF WALK.
FROM EACH OTHER AND
A MINIMUM OF 6 INCHES
BARS SHALL BE SPACED
(TYP. FOR 3)
SIDEWALKS.
NEW AND EXISTING
CONNECTIONS BETWEEN
EMBEDDED 6", AT ALL
BARS, 12" LONG,
INSTALL #4 REINFORCING
"21
2
CA-6 STONE BASE
(3")
(TYP.)
$FILEABBREV$
6"
PVT-12
5"
DATE: MARCH 2017
SIDEWALK
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
ALL UTILITY TRENCHES FOR NEW SIDEWALK.
7. USE 2 #4 REINFORCING BARS, 10' LONG OVER
6. FORMBOARD REQUIREMENTS: MINIMUM 2" X 6".
ABOVE SLAB BOTTOM.
SHALL BE INSTALLED THROUGH DRIVEWAYS AT 2"
5. WELDED WIRE FABRIC (6X6/6X6) OR FIBER MESH
SLOPE.
" PER FOOT CROSS- 414. SIDEWALK SHALL HAVE
CONSTRUCTED IN SIDEWALK EVERY FIVE FEET.
3. TOOLED CONTRACTION JOINTS SHALL BE
GUTTER.
AND AT ALL ABUTTING DRIVEWAYS AND CURB AND
BE CONSTRUCTED IN SIDEWALK EVERY 100 FEET
" THICK) SHALL432. PREFORMED EXPANSION JOINTS (
COMPRESSIVE STRENGTH OF 3,500 PSI AT 14 DAYS
CLASS "SI" CONCRETE WITH A MINIMUM
1. ALL SIDEWALK SHALL BE CONSTRUCTED WITH IDOT
GENERAL NOTES:
THICKNESS SHALL MATCH THAT OF THE DRIVEWAY.
8. AT DRIVEWAYS, SIDEWALK PCC AND BASE
BEEN VERIFIED BY THE VILLAGE TO BE IN COMPLIANT.
UNTIL ALL FACILITIES IN THE PUBLIC ROW HAVE
VILLAGE WILL NOT ACCEPT PUBLIC IMPROVEMENTS
WITH CURRENT ADA/PROWAG REGULATIONS. THE
RAMPS AND SIDEWALKS ARE FULLY COMPLIANT
RESPONSIBLE FOR ENSURING THAT ALL CURB
DEVELOPER AND THEIR CONTRACTOR SHALL BE
AS PART OF THE ROADWAY CONSTRUCTION. THE
WITHIN THE PUBLIC ROW SHALL BE CONSTRUCTED
3. FOR DEVELOPMENT PROJECTS, ALL CURB RAMPS
ELEVATIONS, SLOPES AND GRADE BREAKS.
DETECTABLE WARNINGS, PROPOSED SPOT
REQUIREMENTS, INCLUDING PLACEMENT OF
COMPLIANCE WITH CURRENT ADA/PROWAG
WITH SUFFICIENT INFO TO DEMONSTRATE
FOR EACH CURB RAMP WITHIN THE PUBLIC ROW
2. DEVELOPMENT PLANS SHALL INCLUDE A DETAIL
SUBMITTED TO THE VILLAGE FOR REVIEW.
RAMP DETAILS SHALL BE INCLUDED IN PLANS
REGULATIONS. APPLICABLE IDOT STANDARD CURB
RAMPS, AS WELL AS CURRENT ADA AND PROWAG
CURRENT IDOT STANDARD DETAILS FOR CURB
CONSTRUCTED IN STRICT COMPLIANCE WITH
1. ALL SIDEWALKS AND CURB RAMPS SHALL BE
ADA/PROWAG COMPLIANCE NOTES:
MATCH SLOPE
DIRECTION OF EXIST.
GRADING (2.0% MAX)
(TYP.)
R.O.W.
AT 45° ANGLE
BEVEL EDGES
8" AGGREGATE BASE COURSE, CA 6
10' FOR COLLECTOR STREETS
WIDTH = 8' FOR LOCAL STREETS
REQUIREMENTS.
AS REQUIRED TO MEET MINIMUM STABILITY
RE-USED MUST BE TESTED AND COMPACTED
ALL EXISTING SUBGRADE MATERIALS TO BE
NOTE:
WIDTH + 2'
WIDTH
WIDTH/2
2'
1'
PVT-14
DATE: SEPTEMBER 2014
PATH PAVEMENT
BITUMINOUS BICYCLE
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
pvt-14 (bituminous bikepath)
COMPACTED SUBGRADE
INSTALLED PER MANUFACTURER RECOMMENDATIONS.
TENSAR TRIAX TX5 GEOGRID (OR APPROVED EQUAL)
COURSE, MIX "D", N50
2" HOT-MIX ASPHALT SURFACE
R.O.W.
EXPANSION JOINT
T=
63.5
8’
22%%d 22%%d
LINE
SET BACK
30’
R.O
.W.
15’R
PVT-15
1’
5’
62’R 11’
66’
5’
1’
5’
1’
98.4
7’ T
O C
EN
TE
R
60’R
31’
NOTES:
1. MINIMUM PARKWAY WIDTH
SHALL BE 11.0’.
...\PVT-15 (Cul-De-Sac Concentric).dgn
11.5’ 11.5’
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
CONCENTRIC CUL-DE-SAC
DATE: JUNE 2007
45.0’ R
B/C
NOTES:
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
ECCENTRIC CUL-DE-SAC
DATE: JUNE 2007
30’
SET
BACK LINEEXPANSION JOINT
11.0
’
11.0’
37%%d-30’
45.0’R. B
/C
62’R
. R
.O.W
.
45.0
’R. B
/C
TR
AN
SIT
ION
CU
RB
43’R. B/C
60%%d
11
4.6
6’(3
4.9
5M
) T
O C
EN
TE
R
60’R
R.O.W.
1. MINIMUM PARKWAY WIDTH
PVT-16
50’ MIN. ARC
11.5’
5’
1’
T=63.5
7’
15’R
15’R
66’
31’11.5’
5’
1’
11.5’
5’
1’
SHALL BE 11.0’.
...\PVT-16 (Cul-De-Sac Eccentric).dgn
______
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
___________
_____________
DATE: APRIL 2007
...\PVT-16 (Cul-De-Sac Eccentric).dgn
SECTION B-B
SECTION A-A
LC
LC
A
A
B B
EXISTING SUBBASE (TYP.)
EXISTING BASE (TYP.)
EXISTING BINDER (TYP.)
EXISTING SURFACE (TYP.)
(TYP.)
PROPOSED SUBBASE
PROPOSED SURFACE
PROPOSED BINDER
PROPOSED SUBBASE
PROPOSED BASE
EXISTING SUBBASE
EXISTING BASE (TYP.)
EXISTING BINDER (TYP.)
EXISTING SURFACE (TYP.)
(TYP.)
PROPOSED SURFACE
PROPOSED BINDER
PROPOSED CURB &
GUTTER18"
PROPOSED BASE
IS DIFFICULT, CONCRETE SHALL BE USED.
FOR WIDENING LESS THAN 8’(2.44M) WHERE COMPACTION
PROPOSED
WIDENING
EXISTING ROADWAY EDGE
EXISTING CURB
& GUTTER
(TYP.)
EDGE OF BUTT JOINT
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
BUTT JOINT
DATE: JUNE 2007...\PVT\PVT-17 (Butt Joint).dgn
PVT-17
6’
3’ (TYP.)
3’
6’
C
SECTION A-A
VARIABLE
SECTION B-B SECTION C-C
CONSTRUCTION JOINT
CONSTRUCTION JOINT
SECTION F-F
36"
A
BB
A
B B
C
C
36" MIN.
B
VARIABLE
F
B
F
EXISTING LONGITUDINAL JOINT
MIN.
(BUILT IN TWO OPERATIONS)
EXIST. PAV’T
EXIST. PAVEMENT(3’-0") TO
(5’-0")
(3’-0") TO
(5’-0")
(BUILT IN TWO OPERATIONS)
GENERAL NOTES:
LLC
CL
PVT-18
...\PVT-18 (Bituminous Pavement Patching).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
BITUMINOUS PAVEMENT
PATCHING
DATE: JUNE 2007
ANGLES NOT LESS THAN 60%%176
THAN 60%%176
1. EXISTING TIE BARS SHALL BE EITHER CUT OR REMOVED. MARGINAL BARS SHALL BE CUT.
2. IN LOCATIONS WHERE BITUMINOUS PATCHES WILL BE OVERLAYED WITH BITUMINOUS
SURFACE COURSE, STRIP REFLECTIVE CRACK CONTROL TREATMENT SHALL BE APPLIED
TO ALL PAVEMENT JOINTS AND CENTERED ALONG THE RESPECTIVE JOINTS.
3. IN LOCATIONS WHERE THE PAVEMENT PATCH WILL NOT BE OVERLAYED, TWO (2) INCHES
OF BITUMINOUS SURFACE COURSE SHALL BE LAID IN THE FINAL LIFT OF THE PATCH.
4. THE DEPTH OF THE BITUMINOUS PAVEMENT PATCH SHALL MATCH THE FULL DEPTH OF
THE EXISTING PAVEMENT, BUT SHALL NOT BE LESS THAN THE VILLAGE STANDARD
FOR THE RESPECTIVE PAVEMENT SECTION.
PAVEMENT
PATCHING LIMITS
STRIP REFLECTIVE
CRACK CONTROL
TREATMENT - SYSTEM B
PER IDOT STANDARDS
ANGLES NOTLESS
...\PVT-19 (open cutting pavement).dgn
VARIABLE
IDOT CA-7
BEDDING AND 4"
PVT-19
UTILITY PIPE
CONTROLLED LOW-STRENGTH
MATERIAL (CLSM)
TOP OF PAVEMENT
NEW PAVEMENT
MATCH EXISTING PAVEMENT SECTION
12" MIN. 12" MIN.
SUBGRADE
ELEVATION
IF ENCOUNTERED, REMOVE
UNSUITABLE MATERIAL AND
REPLACE WITH AGGREGATE
MATERIAL, AS APPROVED
BY VILLAGE
NOTES:
1. THIS DETAIL SHALL BE USED FOR TRENCHING OPERATIONS WITHIN THE
PUBLIC RIGHT-OF-WAY THAT ARE WITHIN FIVE (5) FEET OF STREETS,
DRIVEWAYS, CURB AND GUTTER, PARKING LOTS AND OTHER PAVED AREAS
INTENDED FOR VEHICULAR TRAVEL AS REQUIRED BY THE VILLAGE.
2. CONTROLLED LOW-STRENGTH MATERIAL (CLSM) SHALL BE IN
ACCORDANCE WITH SECTION 593 OF THE IDOT SPECIFICATIONS AND
SECTION 20-3.03 OF THE STANDARD SPECIFICATIONS FOR WATER AND
SEWER CONSTRUCTION IN ILLINOIS, LATEST VERSIONS.
3. THERMAL PROTECTION SHALL BE PROVIDED PER IDOT STANDARD
SPECIFICATIONS AND AS DIRECTED BY THE VILLAGE.
6"
HAUNCHING TO
6" ABOVE PIPE
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
OPEN CUTTING PAVEMENT
WITHIN THE PUBLIC
RIGHT-OF-WAY
DATE: OCTOBER 2009
PVT-20
...\PVT\PVT-20 (Crack Seal).dgn
DATE: MAY 2011
SEALING
PAVEMENT CRACK
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
CROSS SECTION
PAVEMENT CRACK
1/32" MAX
1"
1" PER SPECIFICATIONS
ROUTE & FILL CRACK
PRIOR TO THE START OF ANY WORK.
CONTRACTOR SHALL SUBMIT A CONSTRUCTION SCHEDULE AND SEQUENCE OF STREETS TO BE CRACK SEALED AT LEAST SEVEN (7) DAYS
SEALANT TO MINIMIZE TRACKING BY VEHICULAR TRAFFIC.
A COVER CONSISTING OF DRY SAND APPROVED BY THE ENGINEER SHALL BE APPLIED IMMEDIATELY TO THE HOT-POURED RUBBER-ASPHALT
A RESIDUAL AMOUNT OF SEALANT MATERIAL SHALL BE APPLIED TO FILL ANY EXCESSIVE SAGS OR VOIDS AFTER THE INITIAL APPLICATION.
TYPE EFFECT APPROXIMATELY 2 INCHES WIDE FLUSH WITH THE PAVEMENT SURFACE WITH THE EDGES FEATHERED OUT. IF NECESSARY,
PENETRATION, THE SEALANT SHALL BE "SQUEEGEED" ALONG THE CRACK WITH A "V" SHAPED SQUEEGEE, TO PROVIDE A "BAND AID"
OR JOINT UNTIL FULL, LEAVING NO EXCESSIVE SAGS OR VOIDS IN APPLIED MATERIAL ALONG THE CRACK. TO ENSURE FULL DEPTH
AS RECOMMENDED BY THE APPLICABLE MANUFACTURER’S SPECIFICATIONS. THIS SEALANT MATERIAL SHALL BE FORCED INTO THE CRACK
THE HOT-POURED RUBBER-ASPHALT MATERIAL SHALL BE MELTED AND MIX-AGITATED TO THE PROPER TEMPERATURE, RATE AND TIME
APPLIED IMMEDIATELY FOLLOWING THE CLEANING OF THE CRACKS.
ROUTING OF CRACKS SHALL BE FOLLOWED BY CLEANING OF THE CRACKS WITH FORCED AIR. THE SEALANT MATERIAL SHALL BE
ROUTING. STREETS HAVING A CONCRETE SURFACE SHALL NOT REQUIRE ROUTING OF THE CRACKS PRIOR TO CLEANING AND SEALING.
ROUTED AS THIS MAY POP LOOSE THE SURROUNDING ASPHALT. THESE AREAS SHALL BE BLOWN CLEAN AND SEALED WITHOUT
ROUTED TO A MINIMUM DEPTH OF ONE INCH. CRACKS THAT ARE BORDERED BY EXCESSIVE "ALLIGATORED" AREAS SHALL NOT BE
ASPHALT MATERIAL, ALL CRACKS AND JOINTS TO BE SEALED SHALL BE ROUTED. ALL CRACKS LESS THAN ¾ INCH WIDE SHALL BE
ALL CRACKS AND JOINTS UP TO 1-‰ INCHES IN WIDTH SHALL BE SEALED. PRIOR TO APPLICATION OF THE HOT-POURED RUBBER-
THE CRACK FILLER MAY BE PLACED WHEN AIR TEMPERATURES IN THE SHADES ARE 40^F AND THE FORECAST IS FOR RISING TEMPERATURE.
FILLING MATERIAL SHALL BE PLACED ONLY WHEN THE CRACKS ARE IN A DRY CONDITION AND WEATHER CONDITIONS ARE FAVORABLE.
SEVEN (7) DAYS PRIOR TO THE START OF ANY WORK. THE POURING TEMPERATURE OF THE CRACK SEALER SHALL BE 370^F. CRACK
THE CONTRACTOR SHALL SUBMIT THE MANUFACTURER’S SPECIFICATIONS FOR THE HOT-POURED RUBBER-ASPHALT MATERIAL AT LEAST
EXCEEDS REQUIREMENTS OF: ASTM-D-1190, AASHTO-M-173, SS-S-164
SAFE HEATING TEMPERATURE - 390^F
POURING TEMPATURE - 370^F
ASTM D-3405
FEDERAL SPECIFICATIONS SS-S-1401
AT THE TIME OF THE CONTRACT.
THE SEALING COMPOUND SHALL BE THE RUBBER-ASPHALT HOT-POURED TYPE CONFORMING TO THE FOLLOWING SPECIFICATION IN EFFECT
THE ENGINEER.
THIS WORK SHALL CONSIST OF CLEANING EXISTING ROADWAY CRACKS AND PLACING RUBBER SEALANT AT THE LOCATIONS DESIGNATED BY
SPECIFICATIONS:
ENGINEER.
ROADWAYS IN ACCORDANCE WITH THIS DETAIL SHALL BE COMPLETED TO THE SATISFACTION OF THE
NOTE: PRIOR TO FINAL ACCEPTANCE OF A SUBDIVISION BY THE VILLAGE, CRACK SEALING OF ALL PUBLIC
PINNED JOINT
SIDEWALK
CURB & GUTTER
NOTES:
R.O.W.
PVT-21
3/4" PREFORMED
...\PVT-21 (Driveway Pinning).dgn
NEW PCC DRIVEWAY APRON
PER STD. DETAIL PVT-10
SEE NOTE #1
EXPANSION JOINT
EXISTING PCC DRIVEWAY
PAVEMENT TO REMAIN
(SAWCUT PAVEMENT PRIOR
TO REMOVAL)
DRIVEWAY APRON
6" FROM EDGE (TYP.)
1. AT LOCATIONS WHERE ONLY A PORTION OF DRIVEWAY
APRON IS TO BE REMOVED, NEW DRIVEWAY PAVEMENT
SHALL BE CONCRETE AND SHALL BE PINNED TO THE
EXISTING DRIVEWAY APRON WITH #4 REBAR A MINIMUM
OF 6" INTO THE EXISTING SLAB. AFTER INSTALLATION,
REBAR SHALL PROTRUDE FROM EXISTING DRIVEWAY
PAVEMENT A MINIMUM OF 6". SIX (6) REBAR SHALL BE
EVENLY SPACED IN EACH DRIVEWAY, STARTING 6" FROM
EITHER DRIVEWAY EDGE.
2. FORMBOARD REQUIREMENTS: MINIMUM 2" X 6".
3. WELDED WIRE FABRIC (6"X6") OR WIRE MESH SHALL BE
INSTALLED IN NEW DRIVEWAY PAVEMENT AT 2" ABOVE
BOTTOM SLAB PER STD. DETAIL PVT-10.
4. PREFORMED EXPANSION JOINTS (3/4" THICK) SHALL
BE CONSTRUCTED AT LOCATIONS WHERE NEW
DRIVEWAY PAVEMENT ABUTS CURB AND GUTTER.
5. ALL AGGREGATE SUBBASE SHALL BE MECHANICALLY
COMPACTED.
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
TYPICAL DRIVEWAY PINNING
DATE: AUGUST 2011
NO SCALE
IDOT CA-7
UNDER OR WITHIN
5 FEET
HORIZONTALLY OF
PAVEMENT,
SIDEWALK, CURB
& GUTTER OR
DRIVEWAYS, OR
WHERE INDICATED
ON PLANS
IDOT CA-7
BEDDING AND
HAUNCHING
EXCAVATED MATERIALS,
COMPACTED TO 85%
MODIFIED PROCTOR
MAXIMUM DENSITY,
EXCEPT WHERE CA-7
IS REQUIRED
STORM SEWER SHALL BE
REINFORCED CONCRETE
PIPE, COMPLYING WITH
ASTM C76, CLASS IV, WITH
RUBBER RING GASKET
JOINTS MEETING ASTM
C443. WHERE ELLIPTICAL
PIPE IS USED, IT SHALL
COMPLY WITH ASTM C507.
...\stm-1 (storm sewer installation).dgn
4"
5’-6
" M
IN
. C
OV
ER
NOTES:
1. STORM SEWER SHALL BE TELEVISED FOLLOWING COMED AND
NICOR UNDERGROUND UTILITIES AND PRIOR TO THE ISSUANCE
OF THE FIRST CERTIFICATE OF FINAL OCCUPANCY.
STM-1
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
STORM SEWER INSTALLATION
DATE: JUNE 2007
NOTE:
1. MANHOLE BARREL JOINTS SHALL BE TONGUE AND GROOVE TYPE WITH TWO ROWS OF EXTRUDIBLE PREFORMED PLASTIC
GASKET MATERIAL (BUTYL ROPE).
2. INTERIOR JOINTS SHALL BE "BUTTERED" WITH NON-SHRINK GROUT.
3. STORM MANHOLES SHALL HAVE A WALL THICKNESS OF 6" FOR 5’ DIAMETER STRUCTURES AND 7" FOR 6’ DIAMETER
STRUCTURES
4. SEE CASTING INSTALLATION AND ADJUSTING DETAIL FOR CASTING REQUIREMENTS.
DRAINAGE FABRIC 18" WIDE
MIRAFI 140S OR
APPROVED EQUAL. *
5"
4’ FOR SEWER 24" &
UNDER, 5’ FOR SEWER 27"
TO 36" OR AS INDICATED
ON PLANS
STEPS SHALL BE COPOLYMER
POLYPROPYLENE PLASTIC WITH A
CONTINUOUS 12-INCH STEEL
REINFORCEMENT AS MANUFACTURED BY
M.A. INDUSTRIES, INC., OR APPROVED EQUAL
PRECAST CONCRETE
6" BASE (TYP.)
5" (MIN.)
8"
2’-0"
16
"
(TY
P.)
BENCH FOR ALL
MANHOLES
4" CA-7 BEDDING
FLOW
NO SCALE
1
1
CONCRETE SECTIONS AND
BOTTOM PER ASTM C478
R-2"–
14"
5"
2’-0"
CLASS SI
CONCRETE
*NOTE: FOR STORM SEWER ONLY
1" DIA. WEEP HOLES
(6 EACH)
AT 60° TYPICAL *
PLAN
SECTION
6"
TOPSOIL & SOD.
PAVEMENT OR
FABRIC
A
12" 12"
6"
STONEWASHED
MORTAR WEEP HOLES LOWERTHAN 6" BELOW FRAME *
+
60
HOLES
WEEP
A
STM-2
...\stm-2 (storm manhole type a).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
STORM MANHOLE TYPE A
DATE: JUNE 2007
WEEP
HOLES
DRAINAGE FABRIC 18" WIDE
MIRAFI 140S
OR APPROVED EQUAL.
SECTION
PLAN
+
FABRIC
1" DIA. WEEP HOLES
(6 EACH)
AT 60 TYPICAL
PAVEMENT ORTOPSOIL & SOD.
WASHEDSTONE
A A
60
UNLESS OTHERWISE
SPECIFIED ON PLANS
STEPS SHALL BE COPOLYMER
POLYPROPYLENE PLASTIC
WITH A CONTINUOUS 1/2
-INCH STEEL REINFORCEMENT
AS MANUFACTURED BY M.A.
INDUSTRIES, INC., OR
APPROVED EQUAL
TWO ROWS EXTRUDIBLE
PREFORMED PLASTIC
GASKET (TYPICAL ALL
JOINTS)
R 2"
ROTATE CB TOP SECT. AS NECESSARY TO
ACHIEVE OPTIMAL CASTING ALIGNMENT
NO SCALE
NOTES:
1. SEE CASTING INSTALLATION AND ADJUSTMENT DETAIL FOR
CASTING REQUIREMENTS.
2. INTERIOR JOINTS SHALL BE "BUTTERED" WITH NON-SHRINK
GROUT.
3. STRUCTURE SHALL COMPLY WITH ASTM C478.
4" C
A-7
BE
DD
IN
G
2’-6
"
T4’-0"
6"
16" (
TY
P)
8"
2’-0"
2’-6
" T
O 3
’-0
"
T
6"
12"12"
6"
MORTAR WEEP HOLES LOWER
THAN 6" BELOW FRAME
...\stm-3 (catch basin type a).dgn
STM-3
4. T = STRUCTURE INSIDE DIAMETER +1" (5" MINIMUM)
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
CATCH BASIN TYPE A
DATE: JUNE 2007
SECTION
PLAN
+
NO SCALE
4" CA-7 BEDDING
T
4"
2’-0"
T 2’-0"
6"
6"
12" 12"
WEEP
HOLES
MORTAR WEEP HOLES LOWER
THAN 6" BELOW FRAME
DRAINAGE FABRIC 18" WIDE
MIRAFI 140S
OR APPROVED EQUAL.
FABRIC
1" DIA. WEEP HOLES
(6 EACH)
AT 60 TYPICAL
PAVEMENT ORTOPSOIL & SOD.
WASHEDSTONE
AA
60
15
" S
UM
P
VA
RIA
BL
E (
46
" M
INIM
UM
)
OUTLET
6"
8"
MA
X.
PRECAST ADJUSTINGRINGS (2 MAX.)
NOTES:
1. FRAMES AND LIDS TO BE AS SHOWN IN GENERAL NOTES.
2. CATCH BASINS TO BE OF PRECAST REINFORCED CONCRETE
CONSTRUCTION ONLY.
3. FOR ADJUSTMENTS, USE ONLY PRECAST CONCRETE ADJUSTING
RINGS, MAXIMUM OF 8" TOTAL HEIGHT.
4. ADJUSTING RINGS AND FRAMES TO BE JOINED WITH MORTAR.
5. FOR RIM AND PIPE INVERT ELEVATIONS, REFER TO PLANS.
6. T = STRUCTURE INSIDE DIAMETER +1" (MINIMUM 5").
...\stm-4 (catch basin type c).dgn
STM-4
TOP OF
MASONRY
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
CATCH BASIN TYPE C
DATE: JUNE 2007
CONCRETE FILLET
BEDDING
4" CA-7
NO SCALE
PRECAST CONCRETE
BOTTOM
CAST-IN-PLACE
SLOPE TO DRAIN
R=2"
NOTES:
1. SEE CASTING INSTALLATION AND ADJUSTMENT
DETAIL FOR CASTING REQUIREMENTS.
2. INTERIOR JOINTS SHALL BE "BUTTERED" WITH
NON-SHRINK GROUT.
3. STRUCTURE SHALL COMPLY WITH ASTM C478.
2’-0" DIA.
5" MIN. 5" MIN.
...\STM\stm-5 (inlet).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
INLET
DATE: JUNE 2007
STM-5
NO SCALE
...\stm-6 (casting install & adjust).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
CASTING INSTALLATION AND
ADJUSTING
DATE: JUNE 2007
PRECAST ADJUSTING
RINGS (SEE NOTE 1)
FOR GROOVED
ADJUSTING RINGS
NOTES:
1. THERE SHALL BE A MAXIMUM OF 2 ADJUSTING RINGS WITH A MAXIMUM TOTAL HEIGHT OF 12".
2. ALL STRUCTURES IN CURB AND GUTTER OR PAVED AREAS SHALL USE PREFORMED RUBBER
ADJUSTING RINGS.
3. IF THE CASTING MUST BE INSTALLED ON A SLOPE, PREFORMED RUBBER TAPERED RINGS MAY BE
USED.
4. ADJUSTING RINGS 2" OR LESS IN THICKNESS SHALL BE PREFORMED RUBBER.
5. THE FOLLOWING CASTING, OR APPROVED EQUAL, SHALL BE UTILIZED AS INDICATED:
A. SANITARY MANHOLES: EAST JORDAN IRON WORKS #1050, EX HD WATERTIGHT LID WITH CONCEALED
PICKHOLE, O-RING GASKETS, AND "SHOREWOOD" AND "SANITARY" CAST IN LID.
B. WATER VALVE VAULTS: EAST JORDAN IRON WORKS #1050, EX HD WATERIGHT LID WITH CONCEALED
PICKHOLE, O-RING GASKETS, AND "SHOREWOOD" AND "WATER" CAST IN LID.
C. STORM MANHOLES: EAST JORDAN IRON WORKS #1050, EX HD LID WITH CONCEALED PICKHOLE, AND
"SHOREWOOD" AND "STORM" CAST IN LID, FOR LIDS INDICATED AS "SOLID" ON PLANS. FOR LIDS
INDICATED AS "OPEN" ON PLANS, USE THE SAME CASTING, BUT WITH A TYPE M1 RADIAL FLAT GRATE.
D. DRAINAGE STRUCTURES IN AREAS WITH UNPAVED SURFACES: EAST JORDAN IRON WORKS 6527.
E. DRAINAGE STRUCTURES IN MOUNTABLE CURB AND GUTTER: EAST JORDAN IRON WORKS #7171 WITH
TYPE M1 GRATE.
F. DRAINAGE STRUCTURES IN BARRIER CURB AND GUTTER: EAST JORDAN IRON WORKS #7210 WITH
TYPE M2 GRATE.
TOP SECTION
ONE ROW
OF
EXTRUDIBLE
PREFORMED
PLASTIC
GASKET
PER
GROOVE
FOR
GROOVED
ADJUSTING
RINGS.
BUTT ENDS
TO GRADE
SHOWN ON
PLANS –
0.5°
CASTING
FOR SMOOTH FACED
ADJUSTING RING TWO
ROWS OF EXTRUDIBLE
PREFORMED PLASTIC
GASKET EACH
JOINT-OVERLAY ENDS
OF GASKET. ONE ROW
ONLY REQUIRED ON
STORM STRUCTURES
AND WATER VALVES
TOP
SECTION
TYPE A MH
CATCH
BASIN INLET
VALVE VAULT
2" MIN
12"MAX
STM-6
SECTION A-A
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
SUBSURFACE DRAIN TILE
& SUMP PUMP CONNECTION
DATE: JUNE 2007
FINISH GRADE
EXISTING DRAINAGE
CASTING
STRUCTURE WITH
NON-SHRINK
MORTAR
COLLAR
6" MIN.
PROPOSED
DRAIN TILE
CONNECTION HOLE SHALL
A
A
DRAIN TILE PIPE SHALL
40 P.V.C.
BE CORE DRILLED.
PERFORATED
TOPSOIL
NON-WOVEN GEOTEXTILE
FABRIC
6" MIN. 6"MIN.
6" MIN.
3/4" WASHED AGG.
MIN. 6" AROUND PIPE.
STM-7
BE 4" DIA. SCHEDULE
PERFORATIONS
(DRAIN TILE ONLY)
NOTES:
1. SEE DETAIL STM-8 FOR RESIDENTIAL SUMP DISHARGE SERVICE LINE.
...\STM-7 (Drain Tile & Sump Pump Connection).dgn
4" DIAMETER DRAIN TILE
OR SUMP PUMP PIPE
GRANULAR
FILL
FINISHED LOCATION TO
HOUSE
NOTES:
1. SUMP PUMP CONNECTION LINES SHALL BE POLYVINYL CHLORIDE (PVC) SDR 35
CONFORMING TO ASTM D-3034, SIZE AS INDICATED ON THE PLANS.
2. TRUNK LINES SHALL BE INSTALLED A MINIMUM OF THIRTY (30) INCHES BELOW THE TOP
OF CURB AND FOLLOW THE CURB LINE FOR GRADE, AND SHALL BE LOCATED 2 FEET
BEHIND THE FRONT PROPERTY LINE.
3. 10 GAUGE UNDERGROUND FEEDER TRACER WIRE SHALL BE INSTALLED IMMEDIATELY
ABOVE THE TRUNK LINES AND SHALL TERMINATE AT THE CLEANOUTS OR STUBS. TRACER
WIRE SHALL BE STRAPPED TO ALL STUBS AND CLEANOUTS AND SHALL EXTEND
CONTINUOUSLY ALONG ALL PIPES, STUBS, AND CLEANOUTS. ADEQUATE WIRE SHALL BE
LEFT IN ALL STRUCTURES TO ALLOW IT TO BE RAISED ABOVE THE FRAME. TRACER WIRE
SHALL BE LOOPED BACK TO THE SERVICE STUB AND SHALL BE EXTENDED UP THROUGH
THE CLEANOUT TO SURFACE GRADE. SPLICES IN TRACER WIRE SHALL USE A NO. 8 SPLIT
BOLT SEALED WITH SELF-VULCANIZING TAPE.
4. UNDERGROUND CONTRACTOR SHALL ROTATE ELBOWS TO INSTALL SERVICE STUBS AS
SHOWN IN TEMPORARY LOCATION.
5. HOUSE CONTRACTOR SHALL ROTATE ELBOWS TO INSTALL SERVICES AS SHOWN IN
FINISHED LOCATION.
6. ALL CONNECTIONS TO INLETS, CATCH BASINS, OR
MANHOLES FOR SERVICE STUBS OF SUMP PUMP
MAINLINES SHALL BE CORED AND NOT SAWCUT.
7. PRIOR TO FINAL ACCEPTANCE OF THE SUMP
PUMP COLLECTION SYSTEM, THE ENTIRE SYSTEM SHALL
BE TELEVISED. A COPY OF THE VIDEO TAPE SHALL BE
DELIVERED TO THE PUBLIC WORKS DEPT. AND ANY
OBSTRUCTIONS SHALL BE REPAIRED.
ELEVATION
NO SCALE
REMOVABLE WATER
TIGHT PLUG
PROPERTY
LINEPUBLIC
WALK
STORM
STRUCTURE
CLEANOUT
TYPICAL TRUNK LINE (PLAN VIEW)
NO SCALE
TYPICAL TRUNK LINE (PROFILE VIEW)
NO SCALE
45 BENDS ONLY, 90 BENDS
ARE NOT PERMITTED
6" SUMP PUMP TRUNK SEWER
4" SERVICE LINE (TYP.)
4" SERVICE LINE (TYP.)
W/CONNECTIONSONLY (TYP.)
SEE SAN-X FOR CONNECTION DETAIL
30"
3’-6"
MIN
IMU
M
...\STM-8 (Sump Discharge Service Line).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
SUMP DISCHARGE SERVICE
LINE
DATE: JUNE 2007
STM-8
STM-9
$FILEABBREV$
SIDE VIEW
1
SECTION A-A
1
4
PLAN
3
5
AA
#
1
2
3
4
5
TIE ANCHORS
WITH EXPANSION
LAP HORIZONTALS
#5 @ 9" EACH WAY
8"
FLOW
DIA.
PIP
E
INVERT
2" CL.
DIA.
PIP
EFLOW
6"
INVERT
INVERT
(MIN.)
3" CL.
#6 @ 9" EACH WAY
FLOW FLOW
8"
CA-7 GRANULAR BACKFILL
2' (MIN)
SUMP DEPTH
18" MIN.
@ JOINT
MASTIC SEAL
6
UPSTREAM PIPE DIAMETER (IN)
DOWNSTREAM PIPE DIAMETER (IN)
DOWNSTREAM INVERT ELEV
UPSTREAM INVERT ELEV
8
6'-DIA.
MANHOLE, TYPE A,
6'-DIA.
MANHOLE, TYPE A,
2
ORIFICE
2-YEAR
ORIFICE
2-YEAR
2-YEAR ORIFICE SIZE (IN)
2-YEAR ORIFICE ELEV
5
7
6
12" MIN.
INTO PRECAST WALL BOTH SIDES
@ 9" CENTERS INTO MIN. 3"
†" EXPANSION TIE ANCHORS
TABLE TO BE COMPLETED BY DESIGNER AND INCLUDED IN PLANS FOR EACH PROJECT
MANHOLE STEPS (SEE NOTE 3)
8"6" MIN.
ORIFICE
100-YEAR
6ORIFICE
100-YEAR
7
8STRUCTURE RIM ELEV
100-YEAR ORIFICE SIZE (IN)
TOP OF WEIR ELEV
100-YEAR ORIFICE ELEV
TOP OF WEIR
7 TOP OF WEIR
(SEE STM-6)
C.I. FRAMES AND LIDS
RS#2RS#1 RS#3 RS#4
4. EXTERIOR JOINTS SHALL BE WRAPPED WITH MACWRAP OR APPROVED EQUAL
AT 16" ON CENTER
3. COATED CAST IRON MANHOLE STEPS SHALL BE PROVIDED IN EACH CHAMBER
STRUCTURE WALLS/BASE AND WEIR WALL CONFORMING TO ASTM C-923
2. WATERTIGHT CONNECTIONS REQUIRED BETWEEN STRUCTURE AND PIPE AND
1. RESTRICTOR ORIFICES SHALL BE CAST INTO THE CONCRETE WEIR WALL
NOTES:
DATE: MARCH 2017
RESTRICTOR STRUCTURE
DETENTION POND
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
NO SCALE
IDOT CA-7
UNDER OR
WITHIN 5 FEET
HORIZONTALLY OF
PAVEMENT,
SIDEWALK, CURB
& GUTTER OR
DRIVEWAYS, OR
WHERE INDICATED
ON PLANS
IDOT CA-7
BEDDING,
HAUNCHING AND
INITIAL BACKFILL
EXCAVATED MATERIALS,
COMPACTED TO 85%
MODIFIED PROCTOR
MAXIMUM DENSITY,
EXCEPT WHERE CA-7
IS REQUIRED
4"
12
"
...\san-1 (sanitary sewer installation).dgn
SAN-1
6’
MIN
. C
OV
ER
PIPE MATERIAL SHALL BE IN
ACCORDANCE WITH CHART
PROVIDED BELOW.
6’ UP TO 15’
DEPTHDIA.
4" - 12"
PVC, SDR 26
ASTM 2241
PVC, SDR 26
ASTM 224114" - 24"
24" - 36"
PVC, DR 25
AWWA C905
PVC, DR 25
AWWA C905
PVC, DR 18
AWWA C905
PVC, DR 18
AWWA C900
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
SANITARY SEWER
INSTALLATION
DATE: JUNE 2007
NOTES:
1. JOINTS FOR GRAVITY SANITARY SEWER SHALL USE PUSH ON BELL AND SPIGOT TYPE WITH RUBBER RING
GASKETS CONFORMING TO ASTM D3034 FOR SDR 26 APPLICATIONS AND ASTM D3034 FOR AWWA C900
AND C905 APPLICATIONS.
2. GRAVITY SANITARY SEWER FITTINGS SHALL COMPLY WITH ASTM D2241 SDR26, AWWA C900 DR 18, OR AWWA
DR 25 DEPENDANT UPON DEPTH. THE FITTINGS SHALL BE MADE WITH MANUFACTURER’S STANDARD PIPE BELLS
AND GASKETS. GRAVITY SEWER RISERS AND SERVICE PIPE AND FITTINGS SHALL COMPLY WITH ASTM D2241
SDR 26, AWWA C900, OR AWWA C905 DEPENDANT UPON DEPTH..
3. WHERE INDICATED ON THE PLANS, SANITARY SEWER PRESSURE PIPE SHALL COMPLY WITH ASTM D2241 FOR
160 PSI PRESSURE RATED PIPE SDR 26, MADE OF TYPE 1, GRADE 1 POLYVINYL CHLORIDE CONFORMING TO
ASTM D1784. JOINTS SHALL USE PUSH-ON BELL AND SPIGOT TYPE WITH RUBBER RING SEAL GASKETS
CONFORMING TO ASTM D3139.
4. PRESSURE SANITARY SEWER FITTINGS SHALL BE FACTORY FABRICATED WITH ATTACHED MAIN LINE COUPLING,
WITH SAME RATING AS PIPE. PRESSURE SEWER RISERS AND SERVICE PIPE AND FITTINGS SHALL COMPLY WITH
ASTM D2241, 160 PSI PRESSURE RATED, SDR 26 PIPE. SEPARATE NOTIFICATION SHALL BE PROVIDED TO
PUBLIC WORKS DEPARTMENT PRIOR TO INSTALLING PRESSURE SANITARY SEWERS.
5. ALL SANITARY SEWERS SHALL BE PRESSURE TESTED IN ACCORDANCE WITH ARTICLE 31-1.11B(3) OF THE
STANDARD SPECIFICATIONS FOR SEWER & WATER CONSTRUCTION IN ILLINOIS, FIFTH EDITION; AND DEFLECTION
TESTED IN ACCORDANCE WITH ARTICLE 31-1.11B(4) OF THE STANDARD SPECIFICATIONS FOR SEWER & WATER
CONSTRUCTION IN ILLINOIS, FIFTH EDITION. DEFLECTION TESTING SHALL BE DONE NO SOONER THAN 30 DAYS
AFTER THE PIPE HAS BEEN BACKFILLED. NO SOONER THAN 30 DAYS AFTER SEWERS HAVE BEEN INSTALLED,
THEY SHALL BE INSPECTED BY CLOSED CIRCUIT COLOR TELEVISION TO DETERMINE IF ANY PIPE INSTALLATION
DEFECTS HAVE OCCURRED, AND TO DETERMINE THE LOCATION OF SERVICES. ONE COPY OF THE VIDEOTAPE
AND WRITTEN INSPECTION REPORT SHALL BE FURNISHED TO THE VILLAGE.
6. SEWER PLUGS SHALL BE INSTALLED AT DOWNSTREAM ENDS OF ALL
NEW SEWERS AND LEFT IN PLACE UNTIL VILLAGE ACCEPTS SEWERS.
SEWER PLUGS SHALL BE INSTALLED AT UPSTREAM ENDS OF NEW
SEWERS AT THE END OF EACH DAY’S WORK.
15’ AND DEEPER
Ecc. Cone Sec.(L)
Wall Thickness
Inside M.H. Dia.
Pipe Dia.
PLAN
2’-6"
5"
21"
48"
6"
3’-9"
60"
A A
SECTION A-A
<_ 21">
MANHOLE DEPTH
t
12’ 12’
8" 10"
_< >
DE
PT
H
VA
RIA
BL
E
PR
EC
AS
T R
EIN
FO
RC
ED
CO
NC
. S
EC
TIO
NS
1/2 PIPE DIA.
L
t
24" DIA.
ST
EP
S
O.C
. M
AX
.
PRECAST REINFORCED CONCRETEMANHOLE BOTTOM WITH INTEGRAL SIDEWALL
ALL SANITARY MANHOLE INVERTS
PROVIDE CONCRETE FILLET FOR
2% SLOPE (TYP.)
POURED CONCRETE FILLET
RUBBER BOOT
ECCENTRIC CONE SECTION
IN PAVED AREAS, USE CA-6
GRANULAR TRENCH BACKFILL
AROUND MANHOLE TO
SUBGRADE ELEVATION
CONC. ADJUSTING RINGS
(2 RINGS MAX. NO MORE THAN
RING SHALL BE USED)
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
SANITARY SEWER MANHOLE
DATE: JUNE 2007...\SAN-2 (Sanitary Sewer Manhole).dgn
SAN-2
12" MAX. PRECAST
8"
16"
ONE 2" ADJUSTING
CA-7 AGGREGATE
6"
TOP OF CASTING
SEE SAN-3
NOTE:
1. SANITARY MANHOLES SHALL HAVE WATERSTOP GASKETS CAST
TO STRUCTURES AT ALL PIPE PENETRATIONS. (SEE MANHOLE PIPE CONNECTION DETAIL)
2. SANITARY MANHOLES SHALL HAVE CRETEX INTERNAL CHIMNEY
ALS AND PARSONS RAINSTOPPER INSERTS.
3. SANITARY MANHOLES SHALL HAVE INTEGRAL BASES.
4. MACWRAP EXTERNAL JOINT SEALING BANDS IN ACCORDANCE
TH ASTM C-877, OR APPROVED EQUIVALENT, MUST BE PROVIDED AT
NITARY MANHOLE JOINTS.
5. INTERIOR JOINTS SHALL BE "BUTTERED" WITH NON-SHRINK GROUT.
6. STORM MANHOLES SHALL HAVE A WALL THICKNESS OF 6" FOR 5’
AMETER STRUCTURES AND 7" FOR 6’ DIAMETER STRUCTURES
7. SANITARY MANHOLES SHALL PASS VACUUM-TESTING PER ASTM C-1244.
8. SEE CASTING INSTALLATION AND ADJUSTING DETAIL FOR CASTING REQUIREMENTS.
DD
CAST CLOSED LID
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
SANITARY MANHOLE
FRAME & COVER
DATE: JUNE 2007
(SEAL TITE CONCEALED PICK HOLE)
1) DUCTILE IRON SHALL BE GRADE 60-40-18 AND SHALL BE TESTED IN
ACCORDANCE WITH FEDERAL SPECIFICATIONS.
2) ALL FRAMES AND COVERS SHALL HAVE MACHINED HORIZONTAL AND
VERTICAL BEARING SURFACES. PICK HOLES SHALL NOT CREATE
OPENINGS IN THE COVER.
3) THE MANHOLE COVERS SHALL HAVE RAISED LETTERS AS SHOWN.
4) MINIMUM WEIGHTS FOR CASTINGS AS SHOWN.
5) DIMENSIONS FOR CASTINGS ARE COMPARABLE TO EAST JORDAN 1022-3
OR NEENAH R-1772-CVH.
6) WATERPROOF, BOLTDOWN FRAME AND COVER SHALL BE USED
AS NOTED ON THE PLANS. NEENAH R-1916-F1
OR EAST JORDAN IRON WORKS 1040-ZPT (OR APPROVED EQUAL).
SEAL TITE LID
SEAL TITE CONCEALED PICK HOLE2-1/4"
2-1/2"
5/8" MIN. FOR D.I.
3/4" MIN. FOR C.I.
1-3/8"
1-3/8"
SAN-3
...\SAN-3 (Sanitary Sewer Manhole Frame & Cover).dgn
"VILLAGE OF SHOREWOOD"
SANITARY STAMPED IN LID
2" RAISED LETTERS
SANITARY
VILLAGE
OF
SHOREWOOD
WHEN PLACING FIELD-POURED
INVERT CHANNELS, PACK ANNULAR
SPACES WITH EXTRUDIBLE
PREFORMED PLASTIC GASKET
MATERIAL TO PREVENT INVERT
CONCRETE FROM ENTERING SPACE
BETWEEN PIPE AND FLEXIBLE
BOOT
FLEXIBLE BOOTS MEETING ASTM
C923 CLAMP-ON TYPE
(CAST-IN BOOT SHOWN;
PRESSED-IN BOOT ALSO
PERMITTED)
INVERT CHANNEL
CONCRETE
INSTALL PIPE IN
ACCORDANCE WITH
BOOT MFR’S INST.
OR
CLAMP SECURELY IN ACCORDANCE
WITH BOOT MFR’S INSTRUCTIONS.
USE A MINIMUM OF 2 STAINLESS
STEEL CLAMPS.
FLEXIBLE BOOTS
MEETING ASTM
C923 "A-LOCK"
TYPE
...\san-4 (sanitary pipe connection).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
SANITARY MANHOLE PIPE
CONNECTION
DATE: JUNE 2007
SAN-4
FLOW
ALL PIPING SHOWN
SHALL BE DUCTILE
IRON CLASS 52 M.J.
PIPE AND MEGALUG
FITTINGSNO SCALE
FOR INCOMING PIPE
SMALLER THAN 12", USE
VERTICAL PIPE OF SAME
DIAMETER. FOR INCOMING
PIPE 12" TO 18" USE 12"
VERTICAL PIPE. SEE PLANS
FOR PIPES LARGER THAN
18".
8" MIN. CLASS SI
CONC. ENCASEMENT
TO TOP OF BEND
...\san-5 (drop connection).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
DROP CONNECTION
DATE: JUNE 2007
SAN-5
SAN-6
...\SAN-6 (Non-Residential Sewer Service).dgn
ROW
~ PUBLIC ROADWAY
EOP PUBLIC ROADWAY
NEW SEWER MANHOLE
FOR SERVICE CONNECTOR
SEWER SERVICE
NEW SEWER
MANHOLE
PRIVATE DEVELOPMENT
(MULTI-TENANT)
CLEANOUT (TYP.)
EXISTING SEWER
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
NON-RESIDENTIAL
SEWER SERVICE
DATE: JUNE 2007
WYE BRANCH
WYE BRANCH
6" PVC
PROPERTY LINE
30° OR 45° ELBOW
6" SERVICE RISER
1% MIN SLOPE
4"X4" WOOD
MARKER POST,
PAINTED GREEN,
3’-0" ABOVE
FINISHED GRADE,
TO 2’-0" BELOW
FINISHED GRADE
MANUFACTURER’S
PLUG
NOTES:
1. IF f < 45° USE PVC PUSH-ON JOINT WYE, P.V.C. ELBOW, P.V.C.
RISER PIPE & P.V.C. TOP ELBOW.
2. IF f > 45° USE DUCTILE IRON M.J. TEE WITH P.V.C./DUCTILE
TRANSITION GASKET, DUCTILE IRON RISER PIPE AND DUCTILE IRON
TOP ELBOW.
3. ALL PVC PIPE AND FITTINGS SHALL BE ASTM D3034, SDR 26,
WITH ELASTOMERIC GASKET TYPE JOINTS COMPLYING WITH ASTM F477
AND ASTM D3212, OR PRESSURE-RATED PIPE AND FITTINGS PER
ASTM D2241 AS NOTED ON THE PLANS.
4. A MINIMUM DISTANCE OF 3 FT IS REQUIRED BETWEEN 45° BENDS.
5. TRENCH BACKFILL SHALL BE INSTALLED PER SANITARY SEWER
INSTALLATION DETAIL.
2’-0"
10% MAX SLOPE
f VARIES
...\san-7 (residential sewer service).dgn
SAN-7
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
RESIDENTIAL SEWER SERVICE
DATE: JUNE 2007
NO SCALE
NOTES:
2. MAINS SHALL BE PRESSURE TESTED AT A MINIMUM
PRESSURE OF 150 PSI FOR TWO HOUR WITHOUT PRESSURE
LOSS OR FURTHER PRESSURE APPLICATION. TEST SHALL
BE PERFORMED IN ACCORDANCE WITH AWWA C600 AND
AWWA C603. IF MAINS TO BE TESTED INCLUDE CONCRETE
THRUST BLOCKING, DO NOT BEGIN TEST UNTIL AT LEAST 5
DAYS AFTER THE INSTALLATION OF THE THRUST BLOCKING.
3. AFTER COMPLETING A SATISFACTORY PRESSURE TEST,
SEWER MAIN CONSTRUCTION IN ILLINOIS, LATEST EDITION. ...\wtr-1 (watermain installation).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
WATER MAIN INSTALLATION
DATE: JUNE 2007
WTR-1
IDOT CA-7 UNDER
OR WITHIN 5 FEET
HORIZONTALLY OF
PAVEMENT,
SIDEWALK, CURB
& GUTTER OR
DRIVEWAYS, OR
WHERE INDICATED
ON PLANS
IDOT CA-7
BEDDING,
HAUNCHING AND
INITIAL BACKFILL
EXCAVATED MATERIALS,
COMPACTED TO 85%
MODIFIED PROCTOR
MAXIMUM DENSITY,
EXCEPT WHERE CA-7 IS
REQUIRED
DUCTILE IRON WATER MAIN
PER AWWA C151, THICKNESS
CLASS 52 PER AWWA C150,
WITH PUSH-ON JOINTS PER
AWWA C111 WITH SYNTHETIC
RUBBER GASKETS, CEMENT
LINING PER AWWA C104, AND
FITTINGS PER AWWA C110
OR AWWA C153
1. PRESSURE AND LEAKAGE TESTS AND CHLORINATION
SHALL BE COORDINATED WITH VILLAGE UTILITY FOREMAN.
6"
4"
5’-6" M
IN
. C
OV
ER
THE WATER MAIN SHALL BE LEAKAGE TESTED FOR 24 HOURS
AT SYSTEM PRESSURE, IN ACCORDANCE WITH
THE STANDARD SPECIFICATIONS FOR WATER &
UNDISTURBED EARTH
UNDISTURBED EARTH
UNDISTURBED EARTH
UNDISTURBED EARTH
TRENCH WALL (TYP.)
TRENCH WALL (TYP.)
TRENCH WALL (TYP.)
PLANS
SECTION
NO SCALE
NOTES
1. PROVIDE PRECAST OR CAST-IN-PLACE
IDOT CLASS SI CONCRETE THRUST BLOCKS
OF ADEQUATE SIZE AND THRUST
BEARING SURFACE TO PREVENT MOVEMENT
OF PIPELINE UNDER PRESSURE.
3. PLACE THRUST BLOCKING SO THE FITTING
JOINTS WILL BE ACCESSIBLE FOR REPAIR.
2. PLACE THE BASE AND THRUST BEARING
SIDES OF THRUST BLOCK DIRECTLY AGAINST
UNDISTURBED EARTH.
4. ALL FITTINGS SHALL HAVE MECHANICAL JOINTS
WITH MEGA-LUG RETAINER GLANDS BY EBAAIRON, AND DURATRON SAC-NUTS ON 50%
OF ALL BOLTS.
...\WTR\wtr-2 (thrust block).dgn
WTR-2
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
THRUST BLOCK
INSTALLATIONS
DATE: JUNE 2007
1) VALVE MUST ALIGN WITH THE CENTER OF VAULT OPENINGS.
3) BUTTERFLY VALVES AND PRESSURE TAP VALVES REQUIRE ECCENTRIC CONES.
4) WHEN ADJUSTMENTS ARE NECESSARY, THEY SHALL BE PERFORMED WITH A MAXIMUM OF
TWO (2) PRECAST CONCRETE RINGS SET IN A BED OF PREFORMED NON-HARDENING
PRECAST CONC.
BLOCK SUPPORT
INTEGRAL BOTTOM
SOLID PRECAST
RUBBER BOOT (TYP.)
2’-8"
MASTIC
PREFORMED NON-HARDENING
FINISHED GRADE
TOP OF CASTING
...\WTR\WTR-3 (Valve Vault).dgn
WTR-3
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
VALVE VAULT
DATE: JUNE 2007
2’
4’
8"
6"
6" 6"
PRECAST CONCRETE MANHOLESECTIONS - ASTM C478
EXTRUDIBLEPREFORMEDPLASTIC GASKET
(TYPICAL ALL
SECTION JOINT)
5’-6
" M
IN
.
CA-7
SEE WTR-5
2) CONES MUST BE CONCENTRIC WITH VALVES 12" AND SMALLER.
MASTIC MATERIAL( CONSEAL CS-102B, OR APPROVED EQUAL) TO A MAXIMUM HEIGHT OF 12".
WATEROUS C-515AFC2500 DUCTILE IRONGATE VALVE WITH STAINLESS STEEL HARDWARE FOR VALVES
UP TO AND INCLUDING 12"
AWWA *C504 (PRESSURE
CLASS 150B) BUTTERFLY
VALVE FOR 16" AND LARGER
6) DURATION SAC-NUTS SHALL BE USED ON 50% OF ALL BOLTS.
7) ALL HARDWARE SHALL BE STAINLESS STEEL.
8) USE 4’-0" DIAMETER FOR WATER MAIN SIZES 8" OR LESS,
USE 5’-0" DIAMETER FOR WATER MAIN SIZES 10" THRU 20",
USE 6’-0" DIAMETER FOR WATER MAIN SIZES GREATER THAN 20".
BUTTERFLY VALVES SHALL:
9) HAVE A CAST IRON BODY, AND BE RUBBER-SEATED, TIGHT-CLOSING TYPE
SUITABLE FOR BURIED SERVICE.
10) HAVE ANSI CLASS 125 STANDARD FLANGE OR VICTAULIC COUPLING ENDS.
11) HAVE VALVE SHAFT OF EITHER 18-8 OR TYPE 304 STAINLESS STEEL,
EXTENDED THROUGH VALVE DISC AND BODY INTO OPERATOR.
12) HAVE A FULLY ENCLOSED, SEALED, GREASE-PACKED INTEGRAL GEARED
MANUAL OPERATOR WITH A 2-INCH SQUARE OPERATING NUT.
5) MANHOLE STEPS SHALL BE AT 16" O.C. COPOLYMER POLYPROPYLENE PLASTIC WITH
CONTINUOUS 12" STEEL REINFORCEMENT BY M.A. INDUSTRIES, INC. OR APPROVED EQUAL.
SEE CASTING
ADJUSTMENT DETAIL
FRAME AND COVER:
EJIW 1050 EX HD , OR
PRECAST CONC.
ADJUSTING RINGS
FOR WATER MAIN SIZES 8" OR LESS,
FOR WATER MAIN SIZES 10" THRU 20",
FOR WATER MAIN SIZES GREATER THAN 20".
NEENAH R-1712
(NO MORE THAN 2 RINGS
OR 12" OF ADJUSTMENT)
PRECAST CONCRETE
ASTM C478
USE 6’-0" DIAMETER
CONC. BOTTOM
6" MIN. CAST-IN-PLACE
PRECAST CONC. OR
MIN.
THRUST BLOCK
CONCRETE
MAIN
EXIST. WATER
MIN
.
GRANULAR BEDDING MATERIAL: CA-7
CONCRETE SUPPORT
FINISHED GRADE
WATER MAIN
NOTES:
1. ECCENTRIC CONE REQUIRED
2. USE 4’-0" DIAMETER
USE 5’-0" DIAMETER
NO SCALE
3. TAPPING OF WATER MAINS SHALL BE DONE ONLY IN THE
PRESENCE OF AN AUTHORIZED VILLAGE REPRESENTATIVE,
AND AFTER 48 HOURS PRIOR NOTICE TO THE VILLAGE.
EXTRUDIBLE PREFORMED
PLASTIC GASKET
(TYPICAL ALL
SECTION JOINTS)
WATEROUS C-515 AFC
2500, DUCTILE
IRON, WITH STAINLESS
STEEL HARDWARE
EXTRUDIBLE PREFORMED
PLASTIC GASKET
RUBBER BOOT
MANHOLE STEPS @ 16"
C. TO C. COPOLYMER
POLYPROPYLENE PLASTIC
W/ CONTINUOUS 1/2"
STEEL REINFORCEMENT
BY M.A. INDUSTRIES,
INC., OR APPROVED
EQUAL
STAINLESS STEEL
TAPPING SLEEVE:
SMITH-BLAIR STYLE
NO. 662
4. DURATION SAC-NUTS SHALL BE USED ON 50% OF
ALL BOLTS.
6"
4"
8"
5’-6
" M
IN
. C
OV
ER
TOP OF CASTING AND LID
SEE WTR-5
...\wtr-4 (pressure connection valve vault).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
PRESSURE CONNECTION
VALVE VAULT
DATE: JUNE 2007
WTR-4
MANHOLE SECTIONS:
WATER
DD
CAST CLOSED LID
1) DUCTILE IRON SHALL BE GRADE 60-40-18 AND SHALL BE TESTED IN
ACCORDANCE WITH FEDERAL SPECIFICATIONS.
2) ALL FRAMES AND COVERS SHALL HAVE MACHINED HORIZONTAL AND
VERTICAL BEARING SURFACES. PICK HOLES SHALL NOT CREATE
OPENINGS IN THE COVER.
3) THE MANHOLE COVERS SHALL HAVE RAISED LETTERS AS SHOWN.
4) DIMENSIONS FOR CASTINGS ARE COMPARABLE TO EAST JORDAN 1022-3
5) LIDS AND FRAMES TO MEET AASHTO H-20 LOADING SPECIFICATIONS.
6) ALL CASTINGS SHALL BE SHOP PAINTED WITH ASPHALTIC BASE PAINT.
OR NEENAH R-1772-C.
SEAL TITE LID
SEAL TITE CONCEALED PICK HOLE
2-1/2
" M
IN
.
2-1/2"
2-1/4"
1-3/4"
3/4
" M
in.
5/8" 5/8"
(SEAL TITE CONCEALED PICK HOLE)
5/8" MIN. FOR D.I.
3/4" MIN. FOR C.I.
1-3/8"
1-3/8"
6" DIA.
22-3/4"
2" RAISED LETTERS
"VILLAGE OF SHOREWOOD"
...\WTR-5 (Valve Vault Frame & Cover).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
VALVE VAULT
FRAME & COVER
DATE: JUNE 2007
WTR-5
VILLAGE
OF
SHOREWOOD
TYLER "SWIVEL-TEE"
NO SCALE
1 C.Y. (MIN)
BREAK FLANGE
CONCRETE
MECHANICAL JOINT WITH FIELD-LOK
MARKED "WATER"
CAST IRON COVER
18" (MIN.)
26" (MAX.)
CA-7
COVER W/ PLASTIC
5'-6" COVER
VALVE BOX
STABILIZER
OR CLOW MEDALLION
MUELLER
10360
6" AUXILIARY GATE
VALVE: AWWA C-509
BLOCKS
CONCRETE THRUST
BLOCKING
GASKET AND MEGA LUG RESTRAINT
SAFETY RED.
4. HYDRANT SHALL BE PAINTED ACE BRAND RUST STOP
HYDRANT DRAIN HOLE IS NOT OBSTRUCTED.
3. THRUST BLOCKING SHALL BE CONSTRUCTED SO
AND BONNET SHALL BE STAINLESS STEEL.
2. ALL BOLTS & NUTS ON AUXILIARY VALVE SEAL PLATE
SHALL BE STAINLESS STEEL.
1. ALL BOLTS & NUTS BELOW GRADE ON FIRE HYDRANT
NOTES:
$FILEABBREV$
WTR-6
(FLANGED JOINT NOT PERMITTED)
MECHANICAL JOINT
DATE: SEPTEMBER 2014
FIRE HYDRANT
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
5CD250EAST JORDAN
MIN.
NO SCALE
SECTION
PLAN
WATER MAIN
HORIZONTAL OFFSET
FIN. GRADE
PR
OP
ER
TY
LIN
E
CURB STOP:
SERVICE PIPE: ASTM B88,
(ONE PIECE OF PIPE - NO SPLICES)
VARIABLE
SERVICE BOX:
MUELLER, P-25155
MUELLER H-10300
TYPE K,
COMPRESSION
FITTINGS
WATER MAIN
CORPORATION STOP:
MUELLER, H-15013
PRECAST CONCRETE BLOCK45°
WATER MAIN INSTALLATION DETAIL.
1. TRENCH BACKFILL SHALL BE INSTALLED PER
NOTES:
2. PLACE AND HAND-TAMP AT LEAST 1/4 CUBIC
YARDS OF SAND AROUND CORPORATION STOP.
SHALL BE 18 INCHES.
3. MINIMUM DISTANCE BETWEEN SERVICE TAPS
WITH STATIONARY
EXTENSION ROD
6"
5'-
0"
MIN.
45°
10"
22"
10"
$FILEABBREV$
WTR-7
7. SEE DETAIL MSC-3 FOR SERVICE LATERAL LOCATIONS.
CLOSED AT THE CORP STOP AND RE-TAPPED.6. ALL SERVICES TO BE ABANDONED OR RELOCATED SHALL BE
5. SERVICES SHALL NOT BE LOCATED WITHIN DRIVEWAYS.
1'
DATE: MARCH 2017
RESIDENTIAL WATER SERVICE
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
4. MINIMUM RESIDENTIAL SERVICE DIAMETER SHALL BE 1".
LOCK PIN
REMOVABLE LOCKABLE UPPER
HOUSING (MOLDED)
BOTTOM MOLDED
HOUSING
BRASS ELBOW
COPPER TUBING
PVC NIPPLE
VALVE STEM
WELDED STOP LOCKS
PVC NIPPLE
FLARED CORPORATION
ASTM 88, TYPE K,
FLARED FITTINGS
(ONE PIECE OF PIPE)
3/4" SERVICE PIPE:
FLARED CURB STOP WITH
45°
FORD OR McDONALD
VALVE: MUELLER,
STOP WITH PLUG
SERVICE BOX:
VARIABLE
STEEL ANCHOR POST
16" M
INIM
UM
22
" M
AX
IMU
M
FINISHED GRADE
...\WTR-8 (Water Sampling Station).dgn
WTR-8
RETAINING WASHER
STAINLESS STEEL ANCHOR
BOLTS AND NUTS
BRONZE BALL VALVE
W/ CHROME PLATED BALL
BRASS PET COCK
PUMP CONNECTOR
(COPPER TUBING)
BRASS WATER NOZZLE
(NON-THREADED)
OPERATING HANDLE (OFF-ON)
PRECAST CONCRETE BLOCK
WATER MAIN
1) SAMPLING STATION SHALL BE GIL INDUSTRIES
MODEL EH101-50 OR APPROVED EQUAL.
2) LOCATION OF SAMPLING STATION SHALL BE
DETERMINED DURING FINAL ENGINEERING OF THE
PROPOSED DEVELOPMENT.
3) CONTRACTOR SHALL HAVE SAMPLING STATION
STAKED FOR LOCATION AND ELEVATION AND APPROVED
BY THE VILLAGE PRIOR TO INSTALLATION.
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
WATER SAMPLING STATION
DATE: JUNE 2007
MUELLER H-10300, OR
McDONALD 5614
BALL VALVE AND MINNEAPOLIS PATTERN:
MUELLER OR McDONALD
HANDHOLE
POSITION
TRAFFIC
FLOW
POLE SHAFT
90%%d
DECORATIVE
ARM
STANDARD DETAIL
FOR
ELE-1
VILLAGE OF SHOREWOOD3. UPON FINAL ACCEPTANCE OF PUBLIC LIGHTING
IMPROVEMENTS BY THE VILLAGE,
DEVELOPER/CONTRACTOR SHALL PROVIDE
A NON-REFUNDABLE CASH DEPOSIT
EQUIVALENT TO 10% OF THE TOTAL
CONSTRUCTION COST OF THE LIGHT POLE
STANDARDS AND FIXTURES FOR FUTURE
VILLAGE LIGHTING MAINTENANCE PURPOSES.
NOTE:
2. DIRECT CONNECTED LIGHT POLES SHALL BE
PROVIDED WITH 120V BUTTON-TYPE
PHOTOELECTRIC CELL.
1. LIGHT POLE ASSEMBLY SHALL BE SUN VALLEY
DETAIL NO. CS-4092 REV. 9, OR APPROVED EQUAL.
ORNAMENTAL TYPE
LIGHT POLE
SHEET 1 OF 2
DATE: MARCH 20094. SEE SHEET 2 OF 2 FOR SPECIFICATIONS.
TWIN ASSEMBLY
BOLT
15" DIA.
CIRCLE
ABOVE GRADE
ANCHOR RING 1"NOM.
20"
NOM.
32"
SLEEVE
PROVIDED
ANCHOR RING 1"
ABOVE GRADE
20"NOM.
32"NOM.
48"
36"
30"
33"
18’-0"
16’-0"
INTERNAL
HAND
HOLE
18’-0"
SINGLE ASSEMBLY
N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-1 (Ornamental Light Pole).dgn
OPTICS: SEGMENTED REFLECTOR AND CLEAR ACRYLIC DIFFUSER.
TWIN ASSEMBLY-TYPE III (ASYMMETRIC) LIGHT DISTRIBUTION.
SINGLE ASSEMBLY-TYPE III (ASYMMETRIC) LIGHT DISTRIBUTION.
LAMP HOLDER: MOGUL BASE, PORCELAIN.
BALLAST: H.P.F./C.W.A. AUTOTRANSFORMER,-20^ STARTING TEMPERATURE.
(MULTI-TAP VOLTAGE, WIRED FOR 120V.)
ARM: DURABLE CORROSION RESISTANT, CAST, AND EXTRUDED
ALUMINUM CONSTRUCTION.
BASE: ONE PIECE CORROSION RESISTANT, DURABLE CAST ALUMINUM
CONSTRUCTION. MINIMUM .210 WALL THICKNESS, BASE CONSISTS
OF A SMOOTH, TAPERED BOTTOM SECTION, AND A HIGHLY DETAILED,
DECORATIVE FLUTED SECTION, A DECORATIVE CAST ALUMINUM
COLLAR AND FLUTED HAND HOLE COVER CONTOURED TO BASE DESIGN.
HAND HOLE COVER SUPPLIED WITH TAMPER RESISITANT HARDWARE.
GROUNDING LUG PROVIDED INSIDE BASE OPPOSITE HAND HOLE.
ANCHORAGE: (4) 1"X36" FULLY GALVANIZED ANCHOR BOLTS. EACH BOLT
SUPPLIED WITH TWO NUTS AND TWO WASHERS.
LUMINAIRE: HOUSING AND DOOR FRAME-HEAVY WALL CAST
ALUMINUM CONSTRUCTION WITH REMOVABLE BALLAST
TRAY FOR EASY BALLAST ACCESS. REFLECTOR-HEAVY
WALL ALUMINUM CONSTRUCTION.
SPECIFICATIONS:
ELE-1
2. POLE ASSEMBLY RATED FOR 90 M.P.H. SUSTAINED WIND
LOADS PLUS 1.3 WIND GUST.
NOTE: 1. HAND HOLE COVER TO READ "VILLAGE OF SHOREWOOD".
3. OPTIONS:
- SPEAKER BRACKET
- BANNER ARMS (ROTATABLE OR FIXED) SPECIFY.
- FLAG HOLDER (ROTATABLE OR FIXED) SPECIFY.
- GFI
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
ORNAMENTAL TYPE
LIGHT POLE
SHEET 2 OF 2
DATE: MARCH 2009
SHAFT: 16 FLUTES TAPERED ALUMINUM SHAFT (.188 WALL THICK.)
HAS 7" BUTT TAPERING TO 4.5" TOP. SHAFT PROVIDED WITH
INTERNAL REINFORCING SLEEVE FOR GREATER STRUCTURAL
SUPPORT. SLEEVE AND SHAFT WELDED TO BASE.
N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-1 (Ornamental Light Pole).dgn
LAMP: 150 W. H.P.S.- PUBLIC STREET
250 W. H.P.S. - COMMERCIAL APPLICATION
FINISH: ELECTROSTATICALLY APPLIED BAKED ON TEXTURED ACRYLIC
ENAMEL-HIGH GLOSS (COLOR: BLACK).
HANDHOLE
POSITION
TRAFFIC
FLOW
POLE SHAFT
90%%d
DECORATIVE
ARM
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD3. UPON FINAL ACCEPTANCE OF PUBLIC LIGHTING
IMPROVEMENTS BY THE VILLAGE,
DEVELOPER/CONTRACTOR SHALL PROVIDE
A NON-REFUNDABLE CASH DEPOSIT
EQUIVALENT TO 10% OF THE TOTAL
CONSTRUCTION COST OF THE LIGHT POLE
STANDARDS AND FIXTURES FOR FUTURE
VILLAGE LIGHTING MAINTENANCE PURPOSES.
NOTE:
2. DIRECT CONNECTED LIGHT POLES SHALL BE
PROVIDED WITH 120V BUTTON-TYPE
PHOTOELECTRIC CELL.
1. LIGHT POLE ASSEMBLY SHALL BE SUN VALLEY
DETAIL NO. CS-5198 REV. 1, OR APPROVED EQUAL.
DATE: MARCH 2009
4. SEE SHEET 2 OF 2 FOR SPECIFICATIONS.
ELE-1A
BOLT CIRCLE
12" DIA.
HAND
HOLE
ABOVE RING 1"ANCHOR
GRADE
NOM.
17"
NOM.
25"
10’-0"
31"
22"
42"
N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-1A (Ped Level Ornamental Light Pole).dgn
26 1/2 "
10’-11 1/2 "
PEDESTRIAN SCALE (10’)
ORNAMENTAL TYPE
LIGHT POLE
SHEET 1 OF 2
LAMP HOLDER: MEDIUM BASE PORCELAIN.
SPECIFICATIONS:
ELE-1A
2. POLE ASSEMBLY RATED FOR 90 M.P.H. SUSTAINED WIND
LOADS PLUS 1.3 WIND GUST.
NOTE: 1. HAND HOLE COVER TO READ "VILLAGE OF SHOREWOOD".
3. OPTIONS:
- SPEAKER BRACKET
- BANNER ARMS (ROTATABLE OR FIXED) SPECIFY.
- FLAG HOLDER (ROTATABLE OR FIXED) SPECIFY.
- GFI
VILLAGE OF SHOREWOOD
ORNAMENTAL TYPE
LIGHT POLE
SHEET 2 OF 2
DATE: MARCH 2009
FIXTURE: HOUSING - HEAVY WALL CAST ALUMINUM CONSTRUCTION.
LUMINAIRE SUPPLIED WITH AN ALUMINUM HOOD, A DECORATIVE
GASKETED HINGED CAGE AND A CAST ALUMINUM FITTER.
OPTICS: PRECISELY DESIGNED UPPER BOROSILICATE PRISMATIC
GLASS REFLECTOR REDIRECTS UPWARD LIGHT DOWNWORD
TOWARD THE PRECISELY DESIGNED PRISM STRUCTURE OF
THE LOWER BOROSILICATE GLASS REFRACTOR TO PROVIDE
A TYPE III (ASYMMETRIC) LIGHT DISTRIBUTION.
BALLAST: H.P.F./C.W.A. AUTOTRANSFORMER,-20^ STARTING TEMPERATURE.
(MULTI-TAP VOLTAGE)
SHAFT: 4" DIA. EXTRUDED FROM 6063 ALLOY ALUMINUM. HEAT TREATED
TO PRODUCE A T6 TEMPER. WALL THICKNESS .188 MINIMUM. DECORATIVE
SHAFT HAS EVENLY SPACED HIGHLY DETAILED RAISED VERTICAL
FLUTES EXTENDING THE ENTIRE LENGTH OF THE SHAFT. SHAFT IS
CIRCUMFERENTIALLY WELDED TO BASE.
BASE: ONE PIECE CORROSION RESISTANT, DURABLE CAST ALUMINUM
CONSTRUCTION. MINIMUM .210 WALL THICKNESS, BASE CONSISTS
OF A SMOOTH, TAPERED BOTTOM SECTION, AND A HIGHLY DETAILED,
DECORATIVE FLUTED SECTION, A DECORATIVE CAST ALUMINUM
COLLAR AND A FLUTED HAND HOLE COVER CONTOURED TO BASE DESIGN.
HAND HOLE COVER SUPPLIED WITH TAMPER RESISITANT HARDWARE.
GROUNDING LUG PROVIDED INSIDE BASE OPPOSITE HAND HOLE.
ANCHORAGE: (4) 3/4 "X18" FULLY GALVANIZED ANCHOR BOLTS. EACH BOLT
SUPPLIED WITH TWO NUTS AND TWO WASHERS.
N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-1A (Ped Level Ornamental Light Pole).dgn
LAMP: 70 W. H.P.S.
STANDARD DETAIL
FOR
PEDESTRIAN SCALE (10’)
FINISH: POLYESTER POWDER COAT - HIGH GLOSS (COLOR: BLACK)
ELE-2
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
3. UPON FINAL ACCEPTANCE OF PUBLIC LIGHTING
IMPROVEMENTS BY THE VILLAGE,
DEVELOPER/CONTRACTOR SHALL PROVIDE
A NON-REFUNDABLE CASH DEPOSIT
EQUIVALENT TO 10% OF THE TOTAL
CONSTRUCTION COST OF THE LIGHT POLE
STANDARDS AND FIXTURES FOR FUTURE
VILLAGE LIGHTING MAINTENANCE PURPOSES.
NOTE:
2. DIRECT CONNECTED LIGHT POLES SHALL BE
PROVIDED WITH 120V BUTTON-TYPE
PHOTOELECTRIC CELL.
4. SEE SHEET 2 OF 2 FOR SPECIFICATIONS. DATE: MARCH 2009
PEDESTRIAN SCALE
SYMMETRICAL
ORNAMENTAL TYPE
LIGHT POLESHEET 1 OF 2
33"
23"
10’-0"
17"NOM.
25"NOM.
ANCHORRING 1"ABOVEGRADE
12" DIA.BOLTCIRCLE
HANDHOLE
1. LIGHT POLE ASSEMBLY SHALL BE SUN VALLEY
DETAIL NO. CS-5201 REV. 1, OR APPROVED EQUAL.
N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-2 (Ped Symmetrical Ornamental Light Pole).dgn
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
DATE: MARCH 2009
PEDESTRIAN SCALE
SYMMETRICAL
ORNAMENTAL TYPE
LIGHT POLE
SHEET 2 OF 2
ELE-2
LAMP HOLDER: MEDIUM BASE, PORCELAIN.
BALLAST: H.P.F./C.W.A. AUTOTRANSFORMER,-20^ STARTING TEMPERATURE.
(MULTI-TAP VOLTAGE, SPECIFY VOLTAGE)
BASE: ONE PIECE CORROSION RESISTANT, DURABLE CAST ALUMINUM
CONSTRUCTION. MINIMUM .210 WALL THICKNESS. BASE CONSISTS
OF A SMOOTH, TAPERED BOTTOM SECTION, AND A HIGHLY DETAILED,
DECORATIVE FLUTED SECTION, A DECORATIVE CAST ALUMINUM
COLLAR AND FLUTED HAND HOLE COVER CONTOURED TO BASE DESIGN.
HAND HOLE COVER SUPPLIED WITH TAMPER RESISITANT HARDWARE.
GROUNDING LUG PROVIDED INSIDE BASE OPPOSITE HAND HOLE.
SPECIFICATIONS:
2. POLE ASSEMBLY RATED FOR 90 M.P.H. SUSTAINED WIND
LOADS PLUS 1.3 WIND GUST.
NOTE: 1. HAND HOLE COVER TO READ "VILLAGE OF SHOREWOOD".
3. OPTIONS:
- SPEAKER BRACKET
- BANNER ARMS (ROTATABLE OR FIXED) SPECIFY.
- FLAG HOLDER (ROTATABLE OR FIXED) SPECIFY.
- GFI
SHAFT: 16 FLUTES TAPERED ALUMINUM SHAFT (.188 WALL THICK.)
HAS 6" BUTT TAPERING TO 4.6" TOP. SHAFT PROVIDED WITH
INTERNAL REINFORCING SLEEVE FOR GREATER STRUCTURAL
SUPPORT. SLEEVE AND SHAFT WELDED TO BASE.
LUMINAIRE: DURABLE CORROSION RESISTANT CAST ALUMINUM. HOUSING
TOP HINGES FOR EASY RE-LAMPING. LUMINAIRE SUPPLIED WITH
CLEAR ACRYLIC DIFFUSER.
OPTICS: SEGMENTED HORIZONTAL REFLECTOR COMBINES WITH CLEAR
ACRYLIC DIFFUSER TO PRODUCE TYPE III (ASYMMETRIC) LIGHT
DISTRIBUTION.
ANCHORAGE: (4) 3/4 "X24" FULLY GALVANIZED ANCHOR BOLTS. EACH BOLT
SUPPLIED WITH TWO NUTS AND TWO WASHERS.
N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-2 (Ped Symmetrical Ornamental Light Pole).dgn
LAMP: 70 W. H.P.S.
FINISH: POLYESTER POWDER COAT - HIGH GLOSS (COLOR: BLACK)
1
2
3
4
5
6
7
PHASE CONDUCTOR
GROUND CONDUCTOR
8
NEUTRAL CONDUCTOR
9
TO 240 VOLT
ROADWAY
LUMINAIRE
(NOTE 2)
1 CONNECTOR KIT METHOD
WITH 6A FUSES INSIDE A
TWO POLE FUSE HOLDER
AND INSULATING BOOTS
2 NO. 10 A.W.G. THWN WIRE
3 MULTIPLE COMPRESSION
FITTINGS (SPLICE)
4 CONCRETE FOUNDATION
5 WIRE AS SHOWN ON PLANS
6 UNIT DUCT IN PVC RACEWAY
7 POLE GROUND LUG
8 #6 GROUND WIRE MECHANICALLY
CLAMPED TO GROUND ROD
9 5/8 " DIA.x10’ GROUND ROD
NOTES:
1. TWIN HEADED LIGHT POLES HAVE SEPARATE FUSING & CIRCUIT
FOR SECOND FIXTURE.
2. DIRECT CONNECTED LIGHT POLES HAVE 120 VOLT LUMINAIRES.
ELE-5
DATE: JULY 2007
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
LIGHT POLE HANDHOLE
WIRING DIAGRAM
COMMISSION TYPE COPPER
SLEEVE (SIZED FOR ACTUAL
NUMBER OF CABLES AND MFG.
SUGGESTED CRIMP TOOL USED)
SEALANT TAPE OR INSERT
(AROUND AND THROUGH
CROTCH SPACE)
EXPOSED SEALANT
TRIMMED CABLES
HEAT-SHRINKABLE CAP WITH
FACTORY APPLIED
WATERPROOF SEALANT,
(SIZED TO ACCOMMODATE
NUMBER OF CABLES)
ELECTRIC CABLES IN
CONDUIT (SIZE &
NUMBER AS NOTED ON
CONTRACT DRAWINGS)
#10 AWG ELECTRIC CABLE
TO LUMINAIRE
ELE-6
DATE: JULY 2007
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
SPLICING ELECTRIC CABLES
TRENCH BACKFILL
RED WARNING TAPE
6" WIDE
~ OF TRENCH
30" M
INIM
UM
12" MAXIMUM WIDTH
EXCEPT AS APPROVED
BY THE VILLAGE
TRENCH CROSS SECTION
R.O.W. R.O.W.
STREET CROSSING
1 CONDUIT SHALL BE HEAVY WALL RGS CONDUIT.
2 CONDUIT SHALL EXTEND A MINIMUM OF 2 FT. BEYOND BACK OF CURB.
3 CONDUIT SHALL BE A MINIMUM OF 30" BELOW CURB BOTTOM.
VARIABLE
MIN
30"
RGS CONDUIT
MIN. 2’ MIN. 2’
CONDUIT/DUCT SIZES
AS SHOWN ON PLANS
ELE-7
DATE: JULY 2007
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
CONDUIT INSTALLATION
PHASE CONDUCTOR
GROUND CONDUCTOR
NEUTRAL CONDUCTOR
58
"
13"
12"
60A-120V CIRCUIT
BREAKER, 22K AIC
NEUTRAL/GROUND
BUS
TO STREET
LIGHT
1/C #6, 1/C #6
NEUTRAL &
1/C #6 GROUND
1/C #6 & 1/C #6
NEUTRAL
#8 AWG GROUND
WIRE
NEMA 3R PEDESTAL
ENCLOSURE, MILBANK
MODEL #U4329-0
SEE NOTE 1
NOTE 2
COM ED TRANSFORMER/
PEDESTAL
3/4 "x10’ COPPER
CLAD GROUND ROD
W/ MECHANICAL
CONNECTION
1.
2.
3.
4.
5.
6.
7.
1" SCH 40 HDPE
CONDUIT (NOTE 7)
GENERAL NOTES:
DISCONNECT ENCLOSURE SHALL BE LOCATED A MINIMUM OF 10’ FROM COM ED
TRANSFORMER/PEDESTAL.
INSTALL CONDUIT TO WITHIN 3’ FROM COM ED TRANSFORMER/PEDESTAL WITH SUFFICIENT
CABLE/DUCT COILED UP. CONNECTION BY COM ED.
UNDERGROUND CONDUIT SHALL BE INSTALLED IN EASEMENTS OR RIGHT-OF-WAY ONLY. CONTRACTOR
SHALL SUBMIT A WIRING DIAGRAM TO THE VILLAGE FOR REVIEW AND APPROVAL PRIOR TO
CONSTRUCTION, AND SHALL SUBMIT AN AS-BUILT CONDUIT PLAN AFTER CONSTRUCTION.
PROVIDE GROUND RODS AT SERVICE DISCONNECT AND AT EACH LUMINAIRE AS SHOWN.
PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN RUN(S) TO LUMINAIRE(S) PER NEC.
SPLICE CONDUCTORS IN POLE BASE(S) USING COMPRESSION SLEEVES PER VILLAGE
OF SHOREWOOD STANDARD DETAIL.
PROVIDE DUAL IN-LINE FUSEHOLDERS WITH 6A TIME-LAG FUSES IN POLE BASE(S)
FOR EACH LUMINAIRE. USE THWN-#10 STRANDED COPPER WIRE IN POLE(S) FROM
HANDHOLE TO THE LUMINAIRE(S).
USE PVC SCH 80 CONDUIT FOR ALL INSTALLATION WITHIN RIGHT-OF-WAYS.
ELE-8
DATE: JULY 2007
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
DIRECT CONNECTED STREET
LIGHT SERVICE DISCONNECT
FURNISHED BY
CONTRACTOR
INSTALLED BY
C.E. CO.
FURNISHED &
INSTALLED
CONTRACTOR10’
BY
C.E
. C
O.
HE
IGH
T A
S R
EQ
’D
5/8"x10’ COPPERWELD GROUND
ROD W/ #4 AWG SOLID COPPER
GROUND WIRE ATTACHED W/
CLAMPS, LISTED FOR DIRECT
BURIAL SERVICE
GRADE LINE
MIN
.
10’-2" GALV. CONDUIT
2 HOLE STRAPS, AS
REQUIRED
2" RIGID GLAVANIZED
STEEL (RGS) ELBOW
CONTRACTOR TO INSTALL
SUFFICIENT CABLE SLACK
TO REACH COM ED
SECONDARY/TRANSFORMER
WITHOUT SPLICING
30
"
COM ED WOOD UTILITY POLE
(NOTE 3)
COM ED TO INSTALL
FROM 10 FT. ABOVE
GRADE AND UP
2" RGS CONDUIT TO
LIGHTING CONTROLLER
NOTES:
1. ALL WORK SHALL CONFORM TO COM ED’S BOOK OF "INFORMATION
AND REQUIREMENTS FOR THE SUPPLY OF ELECTRIC SERVICE."
2. CONTRACTOR TO PROVIDE CONDUIT BUSHING AND SEALING
COMPOUND.
ELE-9
DATE: JULY 2007
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
COM ED OVERHEAD
CONNECTION FOR
LIGHTING CONTROLLER
CABINET OUTLINE
PHASE CONDUCTOR
NEUTRAL CONDUCTOR
GROUND CONDUCTOR
N.O.
N.C.
AUTOHAND
OFF
A B C D
BRANCH CIRCUIT WIRING,
MINIMUM (4/C #6 & 1/C #6 GND
IN 1 1/4 " UNIT DUCT), TYP.
LATCHING
CONTACT
CLEARING
CONTACT
SPARE
NEUTRAL
BUS
#6 TYP.
METER TO BE SUPPLIED
BY LOCAL UTILITY
COMPANY
100A-120/240V, 1},
3 WIRE, 60 HZ SERVICE
1/C NO. 2
NEUTRAL
GROUND
BUS
NO. 6
BONDING
JUMPER
10 13 17
14
3129
1
9
11
7
2
5
15
6
8
9
9
4
16
NO. 6 COPPER
WIRE TO
GROUND FIELD
PHOTOCELL MOUNTED
IN CABINET OVERHANG
DATE: JULY 2007
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
LIGHTING CONTROLLER
SHEET 1 OF 4
ELE-10A
ITEM
10 SERVICE CABLES
12 CONTROL WIRE
11 LAMPHOLDER WIRE
1 MAIN CIRCUIT BREAKER
4 AUXILIARY RELAY
20 AMPERE, 1P, 120V RATING, 22K AIC
15 AMPERE, 1P, 120V RATING, 22K AIC
13 SURGE ARRESTOR
7 CONTACTOR
15 DOOR SWITCH
SPECIFICATION
SIEMENS NO. ED41B020
SIEMENS NO. ED41B015
SIEMENS NO. ED42B030
MARATHON
N/A
N/A
N/A
SQUARE D NO. SDSA 1175
SQUARE D NO. 9001 KYK 111
SIEMENS NO. ED42B100
OMRON NO. A-20GQ-K
3-600V XLP NO. 12
100 AMPERE, 2P, 240V RATING, 22K AIC
MFG/MODEL NO. OR EQUAL
RECEPT: LEVITON NO. 8899,
BOX: APPLETON NO. WSM150
COVER: APPLETON NO. WHG1
RAB NO. VX100DG
SQUARE D NO. 8903SQO10V02100 AMPERE, 2P, 120V COIL, MECH HELD
120 V OPERATED DPDT 60 HZ COIL 600V
2 N.O. & 2 N.C. CONTACTS
17 PHOTOCELL
2 LAMPHOLDER CIRCUIT
BREAKER
5 CABINET RECEPTACLE
AND BOX
6 CABINET LIGHT & BOX
8 BRANCH LINE CIRCUIT
BREAKERS
9 POWER DISTRIBUTION
BLOCK
14 PHOTOELECTRIC
CONTROL WIRE
16 HAND-AUTO-OFF
CONTROL SWITCH
20A, 3 POS. MTD IN CAST
ALUM. ENCLOSURE
20A/120V, DOOR MOUNTED SNAP
ACTION TYPE PLUNGER SWITCH
120V, MTD. ON CABINET, DELAY TYPE,
SPST-NC
FISHER PIERCE NO.
FPFA-105M-120V
COMMERCIAL GRADE GFCI 20A/120V,
MOUNTED IN A WEATHERPROOF CAST
ALUMINUM SINGLE GANG BOX WITH
WEATHERPROOF COVER
120V WEATHERPROOF LAMPHOLDER
MOUNTED IN A CAST ALUMINUM
BOX & EXT. GRADE 100W LAMP
MAGNECRAFT NO.
389FXBXC1-120A
5-30 AMPERE, 2P, 240V RATING, 22K AIC
3 PHOTOELECTRIC CONTROL
CIRCUIT BREAKER
600 VOLT, INSULATED, SIZE AS
REQUIRED
2-600V MTW NO. 12
2-600V MTW NO. 12
3-600V (XLP-TYPE USE) NO. 2
10 K AMPERE RATING
3-600V MTW NO. 12
DATE: JULY 2007
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
LIGHTING CONTROLLER
SHEET 2 OF 4
ELE-10B
NOTESCABINETS SHALL BE FABRICATED FROM 0.125-INCH SHEET TYPE 5052-H32 ALUMINUM, FORMED
AND ARC WELDED ASSEMBLY.
ALL SCREWS AND HARDWARE SHALL BE PLATED, GALVANIZED, OR MADE OF BRASS, ALUMINUM
OR STAINLESS STEEL.
NAME PLATE SHALL HAVE ENGRAVED 0.75-INCH HIGH LETTERS FILLED IN BLACK: "STREET
LIGHTING."
CABINET SHALL BE PRIMED AND PAINTED AS SPECIFIED. FINISH COAT SHALL BE
RAL6005 GREEN POWDER PAINT.
ELECTRIC UTILITY METER BOX SHALL BE MOUNTED ON THE SIDE OF CONTROL CABINET
AS SHOWN ON THE PANEL LAYOUT DIAGRAM.
THE COMPLETED CONTROLLER WITH ALL OF ITS COMPONENTS SHALL BE UL LISTED AS
AN "ENCLOSED INDUSTRIAL CONTROL PANEL UNDER UL508A.
METAL MOUNTING PANEL SHALL BE #10 GAUGE GALVANIZED SHEET STEEL FLANGED
BACK 0.75-INCHES ID ON 4 SIDES.
CIRCUIT BREAKERS, CONTACTORS AND OTHER COMPONENTS SHALL BE MOUNTED ON
0.125-INCH THICK GLASTIC INSULATION BACK PANEL.
ALL DEVICES SHALL BE FRONT REMOVABLE.
BUS BAR SHALL HAVE 22 LUG TERMINALS SIZED TO ACCOMMODATE REQUIRED WIRE
SIZES. NEUTRAL BUS SHALL BE PAINTED WHITE. GROUND BUS SHALL BE PAINTED GREEN.
ALL LUGS SHALL BE COPPER SCREWS AND CONNECTORS, SPRING HELD.
ALL WIRING TERMINATIONS SHALL BE RATED NOT LESS THAN 75 DEGREE CENTIGRADE.
ALL CONTROL WIRING SHALL BE 600V MACHINE TOOL WIRE TYPE MTW.
ALL POWER WIRING SHALL BE 600V TYPE RHH/RHW.
A LAMINATED COPY OF THE CIRCUIT SCHEMATIC DIAGRAM SHALL BE ATTACHED TO
THE INSIDE OF THE CONTROLLER.
ALL 120 VOLT SYSTEM AND ALL CONTROL WIRING SHALL BE #12 AWG STRANDED UNLESS
OTHERWISE INDICATED.
ALL WIRING SHALL BE NEATLY DRESSED AND SUPPORTED.
CONNECTION OF SURGE ARRESTOR TO LINE SIDE OF MAIN CIRCUIT BREAKER SHALL
NOT BE "DOUBLE LUGGED."
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
DATE: JULY 2007
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
LIGHTING CONTROLLER
SHEET 3 OF 4
ELE-10C
10’-0"
TY
P. E
A. L
EG
GROUND FIELD DETAIL (TYP.)
12"x12" GREEN POLYMER CONCRETE
ACCESS WELL WITH "GROUND" LOGO
EMBOSSED IN COVER, TYP. OF 3
GROUND LINE
NAME
PLATE
4"
CABINET DOOR SHALL
FACE AWAY FROM
ROADWAY
1" CHAMFER
LOUVERED DOOR WITH
FILTER AND SCREEN
CABINET SHALL HAVE
CORBIN LOCK AND
ALSO BE PADLOCKABLE
ENDS OF CONDUITS TO
BE SEALED TO PREVENT
ENTRANCE OF MOISTURE
TRAFFIC BOX ENCLOSURE
ARRANGED FOR MOUNTING
ON CONCRETE FOUNDATION
COM ED
SERVICE
METER
SIZE OF CONCRETE PAD
WHERE NO SIDEWALK
EXISTS-24"x30"x5"
COMPACTED
SAND BASE
3/4 "x10’ COPPERWELD
GROUND ROD, TYP. SEE
GROUND FIELD DETAIL
THIS SHEET
UNDISTURBED GROUNDCONCRETE
FOUNDATION
1/2 " DIA. x 12"
ANCHOR BOLTS
VENT IN OVERHANG WITH
SCREEN
4’-6"
2’-6"
TYPE IV ALUMINUM FABRICATED,
NEMA 3R ENCLOSURE FACTORY
PAINTED GREEN WITH SLOPED
TOP AND SHIELD. CABINET SHALL
BE MANUFACTURED BY SOUTHERN
MFG (DIV OF ACCORD INDUSTRIES)
AND AS COMPACT AS POSSIBLE
6 #4 VERTICAL
PLACED
#4 @ 12" TIES
BUSHING
3" PVC RACEWAYS.
CONTRACTOR TO
COORDINATE,
NUMBER AND
ORIENTATION
(PROVIDE 2 SPARES)
LIGHTING CONTROLLER CABINET & FOUNDATION
3/4 " X 10’ COPPERCLAD
GROUND ROD MIN. 1’-0"
BELOW GRADE (TYP.)
EXOTHERMIC WELD, TYP.)
NO. 6 COPPER
GROUND WIRE
(TYP. EACH LEG)
NO. 6 COPPER
GROUND WIRE TO
LIGHTING CONTROLLER
GROUND BUS
STEEL PLATE LETTERING
3/4 " SIZE W/ "STREET
LIGHTING" ENGRAVED ON
CORROSIVE RESISTANT
PLATE
2" RGS SERVICE
CONDUIT TO COM ED
POLE OR TRANSFORMER
DATE: JULY 2007
STANDARD DETAIL
FOR
VILLAGE OF SHOREWOOD
LIGHTING CONTROLLER
SHEET 4 OF 4
ELE-10D
...\SGN\sgn-1 (sign standards).dgn
SGN-1
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
SIGN STANDARDS
SHEET 1 OF 2
DATE: JUNE 2007
1. SIGN POSTS
A. ALL SIGN POSTS SHALL BE MADE OF A SQUARE TWO PIECE UNISTRUT TELESPAR AND
SHALL BE 12-GAUGE HOT DIPPED GALVANIZED STEEL.
B. THE BASE POST SHALL BE A MINIMUM OF 36 INCHES IN LENGTH AND SHALL MEASURE A
MINIMUM OF 2 INCHES O.D. SQUARE.THE SIGN POST LENGTH SHALL VARY DEPENDING ON
THE SIGN IN ORDER TO MAINTAIN A DISTANCE OF A MINIMUM OF 7 FEET FROM GRADE TO
THE BOTTOM OF THE SIGN AND SHALL MEASURE A MINIMUM OF 1 3/4 INCHES O.D. SQUARE.
C. THE BASE POST SHALL BE DRIVEN PLUMB INTO UNDISTURBED SOIL WITH A MAXIMUM OF
3 INCHES ABOVE GRADE.THE TOP OF THE POST SHALL NOT BE DISTORTED OR DAMAGED
FROM DRIVING IT INTO THE SOIL.
D. THE ASSEMBLY SHALL BE SECURED WITH A GALVANIZED OR EQUAL BOLT, FLAT WASHER, AND
LOCK NUT.THE END OF BOLT IS TO BE PEENED OVER SO THE LOCK NUT CANNOT BE REMOVED.
2. SIGNS
A. STREET NAME SIGN BLADES SHALL BE 9-INCH WIDE EXTRUDED ALUMINUM WITH WHITE
DIAMOND GRADE SHEETING. STREET NAMES SHALL BE MADE OF 6 INCH SERIES "B"
LETTERS.THE STREET DESIGNATION SUFFIX SHALL BE MADE OF 3 INCH SERIES "B"
LETTERS.THE LETTERS SHALL BE PLACED STRAIGHT AND EVENLY SPACED.
B. THE BASE COLOR SHALL BE DIAMOND GRADE WHITE WITH GREEN E.C. FILM LETTERING
AND SHALL VARY IN LENGTH ACCORDING TO THE STREET NAME.THE VILLAGE OF
SHOREWOOD LOGO SHALL BE ON THE LEFT SIDE OF THE SIGN AND SHALL BEGIN 3
INCHES FROM THE END OF THE BLADE.THE LETTERING SHALL BEGIN 2 INCHES FROM
THE LOGO AND END 3 INCHES FROM THE END OF THE BLADE.
C. STOP SIGNS (R1-1) SHALL BE 30-INCH WITH DIAMOND GRADE VIP SHEETING.
THE"ALL WAY" PLACARD (R1-4) SHALL BE APPLIED TO ALL STOP SIGNS AT ALL WAY STOP
INTERSECTIONS.
D. STOP SIGNS (R1-1) SHALL BE 36-INCH WITH DIAMOND GRADE VIP SHEETING AT
ALL INTERSECTIONS WITH U.S. ROUTE 52 AND ILLINOIS ROUTE 59.
E. YIELD SIGNS (R1-2) SHALL BE 36-INCH WITH DIAMOND GRADE VIP SHEETING.
F. SPEED LIMIT SIGNS FOR LOCAL ROADS SHALL HAVE BLACK LETTERING AND BORDERS ON A
WHITE BACKGROUND WITH DIAMOND GRADE VIP SHEETING.
1. SPEED LIMIT SIGNS FOR LOCAL ROADS SHALL BE 24-INCH X 36-INCH WITH
"RESIDENTIAL" "25 MPH" "UNLESS OTHERWISE POSTED" TEXT.
2. SPEED LIMIT SIGNS (R2-1) FOR COLLECTOR STREETS SHALL BE 24-INCH X 30-INCH.
...\sgn-1a (sign standards).dgn
SGN-1
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
SIGN STANDARDS
SHEET 2 OF 2
DATE: JUNE 2007
G. WEIGHT LIMIT - 5 TONS (R12-1) SIGNS SHALL HAVE BLACK LETTERING AND
BORDERS ON A WHITE BACKGROUND AND SHALL BE 24-INCH X 30-INCH WITH
DIAMOND GRADE VIP SHEETING.
H. SPRINKLING RESTRICTION SIGNS SHALL HAVE BLACK LETTERING AND BORDERS
ON A WHITE BACKGROUND AND SHALL BE 24-INCH X 30-INCH WITH DIAMOND GRADE
VIP SHEETING WITH "SPRINKLING ALLOWED" "6AM TO 10AM" "6PM TO 10PM"
"ODD/EVEN" TEXT.
I. NO PARKING ON VILLAGE STREETS AFTER 2 INCH SNOWFALL SINGS SHALL HAVE
RED LETTERING AND BORDERS ON A WHITE BACKGROUND AND SHALL BE 24-INCH
X 30-INCH WITH DIAMOND GRADE VIP SHEETING.
3. HARDWARE AND INSTALLATION
A. ALL BANDING, BUCKLES AND CLIPS SHALL BE STAINLESS STEEL AND
POWDER - COATED BLACK. BANDING SHALL HAVE A MINIMUM OF * INCH WIDTH AND
SHALL HAVE A MINIMUM OF 30 THOUSANDS INCH THICKNESS.
B. ALL STREET NAME SIGNS SHALL BE MOUNTED ON A STREET LIGHT POLE USING
A 14 INCH WING BRACKET FOR BLADES UNDER 36 INCHES AND A 24 INCH
WING BRACKET FOR BLADES 36 INCHES OR OVER.ALL WING BRACKETS SHALL BE MADE
FOR EXTRUDED BLADES; MOUNTED TO STREET LIGHT POLES WITH THREE BANDS;
SECURED USING 5/16 INCH BY 1* INCH GALVANIZED BOLTS OR EQUAL, WITH A
FLAT WASHER AND LOCK NUT; AND BE PLACED A MINIMUM OF 12 FEET ABOVE
GRADE ON THE LIGHT POLE.REGULATORY SIGNS SHALL BE MOUNTED WITH
VANDAL-PROOF HARDWARE.
C. ALL STREETS NAME SIGNS SHALL BE PLACED A MINIMUM OF 12 FEET FROM GRADE
AND PLACED PARALLEL TO THE STREET NAMED.
D. ALL SIGN INSTALLATIONS SHALL CONFORM TO THE MANUAL ON UNIFORM TRAFFIC
CONTROL DEVICES, 2003 EDITION AND SHALL BE CONSISTENT WITH THE APPROVED
TRAFFIC CONTROL, STRIPING, AND SIGNAGE PLANS. IN THE CASE OF A CONFLICT,
THE VILLAGE OF SHOREWOOD CODE SHALL TAKE PRECEDENCE.
E. FOR NEW SUBDIVISION CONSTRUCTION, PERMANENT STREET SIGNS MAY BE MOUNTED
ON A TEMPORARY POST WITH A MINIMUM OF 2-POUND GREEN OR GALVANIZED U POST
AND WITH A MINIMUM LENGTH OF 12 FEET.STREET SIGNS AND REGULATORY SIGNS ARE
TO BE ERECTED PRIOR TO THE ISSUANCE OF THE FIRST BUILDING PERMIT.THE SIGNS
SHALL BE INSTALLED IN ACCORDANCE WITH THE APPROVED SIGNAGE PLAN.THE
DEVELOPER IS SOLELY RESPONSIBLE FOR THE MAINTENANCE OF THE SIGN
INSTALLATIONS UNTIL THE VILLAGE ACCEPTS THE SIGNS. ALL PERMAMENT
SIGNS SHALL BE INSTALLED ON PERMAMENT MOUNTS AT THE TIME OF ROADWAY
SURFACE PLACEMENT.
F. ALL SIGNS ON TEMPORARY POSTS WILL BE TRANSFERRED TO A LIGHT POLE
OR A SQUARE POST WHERE THERE IS NO LIGHT POLE. SIGNS MUST BE TRANSFERRED
TO THE POLE/POST AT THE TIME STREET LIGHTING IS INSTALLED OR AT THE
REQUEST OF THE VILLAGE.
AFTER 2-INCH
SNOWFALL
STREETS
ON VILLAGE
PARKING
NO
...\SGN\sgn-2 (no parking).dgn
24"
30
"
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
NO PARKING SIGN
DATE: JUNE 2007
SGN-2
RESIDENTIAL
25
POSTED
OTHERWISE
UNLESS
LIMIT
SPEED
NOTES:
1. PREFERRED LETTER SIZES NOTED.
2. PLACE ABOVE WEIGHT LIMIT SIGN ON SAME POST.
...\sgn-3 (residential speed limit).dgn
SGN-3
3 12"
8"
2"
24"
36
"
3"
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
RESIDENTIAL SPEED
LIMIT SIGN
DATE: JUNE 2007
6"
30
"
ODD / EVEN
6PM TO 10 PM
6AM TO 10 AM
SPRINKLING
ALLOWED
YEAR ROUND
REGULATION
...\SGN\sgn-4 (sprinkling).dgn
SGN-4
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
SPRINKLING SIGN
DATE: JUNE 2007
NOTE:
1. THIS SIGN IS TO BE DELIVERED TO THE PUBLIC WORKS DEPARTMENT, NOT INSTALLED.
30
"
24"
TONS
5
LIMIT
WEIGHT
...\SGN\sgn-5 (weight limit).dgn
SGN-5
24"
30
"
NOTE: PLACE UNDERNEATH SPEED LIMIT SIGN ON SAME POST.
VILLAGE OF SHOREWOOD
STANDARD DETAIL
5 TON WEIGHT
LIMIT SIGN
DATE: JUNE 2007
SGN-6
...\SGN\SGN-6 (Sign Spacing).dgn
TO
RE
SID
EN
TIA
L
SU
BD
IVIS
ION
VILLAGE OF SHOREWOOD
SIGN SPACING
FOR
TYPICAL RESIDENTIAL
SUBDIVISION ENTRANCE
DATE: JULY 2007
25
’7
5’
75
’
VILLAGE STANDARD
NO PARKING SIGN
VILLAGE STANDARD
WEIGHT LIMIT SIGN OVER
SPRINKLING SIGN
VILLAGE STANDARD
SPEED LIMIT SIGN
END CURB RETURN
SGN-7
...\SGN-7 (Signage for future).dgn
NOTE:
TO BE MOUNTED ON TYPE III BARRICADES BELOW ROAD CLOSED SIGN.
RUTUF SE T TREE
TC CONNE ONI
30"
.5"
.75
"
60"
5"
8"
4"
8"
5"
R1.8
75"
27.75" 27.75"
21.00" 21.00"
VILLAGE OF SHOREWOOD
SIGNAGE
FOR
FUTURE STREET
CONNECTION
DATE: JULY 2007
6"
6"
ELEVATION
701.25
6"
36" M
INIM
UM
72" M
INIM
UM
PERMANENT BENCHMARK
PERMANENT CONCRETE
MONUMENT
NO SCALE
FINISHED
GRADE
...\MSC-1 (Permanent Monuments).dgn
MSC-1
6" P.V.C.
PIPE
STAMPED BRASS
DISK, 4" DIA. MIN.
6" P.V.C.
PIPE
6" SCREW ON CAP
TO BE SET FLUSH
WITH FINISHED GRADE
TOP OF CONCRETE
MONUMENT TO BE
SET FLUSH WITH
FINISHED GRADE
NOTES:
1. PERMANENT CONCRETE MONUMENTS SHALL BE PLACED AT ALL CORNERS AND CHANGES IN BEARING
OF THE EXTERIOR BOUNDARY.
2. A MINIMUM OF ONE PERMANENT BENCHMARK SHALL BE ESTABLISHED FOR EACH 50 ACRES, OR
FRACTION THEREOF, SUBDIVIDED, AT A LOCATION DESIGNATED ON THE CONSTRUCTION PLANS AND
APPROVED BY THE VILLAGE ENGINEER.
(1) # 4 BAR
IN CENTER
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
PERMANENT
MONUMENTS
DATE: JUNE 2007
VIL
LA
GE
OF SHORE
WO
OD
B
EN
CHMARK NO. 1
1
2
NOTES:
1. CASING PIPE SHALL BE NEW PIPE CONFORMING TO ASTM C139 GRADE A WITH CONTINUOUS FIELD-WELDED
BUTT JOINTS IN ACCORDANCE WITH AWWA C206, A MINIMUM YIELD STRENGTH OF 35,000 PSI, AND THE
FOLLOWING MINIMUM WALL THICKNESS:
NOMINAL PIPE SIZE - INCHES MINIMUM WALL THICKNESS - INCHES
UNDER HIGHWAY UNDER RAILROAD
UNDER 14 0.188 0.2500
14 AND 16 0.250 0.3125
18 0.250 0.3125
20 0.250 0.3750
24 0.312 0.4375
30 0.312 0.5000
36 0.375 0.5625
42 0.375 0.563
48 0.375 0.625
54 0.500 0.719
60 0.575 0.781
66 0.650 0.875
72 0.650 0.938
2. COAT EXTERIOR SURFACES OF THE CASING PIPE WITH COAL-TAR EPOXY COMPLYING WITH AWWA C210.
3. PROVIDE CARRIER PIPE SUPPORT SYSTEM TO POSITION CARRIER PIPE AT THE INDICATED ELEVATION AND
SLOPE WITHIN THE CASING, USING POWERSEAL CASING CHOCK MODEL 4810 STAINLESS STEEL SPACERS
CONSISTING OF 4 GAUGE TYPE 304 STAINLESS STEEL SHELLS, PVC LINER, HIGH MOLECULAR WEIGHT POLYMER
RUNNERS, AND STAINLESS STEEL BOLTS AND LOCK NUTS, OR APPROVED EQUAL. A MINIMUM OF THREE
SPACERS SHALL BE PROVIDED PER CARRIER PIPE LENGTH, ON 6-FOOT CENTERS.
4. FILL ANNULAR SPACE BETWEEN CARRIER AND CASING PIPES FOR ALL PIPES EXCEPT WATER MAINS WITH PEA
GRAVEL.
5. CONSTRUCT END SEALS WITH CONCRETE BRICK LAID LENGTHWISE WITH MORTAR OR PREMANUFACTURED
RUBBER END SEALS MADE SPECIFICALLY FOR THIS PURPOSE.
6. FILL VOIDS AROUND EXTERIOR OF CASING PIPE WITH MEARL GEOFOAM LIQUID CONCENTRATE LOW DENSITY
CELLULAR CONCRETE GROUT HAVING A MINIMUM NET DENSITY OF 45 PCF AND A MINIMUM COMPRESSIVE
STRENGTH AT 28 DAYS OF 160 PSI.
NO SCALE
PEA GRAVEL
(SEE NOTE 4)
CASING SPACERS (SEE NOTE 3)
CASING PIPE (SEE
PLANS FOR SIZE)
CARRIER PIPE (SEE
PLANS FOR SIZE AND
MATERIAL)
...\MSC\msc-2 (casing pipe).dgn
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
CASING PIPE
DATE: JUNE 2007
MSC-2
Lot
SERVICE
SANITARY SEWER
WATER SERVICE
WS
SS
Lot
Street
STOP
CORPORATION
DRIV
EW
AY
PR
OP
OS
ED
SANITARY SEWER
WATER MAIN
(TYP)
PROPERTY LINE
LOCATED AT
BUFFALO-BOX
CURB STOP W/
(TYP)
AT PROPERTY LINE
SERVICE LOCATED
PLUG END OF
$FILEABBREV$
MSC-3
DRIV
EW
AY
PR
OP
OS
ED 10' MIN10' MIN
10' MIN 10' MIN
10' MIN
NOTES:
1.) THE END OF EACH WATER SERVICE SHALL BE MARKED WITH A BLUE 4"x4" POST AND
STAMPED "W" ON CURB.
2.) THE END OF EACH SANITARY SEWER SERVICE SHALL BE MARKED WITH A GREEN 4"x4" POST
AND STAMPED "S" ON THE CURB.
3.) BOTH SERVICE LATERALS SHALL BE LOCATED WITHIN 30 FEET OF A PROPERTY LINE. SERVICES
SHALL NOT BE INSTALLED IN SIDE YARD PUBLIC UTILITY AND/OR DRAINAGE EASEMENTS.
4.) DRIVEWAY LOCATION SHALL BE ON OPPOSITE SIDE OF LOT FROM SERVICE LATERALS.
5.) BUFFALO BOXES SHALL BE LOCATED BETWEEN BACK OF SIDEWALK AND PROPERTY LINE.
OF ANY SERVICE.7.) PARKWAY TREES SHALL NOT BE PLANTED WITHIN 10 FEET
6.) WATER SERVICE AND SANITARY SERVICE SHALL HAVE A
MINIMUM 10 FOOT HORIZONTAL SEPARATION.
DATE: OCTOBER 2016
TYPICAL SERVICE LATERALS
FOR
STANDARD DETAIL
VILLAGE OF SHOREWOOD
35' MAX
35' MAX
STANDARD IL DESIGN
PARKING
RESERVED
VILLAGE OF SHOREWOOD
STANDARD DETAIL
FOR
HANDICAP STALL
DATE: JUNE 2007
ACCESSIBLE ROUTE
AISLE
ACCESS
R7-8
ILLINOIS STANDARD
R7-I101
18’
$350 FINE
NOTE:
1. A HIGH QUALITY YELLOW PAINT
RECOMMENDED BY THE PAINT
MANUFACTURER FOR PAVEMENT
STRIPING SHALL BE USED.
RAMPS AS
NECCESSARY
8’-0" 8’-0" 8’-0" 8’-0"
16’-0"16’-0"
THIS PLATE MAY BE
MOUNTED DIRECTLY
BELOW THE R7-8 SIGN
OR COMBINED WITH
THAT SIGN ON A SINGLE
12" BY 24" PANEL.
CURB FACE
THE ARROW SHOULD BE
OMITTED WHERE THERE
IS ONLY ONE SPACE.
THE ARROW MAY ALSO
BE MADE TO POINT IN
ONLY ONE DIRECTION.
THE SIGN MUST BE
SUPPLEMENTED WITH
THE ILLINOIS STANDARD
R7-I101 PLATE GIVING
THE AMOUNT OF THE
FINE FOR ILLEGALLY
PARKING IN THE
RESERVED SPACE(S).
MSC-4
...\MSC\MSC-4 (Handicap Stall).dgn
2. REFER TO THE VILLAGE
ORDINANCE FOR MINIMUM
REQUIRED NUMBER OF
HANDICAP STALLS.
3. HANDICAP LOGO SHALL BE
INSTALLED USING YELLOW
PAINT.