standard for leakage testing
TRANSCRIPT
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 1/18
Heating and
Ventilating
Association
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 2/18
DW/143 Ductwork Leakage Testing \ p ra cti ca l g uid •A practical guide to
DuctworkLeakage
Testing
(HVCA)
HEATING AND VENTILATING
CONTRACTORS' ASSOCIATION
Esca House, 34 Palace Court, London W2 4JG
Telephone: (020) 7313 4900 Fax: (020) 7727 9268
e-mail: [email protected] web: www.hvca.org
COPYRIGHT © 2000
by the Heating and Venti lating Contractors ' Association All rights reserved
(Revised) 20()()
ISBN: 0-903783-30-4
1
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 3/18
CONTENTS Page................ ,1,. ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• , 1 • •• •• ,1 •••••••••••••••••••••••••••••••••
Acknowledgements 2
Cautions 2Preface 3
PART ONE
Practical guide to leakage testing 4-6
Example of complete test sheet 7Hints on leakage testing 8-9
PART TWO
Ductwork classification and air leakage 10
Appendix A: Air leakage from ductwork 11-13Appendix B: Air leakage testing procedure 13-16
ACKNOWLEDGEMENTS
The HVCA records its appreciation and thanks to the persons and organisations who have freely
contributed to this work, and in particular to the members of the Drafting Panel.
Original DW/143 Drafting Panel 1983
J. H. G. Gardner (Chairman)
K.Angood
H. Brierley
H. Brocklehurst
P. Doyle
K.Waldron
K.Wheatley
Ductwork Group Technical Sub-Committee 2000
E. Poppleton (Chairman)
C. Collins
S. V . Howard
B. James
J. E. Murray
C. Robertson
G. P. Keller (Secretary, Ductwork Group)
J. M. Paynton (Former Secretary, Ductwork Group)
R. J. Miller (Former Secretary, Ductwork Group)
Front cover photograph by kind permission of Commtech Limited
WHERE NOT MANDATORY, DUCT LEAKAGE TESTING IS GENERALLY AN
UNJUSTIFIED SUBSTANTIAL EXPENSE.
FINANCIAL CAUTION
It is essential to realise that except where it is mandatory in Class C ductwork in DW/144 this document
is not an endorsement of the routine testing of ducts but purely a guide to outline the procedures,
necessary for testing ducts for conformity with air leakage limits.
When proper methods of assembly and sealing of ducts are used a visual inspection will suffice for the
verification of a well engineered construction.
2
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 4/18
PREFACE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Edgar Poppleton Chairman, Technical Sub-Committee Ductwork Group, 2000
Dctwork Specification DW1142, published by the HVCA in 1982, provided
for the first time in a long series of such publications for leakage limits overthe whole range of air pressures covered by the specification and (where
required) a test procedure to establish conformity.
Although leakage testing of high-pressure ductwork is still mandatory in DWI144
(as was the case in previous ductwork specifications issued by HVCA) the leakage
testing of ductwork designed to operate at low and medium pressures is required only
where so specified in individual job specifications.
With the retention of three pressure classifications in DW/144it is hoped that
the designer, having control over performance standards, will find leakage
testing an unnecessary contract expense with regard to low and medium
pressure ductwork see note Financial Caution (page 2).
Ductwork contractors faced with a job calling for leakage testing should take this
requirement very seriously and satisfy themselves as the job progresses that the
required leakage rate or rates are within the limits set by the designer or the client.
The cost of making good an installation that has been found on completion to have
failed in this respect can be very expensive.
DWI144 specifies leakage limits for the ductwork alone, because the ductwork
contractor has no control over the leakage characteristics of the various components
which go to make up the whole of the air distribution system. Where a job
specification calls for a leakage limit for the whole system, it will be for the designer
or client to ensure that the leakage rates of the components are also within the
required limits.
Edgar Poppleton Chairman,
Technical Sub-Committee Ductwork Group, 2000
3
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 5/18
Part One
A practical guide to
ductwork leakagetesting
1 General
With regard to air leakage, the responsibili-
ties for ensuring the achievement of a satis-
factory job is divided between the drawing
office, the factory and the ductwork installers
on site. It is essential that there is full co-operation between them.
2 The drawing office
2.1 Establish with the client or his represent-
atives the class of ductwork called for in the
job specification, i.e.:
Class A: up to 500 Pa positive
Class B: up to 1000 Pa positive
Class C: up to 2000 Pa positive
2.2 Establish with the client or their represent-
ative that the required leakage rate or rates
are for the ductwork alone (eg excluding
dampers, fire dampers, air handling units,
fans, coils, attenuators, terminal boxes)
unless, by prior agreement, the casings
for any such items have been manufac-
tured/sealed, by the supplier, to the required
standard of DW/144.
Additionally, establish the type of gasket
material required in relation to the pressure
class/velocity of the system.
Note:- Specific gasket material may be
required in locations such as clean rooms,
hospitals etc.
If a leakage limit is laid down for the whole
system, it will be for the client or the design-
er to ensure that the leakage characteristics
of the components are acceptable.
2.3 Agree with the client or designer the test
pressure for each section of the installation.
(Note that whilst duct construction specifica-
tion is related to the highest test class of the
duct installation it is important that each duct
test zone should only be tested to a pressure
to cover the mean working pressure of that
particular section of ducting - see A.9(b).
2.4 Decide on the best way to isolate the
installation into test zones. When doing so,
the drawing office should bear in mind the
test pressures called for, the allowable air
losses, the work sequence on site and the
capacity of the test equipment.
2.5 Arrange for the supply of suitable blanking
medium, e.g. heavy-duty polythene sheet.
2.6 Make sure that all test points and blanking
devices can be reached with the minimum of
difficulty after the ductwork has been
installed.
2.7 Ensure that a reading can be obtained, by
planning test sections to have a permitted
leakage of approximately 25 per cent less
than the total volume generated by the test
rig at the pressure required for each section.
2.8 Provide the ductwork installers with details
of the test zones, duct operating pressures
and test pressures; and indicate the nature of
the blanking devices, gasket material and
sealant to be used.
2.9 Prepare test sheets grvmg the information
called for on the sample test sheet shown on
page 7.
This information should indicate the test
content, the surface area of the ductwork to
be tested, and the permitted leakage of each
section to be tested (this leakage is to be
expressed in litres per second per square
metre of the ductwork surface area).
3 The factory
3.1 Take care to make components with a good
fit to minimise the use of sealant. A poor fit
cannot be remedied by the use of more
sealant - it will not work.
4
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 6/18
3.2 Seal all longitudinal seams, laps, cross joints,
rivets and duct penetrations generally, in
accordance with the requirements of
DW/144.
3.3 Make sure that sealant is properly applied to
the ends of all lock forms and other types of
longitudinal seam, and to the corners and
junctions between those seams and the cross
joints.
3.4 Take special care to have as small a clearance
as possible where there are penetrations of
the duct, as for example, damper spindles.
3.5 Fit and seal branch connections carefully, asrequired by DW/144.
3.6 To be sure of minimum leakage, special care
must be taken in the fitting and sealing of
access doors and panels etc.
3.7 To avoid the danger of breaking the seals, the
ductwork when ready to despatch to site
must be handled and loaded carefully.
4 Site work
For full details of procedure see Fig. 1 on Pages
8 and 9 and Appendix B Pages 14 and 15 .
4.1 Understand the proper use of the test rig.
It is expensive precision equipment. The
instructions must be read carefully and the
equipment handled in a responsible manner.
4.2 Make sure that the right type of test rig is
available for the job. A rig suitable for high-
pressure leakage testing is seldom suitable or
economic for testing low- or medium- pres-
sure ductwork, and vice versa.
4.3 Note that leakage testing is always done
under positive pressure even when the duct-
work is to operate under negative pressure.
4.4 Before installation, inspect all duct sections
to make sure that factory applied sealantshave not been damaged in transit. Make
good where any damage is noticed.
4.5 Ensure the correct gasket material has
been supplied and the application is in accor-
dance with the manufacturer's instructions.
Check with the drawings and specifications
where sealants are to be used on the crossjoints, and apply the sealants as necessary.
(Use only as much sealant as will do the job
- too much sealant is as bad as too little.)
4.6 Pay special attention to the sealing of joints
that will be difficult to reach after installation
of the ductwork.
4.7 Fix the blanking plates or other types of tem-
porary seal in the positions shown by the draw-
ing office. (Ensure that the blanking material isaccessible for subsequent removal.)
4.8 At the earliest opportunity agree with the
client or their representative on a progressive
testing programme.
4.9 Before presentation to the client or their rep-
resentative, it is essential that a preliminary
test is carried out on each section of the work
at the earliest opportunity to ensure that the
ductwork has been correctly manufactured
and site sealant correctly applied.
4.10 If these preliminary tests show that the leak-
age is over the limit, then:
4.10.1 Look for any obvious places where
there may be leaks, for example, an
open access door or missing or
punctured polythene blanks.
Simple methods of locating any
leakage are:
a) by listening for them;
b) by feeling for them especially
with a wet hand;
c) by applying soapy water over
the seams or joints;
d) by (with the agreement of the
client) using a smoke pellet.
NOTE When smoke pellets are
used, the smoke should be intro-
duced downstream of the test rigand not on its intake side.
5
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 7/18
4.10.2 Reseal or correct where you have
found the leakage source(s).
Manufacturing faults should
be reported to the factory
immediately.
4.10.3 Repeat the test after allowing
enough time for the sealant to cure.
(Remember that sealants take
longer to cure in cold weather.
Read the sealant manufacturer's
instructions. )
4.11 When satisfied with the results of the
preliminary tests then:-
4.11.1 On successful completion of thetest, offer the section to the client or
their representative for formal
acceptance and signature on the test
sheet;
4.11.2 A permanent record of tests must
be retained.
4.12 As tests are satisfactorily completed, remove
all blanking-off devices.
6
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 8/18
5 Example of a completed test sheetBased on ductwork shown on pages 8 and 9
Test No ..
General
Name of job ( Y ~ t t . ~ ~ f . : ! : ! ! : . . ' P ! . ~ C ! . .Building Ref. .. ( ' ( f ! . ' ! t . ! ? ( q r : ! ; .!. .
Part 1 - Physical details
a Section of ductwork to be tested . ~ ( d . . 4 ? ' ! t . f . I ! t . . 4 ? ' # ! ! ! . ' ! 1 . . ~ ( d J J . q p . ( . .
b Drawing Number ..g 9 . 1 : ~ ~ ! ! . ! . . .c Pressure Classification C/t l88 'C I (PROVIDED BY DESIGNERS). . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .
d Test static pressure ! . ~ 9 . Q T . t 1 . ~ p . q ! . J ? ( l : { I f- ! ¥ . ! - ? f N r F ' ! , E ; l ! ~ . I J U . F ? : . T f - ! T . A J ! ! J . I , :/ . 7 . ~
e Leakage factor ... Q . . ~ - ? . / ! t . ' E ! ! # . ~ ~ ! 1 : J : . ( .~~?"! .~:: . : .~.~~~.~:.~: !f Surface area of duct under test 80 St tJ It lre met res (FROM CALCULATIONS BELOW). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
g Maximum permitted leakage . ! . { ? / ( t : ( e . ~ ! 2 ? ~ 0 ( : . : : ! ! .
Part 2 - Test particulars
a Duct static pressure reading ! . - ? .9 . 9 .J l . t ! . ? ! . q ( ~ ( l ! M P . Rff. Mf. l 'f9 .Af li ! flWt{ ! l i~ !J ! . !r ; ) .
b Manufacturer and type of flow measuring device ~·.e S.~~ ..!.qg.7!~ .'!!~ .A to 100
N..I. (FROM RIG MANUFACTURERS
C Range of measurement of flow measuring device ~<r: .~?1.~~0 !:~~1!l!f'!:1!.~~!.
d Reading of flow measuring device g q _ . .~.P'q~fq!2? ( l : ! 1 . C ! t ; t , . ~ ! r : ! .
18/ '-1- .1 . (DERIVED FROM CHART SUPPLIED WITH RIG USING "d")
e Interpreted air flow leakage rate / ! r?:~. '?/~~0. ~ ~ ? " ! .E _ . R _ ~ c : ~ . ~ .E _ ~ I ? ~ ~ R _ . ~ ~ ~ . K : :. G _ ~ . I ? , If ? ~ ~ r .~ : !
f Duration of test (normally 15 minutes) ..!.-? ..'!!/ l(fI.~~ ..
D~te of test ! . : ! . . : 9 . 9 . Carried out by(.s~'!. t(:.~g.t!!.~:. . . . . . . . .Witnessed by ..~.~~ ..ignature] (Signature)
Printed Name.:~.ij.9.!'~~&........... Printed Name . r . ! . .~ , : ? ~ p . ~ . < ? ~ . .
and Company . r . ! l ? f P I ( F ! . J ? . ~ t . d : . . . . . . and Company / ! ~ .f ~ '! . J ? I ( ! . ~ ~ t . ~ . .
Periphery Length Area
millimetres metres square metres
3100 17.55 54.40
2500 5.57 13.93
1200 1.20 1.44
958 7.00 6.70
785 4.50 3.53
TOTAL 80.00
7
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 9/18
Fig. 1 Hints on Ductwork Leakage Testing
Take special care
with inaccessible
joints
6OOx6S0
800 x 7S0
FLEX
Kee p le ng th to a m in imum
aD d make su re tha t both
e nd c on ne ctio ns a re co r r e c t l y
sealed aD d tha t th e flexible
duc t itselfhas no leaks.
47S
TES T R IG
To be connected and o pe ra te d in
accordance wi1h t he appara tus
instructions. In general , site on
f irm le ve l base and ensure gauges
a re topped up with correct fluid
an d ze roed prior to commeocingFi t correct flow test. Inc l ined manometa' to read
measu r i ng device. leakage rate or pressu re d r op
w hic h c an be converted to leakage
rate by re ference to graph.
Iaorder toavoid
iKornct .........ofdad preaue
8ae tube froIIl tile
vertlal ... ometer...... be COaaeaMdirectly to the
network aader test.
SEQUENCE OF TEST
1. Prepare test sheet
2. Connect a n d adjust test rigto c or re ct p re ss ure .
3 . Rea d o ff le ak ag e rate.
4. R ese al ifn ec essa ry (a llo w time to cure).
S.Maintain test for IS mins.
6. S w itch o ff aD d allow to zero.
7. Reapply test pressu re aud check reading.
8. Re c or d d e ta ils on test sheet and ob ta in s ig natu re .
WARNINGTake care not to over prwsurtsesystem under test
8
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 10/18
11Ie . . .. . .. . .. . .. . .. dKtwoItl ......... _ ...... 011 . .. . 7
2500
rr<8OOX750~ I1 0 0 0 1
~=", ' "
K3 5 0 0 /
700 " , ' " V"
" "-.I 550 I~ I 0 " " -
f v tv----JJ \ ~
~p-- . .
3 ( ]50 ~ ~ = = b:=!!! ~f - - : : : : : v
~
.r
.>1oIi~
~.> ~
/ r - - - - - - -
Blank off all op e n
ends. Remembe r tor--
blaDk instrument
1appiogs a o d test
boles.4175
I--
I---
~
BIaDt at conven ient ~ ~er t ica l lD lDOl l le ter
to read p resswe place with access
for ease of re mova l ~. . . . .
intest sect ion . : : - - .
800 X 750 -~~ - - ~ - - - ~__.."""
H OW TO FIN D LEA KS
1.Look - par t icu lar ly at blaub, access openings
aD d difficult joints .
2. Listen - with test rignaming, leaks
should be audible.
3 . Feel - runn ing your hand (particularly ifwet)ove r joints ca n beJp to locate leab.
4. Soap a o d Water - paiDt ove r joints a o d look for bubbles •
5. Smoke Pellet - p la ced ins id e duc twork (obtain permission for use)
ORO No. 20433/12
9
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 11/18
Part Two
6 This section, apart from Appendix 'B', is
extracted from DW/144 - Specification for
Sheet Metal Ductwork, and for ease of refer-
ence the numbering as in DW /144 has been
retained. The leakage limits for EUROVENT
classifications A, Band C, as set out in their
document 2/2 (Air Leakage in Ductwork) have
been adopted for the low pressure, medium
pressure and high pressure Class C classifica-
tions.
Ductwork classification and
air leakage
6.1 Classification and air leakage limits
Ductwork classification and air leakage
limits are set out in Table l.
6.2 Compatibility with CEN
The leakage factors used in Table Ifor
Classes A, Band C are the same as those for
the classes similarly designated in the CEN
Document Pr EN 12237IPr EN1507.
6.3 Leakage at various pressures; and other
relationships
Applying the limits specified in Table 1,
Appendix A (Table 17) sets out the permitted
leakage at each of a series of pressures up to
a maximum for each class. Included in that
appendix is a graphical presentation of the
pressure/leakage relationship (see fig 178).
Appendix A, also gives details of the basis
for the leakage limits specified III
Table 1.
Table 1 Ductwork Classification and Air Leakage Limits
Staticressure limit
6.4 Air leakage testing
Air leakage testing of low and medium pres-
sure ductwork is not mandatory under the
specification DW/144.
Air leakage testing of high pressure ductwork
is mandatory under the specification DWIl44
and for details of testing procedure refer to
Part 1 of this guide.
Pa500
0.003 X pO.65
Air leakage limitslitres per second per squaremetre of duct surface area
Maximum air
t---P-OS-)'t-)'v-er-N--ti----I velocityega ve
PaS O O
mls10 0.027 X pO.65
1000
2000
Where p is the differential, pressure in pascals.
20 0.009 X pO.6550
750 40
10
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 12/18
APPENDIX A
Air leakage from
ductworkA.1 Introduction
Leakage from ducted air distribution systems
is an important consideration in the design
and operation of ventilation and air condi-
tioning systems. A ductwork system that has
limited air leakage, within defined limits, will
ensure that the design characteristics of the
system can be maintained. Itwill also ensure
that energy and operational costs are main-tained at optimum levels.
Ductwork constructed and installed in accor-
dance with DWI144 should minimise a level
of air leakage that is appropriate to the oper-
ating static air pressure in the system.
However, it is recognised that the environ-
ment in which systems are installed is not
always conducive to achieving a predictable
level of quality in terms of system air leakage
and it is therefore accepted that designers
may sometimes require the systems to be test-
ed in part or in total. It should be recognised
that the testing of duct systems adds a signif-
icant cost to the installation and incurs some
extra time within the programme (See 4.1 and
6.4 of DW/144 re mandatory testing).
A.2 Duct pressure
Ductwork constructed to DW1144 will be
manufactured to a structural standard that is
compatible with the system operating pressure.
There are three classes of duct construction to
correspondwith the threepressureclassifications:
Class A
Low pressure ducts suitable for a maximum
positive operating pressure of 500 Pascals
and a maximum negative pressure of -500
Pascals.
Class B
Medium pressure ducts suitable for a maxi-
mum positive operating pressure of 1000Pascals and a maximum negative pressure of
-750 Pascals.
Class C
High pressure ducts suitable for a maximum
positive operating pressure of 2000 Pascals
and a maximum negative pressure of -750
Pascals.
A.3 Leakage fromductwork
Leakage from sheet metal air ducts occurs at
the seams and joints and is therefore propor-
tional to the total surface area of the ductwork
in the system. The level of leakage is similar-
ly related to the air pressure in the duct sys-
tem and whilst there is no precise formula for
calculating the level of air loss it is generallyaccepted that leakage will increase in propor-
tion to pressure to the power of 0.65.
The effect of air leakage from high pres-
sure/velocity ductwork is critical in terms of
system performance, energy consumption
and the risk of high frequency noise associat-
ed with leakage.
These problems are less critical with medium
pressure/velocity systems, but should be
considered.
Low pressure/velocity ducts present thelowest risk in terms of the effect of leakage on
the effective operation of the system.
A.4 System leakage loss
As there is no direct relationship between the
volume of air conveyed and the surface area
of the ductwork system required to match the
building configuration it is difficult to express
air leakage as a percentage of total air vol-
ume.
Similarly, the operating pressure will vary
throughout the system and as leakage is relat-
ed to pressure the calculations are complex.
However, it is generally accepted that in typ-
ical good quality systems the leakage from
each class of duct under operating conditions
will be in the region of:
Class A low pressure 6%
Class B medium pressure 3%
Class C high pressure 2%
11
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 13/18
A.S Specifying air leakage testing
Respecting both the cost and programme
implications associated with testing ducts for
leakage, the designer may, for example indi-
cate that a particular system is tested as
follows:
a) High pressure ducts - all tested.
b) Medium pressure ducts - 10% of the
ductwork shall be selected at random and
tested.
c) Low pressure - untested.
Table 17 Air leakage rates
Maximum leakage of ductwork
Sta t ic Low-pressure Medium-pressure High-pressure
pressure Class A Class B Class C
differential
1 2 3 4
Pa Litres per second per square metre of surface area
100 0.54 0.18
200 0.84 0.28
300 1.10 0.37
400 1.32 0.44
500 1.53 0.51
600 0.58 0.19
700 0.64 0.21
800 0.69 0.23
900 0.75 0.25
1000 0.80 0.27
1100 0.29
1200 0.30
1300 0.32
1400 0.33
lSOO 0.35
1600 0.36
1700 0.38
1800 0.39
1900 0.40
2000 0.42
Note: Recommended 'mean' test pressures are highlighted in
bold type with the actual selection being left to the test
operator.
In the case where a random test is selected for
medium pressure ducts the following clause is
suggested for inclusion by the designer.
The designer shall select at random a maxi-
mum of 10% of the duct system to be testedfor
air leakage. The duct shall be tested at the
pressure recommended in Table 17of DWI144
for the classification for the section of the
ductwork that is to be tested.
The tests shall be carried out as the work pro-
ceeds and prior to the application of thermal
insulation.
In the event of test failure of the randomly
selected section, the designer shall have the
right to select twofurther sections at random
for testing. Where successive failures are
identified there shall be a right to require thecontractor to apply remedial attention to the
complete ductwork system.
The contractor shall provide documented
evidence of the calculations used to arrive at
the allowable lossfor the section to be tested
and the client, or his agent, shall witness and
sign the results of the test.
A.6 Special cases
There may be situations on a project wherecircumstances dictate that special considera-
tion be given to containing air losses, e.g. a
long run of ductwork may incur a dispropor-
tionate level of air loss.
In cases such as this example the designer can
specify an improved standard of airtightness,
i.e. 80% of allowable loss for Class 'B' ducts.
The designer should not specify a Class 'C'
test at Class 'C' pressure for a Class 'B' duct.
A.7 Suggested range of testing
(see cautionary note on page 2 of this guide)
• High pressure ducts 100% test
• Medium pressure ducts see A5
• Low pressure ducts Untested
• Exposed extract systems Untested
• Ceiling void extract
systems
• Secondary ducts from
VAV or fan coil units
• Flexible ducts
Untested
Untested
Untested
12
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 14/18
• Final connections and
branches to grilles and
diffusers Untested
A.S Testing of plant items
Items of inline plant (eg. Figs. 168 to 175) will
not normally be included in the air leakage
test. The ductwork contractor may include
such items in the test if the equipment has a
certificate of conformity for the pressure class
and air leakage classification for the system
under test.
A.9 Designer'scalculations
The designer can calculate with reasonableaccuracy the predicted total loss from a sys-
tem by:
a) Calculating the operating pressure in
each section of the system.
b) Calculating the surface area of the
ductwork in each corresponding pressure
section.
c) Calculating the allowable loss at the
operating pressure for each section of the
system (see Table 17 for allowable leak-
age figures).
A.10 Variable pressures in systems
Designers can achieve significant cost savings
by matching operating pressures throughout
the system to constructional standards and
appropriate air leakage testing, e.g. the prac-
tice of specifying construction standards for
whole duct systems based on fan discharge
pressures may incur unnecessary costs on a
project.
For example, some large systems could well
be classified for leakage limits as follows:
Plant room risers Class C
Main floor distribution Class B
Low pressure outlets Class A
~p.p.~~~~~~ .
Air leakage testing
Procedure
B.1 General
Section 6 (page 10)of this specification deals
with the performance requirements of duct-
work in respect of air leakage, and Table 17
(Appendix A) tabulates the limits of leakage
applicable to each class of ductwork.
Appendix B is solely concerned with recom-
mendations for the testing procedure.
B.2 Extent of ductwork to be
tested
B.2.1 The procedure set out in this section
is limited to the ductwork and those
items of in-line plant equipment that
are manufactured/sealed to the crite-
ria set out in Table 1 (also see
Appendix A.8).
B.2.2 The extent of the ductwork to betested and the method of selection
(where not included in the job spec-
ification) should be determined in
collaboration between the designer
and the ductwork contractor with
consideration having been given to
the recommendations outlined in
Appendix A.
B.2.3 Fit blanking devices in accordance
with the drawing office guidance
notes (Part 1, Section 2). To enable a
blank to be cut out after the testing is
completed, access may be required
adjacent to each blank.
B.2.4 Alternatively, rigid removable
blanking plates can be used,
although this involves remaking
joints.
13
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 15/18
DW/143 Ductwork Leakage Testing \ practic t!
Fig. 178 Permitted leakage at various pressures
Leakage in litres per second per square metre duct surface area
l
ut\
~
~t\ ~t\ ~
= =". . .= =
~'\~,¢.
~Il~,~l'P~'\
1 \
I'\: ~! I I i . : 11
~
p~11~~»
" " 4 t . . . . . ,0)
" " "
,
" " I i i i i I
1 0 . t,
" " " 1 " " 1
000N
00
~
00
: = :
0
0
~
00
~
00
~
00
:: !
00
~'";~
0 '"~S : : ! Q.
. 50 <Ii0 ~:2 =Ii
'" '0 ~0 : e\
t0 =
'"'"O
t~
00r--
00'>D
00V)
00
'1"
00
'"
00N
0
:2
0
14
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 16/18
B.3 Testing to be completed
before insulation, etc.
Testing shall be satisfactorily completed
before insulation or enclosure of the duct-work and before terminal units (if any) are
fitted.
B.4 Re·testing procedure where
necessary
B.4.1 The air leakage rate for any section
shall not be in excess of the permit-
ted rate for that section. Ifa first test
produces leakage in excess of the
permitted maximum, the sectionshall be resealed and retested until a
leakage not greater than the permit-
ted maximum for that section is
achieved.
B.4.2 If at the time of witnessing the test it
is apparent that excessive additional
sealing of seams or joints has been
done in order to meet the required
leakage level, the section of duct-
work under test shall not be countedas part of the tested ductwork,
except where the whole of the duct-
work is required to be tested.
B.S Minimum area to be tested
The section of ductwork to be tested shall
have an area large enough to enable the test
rig to register a measurable leakage.
B.6 Test pressures and leakage
rates
The maximum permissible leakage rates for
the full range of pressures are given in Table17. The recommended test pressures for the
various classes of ductwork are set out in
Table 2, and unless otherwise specified, the
choice of test pressure shall be at the discre-
tion of the test operator.
B.7 Test rig
B. 7.1 The accuracy of the test rig shall be
within:
± 10 per cent of the indicated flowrate, or 0.4 litres per second,
whichever is the greater; and
± 5 per cent at the indicated static
pressure in the duct under test.
B.7.2 The test rig shall be inspected by
the user before use on site, and
shall have a calibration certificate,
chart or graph dated not earlier than
one year before the test for which it
is used.
B.7.3 A schematic arrangement of an air
leakage test is given in Fig. 2.
B.8 Procedure
B.8.1 The section of ductwork to be test-
ed for air leakage shall be sealed.
Main ducts should be provided
Staticpressuredifferential
Low-pressureClass A
Pa
200
400
800
1200
1500
15
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 17/18
with flanged joints to enable
blanking plates to be fitted, while
small open ends may be sealed with
polythene or inflatable bags, which
should be left in position until final
connections are made.
B.9.1 Complete Part 1 of the Test Sheet.
B.9.2 Connect test rig to section of duct-
work to be tested.
B.9.3 Adjust test rig until the static pres-sure differential is obtained.
B.8.2 On low-pressure systems, final
grille spigots made as a second fix
operation shall be excluded from the
test. The joint shall, where practica-
ble, be checked by external visual
examination.
B.9.4 Check that the measured leakage is
within the permitted rate. (No addi-
tion shall be made to the permissible
leakage rate for access doors, access
panels or dampers where these are
included in the ductwork.)
B.8.3 Sufficient time shall be allowed
between installation and leakage
testing for sealants to cure.
B.9.5 Maintain the test for fifteen minutes
and check that the leakage rate hasnot increased.
B.8.4 Special care must be exercised in
making all joints which fall outside
the scope of the testing procedure,
i.e., joints between tested sections
of ductwork and between ductwork
and items of in-line equipment not
included in the test.
B.9.6 Reduce pressure in section to zero
by switching off the fan; then imme-
diately re-apply test pressure to
establish that the air leakage rate is
not greater than the previous read-
ing.
B.8.5 Due notice of tests shall be given, so
that arrangements for witnessing thetests can be made.
B.9.7 Record details on Part 2 of the Test
Sheet and complete, including wit-nessing.
B.9 Testing sequence 8.10Air leakage test sheet
The recommended sequence of testing is as
follows.
A example of a suitable Test Sheet is given
on page 7.
fan
Fig. 2 Schematic arrangement of an air leakage test
Blanking
plate
/'
Flow measuring device
(may be located onthe suction side ofthe fan)
Duct under test
Bleed valve (not necessary
/ if variable speedfan used)
Inclined gauge
16
8/3/2019 Standard for Leakage Testing
http://slidepdf.com/reader/full/standard-for-leakage-testing 18/18
(HVCA)
Heating and Ventilating Contractors' Association
Esca House 34 Palace Court London W2 4JG
Tel: 020 7313 4900
Fax: 020 7727 9268
e-mail [email protected]
web site www.hvca.org.uk