steam powered absorption chiller installation and operation manual tt

Upload: romihamdani

Post on 11-Oct-2015

34 views

Category:

Documents


0 download

DESCRIPTION

Steam Powered Absorption Chiller Installation and Operation Manual TT

TRANSCRIPT

  • Thermal Technologies Europe AB | www.thermatec.se | [email protected]

    Steam-fired LiBr Absorption ChillerInstallation & Operation Manual

    V5.1

  • Contents Part 1 Working Conditions ............................................................................................................................. 1 Part 2 Working Principle and Cooling cycle .................................................................................................. 2 Part 3 Main Parts and Their Functions ........................................................................................................... 4 Part 4 Properties of LiBr Solution .................................................................................................................. 6 Part 5 Control System and Protections........................................................................................................... 8 Part 6 Installation of system ......................................................................................................................... 13 Part 7 Preparation and Operation ................................................................................................................. 16 Part 8 Operation Record and Management .................................................................................................. 23 Part 9 Troubleshooting ................................................................................................................................. 27 Part 10 Maintenance .................................................................................................................................... 31 Appendix 1Saturated water vapor temperature & pressure table ............................................................ 37 Appendix 2System diagram .................................................................................................................... 38 Appendix 3Solubility curve of LiBr solution .......................................................................................... 39 Appendix 4Users water system linkage diagram ................................................................................... 40 Appendix 5Control cabinet I/O terminals ............................................................................................... 41 Appendix 6Electrical principle diagram ................................................................................................. 42

    Thermal Technologies Europe AB | www.thermatec.se | [email protected]

  • 1

    Part 1 Working Conditions

    Chilled water outlet temperature: 5

    Cooling water inlet temperature: 1834

    Chilled/Cooling water system pressure: 0.8MPa (except special orders)

    Cooling water: Clean fresh water, with its quality complying with Table 8-1

    Working steam: Saturated vapor with dryness fraction>99% and overheating

    degree20C (except other vapors specified in the contract)

    Power supply: 3 phase, 380V/50Hz

    Machine room temperature: 5C40C

    Machine room relative humidity: 85%

    Machine room should be free of dust

    Warning: 1. The chiller is a type of vacuum equipment and all valves on it have been

    firmly sealed before shipment from factory. Any forms of modification to these valves are prohibited, that may damage or even destroy the chiller.

    2. The chiller should be stored at a place where it is protected from rain and the relative humidity is not greater than 85%, otherwise the electrical elements may be damaged.

    3. The chiller should be unpacked only by our companys professional commissioning personnel or properly trained individuals.

    4. Do install a strainer (60-80 meshes) at the steam inlet. 5. Do install a check valve at the steam inlet. 6. The customers chilled water pump and cooling water pump are required to

    be in linkage with the chiller, otherwise the freezing of tubes may occur.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 1

  • 2

    Part 2 Working Principle and Cooling cycle

    1. Working principle

    Any liquid absorbs heat from its surroundings as it vaporizes. And the lower the

    atmospheric pressure, the lower the vaporizing temperature. For example, water vaporizes at

    100 under one atmospheric pressure, but under the 0.00891 atmospheric pressure, it

    vaporizes at 5.

    That is the basic working principle of a LiBr absorption chiller. Water (the refrigerant)

    vaporizes in the high-vacuum absorber and absorbs heat from the water to be chilled. The

    refrigerant vapor is then absorbed by the LiBr solution (the absorbent) and circulated by pumps

    to keep the process going cyclically.

    Fig.2-1 Working principle

    2. Cooling cycle

    The working principle of a steam-fired double-effect LiBr absorption chiller is shown as

    Figure 2-1. The diluted solution from the absorber, pumped by the solution pump, passes the

    low-temperature heat exchanger (LTHE), condensed water heat exchanger (CWHE) and

    6FF54F

    F3

    F2

    1F

    1

    2

    3

    4

    5

    6

    7

    8

    5 4

    8

    7

    6 3

    2

    1Cooling water

    out

    Chilled water out

    Cooling water in

    Chilled water in

    CondenserLow-temp generator

    Steam in

    High-temp generator

    Evaporator Absorber

    High-temp generator pressure

    High-temp generator intermediate solution temp

    Automatic decrystallizing tube temp

    Evaporator liquid levelEvaporation temp

    Automatic purge device liquid level

    Cooling water inlet tempCooling water inlet target flowmeter

    Chilled water inlet tempChilled water inlet target flowmeter

    Chilled water outlet tempChilled water outlet target flowmeter

    F1 Main purge valveF2 Ultimate vacuum purge valveF3 Absorber purge changeover valveF4 Refrigerant water sampling valveF5 Solution sampling valveF6 Refrigerant water regereration valve

    Condensate out

    Steam trap

    Condensate heat exchanger

    Low-temp heat exchanger

    Auto

    mati

    c de

    crys

    talliz

    ing t

    ube

    High-temp heat exchanger

    Aut

    omati

    c pu

    rge d

    evice

    Cooler

    Vacuum pump Refrigerant pump

    Solution pump

    Oil trap

    Concentrated solution

    Intermediate solution

    Diluted solution

    Chilled water Cooling water

    Refrigerant water

    Refrigerant vapor

    Steam

    Condensate

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 2

  • 3

    high-temperature heat exchanger (HTHE) and enters the high-temperature generator (HTG),

    where it is boiled by the working steam flowing in the tubes to generate high-pressure,

    high-temperature refrigerant vapor. The diluted solution turns into the intermediate solution.

    The intermediate solution flows via HTHE into the low-temperature generator (LTG),

    where it is heated by the refrigerant vapor from HTG to generate refrigerant vapor. The

    intermediate solution becomes the concentrated solution.

    The high-pressure, high-temperature refrigerant from HTG, after heating the intermediate

    solution in LTG, condenses into refrigerant water. The refrigerant water then, together with the

    refrigerant vapor from LTG, enters the condenser, where the mixture is cooled by the cooling

    water and turns into refrigerant water.

    The refrigerant water generated in the condenser passes through a U-pipe and enters the

    evaporator. Part of the refrigerant water vaporizes due to the very low pressure in the

    evaporator, while the majority of it is pumped by the refrigerant pump and sprayed on the

    evaporator tube bundle. The refrigerant water sprayed on the tube bundle then absorbs the heat

    from the water flowing in the tube bundle and vaporizes.

    The concentrated solution from LTG flows via LTHE into the absorber and is sprayed on

    the tube bundle. After being cooled by the water flowing in the tube bundle, the concentrated

    solution absorbs the refrigerant vapor from the evaporator and becomes diluted solution. In this

    way, the concentrated solution continuously absorbs the refrigerant vapor generated in the

    evaporator, keeping the evaporation process continuing. In the meantime, the diluted solution is

    transmitted by the solution pump to HTG, where it is boiled and concentrated again. Thus a

    cooling cycle is completed and the cycle repeats.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 3

  • 4

    Part 3 Main Parts and Their Functions

    The steam-fired double-effect LiBr absorption chiller mainly consists of the

    high-temperature generator (HTG) (not available for single-effect models), low-temperature

    generator (LTG), condenser, evaporator, absorber, high-temperature heat exchanger (HTHE)

    (not available for single-effect models), low-temperature heat exchanger (LTHE), condensed

    water heat exchanger (CWHE)automatic purge device, vacuum pump, solution pump,

    refrigerant pump, electric valve, electric control cabinet, etc.

    Table 3-1

    S/N Part Name Function

    1 HTG

    Boils the solution with the working steam to generate the primary refrigerant

    vapour which will enter LTG and concentrates the solution into the

    intermediate solution which will flow to HTHE.

    Working condition: absolute pressure700mmHg

    solution temperature155C

    2 LTG

    Utilizes the primary refrigerant vapour to concentrate the intermediate

    solution into concentrated solution. The primary refrigerant vapour changes

    into refrigerant water and the secondary refrigerant vapour is created.

    For a single-effect model, LTG evaporates the solution with the working

    steam to generate the refrigerant vapour, and the solution becomes

    concentrated solution.

    Working condition: absolute pressure55mmHg

    solution temperature90C

    3 Condenser

    Condenses the refrigerant vapour from LTG into refrigerant water and cools

    down the primary refrigerant water from HTG, with the heat generated taken

    away by the cooling water.

    Working condition: absolute pressure55mmHg.

    4 Evaporator Evaporates the refrigerant water to cool down the chilled water.

    Working condition: absolute pressure7mmHg

    5 Absorber Uses the concentrated solution to absorb the refrigerant vapour from the

    evaporator, with the heat being taken away by the cooling water.

    6 HTHE Recovers heat from the intermediated solution in HTG, improving the

    thermodynamic coefficient of the chiller.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 4

  • 5

    7 LTHE Recovers heat from the concentrated solution in LTG, improving the

    thermodynamic coefficient of the chiller.

    8 CWHE Recovers heat from the condensate of the working steam in HTG, improving

    the thermodynamic coefficient and lowering the steam consumption of the

    chiller.

    9 Automatic

    purge device They constitute the purge system which removes the non-condensable gas in

    the chiller, guaranteeing the performance and extending the service life of the

    chiller. 10 Vacuum pump

    11 Refrigerant

    pump

    Circulates the refrigerant water, making it dispersed evenly on the heat

    transfer tube bundle in the evaporator.

    12 Solution pump Circulates the solution.

    13 Electric valve

    set

    Regulates the input of working steam or cuts off the working steam

    14 Electric control

    cabinet

    Accommodates components of the control system.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 5

  • 6

    Part 4 Properties of LiBr Solution

    1. General properties

    Lithium bromide (LiBr) is similar to sodium chloride (NaCl) in property. As a stable

    substance, it is nonperishable, non-decomposable and nonvolatile in the atmosphere. Its

    solution is a clear, transparent, and nontoxic liquid, which has a bitter taste and can cause slight

    itching on the skin. LiBr solution becomes slight yellow after lithium chromate (Li2CrO3) is

    added in, and remains clear with lithium molybdate (Li2MoO4). Avoid touching it directly with

    skin, splashing it into eyes and tasting it.

    The quality of the LiBr solution decides the chiller performance to a large extent.

    Therefore, strict measures must be taken to control its quality, which should meet the following

    standards:

    Concentration: 500.5%

    Alkalinity: pH 9.0~10.5

    Li2CrO3 content: 0.10.3% ( Li2MoO4 content: 0.012~0.018%) Maximum content of impurities:

    ChlorideCl-: 0.05%

    SulphateSO4-: 0.02% BromateBO4-: non-reaction

    AmmoniaNH3: 0.0001%

    BariumBa: 0.001% CalciumCa: 0.001%

    MagnesiumMg: 0.001%

    2. Solubility

    The concentration of the saturated LiBr solution is about 60% at normal temperature. At a

    given concentration, crystals separate out from the solution when the temperature drops. And at

    a given temperature, crystals separate out when the concentration rises. Crystallization must

    be avoided during the chillers operation and shutdown period. See Appendix 3 for the

    solubility curve of LiBr solution.

    3. Specific gravity

    The specific gravity of LiBr solution is greater than that of water and is a function of the

    concentration and temperature of the solution itself. So once the specific gravity and

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 6

  • 7

    temperature of the solution is measured, the concentration can be obtained.

    4. Causticity

    Though LiBr solution has little caustic effect on common metals under vacuum condition,

    it causes severe corrosion with presence of an extremely little amount of oxygen within the

    chiller. Therefore, preventing air leaking into the chiller is the fundamental measures for

    anti-corrosion. Adding proper amount of Li2CrO3(Li2MoO4) in the LiBr solution and keeping

    pH value at 9.0~10.5 also effectively reduces its caustic effect on metals.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 7

  • 8

    Part 5 Control System and Protections

    1. Components of control system

    The control system of the chiller is composed of the PLC, touch screen, inverter,

    temperature acquisition module, analog output module, liquid level controller, AC contactor,

    thermal relay, intermediate relay, etc. Its peripheral input sensors include target flow switch,

    liquid level electrode, platinum resistor, pressure switch, etc.

    2. Functions of control system

    S/N Function Description

    1 Touch screen

    operation

    Easy and reliable touch operation compared to mechanical

    contacts.

    2 Human-machine

    dialogue

    Customers can change the parameter settings, correct the

    measured values of parameters, learn how to operate and

    maintain the chiller and have access to the memory through the

    human-machine interface.

    3 Clock display Time can be displayed on the screen, including the year, month,

    date, hour, minute, second and weekday.

    4 Auto start/stop The chiller can be automatically started or stopped at the

    customer set time.

    5 Information display Information about the chiller operating status, parameter setting,

    correction, etc. is displayed in different pages on the screen.

    6 Real-time test and display

    Parameters such as temperature, flow and liquid level are

    monitored and displayed in real-time mode.

    7 Password protection

    Three-level password protection system (power-on password,

    parameter correction password and parameter setting password)

    prevents unauthorized operations.

    8 Auto load-adjusting

    When the load varies, the steam input and circulating solution

    amount are automatically controled, making the chiller operating

    at the best status.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 8

  • 9

    9 Solution pump

    inverter control

    The solution pump is controlled by an inverter, ensuring

    optimum circulating amount of the solution and optimum liquid

    level in HTG.

    10 Interlock control

    system

    The chilled water pump, cooling water pump and cooling tower

    fan are automatically started or stopped according to the

    operating condition, thus realizing automatic control throughout

    the air conditioning system.

    11 Fault protection and alarm

    Once a fault occurs in the water system or the chiller itself, the

    degree of the fault is automatically identified, an alarm is given

    and corresponding protective measures are taken.

    12 Self-diagnosis Faults are automatically diagnosed. Their location, cause and

    remedy are suggested.

    13 Fault record Information about faults, such as occurring time and type, is

    stored automatically.

    14 Remote control (extended function)

    Control and monitoring of the chiller can be conducted from a

    remote place and or via a DCS/PLC system.

    15 Telephone networking (extended function)

    Various data can be transmitted via the telephone network. Our

    company can learn about the operation status of customers units

    at any place by telephone, thus achieving active after-sale

    service.

    16 Building interface (extended function)

    Reserved interface, used for linking with the building control

    center.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 9

  • 10

    3. Operation sequence of the AI (artificial intelligence) system

    Close air switch K1

    Close air switch K2

    Input power-on password

    Function selection menu

    Chiller function selection

    Operation mode selection

    Auxiliary function selection

    Coo

    ling

    Aut

    o ru

    n

    Man

    ual r

    un

    Tim

    ed o

    pera

    tion

    Rem

    ote

    cont

    rol

    Con

    trol p

    aram

    eter

    cor

    rect

    ion

    Con

    trol p

    aram

    eter

    setti

    ng

    Faul

    t man

    agem

    ent

    Syst

    em fu

    nctio

    n

    Ope

    ratio

    n re

    cord

    retri

    eval

    Auto run (cooling)

    Cooling + auto run

    Manual run (cooling)

    Cooling + manual run

    Timed operation (cooling)

    Cooling + timed operation

    Remote control (cooling)

    Cooling + remote control

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 10

  • 11

    4. Safety protection functions

    Note: A single-effect absorption chiller doesnt have the long-time low liquid level fault in

    HTG, high-pressure fault in HTG and false liquid level fault in HTG.

    Power supply phase loss or phase reversed

    Solution pump or inverter fault

    Long-time low liquid level fault in HTG

    High-pressure fault in HTG

    Low-temp fault of chilled water

    Stop of chilled water supply

    Chilled water flow sensor fault

    Stop of cooling water supply

    Cooling water flow sensor fault

    Refrigerant pump fault

    False liquid level fault in HTG

    High-temp fault in HTG

    Evaporation low-temp fault

    Cooling water high-temp fault

    Cooling water low-temp fault

    De-crystallizing tube high-temp fault

    Chilled water inlet-outlet temp difference overlarge fault

    Chilled water inlet temp sensor fault

    Chilled water outlet temp sensor fault

    Evaporating temp sensor fault

    Cooling water temp sensor fault

    HTG temp sensor fault

    De-crystallizing tube temp sensor fault

    Vacuum pump fault

    Chiller stops, with alarm

    If faults occur during auto/manual run, the chiller switches to dilution operation, with alarm

    This function doesnt affect the control of the chiller.

    If faults occur during auto run, the chiller switches to dilution operation. If faults occur during manual run, these functions dont affect the control of the chiller. In both cases, alarm is given

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 11

  • 12

    5. Main parameter settings

    AI system is an intelligent control system, which collects the real-time operating data about

    the customer system and the chiller itself and adjusts the steam input and the circulating

    amount of the solution based on the data. The default settings of the parameters listed below

    may be reset by users as required.

    Table 5-1

    S/N Parameter name Default setting Setting range

    1 Cooling water outlet temp 7C 620C

    2 Temp difference between cooling water

    inlet and outlet temp 5C 510C

    3 HTG temp(cooling) 160C (98C for

    singe-effect models)

    145~160C (90~101C for

    singe-effect models)

    4 Pressure of pressure controller 0.02MPa Change prohibited

    5 Inverter highest operating frequency 50Hz 40 50Hz (non-settable for

    certain models)

    6 Power-on password 1 09999

    7 Parameter setting password **** 09999

    8 Parameter correction password **** 09999

    Parameter setting procedure

    Input the power-on password and parameter setting password, enter the parameter

    setting menu and set the parameter.

    For safe operation purpose, parameters should be set by professional technicians!

    6. Grounding requirement

    To ensure safe and reliable operation of the chiller, the chiller is required to have a special

    ground pole with the grounding resistance not greater than 10. The grounding terminals of the chillers electrical devices should be securely connected to this pole. Without a special

    ground pole (or a neutral line), the chiller may be damaged and people be injured.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 12

  • 13

    Part 6 Installation of system

    1. Machine room

    Try to select a machine room which is close to the steam source and to where the

    chilled water is used.

    The machine room should have enough brightness and good ventilation with the relative humidity less than 85%. In case the chiller is installed outside the room, the

    electrical devices and measuring instruments should be protected from moisture, rain,

    sunshine, etc.

    Sufficient space should be reserved around the chiller for maintenance: 1m in the

    lengthwise direction, 0.2m above the chiller, 1.2m on the control cabinet side and

    0.5m on other sides. And on either end of the chiller, a tube-drawing apace, not less

    than the distance between the two tube sheets, should be kept so that the heat transfer

    tubes can be drawn out.

    The machine room should be equipped with necessary devices like electric outlets and water taps. And there should be drains around the chiller.

    2. Placement of chiller

    Since the LiBr absorption chiller runs stably

    with slight vibration, its foundation may be

    designed according to its static load (i.e. operating

    weight)

    After putting the chiller in place, calibrate the

    chiller horizontally with the help of the 4 basic

    holes in the two tube sheets. The error of the level

    degree should not be greater than 0.002. The level

    degree can be regulated through the cushion block

    located between the foundation and the support of

    the chiller and can be measured with a gradient or a

    transparent plastic connecting pipe.

    Basic holes

    Wat

    er-f

    illed

    pla

    stic

    pip

    e

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 13

  • 14

    3. Piping

    Flexible connectors and manometers should be mounted at the inlets/outlets of the chilled

    water and cooling water. If the dryness of the working steam is less than 0.90, a steam-water

    separator should be mounted. At the inlets of chilled and cooling water there should be

    strainers with 3-6mm meshes, or the cooling capacity may decrease and frozen tubes may

    occur. And at the inlet of the working steam, there should be a strainer with 60-80 meshes,

    otherwise failure in the electric valve may occur.

    The steam piping is suggested as below:

    In certain cases the steam supply cannot be cut off suddenly, for it may affect the

    production process or the system. In such cases, replace the motorized two-way valve with a

    three-way valve (as shown below).

    4. Steam condensate piping

    The pressure of the steam condensate usually stands at 0.05MPa. If the condensate cannot

    return to the boiler room by itself, install a condensate tank at the condensate exit and then

    Steam

    Steam piping diagram(for reference)

    Strainer(80-100 meshes)

    Strainer(80-100 meshes)

    Cut-off valve

    Cut-off valve

    Cut-off valve

    Pressure reducing

    valve

    Electric valve

    Pipe reducer

    HTG end enclosure

    Steam

    Cut-off valve

    Cut-off valve

    Cut-off valve

    Strainer(80-100 meshes)

    Strainer(80-100 meshes)

    Pressure reducing

    valveElectric valve

    Pipe reducer

    HTG end enclosure

    to cooling equipment when the chiller stops

    3-way steam valve piping diagram(for reference)

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 14

  • 15

    pump the condensate to the boiler room. The condensate tank should be lower than lowest

    place of HTG. The weight of all external pipes connected to the chiller must be carried by

    the chiller!

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 15

  • 16

    Part 7 Preparation and Operation

    1. Preparation for initial start

    Preparation of instruments and tools: Hand tools

    Absolute pressure gauge

    Digital multi-meter Liquid-charging flexible pipe: diameter 1 inch25mmlength 6m.

    Densi-meter and mercury thermometer

    Check of jobsite piping Check the chilled/cooling water pipes according to the Piping system diagram

    Check if the inlets/outlets of the water system, water pumps and cooling tower are

    misconnected;

    Check if there is a discharge valve on each pipeline;

    Check if there is leakage at flanged connections;

    Make sure the chilled/cooling water flow rate meets the operation requirement and check the pressure borne by the chiller water system;

    A hand-operated cut-off valve and pressure reducing valve should be installed on the

    steam pipe;

    Check if a drain valve has been installed at the lowest site of both the steam pipe and

    the steam condensate pipe.

    Check of purge system Check if the vacuum pump oil brand number is correct;

    Check if the vacuum pump oil has been emulsified and the oil level is in the middle of

    the sight glass;

    Check the ultimate vacuum of the vacuum pump: close the main purge valve F1, start

    the vacuum pump and pump the oil trap only. Connect a McLeod vacuum gauge to the

    ultimate vacuum purge valve F2, start the vacuum pump and let it run for 3-5 minutes.

    If the reading on the McLeod vacuum gauge is consistent with the ultimate vacuum of

    the pump, that indicates the vacuum pump is excellent in performance.

    Check of wiring All system equipment is required to be checked.

    Check if the wiring complies with the Wiring diagram and meets the requirement.

    Check if the power supply for the cooling tower fan/chilled water pump/cooling water pump is correctly connected.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 16

  • 17

    Check if the voltage and frequency of the power supply match the motor nameplate parameters and meet the requirements of the control system.

    Check the permitted overload capacity and fuse size of each motor.

    Check if all electrical devices have been earthed as required. During operation, check if all motors lubrication, power supply and rotation direction

    are normal.

    Do not start the solution pump or refrigerant pump before the LiBr solution is fully

    charged into the chiller. Otherwise, the pump will be seriously damaged. Charging of LiBr solution

    The LiBr solution is generally a 50% mixed solution, in which 0.2% lithium chromate (or

    0.015% lithium molybdate) has been added as a corrosion inhibitor. The pH value of the

    solution has been adjusted within the range of 9~10.5. It is recommended to recheck the

    solution and take a sample and reserve the sample prior to the charging.

    Charging principle The solution is sucked into the absorber by the high vacuum in the chiller sucks via the

    sampling valve (F5) located at the solution pump outlet.

    Attention points a) Do not start the solution pump while charging the solution.

    b) Do not charge the solution directly from a small container into the chiller. That may

    bring air into the chiller.

    c) When the charging begins, start the vacuum pump to

    remove non-condensable gases out of the chiller.

    Charging method Prepare a solution container (made of corrosion

    resistant material), pour the solution in it(if solution is turbid

    or dirty, filter it first), and connect as the figure on the right.

    Fill the flexible pipe with solution to keep air out. Connect

    one end of the pipe with the sampling valve, and dip the other end in the container. Notice:

    keep the flexible pipe filled with water to prevent air entering; and the end dipped in the

    container should be at least 30mm away from the bottom of the container lest the deposits and

    impurities flow into the chiller with the solution.

    Charging amount Refer to the nominal parameter table for the charging amount of the solution. Whether

    Flexible pipe

    Solution container

    Sampling valve

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 17

  • 18

    the amount is appropriate can be judged by observing if it meets the circulating requirement of

    the chiller under the standard operation condition.

    2. Operation of the chiller

    Manual run screen

    Manual run procedure

    a) Start the chilled water pump and open its discharge valve, and regulate the flow rate to

    the rated valve;

    b) Start the cooling water pump and open its discharge valve, and regulate the flow rate to

    the rated value;

    c) Open the hand-operated steam valve and condensate drain valve, drain the condensate

    water in the steam supply pipe, and regulated the steam pressure to the rated value.

    d) Turn on the power switch in the control cabinet. The start-up menu is displayed on the

    touch screen. Press Power-on password key, input the pre-set power-on password,

    press Confirmation and then enter the Manual run menu following the prompts on

    the screen;

    e) Press Chilled water pump, Cooling water pump, Solution pump and Refrigerant

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 18

  • 19

    pump keys(highlighted after pressed) in sequence. Start the electric valve slowly. The

    chiller enters normal operation. When the screen indicates that the cooling water inlet

    temperature is equal to or greater than 30, start the cooling tower.

    f) Stop procedure: Close all valves first. The chiller starts the dilution operation. Wait until

    the temperature of the solution at the HTG exit drops below 80, stop the Solution

    pump, Refrigerant pump, Cooling water pump and Chilled water pump in

    sequence. Press Back key in the upper right corner of the screen returning to the

    start-up menu, then switch off the control power supply.

    Function of other touch keys

    Vacuum pumpUsed to start the vacuum pump

    Alarm silenceUsed to eliminate the fault warning sound temporarily

    Solution pump frequencyUsed to display the frequency of the current voltage

    HTG levelUsed to display the HTG liquid level, which can be regulated by changing

    the frequency of the inverter

    Right part of screen: Used to display main operating parameters

    Manual run of the chiller is only for commissioning and must be performed by

    professional personnel!

    To prevent the heat transfer tubes in the evaporator from being frozen due to stop of

    cooling water flow, observe the following items:

    Confirm that the target flow switch works normally before starting the chiller.

    When starting the chiller, start the chilled water pump (and confirm it has run)

    first and then the cooling water pump.

    After dilution and shutdown, stop the cooling water pump first and then the

    chilled water pump.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 19

  • 20

    Auto run screen

    Auto run procedure

    a) Enter the function selection menu and select Auto run.

    b) Press the Auto start key. The chilled water pump, cooling water pump, solution pump,

    electric valve and refrigerant pump are started in sequence. If any fault occurs, the

    chiller begins dilution operation and gives an alarm and the screen automatically

    switches to the fault management menu, which provides information about the fault and

    its treatment.

    c) Stop procedure: Press the Auto stop key and the chiller begins the dilution operation.

    Once the HTG temperature drops to the pre-set value, the chiller stops automatically.

    Then stop the cooling water pump, and two minutes later stop the chilled water pump

    and turn off the power supply to the chillerwhen the chilled water pump and cooling

    water pump are not interlocked with the chiller.

    Note: Solution pump, Refrigerant pump, Electric valve, Chilled water pump, Cooling

    water pump, and Cooling tower are used only for display. They cannot be operated.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 20

  • 21

    The frequency of the solution pump has been set in the factory, no people other than

    professional technicians is permitted to modify it!

    Close the steam cut-off valve first after the chiller is stopped (whether automatically

    or manually), otherwise hazardous faults such as crystallization in HTG or high pressure

    may occur.

    5. Purging

    In cooling cycle

    In cooling operation, purge valves 1 and 2 are closed.

    When the liquid level in the gas tank falls below the

    sight glass or the control cabinet operation panel requires,

    the vacuum pump should be started for purging. Purging

    steps are:

    1) Start the vacuum pump and keep it running for about half a minute;

    2) Open valve 1 and pump for at least three minutes;

    3) Open valve 2 and keep pumping until the cooling effect recovers;

    4) Close valve 1 first and then valve 2;

    5) Let the vacuum pump run for another half an hour, and then stop it.

    Attention: If valve 2 is not closed, non-condensable gases in the gas tank will return to the inside of the chiller through it.

    In shutdown period During a long period of shutdown, the purging should be performed once every month,

    each time for about one hour. The method is: start the vacuum pump and open valves 1 and 2.

    After purging, close valve 1 first and then stop the vacuum pump and close valve 2, otherwise

    the vacuum pump oil will be pumped into the chiller and degrade the cooling performance

    greatly.

    The chiller must be kept highly airtight and the air in it must be pumped out timely,

    1

    2

    Purge valve 1

    Purge valve 2

    Sight glass

    Vacuum pump

    Gas

    takn

    Solu

    tion

    in

    Oil trap

    Ejector

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 21

  • 22

    otherwise the life of the chiller will be shortened and the energy consumption increased dramatically!

    Replacement of diaphragms

    1) The diaphragms of valves 1 and 2 must be replaced every 3 years.

    2) Other valve diaphragms must be replaced every 5 years.

    Maintenance of the vacuum pump

    1) If a water layer emerges at the bottom of the vacuum pump oil, drain it out slowly. During the pumping of the vacuum pump, the gas ballast valve on it should be left

    open so that the water vapor can be removed out of the pump.

    2) If the vacuum pump oil is emulsified and turns white, replace it.

    Secondary seal for the vacuum valve

    Sealing rings wear out due to the rotation of the valve shaft, which in turn will cause gas

    leakage; therefore, great attention should be paid to the secondary seal.

    1) Remove the oil stains, scrap iron and sealant residues on the valve cap screw thread,

    valve body screw thread and O-rings with a steel brush;

    2) Spray Letai detergent on them, brush again and dry them;

    3) Spread a layer of Letai 567 sealant for pipe thread;

    4) Tighten the valve cap with a spanner to secure the seal.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 22

  • 23

    Part 8 Operation Record and Management 1. Operation record form

    The operation record is an important document to track the operation status of the chiller.

    It is usually recorded at an interval of 1 to 2 hours, which may be longer or shorter as

    required.

    Operation Record Form for Steam-fired Chillers Model or S/N Date Recorder

    Recording items Time

    Unit

    Evaporator Chilled water

    inlet temp

    Chilled water

    outlet temp

    Evaporation

    temp

    Chilled water

    inlet pressure

    MPa

    Chilled water

    outlet pressure

    MPa

    Chilled water

    flowrate

    m3/h

    HTG Steam

    consumption

    Kg/h

    Steam temp

    Steam pressure kPa

    Solution temp at

    HTG outlet

    Condensate

    discharge temp

    HTHE Intermediate

    solution outlet

    temp

    Diluted solution

    outlet temp

    LTHE Diluted solution

    inlet temp

    Concentrated

    solution inlet

    temp

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 23

  • 24

    Concentrated

    solution outlet

    temp

    Absorber Cooling water

    inlet temp

    Cooling water

    outlet temp

    Cooling water

    inlet pressure

    MPa

    Cooling water

    flowrate

    m3/h

    Condenser Cooling water

    outlet temp

    Cooling water

    outlet pressure

    MPa

    Note

    2. Operation management

    Management of solution In the initial stage of the operation of the chiller, the content of lithium chromate (or

    lithium molybdate) in the solution would decrease due to the generation of the protective film.

    And if there is rust or air in the chiller, even an extremely little amount, will lead to chemical

    reactions, which in turn will raise the pH value of the solution and even accelerate corrosion of

    the chiller. Therefore, the solution should be sampled to check the content of lithium chromate

    (or lithium molybdate), iron ion, copper ion, chlorine ion, etc. as well as the pH value of the

    solution after the chiller has run for a period of time.

    If the content of lithium chromate (or lithium molybdate) drops below 0.1% (or 0.012%),

    add some more in time. And the pH value should be kept between 9.0 and 10.5. If its too high,

    adjust it with hydro bromic acid (HBr); if its too low, adjust it with lithium hydroxide ( LiOH).

    Management of refrigerant water If the specific weight of the refrigerant water is greater than 1.0 during the running of the

    chiler, which means the refrigerant water contains lithium bromide. This is also called

    Polluted refrigerant water, which will lower the cooling capacity. The refrigerant water is

    usually regarded normal when its specific weight is less than 1.02, otherwise it must be

    regenerated and the cause of the pollution be analyzed to prevent its recurrence.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 24

  • 25

    Regeneration of the refrigerant water is as follows:

    1) Start the refrigerant pump and open the regeneration valve F3, pumping the

    refrigerant water in the evaporator into the absorber via a by-pass.

    2) Close F3 and stop the refrigerant pump; 3) When the solution has been concentrated and the refrigerant water has condensed on

    the evaporator to a certain amount, restart the refrigerant pump.

    Replenishment of octanol

    Octanol is insoluble in the solution. After the chiller has run for some time, part of octanol

    will float on the surface of the refrigerant water and the solution. And since octanol is a volatile

    substance, the running of the vacuum pump will bring some octanol out of the chiller, thus

    reducing its circulating amount and affecting the chillers performance. Therefore, octanol

    should be replenished as required.

    The method for charging octanol is similar to that for the solution. Remember to start the

    vacuum pump after the charging to remove the air that might leak into the chiller during the

    charging.

    Management of water quality

    The performance and life span of the chiller depend largely upon the quality of the cooling

    water. Water of poor quality is easy to scale on the wall of heat transfer tubes, reducing the

    cooling capacity.

    The water used in the LiBr absorption chiller should comply with the requirements shown

    in Table 8-1. If the water is too hard, soften it before using it.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 25

  • 26

    Table 8-1 Water quality standard

    Item Unit

    Quality of cooling water Quality

    standard for

    recharged

    water

    Standard

    value

    Tendency

    Corrosion Scaling

    PH25 6.58.0 + + 6.58.0

    Conductivity(25 microhm/cm

  • 27

    Part 9 Troubleshooting 1. Crystallization

    During cooling cycle, when crystallization occurs in the concentrated solution in LTHE or

    pipes, the temperature of the automatic de-crystallizing tube will rise and an alarm will be

    given, while the temperature of the concentrated solution pipe leading to the absorber fall

    dramatically.

    Remedy Stop the cooling water pump and chilled water pump, and close the steam cut-off

    valve to 40%. Now the high-temperature concentrated solution coming out of LTG

    flows directly into the absorber via the de-crystallizing tube and heats the diluted

    solution in the absorber. The heated diluted solution then enters LTHE, heats the

    concentrated solution there and melts the crystals.

    For crystals in pipes, melt them by heating them directly with steam, high-temperature water or flames.

    2. Refrigerant water pollution In cooling operation, the phenomenon of LiBr solution mixing into the refrigerant water is

    referred to as refrigerant water pollution.

    Severe pollution will result in a great drop in chiller performance or even operation failure.

    The refrigerant water should be regenerated if its density exceeds 1.02.

    Regenerating method

    With the refrigerant pump running, open the refrigerant water by-pass valve, diverting the polluted refrigerant water in the evaporator to the absorber.

    Causes of refrigerant water pollution

    Circulating solution amount is too large and the liquid level in the generator is too high.

    At the beginning of the chiller operation, the pressure of the solution vapor rises too

    fast, causing the solution in the generator to boil too violently and enter the

    condenser.

    The cooling water temperature is too low.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 27

  • 28

    3. Common faults and remedies (see Table 9-1)

    Table 9-1

    S/N Faults Possible causes Remedies

    1 Chiller cant be started

    aNo power is connected to the control cabinet

    bFuse in the control cabinet blows

    aCheck the main power supply and control switch

    bCheck the grounding wiring or short circuits, and replace the fuse

    2

    Cooling capacity lower than the set point

    a Poor sealing causes air leakage into the chiller

    b Refrigerant water is polluted

    c Circulating amount of the diluted solution is too small

    d Vacuum pump is poor in pumping performance

    e Spraying device is blocked f Scaling or clogging of heat

    transfer tubes g Cooling water temp is too

    high h Cooling water flow rate is

    too small i Vapor pressure is too low

    a Start the vacuum pump to pump air out and eliminate the leakage

    b Examine the density of refrigerant water. If it is over 1.02, regenerate it

    c Increase the frequency of the inverter

    d Test the vacuum pumps performance and repair the fault

    e Clean or replace spraying device f Eliminate scales and impurities on

    the inside wall of heat transfer tubes g Regulate the cooling tower and

    check the cooling water system h Raise the cooling water flow rate i Increase the vapor pressure

    3 Chilled water outlet temp is too high

    a External load is greater than the chillers cooling capacity

    b Cooling water flow rate is too small or its temp is too high

    c Set point of the chilled water is too high

    d The amount of octanol decreases

    e There are non-condensable gases in the chiller

    a Decrease external load b Increase the cooling water flow rate

    or decrease its temp c Reset the set point of the chilled

    water temp d Add octanol e Start the vacuum pump to pump out

    non-condensable gases

    4 Refrigerant water is polluted

    a Circulating amount of the solution sent to HTG is too large and liquid level in HTG is too high

    b Cooling water temp is too low and cooling water amount is too large

    a Regulate the frequency of the inverter

    b Decrease the amount of the cooling water

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 28

  • 29

    5 Crystallization in LTHE

    a Cooling water temp is too low

    b Circulating amount of the solution sent to HTG is too small

    a Increase the cooling water temp and decrease its flow rate moderately

    b Increase the circulating amount of the solution which is sent to HTG

    6 Crystallization of solution after shutdown

    a Dilution time is too short b Chillers ambient temp is

    too low

    a Increase the dilution time, guaranteeing full mixture of the solution

    b Add refrigerant water to dilute the solution, preventing it from crystalizing

    7 Cavitation erosion in solution pump

    a Insufficient solution amount

    b Crystallization of solution

    a Add solution b Melt crystals

    8 Purge system runs abnormally

    Incorrect operation of purge valves

    Check if the valves are correctly opened or closed, or tightened.

    9 Vacuum degree drops Leakage

    Check to see if valves or instruments connected directly to atmosphere are loose, or valve diaphragms become aged

    4. Treatment for action of safety devices

    During operating, the chiller will stop automatically and give an alarm if any failure

    occurs and the safety protection level has been reached. Remedies for the action of safety

    devices are listed in Table 9-2 below.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 29

  • 30

    Table 9-2 Remedies for action of safety devices

    S/N Location of action Remedies

    1 Cooling/chilled water flow switch operates

    a Check to see if the operation of water pumps is normal. b Check to see if pressure is normal and if air enters water system.

    Discharge air if air enters water system. c Check to see if valves are open and open them wider. d Check to see if filters are clogged.

    2 Cooling/refrigerant water temp over load alarm

    a Check to see if external load is lower than the cooling capacity adjusting range.

    b Check to see if cooling water temperature is too low.

    3 HTG pressure switch operates

    a Check the airtightness of the chiller, seeing if the purge system operates normally, and if there is any leakage.

    b Check to see if vapor pressure is too high. c Check to see if the cooling water flow rate is too small. d Check to see if scaling occurs in the absorber/condenser heat

    transfer tubes.

    4 HTG low liquid level alarm

    a Check to see if the level control electrode is sensitive. b Check to see if the solution pump runs normally. c Check to see if the liquid level is normal.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 30

  • 31

    Part 10 Maintenance 1. Maintenance during short-term shutdown

    During short-term shutdown(less than two weeks), the chiller should be maintained as

    follows:

    Keep a high vacuum degree in the chiller. If air enters the chiller, pump it out timely.

    Track the temperature change to prevent crystallization.

    During dilution before shutdown, transfer all refrigerant water in the evaporator to the absorber via the by-pass valve, ensuring full dilution of the solution.

    When doing repairs during shutdown period, such as replacing the canned pump or

    valves, avoid exposing the inside of the chiller to the atmosphere for a long time. So

    conduct the repair quickly, otherwise the chiller may be eroded.

    2. Maintenance during long-term shutdown Great attention should be paid to the long-term shutdown maintenance in order to ensure

    the chillers high performance and long life. The maintenance work includes:

    Preventing air leaking into the chiller and causing corrosion Vacuum method: Start the vacuum pump regularly (every 15-30 days) to pump out

    air which has leaked into the chiller.

    Nitrogen method: Charge high-purity nitrogen gas (99.999%) into the chiller until the pressure reaches 0.02MPa. Before charging, purge the valve and rubber

    tube with the nitrogen gas to prevent air entering the chiller.

    For both methods, the diaphragm valves should be sealed lest it should be opened by accident!

    Preventing crystallization

    During the dilution operation prior to shutdown, transfer all refrigerant water in the evaporator to the absorber via the by-pass valve, allowing solution coming

    from different parts of the chiller to mix fully and preventing crystallization.

    Cleaning heat transfer tubes and water system Open the water chambers of the absorber, condenser and evaporator, check heat

    transfer tubes, and remove residues in water chambers and heat transfer tubes.

    If there is scale in the tubes, chemical methods may be used to remove it. The 81-A acidic cleaning agent produced by Shanghai No.2 Reagent Factory is

    recommended. The cleaning process is as follows: make the cleaning agent into a

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 31

  • 32

    5-10% solution, heat it to 50-60 and circulate it through the transfer tubes. It

    normally takes about 18 hours to eliminate 1mm-thick scale. After the cleaning,

    drain the cleaning agent, charge 0.5-1% solution of trisodium phosphate (Na3PO4)

    or sodium carbonate (Na2CO3) into the tubes and circulate it to neutralize the

    acidic solution left in the tubes.

    Preventing oxygen corrosion and icing

    After cleaning up heat transfer tubes and water system,

    If icing is impossible, the water system should be fully charged with water to

    prevent oxygen corrosion in water chambers of the absorber, condenser and

    evaporator.

    If icing is possible, drain heat transfer tubes and water system and dry them to

    avoid frozen tubes and reduces oxygen corrosion.

    Check and replace failed parts Such as the graphite bearing of the canned pump, valve sealing rings,

    diaphragms of diaphragm valves, auto-control components and spring for the

    rotary vanes of the vacuum pump.

    While replacing the parts of the vacuum system, avoid exposing the inside of the

    chiller to the atmosphere for a long time.

    All electrical equipment and instruments should be protected against moisture.

    3. Treatment of LiBr solution

    If LiBr solution becomes turbid and turns dark red, black or green, it must be treated.

    There are two methods to treat the solution

    Deposition method: put the LiBr solution in a large container, after a certain period

    of time, the deposits will settle on the bottom of the container and the solution will

    become clear again. Extract the upper clean solution and reuse it.

    Filtering method: use a strainer made of propylene, with its meshes being 3mm in

    diameter, to filter the solution. While filtering solution containing deposits, it is

    recommended to filter it after it has been deposited for 1 or 2 days. Do not use a

    strainer made of cotton fiber.

    Then measure the content of lithium chromate (or lithium molybdate) and pH value, and

    adjust them to the specified values.

    4Regular check The chiller should be checked periodically, during both operation period and shutdown

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 32

  • 33

    period, to maintain its good performance and safety running. The check items are listed in the

    following table.

    Table 10-1 Regular check items

    Items Check points Check cycle

    daily weekly monthly yearly

    Vacuum pump a) Pollution and emulsification of oil b) Performance of vacuum pump c) Insulation of motor

    Solution pump & refrigerant

    pump

    a) Operating status of the chiller. Check to see If there is any unusual noise

    b) If power supply to motor exceeds the normal value

    c) Insulation of motor d) Dismantlement and check of vanes; cleaning

    of return pipes

    Every about 5 years

    e) Replacement of graphite bearing Every 5 years

    LiBr solution

    a) Concentration b) Cleanness degree c) pH value and lithium chromate(or lithium

    molybdate) concentration

    Refrigerant water

    Check its pollution condition and decide whether to regenerate it

    Heat transfer tubes

    a) Corrosion of inner wall b) Scaling on inner wall

    Sealing of chiller

    a) Change of temperature difference between diluted solution and cooling water; change of cooling effect

    b) Record of pressure changes during shutdown period

    Diaphragm valves and

    solution adjusting valves

    a) Sealing condition b) Replacement of diaphragms of valves 1 and 2 Every 3

    years c) Replacement of diaphragms of other

    diaphragm valves Every 5

    years

    d) Replacement of the O-ring of the changeover valve

    Every 5 years

    Pressure gauge and control

    cabinet

    a) Calibration of indication b) Insulation of electrical devices c) Reliability of switches for electrical devices

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 33

  • 34

    Operation Rules

    (Double-effect steam-fired LiBr absorption chiller)

    1. Machine room management rule (1) The operators must observe this rule to ensure safe running of the chiller.

    (2) There should be strict management regulation and shift regulation for the machine room.

    (3) There should be personnel on duty in the machine room during running of the chiller.

    (4) No one other than qualified persons is allowed to operate the chiller alone.

    (5) No one other than the operators is allowed to enter the machine room without permission.

    (6) No one other than machine room staff is allowed to open or close any valve or other

    components of the chiller, otherwise accident may occur.

    (7) The machine room should have excellent ventilation and the relative humidity in it should

    be controlled below 75%.

    (8) The power supply in the machine room should be normal with stable voltage.

    (9) The machine room should have sufficient high-purity (99.999%) nitrogen gas and

    common tools, materials and spare parts which are necessary for the maintenance of the

    chiller and system.

    2. Safe operation rule (1) It is prohibited to change safety protection parameters. For example, the set point of the

    HTG temperature (cooling) is 160.

    (2) It is prohibited to adjust safety devices. For example, the set point of the pressure

    controller is 0.02MPa.

    (3) It is prohibited to start the chiller if there is any abnormality with safety protection

    functions.

    (4) It is prohibited to start the chiller if there is any abnormality with the target flow regulator

    for chilled water.

    (5) It is prohibited to start the chiller if there is any leakage.

    (6) It is prohibited to start the cooling water pump first and then start the chilled water pump.

    (7) It is prohibited to stop the chilled water pump first and then stop the cooling water pump.

    When the cooling water temperature is low (25), the chilled water pump must be

    stopped two to five minutes after the cooling water pump has been stopped.

    (8) It is prohibited to start the chiller if the chiller is obviously vibrated by the piping system.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 34

  • 35

    3. Chiller operation rule Check the following items each time before starting the chiller

    (1) Confirm that the valves at the chilled/cooling water inlet/outlet are open.

    (2) Confirm that the safety protection parameters are properly set and select Auto

    operation mode on the touch screen.

    (3) Safety devices should work normally, particularly when the flow rate of chilled or

    cooling water is lower than the specified value, an alarm can be given, the working

    steam be cut off, and the chiller be stopped automatically.

    Start sequence

    (1) Start the chilled water pump first, observe its inlet-outlet pressure difference, and

    confirm that the water flow rate meets the operation requirement.

    (2) Start the cooling water pump.

    (3) Open the by-pass valve for the vapor condensate, and close it after the condensate

    water in the pipe has been drain. Then open the vapor cut-off valve.

    (4) Press the Auto key.

    (5) Start the cooling tower fan when the cooling water inlet temperature reaches 30 (if

    the system adopts interlock control, the cooling tower fan will start automatically).

    Stop sequence

    (1) Press the Stop key and manually close the vapor cut-off valve.

    (2) Switch off the power after the automatic dilution process ends.

    (3) Stop the cooling tower fan and cooling water pump.

    (4) Finally, stop the chilled water pump.

    Operation monitoring

    (1) Make detailed operation records which are used for the analysis of the chiller

    operation condition.

    (2) Monitor the liquid level in HTG and the temperature and pressure of the solution in

    HTG. The liquid level mustnt be too low, and the temperature and pressure mustnt

    be too high, otherwise the heat transfer tubes will be damaged.

    (3) Monitor the running of the canned pump. If its shell temperature exceeds 80, stop it

    immediately and troubleshoot the problem.

    (4) Check to see if the working steam pressure is within the specified range.

    (4) Shut off the working steam immediately in any of the following circumstances:

    Loss of chilled water flow or failure in the canned pump

    Serious air leakage Liquid level rises unexpectedly or disappears

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 35

  • 36

    Accidental power failure

    4. Emergency treatment rule

    When any significant fault occurs during the running of the chiller, the machine room staff

    must take corresponding measures as soon as possible.

    Copper tubes are frozen or damaged

    Symptom: Liquid level at various locations rises too greatly and the cooling effect

    disappears.

    Remedy:

    1) Stop the chilled water pump and close the valves at the chilled water inlet and outlet at once.

    2) Turn off the main switch in the control cabinet and stop the cooling water pump.

    3) Drain the water from the water chamber. 4) Charge nitrogen gas into the chiller until the pressure reaches 0.02MPa.

    Discharge the solution into the solution tank for regeneration.

    Sudden power-off during operation 1) Close the vapor cut-off valve at once.

    2) Resume power supply and start the chiller as soon as possible lest the

    concentrated solution should crystallize.

    5. Maintenance rule

    Maintenance should be performed strictly in accordance with the Operation Instruction.

    Maintenance should be performed by or under the direction of qualified personnel.

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 36

  • 37

    Appendix 1Saturated water vapor temperature & pressure table

    Temperature Pressure Temperature Pressure

    kgf/cm2 mmHg kgf/cm2 mmHg

    1 0.006697 4.93 66 0.2666 196.2

    2 0.007194 5.29 68 0.2912 214.3

    4 0.008289 6.10 70 0.3178 233.8

    6 0.009530 7.01 72 0.3463 254.7

    8 0.01932 8.04 74 0.3769 277.3

    10 0.0125 9.2 76 0.4098 301.5

    12 0.014292 10.5 78 0.4451 327.4

    14 0.01629 12 80 0.4829 355.3

    16 0.018529 13.6 82 0.5234 385

    18 0.021034 15.5 84 0.5667 416.9

    20 0.02383 17.5 86 0.6129 450.9

    22 0.026948 19.8 88 0.6623 487.2

    24 0.030415 22.4 90 0.7149 525.9

    26 0.034266 25.2 92 0.7425 546.2

    28 0.038536 28.3 94 0.8306 611

    30 0.043261 31.8 96 0.8941 657.7

    32 0.04848 35.7 98 0.9616 707.3

    34 0.05424 39.9 100 1.033 760

    36 0.06058 44.6 102 1.087 799

    38 0.06756 49.7 104 1.166 858.7

    40 0.07522 55.3 106 1.250 919.6

    42 0.08362 61.5 108 1.339 985.1

    44 0.09281 68.3 110 1.432 1053

    46 0.1028 75.7 112 1.531 1126

    48 0.1138 83.7 114 1.636 1026

    50 0.1258 92.5 116 1.746 1284

    52 0.1388 102.1 118 1.862 1370

    54 0.1530 112.5 120 1.98 1456

    56 0.1683 123.9 125 2.366 1740

    58 0.1850 136.1 130 2.754 2026

    60 0.2031 149.4 135 3.192 2348

    62 0.2227 163.8 140 3.684 2710

    64 0.2438 179.4 145 4.236 3116

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 37

  • 38

    Appendix 2System diagram

    Chilled water system Cooling water system Steam system

    LoadExpansion water tank

    Cooling tower

    Pressure reducing valve

    Working steam in

    Condensate out

    Check valve Steam trap Electric valveCut-off valve

    Filter Flexible connectorThermo-meter

    Pressure gauge

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 38

  • 39

    Appendix 3Solubility curve of LiBr solution

    t

    100.0

    75.0

    50.0

    25.0

    0.0

    -25.0

    -50.050.0 55.0 60.0 65.0 70.0 50.0

    LiBr %

    Crystallization temperature curve of LiBr solution

    (smoothed values) Horizontal axis: LiBr %

    Vertical axis: Crystallization temperature

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 39

  • 40

    Appendix 4Users water system linkage diagram

    3

    : 1AC250V,5A

    ()

    Q131 Q132 Q141 Q142 Q152Q151

    Control cabinet for Hope Deepblue steam-fired absorption chiller

    Chilled water pump run command

    Cooling water pump run command

    Cooling tower fan run command

    Note: 1. The capacity of the output relays for the linkage terminals of above

    water pumps is AC 250V, 5A (resistance load). 2. Q131, Q132, Q141, Q142, Q151 and Q152 are code numbers for wires

    in the control cabinet. Please pay attention not to misconnect them. 3. While running the unit, make sure the chilled water pump and cooling

    water pump are in linkage control.

    Non-voltage output

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 40

  • 41

    Appendix 5Control cabinet I/O terminals

    T3A

    PE

    V4

    04

    PEL1

    NNL2

    0102

    03

    V2U2

    L3W2

    U4

    0506

    0807

    09

    15

    W4NN

    1211

    1013

    14

    A07

    A03

    NN

    1816

    1719

    20

    T0A

    L3NN

    PEL1

    L2U2

    V2U4

    W2V4

    A131

    VPVP

    E211

    E22

    A142

    A141

    A132

    A152

    A151

    W4NN

    NNA07

    A03

    PE

    T0BT0CT1AT1B

    T2B

    T2A

    T1C

    T2C

    A132

    VPE21

    VPA131

    E22

    A142

    A151

    A141

    T0A

    A152

    T1C

    T1A

    T0C

    T0B

    T1B

    T2B

    T2A

    T3A

    T2C

    YW4

    32

    VP

    26

    W5U5

    V5A172THR

    2221

    2325

    24

    E241

    YW1

    YW3

    YW2

    2927

    2830

    31

    E07

    YW5

    VP

    33

    YW5

    VP

    V5U5

    W5THR

    A172

    YW2

    E241

    YW1

    YW3YW4

    T3C

    T3B

    T5B

    T5A

    T5C

    E07

    VP

    T3C

    T3B

    T5B

    T5A

    T5C

    4041

    4342

    4445

    4746

    4853

    4951

    5052

    5554

    6157

    5659

    5860

    6362

    NN

    3839

    NNA11

    NNA12

    NNA11

    A12

    NN

    T4A

    T4BT4C

    T4A

    T4C

    T4B

    E21

    JXP

    JXP

    3435

    3637

    HTG

    tem

    p C

    oolin

    g w

    ater

    in

    let t

    emp

    Evap

    orat

    ion

    tem

    p C

    hille

    d w

    ater

    in

    let t

    emp

    Chi

    lled

    wat

    er

    outle

    t tem

    p So

    leno

    id

    valv

    e se

    t Va

    cuum

    pu

    mp

    Ref

    riger

    ant

    pum

    p th

    erm

    al

    prot

    ectio

    n

    Ref

    riger

    ant

    pum

    p

    Pow

    er su

    pply

    to

    cont

    rol c

    abin

    et

    Exte

    rnal

    ac

    oust

    oopt

    ic

    war

    ning

    Coo

    ling

    tow

    er fa

    n C

    oolin

    g w

    ater

    pu

    mp

    Chi

    lled

    wat

    er

    pum

    p

    Liqu

    id le

    vel

    elec

    trode

    term

    inal

    So

    lutio

    n pu

    mp

    term

    inal

    H

    TG

    high

    pr

    essu

    re

    faul

    t

    Coo

    ling

    wat

    er

    cut-o

    ff

    Chi

    lled

    wat

    er

    cut-o

    ff

    Dec

    ryst

    alliz

    ing

    tube

    tem

    p

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 41

  • 42

    Appendix 6Electrical principle diagram

    Electrical Principle Diagram

    Thermal Technologies Europe AB | www.thermatec.se | [email protected] p. 42