2016 ILLINOIS EDITION FOR ANHYDROUS AMMONIA (NH3) 8 IL Admin Code 215 Ammonia Storage Tank Upgrade Compliance Guide Effective July 1 2016, the State of Illinois upgraded their NH3 storage requirements and put them into law. Some of these new laws are effective immediately and some have a due date as soon as 2020. Gas Equipment Company has all the necessary components and industry-leading experience to get your facilities up to standard, as well as making it the most efficient and SAFEST operation possible. We have included an illustration of an ammonia bulk plant with areas highlighted that may need to change to meet compliance (You should review all state and local requirements with your local authority having juris- diction). We also included: A numbered component cross reference chart linked to the new requirements on the illustration, parts detail pages, a nurse tank guide and a storage tank design guide on the last page. You can complete this guide to determine if any additional repairs or upgrades need to be made as well as meeting the new Illinois laws. Even though some of the deadlines are still a few years away, they will be here before you know it. This edition of GEC Solutions will help you prepare. For 80 years Gas Equipment Company has offered the best equipment avail- able from a select group of premier manufacturers. With branch warehouses throughout the Midwest, we provide same day service and our nationwide warehouses are all linked, offering you immediate prod- uct availability. Most importantly, our staff knowledge and expe- rience is unmatched in the industry. We offer a free inspection of your facilities and equipment. Call us today to schedule your inspection. For Summary Compliance Information visit www.ifca.com and click on “2016_new_nh3_rules_compliance_guide.pdf” Our field repre- senta- tives can help you understand all of your compli- ance options. We offer FREE on-site facility inspections and evaluations. INSIDE • 8 IL Admin Code 215 Ammonia Storage Tank Upgrade Compliance NEW Regulations • Sample Compliance NH3 Storage Layout • Base Engineering WIRE- LESS Emergency Shutdown System • NH3 Storage Equipment • NH3 Nurse Tank Equipment • Bulk Storage Tank Design Guide & Appurtenance Information Form IMPORTANT SAFETY WARNING: Anhydrous Ammonia (NH3) is a hazardous substance and should be handled by experienced and trained personnel only using accepted governmental and industrial safety procedures. Installation, usage, and maintenance of all products must be in compliance with all manufacturer instructions as well as requirements and provisions of ANSI, CGA, and all applicable federal, state, provincial and local standards, codes, regulations, and laws. Failure to follow these codes, regulations and recommendations could result in hazardous installation, bodily injury and/or death. It is the installer’s/operator’s responsibility to confirm that installations are proper- ly designed and installed in accordance with all safety codes, regulations and manufacturer recommendations; including your local authority having jurisdiction. Inspection and maintenance on a periodic basis is essential. Installation and maintenance should be performed only by qualified & certified personnel. Be sure all instructions are read and understood before installation, operation and service.

Upload: others

Post on 16-Apr-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Storage Tank Upgrade Compliance Guide2016 ILLINOIS EDITION FOR ANHYDROUS AMMONIA (NH3) 8 IL Admin Code 215 Ammonia Storage Tank Upgrade Compliance Guide Effective July 1 2016, the

2 0 1 6 I L L I N O I S E D I T I O N F O R A N H Y D R O U S A M M O N I A ( N H 3 )

8 IL Admin Code 215 AmmoniaStorage Tank UpgradeCompliance GuideEffective July 1 2016, the State of Illinois upgraded their NH3 storagerequirements and put them into law. Some of these new laws areeffective immediately and some have a due date as soon as 2020.Gas Equipment Company has all the necessary components andindustry-leading experience to get your facilities up to standard, aswell as making it the most efficient and SAFEST operation possible.

We have included an illustration of an ammonia bulk plant with areashighlighted that may need to change to meet compliance (You shouldreview all state and local requirements with your local authority having juris-diction). We also included: A numbered component cross reference chart linked tothe new requirements on the illustration, parts detail pages, a nurse tank guide and astorage tank design guide on the last page. You can complete this guide to determineif any additional repairs or upgrades need to be made as well as meeting the newIllinois laws. Even though some of the deadlines are still a few years away, they willbe here before you know it. This edition of GEC Solutions will help you prepare.

For 80 years GasEquipment Companyhas offered the bestequipment avail-able from aselect group of premier manufacturers. With branch warehousesthroughout the Midwest, we provide same day service and ournationwide warehouses are all linked, offering you immediate prod-uct availability. Most importantly, our staff knowledge and expe-rience is unmatched in the industry. We offer a free inspectionof your facilities and equipment.

Call us today to schedule your inspection.

For Summary Compliance Informationvisit www.ifca.com and click on

“2016_new_nh3_rules_compliance_guide.pdf”Ourfieldrepre-senta-tives canhelp youunderstand allof your compli-ance options. Weoffer FREE on-sitefacility inspectionsand evaluations.

INSIDE• 8 IL Admin Code 215Ammonia Storage TankUpgrade ComplianceNEW Regulations

• Sample Compliance NH3Storage Layout

• Base Engineering WIRE-LESS EmergencyShutdown System

• NH3 Storage Equipment

• NH3 Nurse TankEquipment

• Bulk Storage TankDesign Guide &AppurtenanceInformation Form

IMPORTANT SAFETY WARNING: Anhydrous Ammonia (NH3) is a hazardous substance and should be handled by experienced andtrained personnel only using accepted governmental and industrial safety procedures. Installation, usage, and maintenance of all productsmust be in compliance with all manufacturer instructions as well as requirements and provisions of ANSI, CGA, and all applicable federal,state, provincial and local standards, codes, regulations, and laws. Failure to follow these codes, regulations and recommendations couldresult in hazardous installation, bodily injury and/or death. It is the installer’s/operator’s responsibility to confirm that installations are proper-ly designed and installed in accordance with all safety codes, regulations and manufacturer recommendations; including your local authorityhaving jurisdiction. Inspection and maintenance on a periodic basis is essential. Installation and maintenance should be performed only byqualified & certified personnel. Be sure all instructions are read and understood before installation, operation and service.

Page 2: Storage Tank Upgrade Compliance Guide2016 ILLINOIS EDITION FOR ANHYDROUS AMMONIA (NH3) 8 IL Admin Code 215 Ammonia Storage Tank Upgrade Compliance Guide Effective July 1 2016, the

2 SOLUTIONS.Illinois NH3 Edition.2016CALL GEC FOR A FREE ON-SITE INSPECTION

16

13

14

15

STORAGE TANK

2524

2019

22

1718

10' - 0"

28

2930

3233

8

11 12

31

34

910

12 3

47

56

27TRANSPORT UNLOADING

23

3"2"

11/4"11/4"

LIQUID/VAPOR TO RISER

LIQUID PUMP

21

26

HIGHLIGHTS OF THE NEW REGULATIONS8 IL Adm Code Part 215 215.55 (p) Container

pressure relief valves shallnot be used over 5 yearspast the manufactureddate. Compliance no laterthan December 31, 2020.

215.25 (a) & (f) If a storage tank is currentlyin use and does not have a U1-A form or abuild sheet or a legible data plate, it must betaken out of service by January 1, 2030.Railroad car tanks permanently mountedand used for storage shall be removed fromservice no later than December 1, 2025.

215.40 (g) (1) Each facility shallprovide the minimum protectionat each non-refrigerated storagetank opening on or beforeDecember 31, 2020 by:

A. The installation of an internalvalve with a manual shutoff valveorB. An approved excess flow valveor back check valve, a manualshutoff valve, and an approvedEmergency Shutoff Valve (ESV)located within 3 feet of the openingof the manual shutoff valve ESVs& internal valves shall be testedannually for the functions required.

215.65 (i) (3) Theminimum protectionfor all bypass linesshall consist of anexcess flow valveand a manual shutoffvalve provided thebypass is located atthe highest elevationof the storage tank.Any bypass line onthe underside of thetank shall have thesame type ofprotection as all otheroutlets on theunderside of the tank– see 215.40 (g) (1)

215.65 (v) & 215.65 (i) (2) Bulkheads shallprovide protection during transport unloading215.65 (v) 6 Caution signs at bulkheads required215.65 (i) (4) Installation of an in-line strainer ora strainer screen on the liquid unloading line atthe Bulkhead.

NH3 Bulk PlantContact GEC for acomprehensive RegOAnhydrous AmmoniaEquipment Catalog.

The illustrations in this guide are intended to inform a professional installer/system designer where valves are generallyinstalled on certain containers or applications. These illustrations are not intended for and must not be used for system design.

Page 3: Storage Tank Upgrade Compliance Guide2016 ILLINOIS EDITION FOR ANHYDROUS AMMONIA (NH3) 8 IL Admin Code 215 Ammonia Storage Tank Upgrade Compliance Guide Effective July 1 2016, the

3SOLUTIONS.Illinois NH3 Edition.2016 CALL GEC FOR A FREE ON-SITE INSPECTION

ITEM PART NUMBER DESCRIPTIONTANK TRIM

1 A3213 Rego 3" Internal Valve2 A7517AP Rego 3” Globe Valve3 A7513AP Rego 2” Globe Valve4 A3212 Rego 2" Internal Valve5 A7509BP Rego 1 1⁄4” Globe Valve6 A3209 Rego 1 1/4" Internal Valve7 SS8001U Rego Hydrostatic Relief Valve8 1750-00115 Thermometer9 C6342-11-108 Magnetel Gauge10 0022-29 Flange Mounting Adapter11 W0164 0-400 Pressure Gauge12 A2805C Rego Combo Valve13 A8564G OR A8574G Multiport relief valve14 RVS-3 Relief valve vent stack w/ cap15 A9095RS, A9091-18LX, A9091M Rotogage16 11011 3” Weather Caps

TRANSPORT UPLOADING17 A7513AP Rego 2” Globe Valve18 A7616 Rego 2” HD Swing Check

w/ Indicator

ITEM PART NUMBER DESCRIPTIONTRANSPORT UPLOADING (con’t.)

19 A7514AP RegO 2" Angle Globe Valve20 A5769H Rego 3-1⁄4” ACME x 2” Adapter21 A3194-90 Rego Steel Acme Cap22 A7509BP Rego 1-1⁄4” Globe Valve23 AA6010 w/ 6016RA Rego 1-1⁄4” ESV w/Pneumatic Actuator24 A7510BP Rego 1-1/4" Angle Globe Valve25 A5765F Rego 1-3⁄4” x 1-1⁄4” Adapter26 A1152C Acme Cap & Chain27 BH-10CV2-2CPLG or

BH-SCH80V2-2CPLG-12IN2 Port Vertical Bulk Head w/2”

3M Full CouplingsL3-32NH3X19FT DOT CERTIFIED NH3 SMART HOSE

LIQUID PUMP28 STYLEC-DI-300 3” Strainer29 LGLD3-VB or Z3500-103-10 Blackmer or Corken 3" V-Belt Pump Unit30 10HP-3PH-ED-E 10 HP Motor31 BV-200 or ZV200 Pump Bypass Valve

RISER32 A7513AP Rego 2” Globe Valve33 AA6016 w/ 6016RA Rego 2” ESV w/Pneumatic Actuator34 A7509BP Rego 1-1⁄4” Globe Valve

WIRELESS EMERGENCY SHUTDOWNRadio Remote Control (Part# ASK1F1WAX200A-AC)Designed specifically for Anhydrous Ammonia Plants, our Remote Emergency Shutdown system was developed to eliminate costly hard-wiringof manual emergency-shutdown switches. Any number of radio transmitter units can be installed within 1000 ft of a receiver control unit. Thesystem is designed to work in conjunction with existing or new plant safety equipment and is easily installed. The ASK system can also beordered to work in conjunction with our Truck Remote Units if required. Transmitter devices are low-voltage intrinsically safe units suitable foruse in Class 1, Div 2, Group “D” hazardous environments. Transmitter batteries will last three-four years and have a test feature and low bat-tery alarm. Remote stop-switch is rugged non-sparking cast aluminum and is fully sealed against extreme weather and temperature condi-tions. Receiver units are designed to easily interface and trip electrical, pneumatic, nitrogen, or mechanical plant shut-off equipment. Systemsare pretested and shipped with a detailed installation guide and schematics. A four-year full replacement warranty and 24/7 lifetime productsupport is included.

TECHNICAL SPECIFICATIONSFREQUENCY OF OPERATION . . .418-914 Mhz (433 Mhz Standard)METHOD OF TRANSMISSION . . .On/Off KeyedNORMAL OPERATING RANGE . .1000’ANTENNA TYPE . . . . . . . . . . . . . .1/2 Wave Rigid ExternalBATTERY REQUIREMENTS . . . . .2 AALOW BATTERY TEST . . . . . . . . . .IncludedRECEIVER POWER SUPPLY . . . .12/24 Volts DC or 120 Volts ACRECEIVER OUTPUT . . . . . . . . . . .10 Amp Dry Contact Relay, Pre-wired Plug-insCONSTRUCTION . . . . . . . . . . . . .Non-sparking Aluminum Weatherproof

Cylinder Dock/Load Out Riser Bobtail / Transport Bulkhead

Base Receiver(Located Outside Bulk Plant)

Base Wireless EmergencyShut Down Button(Located at Office)

Bulk StorageInternal Valves

Base Wireless Transmitter(Operator Hand Held)

Solenoid Valve(Base Actuated)

Shuttle Valve

EMERGENCYSHUT OFFVALVE SHUT DOWN

OPERATE

EMERGENCY STOP

BBABASBASEBASE Battery Test

Bat ter y T est

EMERGENCYSHUT OFFVALVE SHUT DOWN

OPERATE

EM ER GE N CYST O P

EMERGENCYSHUT OFFVALVE SHUT DOWN

OPERATE

BBABASBASEBASE

BBABASBASEBASE

P4-ECO-AIR-IVS 100Internal Valve System

1 2

17

4

8

43

3

55

61

3

4

8

PNEUMATICALLY OPERATED COMPONENTSINDEX PART NUMBER DESCRIPTION1 ASK1F1WAX200A-AC BASE Shut Down System

2 P4-ECO-AIR-IVS100 Internal Valve Actuator System,PLC Driven Compressor

3 6016-C(D) / 6016RA ESV Pneumatic Actuators4 125T-3-10-20 Toggle Switch5 A3213RA

Pneumatic Rotary Actuator6 A3212RA7 ESV-SIGN Small Emergency Shut-Off Sign8 ESV-SIGN-R Large Emergency Shut-Off Sign

Page 4: Storage Tank Upgrade Compliance Guide2016 ILLINOIS EDITION FOR ANHYDROUS AMMONIA (NH3) 8 IL Admin Code 215 Ammonia Storage Tank Upgrade Compliance Guide Effective July 1 2016, the

4 SOLUTIONS.Illinois NH3 Edition.2016CALL GEC FOR A FREE ON-SITE INSPECTION

STORAGE TANK COMPONENTS

Swing-Check ESVs for Bulk Plants

A6010

Threaded Internal Valve for Delivery Trucks,Transports, and Stationary Storage Tanks

A3209D A3209DT

A3211D

A3213D

A3212R

Relief Valves

Rough Rider®CM6339-11-72Magnetel®

6339-11Eliminator®P6293-R4400

Rotogauge®A9090

A7616 A7624A7794

Magnetel® Gauge for Storage Tanks, Eliminator® Gauge for Storage Tanks,and Rough Rider® for Trucks

AA8533MAAA8542

A8560A8570

Globe Valves

A7513APA7514AP

A7517FP

Pull-Away Valves

A2141A6L

A2141A6

Excess Flow Valves

A2137

A7537N4

A3500L4

A6016 A6024

Nozzles

A7793

A7914A

Nozzles

A3185A2805C

TSS31691008SS-400

Storage Misc.

A3217AR

Page 5: Storage Tank Upgrade Compliance Guide2016 ILLINOIS EDITION FOR ANHYDROUS AMMONIA (NH3) 8 IL Admin Code 215 Ammonia Storage Tank Upgrade Compliance Guide Effective July 1 2016, the

5SOLUTIONS.Illinois NH3 Edition.2016 CALL GEC FOR A FREE ON-SITE INSPECTION

GEC carries a complete line of components including pumps,compressors, valves, gauges hoses and actuator systems

LB361-LU

Part # DescriptionLGLD3E-VB-L/MTR 3” V-Belt Unit less motor10 HP TEFC 3PH 10 HP 3-phase TEFC motor

LB361-LULiquid transfer & vapor recoverycompressor unit with 15 HP3-phase TEFC motor

Blackmer Pump & Compressor

LGLD3E-VB-L/MTR

For protection of piping systems against truck pull-away with hose still connected. These bulkheads are made of 10” channel. Whenanchored in a concrete block (approximately 4 ft. x 4 ft. x 4 ft.) the bulkhead becomes a sound wall of protection against most pull-aways.

Part # DescriptionBH-10CV2-2CPLG 2-PORT VERTICAL BULKHEAD W/2" 3M FULL CPLGS*BH-10CV2-3CPLG 2-PORT VERTICAL BULKHEAD W/3" 3M FULL CPLGS*BH-10CV3-2CPLG 3-PORT VERTICAL BULKHEAD W/2" 3M FULL CPLGS*BH-10CV3-3CPLG 3-PORT VERTICAL BULKHEAD W/3" 3M FULL CPLGS*

Bulkhead StanchionsSafety Stanchions are designed for safe transfer of ammonia at the bobtail loading andtransport unloading points in a bulk plant. The stanchion is Rigid All-Steel construction.

BH-10CV2

ESV

Transport unloading Risersw/Hoses/Valves on STD 2 Hole BH

Both Liquid & Vapor Line

Flex-Union w/ Nipple

Flex Connector

BH-10CV2-2CPLG

Piping fromstorage

Grade

5/8" Rebar holes

65"

10"

12"

24" Minimum Depth*

16"

30"

*Check with local codes for proper above grade height.Bulkheads shall be anchored in reinforced concrete to preventdisplacement of the bulkhead. Reinforcement rod not supplied.

BH-10CV3-2CPLG

BH-10CV2-PKGPiping Kit installed. Bulkhead

not included.

BULKHEAD INSTALLATION RECOMMENDATIONS

TRANSFER EQUIPMENT

Part # Description QTYREL90-200X114 2"X1-1/4" REDUCING 90 DEGREE ELBOW 3000#

2EL90-200-2M FS ELBOW 90 DEGREE 2 INCH AT 2000#N-200X12 2" M.NPT X 12" EXTRA HEAVY SCH 80 BLACK PIPE NIPPLE 4

BH-10CV2-PKG includes fittings below:

NOTE: Piping kit for BH-10CV2-2CPLG, BH-10CV3-2CPLG bulkheads only.

* NOT APPROVED FOR USE IN TEXAS

Page 6: Storage Tank Upgrade Compliance Guide2016 ILLINOIS EDITION FOR ANHYDROUS AMMONIA (NH3) 8 IL Admin Code 215 Ammonia Storage Tank Upgrade Compliance Guide Effective July 1 2016, the

6 SOLUTIONS.Illinois NH3 Edition.2016CALL GEC FOR A FREE ON-SITE INSPECTION

NH3 Anhydrous Ammonia Transfer Hose AssembliesDesigned to handle NH3/Anhydrous Ammoniatransfer applications

Hose ID Working Pressure Burst Pressure Part #3/4”

350 1750

R300061500001” R32008140000

1 1/4” R320101400001 1/2” R320123200002” R32016330000

Century 2000 APPLICATION:• Low-permeation, anhydrousammonia transfer hose• Developed for use with nursetanks• Distinctly identified with a boldgreen stripe• Branded with removal date• Pro-rated six-year warranty foragricultural applications onlywhen coupled by an approveddistributer

TEMPERATURE RANGE:• -40°F to +180°F• -40°C to +82°C

BURST PRESSURE:• Minimum 5:1

MATERIAL TUBE:• Extruded , high-grade, low-per-meation EPDM

REINFORCEMENTS:• Multiple high-tensile textilebraids

MATERIAL COVER:• Black abrasion and weatherresistant EPDM• Cover is pin-pricked, which pro-motes better dissipation of theanhydrous ammonia andassists in resisting cover blisters

BRANDING:• Green longitudinal mylarstripe: CENTURY 2000 •

ANHYDROUS AMMONIA350 PSI• Embossed stripe: N2000– ANHYDROUS AMMONIA– 350 PSI MAX W.P. • * • FORAG. SVC. • REMOVE HOSEBEFORE ** • 10001

– *** • REFER TO INDUSTRYRECOMMENDATIONSINCL RMA/IP-11-2 FORCARE

* Year of Manufacture”** Year of Manufacture plus 6years*** Year-Month of Manufacture

STANDARD LENGTHS:• 100 feet, 30.5 meters

Smart-Hose assemblies are designed and engineered with avalve integrated in each end fitting. If the hose assembly expe-riences a catastrophic hose failure, the Smart-Hose SafetySystem is designed to instantaneously shut off the flow in bothdirections. Designed as a passive safety device, the Smart-Hose Safety System needs no human intervention to activate.

The Smart-Hose Safety System is integrated intoNH3/Anhydrous Ammonia transfer hose assemblies anddesigned to meet the most rugged applications found in theFertilizer Industry. All NH3/Anhydrous Ammonia transfer hose

assemblies are designed to meet DOT HM 225 Standards.

• Each hose is tested under water with dry air or nitrogen toworking and test pressure• Each hose is serial numbered• Each hose is shipped with a Test Certificate and OperatingBooklet• Each hose meets US Passive Shutoff Mandate forMC330/331 Transports• Each hose meets HM 225• 316 Stainless Steel fittings are designed for reuse on new hose

LL3 Design L

a

assemblies and All NH3 / Anydrous Ammonia Each hose is tested under water with dry air or nitrogen to working and test pressure Each hose is serial numbered Each hose is shipped with a Test Certificate and Operating Booklet Each hose meets US Passive Shutoff Mandate for MC330/331 Transports 316 Stainless Steel fittings are designed for reuse on new hose

H

LL3-B Design *Available in 2” ID

S a

All NH3 / Anydrous Ammonia Each hose is tested under water with dry air or nitrogen to working and test pressure Each hose is serial numbered Each hose is shipped with a Test Certificate and Operating Booklet Each hose meets US Passive Shutoff Mandate for MC330/331 Transports 316 Stainless Steel fittings are designed for reuse on new hose

H

Krug CompressorFor efficient transferof Anhydrous AmmoniaPart # Description

K20-3G 5-HP Engine, gasolinecarburetion, compressor

Part # Description

DG0000-V-ISCellular Ammonia Monitor for Class I,Division I, Group D Locations -Includes 5’ Harness Assy. w/Remote

Ready Sensor

DG0001-V-ISCellular Ammonia Monitor for Class I,Division I, Group D Locations -

Monitor Only

DG0001-VCellular Ammonia Monitor for Class I,Division 2, Group D Locations -

Includes 5’ Harness

DG0000-VCellular Ammonia Monitor for Class I,Division 2, Group D Locations -

Monitor Only

IS Cellular Ammonia Monitor

®

TRANSFER EQUIPMENT

LL1 Design

assemblies and All NH3 / Anydrous Ammonia Each hose is tested under water with dry air or nitrogen to working and test pressure Each hose is serial numbered Each hose is shipped with a Test Certificate and Operating Booklet Each hose meets US Passive Shutoff Mandate for MC330/331 Transports 316 Stainless Steel fittings are designed for reuse on new hose

H

TM-GSLRH10

BulkPart # Description

TM-GSLTH10 8” Taylor Dialw/10 ft. cable

TM-GSLRH10 8” Magnetel Dialw/10 ft. cable

TM-GSLSH10 4” Magnetel Dialw/10 ft. cable

TM-GSHB10A10 ft. harness assy.w/sensor F/LG 8” &4” dial replacement

DG0000-V

Page 7: Storage Tank Upgrade Compliance Guide2016 ILLINOIS EDITION FOR ANHYDROUS AMMONIA (NH3) 8 IL Admin Code 215 Ammonia Storage Tank Upgrade Compliance Guide Effective July 1 2016, the

7SOLUTIONS.Illinois NH3 Edition.2016 CALL GEC FOR A FREE ON-SITE INSPECTION

Pressure GaugeW0164

Safety Relief ValveAA3130UA250AA3130UA265

Vapor Bleeder ValveA7551P orA7550P

Hose End ValveA7797A orA7708L with A7575L4

Liquid Withdrawal ValveA8017D Series Fixed Liquid

Level GaugeTSS3169

Liquid Filler ValveA8016DP

Liquid Filler ValveA8016DP

Pressure GaugeW0164

Safety Relief ValveAA3130UA250/265

Liquid Withdrawal ValveA8017DH/DP Fixed Liquid

Level GaugeTSS3169

Vapor Return ValveA8016DP

Part # DescriptionA8017DP Liquid Withdrawal ValveA8016DP Liquid Fill Valve or Vapor Return ValveTSS3169 Vent valve, 1⁄4” SS, Teflon

AA313OUA250 3⁄4” Relief Valve (5 yr. replacement)

RegO Nurse Tank Valves

A8017DP AA313OUA250

TSS3169

A8016DP

Pressure GaugesPart # DescriptionW0160 0-60# Pressure GaugeW0164 400# Pressure Gauge

W0164

Part # DescriptionA6280-1-41 Sr. top mount gauge; 41” dia., 1” riser heightA6280-1-46 Sr. top mount gauge; 46” dia., 1” riser heightA6480-00012 N-Serv gauge; All stainless steel; 46” dia.A6480-00013 N-Serv gauge; All stainless steel; 41” dia.3180-18002 Sr. Universal dial kit

Rochester Gauges

Universal Dial Kit

A6480 SeriesA6200 Series

A7707L A7797

Part # Description

A7707L Quick acting hose end valve withlocking handle

A7708L 90º quick acting hose end valvewith locking handle

A7575L4 Liquid safety hose coupling

A7797A Quick acting minimum lossshutoff valve

RegO Hose End Valves

RegO PullawaysPart # DescriptionA2141A8 1” PullawayA2141A10 1 1⁄4” Pullaway

A2141

Part Number Length DescriptionE16NH3X12.5FT 12.5' 1” x 12.5’ - 1” NPT Male EndsE20NH3X12.5FT 12.5 1 1⁄4” x 12.5’ - 1 1⁄4” NPT Male EndsE16NH3X15FT 15' 1” x 15’ - 1” NPT Male EndsE20NH3X15FT 15' 1 1⁄4” x 15’ - 1 1⁄4” NPT Male Ends

NH3 Hose Assemblies

NURSE TANK COMPONENTS

E16NH3X12.5FT

Page 8: Storage Tank Upgrade Compliance Guide2016 ILLINOIS EDITION FOR ANHYDROUS AMMONIA (NH3) 8 IL Admin Code 215 Ammonia Storage Tank Upgrade Compliance Guide Effective July 1 2016, the

8 SOLUTIONS.Illinois NH3 Edition.2016CALL GEC FOR A FREE ON-SITE INSPECTION

C

D

B A

F

E

G H

9

13

10 11 12 1 2 3

8 7 6

5

4

Bulk Storage Tank Design GuideContact

Company NameDate of Inspection

CityState

Inspected by

Data Plate InformationManufacturerManufacturer YearSerial #Water CapacityO.D.Working PressureOAL

Head TypeA HemisphericalB Semi-Ellipsoidal

Relief ValvesSize Part # Qty

CD

Liquid Level Gauge Part #E FloatF Rotary

Float Gauge Flange (Mark Correct Type)G CenterlineH Straddle

Pier Measurement (c/c)Paint ConditionManway: Location

Storage Opening Type (Mark Correct Type)Half CouplingFull Coupling

Storage Openings (Liquid-L / Vapor-V)Size L / V Part #

12345678910111213

Houston TX(800) 334-7816

Kansas City MO(800) 821-5062

Little Rock AR(800) 643-8222