storm & sump tank
DESCRIPTION
Storm & Sump TankTRANSCRIPT
-
Project:
Section:
Drawing Ref:
Reference:
Treatment Plant Design = 550 p.e.
= 225 l/p/day
Operating at Full Capacity = 123750 l/day
= 123.75 m3/day
= 5.15625 m3/hr
Volume of Storm Tank =
DWF 1 = 6 DWF 2 = 3
3 hours
Storage Tank Volume = 46.41 m3
5.15625 m3/hr
DWF = 3
2 hours
31 m3
Operating at Full Capacity =
Retention Time (hrs) =
Storage Tank Volume =
The existing sump measures 4.5 x 4.5 x 1.5 on site, giving
a volume of approximately 32.5 m3, therefore the
retention time in this sump exceeds a 2 hour retention
period, at 3DWF, prior to the emergency overflow to the
reed beds.
Retention Time =
(DWF 1 - DWF 2) x Retention Time
Sump Storage Tank Sizing
Avg. Flow per person per day
Using a design concept of providing storage for the
difference between 6 times DWF and 3 times DWF for a
period if 2 hours, we can say
Storm Tank Storage
Job No. :
Keadue WWTP Upgrade Works
Calculation Sheet No :
Storm & Sump Storage Tank Design
Calculations By: Checked By: Date:
Ken Geelan
Calculations Output
INSERT RELEVANT DATA INTO HIGHLIGHTED AREAS