  • Project:

    Section:

    Drawing Ref:

    Reference:

    Treatment Plant Design = 550 p.e.

    = 225 l/p/day

    Operating at Full Capacity = 123750 l/day

    = 123.75 m3/day

    = 5.15625 m3/hr

    Volume of Storm Tank =

    DWF 1 = 6 DWF 2 = 3

    3 hours

    Storage Tank Volume = 46.41 m3

    5.15625 m3/hr

    DWF = 3

    2 hours

    31 m3

    Operating at Full Capacity =

    Retention Time (hrs) =

    Storage Tank Volume =

    The existing sump measures 4.5 x 4.5 x 1.5 on site, giving

    a volume of approximately 32.5 m3, therefore the

    retention time in this sump exceeds a 2 hour retention

    period, at 3DWF, prior to the emergency overflow to the

    reed beds.

    Retention Time =

    (DWF 1 - DWF 2) x Retention Time

    Sump Storage Tank Sizing

    Avg. Flow per person per day

    Using a design concept of providing storage for the

    difference between 6 times DWF and 3 times DWF for a

    period if 2 hours, we can say

    Storm Tank Storage

    Job No. :

    Keadue WWTP Upgrade Works

    Calculation Sheet No :

    Storm & Sump Storage Tank Design

    Calculations By: Checked By: Date:

    Ken Geelan

    Calculations Output

    INSERT RELEVANT DATA INTO HIGHLIGHTED AREAS