Inverter Air Conditioning for Light Commercial Use

SuperDigital Inverter

22

Toshiba Super Digital Inverter series air conditioners combine economy and ecology in a compact body. They feature state-of-the-art technology, flexible control, and easy installation to bring natural comfort and convenience to any business environment. A complete range of indoor units: Cassette, Ducted, Ceiling and High wall units.

Very efficient energy consumption, Keeps down operating costs. EER of 4.52* and COP of 4.79* achieved by Toshiba’s unrivalled Super Digital Inverter technologies and newly developed components.

*4HP outdoor unit

A low minimum speed of 10 rps has been achieved. This has further improved the operating efficiency when the load is low (the minimum in Series 2 was 15 rps).

Large-area magnet

Rotor with slit

High power motor

Newly designed compression path

More precise components

The structure and shape of each compressor component has been optimised. The area of the rotor magnet has been increased and a slit introduced to the design. These improvements have further enhanced efficiency and reduced noise.

Note: Actual component may vary considerably from specifications depending on product model.

2 HP 5 HP4 HP3 HP

(EER)

4-way cassette / Cooling

6.0

5.0

4.0

3.0

2.0

1.0

3.613.82

4.52

3.96

2 HP 5 HP4 HP3 HP

4-way cassette / Heating(COP)

6.0

5.0

4.0

3.0

2.0

1.0

4.634.19 4.36

4.79

Vector-controlled inverter

High efficiency heat-transfer (flat fin)

DC fan motor

Bat wing fan

Wide-flow grille

DC twin rotary compressor

Vector IPDU control changes the motor current wave to a smooth sine pattern so that noise emitted from the driveunits is greatly reduced.

Heat-transfer tube with improved heat-transfer coefficient.

Highly Efficient DC Motor.

New development for high-pressure low-volume fan.

Optimizing ventilation performance, Bringing out the full effect of fan and motor.

A low minimum speed of 10 rps has been achieved.

An ozone layer depletion coefficient of zero has become absolutely essential for an advanced air conditioning system.

The new structure allows a huge reduction in energy loss. The balanced magnetic-action force to rise and the rotor’s weight minimized the friction laid on the axis provides excellent operation efficiency.

Super Digital Inverter

Friction loss Reducing friction loss

Stator RotorRotor’s weight

Magnetic center

Magnetic actionCurrent model New model

R410A refrigerant

5.56 5.56

6.49

5.675.96

5.56 5.38

4.90

Rated 50% load

Superior EER

ECO-driving DC twin rotary

The industry's first magnetic-action control

Heating: °C WB

Heating operation range

-20°C -15°C 15°C0°C

SDl (2-6HP)

SDl (1.5-1.7HP)

Heater operation is possible starting from an outdoor temperature of -20°C creates a comfortable space even during cold winters, while cooling operation is possible at -15°C outdoor temperature. This enables wider applications and use of the system in colder regions.

This enables indoor unit type and Ceiling type to maintain energy efficiency at the time of purchase for a long time. The mechanism of the wash-off 1. The aqua resin coating prevents dirt from sticking to the fins.

WaterOil/

Aquaresincoating

Dirt

Water

Oil/

Dirt

Aqua

resincoating

Quiet operation

Low-noise design. If the outdoor temperature is 30°C or less, operates at under 45dB(A). It’s possible to automatically operate the quiet operation mode below 35°C air temperature.

8°C operation for frost protection is possible for the combination with Super Digital Inverter. (4-Way and Slim Duct series 4)

2. The condensation water flows and washes away dirt. 3. After washing, a drying operation suppresses the propagation of mold.

Improve reliability for smooth drainage. The outdoor unit of Super Digital Inverter is equipped with “Sub cool path” preventing freeze under a heat exchanger. (Only 3HP to 6HP)

Ann

ual o

pera

tion

(h)

Ope

ratio

n so

und

dB(A

)

Air temperaure (°C)

Operation below air temperature 30 (°C)

22 23 24 25 26 353433323130292827 0

60

120

180

240

300

35

40

45

50

Enable the outdoor unit to be installed out of sight increases installation flexibility. (Only 4HP to 6HP)

Rear side

Piping panel taken out in 4 directions

Front

Under

Rear

LateralSub cool path

Super Digital Inverter leads the industry with support for height differences of up to 30 meters on a single system. That is enough height to cover an 8-story building.

Sing

le s

yste

m

8F7F6F5F4F3F2F1F

Height between indoor units

30m

Farthest equivalent length 75m3

Operating temperature range

Self-Clean operation-Continuing high performance for energy saving

Frost protection

Sub cool path

Height Difference

Compatible with pipes up to 75 meters long

4

Equivalent (HP) 1.5HP 1.7HP 2HP 3HP 4HP 5HP 6HP

Standard RAV-SP404ATP-E RAV-SP454ATP-E RAV-SP564ATP-E RAV-SP804ATP-E RAV-SP1104AT-E RAV-SP1404AT-E -

Light Anti-Corrosion protection - - - - RAV-SP1104ATZ-E RAV-SP1404ATZ-E -

Heavy Anti-Corrosion protection - - RAV-SP564ATJP-E RAV-SP804ATJP-E RAV-SP1104ATZG-E RAV-SP1404ATZG-E -

3-phase model

50Hz

Standard RAV-SP1104AT8-E RAV-SP1404AT8-E RAV-SP1604AT8-E

Light Anti-Corrosion protection RAV-SP1104AT8Z-E RAV-SP1404AT8Z-E RAV-SP1604AT8Z-E

Heavy Anti-Corrosion protection RAV-SP1104AT8ZG-E RAV-SP1404AT8ZG-E RAV-SP1604AT8ZG-E

60Hz

Standard RAV-SP1104AT7 RAV-SP1404AT7 RAV-SP1604AT7

Light Anti-Corrosion protection RAV-SP1104AT7Z RAV-SP1404AT7Z RAV-SP1604AT7Z

Heavy Anti-Corrosion protection RAV-SP1104AT7ZG RAV-SP1404AT7ZG RAV-SP104AT7ZG

Compact 4-way cassette type

Single RAV-SM404MUT-E RAV-SM454MUT-E RAV-SM564MUT-E N/A N/A N/A N/A

Twin (x 2) N/A N/A N/A RAV-SM404MUT-E RAV-SM564MUT-E N/A N/A

Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM564MUT-E

4-way cassette type

Single N/A N/A RAV-SM564UTP-E RAV-SM804UTP-E RAV-SM1104UTP-E RAV-SM1404UTP-E RAV-SM1604UTP-E

Twin (x 2) N/A N/A N/A N/A RAV-SM564UTP-E RAV-SM804UTP-E RAV-SM804UTP-E

Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM564UTP-E

Slim duct type

Single RAV-SM404SDT-E RAV-SM454SDT-E RAV-SM564SDT-E N/A N/A N/A N/A

Twin (x 2) N/A N/A N/A RAV-SM404SDT-E RAV-SM564SDT-E N/A N/A

Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM564SDT-E

Standard duct type

Single RAV-SM406BTP-E RAV-SM456BTP-E RAV-SM566BTP-E RAV-SM806BTP-E RAV-SM1106BTP-E RAV-SM1406BTP-E RAV-SM1606BTP-E

Twin (x 2) N/A N/A N/A RAV-SM406BTP-E RAV-SM566BTP-E RAV-SM806BTP-E RAV-SM806BTP-E

Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM566BTP-E

Ceiling type

Single N/A N/A RAV-SM567CTP-E RAV-SM807CTP-E RAV-SM1107CTP-E RAV-SM1407CTP-E RAV-SM1607CTP-E

Twin (x 2) N/A N/A N/A N/A RAV-SM567CTP-E RAV-SM807CTP-E RAV-SM807CTP-E

Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM567CTP-E

High wall type

Single N/A N/A RAV-SM566KRT-E RAV-SM806KRT-E N/A N/A N/A

Twin (x 2) N/A N/A N/A N/A RAV-SM566KRT-E RAV-SM806KRT-E RAV-SM806KRT-E

Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM566KRT-E

1-phase model

Super Digital Inverter Combinations

5

Available Indoor Units

5

Indoor unit (RAV-) SM404MUT-E SM454MUT-E SM564MUT-E

Outdoor unit

Standard (RAV-) SP404ATP-E SP454ATP-E SP564ATP-E

Light Anti-Corrosion protection (RAV-) - - -

Heavy Anti-Corrosion protection (RAV-) - - SP564ATJP-E

Power supply 1-phase 50Hz 230V (220–240V)

Cooling*1

Capacity kW 3.6 4.0 5.0

Range, min-max kW 1.5-4.0 1.5-4.5 1.2-5.6

Power consumption kW 1.00 1.19 1.56

EER (Energy Efficiency Ratio)

Capacity 100% 3.60 3.36 3.21

Capacity 80% 3.95 3.94 3.45

Capacity 50% 4.47 4.82 4.03

Heating*1

Capacity kW 4.0 4.5 5.6

Range, min-max kW 1.5-5.0 1.5-5.6 0.9-7.4

Power consumption kW 0.97 1.16 1.54

COP (Coefficient of Performance)

Capacity 100% 4.12 3.88 3.64

Capacity 80% 4.27 4.04 3.93

Capacity 50% 4.44 4.33 4.52

Indoor unit

Standard air flow (H/M/L) m3/h 660/552/468 660/552/468 798/672/546

Sound pressure level (H/M/L) dB(A) 40/36/31 40/36/31 43/39/34

Sound power level (H/M/L) dB(A) 55/51/46 55/51/46 58/54/49

Main unit dimensions (H/W/D) mm 268/575/575 268/575/575 268/575/575

Weight kg 17 17 17

Panel dimensions (H/W/D) mm 27/700/700 27/700/700 27/700/700

Panel weight kg 3 3 3

Outdoor unit

Compressor type DC twin rotary

Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø12.7 / ø6.4 ø12.7 / ø6.4

Standard / Min. pipe length m 7.5 / 5 7.5 / 5 7.5 / 5

Max. pipe total length m 30 30 50

Maximum height difference m 30 30 30

Outer dimensions (H/W/D) mm 550/780/290 550/780/290 550/780/290

Weight kg 40 40 44

Standard air flow (Fan unit) m3/h 2400 2400 2400

Sound pressure level, Cooling/Heating*2 dB(A) 45/47 45/47 47/48

Sound power level, Cooling/Heating dB(A) 62/64 62/64 63/64

Operating range, Cooling/Heating °C -15~43 / -15~15 -15~43 / -20~15

6

Perfectly fit for 600 x 600 grid system ceiling

Perfect for grid system ceiling Designed for simple & easy installation and maintenance

This compact unit (575 x 575 mm) fits perfectly into ceilings and matches standard architectural modules, without the need to cut ceiling tiles.

The slim flat stylish panel design is only 268 mm in height even when an electrical box is located inside the unit. Easy access to electrical box is achieved by simply removing the suction grill. Easy installation is also possible using the panel adjust pocket. Use the “adjust pocket” function for fine adjustments after installation.

The drain up height is 850 mm. Available for ceilings up to 3.5 m in height.

*1 Rated conditions Cooling : Indoor air temperature 27oC DB / 19oC WB, Outdoor air temperature 35oC DB Heating : Indoor air temperature 20oC DB, Outdoor air temperature 7oC DB / 6oC WB*2 Sound pressure levels measured in an anechoic chamber

Maximum height

3.5m

RBC-UM11PG(W)-E

Panel

Options

Compact 4-way cassette type

TCB-FF101URE2

Auxiliary fresh air flange

Panel

RBC-UM11PG(W)E

Indoor unit (RAV-) SM564UTP-E SM804UTP-E SM1104UTP-E SM1404UTP-E SM1104UTP-E SM1404UTP-E SM1604UTP-E

Outdoor unit

Standard (RAV-) SP564ATP-E SP804ATP-E SP1104AT-E SP1404AT-E SP1104AT8-E, SP1104AT7

SP1404AT8-E, SP1404AT7

SP1604AT8-E, SP1604AT7

Light Anti-Corrosion protection (RAV-) - - SP1104ATZ-E SP1404ATZ-E SP1104AT8Z-E, SP1104AT7Z

SP1404AT8Z-E, SP1404AT7Z

SP1604AT8Z-E, SP1604AT7Z

Heavy Anti-Corrosion protection (RAV-) SP564ATJP-E SP804ATJP-E SP1104ATZG-E SP1404ATZG-E SP1104AT8ZG-E, SP1104AT7ZG

SP1404AT8ZG-E, SP1404AT7ZG

SP1604AT8ZG-E, SP1604AT7ZG

Power supply 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V 3-phase 50Hz 400V (380-415V) / 3-phase 60Hz 380V

Cooling*1

Capacity kW 5.3 7.1 10.0 12.5 10.0 12.5 14.0

Range, min-max kW 1.2-5.6 1.9-8.0 2.6-12.0 2.6-14.0 2.6-12.0 2.6-14.0 2.6-16.0

Power consumption kW 1.47 1.86 2.21 3.16 2.37 3.46 4.49

EER (Energy Efficiency Ratio)

Capacity 100% 3.61 3.82 4.52 3.96 4.22 3.61 3.12

Capacity 80% 4.25 4.40 5.31 4.64 4.79 4.10 3.53

Capacity 50% 5.56 5.56 6.49 5.67 5.88 5.43 5.07

Heating*1

Capacity kW 5.6 8.0 11.2 14.0 11.2 14.0 16.0

Range, min-max kW 0.9-8.1 1.3-11.3 2.4-13.0 2.4-16.5 2.4-15.6 2.4-18.0 2.4-19.0

Power consumption kW 1.21 1.91 2.34 3.21 2.42 3.42 4.30

COP (Coefficient of Performance)

Capacity 100% 4.63 4.19 4.79 4.36 4.63 4.09 3.72

Capacity 80% 5.15 4.71 5.01 4.57 5.09 4.50 4.09

Capacity 50% 5.96 5.56 5.38 4.90 6.09 5.47 5.33

Indoor unit

Standard air flow (H/M/L) m3/h 1050/870/780 1230/960/810 2010/1440/1170 2100/1440/1230 2010/1440/1170 2100/1440/1230 2130/1500/1260

Sound pressure level (H/M/L) dB(A) 32/29/28 35/31/28 43/38/33 44/38/34 43/38/33 44/38/34 45/40/36

Sound power level (H/M/L) dB(A) 47/44/43 50/46/43 58/53/48 59/53/49 58/53/48 59/53/49 60/55/51

Main unit dimensions (H/W/D) mm 256/840/840 256/840/840 319/840/840 319/840/840 319/840/840 319/840/840 319/840/840

Weight kg 20 20 24 24 24 24 24

Panel dimensions (H/W/D) mm 30/950/950 30/950/950 30/950/950 30/950/950 30/950/950 30/950/950 30/950/950

Panel weight kg 4.2 4.2 4.2 4.2 4.2 4.2 4.2

Outdoor unit

Compressor type DC twin rotary DC twin rotary

Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5

Standard / Min. pipe length m 7.5 / 5 7.5 / 5 7.5 / 3 7.5 / 3 7.5 / 3 7.5 / 3 7.5 / 3

Max. pipe total length m 50 50 75 75 75 75 75

Maximum height difference m 30 30 30 30 30 30 30

Outer dimensions (H/W/D) mm 550/780/290 890/900/320 1340/900/320 1340/900/320 1340/900/320 1340/900/320 1340/900/320

Weight kg 44 66 93 93 95 95 95

Standard air flow (Fan unit) m3/h 2400 3000 6060 6180 6060 6180 6180

Sound pressure level, Cooling/Heating*2 dB(A) 47/48 48/49 49/50 51/52 49/50 51/52 51/53

Sound power level, Cooling/Heating dB(A) 63/64 64/65 66/67 68/69 66/67 68/69 68/70

Operating range, Cooling/Heating °C -15~43 / -20~15 -15~46 / -20~15

*1 Rated conditions Cooling : Indoor air temperature 27oC DB / 19oC WB, Outdoor air temperature 35oC DB Heating : Indoor air temperature 20oC DB, Outdoor air temperature 7oC DB / 6oC WB*2 Sound pressure levels measured in an anechoic chamber

RAV-SPxx04AT8(Z),(ZG)-E: 3-phase 50Hz 400V (380-415V), RAV-SPxx04AT7(Z),(ZG): 3-phase 60Hz 380V

7

The wide air flow in all direction

Multi-louver individual control New Long-life pre-filter

Individual louver control enables airflow to be chosen according to user preferences. The angles of each louver can be set individually in 3 different choices of swing patterns; Standard swing, Diagonally opposite swing and Turn-around swing

(1) Standard swing (2) Diagonally opposite swing

(3) Turn-around swing

A new long-life pre-filter has a surface 1.5 times of current filters to improve Dust-collection performance.

Easy installation

Light weight unit (24kg at 5HP) Easy panel installation, The panel is attached using the bolt that is already installed on the indoor unit.

Built-in condensate drain pump

300mm or less

850mm or less

210mm

4-way cassette type

Indoor unit (RAV-) SM404SDT-E SM454SDT-E SM564SDT-E

Outdoor unit

Standard (RAV-) SP404ATP-E SP454ATP-E SP564ATP-E

Light Anti-Corrosion protection (RAV-) - - -

Heavy Anti-Corrosion protection (RAV-) - - SP564ATJP-E

Power supply 1-phase 50Hz 230V (220–240V)

Cooling*1

Capacity kW 3.6 4.0 5.0

Range, min-max kW 1.5-4.0 1.5-4.5 1.2-5.6

Power consumption kW 1.03 1.20 1.56

EER (Energy Efficiency Ratio)

Capacity 100% 3.50 3.33 3.21

Capacity 80% 3.83 3.91 3.45

Capacity 50% 4.34 4.77 4.03

Heating*1

Capacity kW 4.0 4.5 5.6

Range, min-max kW 1.5-5.0 1.5-5.6 0.9-7.4

Power consumption kW 1.00 1.15 1.44

COP (Coefficient of Performance)

Capacity 100% 4.00 3.91 3.89

Capacity 80% 4.10 4.09 4.11

Capacity 50% 4.35 4.41 4.52

Indoor unit

Standard air flow (H/M/L) m3/h 690/600/522 690/600/522 780/678/582

External static pressure-Standard (Upper-Lower) Pa 5-15-30-45 5-15-30-45 4-14-29-44

Sound pressure level-Under air inlet dB(A) 39/36/33 39/36/33 45/40/36

Sound pressure level-Back air inlet dB(A) 30/28/26 30/28/26 33/31/28

Sound power level (H/M/L) dB(A) 54/51/48 54/51/48 60/55/54

Dimensions (H/W/D) mm 210/845/645 210/845/645 210/845/645

Weight kg 22 22 22

Outdoor unit

Compressor type DC twin rotary

Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø12.7 / ø6.4 ø12.7 / ø6.4

Standard / Min. pipe length m 7.5 / 5 7.5 / 5 7.5 / 5

Max. pipe total length m 30 30 50

Maximum height difference m 30 30 30

Outer dimensions (H/W/D) mm 550/780/290 550/780/290 550/780/290

Weight kg 40 40 44

Standard air flow (Fan unit) m3/h 2400 2400 2400

Sound pressure level, Cooling/Heating*2 dB(A) 45/47 45/47 47/48

Sound power level, Cooling/Heating dB(A) 62/64 62/64 63/64

Operating range, Cooling/Heating °C -15~43 / -15~15 -15~43 / -20~15

*1 Rated conditions Cooling : Indoor air temperature 27oC DB / 19oC WB, Outdoor air temperature 35oC DB Heating : Indoor air temperature 20oC DB, Outdoor air temperature 7oC DB / 6oC WB*2 Sound pressure levels measured in an anechoic chamber

8

Slim design for greater application flexibility

Functional design

Only 210 mm in height for greater application flexibility.

4-step static pressure setup.

Concealed installation within a ceiling void.

Auxiliary fresh air intake available.

Slim & quiet

Quiet, powerful operation.

Perfect comfort throughout the room and can be used with any style of air diffuser.

210mm210mm

Slim duct type

Options

TCB-FF101URE2

Auxiliary fresh air flange

9

Indoor unit (RAV-) SM406BTP-E SM456BTP-E SM566BTP-E SM806BTP-E SM1106BTP-E SM1406BTP-E SM1106BTP-E SM1406BTP-E SM1606BTP-E

Outdoor unit

Standard (RAV-) SP404ATP-E SP454ATP-E SP564ATP-E SP804ATP-E SP1104AT-E SP1404AT-E SP1104AT8-E, SP1104AT7

SP1404AT8-E, SP1404AT7

SP1604AT8-E, SP1604AT7

Light Anti-Corrosion protection (RAV-) - - - - SP1104ATZ-E SP1404ATZ-E SP1104AT8Z-E, SP1104AT7Z

SP1404AT8Z-E, SP1404AT7Z

SP1604AT8Z-E, SP1604AT7Z

Heavy Anti-Corrosion protection (RAV-) - - SP564ATJP-E SP804ATJP-E SP1104ATZG-E SP1404ATZG-E SP1104AT8ZG-E, SP1104AT7ZG

SP1404AT8ZG-E, SP1404AT7ZG

SP1604AT8ZG-E, SP1604AT7ZG

Power supply 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V 3-phase 50Hz 400V (380-415V) / 3-phase 60Hz 380V

Cooling*1

Capacity kW 3.6 4.0 5.0 7.1 10.0 12.5 10.0 12.5 14.0

Range, min-max kW 1.5-4.0 1.5-4.5 1.2-5.6 1.9-8.0 2.6-12.0 2.6-14.0 2.6-12.0 2.6-14.0 2.6-16.0

Power consumption kW 1.07 1.23 1.56 2.06 2.64 3.83 2.64 3.86 4.65

EER (Energy Efficiency Ratio)

Capacity 100% 3.38 3.24 3.21 3.45 3.79 3.26 3.79 3.24 3.01

Capacity 80% 3.69 3.81 3.23 3.89 4.44 3.83 4.30 3.68 3.41

Capacity 50% 4.19 4.65 3.47 4.93 5.43 4.66 5.71 4.88 4.90

Heating*1

Capacity kW 4.0 4.5 5.6 8.0 11.2 14.0 11.2 14.0 16.0

Range, min-max kW 1.5-5.0 1.5-5.6 0.9-7.4 1.3-10.6 2.4-13.0 2.4-16.5 2.4-15.6 2.4-18.0 2.4-19.0

Power consumption kW 1.04 1.24 1.55 2.21 2.77 3.67 2.77 3.67 4.60

COP (Coefficient of Performance)

Capacity 100% 3.84 3.63 3.61 3.62 4.04 3.81 4.04 3.81 3.48

Capacity 80% 3.95 3.79 3.80 3.79 4.25 4.00 4.44 4.18 3.82

Capacity 50% 4.17 4.09 4.12 4.08 4.55 4.29 5.33 5.09 4.98

Indoor unit

Standard air flow (H/M/L) m3/h 798/630/480 798/630/480 798/630/480 1200/930/720 2100/1650/1260 2100/1650/1260 2100/1650/1260 2100/1650/1260 2100/1650/1260

External static pressure (factory setting) Pa 30 30 30 30 50 50 50 50 50

External static pressure-Standard (Upper-Lower) Pa 30(120-30) 30(120-30) 50(120-30) 30-40-50-65-80-100-120 (7 steps)

Sound pressure level (H/M/L) dB(A) 33/29/25 33/29/25 33/29/25 34/30/26 40/36/33 40/36/33 40/36/33 40/36/33 40/36/33

Sound power level (H/M/L) dB(A) 48/44/40 48/44/40 48/44/40 49/45/41 55/51/48 55/51/48 55/51/48 55/51/48 55/51/48

Dimensions (H/W/D) mm 275/700/750 275/700/750 275/700/750 275/1000/750275/1400/750275/1400/750 275/1400/750 275/1400/750 275/1400/750

Weight kg 23 23 23 30 40 40 40 40 40

Outdoor unit

Compressor type DC twin rotary DC twin rotary

Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5

Standard / Min. pipe length m 7.5 / 5 7.5 / 5 7.5 / 3 7.5 / 3 7.5 / 3 7.5 / 3

Max. pipe total length m 30 30 50 50 75 75 75 75 75

Maximum height difference m 30 30 30 30 30 30 30 30 30

Outer dimensions (H/W/D) mm 550/780/290 550/780/290 550/780/290 890/900/320 1340/900/320 1340/900/320 1340/900/320 1340/900/320

Weight kg 40 44 66 93 95 95 95

Standard air flow (Fan unit) m3/h 2400 3000 6060 6180 6060 6180 6180

Sound pressure level, Cooling/Heating*2 dB(A) 45/47 45/47 47/48 48/49 49/50 51/52 49/50 51/52 51/53

Sound power level, Cooling/Heating dB(A) 62/64 62/64 63/64 64/65 66/67 68/69 66/67 68/69 68/70

Operating range, Cooling/Heating °C -15~43 / -15~15 -15~43 / -20~15 -15~46 / -20~15

*1 Rated conditions Cooling : Indoor air temperature 27oC DB / 19oC WB, Outdoor air temperature 35oC DB Heating : Indoor air temperature 20oC DB, Outdoor air temperature 7oC DB / 6oC WB*2 Sound pressure levels measured in an anechoic chamber

RAV-SPxx04AT8(Z),(ZG)-E: 3-phase 50Hz 400V (380-415V), RAV-SPxx04AT7(Z),(ZG): 3-phase 60Hz 380V

Wide range of application opportunities

Compact sizing High static pressure

Compact size especially in height (275 mm), new slimmer chassis offers wide range of installation opportunities to customer.

External static pressure can be raised as high as 120 Pa, so that all areas of the room can be reached for even temperature distribution, no matter how complex the layout.

Built-in High-lift drain pump

New spigot shaped flange as new accessories

The flexible piping layout is made possible by an optionally available drain-pump kit that raises the drain piping up to 850 cm from the drain port.

New spigot shaped flange has higher static pressure with optimized design, the static pressure drops only 20Pa from rectangle flange states. Maximum Static pressure will be 100Pa* with all models. (*static pressure with filter which included in, and intake from back ward)

Flexible duct is accessible, Allows complete design flexibility

Polygonal rooms Narrow rooms Rooms with fixtures and obstacles

Wide range of application opportunities

Standard duct type

Indoor unit (RAV-) SM567CTP-E SM807CTP-E SM1107CTP-E SM1407CTP-E SM1107CTP-E SM1407CTP-E SM1607CTP-E

Outdoor unit

Standard (RAV-) SP564ATP-E SP804ATP-E SP1104AT-E SP1404AT-E SP1104AT8-E, SP1104AT7

SP1404AT8-E, SP1404AT7

SP1604AT8-E, SP1604AT7

Light Anti-Corrosion protection (RAV-) - - SP1104ATZ-E SP1404ATZ-E SP1104AT8Z-E, SP1104AT7Z

SP1404AT8Z-E, SP1404AT7Z

SP1604AT8Z-E, SP1604AT7Z

Heavy Anti-Corrosion protection (RAV-) SP564ATJP-E SP804ATJP-E SP1104ATZG-E SP1404ATZG-E SP1104AT8ZG-E, SP1104AT7ZG

SP1404AT8ZG-E, SP1404AT7ZG

SP1604AT8ZG-E, SP1604AT7ZG

Power supply 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V 3-phase 50Hz 400V (380-415V) / 3-phase 60Hz 380V

Cooling*1

Capacity kW 5.0 7.1 10.0 12.5 10.0 12.5 14.0

Range, min-max kW 1.2-5.6 1.9-8.0 2.6-12.0 2.6-14.0 2.6-12.0 2.6-14.0 2.6-16.0

Power consumption kW 1.37 1.86 2.45 3.90 2.37 3.72 4.50

EER (Energy Efficiency Ratio)

Capacity 100% 3.65 3.82 4.08 3.21 4.22 3.36 3.11

Capacity 80% 4.00 4.37 4.79 3.76 4.62 3.82 3.53

Capacity 50% 4.72 5.63 5.81 4.60 5.21 5.08 5.07

Heating*1

Capacity kW 5.6 8.0 11.2 14.0 11.2 14.0 16.0

Range, min-max kW 0.9-7.4 1.3-10.6 2.4-13.0 2.4-16.5 2.4-14.0 2.4-18.0 2.4-19.0

Power consumption kW 1.28 1.92 2.39 3.62 2.53 3.56 4.31

COP (Coefficient of Performance)

Capacity 100% 4.38 4.17 4.69 3.87 4.43 3.93 3.71

Capacity 80% 4.87 4.71 4.92 4.06 4.57 4.31 4.08

Capacity 50% 5.71 5.71 5.23 4.35 4.79 5.22 5.33

Indoor unit

Standard air flow (H/M/L) m3/h 900/720/540 1410/1002/750 1860/1350/1020 2040/1530/1200 1860/1350/1020 2040/1530/1200 2040/1530/1260

Sound pressure level (H/M/L) dB(A) 37/35/28 41/36/29 44/38/32 46/41/35 44/38/32 46/41/35 46/42/36

Sound power level (H/M/L) dB(A) 52/50/43 56/51/44 59/53/47 61/56/50 59/53/47 61/56/50 61/57/51

Dimensions (H/W/D) mm 235/950/690 235/1270/690 235/1586/690 235/1586/690 235/1586/690 235/1586/690 235/1586/690

Weight kg 23 29 35 35 35 35 35

Outdoor unit

Compressor type DC twin rotary DC twin rotary

Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5

Standard / Min. pipe length m 7.5 / 5 7.5 / 5 7.5 / 3 7.5 / 3 7.5 / 3 7.5 / 3 7.5 / 3

Max. pipe total length m 50 50 75 75 75 75 75

Maximum height difference m 30 30 30 30 30 30 30

Outer dimensions (H/W/D) mm 550/780/290 890/900/320 1340/900/320 1340/900/320 1340/900/320 1340/900/320 1340/900/320

Weight kg 44 66 93 93 95 95 95

Standard air flow (Fan unit) m3/h 2400 3000 6060 6180 6060 6180 6180

Sound pressure level, Cooling/Heating*2 dB(A) 47/48 48/49 49/50 51/52 49/50 51/52 51/53

Sound power level, Cooling/Heating dB(A) 63/64 64/65 66/67 68/69 66/67 68/69 68/70

Operating range, Cooling/Heating °C -15~43 / -20~15 -15~46 / -20~15

*1 Rated conditions Cooling : Indoor air temperature 27oC DB / 19oC WB, Outdoor air temperature 35oC DB Heating : Indoor air temperature 20oC DB, Outdoor air temperature 7oC DB / 6oC WB*2 Sound pressure levels measured in an anechoic chamber

RAV-SPxx04AT8(Z),(ZG)-E: 3-phase 50Hz 400V (380-415V), RAV-SPxx04AT7(Z),(ZG): 3-phase 60Hz 380V10

Smooth curve design & Low noise level

Smooth Curve for pliant Shape New Designed Wide Flap

All-new chassis and new rounded design, This new models have been developed in response to customers’ needs for ceiling units that better match their room interiors.

Previous model New model

Comfortable ambience

New fan has adopted the turbulence prevention rib to optimize the ventilating way. Air volume has increased and noise level also has decreased compared with previous model. Winds of new ceiling type of 4HP to 6HP can be reached up to 4.3 metre.

10 16 22 28 34 (C)

Temperature (deg.C)

Previous model New model

Center

0.5m above the floor

Temperature measuring section

3m

3m

8m

8m

8m

8m

Flap control

The airflow angle is automatically set to the most suitable setting according to your cooling or heating needs, and an automatic swing mode enables airflow to reach all areas of the room to create a comfortable ambience.

New Drain pump kit available as an option

The Drain pump kit makes draining easier. Glass built into Drain Pump Kit helps reduce mould formation.

The new air outlet has realized both High noise reduction and large air volume.

30% Extension

Ceiling type

Indoor unit (RAV-) SM566KRT-E SM806KRT-E

Outdoor unit

Standard (RAV-) SP564ATP-E SP804ATP-E

Light Anti-Corrosion protection (RAV-) - -

Heavy Anti-Corrosion protection (RAV-) SP564ATJP-E SP804ATJP-E

Power supply 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V

Cooling*1

Capacity kW 5.0 7.1

Range, min-max kW 1.2-5.6 1.9-8.0

Power consumption kW 1.44 2.21

EER (Energy Efficiency Ratio)

Capacity 100% 3.47 3.21

Capacity 80% 3.81 3.76

Capacity 50% 4.31 4.61

Heating*1

Capacity kW 5.6 8.0

Range, min-max kW 0.9-7.3 1.3-10.6

Power consumption kW 1.50 2.34

COP (Coefficient of Performance)

Capacity 100% 3.73 3.42

Capacity 80% 3.86 3.58

Capacity 50% 4.06 3.85

Indoor unit

Standard air flow (H/M/L) m3/h 840/750/660 1020/750/660

Sound pressure level (H/M/L) dB(A) 42/39/36 47/41/36

Sound power level (H/M/L) dB(A) 57/54/51 62/56/51

Dimensions (H/W/D) mm 320/1050/228 320/1050/228

Weight kg 12 12

Outdoor unit

Compressor type DC twin rotary

Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø15.9 / ø9.5

Standard / Min. pipe length m 7.5 / 5 7.5 / 5

Max. pipe total length m 50 50

Maximum height difference m 30 30

Outer dimensions (H/W/D) mm 550/780/290 890/900/320

Weight kg 44 66

Standard air flow (Fan unit) m3/h 2400 3000

Sound pressure level, Cooling/Heating*2 dB(A) 47/48 48/49

Sound power level, Cooling/Heating dB(A) 63/64 64/65

Operating range, Cooling/Heating °C -15~43 / -20~15

*1 Rated conditions Cooling : Indoor air temperature 27oC DB / 19oC WB, Outdoor air temperature 35oC DB Heating : Indoor air temperature 20oC DB, Outdoor air temperature 7oC DB / 6oC WB*2 Sound pressure levels measured in an anechoic chamber

11

Elegant and slim

Slim-line design

With is attractive, slim-line design, the unit can easily blend in with any room interior. The filtration system further the indoor air quality benefits of this high-wall unit.

SWING

Cooling mode

Heating mode

Cooling

Self cleaning function

Toshiba’s self-cleaning function is designed to reduce the humidity that causes mold to form inside an air-conditioning unit 20 minutes of fan operation after shut down dries the moist air and helps reduce mold formation on heat exchanger coils.

Normal Operation

Self-cleaning Function

Moisture stays trapped inside

20 minutes of fan operation after shut down dries the moist air and helps reduce mold formation on heat exchanger coils.

High wall type

Optimum air distribution

70° directional Auto-swing louver mode allows optimum air distribution throughout the room. Total comfort is granted, thanks also to Automatic air volume control and Automatic cooling/heating.

12

Twin and Triple system

Indoor unit type

Outdoor unit (RAV-)

Indoor unit (RAV-) HP

Cooling Capacity EER Heating Capacity COP

Rated (kW)

min-max (kW)

Power consumption (kW) 100% 80% 50% Rated

(kW)min-max

(kW)Power consumption

(kW) 100% 80% 50%

Twin

sys

tem

: Su

pe

r Dig

ital I

nve

rte

r 1-p

ha

se

Compact 4-way cassette

SP804AT(J)P-E SM404MUT-E 3 7.1 1.9-8.0 2.21 3.21 3.69 4.77 8.0 1.3-10.6 2.16 3.70 4.18 5.06

SP1104AT(Z)(ZG)-E SM564MUT-E 4 10.0 2.6-12.0 2.67 3.75 4.23 5.17 11.2 2.4-13.0 2.67 4.19 4.39 4.71

4-way cassetteSP1104AT(Z)(ZG)-E SM564UTP-E 4 10.0 2.6-12.0 2.21 4.52 5.31 6.49 11.2 2.4-13.0 2.34 4.79 5.01 5.38

SP1404AT(Z)(ZG)-E SM804UTP-E 5 12.5 2.6-14.0 3.16 3.96 4.64 5.67 14.0 2.4-16.5 3.21 4.36 4.57 4.90

Slim ductSP804AT(J)P-E SM404SDT-E 3 7.1 1.9-8.0 2.21 3.21 3.69 4.77 8.0 1.3-10.6 2.16 3.70 4.18 5.06

SP1104AT(Z)(ZG)-E SM564SDT-E 4 10.0 2.6-12.0 2.77 3.61 4.39 5.36 11.2 2.4-13.0 2.67 4.19 4.39 4.71

Standard duct

SP804AT(J)P-E SM406BTP-E 3 7.1 1.9-8.0 2.06 3.45 3.89 4.92 8.0 1.3-10.6 2.21 3.62 3.79 4.08

SP1104AT(Z)(ZG)-E SM566BTP-E 4 10.0 2.6-12.0 2.64 3.79 4.44 5.43 11.2 2.4-13.0 2.77 4.04 4.25 4.55

SP1404AT(Z)(ZG)-E SM806BTP-E 5 12.5 2.6-14.0 3.83 3.26 3.83 4.66 14.0 2.4-16.5 3.67 3.81 4.00 4.29

CeilingSP1104AT(Z)(ZG)-E SM567CTP-E 4 10.0 2.6-12.0 2.45 4.08 4.79 5.81 11.2 2.4-13.0 2.39 4.69 4.92 5.23

SP1404AT(Z)(ZG)-E SM807CTP-E 5 12.5 2.6-14.0 3.90 3.21 3.76 4.60 14.0 2.4-16.5 3.62 3.87 4.06 4.35

High wallSP1104AT(Z)(ZG)-E SM566KRT-E 4 10.0 2.6-12.0 2.77 3.61 4.24 5.17 11.2 2.4-13.0 2.80 4.00 4.19 4.48

SP1404AT(Z)(ZG)-E SM806KRT-E 5 12.3 2.6-13.5 3.88 3.17 3.72 4.54 14.0 2.4-16.5 3.83 3.66 3.84 4.12

Twin

sys

tem

: Su

pe

r Dig

ital I

nve

rte

r 3-p

ha

se

Compact 4-way cassette

SP1104AT8(Z)(ZG)-E SM564MUT-E 4 10.0 2.6-12.0 2.79 3.58 4.06 5.00 11.2 2.4-14.0 2.67 4.19 4.59 5.54

SP1104AT7(Z)(ZG) SM564MUT-E 4 10.0 2.6-12.0 2.79 3.58 4.06 5.00 11.2 2.4-14.0 2.67 4.19 4.59 5.54

4-way cassette

SP1104AT8(Z)(ZG)-E SM564UTP-E 4 10.0 2.6-12.0 2.37 4.22 4.79 5.88 11.2 2.4-15.6 2.42 4.63 5.09 6.09

SP1104AT7(Z)(ZG) SM564UTP-E 4 10.0 2.6-12.0 2.37 4.22 4.79 5.88 11.2 2.4-15.6 2.42 4.63 5.09 6.09

SP1404AT8(Z)(ZG)-E SM804UTP-E 5 12.5 2.6-14.0 3.46 3.61 4.46 5.43 14.0 2.4-18.0 3.42 4.09 4.50 5.47

SP1404AT7(Z)(ZG) SM804UTP-E 5 12.5 2.6-14.0 3.46 3.61 4.46 5.43 14.0 2.4-18.0 3.42 4.09 4.50 5.47

SP1604AT8(Z)(ZG)-E SM804UTP-E 6 14.0 2.6-16.0 4.49 3.12 3.53 5.07 16.0 2.4-19.0 4.30 3.72 4.09 5.33

SP1604AT7(Z)(ZG) SM804UTP-E 6 14.0 2.6-16.0 4.49 3.12 3.53 5.07 16.0 2.4-19.0 4.30 3.72 4.09 5.33

Slim ductSP1104AT8(Z)(ZG)-E SM564SDT-E 4 10.0 2.6-12.0 2.79 3.58 4.06 5.00 11.2 2.4-14.0 2.67 4.19 4.59 5.54

SP1104AT7(Z)(ZG) SM564SDT-E 4 10.0 2.6-12.0 2.79 3.58 4.06 5.00 11.2 2.4-14.0 2.67 4.19 4.59 5.54

Standard duct

SP1104AT8(Z)(ZG)-E SM566BTP-E 4 10.0 2.6-12.0 2.64 3.79 4.30 5.71 11.2 2.4-15.6 2.77 4.04 4.44 5.33

SP1104AT7(Z)(ZG) SM566BTP-E 4 10.0 2.6-12.0 2.64 3.79 4.30 5.71 11.2 2.4-15.6 2.77 4.04 4.44 5.33

SP1404AT8(Z)(ZG)-E SM806BTP-E 5 12.5 2.6-14.0 3.86 3.24 3.68 4.88 14.0 2.4-18.0 3.67 3.81 4.18 5.09

SP1404AT7(Z)(ZG) SM806BTP-E 5 12.5 2.6-14.0 3.86 3.24 3.68 4.88 14.0 2.4-18.0 3.67 3.81 4.18 5.09

SP1604AT8(Z)(ZG)-E SM806BTP-E 6 14.0 2.6-16.0 4.65 3.01 3.41 4.90 16.0 2.4-19.0 4.60 3.48 3.82 4.98

SP1604AT7(Z)(ZG) SM806BTP-E 6 14.0 2.6-16.0 4.65 3.01 3.41 4.90 16.0 2.4-19.0 4.60 3.48 3.82 4.98

Ceiling

SP1104AT8(Z)(ZG)-E SM567CTP-E 4 10.0 2.6-12.0 2.37 4.22 4.62 5.21 11.2 2.4-14.0 2.53 4.43 4.57 4.79

SP1104AT7(Z)(ZG) SM567CTP-E 4 10.0 2.6-12.0 2.37 4.22 4.62 5.21 11.2 2.4-14.0 2.53 4.43 4.57 4.79

SP1404AT8(Z)(ZG)-E SM807CTP-E 5 12.5 2.6-14.0 3.72 3.36 3.82 5.08 14.0 2.4-18.0 3.56 3.93 4.31 5.22

SP1404AT7(Z)(ZG) SM807CTP-E 5 12.5 2.6-14.0 3.72 3.36 3.82 5.08 14.0 2.4-18.0 3.56 3.93 4.31 5.22

SP1604AT8(Z)(ZG)-E SM807CTP-E 6 14.0 2.6-16.0 4.50 3.11 3.53 5.07 16.0 2.4-19.0 4.31 3.71 4.08 5.33

SP1604AT7(Z)(ZG) SM807CTP-E 6 14.0 2.6-16.0 4.50 3.11 3.53 5.07 16.0 2.4-19.0 4.31 3.71 4.08 5.33

High wall

SP1104AT8(Z)(ZG)-E SM566KRT-E 4 10.0 2.6-12.0 2.92 3.42 4.02 4.91 11.2 2.4-14.0 2.85 3.93 4.13 4.41

SP1104AT7(Z)(ZG) SM566KRT-E 4 10.0 2.6-12.0 2.92 3.42 4.02 4.91 11.2 2.4-14.0 2.85 3.93 4.13 4.41

SP1404AT8(Z)(ZG)-E SM806KRT-E 5 12.3 2.6-13.5 4.00 3.08 3.61 4.41 14.0 2.4-18.0 3.88 3.61 3.97 4.24

SP1404AT7(Z)(ZG) SM806KRT-E 5 12.3 2.6-13.5 4.00 3.08 3.61 4.41 14.0 2.4-18.0 3.88 3.61 3.97 4.24

SP1604AT8(Z)(ZG)-E SM806KRT-E 6 14.0 2.6-16.0 5.10 2.75 3.22 3.93 16.0 2.4-19.0 4.88 3.28 3.60 3.86

SP1604AT7(Z)(ZG) SM806KRT-E 6 14.0 2.6-16.0 5.10 2.75 3.22 3.93 16.0 2.4-19.0 4.88 3.28 3.60 3.86

Indoor unit type

Outdoor unit (RAV-)

Indoor unit (RAV-) HP

Cooling Capacity EER Heating Capacity COP

Rated (kW)

min-max (kW)

Power consumption (kW) 100% 80% 50% Rated

(kW)min-max

(kW)Power consumption

(kW) 100% 80% 50%

Trip

le s

yste

m: S

up

er D

igita

l In

vert

er 3

-ph

ase Compact

4-way cassette

SP1604AT8(Z)(ZG)-E SM564MUT-E 6 14.0 2.6-16.0 4.99 2.81 3.18 4.58 16.0 2.4-19.0 4.60 3.48 3.82 5.00

SP1604AT7(Z)(ZG) SM564MUT-E 6 14.0 2.6-16.0 4.99 2.81 3.18 4.58 16.0 2.4-19.0 4.60 3.48 3.82 5.00

4-way cassetteSP1604AT8(Z)(ZG)-E SM564UTP-E 6 14.0 2.6-16.0 4.49 3.12 3.53 5.07 16.0 2.4-19.0 4.30 3.72 4.09 5.33

SP1604AT7(Z)(ZG) SM564UTP-E 6 14.0 2.6-16.0 4.49 3.12 3.53 5.07 16.0 2.4-19.0 4.30 3.72 4.09 5.33

Slim ductSP1604AT8(Z)(ZG)-E SM564SDT-E 6 14.0 2.6-16.0 4.99 2.81 3.18 5.00 16.0 2.4-19.0 4.60 3.48 3.18 5.00

SP1604AT7(Z)(ZG) SM564SDT-E 6 14.0 2.6-16.0 4.99 2.81 3.18 5.00 16.0 2.4-19.0 4.60 3.48 3.18 5.00

Standard ductSP1604AT8(Z)(ZG)-E SM566BTP-E 6 14.0 2.6-16.0 4.65 3.01 3.41 4.90 16.0 2.4-19.0 4.60 3.48 3.82 4.98

SP1604AT7(Z)(ZG) SM566BTP-E 6 14.0 2.6-16.0 4.65 3.01 3.41 4.90 16.0 2.4-19.0 4.60 3.48 3.82 4.98

CeilingSP1604AT8(Z)(ZG)-E SM567CTP-E 6 14.0 2.6-16.0 4.50 3.11 3.53 5.07 16.0 2.4-19.0 4.31 3.71 4.08 5.33

SP1604AT7(Z)(ZG) SM567CTP-E 6 14.0 2.6-16.0 4.50 3.11 3.53 5.07 16.0 2.4-19.0 4.31 3.71 4.08 5.33

High wallSP1604AT8(Z)(ZG)-E SM566KRT-E 6 14.0 2.6-16.0 5.10 2.75 3.22 3.93 16.0 2.4-19.0 4.88 3.28 3.60 3.86

SP1604AT7(Z)(ZG) SM566KRT-E 6 14.0 2.6-16.0 5.10 2.75 3.22 3.93 16.0 2.4-19.0 4.88 3.28 3.60 3.86

13

4-way cassette type

Packing A

Air dischargeparts A

Refrigerantpipingside

Drain pipingside

Packing B

Packing BAir dischargeparts B

Air dischargeparts C

Air discharge direction kit

TCB-BC1602UE

Air inlet grille

Panel

Fresh air inlet box

Spacer for height adjustment

RBC-U31PGP(W)-ERBC-U31PGP(WS)-E

TCB-SP1602UE

TCB-GB1602UE

TCB-GFC1602UETCB-FF101URE2

Spacer for height adjustment

RBC-U31PGP(W)-E

RBC-U31PGP(WS)-E

1394

694

994

Standard duct type

TCB-SF56C6BPE

TCB-SF80C6BPE

TCB-SF160C6BPE

Model

SM406BTP-E, SM456BTP-E, SM566BTP-E

SM806BTP-E

Compatible (RAV-)

SM1106BTP-E, SM1406BTP-E

TCB-SF56C6BPETCB-SF80C6BPETCB-SF160C6BPE

(Unit:mm)

Ceiling type

Drain pump kit

Elbow piping

TCB-KP13CE, TCB-KP23CE

TCB-DP31CE

RBC-AX33CEWireless remote controller

TCB-PCUC1E

Optional connecting kit

Options

14

Parts Name Model Name Applied Model Remarks

Controllers

Wired remote controller

RBC-AMT32E All indoor units

RBC-AMS41E All indoor units

RBC-AMS51E-ES/-EN All indoor units

Simple wired remote controller RBC-AS41E All indoor units

Wireless remote controller kits

RBC-AX32U(W)/(WS)-E 4-way cassette

RBC-AX33CE Ceiling

TCB-AX32E2 All indoor units

Remote controller kits

TCB-EXS21TLE - Use with wired remote controller

TCB-CC163TLE2 - Use with wired remote controller

TCB-SC642TLE2 All indoor units

BMS-CM1280TLE All indoor units

TCC-Link TCB-PCNT30TLE2 All indoor units except High-wall

Accessories

Fresh air inlet box TCB-GB1602UE4-way cassette

Use with TCB-GFC1602UE

Fresh air filter chamber TCB-GFC1602UE

Auxiliary fresh air flange TCB-FF101URE2 4-way cassette, compact 4-way cassette and Slim duct

Spacer for height adjustment TCB-SP1602UE 4-way cassette

Air discharge direction kit TCB-BC1602UE 4-way cassette

Drain pump kit TCB-DP31CE Ceiling Use with TCB-KP13CE, TCB-KP23CE

Elbow piping kitTCB-KP13CE Ceiling

TCB-KP23CE Ceiling

Optional connecting kit TCB-PCUC1E Ceiling

Branch kit

RBC-TWP30E2Super Digital Inverter 1-phase, 3-phase model

RBC-TWP50E2

RBC-TRP100E "1:3" Triple system of Super Digital Inverter 3-phase model

Application controlTCB-PCOS1E2

Super Digital Inverter 1-phase modelTCB-KBOS2E

Features

Features Applied Model

Comfort

Inverter Allows step-less regulation of the air-conditioner’s power,which reduces energy consumption and improves comfort.

All indoor units

Individual Louver control Enables airflows to be chosen according to user preferences. 4-way cassette

Auto-turn Louver Air outlet grilles move automatically to fill every corner of the room with warm or cool air.

All indoor units except Slim duct and Standard duct

Automatic Air Volume control Depending on the difference between the room temperature and the set temperature, switches automatically between High, Low and Very Low.

All indoor units

Long-life Filter Built-in long-life filter makes maintenance easier. All indoor units except High wall

Hot Start When using the heater for preheating or defrosting, stops the indoor fan to prevent cold air from being blown into the room.

All indoor units

Dry Gradually dehumidifies the room to create even greater comfort. All indoor units

Operativity

Filter Sign Automatic displays on the remote controller say when to perform maintenance for the indoor unit filter.

All indoor units except High wall

Limit Timer Uses a 168-hour timer with three modes - “ON timer”, “OFF timer” and “Repeat OFF timer”.

All indoor units except High wall

On/Off Timer The operation start and stop times can be set with a digital clock.

High wall

20 minutes of fan operation after shut down

20 minutes of fan operation after shut down dries the moist air and helps reduce mold formation on heat exchanger coils.

High wall

Installation

Cooler Compatible with an Outdoor Temperature of -15°C

Stable cooler operation is possible when the outdoor temperature is as low as -15 ° C.

All indoor units

Built-in Drain Pump The built-in drain pump makes draining easier. (In the ceiling cassette type, it is built in to the main unit.)

All indoor units except High wall

Controllers & Accessories

15

Remote controllers

RBC-AMT32E

Standard wired remote controller can be connected to a single indoor unit or a group of up to 8 indoor units. Power save operation limits the greatest current value.The remote controller allows error to be displayed while the protective device works or a error occurs.

Remote controller with weekly timer(7-day timer function)

Wired remote controller with clock display and a built in 7-day timer function, possible to program 8 functions for each day of the week. *The following items can be set in program: operation time, operation start/stop, operation mode, temperature setting, restriction on button operation

Standard Remote controller

RBC-AMS41E

RBC-AMS51E-ES RBC-AMS51E-EN

Wired remote controller with a built in 7-day timer-featuring a new multi-language,LCD display with backlight, energy saving options and a return back function.• Possibility to set and display the room name to easily set-up and monitor the working parameter.• New modern and desirable controller design with menu driven display.• Save mode by schedule timer to optimise energy consumption.• Room temperature display always available.• Two “Hot Keys” (F1, F2) for easy operation of air conditioner functions.• Easy to read layout including display of indoor unit model name and serial number.• Built-in backup power. Settings are kept in memory up to 72 hours in case of power failure.• Remote TA sensor available in controller.• Can be connected to a single indoor unit or a group of up to 8 indoor units.

Lite-Vision plus Remote Controller

Simple wired remote controller can be connected to a single indoor unit or a group of up to 8 indoor units.• Start/Stop• Temperature setting• Air flow changing• Check code display

RBC-AS41E

Simple wired remote controller

TCB-EXS21TLE

• Schedule timer mode– 6 programmings per day– Enabling 8 groups to be programmed– A maximum of 64 indoor units can be controlled– A maximum of 100 hours back-up power supply• Weekly timer mode– 7 types of weekly schedule and 3 programmings per day

Schedule timer

TCB-CC163TLE2

• Individual control of up to 16 indoor units.• Setting of simultaneous ON/OFF 3 times per day combined with the weekly timer.

ON-OFF controller

Central remote controller

TCB-SC642TLE2

• Individual control for max. 64 indoor units divided into 1 to 4 zone (Up to 16 indoor units for each zone)• Up to 16 outdoor header units are connectable• 4 types of central control settings to inhibit individual operation by remote controller can be selected• Usable with other central control devices(Max. 10 devices in one control circuit)• Two control mode selectivity(Central controller mode ) Remote controller mode• Setting of simultaneous ON/OFF 3 times per day combined with the weekly timer.

• OperationIndividual operation of 128 indoor units availableReturn Back OperationWeekly Schedule Operation*(ON/OFF)* Schedule timer necessary• MonitoringZone setting (64 zones x 2)Individual unit operation mode operation restrictionAlarm displayControl inputStatus output

Central remote controller

BMS-CM1280TLE

• Start/Stop • Changing mode • Temperature setting

RBC-AX32U(W)/(WS)-EIntegral receiver (For 4-way cassette)

RBC-AX33CEIntegral receiver(For ceiling)

TCB-AX32E2Sensor unit; Stand alone receiver(For 4-way cassette, Compact 4-way cassette (600 x 600), Ceiling, Duct type, High wall)

Wireless remote controller kit

• Air flow changing• Timer function Either “ON” time or “OFF” time or “CYCLIC” can be set how many 30 min. later ON or OFF is operated.• Control by 2 remote controllers is available.Two wireless remote controllers can operate one indoor unit. The indoor unit can then be operated separately from the two different locations.• Check code display

Toshiba refrigeration and air-conditioning units are designed and manufactured on the assumption that the product is used with a specific refrigerant suitable for each unit.

We have recently seen some cases where the type of refrigerant used is different from the one originally installed in the product. Such actions may cause mechanical defects, malfunctions, failures and in some cases result in a serious safety issue. Therefore do not install any refrigerant other than the one specified by Toshiba Carrier Corporation for its respective products.

The type of the refrigerant used for each of our products is shown in the accompanying owners manual, or on the product label attached on the product itself.

Toshiba Carrier Corporation shall not assume any liability for failures, malfunctions or safety in its products if the refrigerant used is different from the one specified.

Installation and the use of refrigerants not specified by Toshiba Carrier Corporation

SAFETY PRECAUTIONS

For operation:

• Before use, read through the operating instructions to ensure proper use.

Concerning the purpose for which the air conditioners are to be used

• The air conditioners presented in this catalogue are air conditioning/heating units to be used solely by general consumers.– Do not use these air conditioners for special applications such as for the storage of food items, animals, plants, precision machines or works

of art. Doing so may degrade the quality of the items.– Do not use these air conditioners for air-conditioning applications in vehicles or ships. Doing so may cause water and/or power leakages.

Precautions for using air conditioners

Concerning the automatic defrosting unit

When the outdoor air temperature drops, frost may form on the heat exchanger of the outdoor unit. In such cases, the automatic defrosting unit will be activated, and it will take 5 to 8 minutes for the heating operation to be restored.

Concerning the air conditioner's operating conditions and their selection

(1) Avoid using the air conditioner in the following locations.• Locations with acidic or alkaline atmospheres (locations at which

highly acidic or alkaline air is directly drawn in, such as in hot springs areas from which sulfur gases are given off, or where chemicals, vinegar, exhaust air from burners, etc., are given off) The heat exchangers and other parts may become corroded.

• Locations with atmospheres filled with coolant or other machine oil or steam exhaust (such as at food preparation factories or machine plants). The heat exchangers may corrode; frost may form as a result of heat exchanger malfunction; air conditioner operating performance may be compromised or condensation may form as a result of clogged filters; plastic parts may incur damage; heat-insulation materials may become separated, etc.

(2) Before using an air conditioner in any of the following locations, consult with your dealer or a qualified contractor.• Locations where vapors from edible oils are given off (such

as in bakeries or kitchens and restaurants that use edible oils) ...The air conditioner's operating performance may be compromised or condensation may form as a result of clogged filters, and the plastic parts may incur damage. In line with the prevailing conditions, take countermeasures such as tailoring the installation conditions in accordance with the conditions, using air conditioners designed for kitchens or oil guard filters, etc.

• Locations with disinfectant-induced chlorine atmospheres (water tanks, etc.) The metal parts in the heat exchangers, motors, etc., may become corroded.

• Locations with high salinity (coastal areas, etc.) Corrosion may occur so use outdoor units specifically designed to withstand exposure to salt.

• Locations where power is supplied from independent power generators. The power line frequency and/or voltage may fluctuate, possibly causing the air conditioner to malfunction.

• Locations where high frequencies or electrical noise is generated (from high-frequency welders used for vinyl welding and processing, high-frequency therapeutic devices used for thermotherapy, etc.) The electronic components may be adversely affected, possibly causing the air conditioner to malfunction.

• Locations where electronic equipment is installed. Electrical noise may adversely affect the operation of the electronic equipment.

(3) Concerning use in locations with high ceilings • In locations with high ceilings, use of circulators for improving

the temperature distribution during heating is recommended.

(4) Concerning use in high-humidity environments• When the ceiling-recessed type of indoor unit is installed in a

location, such as those described below, and it is very hot and humid inside the ceiling, condensation may form on the external surfaces of the indoor unit and drip down. In such cases, add external heat-insulating materials.– Locations such as food preparation sites in which the areas

above the ceilings are hot and humid– Locations in which outside air is drawn in and routed above the

ceiling– Above ceilings with a slate roof or tiled roof overhead

(5) Even when an air conditioner is shut down, it will still consume a small amount of power to protect the unit. If the air conditioner will not be used for a prolonged period, turn OFF the main switch (ground fault circuit breaker). However, before the unit is to be used again, turn ON the main switch (ground fault circuit breaker) for at least 12 hours in order to prevent trouble.

- Toshiba is committed to continuously improving its products to ensure the highest quality and reliability standards, and to meet local regulations and market requirements. All features and specifications are subject to change without prior notice.

- Products listed in this leaflet use HFC refrigerant R410A with a GWP of 2,088*. Notice:

*The GWP value is calculated based on information provided in the EU F-gas Regulation and IPCC Fourth Assessment Report.

T201511-LC-SDI