swgr presentation without animation
TRANSCRIPT
-
7/31/2019 Swgr Presentation Without Animation
1/86
PROTECTION ANDINTERLOCKING SCHEME OF
MV SWITCHGEAR
BY MURTAZA HUSSAINSR ENGR, SWE
-
7/31/2019 Swgr Presentation Without Animation
2/86
SWITCHGEAR IEC/IS
BHEL Manufacture Switchgear as per IEC:62271-100-
2001, IS:3427:1997/IEC:298:1990, IS:13118:1991/IEC:56:1987
IEC:62271-100-2001 High voltage alternating current circuit breaker.
IS:3427:1997/IEC:298:1990 AC Metal enclosed switchgear and Controlgearfor rated voltage above 1 kV & upto & including 52 kV.
IS:13118:1991/IEC:56:1987 Specification for High Voltage Alternatingcurrent circuit breaker.
-
7/31/2019 Swgr Presentation Without Animation
3/86
A MECHANICAL SWITCHING DEVICE CAPABLE OF MAKING,
CARRYING, AND BREAKING CURRENTS UNDER NORMAL CIRCUIT
CONDITIONS AND ALSO MAKING, CARRYING FOR A SPECIFIED TIME
AND BREAKING CURRENTS UNDER SPECIFIED ABNORMAL CIRCUIT
CONDITIONS SUCH AS THOSE OF SHORT CIRCUIT.
SWITCHGEAR
A GENERAL TERM COVERING SWITCHING DEVICES AND THEIR
COMBONATION WITH ASSOCIATED CONTROL, MEASUREING,PROTECTIVE AND REGULATING EQUIPMENT, ALSO ASSEMBLIES
OF SUCH DEVICES AND EQUIPMENT WITH ASSOCIATED
INTERCONNECTIONS, ACCESSORIES, ENCLOSURE AND
SUPPORTING STRUCTURES.
CIRCUIT BREAKER
-
7/31/2019 Swgr Presentation Without Animation
4/86
CHAMBERS IN SWITCHGEAR
Instrument Chamber
(Relay/meters/switchesetc.)
HT CHAMBER
LT CHAMBER
Breaker Chamber
Busbar Chamber
CT/PT Chamber
-
7/31/2019 Swgr Presentation Without Animation
5/86
LOCATION OF VARIOUS MAJOR
COMPONENTS IN SWITCHGEAR
Circuit Breaker
Current Transformer
Instruments
Potential Transformer
Surge Suppressor
Busbar
INSERT PICTURE
-
7/31/2019 Swgr Presentation Without Animation
6/86
-
7/31/2019 Swgr Presentation Without Animation
7/86
SWITCHGEAR IN POWER SYSTEM CAN ACT AS :
Line PT
Bus PT
Bus Coupler
Plant Feeder / Outgoing feeder
Transformer Feeder
Motor Feeder
TIE Feeder
Incomer Feeder
-
7/31/2019 Swgr Presentation Without Animation
8/86
Incomer Feeder: Switchgear Panel intended for supply power to the Switchboard.
TIE Feeder: Switchgear panel which connects the two same voltage levelswitchboard. Power can flow in either direction TIE feeder.
Motor Feeder: Switchgear panel employed for feeding the motor.
Plant / Outgoing Feeder: Switchgear panel employed for supply power to otherswitchboard.
Bus PT: Switchgear panel having voltage transformer and used for thedetection of bus voltage.
Feeder/Line PT: Switchgear panel having voltage transformer and used forthe detection of feeder/line side voltage.
Transformer Feeder: Switchgear panel employed for feeding the transformer.
-
7/31/2019 Swgr Presentation Without Animation
9/86
TIE INCOMER
LINE PT
BUSP
T
TRAF
OFDR
MOTOR
FDR
Typical Power Plant Single Line Diagram (SLD) (PART)
OUTGOING/PLANT FDR
-
7/31/2019 Swgr Presentation Without Animation
10/86
SWITCHGEAR INTERLOCK SCHEME
The major functions of switchgears are protection, control andfacilitating the maintenance of the electrical network including the
switchgear itself.Control and inter-locking schemes constitute a very important aspectof medium voltage switchgears. The switching operation involves avariety of control and inter-locking schemes.
Following are the variety of schemes which are being used:
Automatic supply transfer schemes.
Synchronizing schemes and
Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
11/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and
Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
12/86
SAFETY INTERLOCKS:
i) The VCB truck cannot be racked in or out unless circuit
breaker is in 'Open' condition.
ii) The VCB truck can not be racked in unless secondaryPlug & socket are engaged.
iii) The circuit breaker closing operation is not possible
Unless secondary plug & socket are engaged.
iv) The secondary plug and socket can not be disengaged When theVCB truck is in 'Service or any Intermediate position
between these two positions.
v) The circuit breaker closing operation is not possible unless thetruck is in 'Service' or 'Test' position.
vi) The interlock mechanism cannot be operated unless the circuitbreaker is in 'Open' condition.
-
7/31/2019 Swgr Presentation Without Animation
13/86
IX) Earthing Truck (Test to Service) Limit Switch
VIII) Provision for Earthing
Earthing feature & Interlock (operation of Earthing module)a) FEB Feeder Earthing Breakerb) BEB Bus Bar Earthing Breaker
VII) Inter changeability of trucks of different current ratings are notpossible.
-
7/31/2019 Swgr Presentation Without Animation
14/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and
Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
15/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and
Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
16/86
CLOSING CIRCUIT :
The closing circuit
consists of fuses, control
switch, anti pumping
device, spring chargedlimit switch & closing coil.
Closing command is
executed by control switch
through breaker NC
contact when spring is
charged. All auxiliaryswitch contacts position
changes i.e. NO contact
closes and NC contact
opens. The CB can beclosed manually by green
coloured manual closeknob provided in the
mechanism box.
-
7/31/2019 Swgr Presentation Without Animation
17/86
ANTI
PUMPING :
Anti pumpingdevice prevent theCB from gettingrepeated closingand trippingimpulses when a
continuous closingcommand is givenbefore the trippingimpulse iswithdrawn.
-
7/31/2019 Swgr Presentation Without Animation
18/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and
Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
19/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and
Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
20/86
Tripping Schemes
Shunt Tripping Schemes
Series Tripping Schemes
-
7/31/2019 Swgr Presentation Without Animation
21/86
SHUNT TRIPPING CIRCUIT :
The tripping circuit consists of fuses, control switch, protective relay & tripping coil. Breaker can beopened intentionally by control switch & on fault, breaker gets tripping command from relay. All aux.
switches will restore their original positions i.e. NO will open and NC will close.Note :The tripping spring gets charged while the closing spring isdischarged.
-
7/31/2019 Swgr Presentation Without Animation
22/86
Series Tripping Schemes
Using Relays
Using Summation CT
Using Motor Protection Circuit Breaker (MPCB)
Using Time Limit Fuses
-
7/31/2019 Swgr Presentation Without Animation
23/86
-
7/31/2019 Swgr Presentation Without Animation
24/86
-
7/31/2019 Swgr Presentation Without Animation
25/86
-
7/31/2019 Swgr Presentation Without Animation
26/86
PANEL ILLUMINATION :
40W filament lamp is provided
inside the instrument panel. Thedoor operated panel illumination
lamp gets automatically lighted
on opening the door.
3 PIN SOCKET& SWITCH:
5/15 Amps, 240 V, 5 Pin socket
with piano switch is also providedon the panel for hand lamp.
-
7/31/2019 Swgr Presentation Without Animation
27/86
ANTI CONDENSATION :
Two tubular heaters with
thermostat and piano switch
are provided for anti
condensation in breaker
chamber and CT chamber.
-
7/31/2019 Swgr Presentation Without Animation
28/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and
Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
29/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and
Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
30/86
Trip Circuit Supervision Schemes
The Trip circuit extends beyond the protection relay and othercomponents such as fuses, relay contacts, switches etc requiresconsiderable amount of circuit breaker wiring with intermediateterminal boards. These interconnections coupled with theimportance of the circuit, results in the requirement to monitor theintegrity of the circuit .
-
7/31/2019 Swgr Presentation Without Animation
31/86
-
7/31/2019 Swgr Presentation Without Animation
32/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and
Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
33/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and
Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
34/86
Voltage Selection Schemes
Voltage signals to instruments and meters mounted on switchgear panels
are derived from the potential transformer (PTs). These PTs are either Busconnected or Feeder connected. Incase of fault any source feeder,arrangement should be made in such a way that PT signal should beavailable to meters and instruments
Need for Voltage Selection scheme ?
-
7/31/2019 Swgr Presentation Without Animation
35/86
-
7/31/2019 Swgr Presentation Without Animation
36/86
-
7/31/2019 Swgr Presentation Without Animation
37/86
SWITCHGEAR INTERLOCK SCHEME
-
7/31/2019 Swgr Presentation Without Animation
38/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
SWITCHGEAR INTERLOCK SCHEME
-
7/31/2019 Swgr Presentation Without Animation
39/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
40/86
Alarm Schemes
Alarm Cancellation Scheme Alarm Annunciation Scheme
SWITCHGEAR INTERLOCK SCHEME
-
7/31/2019 Swgr Presentation Without Animation
41/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
SWITCHGEAR INTERLOCK SCHEME
-
7/31/2019 Swgr Presentation Without Animation
42/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
43/86
c) The phase difference of the two supplies must be within acceptable limits.
Synchronizing SchemesTo bring new bus (source) into the switchboard when old one is running
and shifting to new one.
To meet synchronizism that means two AC supplies are correctly paralleledfollowing condition should be satisfied.
A check synchronizing relay is used to prevent inter-connection of two badlysynchronized supplied. Its dual purpose is to Safeguard manualsynchronizing.
Methods adopted for synchronization are :
Manual Synchronization
By Check Synchronizing Relays
a) The voltages of the two supplies must be within acceptable limits.
b) The frequencies of the two supplies must be within acceptable limits.
-
7/31/2019 Swgr Presentation Without Animation
44/86
-
7/31/2019 Swgr Presentation Without Animation
45/86
-
7/31/2019 Swgr Presentation Without Animation
46/86
AUTO SYNCHRONIZING
SWITCHGEAR INTERLOCK SCHEME
-
7/31/2019 Swgr Presentation Without Animation
47/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
SWITCHGEAR INTERLOCK SCHEME
-
7/31/2019 Swgr Presentation Without Animation
48/86
SWITCHGEAR INTERLOCK SCHEME
Automatic supply transfer schemes.
Synchronizing schemes and Alarm schemes,
Voltage selection schemes;
Trip circuit supervision schemes;
Tripping schemes;
Closing Scheme;
Safety Interlocks & schemes using position limit switches;
-
7/31/2019 Swgr Presentation Without Animation
49/86
Automatic Supply Transfer SchemesRequirement of Automatic Bus Transfer Scheme ?
Unit Switchgear
Station Switchgear
-
7/31/2019 Swgr Presentation Without Animation
50/86
Modes of Bus Transfer
A. Manual Bus Transfer
i) Without Voltage Interruption
ii) With Voltage Interruption
a) Slow changeover
b) Fast changeover
B. Automatic Bus Transfer (under fault condition) with Voltage Interruption
a) Slow changeover
b) Fast changeover
El i l I l k
-
7/31/2019 Swgr Presentation Without Animation
51/86
Electrical Interlockin Closing Circuit
Electrical Interlockin Tripping Circuit
Electrical Interlocking scheme is guided by the logic diagram.
Protection Schemes for Medium Voltage Switchgear
-
7/31/2019 Swgr Presentation Without Animation
52/86
Protection Schemes for Medium Voltage Switchgear
Importance of Protection System in Electrical System ?
5-S Principles
Security : Protective system should be reliable so that security of supply is ensured.
Sensitivity : Protective system should be able to sense minimum value of faultcurrent, thereby reducing the consequent damage.
Speed : Protective system should be able to isolate fault in the shortest possibletime.
Selectivity : Protective system should be able to select and trip only the nearestcircuit breaker.
Stability : Protective system should not operate for external faults.
FAULT : It is defined as any abnormal condition, which causes reduction in thebasic insulation level strength of system.
FAULT DETECTION : POSITIVE, NEGATIVE & ZERO Phase sequence
component of system.
PROTECTION SCHEMES IN MV SWITCHGEAR
-
7/31/2019 Swgr Presentation Without Animation
53/86
PROTECTION SCHEMES IN MV SWITCHGEAR
Non Directional Over Current for Phase Faults (50/51)
Non Directional Over Current for Earth Fault (50N/51N)
Directional Over Current for Phase Faults (67)
Directional Over Current for Earth Fault (67N)
-
7/31/2019 Swgr Presentation Without Animation
54/86
UNIT PROTECTION SCHEME
- Pilot Wire Protection Scheme
- Bus Differential Protection Scheme
- Motor/ Transformer Differential Protection Scheme
- Restricted Earth Protection Scheme
In Unit Protection sections of power system are protected individually asa complete unit without reference to other section.
Some of the Unit scheme which MV Switchgear employed
For the protection of CABLE connecting two Feeder
For the protection of BUSBAR
For the protection of MOTOR/ TRANSFORMER WINDINGS
For the protection of TRANSFORMER WINDINGS
-
7/31/2019 Swgr Presentation Without Animation
55/86
TRANSFORMER PROTECTION
Non- Directional Over Current and Earth Fault Protection(50/51/50N/51N)
Sensitive Earth Fault Protection (50N/2)
Differential Protection (87T)
Restricted Earth Fault Protection (64R)
Incipient Faults (49/63TX)
-
7/31/2019 Swgr Presentation Without Animation
56/86
MOTOR PROTECTION
Wide range of A.C Motors
Motor characteristics due to various duties
All Motor needs protection and choice should
be independent of a type of motor & loadconnected.
O OT CT O
-
7/31/2019 Swgr Presentation Without Animation
57/86
NEED FOR PROTECTION
Allowing operation under normal conditions.
Quick isolation from supply under abnormalconditions.
Averting damage to the motor & drivenmechanism.
Enhancement of life of motor.
MOTOR PROTECTION
-
7/31/2019 Swgr Presentation Without Animation
58/86
MOTOR PROTECTIONA. MOTOR INDUCED
B. LOAD INDUCED
C. ENVIRONMENT INDUCED
D. SOURCE OR SYSTEM INDUCED
E. OPERATION AND APPLICATION INDUCED
1. INSULATION FAILURE
2. BEARING FAILURE
3. MECHANICAL FAILURE
4. LOSS OF FIELD (SYNCHRONOUS MOTOR)
1. OVERLOAD/ UNDERLOAD
2. JAMMING
3. HIGH INERTIA
1. HIGH AMBIENT TEMPERATURE2. HIGH CONTAMINATED LEVEL-BLOCKED VENTILATION
3. COLD, DAMP AMBIENT TEMPERATURE
1. PHASE FAILURE
2. OVER VOLTAGE/UNDER VOLTAGE
3. PHASE REVERSAL
4. OUT-OF-STEP
1. SYNCHRONIZING, CLOSING OR RECLOSING OUT OF PHASE
2. HIGH DUTY CYCLE
3. JOGGING
MOTOR PROTECTION
-
7/31/2019 Swgr Presentation Without Animation
59/86
MOTOR PROTECTION
Thermal Over Load protection (49)
Single phasing/Negative Phase Sequence Protection (46)
Short-circuits between phases or between phase and earth in themotor winding or its connections. (50/51)
Partial or complete collapse of voltage (27)
Locked rotor (51S)
Start or Stall Protection(48/51LR)
Earth Fault Protection (50N)
Loss-Of-Load Protection (37)
Out of Step Protection (46)
RTD/BTD Protection (26)
Limitation of the number of start, Time between start (66)
-
7/31/2019 Swgr Presentation Without Animation
60/86
EXPECTATIONS FROM MODERN MOTOR PROTECTIONRELAYS:
1. The design of a modern motor protection relay must beadequate to cater for the protection needs of any one of the vastrange of motor designs in service and many of designs havingno permissible allowance for overload.
2. The relay should ideally be matched with the motorcharacteristics and be capable of close sustained overloadprotection, a wide range of relay adjustment id desirabletogether with good accuracy & low thermal overshoot.
3. Relay curves should take into account the extremes of zero pre-fault current known as the COLD condition & full rated currentpre-fault known as HOT condition.
-
7/31/2019 Swgr Presentation Without Animation
61/86
PROTECTION AGAINST SWITCHING SURGES
-
7/31/2019 Swgr Presentation Without Animation
62/86
PROTECTION AGAINST SWITCHING SURGES:
What is an Electrical Surge ?
External surge & Internal surge
Atmospheric Lightning cause External surge
Switching action of devices cause internal surge
CAUSES OF SURGE GENERATION:
Normal Switching On of a stationary motor.
Normal switching Off of a stationary motor.
Switching a Stalled motor or one running upto speed.
PROTECTION AGAINST
-
7/31/2019 Swgr Presentation Without Animation
63/86
PROTECTION AGAINST
SWITCHING SURGES:
SURGE PROTECTION DEVICES:These devices limits the over voltages in electrical system to the specified protection
level, principally lower than the withstand voltage of equipment. a/ C-R type surge suppressors.
b/ ZnO type surge arrestors.
IOCL SPECIFIC SCHEMES
-
7/31/2019 Swgr Presentation Without Animation
64/86
IOCL SPECIFIC SCHEMES
BUS DIFFERENTIAL
MOTOR RE-ACCELERATION
PILOT WIRE PROTECTION
TWO OUT OF THREE BREAKER SCHEME
MOTOR DIFFERENTIAL
-
7/31/2019 Swgr Presentation Without Animation
65/86
THANKYOU
-
7/31/2019 Swgr Presentation Without Animation
66/86
-
7/31/2019 Swgr Presentation Without Animation
67/86
-
7/31/2019 Swgr Presentation Without Animation
68/86
-
7/31/2019 Swgr Presentation Without Animation
69/86
-
7/31/2019 Swgr Presentation Without Animation
70/86
-
7/31/2019 Swgr Presentation Without Animation
71/86
-
7/31/2019 Swgr Presentation Without Animation
72/86
-
7/31/2019 Swgr Presentation Without Animation
73/86
Differential relay for bus bar protection can be implemented in one of the following three ways:1.Sample by sample comparison. 2.Comparison of current phasors. 3.High impedance busdifferential relay The main difficulty in bus differential protection is that significant differential
-
7/31/2019 Swgr Presentation Without Animation
74/86
differential relay. The main difficulty in bus differential protection is that significant differentialcurrent may appear due to saturation of CT on external fault. When a CT saturates, its secondarycurrent is not scaled replica of primary current. Therefore, sum of CT secondary current is notequal to sum of primary currents even though primary CT currents sum to zero.
This causes a differential relay to operate on even external faults, leading to maloperation of bus
protection scheme. This compromises security and is not acceptable. While the percentagedifferential can provide security against normal CT errors due to mismatch of CT turns ratio andmagnetization current; it is not adequate to handle severe CT saturation problem. So the relevantquestions to be asked now are: (1)How was this problem handled in the past, i.e. in the era priorto numerical relays? (2)How do numerical relays cope with this problem? High Impedance BusDifferential Relay This approach has been the most successful with traditional electromechanical and solid state relay. It is based upon the following ingenious and innovative thinking.If you cannot beat CT saturation, exploit it! In fact this is now a well accepted principle in theory ofsystematic innovation, also known as TRIZ (a Russian acronym), that one innovative way to
problem solving is to exploit the harm:
If you cannot undo the harm, stretch the harm to the extreme and then exploit it to youradvantage".Recall that when a CT core saturates, it behaves more like an air core device. The couplingbetween the primary and secondary winding is negligible. The impedance now offered by the CTas seen from the CT secondary terminals is very low and it equals the impedance of the CTsecondary winding. The CT is no more a current source with high impedance shunt. Rather, it is aplain low impedance path. Thus, if we increase the impedance of the relay element which was tocarry the differential current significantly, then sum of all the CT secondary currents (except forthe saturated CT) will be diverted into the low impedance path of saturated CT's secondary.Therefore, differential current would be negligible and hence protection system will not operate(See fig 38.6).Thus, now saturation of CT itself is responsible for saving a false operation.
In contrast, numerical relays offer a low impedance path. Hence, thisscheme of differential bus bar protection cannot be emulated with
-
7/31/2019 Swgr Presentation Without Animation
75/86
scheme of differential bus bar protection cannot be emulated withnumerical relays. Therefore, with numerical relays the busbar protectionhas to be very fast. i.e preferably decision making has to be completedbefore the CT saturates. Recall that saturation of CT is primarily aconsequence of DC offset current. The time for CT core saturation also
depends upon time constant (L/R) of transmission line. If the protectionsystem could reach trip decision before the onset of CT core saturation,then it would be reliable. Hence, numerical relaying based bus barprotection is expected to operate in quarter of a cycle. Development ofsuch protection scheme requires ingenuity because of the well knownspeed vs accuracy conflict. Non linear % Differential Characteristics Ifthe CT core saturation factor could be discounted for, then we could
use constant % differential characteristic for bus bar differentialprotection. We model a CT as scaled current source due totransformation ratio in parallel with magnetizing impedance (Norton'sequivalent). However, the magnetizing impedance itself is nonlinear. Itis large when CT core is not saturated and small when CT core issaturated. The current in this branch directly contributes to thedifferential current.
This suggests that % differential characteristics should be modified tohave higher slopes to take care of CT saturation A fast protection
-
7/31/2019 Swgr Presentation Without Animation
76/86
have higher slopes to take care of CT saturation. A fast protectionscheme can be devised by instantaneous sample based differentialprotection scheme. In contrast, a phasor summation scheme will beinherently slower as correct phasor estimates will have to wait until themoving window is totally populated with post fault current samples. Oneway out of this imbroglio is to use a smaller data window (e.g. 3 samplewindow). On the other hand, the comparison scheme basedcomputation of instantaneous samples can be error prone due to noisetransient related problem. To obtain reliability, it is necessary thatconsistent differential current should be obtained. A transient monitorfunction can be used to check that. A transient counter is initialized tozero. If a fault is detected due to presence of differential current, thencounter is incremented. Conversely, if counter is greater than zero, andno fault is detected (small enough differential current magnitude) thencounter is decremented. If the counter crosses a preset threshold value,trip decision is implemented. This scheme will not trip on transient.
However, in addition to internal faults, it will also trip on external fault.For this purpose, the differential protection relay also has to have aninbuilt feature to detect CT saturation. One way to detect CT coresaturation is based on measuring current change in consecutivesamples with the expected sinusoidal signal model. A change muchbeyond the expected change in sinusoidal model indicates CT coresaturation. Many more innovative schemes can be thought out to detectCT saturation which is beyond the scope of this lecture.
-
7/31/2019 Swgr Presentation Without Animation
77/86
-
7/31/2019 Swgr Presentation Without Animation
78/86
-
7/31/2019 Swgr Presentation Without Animation
79/86
-
7/31/2019 Swgr Presentation Without Animation
80/86
-
7/31/2019 Swgr Presentation Without Animation
81/86
-
7/31/2019 Swgr Presentation Without Animation
82/86
-
7/31/2019 Swgr Presentation Without Animation
83/86
-
7/31/2019 Swgr Presentation Without Animation
84/86
NEED OF STABILIZING RESISTOR & METROSIL
-
7/31/2019 Swgr Presentation Without Animation
85/86
IN HIGH IMPEDENCE CIRCUIT
Stabilizing resistor are used to Limit the heavy fault current to safevalue for relays
Metrosil are used to limit voltage drop across the relays
HIGH & LOW IMPEDENCE CIRCUITS
-
7/31/2019 Swgr Presentation Without Animation
86/86
HIGH & LOW IMPEDENCE CIRCUITS
The high impedance protection is "more sensitive" compared tolow impedance protection. Apart from that high impedanceprotection is faster that of low impedance protection. But this is atthe cost of high CT requirements like same CT ratio and high CTknee point voltage requirement. More over to make theprotection stable for thro fault, we need to consider stabilising
resistor and metrosil. Another alternative to high impendence differential protection is
using low impedance protection. It involves comparatively lesscomplexity than that of High impedance protection as it does notrequire any external component like stabilising resistor / metrosil.Here the thro fault stability is achieved thro biasing technique.
When compared to high impedance low impedance will be bitslower, but the CT requirement is less as it can be used withdifference CT ratios with 5P class of CT's and comparativelyless Vk requirement.