swgr presentation without animation

Upload: sam

Post on 05-Apr-2018

231 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 Swgr Presentation Without Animation

    1/86

    PROTECTION ANDINTERLOCKING SCHEME OF

    MV SWITCHGEAR

    BY MURTAZA HUSSAINSR ENGR, SWE

  • 7/31/2019 Swgr Presentation Without Animation

    2/86

    SWITCHGEAR IEC/IS

    BHEL Manufacture Switchgear as per IEC:62271-100-

    2001, IS:3427:1997/IEC:298:1990, IS:13118:1991/IEC:56:1987

    IEC:62271-100-2001 High voltage alternating current circuit breaker.

    IS:3427:1997/IEC:298:1990 AC Metal enclosed switchgear and Controlgearfor rated voltage above 1 kV & upto & including 52 kV.

    IS:13118:1991/IEC:56:1987 Specification for High Voltage Alternatingcurrent circuit breaker.

  • 7/31/2019 Swgr Presentation Without Animation

    3/86

    A MECHANICAL SWITCHING DEVICE CAPABLE OF MAKING,

    CARRYING, AND BREAKING CURRENTS UNDER NORMAL CIRCUIT

    CONDITIONS AND ALSO MAKING, CARRYING FOR A SPECIFIED TIME

    AND BREAKING CURRENTS UNDER SPECIFIED ABNORMAL CIRCUIT

    CONDITIONS SUCH AS THOSE OF SHORT CIRCUIT.

    SWITCHGEAR

    A GENERAL TERM COVERING SWITCHING DEVICES AND THEIR

    COMBONATION WITH ASSOCIATED CONTROL, MEASUREING,PROTECTIVE AND REGULATING EQUIPMENT, ALSO ASSEMBLIES

    OF SUCH DEVICES AND EQUIPMENT WITH ASSOCIATED

    INTERCONNECTIONS, ACCESSORIES, ENCLOSURE AND

    SUPPORTING STRUCTURES.

    CIRCUIT BREAKER

  • 7/31/2019 Swgr Presentation Without Animation

    4/86

    CHAMBERS IN SWITCHGEAR

    Instrument Chamber

    (Relay/meters/switchesetc.)

    HT CHAMBER

    LT CHAMBER

    Breaker Chamber

    Busbar Chamber

    CT/PT Chamber

  • 7/31/2019 Swgr Presentation Without Animation

    5/86

    LOCATION OF VARIOUS MAJOR

    COMPONENTS IN SWITCHGEAR

    Circuit Breaker

    Current Transformer

    Instruments

    Potential Transformer

    Surge Suppressor

    Busbar

    INSERT PICTURE

  • 7/31/2019 Swgr Presentation Without Animation

    6/86

  • 7/31/2019 Swgr Presentation Without Animation

    7/86

    SWITCHGEAR IN POWER SYSTEM CAN ACT AS :

    Line PT

    Bus PT

    Bus Coupler

    Plant Feeder / Outgoing feeder

    Transformer Feeder

    Motor Feeder

    TIE Feeder

    Incomer Feeder

  • 7/31/2019 Swgr Presentation Without Animation

    8/86

    Incomer Feeder: Switchgear Panel intended for supply power to the Switchboard.

    TIE Feeder: Switchgear panel which connects the two same voltage levelswitchboard. Power can flow in either direction TIE feeder.

    Motor Feeder: Switchgear panel employed for feeding the motor.

    Plant / Outgoing Feeder: Switchgear panel employed for supply power to otherswitchboard.

    Bus PT: Switchgear panel having voltage transformer and used for thedetection of bus voltage.

    Feeder/Line PT: Switchgear panel having voltage transformer and used forthe detection of feeder/line side voltage.

    Transformer Feeder: Switchgear panel employed for feeding the transformer.

  • 7/31/2019 Swgr Presentation Without Animation

    9/86

    TIE INCOMER

    LINE PT

    BUSP

    T

    TRAF

    OFDR

    MOTOR

    FDR

    Typical Power Plant Single Line Diagram (SLD) (PART)

    OUTGOING/PLANT FDR

  • 7/31/2019 Swgr Presentation Without Animation

    10/86

    SWITCHGEAR INTERLOCK SCHEME

    The major functions of switchgears are protection, control andfacilitating the maintenance of the electrical network including the

    switchgear itself.Control and inter-locking schemes constitute a very important aspectof medium voltage switchgears. The switching operation involves avariety of control and inter-locking schemes.

    Following are the variety of schemes which are being used:

    Automatic supply transfer schemes.

    Synchronizing schemes and

    Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    11/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and

    Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    12/86

    SAFETY INTERLOCKS:

    i) The VCB truck cannot be racked in or out unless circuit

    breaker is in 'Open' condition.

    ii) The VCB truck can not be racked in unless secondaryPlug & socket are engaged.

    iii) The circuit breaker closing operation is not possible

    Unless secondary plug & socket are engaged.

    iv) The secondary plug and socket can not be disengaged When theVCB truck is in 'Service or any Intermediate position

    between these two positions.

    v) The circuit breaker closing operation is not possible unless thetruck is in 'Service' or 'Test' position.

    vi) The interlock mechanism cannot be operated unless the circuitbreaker is in 'Open' condition.

  • 7/31/2019 Swgr Presentation Without Animation

    13/86

    IX) Earthing Truck (Test to Service) Limit Switch

    VIII) Provision for Earthing

    Earthing feature & Interlock (operation of Earthing module)a) FEB Feeder Earthing Breakerb) BEB Bus Bar Earthing Breaker

    VII) Inter changeability of trucks of different current ratings are notpossible.

  • 7/31/2019 Swgr Presentation Without Animation

    14/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and

    Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    15/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and

    Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    16/86

    CLOSING CIRCUIT :

    The closing circuit

    consists of fuses, control

    switch, anti pumping

    device, spring chargedlimit switch & closing coil.

    Closing command is

    executed by control switch

    through breaker NC

    contact when spring is

    charged. All auxiliaryswitch contacts position

    changes i.e. NO contact

    closes and NC contact

    opens. The CB can beclosed manually by green

    coloured manual closeknob provided in the

    mechanism box.

  • 7/31/2019 Swgr Presentation Without Animation

    17/86

    ANTI

    PUMPING :

    Anti pumpingdevice prevent theCB from gettingrepeated closingand trippingimpulses when a

    continuous closingcommand is givenbefore the trippingimpulse iswithdrawn.

  • 7/31/2019 Swgr Presentation Without Animation

    18/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and

    Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    19/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and

    Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    20/86

    Tripping Schemes

    Shunt Tripping Schemes

    Series Tripping Schemes

  • 7/31/2019 Swgr Presentation Without Animation

    21/86

    SHUNT TRIPPING CIRCUIT :

    The tripping circuit consists of fuses, control switch, protective relay & tripping coil. Breaker can beopened intentionally by control switch & on fault, breaker gets tripping command from relay. All aux.

    switches will restore their original positions i.e. NO will open and NC will close.Note :The tripping spring gets charged while the closing spring isdischarged.

  • 7/31/2019 Swgr Presentation Without Animation

    22/86

    Series Tripping Schemes

    Using Relays

    Using Summation CT

    Using Motor Protection Circuit Breaker (MPCB)

    Using Time Limit Fuses

  • 7/31/2019 Swgr Presentation Without Animation

    23/86

  • 7/31/2019 Swgr Presentation Without Animation

    24/86

  • 7/31/2019 Swgr Presentation Without Animation

    25/86

  • 7/31/2019 Swgr Presentation Without Animation

    26/86

    PANEL ILLUMINATION :

    40W filament lamp is provided

    inside the instrument panel. Thedoor operated panel illumination

    lamp gets automatically lighted

    on opening the door.

    3 PIN SOCKET& SWITCH:

    5/15 Amps, 240 V, 5 Pin socket

    with piano switch is also providedon the panel for hand lamp.

  • 7/31/2019 Swgr Presentation Without Animation

    27/86

    ANTI CONDENSATION :

    Two tubular heaters with

    thermostat and piano switch

    are provided for anti

    condensation in breaker

    chamber and CT chamber.

  • 7/31/2019 Swgr Presentation Without Animation

    28/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and

    Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    29/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and

    Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    30/86

    Trip Circuit Supervision Schemes

    The Trip circuit extends beyond the protection relay and othercomponents such as fuses, relay contacts, switches etc requiresconsiderable amount of circuit breaker wiring with intermediateterminal boards. These interconnections coupled with theimportance of the circuit, results in the requirement to monitor theintegrity of the circuit .

  • 7/31/2019 Swgr Presentation Without Animation

    31/86

  • 7/31/2019 Swgr Presentation Without Animation

    32/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and

    Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    33/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and

    Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    34/86

    Voltage Selection Schemes

    Voltage signals to instruments and meters mounted on switchgear panels

    are derived from the potential transformer (PTs). These PTs are either Busconnected or Feeder connected. Incase of fault any source feeder,arrangement should be made in such a way that PT signal should beavailable to meters and instruments

    Need for Voltage Selection scheme ?

  • 7/31/2019 Swgr Presentation Without Animation

    35/86

  • 7/31/2019 Swgr Presentation Without Animation

    36/86

  • 7/31/2019 Swgr Presentation Without Animation

    37/86

    SWITCHGEAR INTERLOCK SCHEME

  • 7/31/2019 Swgr Presentation Without Animation

    38/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

    SWITCHGEAR INTERLOCK SCHEME

  • 7/31/2019 Swgr Presentation Without Animation

    39/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    40/86

    Alarm Schemes

    Alarm Cancellation Scheme Alarm Annunciation Scheme

    SWITCHGEAR INTERLOCK SCHEME

  • 7/31/2019 Swgr Presentation Without Animation

    41/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

    SWITCHGEAR INTERLOCK SCHEME

  • 7/31/2019 Swgr Presentation Without Animation

    42/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    43/86

    c) The phase difference of the two supplies must be within acceptable limits.

    Synchronizing SchemesTo bring new bus (source) into the switchboard when old one is running

    and shifting to new one.

    To meet synchronizism that means two AC supplies are correctly paralleledfollowing condition should be satisfied.

    A check synchronizing relay is used to prevent inter-connection of two badlysynchronized supplied. Its dual purpose is to Safeguard manualsynchronizing.

    Methods adopted for synchronization are :

    Manual Synchronization

    By Check Synchronizing Relays

    a) The voltages of the two supplies must be within acceptable limits.

    b) The frequencies of the two supplies must be within acceptable limits.

  • 7/31/2019 Swgr Presentation Without Animation

    44/86

  • 7/31/2019 Swgr Presentation Without Animation

    45/86

  • 7/31/2019 Swgr Presentation Without Animation

    46/86

    AUTO SYNCHRONIZING

    SWITCHGEAR INTERLOCK SCHEME

  • 7/31/2019 Swgr Presentation Without Animation

    47/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

    SWITCHGEAR INTERLOCK SCHEME

  • 7/31/2019 Swgr Presentation Without Animation

    48/86

    SWITCHGEAR INTERLOCK SCHEME

    Automatic supply transfer schemes.

    Synchronizing schemes and Alarm schemes,

    Voltage selection schemes;

    Trip circuit supervision schemes;

    Tripping schemes;

    Closing Scheme;

    Safety Interlocks & schemes using position limit switches;

  • 7/31/2019 Swgr Presentation Without Animation

    49/86

    Automatic Supply Transfer SchemesRequirement of Automatic Bus Transfer Scheme ?

    Unit Switchgear

    Station Switchgear

  • 7/31/2019 Swgr Presentation Without Animation

    50/86

    Modes of Bus Transfer

    A. Manual Bus Transfer

    i) Without Voltage Interruption

    ii) With Voltage Interruption

    a) Slow changeover

    b) Fast changeover

    B. Automatic Bus Transfer (under fault condition) with Voltage Interruption

    a) Slow changeover

    b) Fast changeover

    El i l I l k

  • 7/31/2019 Swgr Presentation Without Animation

    51/86

    Electrical Interlockin Closing Circuit

    Electrical Interlockin Tripping Circuit

    Electrical Interlocking scheme is guided by the logic diagram.

    Protection Schemes for Medium Voltage Switchgear

  • 7/31/2019 Swgr Presentation Without Animation

    52/86

    Protection Schemes for Medium Voltage Switchgear

    Importance of Protection System in Electrical System ?

    5-S Principles

    Security : Protective system should be reliable so that security of supply is ensured.

    Sensitivity : Protective system should be able to sense minimum value of faultcurrent, thereby reducing the consequent damage.

    Speed : Protective system should be able to isolate fault in the shortest possibletime.

    Selectivity : Protective system should be able to select and trip only the nearestcircuit breaker.

    Stability : Protective system should not operate for external faults.

    FAULT : It is defined as any abnormal condition, which causes reduction in thebasic insulation level strength of system.

    FAULT DETECTION : POSITIVE, NEGATIVE & ZERO Phase sequence

    component of system.

    PROTECTION SCHEMES IN MV SWITCHGEAR

  • 7/31/2019 Swgr Presentation Without Animation

    53/86

    PROTECTION SCHEMES IN MV SWITCHGEAR

    Non Directional Over Current for Phase Faults (50/51)

    Non Directional Over Current for Earth Fault (50N/51N)

    Directional Over Current for Phase Faults (67)

    Directional Over Current for Earth Fault (67N)

  • 7/31/2019 Swgr Presentation Without Animation

    54/86

    UNIT PROTECTION SCHEME

    - Pilot Wire Protection Scheme

    - Bus Differential Protection Scheme

    - Motor/ Transformer Differential Protection Scheme

    - Restricted Earth Protection Scheme

    In Unit Protection sections of power system are protected individually asa complete unit without reference to other section.

    Some of the Unit scheme which MV Switchgear employed

    For the protection of CABLE connecting two Feeder

    For the protection of BUSBAR

    For the protection of MOTOR/ TRANSFORMER WINDINGS

    For the protection of TRANSFORMER WINDINGS

  • 7/31/2019 Swgr Presentation Without Animation

    55/86

    TRANSFORMER PROTECTION

    Non- Directional Over Current and Earth Fault Protection(50/51/50N/51N)

    Sensitive Earth Fault Protection (50N/2)

    Differential Protection (87T)

    Restricted Earth Fault Protection (64R)

    Incipient Faults (49/63TX)

  • 7/31/2019 Swgr Presentation Without Animation

    56/86

    MOTOR PROTECTION

    Wide range of A.C Motors

    Motor characteristics due to various duties

    All Motor needs protection and choice should

    be independent of a type of motor & loadconnected.

    O OT CT O

  • 7/31/2019 Swgr Presentation Without Animation

    57/86

    NEED FOR PROTECTION

    Allowing operation under normal conditions.

    Quick isolation from supply under abnormalconditions.

    Averting damage to the motor & drivenmechanism.

    Enhancement of life of motor.

    MOTOR PROTECTION

  • 7/31/2019 Swgr Presentation Without Animation

    58/86

    MOTOR PROTECTIONA. MOTOR INDUCED

    B. LOAD INDUCED

    C. ENVIRONMENT INDUCED

    D. SOURCE OR SYSTEM INDUCED

    E. OPERATION AND APPLICATION INDUCED

    1. INSULATION FAILURE

    2. BEARING FAILURE

    3. MECHANICAL FAILURE

    4. LOSS OF FIELD (SYNCHRONOUS MOTOR)

    1. OVERLOAD/ UNDERLOAD

    2. JAMMING

    3. HIGH INERTIA

    1. HIGH AMBIENT TEMPERATURE2. HIGH CONTAMINATED LEVEL-BLOCKED VENTILATION

    3. COLD, DAMP AMBIENT TEMPERATURE

    1. PHASE FAILURE

    2. OVER VOLTAGE/UNDER VOLTAGE

    3. PHASE REVERSAL

    4. OUT-OF-STEP

    1. SYNCHRONIZING, CLOSING OR RECLOSING OUT OF PHASE

    2. HIGH DUTY CYCLE

    3. JOGGING

    MOTOR PROTECTION

  • 7/31/2019 Swgr Presentation Without Animation

    59/86

    MOTOR PROTECTION

    Thermal Over Load protection (49)

    Single phasing/Negative Phase Sequence Protection (46)

    Short-circuits between phases or between phase and earth in themotor winding or its connections. (50/51)

    Partial or complete collapse of voltage (27)

    Locked rotor (51S)

    Start or Stall Protection(48/51LR)

    Earth Fault Protection (50N)

    Loss-Of-Load Protection (37)

    Out of Step Protection (46)

    RTD/BTD Protection (26)

    Limitation of the number of start, Time between start (66)

  • 7/31/2019 Swgr Presentation Without Animation

    60/86

    EXPECTATIONS FROM MODERN MOTOR PROTECTIONRELAYS:

    1. The design of a modern motor protection relay must beadequate to cater for the protection needs of any one of the vastrange of motor designs in service and many of designs havingno permissible allowance for overload.

    2. The relay should ideally be matched with the motorcharacteristics and be capable of close sustained overloadprotection, a wide range of relay adjustment id desirabletogether with good accuracy & low thermal overshoot.

    3. Relay curves should take into account the extremes of zero pre-fault current known as the COLD condition & full rated currentpre-fault known as HOT condition.

  • 7/31/2019 Swgr Presentation Without Animation

    61/86

    PROTECTION AGAINST SWITCHING SURGES

  • 7/31/2019 Swgr Presentation Without Animation

    62/86

    PROTECTION AGAINST SWITCHING SURGES:

    What is an Electrical Surge ?

    External surge & Internal surge

    Atmospheric Lightning cause External surge

    Switching action of devices cause internal surge

    CAUSES OF SURGE GENERATION:

    Normal Switching On of a stationary motor.

    Normal switching Off of a stationary motor.

    Switching a Stalled motor or one running upto speed.

    PROTECTION AGAINST

  • 7/31/2019 Swgr Presentation Without Animation

    63/86

    PROTECTION AGAINST

    SWITCHING SURGES:

    SURGE PROTECTION DEVICES:These devices limits the over voltages in electrical system to the specified protection

    level, principally lower than the withstand voltage of equipment. a/ C-R type surge suppressors.

    b/ ZnO type surge arrestors.

    IOCL SPECIFIC SCHEMES

  • 7/31/2019 Swgr Presentation Without Animation

    64/86

    IOCL SPECIFIC SCHEMES

    BUS DIFFERENTIAL

    MOTOR RE-ACCELERATION

    PILOT WIRE PROTECTION

    TWO OUT OF THREE BREAKER SCHEME

    MOTOR DIFFERENTIAL

  • 7/31/2019 Swgr Presentation Without Animation

    65/86

    THANKYOU

  • 7/31/2019 Swgr Presentation Without Animation

    66/86

  • 7/31/2019 Swgr Presentation Without Animation

    67/86

  • 7/31/2019 Swgr Presentation Without Animation

    68/86

  • 7/31/2019 Swgr Presentation Without Animation

    69/86

  • 7/31/2019 Swgr Presentation Without Animation

    70/86

  • 7/31/2019 Swgr Presentation Without Animation

    71/86

  • 7/31/2019 Swgr Presentation Without Animation

    72/86

  • 7/31/2019 Swgr Presentation Without Animation

    73/86

    Differential relay for bus bar protection can be implemented in one of the following three ways:1.Sample by sample comparison. 2.Comparison of current phasors. 3.High impedance busdifferential relay The main difficulty in bus differential protection is that significant differential

  • 7/31/2019 Swgr Presentation Without Animation

    74/86

    differential relay. The main difficulty in bus differential protection is that significant differentialcurrent may appear due to saturation of CT on external fault. When a CT saturates, its secondarycurrent is not scaled replica of primary current. Therefore, sum of CT secondary current is notequal to sum of primary currents even though primary CT currents sum to zero.

    This causes a differential relay to operate on even external faults, leading to maloperation of bus

    protection scheme. This compromises security and is not acceptable. While the percentagedifferential can provide security against normal CT errors due to mismatch of CT turns ratio andmagnetization current; it is not adequate to handle severe CT saturation problem. So the relevantquestions to be asked now are: (1)How was this problem handled in the past, i.e. in the era priorto numerical relays? (2)How do numerical relays cope with this problem? High Impedance BusDifferential Relay This approach has been the most successful with traditional electromechanical and solid state relay. It is based upon the following ingenious and innovative thinking.If you cannot beat CT saturation, exploit it! In fact this is now a well accepted principle in theory ofsystematic innovation, also known as TRIZ (a Russian acronym), that one innovative way to

    problem solving is to exploit the harm:

    If you cannot undo the harm, stretch the harm to the extreme and then exploit it to youradvantage".Recall that when a CT core saturates, it behaves more like an air core device. The couplingbetween the primary and secondary winding is negligible. The impedance now offered by the CTas seen from the CT secondary terminals is very low and it equals the impedance of the CTsecondary winding. The CT is no more a current source with high impedance shunt. Rather, it is aplain low impedance path. Thus, if we increase the impedance of the relay element which was tocarry the differential current significantly, then sum of all the CT secondary currents (except forthe saturated CT) will be diverted into the low impedance path of saturated CT's secondary.Therefore, differential current would be negligible and hence protection system will not operate(See fig 38.6).Thus, now saturation of CT itself is responsible for saving a false operation.

    In contrast, numerical relays offer a low impedance path. Hence, thisscheme of differential bus bar protection cannot be emulated with

  • 7/31/2019 Swgr Presentation Without Animation

    75/86

    scheme of differential bus bar protection cannot be emulated withnumerical relays. Therefore, with numerical relays the busbar protectionhas to be very fast. i.e preferably decision making has to be completedbefore the CT saturates. Recall that saturation of CT is primarily aconsequence of DC offset current. The time for CT core saturation also

    depends upon time constant (L/R) of transmission line. If the protectionsystem could reach trip decision before the onset of CT core saturation,then it would be reliable. Hence, numerical relaying based bus barprotection is expected to operate in quarter of a cycle. Development ofsuch protection scheme requires ingenuity because of the well knownspeed vs accuracy conflict. Non linear % Differential Characteristics Ifthe CT core saturation factor could be discounted for, then we could

    use constant % differential characteristic for bus bar differentialprotection. We model a CT as scaled current source due totransformation ratio in parallel with magnetizing impedance (Norton'sequivalent). However, the magnetizing impedance itself is nonlinear. Itis large when CT core is not saturated and small when CT core issaturated. The current in this branch directly contributes to thedifferential current.

    This suggests that % differential characteristics should be modified tohave higher slopes to take care of CT saturation A fast protection

  • 7/31/2019 Swgr Presentation Without Animation

    76/86

    have higher slopes to take care of CT saturation. A fast protectionscheme can be devised by instantaneous sample based differentialprotection scheme. In contrast, a phasor summation scheme will beinherently slower as correct phasor estimates will have to wait until themoving window is totally populated with post fault current samples. Oneway out of this imbroglio is to use a smaller data window (e.g. 3 samplewindow). On the other hand, the comparison scheme basedcomputation of instantaneous samples can be error prone due to noisetransient related problem. To obtain reliability, it is necessary thatconsistent differential current should be obtained. A transient monitorfunction can be used to check that. A transient counter is initialized tozero. If a fault is detected due to presence of differential current, thencounter is incremented. Conversely, if counter is greater than zero, andno fault is detected (small enough differential current magnitude) thencounter is decremented. If the counter crosses a preset threshold value,trip decision is implemented. This scheme will not trip on transient.

    However, in addition to internal faults, it will also trip on external fault.For this purpose, the differential protection relay also has to have aninbuilt feature to detect CT saturation. One way to detect CT coresaturation is based on measuring current change in consecutivesamples with the expected sinusoidal signal model. A change muchbeyond the expected change in sinusoidal model indicates CT coresaturation. Many more innovative schemes can be thought out to detectCT saturation which is beyond the scope of this lecture.

  • 7/31/2019 Swgr Presentation Without Animation

    77/86

  • 7/31/2019 Swgr Presentation Without Animation

    78/86

  • 7/31/2019 Swgr Presentation Without Animation

    79/86

  • 7/31/2019 Swgr Presentation Without Animation

    80/86

  • 7/31/2019 Swgr Presentation Without Animation

    81/86

  • 7/31/2019 Swgr Presentation Without Animation

    82/86

  • 7/31/2019 Swgr Presentation Without Animation

    83/86

  • 7/31/2019 Swgr Presentation Without Animation

    84/86

    NEED OF STABILIZING RESISTOR & METROSIL

  • 7/31/2019 Swgr Presentation Without Animation

    85/86

    IN HIGH IMPEDENCE CIRCUIT

    Stabilizing resistor are used to Limit the heavy fault current to safevalue for relays

    Metrosil are used to limit voltage drop across the relays

    HIGH & LOW IMPEDENCE CIRCUITS

  • 7/31/2019 Swgr Presentation Without Animation

    86/86

    HIGH & LOW IMPEDENCE CIRCUITS

    The high impedance protection is "more sensitive" compared tolow impedance protection. Apart from that high impedanceprotection is faster that of low impedance protection. But this is atthe cost of high CT requirements like same CT ratio and high CTknee point voltage requirement. More over to make theprotection stable for thro fault, we need to consider stabilising

    resistor and metrosil. Another alternative to high impendence differential protection is

    using low impedance protection. It involves comparatively lesscomplexity than that of High impedance protection as it does notrequire any external component like stabilising resistor / metrosil.Here the thro fault stability is achieved thro biasing technique.

    When compared to high impedance low impedance will be bitslower, but the CT requirement is less as it can be used withdifference CT ratios with 5P class of CT's and comparativelyless Vk requirement.