symmetrical components.pdf
TRANSCRIPT
Lecture # Symmetrical Components
EE 308 Power Systems 1 18-Apr-13
Introduction
Under the normal (or healthy ) operation condition, balanced 3-Ø system can be performed using per-phase analysis.
Fault types:
This lecture deals to analyze the abnormal system behavior under condition of unsymmetrical short circuits
Unsymmetrical fault analysis requires new tools
– Symmetrical Components
– augmented component models
18-Apr-13 EE 308 Power Systems 2
L-L-L Faults 5 %
L-L-G Faults 10 %
L-L Faults 15 %
L-G Faults 70 %
Unsymmetrical faults
Symmetrical Components Allow unbalanced three-phase phasor quantities
decomposed into three separate but balanced symmetrical components (+ve , -ve and zero sequences)
– applicable to current and voltages
– permits modeling of unbalanced systems and networks
symmetrical components
18-Apr-13 EE 308 Power Systems 3
Positive Sequence
– balanced and having the same phase sequence as the unbalanced supply
Negative Sequence
– balanced and having the opposite phase sequence to the unbalanced supply
Zero Sequence
– balanced but having the same phase and hence no phase sequence
Symmetrical Components
18-Apr-13 EE 308 Power Systems 4
Representative symmetrical components
The phase components are the addition of the symmetrical components
The unknown unbalanced system has three unknown magnitudes and three unknown angles with respect to the reference direction. Similarly, the combination of the 3 sequence components will also have three unknown magnitudes and three unknown angles with respect to the reference direction.
Symmetrical Components
For example, phase voltages,
18-Apr-13 EE 308 Power Systems 5
210
210
210
cccc
bbbb
aaaa
VVVVVVVVVVVV
++=
++=
++=
• A so called “ α “ operator is commonly used in symmetrical component representation.
• It is defined as a vector having 1 as its magnitude and 120 degree as its phase angle.
866.05.01201 j+−=∠= α
( ) ( ) 12012401120112012 −∠=∠=∠×∠=α
Some properties of “α “ operator
012 =++αα Since α is complex, it can not be equal to 1, so that α -1 can not be zero
2α
α
1
Symmetrical Components
Analysis of decomposition of phasors
18-Apr-13 EE 308 Power Systems 6
symmetrical component matrix equation
Symmetrical Components
18-Apr-13 EE 308 Power Systems 7
Decomposition of phasors into symmetrical components
⇒
[ ]( )
( )( )
−−−−−−−−−−−
−=
=Λ −
1111
131
11
111
22
22
2224
2
21
αααααααααααααα
αααααα
αααα == −− 221 ,Since [ ]
=Λ −
αααα
2
21
11
111
31
PhSym
cba
aaa
=
αααα
2
2
2
1
0
11
111
31
Power in Terms of Sequence Components
18-Apr-13 EE 308 Power Systems 8
***3 ccbbaa IVIVIVjQPS ++=+=−φ
[ ] [ ] [ ] *
012012*
*
*
*
3 IVIVIII
VVVST
abcTabc
c
b
a
cba ΛΛ==
=−φ
[ ] [ ] *012
*0120120123
*
IVIV ΛΛ=ΛΛ=−TTTS φ
=
=ΛΛ
111111111
311
111
11
111
2
2
2
2*
αααα
ααααT
( )*22
*11
*00
*0120123 33 aaaaaa
T IVIVIVS ++==− IVφ
( )2*
221*110
*003 coscoscos3 φφφφ aaaaaa IVIVIVP ++=−
Example
One conductor of a 3-Ø line is open as shown in Fig. The current flowing to the ∆-connected load through line a is 10 A. With the current in line a as reference and assuming that line c is open, find symmetrical components of the line currents.
18-Apr-13 EE 308 Power Systems 9
Ex: 11.1 Grainger and Stevenson
a
b
c
Z
Z
Z
AIa010∠=
AIb18010∠=
AIc 0=
=
c
b
a
a
a
a
III
III
αααα
2
2
2
1
0
11
111
31
( )
( )( )
( )( ) AI
AI
AI
a
a
a
3078.502401801001031
3078.501201801001031
001801001031
2
1
0
∠=++∠+∠=
−∠=++∠+∠=
=+∠+∠=
Example … Cont’d
18-Apr-13 EE 308 Power Systems 10
=
2
1
0
2
2
11
111
a
a
a
c
b
a
III
III
αααα
AIIAII
AII
ab
ab
ab
15078.515078.5
0
22
12
1
00
∠==
−∠==
==
αα⇒ ;
AIIAII
AII
ac
ac
ac
9078.59078.5
0
22
2
11
00
−∠==
∠==
==
αα
The result holds for any 3-wire system (absence of neutral connection).
AIII cba 0000 ===
Components have non-zero values although line c is open and can carry no net current.
21 cc IandI
Sequence Impedances
The impedance offered to the flow of a sequence current creating sequence voltages
– positive, negative, and zero sequence impedances
Augmented network models
– Y-connected load
– Transmission line
– 3-Ø transformers
– Synchronous generators
18-Apr-13 EE 308 Power Systems 11
Network components
Balanced Load
18-Apr-13 EE 308 Power Systems 12
3-Ø balanced load with self and mutual elements
Model and governing equations
nncsbmamc
nncmbsamb
nncmbmasa
IZIZIZIZVIZIZIZIZVIZIZIZIZV
+++=+++=+++=
cban IIII ++=
+++++++++
=
a
a
a
nsnmnm
nmnsnm
nmnmns
c
b
a
III
ZZZZZZZZZZZZZZZZZZ
VVV
abcabcabc IZV =
aV
sZ
bV
cV
sZ
sZ
aI
bI
cI
nI
nZ
mZ
mZmZ
Balanced Load
18-Apr-13 EE 308 Power Systems 13
[ ] [ ]ΛΛ==⇒ΛΛ=
Λ=Λ⇒=−−
abcabc
abcabcabcabc
where ZZIZVIZVIZVIZV
1012012012012012
1012
012012
+++++++++
=
2
2
2
2012
11
111
11
111
31
αααα
αααα
nsnmnm
nmnsnm
nmnmns
ZZZZZZZZZZZZZZZZZZ
Z
−−
++=
ms
ms
mns
ZZZZ
ZZZ
00000023
012Z
Transmission Lines
18-Apr-13 EE 308 Power Systems 14
sZ
sZ
sZ
aI
bI
cI
mZ
mZmZ
b
a
c
'b
'a
'c
−−
+=
ms
ms
ms
ZZZZ
ZZ
0000002
012Z
Fully transposed transmission line (i.e., symmetrical) has:
The conductors of a transmission line, being passive and stationary, do not have an inherent direction. Equal +ve and –ve sequence impedances However, as the zero sequence path also involves the earth
wire and or the earth return path, Zero sequence impedance much larger than the +ve (or –ve ) sequence impedance (approx. 2.5 times)
In practice all three phase conductors behave similarly, so that we could consider the mutual coupling between phases also to be equal
Transmission Lines: Summary
While the phase component impedance matrix was a full matrix, although it had completely symmetry
the sequence component impedance matrix is diagonal.
The advantage of a diagonal matrix is that it allows decoupling for ease of analysis.
Ratio of zero sequence impedance to +ve sequence impedance – Order of 2 (single circuit x’mission with earth wire) – About 3.5 (single circuit x’mission with no-earth wire or double circuit)
18-Apr-13 EE 308 Power Systems 15
=
smm
msm
mms
ZZZZZZZZZ
Z
−−
+=
ms
ms
ms
ZZZZ
ZZ
0000002
012Z
Phase component impedance matrix symmetrical component impedance matrix
Synchronous Generator
18-Apr-13 EE 308 Power Systems 16
aI
bI
cI
nI
b
a
c
n
anE
bnE
cnE
nZ
( )[ ]( )[ ]
( )[ ] 2222
1111
0000 2
ZIMLjRIVZIEMLjRIEV
ZIMLjRIV
assaan
aanssaanan
gassaan
−=++−=−=++−=
−=−+−=
ωω
ω
The generator (or a synchronous machine) has a inherent direction of rotation,
and the sequence considered may either have the same direction (no relative motion) or the opposite direction (relative motion at twice the speed).
Thus, the rotational emf developed for the positive sequence and the negative sequence would also be different.
Thus the generator has different values of positive sequence, negative sequence and zero sequence impedance.
Synchronous Generator
18-Apr-13 EE 308 Power Systems 17
1aI
1bI
1cIb
a
c
n
anE
bnE
cnE1Z
2aI
2bI
2cIb
a
c
n
1Z
1Z
2Z
2Z2Z
0aI
0bI
0cIb
a
c
n
0gZ 0gZ
0gZ
03 aInZ
1aI
anE
1Z
Reference for +ve
2aI
2Z
Reference for -ve
0aI
0gZ
nZ3
Reference for zero
positive sequence negative sequence zero sequence
Synchronous Generator
Typical value of sequence impedances of turbo-generator rated 5 MVA, 6.6 kV, 3000 RPM are:
18-Apr-13 EE 308 Power Systems 18
( )( )( )
%5%12%110
%20%12
0
2
1
1
1
=====
ZZ
ssynchronouZtransientZ
transientsubZ
Transformers
Series Leakage Impedance
– the magnetization current and core losses represented by the shunt branch are neglected (they represent only 1% of the total load current)
– the transformer is modeled with the equivalent series leakage impedance
18-Apr-13 EE 308 Power Systems 19
lZZZ == 21
Wye-delta transformers create a phase shifting pattern for the various sequences
• the positive sequence line voltage on HV side leads the corresponding line voltage on LV side by 30 degrees
• For negative sequence line voltage the corresponding phase shift is -30 degrees
Two-winding transformers
Two winding (primary and secondary), three phase transformers may be categorized into
1) star-star
2) earthed star – star
3) earthed star – earthed star
4) delta – star
5) delta – earthed star
6) delta – delta
18-Apr-13 EE 308 Power Systems 20
Two-winding transformers
18-Apr-13 EE 308 Power Systems 21
Reference bus
0tZa b
c d
P S
1) star-star
Keep all a,b,c, and d switches open
2) earthed star – star
Close the switch a and keep open rest of the switches
3) earthed star – earthed star
Close the switches a and b. keep open rest of the switches
4) delta – star (Special case)
Close the switch b and keep open rest of the switches
5) delta – earthed star
Close the switches c and b. keep open rest of the switches
6) delta – delta
Close the switches c and d. keep open rest of the switches
Transformers
18-Apr-13 EE 308 Power Systems 22
single-line networks for zero sequence of two-winding transformers
Transformer : Summary
An unearthed star winding does not permit any zero sequence current to flow so that it could be represented in the single line diagram by a 'break' between the line terminal and the winding.
If the star point is solidly earthed, it could be represented by a solid connection across the break and for an earth connection through an impedance, by 3 times the earthing impedance across the break.
In the case of a delta winding, no current would flow from the line, but a current is possible in the winding depending on the secondary winding connections. This could be represented by a break in connection with the line but with the winding impedance being connected to the reference.
18-Apr-13 EE 308 Power Systems 23
Example For the power system of Fig. draw the positive, negative and zero sequence networks. The generators and transformers are rated as follows:
– Generator1: 25 MVA, 11 kV, X”=0.2, X2 =0.15, X0 = 0.03 pu
– Generator 2: 15 MVA, 11 kV, X”=0.2, X2 =0.15, X0 = 0.05 pu
– Synchronous Motor : 25 MVA, 11 kV, X”=0.2, X2 =0.2, X0 = 0.1 pu
– Transformer 1: 25 MVA, 11 ∆ / 120 Y kV, X = 10 %
– 2: 12.5 MVA, 11 Y / 120 ∆ kV, X = 10 %
– 3: 10 MVA, 120 Y / 11 ∆ kV, X = 10 %
Choose a base of 50 MVA, 11 kV in the circuit of generator 1.
Note: zero sequence reactance of each line is 250 % of its positive reactance.
18-Apr-13 EE 308 Power Systems 24