21.0 to 35.0 kW 20.0 to 33.0 kW SyScroll 20 to 35 Air NEW Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual Chiller | Close Control | Water terminals

Upload: hahanh

Post on 18-Aug-2019

214 views

Category:

Documents


0 download

TRANSCRIPT

21.0 to 35.0 kW20.0 to 33.0 kW

SyScroll 20 to 35 Air NEW

Air Cooled Water Chillers Cooling Only and Heat PumpEngineering Data Manual

Chiller | Close Control | Water terminals

SyScroll 20-35 Air | 3

R410A refrigerant. Simpler refrigerant circuit layout with only one compres-

sor. Great accessibility to internal components for service op-

erations. Aeraulic independence between refrigerant circuit and

condensing side. Optimized fin spacing according coil version (CO/HP). New display on external panel allowing the complete

control of the unit. Wide operating limits. Low water temperature applications in cooling mode

(down to -8 °C). High water temperature applications in heating mode (up

to 55 °C). Improved acoustic performances. New fan motor with integrated grill & condenser. Multistage centrifugal pump equipped as standard. Mechanical gauge kit, available both factory mounted

and field mounted.

Key points

Fan speed control, suitable both for low ambient tem-perature operation in cooling mode and for high ambient temperature operation in heating mode.

ModBus interface available. Phase sequence monitor supplied as standard. User-friendly microprocessor based control. New controller that allows to reduce the use of an exter-

nal water tank. Return and leaving water temperature control logic. Dynamic set point (climatic, 4-20 mA, 0-10 V, 0-5 V, 0-1

V) as standard. Domestic hot water management. Advanced defrost management. Advanced pump management. Time scheduling. Remote terminal available as accessory. Double water set point. Rubber pads supplied as standard. Water filter supplied as standard. Differential pressure switch supplied as standard.

| SyScroll 20-35 Air4

GeneralThe new SyScroll Air air cooled water chillers have been designed and optimized to operate with R410A refrigerant fluid. They are available in cooling only CO and heat pump HP versions.Each version consists of 4 sizes and covers a nominal cooling capacity range from 20.0 to 33.0 kW and a nomi-nal heating capacity range from 21.0 to 35.0 kW.All units are equipped with one scroll compressors.The general operation status of the machine is continu-ously under the new control of an microprocessor based controller.The units can operate with very low water content, thanks to the new microprocessor implementing an auto-adaptive control logic ensuring a total protection of the compressors at different load or water volume conditions. The minimum water volume requested is 4.0 l/kW. An ex-ternal water tank can be supplied as accessory for field installation. All units are equipped with a multistage cen-trifugal pump as standard.A fan speed controller is included in the standard equip-ment allowing the unit operating in cooling mode at low ambient temperature and in heating mode at high ambi-ent temperature.

Conformity with standardsThe units are in conformity with the following standards: Machine Directive: 2006/42/EC Low Voltage Directive: 2006/95/EC Electromagnetic Compatibility Directive: 2004/108/EC Pressure Equipment Directive: 97/23/EC

CabinetThe cabinet is made of heavy gauge galvanized steel. All galvanized steel components are individually painted by a special painting process before the assembly of the unit. This painting system performs a homogeneous protection to the corrosion.The painting is a polyester powder based type, coloured in RAL 7040.The units are suitable for outdoor installation, directly on the building roof or at the ground level.

CompressorsCompressors are hermetic scroll type fitted with an inher-ent motor protection device ensuring protection against overheating. All compressors have direct-on-line starting and are mounted on rubber vibration isolators in order to minimize noise and vibration transmission.A soft start system can be supplied as optional, whereas a phase sequence monitor is supplied as standard.

EvaporatorIndoor heat exchangers are brazed stainless steel plate type. They are insulated with a 10 mm thick closed cell polyethylene foam material and provided with male gas threaded connections. It is protected by a 35 W antifreeze electric heater to en-sure a good protection against freezing at low ambient temperature when the unit is switched off.Maximum working pressure is 10 bar at water side and 45 bar at refrigerant side.

Air cooled condenser coilOutdoor heat exchangers are finned tubes coils. Coils are built with internally grooved copper tubes expanded into corrugated aluminium fins. Fin pitch is differentiated between the two coil configuration (condensing only, re-versible) in order to optimize operating conditions.

SpecificationsSy Scroll Air - SIZES

S

CO HP

BC PH

- -

CO = Cooling Only; HP = Heat Pump; BC = Brine Application; Version - = BLN.

SyScroll 20-35 Air | 5

Condenser fansUnits are equipped with two 500mm diameter axial fans with profiled, sickle shaped blades designed with bioni-cal know how, optimized full bellmouth with static blades (motor suspension) and short diffusor.They are placed directly in front of the coil in order to in-crease the air flow and the heat transfer between air and refrigerant. Fan motors have IP54 protection grade, and thermostat protection placed in the bearings. Both fans are equipped with a safety grill.

Refrigerant circuitRefrigerant circuit is equipped with one hermetic scroll compressor, sight glass, filter-drier and mechanical ex-pansion valve (electronic expansion valve is available as an option).Heat pump units refrigerant circuit is also provided with 4-way reversing valve, bi-flow filter drier, bi-flow expan-sion valve and liquid receiver.

Hydraulic circuitAll units are equipped with multi-stage centrifugal pump providing outdoor available static pressure. Pump impel-ler is insulated with anti-condensation shell. Water filter is supplied as standard. Safety valve and expansion tank are placed on suction side of the pump. Water connections are 1” 1/4 male GAS threaded type.

Control panel

A new optimized control is supplied on all the units with a simple user interface (possibility to customize keys func-tions and to set menus visibility). In addition to standard features as water temperature control (with possibility to choose LWT/EWT probe), the control can also manage following functions.The main features of this control system are: DHW control with anti-legionella function daily and

weekly activated, Dynamic set point (4-20 mA, 0-1V, 0-5V, 0-10V), Double set point, OAT compensation, Boiler / Electrical heater integration, Auto adaptative function to reduce the water content of

the plant, Managing of DHW 3 ways valve (ACCESSORY), Advanced pump management, Remote keyboard (ACCESSORY) with possibility to con-

nect (up to 100 m distance) without any serial interface.

Electrical boardElectric equipment is built in compliance with CE stand-ards. Easy accessible in front of the unit – through an ac-cess panel fixed with screws – the equipment is complete with: Door lock main isolating switch, Compressor contactors and automatic circuit breaker

switches, Phase sequence control, Pressostatic fan speed control, Clamps for remote summer/winter switch, Clamps for external flow switch, Clamps for remote double set-point, Clamps for external interlock, Clamps for remote general alarm, Connection clamps to remote keyboard (OPTIONAL), Clamps for boiler relay control (OPTIONAL), Clamps for dynamic set-point compensation (4-20 mA,

0-1 V, 0-5 V, 0-10 V), Clamps for DHW 3-way valve (ACCESSORY), Soft-starter, Power factor correction capacitors (OPTIONAL).

Standard equipment Fan speed control. Microprocessor card with 4 red digits, 18 LED, 4 buttons. Digital pressure and temperature reading kit. High ambient pressure control. Sequence phase control. Control circuit transformer 230 V/12 V. Compressor/pump hour meter. Main switch. Refrigerant R410A. PED approval. Evaporator antifreeze electric heater. Compressor box. Water differential pressure switch. Water filter. Automatic circuit breaker. Multi stage centrifugal pump.

| SyScroll 20-35 Air6

Factory-installed option: Coil with blue fins treatment (only HP), Coil with “E-Coating” treatment, Soft starter, Electronic Expansion Valve, Coil guard.

Field-installed accessories Compressor jacket, Mechanical Gauge kit, Hydro kit (112 l water tank), Water flow switch, Water pressure switch, In/out valve kit, Remote On/Off control, ModBus protocol kit for BMS, Power factor correction capacitors, Sequencer for up to 4 chillers installation Remote terminal.

SyScroll 20-35 Air | 7

Accessories & Options

SyScroll Air Delivery Abbreviation Description & Befenit

Sequence phases control Std PHC It allows to check the correct sense R-S-T of electric supply phases for 400/3/50 units.

Control circuit transformer 230V/12V Std TRF Voltage transformer to provide correctly the separated voltage to the auxiliary line.

Main switch Std Front operated switch-disconnector with direct mounted handle to cut the power Supply Line according CE standards.

Differential pressure switch Std Prevents the operation of the unit if the circulating chilled fluid is insufficient. Checking water differential pressure.

Antifreeze electric heater kit Std EEH Electrical Heater protects the plate exchanger.

Low ambient kit (pressostatic stepless fan speed control) Std FSC

Electronic speed controllers are designed to control the speed of fan motors in Air Cooled Chiller and Heatpump. Fan Speed controlled by Condensing Pressure in cool mode or by Air Temp in heat mode. Using variable fan speed controllers offers following benefits in commercial refrigeration or air-conditioning applications High Efficiency, Low Noise level, Low air temperature in cool mode and High air temperature in heat mode.

Double set point Std DSP Can manage two different applications (set point) selected by remote dry contact.

Automatic circuit breaker Std ACB

ACB is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. Providing Magnetic and Thermal protection to Compressor motors.

Electronic expansion valves Std EEVIt is the device able to control the refrigerant flow on suction line trough a stepper motor in order to keep the superheat as constant as possible.

Compressor Jacket Option CJ Jacket for each compressors in order to reduce the sound of its.

Modbus protocol kit for BMS Option MBS It permits the integration of the unit with BMS with Modbus protocol trough RS485 port.

Softstarter for compressor Option SSAn electronic device that automatically starts up the compressors gradually. The starting current can be reduced by up to 40% of the direct on line value.

Power factor corrector capacitors Option PFC

The purpose of the power factor corrector capacitor is to minimize the input current distortion and make the current in phase with the voltage. Target is to keep Power Factor about 0.90 in any running condition.

Mechanical gauges kit (HP and LP manometers) Option KM Pressure gauges that display the operating pressure in the high and low pressure sections of the refrigerant circuit.

e-coating AL/CU Option It is a treatment fo AL/CU coil for medium level of pollution and for marine atmosphere.

Coil Guards Option CG Grilles to protect the coils.

Desuperheater Option D Additional exchanger in order to recover 20% of capacity for Domestic Hot Water application.

Remote On/Off control AccessoryIt enables the operator to power on the unit when it is in standby mode, to display alarms and switch over cooling–heat pump. Maximum lenght: 50mt.

Remote keyboard panel Accessory Makes it possible to control the unit through the remote terminal, up to a maximum distance of 100mt of telephone cable.

Sequencer for up to 4 chillers installation Accessory SEQ It can easily pilot up to 4 units, chiller or heat pumps, belonging to the same family, fitted in parallel, 50 metres apart maximum.

Flow switch Accessory FSPrevents the operation of the unit if the circulating chilled fluid is insufficient. It is recommended to install a flow switch to ensure the correct operation of the unit.

Water pressure switch AccessoryMechanical water pressure switch to be mounted on the field installation on installation water piping to prevent very low Water Pressure.

Water filter Accessory Filter to remove impurities from the water supply.

Valve in out Accessory Ball valves makes it possible to insulate unit hydraulic circuit from the rest of the installation.

Accessories are loosed and to install in the field. Options are mounted in factory.

| SyScroll 20-35 Air8

EN 14511-2011

Starting 2012 Campaign Eurovent Certification Company took decision to start certify only performances declared in ac-cording severe European Standard EN14511.

BEFORE 2012: GROSS PERFORMANCESBefore this date all capacity performances are declared, measured and certified by Eurovent, as GROSS performances. COOLING or HEATING CAPACITY was rated without taking in account the negative contribution of the heat exchanger Pres-sure Drop or the positive contribution of the Head Available prevalence in example. POWER INPUT was rated as pure sum of all power input contribution from all motors fitted on the unit. Without taking in account the correction due to power spent to win the exchanger Pressure Drop in example.

AFTER 2012: NET PERFORMANCESAfter this date all data are certified according EN14511. Mainly consequences in example on Water chiller or heatpump are:COOLING or HEATING CAPACITY is now rated taking in account the negative contribution of the heat exchanger Pressure Drop or the positive contribution of the Head Available prevalence in example. In case of Water to Water unit, in example, both exchanger Pressure Drop values are taken in account in the formula. POWER INPUT is now rated as all power input contribution from all motors fitted on the unit taking in account also the correction due to power spent to win the exchanger Pressure Drop in example. As an important consequence of these new rules setted by Eurovent is that EER, COP and ESEER are also affected by these correction. All efficiency index are now calculated, measured and certified according new rules setted by Eurovent according EN14511.

Air to water unit (non ducted outdoor):

Where:Ph = NET heating capacity.Pc = NET cooling capacity.Pe = electrical power input.Phm = is the gross heat capacity, expressed in Watts.Pcm = is the gross cool capacity, expressed in Watts.qwi = is the nominal liquid flow rate.Δpe,wi = is the measured available external static pressure.Δpi,wi = is the measured internal static pressure difference.ηpi = is the efficiency of the pump.

Reference: Guidelines for the declaration of performances according to EN14511:2011 (available a copy upon request for Syste mair customer).

Indoor pump is an integral part Indoor pump is not an integral part

ECC 2011 (gross) EN14511:2011 ECC 2011 (gross) EN14511:2011

Ph Phm(1) Phm

– qwiΔpe,wi

ηpiPhm Phm

+ qwi (–Δpi,wi)

ηpi

Pc Pcm(1) Pcm

+ qwiΔpe,wi

ηpiPcm Pcm

– qwi (–Δpi,wi)

ηpi

Pe Pem(1) Pem

– qwiΔpe,wi

ηpiPem Pem

+ qwi (–Δpi,wi)

ηpi

(1) Measured with the indoor pump not running.

SyScroll 20-35 Air | 9

Refrigerant Flow Diagram - Syscroll 20-35 Air CO

COMPONENTS1 Compressor scroll type2 Air cooled condenser3 Filter drier4 Sight glass5 Expansion valve6 Plate heat exchanger7 Pump8 Drain valve9 Water buffer tank10 Water filter (loose)11 Automatic water charging valve12 Water outlet13 Water inlet14 Water charging line15 Expansion vessel (lt 5)

2

34

5

6

ATA 1

C

FS

N

9

N

L

L

10 8

13

1312

14

11

HYDROKIT

715

S

F

E

D

SBSKM KM

MECHANICAL EXPANSION VALVE(STANDARD)

543ELECTRONIC EXPANSIONVALVE (OPTIONAL)

BT

EEVCONTROL

UNITCONTROL

ST

S

SAFETY/CONTROL DEVICESA High pressure switch (42 bar)AT High pressure transducerB Low pressure switch (1,5 bar)BT Low pressure transducerC Water differential pressure switch (105 mbar)D Air temperature sensorE Outlet water temperature sensorF Inlet water temperature sensorFS Flow switchL Vent valveN Water safety valve (3 bar)S Shrader valve (service/charging point)ST Suction temperature probeKM Manometer (optional)↓ Pipe connection with Shrader valve 1/4” SAE---- Optional components° Probes

| SyScroll 20-35 Air10

Refrigerant Flow Diagram - Syscroll 20-35 Air HP

COMPONENTS1 Compressor scroll type2 Four-way valve3 Air cooled condenser4 Biflow filter drier5 Sight glass6 Biflow expansion valve7 Liquid receiver8 Plate heat exchanger9 Pump10 Drain valve11 Water buffer tank12 Water filter (loose)13 Automatic water charging valve14 Water outlet15 Water inlet16 Water charging line17 Expansion vessel (lt 5)

3

2

ON

H

45

67

8

ATA 1

C

FS

N

11

N

L

L

12 10

15

1514

16

13

HYDROKIT

917

S

F

E

D

I

SB

SKM

KM

MECHANICAL EXPANSION VALVE(STANDARD)

654ELECTRONIC EXPANSIONVALVE (OPTIONAL)

BT

EEVCONTROL

UNITCONTROL

ST

S

SAFETY/CONTROL DEVICESA High pressure switch (42 bar)AT High pressure transducerB Low pressure switch (1,5 bar)BT Low pressure transducerC Water differential pressure switch (105 mbar)D Air temperature sensorE Outlet water temperature sensorF Inlet water temperature sensorFS Flow switchH Defrost temperature sensorI Discharge gas temperature thermostat-dgtL Vent valveM Discharge temperature sensorN Water safety valve (3 bar)S Shrader valve (service/charging point)ST Suction temperature probeKM Manometer (optional)↓ Pipe connection with Shrader valve 1/4” SAE---- Optional components° Probes

SyScroll 20-35 Air | 11

Operating Limits

Model Syscroll 20-35 Air

Chilled liquid

Liquid outlettemperature

Water °C +5 to +18

Brine °C -8 / +5 (with glycol and electronic expansion valve); +5/+18 (standard application)

Temperature spread K 3 to 7Maximum operating pressure bar 3

Heatedliquid

Leaving water temperature

Water °C +25 to +55Temperature spread °C 3 to 15

Maximum operating pressure bar 3

Outdoor airOutdoor air temperature (cooling) °C Refer to diagram ”SYSCROLL 20-35 Air CO/HP - COOLING OPERATION”Outdoor air temperature (heating) °C Refer to diagram “SYSCROLL 20-35 Air CO/HP - HEATING OPERATION”

Power supply voltage V/ph/Hz 400 V, 3 ph + N, 50 Hz (+/- 10%)

Operating limits

Maximum %Glycol (ethylenic or propilenic): 40%.In case of operation with brines (water + glycol + inhibitors) it is strongly suggested the use of dedicated type of pump (contact sales dept).

-15-10

-505

10152025303540455055

-9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Water+Glycol+EEV Water

OAT

(°C)

LWT (°C)

Cooling mode Syscroll 20-35 Air CO

Heating mode

-12 -10 -8 -6 -4 -2 0 2 4 6 8

10 12 14 16 18 20 22

23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57

OAT

(°C)

LWT (°C)

-9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Water+Glycol+EEV Water

OAT

(°C)

LWT (°C)

-15-10

-505

10152025303540455055

Cooling mode Syscroll 20-35 Air HP

| SyScroll 20-35 Air12

Performances corrective factors (brine)

Table 1

Unit capacity, absorbed power, brine flow rate, brine pressure drop, have to be corrected according following formula:

CORRECTED UNIT CAPACITYQCORRECTED/GLYCOL = QNOMINAL x Kc x Kc

E,P

Where Kc : Capacity corrective factor according to LWT (ΔT = 5 [K]) → refer to Table 1 Kc

E : Capacity corrective factor according to glycol percentage (ETHYLENE GLYCOL) → refer to Table 2 Kc

P : Capacity corrective factor according to glycol percentage (PROPYLENE GLYCOL) → refer to Table 4

CORRECTED UNIT ABSORBED POWERPCORRECTED/GLYCOL = PNOMINAL x Ki x Ki

E,P

Where Ki : Absorbed power corrective factor according to LWT (ΔT = 5 [K]) → refer to Table 1 Ki

E : Absorbed power corrective factor according to glycol percentage (ETHYLENE GLYCOL) → refer to Table 2 Ki

P : Absorbed power corrective factor according to glycol percentage (PROPYLENE GLYCOL) → refer to Table 4

CORRECTED BRINE FLOW RATEGCORRECTED/GLYCOL = GRE-CALCULATED x Kf

E,P

Where GRE-CALCULATED : Flow rate according to PCORRECTED/GLYCOL (PCORRECTED/GLYCOL x 860 / ΔT / 3600) Kf

E : Flow rate corrective factor according to glycol percentage (ETHYLENE GLYCOL) → refer to Table 2 Kf

P : Flow rate corrective factor according to glycol percentage (PROPYLENE GLYCOL) → refer to Table 4

CORRECTED BRINE PRESSURE DROPΔPCORRECTED/GLYCOL = ΔPRE-CALCULATED x Kp

E,P

Where ΔPRE-CALCULATED : Pressure drop according to to GCORRECTED/GLYCOL (KBPHE x (GCORRECTED/GLYCOL)2)

KpE : Pressure drop corrective factor according to glycol percentage (ETHYLENE GLYCOL) → refer to Table 2

KpP : Pressure drop corrective factor according to glycol percentage (PROPYLENE GLYCOL) → refer to Table 5

Kc Ki

Leaving water temperature[LWT] (°C)

(ΔT=5 [K])

7 1,000 1,0004 0,887 0,9402 0,816 0,9000 0,748 0,865-2 0,685 0,826-4 0,624 0,788-6 0,568 0,753-8 0,513 0,718

-10 0,461 0,683

SyScroll 20-35 Air | 13

Table 2Ethylene Glycol Percentage 0% 10% 20% 30% 35% 40%Freezing point (*) °C 0 -4 -10 -10 -21 -21Minimum leaving water temperature allowed °C 6 2 -2 -2 -8 -8Capacity corrective factor (**) Kc

E 1 0,995 0,985 0,985 0,963 0,963Absorbed power corrective factor (**) Ki

E 1 0,998 0,995 0,995 0,983 0,983Flow rate corrective factor Kf

E 1 1,015 1,050 1,050 1,123 1,123Pressure drop corrective factor (***) Kp

E 1 1,070 1,160 1,160 1,283 1,283

(*) ASHRAE Handbook Fundamentals.(**) Valid for LWT=7 [°C]. If LWT<7 [°C] consider Kc x Kc

E and Ki x KiE

(***) Valid for LWT > 5 [°C]. If LWT<5°C → refer to Table 3

Table 3Ethylene Glycol

PercentageLWT[°C] Corrective factor Kf

E Corrective factor KpE

10%

5 1,0154 1,07104 1,0154 1,07603 1,0154 1,08102 1,0154 1,0850

20%

1 1,0417 1,19300 1,0423 1,2000-1 1,0428 1,2080-2 1,0434 1,2150

30%

-3 1,0927 1,2990-4 1,0936 1,3060-5 1,0945 1,3200-6 1,0954 1,3330

Table 4Propylene Glycol Percentage 0% 10% 20% 30% 40%Freezing point (*) °C 0 -3 -7 -13 -22Capacity corrective factor (**) Kc

P 1 0,991 0,977 0,945 0,911Absorbed power corrective factor (**) Ki

P 1 0,994 0,991 0,975 0,966Flow rate corrective factor Kf

P 1 1,005 1,030 1,067 1,130

(*) ASHRAE Handbook Fundamentals.(**) Valid for LWT=7 [°C]. If LWT<7 [°C] consider Kc x Kc

P and Ki x KiP

Table 5Ethylene Glycol

PercentageLWT[°C] Corrective factor Kp

p

10%5 1,1124 1,134

20%5 1,1754 1,1963 1,206

30%

5 1,2904 1,3003 1,3100 1,362-2 1,393-4 1,414

40%

5 1,4334 1,4353 1,4560 1,497-2 1,549-4 1,580-6 1,612-8 1,653

| SyScroll 20-35 Air14

Model 20 25 30 35Data @ Eurovent LCP/W/P/C AC conditions (1)Cooling Capacity (2) kW 20,4 23,9 27,7 33,2Cooling Capacity (3) kW 20,8 24,4 28,2 33,7Input Power (2) kW 7,12 7,88 9,47 12,0Input Power (3) kW 6,67 7,41 8,97 11,5EER 100% (2) kW/kW 2,87 3,03 2,93 2,77EER 100% (3) kW/kW 3,12 3,29 3,14 2,93EUROVENT CLASS A A A BEER 75% (3) kW/kW 3,48 3,67 3,59 3,32EER 50% (3) kW/kW 3,70 3,92 3,85 3,61EER 25% (3) kW/kW 3,46 3,71 3,64 3,37ESEER (3) kW/kW 3,56 3,77 3,70 3,44Number of Refrigerant Circuits 1Part Load Steps % 0-100Power Supply 400V/3+N/50HzStartup Type Direct (softstarter as option)Maximum Absorbed Power kW 10 12 13 16Maximum Corrent (FLA) A 20 25 26 35Startup Corrent (LRA) A 105 115 122 144RefrigerantType R410ACharge kg 4,1 4,6 6,0 6,6CompressorNumber 1Type ScrollCrankcase Heater W 70 90 90 90Internal heat exchangerNumber 1Type PlateWater Flow Rate l/s 0,97 1,14 1,32 1,59Available Static Pressure kPa 169 152 144 114Hydraulic Power W 165 173 191 181η 0,366 0,372 0,383 0,377FansNumber 2Type AxialAir Flow Rate mc/h 10.957 10.425 10.425 9.919Total Input Power kW 0,54 0,54 0,54 0,55PumpNumber 1Type CentrifugalInput Power kW 0,57 0,60 0,63 0,65Water ConnectionsType Male Gas ThreadedInlet Diameter inch 1”1/4Outlet Diameter inch 1”1/4WeightShipping kg 254 285 289 304Operating kg 248 279 283 298DimensionsLength mm 1.477 1.477 1.477 1.477Width mm 539 539 539 539Height mm 1.615 1.615 1.615 1.615Acoustic DataSound Power Level dB(A) 73 74 74 75Sound Pressure Level* dB(A) 41 42 42 43

(1) Standard Eurovent LCP/W/P/R AC conditions in cooling mode: EWT/LWT 12°C/7°C, OAT 35°C.(2) GROSS value.(3) NET value - According EN 14511 Standard.(*) Sound pressure level at 10 m.- Values refers to ISO Standard 3744 with parallepiped shape.

Technical data - SyScroll 20-35 Air CO

SyScroll 20-35 Air | 15

Technical data - SyScroll 20-35 Air HP

Model 20 25 30 35Data @ Eurovent LCP/W/P/C AC conditions (1)Cooling Capacity (2) kW 19,8 23,4 26,9 32,9Cooling Capacity (3) kW 20,2 23,9 27,4 33,4Input Power (2) kW 7,36 8,11 9,77 12,0Input Power (3) kW 6,91 7,65 9,27 11,5EER 100% (2) kW/kW 2,69 2,89 2,75 2,74EER 100% (3) kW/kW 2,92 3,12 2,96 2,90EUROVENT CLASS B A B BEER 75% (3) kW/kW 3,28 3,53 3,36 3,31EER 50% (3) kW/kW 3,48 3,76 3,67 3,54EER 25% (3) kW/kW 3,25 3,53 3,45 3,34ESEER (3) kW/kW 3,34 3,61 3,50 3,40Heating Capacity (2) kW 21,4 25,0 28,9 35,5Heating Capacity (3) kW 20,9 24,5 28,4 35,0Input Power (2) kW 7,16 8,16 9,20 11,3Input Power (3) kW 6,70 7,69 8,70 10,8COP (2) kW/kW 2,99 3,06 3,14 3,14COP (3) kW/kW 3,12 3,19 3,26 3,24EUROVENT CLASS B B A ANumber of Refrigerant Circuits 1Part Load Steps % 0-100Power Supply 400V/3+N/50HzStartup Type Direct (softstarter as option)Maximum Absorbed Power kW 10 12 13 16Maximum Corrent (FLA) A 20 25 26 35Startup Corrent (LRA) A 105 115 122 144RefrigerantType R410ACharge kg 5,0 5,6 6,1 7,1CompressorNumber / Type 1 / ScrollCrankcase Heater W 70 90 90 90Internal heat exchangerNumber / Type 1 / PlateWater Flow Rate (Summer / Winter) l/s 0,95 / 1,02 1,12 / 1,19 1,29 / 1,38 1,57 / 1,70Available Static Pressure (Summer / Winter) kPa 172 / 164 154 / 146 148 / 138 116 / 101Hydraulic Power (Summer / Winter) W 162 / 168 172 / 174 190 / 190 182 / 171η (Summer / Winter) 0,364 / 0,368 0,371 / 0,373 0,383 / 0,383 0,378 / 0,370FansNumber / Type 2 / AxialAir Flow Rate mc/h 11.289 10.848 10.848 10.425Total Input Power kW 0,53 0,54 0,54 0,54PumpNumber / Type 1 / CentrifugalInput Power (Summer / Winter) kW 0,57 / 0,58 0,60 / 0,61 0,62 / 0,63 0,65 / 0,66Water ConnectionsType Male Gas ThreadedInlet Diameter / Outlet Diameter inch 1”1/4 / 1”1/4WeightShipping kg 256 287 291 305Operating kg 250 281 286 299DimensionsLength mm 1.477 1.477 1.477 1.477Width mm 539 539 539 539Height mm 1.615 1.615 1.615 1.615Acoustic DataSound Power Level dB(A) 73 74 74 75Sound Pressure Level* dB(A) 41 42 42 43

(1) Standard Eurovent LCP/W/P/R AC conditions in cooling mode: EWT/LWT 12°C/7°C, OAT 35°C. (2) GROSS value.(3) NET value - According EN 14511 Standard. (*) Sound pressure level at 10 m.- Values refers to ISO Standard 3744 with parallepiped shape.

| SyScroll 20-35 Air16

Electrical Data - SyScroll 20-35 Air

400V/3/50HzNOMINAL MAXIMUM

PNOM-CPS INOM-CPS PMAX-CPS IMAX-CPS FLA ISTARTUP-CPS LRA PFC (NOM) PFC*Size kW A kW A A20 6,3 12 8,6 16 101 0,78 > 0.9025 7,1 13 10,2 21 111 0,80 > 0.9030 8,7 15 11,9 22 118 0,83 > 0.9035 11,3 19 14,8 31 140 0,85 > 0.90

Compressor Data

230V/1/50Hz PMAX-FANS IMAX-FANS FLASize kW A20 0,60 2,6025 0,60 2,6030 0,60 2,6035 0,60 2,60

Fans Data

400V/3/50Hz PMAX-PUMP IMAX-PUMP FLASize kW A20 0,72 1,3025 0,72 1,3030 0,72 1,3035 0,72 1,30

Pumps Data

400V/3+N/50HzSTD unit with pump

20 25 30 35

Power input (kW) NominalMaximum

8 8 10 1310 12 13 16

Current input (A) NominalMaximum

16 17 19 2320 25 26 35

Start-up current (A) 105 115 122 144Start-up current (A)** 75 82 87 102

* Power factor correction capacitor option installed.** Soft-starter option installed.

Acoustic Data - SyScroll 20-35 Air

SizeOctave Band (Hz)

Sound Power Level dB(A)

Sound Pressure Level* dB(A)63 125 250 500 1000 2000 4000 8000

Sound Power Level (dB)20 73 71 75 71 68 63 55 48 73 4125 74 72 76 72 69 64 56 48 74 4230 74 72 76 72 69 64 56 48 74 4235 75 73 77 73 70 65 57 49 75 43

* Sound pressure level at 10 m.- Values refers to ISO Standard 3744 with parallepiped shape.

SyScroll 20-35 Air | 17

Cooling Capacities - Syscroll 20-35 Air CO

Model LWT°C

OAT (°C)

25 30 32 35 38 40 42 45 48 50

PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS*

kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

SYSCROLL20 CO

5 22,1 4,87 20,8 5,34 20,2 5,56 19,3 5,90 18,3 6,25 17,6 6,50 16,9 6,78 15,7 7,21 14,5 7,64 13,8 7,927 23,3 4,98 22,0 5,45 21,3 5,67 20,4 6,01 19,3 6,38 18,6 6,64 17,8 6,92 16,6 7,36 15,3 7,809 24,6 5,09 23,1 5,57 22,5 5,79 21,5 6,14 20,4 6,51 19,6 6,78 18,8 7,06 17,6 7,52 16,3 7,97

11 25,9 5,21 24,3 5,70 23,7 5,91 22,6 6,27 21,5 6,64 20,7 6,91 19,9 7,20 18,5 7,6613 27,2 5,33 25,6 5,82 24,9 6,04 23,8 6,40 22,5 6,82 21,7 7,11 20,8 7,39 19,6 7,8015 28,6 5,46 27,0 5,96 26,2 6,21 24,8 6,61 23,7 6,99 22,9 7,24 22,1 7,50 20,8 7,9218 30,9 5,66 29,1 6,13 28,2 6,37 26,8 6,76 25,6 7,14 24,8 7,35 24,1 7,55 23,1 7,80

SYSCROLL25 CO

5 26,0 5,45 24,4 5,98 23,8 6,22 22,7 6,60 21,5 7,00 20,7 7,28 19,8 7,59 18,4 8,07 17,0 8,56 16,2 8,877 27,4 5,58 25,8 6,11 25,1 6,35 23,9 6,74 22,7 7,14 21,9 7,43 20,9 7,75 19,4 8,24 18,0 8,739 28,9 5,70 27,2 6,24 26,4 6,49 25,2 6,88 23,9 7,29 23,1 7,59 22,1 7,91 20,6 8,42 19,1 8,92

11 30,4 5,83 28,6 6,38 27,8 6,62 26,5 7,02 25,3 7,44 24,3 7,74 23,3 8,06 21,8 8,5813 32,0 5,97 30,1 6,52 29,3 6,76 27,9 7,16 26,5 7,64 25,5 7,96 24,5 8,28 23,0 8,7415 33,6 6,12 31,8 6,67 30,7 6,95 29,2 7,40 27,8 7,82 26,9 8,11 26,0 8,40 24,4 8,8618 36,3 6,34 34,2 6,86 33,2 7,13 31,5 7,57 30,0 7,99 29,1 8,24 28,3 8,45 27,2 8,74

SYSCROLL30 CO

5 30,1 6,72 28,3 7,38 27,5 7,67 26,2 8,14 24,9 8,63 23,9 8,98 22,9 9,35 21,3 9,95 19,7 10,5 18,7 10,97 31,7 6,87 29,8 7,53 29,0 7,82 27,7 8,30 26,3 8,80 25,3 9,16 24,2 9,55 22,5 10,2 20,8 10,89 33,4 7,03 31,4 7,69 30,6 7,99 29,2 8,48 27,7 8,99 26,7 9,35 25,6 9,75 23,9 10,4 22,2 11,011 35,2 7,19 33,1 7,86 32,2 8,16 30,7 8,65 29,2 9,16 28,2 9,53 27,0 9,94 25,2 10,613 37,0 7,36 34,8 8,04 33,9 8,33 32,4 8,83 30,6 9,41 29,5 9,82 28,3 10,2 26,7 10,815 38,9 7,54 36,8 8,22 35,6 8,57 33,8 9,12 32,2 9,64 31,2 10,0 30,1 10,4 28,2 10,918 42,0 7,81 39,6 8,46 38,4 8,79 36,5 9,33 34,8 9,85 33,7 10,2 32,8 10,4 31,5 10,8

SYSCROLL35 CO

5 36,1 8,77 33,9 9,62 33,0 10,0 31,5 10,6 29,9 11,3 28,7 11,7 27,5 12,2 25,6 13,0 23,7 13,8 22,5 14,37 38,1 8,97 35,8 9,8 34,8 10,2 33,2 10,8 31,6 11,5 30,4 12,0 29,1 12,5 27,0 13,2 24,9 14,09 40,1 9,16 37,7 10,0 36,7 10,4 35,0 11,1 33,3 11,7 32,0 12,2 30,7 12,7 28,7 13,5 26,6 14,3

11 42,2 9,38 39,7 10,3 38,6 10,6 36,9 11,3 35,1 12,0 33,8 12,4 32,4 13,0 30,3 13,813 44,4 9,60 41,8 10,5 40,7 10,9 38,8 11,5 36,8 12,3 35,4 12,8 34,0 13,3 32,0 14,015 46,6 9,84 44,1 10,7 42,7 11,2 40,5 11,9 38,6 12,6 37,4 13,0 36,1 13,5 33,9 14,318 50,4 10,2 47,5 11,0 46,1 11,5 43,8 12,2 41,7 12,8 40,5 13,2 39,3 13,6 37,7 14,0

(*) Only Compressors.

| SyScroll 20-35 Air18

Cooling Capacities - Syscroll 20-35 Air HP

Model LWT°C

OAT (°C)

25 30 32 35 38 40 42 45 48

PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS*

kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

SYSCROLL20 HP

5 21,5 5,11 20,2 5,60 19,6 5,80 18,8 6,13 17,7 6,56 16,9 6,85 16,2 7,10 15,4 7,41 14,5 7,727 22,6 5,23 21,2 5,73 20,7 5,93 19,8 6,26 18,7 6,66 17,9 6,94 17,2 7,20 16,2 7,579 23,8 5,35 22,4 5,85 21,8 6,06 20,9 6,39 19,8 6,75 19,1 7,01 18,3 7,30 17,1 7,75

11 25,1 5,47 23,6 5,98 22,9 6,19 22,0 6,52 20,9 6,89 20,1 7,16 19,3 7,45 18,0 7,9213 26,3 5,61 24,8 6,11 24,2 6,31 23,1 6,66 21,8 7,11 21,0 7,40 20,3 7,61 19,6 7,8415 27,7 5,74 26,0 6,25 25,4 6,44 24,3 6,79 22,9 7,24 22,1 7,52 21,4 7,7318 29,7 5,94 28,0 6,43 27,4 6,63 26,4 6,97 24,8 7,40 23,9 7,66 23,2 7,84

SYSCROLL25 HP

5 25,3 5,70 23,8 6,24 23,2 6,45 22,2 6,83 20,8 7,31 20,0 7,63 19,2 7,90 18,1 8,25 17,1 8,597 26,7 5,82 25,1 6,38 24,4 6,60 23,4 6,97 22,1 7,42 21,2 7,73 20,3 8,02 19,1 8,439 28,1 5,95 26,4 6,52 25,7 6,75 24,6 7,11 23,4 7,52 22,6 7,81 21,7 8,13 20,2 8,63

11 29,6 6,10 27,8 6,66 27,1 6,89 25,9 7,27 24,7 7,67 23,8 7,97 22,8 8,30 21,3 8,8213 31,1 6,25 29,2 6,81 28,5 7,03 27,3 7,42 25,7 7,92 24,7 8,24 24,0 8,48 23,2 8,7415 32,7 6,39 30,7 6,96 30,0 7,17 28,7 7,56 27,1 8,06 26,1 8,38 25,3 8,6118 35,1 6,62 33,0 7,16 32,4 7,38 31,2 7,76 29,3 8,24 28,2 8,53 27,4 8,73

SYSCROLL30 HP

5 29,1 7,03 27,4 7,71 26,7 7,97 25,5 8,43 24,0 9,03 23,0 9,42 22,1 9,76 20,9 10,2 19,7 10,67 30,7 7,19 28,9 7,87 28,1 8,15 26,9 8,61 25,4 9,17 24,4 9,55 23,4 9,91 22,0 10,49 32,4 7,35 30,4 8,05 29,6 8,33 28,3 8,78 27,0 9,28 26,0 9,65 24,9 10,0 23,3 10,7

11 34,1 7,53 32,0 8,22 31,1 8,51 29,8 8,97 28,4 9,48 27,4 9,85 26,2 10,3 24,5 10,913 35,8 7,72 33,6 8,41 32,8 8,68 31,4 9,16 29,6 9,78 28,5 10,2 27,6 10,5 26,6 10,815 37,6 7,89 35,3 8,59 34,5 8,86 33,0 9,34 31,2 9,96 30,0 10,3 29,1 10,618 40,4 8,17 38,0 8,84 37,3 9,11 35,8 9,58 33,7 10,2 32,4 10,5 31,5 10,8

SYSCROLL35 HP

5 35,7 8,86 33,5 9,7 32,7 10,0 31,2 10,6 29,3 11,4 28,1 11,9 27,0 12,3 25,5 12,8 24,1 13,47 37,6 9,05 35,3 9,9 34,4 10,3 32,9 10,8 31,1 11,5 29,8 12,0 28,6 12,5 26,9 13,19 39,6 9,26 37,2 10,1 36,2 10,5 34,7 11,1 33,0 11,7 31,8 12,2 30,5 12,6 28,5 13,4

11 41,7 9,49 39,2 10,4 38,1 10,7 36,5 11,3 34,7 11,9 33,5 12,4 32,1 12,9 30,0 13,713 43,8 9,72 41,2 10,6 40,1 10,9 38,4 11,5 36,2 12,3 34,8 12,8 33,8 13,2 32,6 13,615 46,0 9,95 43,3 10,8 42,2 11,2 40,4 11,8 38,1 12,5 36,7 13,0 35,6 13,418 49,4 10,3 46,5 11,1 45,6 11,5 43,9 12,1 41,3 12,8 39,6 13,3 38,6 13,6

(*) Only Compressors.

SyScroll 20-35 Air | 19

(*) Only Compressors.

Heating Capacities - Syscroll 20-35 Air HP

Model LWT°C

OAT (°C)

-7 -5 -3 0 5 7 10 15

PHEAT PABS* PHEAT PABS* PHEAT PABS* PHEAT PABS* PHEAT PABS* PHEAT PABS* PHEAT PABS* PHEAT PABS*

kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

SYSCROLL20 HP

30 14,9 4,20 15,8 4,21 16,8 4,23 18,4 4,25 21,2 4,30 22,3 4,33 24,2 4,38 27,8 4,4935 14,4 4,67 15,3 4,69 16,4 4,72 18,0 4,75 21,0 4,81 22,0 4,83 23,9 4,86 27,4 4,9540 14,3 5,30 15,1 5,31 16,1 5,33 17,8 5,34 20,6 5,38 21,7 5,40 23,5 5,43 26,8 5,5045 14,9 6,09 15,3 6,07 16,0 6,06 17,6 6,03 20,3 6,03 21,4 6,04 23,0 6,07 26,2 6,1550 17,3 6,80 19,0 6,45 20,7 6,75 22,5 6,79 25,5 6,88

SYSCROLL25 HP

30 17,4 4,87 18,4 4,88 19,6 4,90 21,5 4,93 24,7 4,99 26,1 5,02 28,3 5,07 32,5 5,2035 16,8 5,41 17,9 5,44 19,2 5,47 21,1 5,51 24,5 5,57 25,8 5,60 27,9 5,64 32,0 5,7440 16,7 6,15 17,7 6,16 18,8 6,17 20,8 6,20 24,1 6,24 25,4 6,26 27,4 6,29 31,3 6,3845 17,4 7,06 17,9 7,04 18,7 7,02 20,5 6,99 23,7 6,99 25,0 7,00 26,9 7,04 30,6 7,1350 20,2 7,89 22,2 7,48 24,2 7,83 26,2 7,87 29,8 7,98

SYSCROLL30 HP

30 20,1 5,58 21,3 5,59 22,7 5,61 24,9 5,64 28,6 5,71 30,2 5,75 32,7 5,81 37,7 5,9635 19,4 6,19 20,7 6,23 22,2 6,26 24,4 6,31 28,4 6,38 29,8 6,41 32,3 6,46 37,0 6,5740 19,4 7,04 20,5 7,05 21,7 7,07 24,1 7,09 27,9 7,14 29,4 7,17 31,7 7,21 36,3 7,3145 20,1 8,08 20,7 8,06 21,6 8,04 23,8 8,00 27,5 8,01 28,9 8,02 31,1 8,06 35,5 8,1650 23,4 9,03 25,7 8,56 28,0 8,96 30,4 9,02 34,5 9,13

SYSCROLL35 HP

30 24,7 7,02 26,2 7,03 27,9 7,05 30,6 7,10 35,1 7,18 37,1 7,23 40,2 7,30 46,2 7,4935 23,8 7,79 25,4 7,83 27,3 7,87 30,0 7,93 34,8 8,02 36,6 8,06 39,6 8,12 45,4 8,2740 23,8 8,85 25,2 8,87 26,7 8,89 29,6 8,92 34,2 8,98 36,1 9,01 38,9 9,06 44,5 9,1945 24,7 10,2 25,4 10,1 26,6 10,1 29,2 10,1 33,7 10,1 35,5 10,1 38,2 10,1 43,5 10,350 28,8 11,4 31,5 10,8 34,4 11,3 37,3 11,3 42,4 11,5

(*) Only Compressors.

| SyScroll 20-35 Air20

Pump Available Static Pressure

40

20

60

80

100

120

140

160

180

200

220

0,00 0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50

P (k

Pa)

G (l/s)

20-25 30-35

Water Circuit Pressure Drop

0

70

60

50

40

30

20

10

0,00 0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50

P (

kPa)

G (l/s)

20-25 30-35

0

5

10

15

20

25

30

35

0,00 0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75

P (

kPa)

G (l/s)

Water Filter* Pressure Drop0

70

60

50

40

30

20

10

0,00 0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50

P (

kPa)

G (l/s)

20-25 30-35

0

5

10

15

20

25

30

35

0,00 0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75

P (

kPa)

G (l/s)

* Φ 1"1/4 diameter, filtration capacity 500 μm / 35 mesh.

SyScroll 20-35 Air | 21

Dimensions SyScroll 20-35 Air

1615

147 1183 147

31

F G

LIFT

ø30

LIFT

ø30

457

2626

508

1441 18181477

31

352

426

38

A

P3 P1

P4 P2

B

E

DC

172

Front view Rear view

Top view

NOTESA Water inlet ø 1 1/4” MGTB Water outlet ø 1 1/4” MGTC Auxiliary linesD Electrical power supplyE Gauge kit (optional)F Main switchG Control keypad/display

1615

147 1183 147

31

F G

LIFT

ø30

LIFT

ø30

457

2626

508

1441 18181477

31

352

426

38

A

P3 P1

P4 P2

B

E

DC

172

Side view

| SyScroll 20-35 Air22

Dimensions Hydrokit 20-35

75

10

250 1480

390

2005

1480

509

1360 60 2645

726

60

9

305

860

92287

292

B

A

C

D

186

P3 P1

P4 P2

Front view Rear view

Top view

NOTESA Water inlet ø 1 1/4” MGTB Water outlet ø 1 1/4” MGTC Tank fill ø 1 1/2” MGTD Water drain ø 3/8” MGT

1615

147 1183 147

31

F G

LIFT

ø30

LIFT

ø30

457

2626

508

1441 18181477

31

352

426

38

A

P3 P1

P4 P2

B

E

DC

172

Side view

SyScroll 20-35 Air | 23

Space requirements

400 mm

200 mm

800 mm

200 mm

200 mm

Weight Distribution

Model SizeWeight distribution Operating

weightShippingweight

P1-P4 coordinates CG coordinates

P1 P2 P3 P4 a b x ykg kg kg kg kg kg mm mm mm mm

SYSCROLL20-35 Air CO

20 54 59 64 69 248 254 457 1.441 264 68025 62 65 74 77 279 285 457 1.441 260 67630 62 66 76 79 283 289 457 1.441 260 66935 68 68 81 81 298 304 457 1.441 255 677

SYSCROLL20-35 Air HP

20 53 60 65 72 250 256 457 1.441 266 66925 61 65 75 80 281 287 457 1.441 263 66530 61 66 77 82 286 291 457 1.441 263 65735 66 68 82 84 299 305 457 1.441 258 663

SYSCROLL20-35

Air CO + Hydrokit

20 99 104 109 114 427 - 457 1.441 260 70525 107 110 119 122 458 - 457 1.441 258 70130 107 110 121 124 462 - 457 1.441 258 69635 113 113 126 126 477 - 457 1.441 255 700

SYSCROLL20-35

Air HP + Hydrokit

20 98 104 110 116 429 - 457 1.441 262 69825 105 110 120 124 460 - 457 1.441 260 69430 106 110 122 127 465 - 457 1.441 260 68835 111 113 126 128 478 - 457 1.441 257 691

P3

P1

Y

XC.G. X

C.G.

Y

a

b

P2

P4

Syst

emai

r · M

ay 2

013

· EDM

SYS

CRO

LL 2

0-35

AIR

-S-1

GB/0

5.13

As p

art o

f our

ong

oing

pro

duct

impr

ovem

ent p

rogr

amm

e, o

ur p

rodu

cts

are

subj

ect t

o ch

ange

with

out p

rior n

otic

e. N

on c

ontr

actu

al p

hoto

s.

Systemair srlVia XXV Aprile, 2920825 Barlassina (MB) Italy

Tel. +39 0362 680 1Fax +39 0362 680 693

[email protected]