System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions 1 Refer to the QuickLIT website for the most up-to-date version of this document. Application System 450 is a family of modular, digital electronic controls that is easily assembled and set up to provide reliable temperature, pressure, and humidity control for a wide variety of Heating, Air Conditioning, Ventilating, and Refrigeration (HVACR) and commercial/industrial process applications. The System 450 reset control modules allow you to configure custom application-specific control systems with reset control and/or real-time setback control for temperature and humidity (only) control applications. System 450 expansion modules allow you to control up to 10 outputs, which can be relay and analog outputs. C450RxN-3 Reset Control models are Single-Pole, Double-Throw (SPDT) relay control modules with temperature reset capability, real-time setback capability, a Liquid Crystal Display (LCD), and a four-button touch pad User Interface (UI) that allow you to set up custom System 450 control systems. The C450RBN-3 model provides one SPDT relay. The C450RCN-3 model provides two SPDT relays. Refer to the System 450™ Series Modular Control Systems with Reset Control Modules Technical Bulletin (LIT-12011842) for more detailed information on designing, installing, setting up, and troubleshooting System 450 Series components and control systems. The System 450 technical bulletin can be accessed and downloaded on the Johnson Controls® Online Product Literature Web site (QuickLIT) at the following Web address: http://cgproducts.johnsoncontrols.com/default.aspx . IMPORTANT: Use this System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output only as an operating control. Where failure or malfunction of the System 450™ Series Control Module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450™ Series Control Module. IMPORTANT: Utiliser ce System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output uniquement en tant que dispositif de régulation. Lorsqu'une défaillance ou un dysfonctionnement du System 450™ Series Control Module risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du System 450™ Series Control Module. System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions C450RBN-3 C450RCN-3 Part No. 24-7664-2888, Rev. C Issued March 2016

Upload: vuongthu

Post on 27-May-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Refer to the QuickLIT website for the most up-to-date version of this document.

System 450™ Series Reset Control Modules with Real-Time Clock and Relay OutputInstallation InstructionsC450RBN-3C450RCN-3

Part No. 24-7664-2888, Rev. CIssued March 2016

Application

System 450 is a family of modular, digital electronic controls that is easily assembled and set up to provide reliable temperature, pressure, and humidity control for a wide variety of Heating, Air Conditioning, Ventilating, and Refrigeration (HVACR) and commercial/industrial process applications.

The System 450 reset control modules allow you to configure custom application-specific control systems with reset control and/or real-time setback control for temperature and humidity (only) control applications. System 450 expansion modules allow you to control up to 10 outputs, which can be relay and analog outputs.

C450RxN-3 Reset Control models are Single-Pole, Double-Throw (SPDT) relay control modules with temperature reset capability, real-time setback capability, a Liquid Crystal Display (LCD), and a four-button touch pad User Interface (UI) that allow you to set up custom System 450 control systems.

The C450RBN-3 model provides one SPDT relay. The C450RCN-3 model provides two SPDT relays.

Refer to the System 450™ Series Modular Control Systems with Reset Control Modules Technical Bulletin (LIT-12011842) for more detailed information on designing, installing, setting up, and troubleshooting System 450 Series components and control systems. The System 450 technical bulletin can be accessed and downloaded on the Johnson Controls® Online Product Literature Web site (QuickLIT) at the following Web address:http://cgproducts.johnsoncontrols.com/default.aspx.

IMPORTANT: Use this System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output only as an operating control. Where failure or malfunction of the System 450™ Series Control Module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450™ Series Control Module.

IMPORTANT: Utiliser ce System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output uniquement en tant que dispositif de régulation. Lorsqu'une défaillance ou un dysfonctionnement du System 450™ Series Control Module risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du System 450™ Series Control Module.

System 450™ Series Reset Control Modules with Real-Time Clock and Relay OutputInstallation Instructions

1

Page 2: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Installation

Location ConsiderationsObserve the following System 450 location guidelines:

• Ensure that the mounting surface can support the module assembly, mounting hardware, and any (user-supplied) panel or enclosure.

• Mount the modules upright and plugged together in a horizontal row where possible (Figure 3). DIN rail mounting is highly recommended.

• Mount modules on flat, even surfaces.

• Allow sufficient space for wires and connections.

• Mount the modules in locations free of corrosive vapors and observe the ambient operating conditions in the Technical Specifications.

• Do not mount the modules on surfaces that are prone to vibration or in locations where radio frequency or electromagnetic emissions may cause interference.

• Do not install the modules in airtight enclosures.

• Do not install heat-generating devices in an enclosure with the modules that may cause the temperature to exceed the ambient operating limit.

MountingMount System 450 modules on 35 mm DIN rail (recommended) or directly to an even wall surface. To mount modules on DIN rail:

1. Provide a section of 35 mm DIN rail that is longer than the module assembly width, and mount the DIN rail horizontally in a suitable location using appropriate mounting hardware/fasteners.

2. Clip the control module on the rail, position the upper DIN rail clips on the top rail, and gently snap the lower clips onto the rail.

3. Clip the remaining power and/or expansion modules to the right of the control module on to the DIN rail and plug the 6-pin module connectors together (Figure 3).

Note: If your System 450 control system uses a power module, the power module must be plugged into the right-hand side of the control module.

To direct-mount modules to wall surfaces:

1. Plug the modules together, remove the module covers, place the assembly against wall surface horizontally in a suitable location, and mark the mount hole locations on the surface (Figure 1).

2. Install appropriate screw fasteners, leaving screw heads approximately one to two turns away from flush to the surface.

3. Place the assembly over screw heads on the mounting slots, and carefully tighten the mounting screws.

Note: If you mount the modules on an uneven surface, do not damage the housings when tightening mounting screws. Use shims/washers to mount module assembly evenly on the surface.

Refer to the control sensor installation instructions for information on locating and mounting control sensors.

Figure 1: System 450 Module Dimensions, mm (in.)

128(5)

63(2-1/2)

63(2-1/2)

75(2-15/16)

38(1-1/2)

35 mmDIN RailMount

Channel

1/2 in. Conduit Hole(Nominal Trade Size)

63(2-1/2)

13(1/2)

40(1-9/16)

FIG

:new

_enc

losu

re_d

ims

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

2

Page 3: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Wiring

See Figure 2 and Table 1 for electrical termination locations and wiring information. See Technical Specifications on page 25 for electrical ratings.

See Figure 5 for the active/passive sensor jumper settings.

!WARNING: Risk of Electric Shock.Disconnect or isolate all power supplies before making electrical connections. More than one disconnection or isolation may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.

AVERTISSEMENT : Risque de décharge électrique.Débrancher ou isoler toute alimentation avant de réaliser un raccordement électrique. Plusieurs isolations et débranchements sont peut-être nécessaires pour -couper entièrement l'alimentation de l'équipement. Tout contact avec des composants porteurs de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles.

IMPORTANT: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations.

IMPORTANT: Do not exceed the System 450 module electrical ratings. Exceeding module electrical ratings can result in permanent damage to the modules and void any warranty.

IMPORTANT: Run all low-voltage wiring and cables separate from all high-voltage wiring. Shielded cable is strongly recommended for input (sensor) and analog output cables that are exposed to high electromagnetic or radio frequency noise.

IMPORTANT: Electrostatic discharge can damage System 450 modules. Use proper Electrostatic Discharge (ESD) precautions during installation and servicing to avoid damaging System 450 modules.

IMPORTANT: Do not connect 24 VAC supply power to the System 450 modules before finishing wiring and checking all wiring connections. Short circuits or improperly connected wires can result in damage to the modules and void any warranty.

IMPORTANT: A System 450 control module and module assembly can be connected to an internal power source (a System 450 power module) or an external power source (24 V power connected to the 24V and COM terminals on the control module), but must not be connected to both power sources simultaneously. Connecting a control module to both internal and external power sources can damage the modules and void any warranty.

IMPORTANT: When connecting System 450 compatible sensors with shielded cable to a System 450 control module, connect the cable shield drain lead to one of the C (common) terminals on the input sensor terminal block. Do not connect the shield at any other point along the cable. Isolate and insulate the shield drain at the sensor end of the cable. Connecting a cable shield at more than one point can enable transient currents to flow through the sensor cable shield, which can cause erratic control operation.

Sn2CSn35V

24V

Sn1C

Common terminals (C)are internallyconnected.

LNC

1

LNO

1

LC1

InternalSPDT Relay

Normally Closed/OffPosition

6-Pin ModuleConnector

Some models have asecond output relay andterminal block labeled

LNC2, LNO2, and LC2.

FIG

:sys

450_

rly_

cntr

l_w

ir

Note:not

The relay output terminals connect to an internal SPDTrelay and do supply any power to the application.

Supply Power andInput Sensor Terminals

Low Voltage (<30 V)

Dry-Contact, Line-VoltageRelay Output Terminals

(Seefor Electrical Ratings.)

Technical Specifications

Active/Passive SensorJumper Positions

Sn-1Sn-2Sn-3

Figure 2: C450RxN-3 Wiring Terminals

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

3

Page 4: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Table 1: System 450 Terminal Wiring Information

Label Terminal Function Wire Sizes

24V Accepts 24 VAC supply power, when a C450YNN power module is not connected, and provides power terminal for 24 VAC (humidity) sensors.

0.08 mm2 to 1.5 mm2

28 AWG to 16 AWG5V Provides 5 VDC power for active sensors.

Sn-1, Sn-2, Sn-3

Accepts passive or active (0-5 VDC) input signals from sensors.Note: In System 450 reset control systems, Sn-1 is the Master sensor (typically an outdoor air temperature sensor) and Sn-2 is the controlled loop sensor (a temperature or humidity sensor).Note: You must position the Active/Passive Sensor Jumper (Figure 3 and Figure 5) correctly for each sensor in your control system before operating the system. See Setting Active/Passive Sensor Jumpers for more information.

C(Three Terminals)

Provide low-voltage common connections for 24 VAC power and passive or active sensors connected to the 5V, Sn1, Sn2, and Sn3 terminals. Note: The three C terminals are connected internally and can be connected to ground in the field.

LNC1, LNC2 Connects equipment control circuit to the normally closed contact on the SPDT1 relay. 0.08 mm2 to 2.5 mm2

28 AWG to 14 AWGLNO1, LNO2

Connects equipment control circuit to the normally open contact on the SPDT1 relay.

LC1, LC2 Connects line (power) to common on the SPDT1 relay.

1. See Internal SPDT Relay insert in Figure 2 for more System 450 relay contact and terminal information. See Technical Specifications for SPDT relay electrical ratings.

Figure 3: System 450 Reset Control System Example for a Three-Stage Boiler with or without Load Balancing (See Figure 9.)

LC

1L

NO

1L

NC

1

LC

2L

NO

2L

NC

2

240VAC

120VAC

LC

1L

NO

1L

NC

1

LC

2L

NO

2L

NC

2

L2L1

L2L1

L2L1

L2L1

L1 L2

C450RCN-1Reset Control Module C450YNN-1

Power Module

C450SCN-1Expansion Module

Sn-1Sn-2Sn-3

RelayOutput 1

RelayOutput 2

RelayOutput 3

RelayOutput 4

Active/Passive Sensor Jumpers(All jumpers set to Passive.)

Note: In 120 VAC applications, L1 must be the Hot lead and L2 must be the Neutral/Common lead.

FIG

:sys

450_

app_

3stg

_bol

r

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

4

Page 5: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Setup and Adjustments

System 450 Reset ComponentsA System 450 reset control system consists of one reset control module, one to three input sensors, and one to ten outputs that provide any combination of (On/Off) relay control or (0–10 VDC or 4–20 mA) analog control. Figure 3 shows a reset control system for two boilers, a boiler water circulation pump, and an outside air damper.

Setting up a Module AssemblyTo set up a System 450 module assembly:

1. Determine the controlled conditions, sensor types, and value ranges required for your control system, and select the appropriate System 450 sensors.

2. Determine the number and type (relay or analog) of outputs required to control your application, and select the appropriate System 450 control module and expansion modules.

3. Assemble the control and expansion modules, starting with the control module on the left.

Note: If you use a C450YNN-1 power module, it must be plugged into the control module. Plug in any expansion modules (for your control system) to the right of the power module.

4. Apply supply power to the module assembly.

You can now set up your control system in the System 450 reset control module UI.

Note: After you power on your module assembly, you can set up your control system in the control module UI before wiring the sensors or outputs to your assembly.

Setting Active/Passive Sensor JumpersBefore putting your System 450 reset control system into operation, you must set up each sensor in your system as either passive or active by positioning the jumper on the terminal pins on the terminal block located below the sensor terminal block. See Figure 3.

Temperature sensors are passive (2-wire) sensors and the corresponding jumpers must be positioned across both pins. Humidity transducers are active (3-wire) sensors and corresponding jumpers must be positioned on one pin (or removed completely).

Figure 5 shows the jumper positions for the System 450 Reset Control example shown in Figure 3.

Figure 4: System 450 Reset Control Module Output Relay LEDs, LCD,and Four-Button Touch Pad User Interface

M

Output (or Sensor) Number:

4

Displays anumerical value that identifies the Output(or Sensor) associated with the Status or Setup Value shown on the screen. OutputNumbers are automatically determined bythe outputs' physical positions (left to right)in the module assembly. ( = Output 4.)

Control Ramp Icon: Displays whether anAnalog Output increases or decreases asthe sensor input increases, and whether theoutput signal strength is at minimum ormaximum when the sensed property is atSetpoint. The Control Ramp icon displayedis determined by the Output's setup values(SP, EP, Pb, OSET, OSP, OEP).

MENU Button: Press to move through thesensor and output setup-start-screens.When moving through the status or setup screens, press to return to the status startscreen or setup start screen.

M

M

Status or Setup Identifier:

or OSP

Displays theunit of measurement, output, sensor number,

setup parameter for the displayed Status orSetup Value. (Setup Identifier represents% Output Signal Strength at Setpoint.)

UP and DOWN Buttons: Press or to selecta different value for any flashing value in theSetup Value field. In the Main/Default (SensorStatus) screen, press and hold both and for 5 seconds to access the Setup Start screens.

Status or Setup Value:

100

Displays the currentinput status, output status, or setup parametervalue for the displayed input sensor or output.

select a different ParameterValue when the value is flashing. ( = 100%.)

Press or to

Light-Emitting Diode (LED): Green LEDson Control Modules and Expansion Moduleswith relays (only) indicates if theassociated Relay Output is On or Off.

FIG

:sys450_rst_cntrl_modul

NEXT Button: In the Main/Default screens, press to scroll through the system statusscreens. In a setup screen, press to save the (flashing) Setup Value and go to thenext setup screen.

Figure 5: Active/Passive Sensor Jumper Positions for System 450 Example Shown in Figure 3

Sensor 1:sets Sn-1 to Passive (Temperature).

Jumper positioned across two pinssets Sn-2 to Passive (Temperature).

Jumper positioned on one pin(or removed) sets Sn-3 to Active (Humidity).

Sensor 2:

Sensor 3:

Jumper positioned across two pins

Sn-1Sn-2Sn-3 FI

G:s

ys45

0_rs

t_jm

prs

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

5

Page 6: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Setting up a Control System in User InterfaceSystem 450 control modules have a backlit LCD and a four-button touch pad UI (Figure 4) that enable you to set up your control system. To set up a control system in the System 450 UI:

1. Build your control system module assembly and connect it to power. See Setting up a Module Assembly on page 5.

Note: Every time a module assembly is powered ON, the control module polls all of the modules to identify output type (relay or analog) and assigns a sequential output number (1 to 9 [0 = 10]) to each output starting with the control module output on the left. The output numbers identify each output’s setup screens in the UI. (See Figure 4.)

2. Access the System 450 setup screens in the UI. See Accessing the System 450 Setup Screens.

3. Set up the control system sensors (inputs) in the UI. See Setting up System 450 Sensors.

4. Set up the control system outputs in the UI. See Setting up System 450 Outputs on page 11.

5. Set up the clock and occupied/unoccupied schedule in the UI for systems that use setback. See Setting up Time and Day of Week on page 20 and Setting up an Occupied/Unoccupied Schedule on page 21.

See Figure 4 for an explanation of the System 450 display screen and the 4-button touch pad features and functions. See Table 3 for Reset Control Sensor Types and associated sensors. See Table 4 through Table 12 for System 450 UI setup information and procedures.

Viewing the Main and System Status Screens

After you install, wire, power on, and set up your control system in the UI, the Main screens appear on the LCD. During normal operation, the Main screens automatically scroll through the current status of each sensor in your control system, the time and day, and the current Reset Setpoint value. See Table 2 for more information on the Main screens.

The System Status screens display the current status of each output in your control system and the runtime hours for each Output Relay. In the Main screen, press

repeatedly to scroll through and view all of the Main and System Status screens in your control system. See Table 2 for more information on the System Status screens.

IMPORTANT: When power is disconnected, the time clock keeps time for 12 hours before resetting to default; the remaining setup values entered into the UI remain in non-volatile memory indefinitely.

IMPORTANT: Do not change the module positions after a System 450 control system is set up in the UI. System 450 control logic is set up in the UI according to the Sensor Types, the output types, and the output numbers. Changing modules or module positions in a module assembly that is already set up in the UI, can change the output numbers, output types, and the setup values of the assembly outputs, which requires setting up the outputs again.

Table 2: System 450 Reset Control Main and Status Screens Information and Procedures (Part 1 of 2)

LCD Screen Name, Description/Function, User Action, and Example

Main Screens: During normal operation, the Reset Control Main screens automatically scroll through the current temperature or humidity sensed at each sensor, the current time and day, and the current calculated Reset Setpoint (RSP) value. See the Main Screens row in the setup screens flow chart in Figure 9 on page 24.Note: You must set up time and day of week for control applications that use the setback feature, but you can also set up time and day on control systems that do not use the setback feature. If the time and day have not been set up, the Time/Day Status screen displays – –:– –, MON, and AM.Note: Main screens are view-only; selections cannot be made in Main screens.1. During normal operation while the LCD is auto-scrolling through the Main screens:

• Press repeatedly to scroll through and view the available System Status screens.

• Press and hold and simultaneously for 5 seconds to access the Setup Start screens and the System 450 system setup screens.

Screen examples show Sensor 1 sensing 27°F outdoor air at the Master sensor, Sensor 2 sensing 151°F at the boiler water supply outlet, the current time and day is 11:32 A.M. on Tuesday, and the current calculated Reset Setpoint is 153°F.

27ºF1

ºF2

151

11:32TUEAM

153RSP

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

6

Page 7: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Accessing the System 450 Setup Screens

You can access the System 450 setup screens from the Main screens. To access the System 450 setup screens:

1. Apply power to your module assembly. After a startup check, the (available) Main screens appear and automatically scroll on the LCD.

Note: The only Main screen displayed, prior to setting up your control system in the UI, is the default time and day status screen, which displays – –:– –, MON, and AM.

2. In any of the Main screens, press and hold and simultaneously for 5 seconds to go to the

Sensor Setup Start screen and access the rest of the System 450 setup screens.

Note: The Sensor Setup Start screen is the first screen displayed when you access the System 450 setup screens. From the Sensor Setup Start screen, you can navigate to all of the remaining setup screens for your control system.

3. Press repeatedly to scroll through all of the Setup Start screens. (See Figure 9 on page 24.)

Note: All Setup Start screens are view-only; selections cannot be made in Setup Start screens. In any Setup Start screen, you can return to the Main screens by pressing and simultaneously. Also, the UI returns to the Main screens after 2 minutes of inactivity in any screen in the UI.

4. Press in any Setup Start screen to go to the setup screens. (See Figure 9 on page 24.)

Setting up System 450 Sensors

You must set up the sensors (inputs) for your control system before you can set up any of the outputs. To set up the sensors, you must access the setup screens. See Accessing the System 450 Setup Screens.

Table 3 provides information about System 450 compatible sensors for Reset Control Modules. Table 4 provides sensor setup information, procedures, and example screens. Figure 9 on page 24 provides a System 450 UI screen flowchart example.

System Status Screens: The System Status screens include all of the Main screens, plus additional status screens for all the outputs in your control system, including the following:• Relay Output Status screens, which display output number and relay status (On/Off). • Analog Output Status screens, which display output number, the current analog signal strength (as a %

of the total signal strength), and the control ramp icon.• Runtime Hours Status screens, which display the runtime (ON) hours for the Relay Outputs in your

control system.See the System Status Screens row in the setup screens flow chart in Figure 9 on page 24.Note: System Status screens (except Runtime Hours Status screens) are view-only; selections cannot be made in Status screens.

Note: When a Runtime Hours Status screen is displayed, you can press and hold for 5 seconds to clear the displayed runtime hours and reset the Relay Output’s total runtime hours to 0.

2. Press repeatedly to scroll through and view the System Status screens for your control system.

Screen examples show Relay Output 1 is On; Analog Output 3 signal strength is 64 (%) and the control ramp icon indicates that the Analog Output is set up with SP<EP and OSP<OEP; Relay Output 2 has 17 hours of total runtime (relay ON).

Table 2: System 450 Reset Control Main and Status Screens Information and Procedures (Part 2 of 2)

LCD Screen Name, Description/Function, User Action, and Example

OnOUT1

64OUT3

17HRS2

Table 3: System 450 Reset Control Sensor Types, Setup Values, and Product CodesSensor Type

Unit of Measurement Value

Range of Usable Values

Resolution Increments Value

Minimum Differential or Proportional Band

Effective Sensing Range

Range of Usable Pb/dIFF and SbK Valuesfor RSP

Range of Usable OSET Values for RSP

Sensor Product Type Number

F F -40 to 250 1 1 -46 to 255 -30 to 30 -30 to 30 A99B-xxx

C C -40 to 121 0.5 0.5 -43 to 124 -17 to 17 -17 to 17 A99B-xxx

rH % Humidity 10 to 95 1 2 1 to 100 -20 to 20 -30 to 30 HE-67Sx-x

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

7

Page 8: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Table 4: System 450 Reset Control Sensor Setup Screen Information and Procedures

LCD Screen Name, Description/Function, User Action, and Example

Sensor Setup Start Screen: The Sensor Setup Start screen is the first screen displayed when you access the System 450 setup screens. From the Sensor Setup Start screen you can navigate to all of the remaining Setup Start screens in your control system. See the Setup Start screens in the column on the left side of the setup flow chart and the Sensor Setup screens row in Figure 9 on page 24.Note: You must set up the sensors for your control system, including the reset setpoint sensor (rES) (if required for your application) before you can set up the control system outputs. All Setup Start screens are view-only; selections cannot be made in Setup Start screens.

1. In the Sensor Setup Start screen, press to go to the first Sensor Type Selection screen (Sn-1); and begin setting up the sensors in your control system. If the sensors are already set up, press (repeatedly) to scroll through the remaining Setup Start screens and continue setting up your control system.

Screen example shows the Sensor Setup Start screen with four flashing dashes.

Sensor Type Selection Screens: The Sensor Type you select for an input sensor automatically determines the setup parameters and values for each output that is set up to reference that sensor. See Table 3 for information about System 450 sensors/transducers, Sensor Types, setup values, and product code numbers.Note: System 450 Reset Control Modules are designed for use with temperature (°C or °F) and humidity (rH) Sensors Types only. Pressure Sensor Types are not available in the reset control module UI. You also can select no Sensor Type (- -) when your control systems uses less than three sensors.Note: In System 450 reset control systems, Sensor 1 (Sn-1) is the Master sensor and must always be a temperature sensor. Sn-2 must be the control loop sensor. The Sn-1 Master sensor is typically (but not always) an outdoor air temperature sensor. Sensor 2 (Sn-2) and Sensor 3 (Sn-3) can be temperature or humidity, depending on your application. The Reset Setpoint sensor (rES) cannot be set up for your control system until both the Sn-1 and Sn-2 are set up in the UI.Note: For an output to operate properly, the selected Sensor Type must match the sensor model wired to the control module, and the correct sensors must be wired to the correct control module input terminals.

2. In the Sn-1 Sensor Type Selection screen, press or to select the desired Sensor Type (°F, °C, or --). Press to save your selection and go to the Sn-2 Sensor Type Selection screen.

3. In the Sn-2 Sensor Type Selection screen, press or to select the desired Sensor Type (°F, °C, rH, or --). Press to save your selection and go to the Sn-3 Sensor Type Selection screen.

Note: If your control system does not use three sensors, simply press while the two dashes are flashing in a Sensor Type Selection screen to save no Sensor Type and go to the next screen.

4. In the Sn-3 Sensor Type Selection screen, press or to select the desired Sensor Type (°F, °C, rH, or --). Press to save your selection and go to the Temperature Offset Setup screen for Sn-1.

Screen examples show Sn-1 set to Sensor Type °F; Sn-2 set to °F; and Sn-3 set to rH.

Temperature Display Offset Selection Screens: You can select a temperature offset for each temperature (only) sensor in your control system. The selected offset value is added to the sensed temperature value to calculate the displayed temperature value (sensed °F + OFFS = displayed °F). The Temperature Display Offset value is typically 0 or a very low value.Sensor Type °F enables an offset of +/- 5°F in 1 degree increments.Sensor Type °C enables an offset of +/- 2.5°C in 0.5 degree increments.Note:

5. Press or to select the desired temperature offset value. Press :• to go to the next Temperature Offset Selection screen (if there are additional temperature

sensors in your control system) and repeat this step for each temperature sensor• to return to the Sensors Setup-Start ScreenScreen example shows 0 as the selected temperature display offset value for Sensor 2.

Sensors Setup Start Screen: The hardwire sensors are setup in the UI.

6. Press to scroll through the remaining Setup Start screens and continue setting up your control system, or press and simultaneously to return to the System 450 Main screens.

SENS– – –

Sn–1ºF

Sn-2ºF

Sn-3rH

OFFS2

0

SENS– – –

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

8

Page 9: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Setting up the System 450 Reset Setpoint

The System 450 Reset Control Modules feature temperature and humidity setpoint reset capability based on a Master temperature sensor (Sn-1) and a control loop sensor (Sn-2).

You easily can set up a custom calculated (floating) Reset Setpoint (RSP) that can be referenced by any of the outputs in your control system. All control system outputs that are set up to reference the Reset Setpoint sensor (rES) use the same RSP setup parameters and RSP to control output. During normal operation the current RSP is displayed in one of the Main screens.

Figure 6 illustrates the relationships between the setup parameters that define the calculated RSP.

Note: You must set up Sn-1 and Sn-2 before you can set up a RSP for your reset control system. Sn-1 is always the Master temperature sensor; typically an outdoor air temperature sensor. Sn-2 is always the control loop sensor; typically a boiler or chiller water supply loop sensor. But Sn-2 can also be a zone temperature or humidity sensor depending on your application, and the RSP can be a temperature or humidity value depending on the Sn-2 Sensor Type you select in the Sensor Setup screens.

Table 5 provides information and procedures for setting up the RSP for your reset control system.

When you select the rES sensor in an output’s Sensor Selection screen, the output references the RSP, and System 450 displays the remaining output setup screens for setting up reset control based on a calculated (floating) setpoint (RSP) or proportional band (RSP + Pb).

Note: If you select Sn-1, Sn-2 or Sn-3 in the Sensor Selection screen, the output references a standard temperature or humidity sensor; and System 450 displays the remaining output setup screens for setting up standard control based on the fixed setpoint or proportional band (SP and EP) you select for the output.

You can also select a Shutdown High Temperature (SdHI) and/or Shutdown Low Temperature (SdLO) to shut down or limit the outputs that reference the rES sensor.

You can also enable Load Balancing (bAL) to balance the runtimes (relay ON times) of all relay outputs (only) that reference the rES sensor.

Figure 6: Example Reset Setpoint Applications for Boiler Water Supply and Chiller Water Supply Showing the Relationships between the Reset Setpoint Setup Parameters

MNSP = Minimum Reset Setpoint11045

MXSP = Maximum Reset Setpoint180

RSTR = Reset Range Start Temperature50

RENd = Reset Range End Temperature0

( [°F] BWS Temperature) (

( [

( [

( [

[°F] CWS Temperature)

°F] BWS Temperature)( [°F] CWS Temperature)

°F] Outdoor Air for BWS)( [°F] Outdoor Air for CWS)

°F] Outdoor Air for BWS) ( [°F] Outdoor Air for CWS)

From 0 to 50°F outdoor air, the (BWS) setpoint is reset between 180 and 110°F. Above 50°F outdoor air, the BWS setpoint is 110°F.Below 0°F outdoor air, the BWS is 180°F.

From 75 to 95°F outdoor air, the (CWS) setpoint is reset between 60 and 45°F. Above 95°F outdoor air, the CWS setpoint is 45°F.Below 75°F outdoor air, the CWS is 60°F.

60

95

75

RSP = Calculated (Floating) Reset Setpoint

Boiler Water Supply

Chiller Water Supply

Tem

pe

ratu

re a

t S

n-2

(a

t S

up

ply

Wat

er

Se

ns

or)

Temperature at Sn-1 (at Master Sensor/Outdoor Air)

MXSP180 (°F) BWS60 (°F) CWS

MNSP110 (°F) BWS45 (°F) CWS

RENd0 (°F) for BWS

75 (°F) for CWS

RSTR50 (°F) for BWS95 (°F) for CWS

HIGHERLOWER

HIGHER

Re

set S

etp

oint

Ra

nge

Outdoor TemperatureReset Control Range

RSP

FIG

:sys450_RSP

_stp

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

9

Page 10: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Table 5: System 450 Reset Setpoint Setup Screen Information and Procedures (Part 1 of 2)

LCD Screen Name, Description/Function, User Action, and Example

Reset Setpoint Setup Start Screen: You can set up a floating Reset Setpoint Sensor Type (rES) that can be referenced by the outputs in your System 450 reset control system. You can also select high and low temperature shutdown values (SdHI and SdLO) and an unoccupied Setback (SbK) for all Outputs with reset; and enable Load Balancing for relay (only) outputs with reset. See the Reset Setpoint Setup Screens row in the setup screens flow chart in Figure 9 on page 24.Note: Sn-1 and Sn-2 must be set up in the UI before the Reset Setpoint Setup Start screen is available. All Setup Start screens are view-only; selections cannot be made in Setup Start screens. 1. Press the Next button to go to the next screen and begin setting up the Reset Setpoint.Screen example shows Reset Setpoint Setup Start screen. The remaining screens in this table show the setup parameter values selected for the RSP, high and low temperature shutdown, unoccupied setback, and load balancing that are used by the outputs setup to reference the rES sensor (Output 2 and Output 4) in the control system example in Figure 3.

Minimum Reset Setpoint Selection Screen: The selected Minimum Reset Setpoint (MNSP) value establishes the lowest (temperature or humidity sensed at Sn-2) setpoint value that outputs with reset control can reference. The MNSP value and the Maximum Reset Setpoint (MXSP) value establish the total (temperature or humidity) range for the floating RSP value. See Figure 6.

2. Press or to select the Minimum Reset Setpoint value for the controlled condition (sensed at Sn-2), then press to save your selection and go to the next screen.

Screen example shows a Minimum Reset Setpoint value of 110 (F).

Maximum Reset Setpoint Selection Screen: The selected Maximum Reset Setpoint (MXSP) value establishes the highest (temperature or humidity sensed at Sn-2) setpoint that outputs with reset control can reference. The MXSP value and the MNSP value establish the total (temperature or humidity) range for the floating RSP value. See Figure 6.

3. Press or to select the Maximum Reset Setpoint value for the controlled condition (sensed at Sn-2), then press to save your selection and go to the next screen.

Screen example shows a Maximum Reset Setpoint value of 180 (F).

Reset Range Start Temperature Selection Screen: The Reset Start Temperature (RSTR) value and the Reset End Temperature (RENd) value establish the temperature range over which the RSP is calculated. RSTR and RENd are sensed at the Sn-1 Master sensor (typically outdoor air temperature). RSTR defines the high limit of temperature range and corresponds with MNSP. As the outdoor air temperature decreases below the RSTR, the RSP is driven from the MNSP towards MXSP. See Figure 6.Note: The relationship between RSTR and RENd (RSTR > RENd or RSTR < RENd) determines whether an increase in temperature sensed at Sn-1 increases or decreases the RSP. The examples shown in Figure 6 (RSTR > RENd) show RSP increases when the temperature increases at the Sn-1 Master sensor.

4. Press or to select the Reset Start Temperature value (sensed at the Master sensor Sn-1), then press to save your selection and go to the next screen.

Screen example shows a Reset Range Start Temperature value of 50 (F) selected.

Reset Range End Temperature Selection Screen: The Reset End Temperature (RENd) value and the RSTR value establish the temperature range over which the RSP is calculated. RSTR and RENd are sensed at the Sn-1 Master sensor (typically outdoor air temperature). RENd defines the low limit of the temperature range and corresponds with the MXSP. As the outdoor air temperature increases above the RENd, the RSP is driven from the MXSP towards MNSP. See Figure 6.

5. Press or to select the Reset End Temperature value (sensed at the Master sensor Sn-1), then press to save your selection and go to the next screen.

Screen example shows a Reset Range End Temperature value of 0 (F) selected.

Shutdown High Temperature Selection Screen: Shutdown High Temperature (SdHI) value establishes a high temperature limit (sensed at the Master sensor) at which relay outputs go to OFF and analog outputs go to the Output at Setpoint (OSP) value for all outputs in your control system that reference the Reset Setpoint sensor (rES). SdHI is typically used for heating systems to shutdown (relay) or limit (analog) output at high outdoor air temperatures.

6. Press or to select the Shutdown High Temperature value (sensed at the Master sensorSn-1) then press to save your selection and go to the next screen.

Screen example shows an Shutdown High Temperature value of 65 (F) selected.

RSET– – –

110MNSP

180MXSP

50RSTR

0RENd

65SdHI

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

10

Page 11: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Setting up System 450 Outputs

After you build and connect power to your control system module assembly, the output numbers and output types for your control system are automatically assigned in the UI.

Note: You must set up the system sensors for your control system before you can set up the outputs.

To set up System 450 outputs in the UI:

1. Access the System 450 setup screens. (See Accessing the System 450 Setup Screens.) The Sensor Setup Start screen appears.

2. At the Sensor Setup Start screen, press repeatedly to scroll through and select the desired Output Setup Start screen. The Output Setup Start screen indicates the output number and the output type for the selected output.

To set up Standard System 450 outputs without Reset Setpoint, see the following sections:

• Setting up a Standard Relay Output on page 11

• Setting up a Standard Analog Output on page 15

To set up System 450 outputs with Reset Setpoint, see the following sections:

• Setting up a Relay Output with Reset Setpoint on page 13

• Setting up an Analog Output with Reset Setpoint on page 18

Setting up a Standard Relay Output

A standard relay output provides On/Off control for your application based on a fixed setpoint sensor (Sn-1, Sn-2, or Sn-3).

Table 6 provides information, procedures, and screen examples for setting up standard relay outputs.

Shutdown Low Temperature Selection Screen: Shutdown Low Temperature (SdLO) value establishes a low temperature limit (sensed at the Master sensor) at which the relay outputs go to OFF and the analog outputs go to the Output at Setpoint (OSP) value for all outputs in your control system that references the Reset Setpoint sensor (rES). SdLO is typically used for cooling systems to shutdown (relay) or limit (analog) output at low outdoor air temperatures.

7. Press or to select the Shutdown Low Temperature value (sensed at the Master sensorSn-1), then press to save your selection and go to the next screen.

Screen example shows no Shutdown Low Temperature value selected.

Unoccupied Setback Selection Screen: The selected Setback (SbK) value determines a (floating) unoccupied setback value (RSP + SbK) for all of the relay and analog outputs that reference the rES sensor. The unoccupied Setback value (RSP + SbK) is referenced during all scheduled unoccupied times.Note: To use the Setback feature in your control system, you must also set up the (real) time and day of week, and a weekly occupied/unoccupied schedule. See Setting up Time and Day of Week and Setting up an Occupied/Unoccupied Schedule for more information and setup procedures.

8. Press or to select the Setback value for the controlled condition (temperature or humidity) during scheduled Unoccupied times, then press to save your selection and go to the next screen.

Screen example shows an Setback value of -10 (F) selected.

Load Balancing Selection Screen: Select ON to enable the Load Balancing feature.When the System 450 Load Balancing feature is enabled (ON), the control system uses the relay ON time of each Relay Output that references the RSP sensor and balances the total ON times of these Relay Outputs by cycling ON the Relay Output with the lowest total ON-time first, and the second lowest ON-time second, and so on. Note: The Load Balancing feature is not available for analog outputs.

9. Press or to enable (ON) or disable (OFF) the Load Balancing feature for your Reset Control system then press to save your selection and return to the Reset Setpoint Start screen.

Screen example shows Load Balancing feature is enabled (ON).

Reset Setpoint Setup Start Screen: The Reset Setpoint is now set up in the UI.

10. Press to scroll through the remaining Setup Start screens and continue setting up your control system, or press and simultaneously to return to the System 450 Main screens.

Table 5: System 450 Reset Setpoint Setup Screen Information and Procedures (Part 2 of 2)

LCD Screen Name, Description/Function, User Action, and Example

SdLO– –

SbK–10

ONbAL

RSET– – –

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

11

Page 12: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Table 6: System 450 Standard Relay Output Setup Screen Information and Procedures (Part 1 of 2)

LCD Screen Name, Description/Function, User Action, and Example

Relay Output Setup Start Screen: The output number and output type (relay or analog) are automatically assigned when you connect power to the module assembly. See the Standard Relay Output Setup Screens row in the setup screens flow chart in Figure 9 on page 24.Note: All Setup Start screens are view-only; selections cannot be made in Setup Start screens.

1. Press to go to the Sensor Selection screen. Screen example shows the Relay Output Setup-Start screen for Output 4. The remaining screens in this table show the parameter values selected for controlling the boiler water circulation pump connected to Relay Output 4 in Figure 3.

Sensor Selection Screen: The sensor you select here determines the output control type (standard or reset control), and output’s setup parameters and value ranges. If a sensor is not selected, the remaining output setup screens do not appear. If a sensor is already selected for this output, the Sensor Selection screen does not appear here and the next screen in the setup sequence appears instead. Note: To set up a Standard Relay Output, you must select Sn-1, Sn-2, or Sn-3 in this screen, and the selected sensor must already be set up in the System 450 UI. See Setting up System 450 Sensors on page 7 for information and procedures on setting up sensors.

2. Press or to select the Sensor (Sn-1, Sn-2, or Sn-3) that this output references, then press to save your sensor selection and go to the next screen.

Screen examples show the initial Relay Output 4 Sensor Selection screen with no sensor selected, followed by the same screen with the (Master) Sensor 1 selected for Relay Output 4.

Relay ON Selection Screen: Select the value at which the relay turns On. Relay ON is defined as relay LED On, relay contacts LNO to LC are closed, and LNC to LC contacts are open.Note: The value ranges and minimum differential are determined by the selected Sensor Type for the sensor that this output references and are enforced in the Relay ON and Relay OFF Selection screens.

3. Press or to select the value at which the output relay turns On, then press to save your selection and go to next screen.

Screen example shows an ON value of 55 (F) selected for Relay Output 4.

Relay OFF Selection Screen: Select the value at which the relay turns Off. Relay OFF is defined as relay LED Off, relay contacts NC to C are closed, and NO to C contacts are open.Note: The value ranges and minimum differential are determined by the selected Sensor Type for the sensor that this output references and are enforced in the Relay ON and Relay OFF Selection screens.

4. Press or to select the value at which output relay turns Off, then press to save your selection and go to next screen.

Screen example shows an OFF value of 65 (F) selected for Relay Output 4.

Minimum Relay ON Time Selection Screen: Minimum ON Time range is 0 to 300 seconds.

5. Press or to select the minimum time that the output relay remains On after reaching the Relay ON value, then press to save your selection and go to the next screen.

Screen example shows 0 seconds selected for the minimum relay-on time for Relay Output 4.

Minimum Relay OFF Time Selection Screen: Minimum Relay OFF Time range is 0 to 300 seconds.

6. Press or to select the minimum time that this output relay remains off after reaching the OFFT value, then press to save your selection and go to the next screen.

Screen example shows 10 seconds selected for the minimum relay-off time for Relay Output 4.

Unoccupied Setback Selection Screen: The selected setback (SbK) value (temperature or humidity) is added to the ON value (ON + SbK) and OFF value (OFF + SbK) to calculate the setback ON and OFF values that this output references during the unoccupied times set up in the Occupied/Unoccupied Schedule Setup screens.Note: To use the Setback feature in your control system, you must also set up the (real) time and day of week, and a weekly occupied/unoccupied schedule. See Setting up Time and Day of Week and Setting up an Occupied/Unoccupied Schedule for more information and setup procedures.

7. Press or to select the Unoccupied Setback value, then press to save your selection and go to the next screen.

Screen example shows 0 (F) selected for the Unoccupied Setback value for Relay Output 4.

OUTR4

– – –

SENS4– –

SENS4Sn-1

55ON4

65OFF4

0ONT4

10OFFT4

0SbK4

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

12

Page 13: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Setting up a Relay Output with Reset Setpoint

A relay output with reset setpoint provides On/Off control to your application based on the Reset Setpoint sensor (rES) that you set up for your control system.

Table 7 provides information, procedures, and screen examples for setting up relay outputs with Reset Setpoint (RSP) and the Reset Setpoint sensor (rES).

Sensor Failure Mode Selection Screen: Select this output’s mode of operation if the referenced sensor or sensor wiring fails. The output operates in the selected mode until the failure is remedied. Sensor Failure mode selections for Relay Outputs include: • ON: Output relay remains on during sensor failure.• OFF: Output relay remains off during sensor failure.

8. Press or to select Sensor Failure Mode for this output if the sensor or sensor wiring fails, then press to save your selection and go to the next screen.

Screen example shows sensor failure mode ON selected for Relay Output 1; the output relay is on if the referenced sensor or sensor wiring fails.

Edit Sensor Screen: Displays the (selected) sensor that this output references. Unless you need to change the sensor, press to complete the output setup and return to the Output Setup Start screen. If you need to change the sensor that this output references, you can select a different sensor in this screen. Note: Changing the sensor that an output references (in the Edit Sensor screen) changes the default setup parameters and values for the output, and requires setting up the output again.

9. If you do not need to change this output’s sensor, press to save the current sensor selection, complete the output setup, and return to the Output Setup Start screen.

To change this output’s sensor, press or to select the sensor that this output references. After you select a different sensor, press to go to the required output selection screen and repeat the output setup procedure for the new Sensor Type values.

Relay Output Setup Start Screen: This Standard Relay Output is now set up in the UI.

Press to scroll through the remaining Setup Start screens and continue setting up your control system, or press and simultaneously to return to the System 450 Main screens.

Table 6: System 450 Standard Relay Output Setup Screen Information and Procedures (Part 2 of 2)

LCD Screen Name, Description/Function, User Action, and Example

ONSNF1

SENS1Sn–1

OUTR1

– – –

Table 7: System 450 Relay Output with Reset Setup Screen Information and Procedures (Part 1 of 3)

LCD Screen Name, Description/Function, User Action, and Example

Relay Output Setup Start Screen: The output number and output type (relay or analog) are automatically assigned when you connect power to the module assembly. See the Relay Output with Reset Setpoint Setup Screens row in the setup screens flow chart in Figure 9 on page 24.Note: All Setup Start screens are view-only; selections cannot be made in Setup Start screens.

1. Press to go to the Sensor Selection screen. Screen example shows the Relay Output Setup Start screen for Output 2. The remaining screens in this table show the parameter values selected for Relay Output 2 to control the temperature of Boiler 1 in Figure 3 based on the RSP set up in Table 5.

Sensor Selection Screen: The sensor selected here determines the output control type (standard or reset control), and the output’s setup parameters and value ranges. If a sensor is not selected, the remaining output setup screens do not appear. If a sensor is already selected for this output, the Sensor Selection screen does not appear here, the next screen in the setup sequence appears instead. Note: To set up a Relay Output with Reset Setpoint, you must select rES in this screen. rES cannot be selected until the Reset Setpoint is set up in the System 450 UI. See Setting up the System 450 Reset Setpoint for information and procedures on setting up the RSP and rES.

2. Press or to select the Reset Setpoint Sensor (rES) for this output to reference, then press to save your sensor selection and go to next screen.

Screen examples show the initial Relay Output 2 Sensor Selection screen with no sensor selected, followed by the same screen with the Reset Setpoint sensor (rES) selected for Relay Output 2.

OUTR2

– – –

SENS2

– –

SENS2

rES

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

13

Page 14: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Reset Differential Selection Screen: Select a dIFF value to establish the fixed differential between the floating Relay-OFF setpoint (RSP) and the floating Relay-ON setpoint (RSP+dIFF). A positive differential (dIFF = +n) turns the relay ON when temperature or humidity increases; typically cooling. A negative differential (dIFF = -n) turns the relay ON when temperature or humidity decreases; typically heating.See Table 3 on page 7 for the (fixed) minimum differential and the range of usable dIFF values for outputs with RSP in your control system.

3. Press or to select the Reset Differential value for this output, then press to save your selection and go to the next screen.

Screen example shows -5 differential selected for Output 2.

Offset from Reset Setpoint Selection Screen: Select an OSET value to shift the (floating) Reset Setpoint (RSP) that the output references to a (floating) offset reset setpoint (RSP+OSET). A positive offset value (OSET = +n) raises the target reset setpoint referenced by the output.A negative offset value (OSET = -n) lowers the target reset setpoint referenced by the output.OSET is typically used to set up sequential offset reset setpoint values and stage multiple Relay Outputs. For example, four boilers can be staged with 0, 2, 4, and 6 (F) OSET values to stage the four boilers ON according to load increases. (You can also enable bAL to load balance the boiler runtimes. See Setting up the System 450 Reset Setpoint for information on the Load Balancing feature.)See Table 3 on page 7 for the range of usable OSET values for the outputs with RSP in your control system.

4. Press or to select the Reset Setpoint Offset value for this output, then press to save your value and go to the next screen.

Screen example shows 0 (F) offset selected for Output 2.

Minimum Relay ON Time Selection Screen: Minimum ON Time range is 0 to 300 seconds.

5. Press or to select the minimum time that the output relay remains On after reaching the Relay ON value, then press to save your selection and go to the next screen.

Screen example shows 5 seconds selected for the minimum ON-Time for Output 2.

Minimum Relay OFF Time Selection Screen: Minimum OFF Time range is 0 to 300 seconds.

6. Press or to select the minimum time that this output relay remains Off after reaching the Relay OFF value, then press to save your selection and go to the next screen.

Screen example shows 0 seconds selected for the minimum OFF-Time for Output 2.

Sensor Failure Mode Selection Screen: Select this output’s mode of operation if the referenced sensor or sensor wiring fails. The output operates in the selected mode until the failure is remedied. Sensor Failure mode selections for Relay Outputs include: • ON: Output relay remains On during sensor failure.• OFF: Output relay remains Off during sensor failure.

7. Press or to select the Sensor Failure Mode for this output, then press to save your selection and go to the next screen.

Screen example shows OFF sensor failure mode selected for Output 2.

Edit Sensor Screen: Displays the (selected) sensor that this output references. Unless you need to change the sensor, press to complete the output setup and return to the Output Setup Start screen. If you need to change the sensor that this output references, you can select a different sensor in this screen. Note: Changing the sensor that an output references (in the Edit Sensor screen) changes the default setup parameters and values for the output, and requires setting up the output again.

8. If you do not need to change this output’s sensor, press to save the current sensor selection, complete the output setup, and return to the Output Setup Start screen.

To change this output’s sensor, press or to select the sensor that this output references. After you select a different sensor, press to go to the required output selection screen and repeat the output setup procedure for the new Sensor Type values.

Table 7: System 450 Relay Output with Reset Setup Screen Information and Procedures (Part 2 of 3)

LCD Screen Name, Description/Function, User Action, and Example

dIFF2

– 5

0OSET2

5ONT2

0OFFT2

OFFSNF2

SENS2

rES

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

14

Page 15: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Setting up a Standard Analog Output

A standard analog output provides an analog signal to control your application based on a fixed setpoint sensor (Sn-1, Sn-2, or Sn-3).

Analog outputs provide an auto-selecting analog signal that is proportional to the sensed input condition. The System 450 analog output senses the impedance of the controlled equipment’s analog input circuit and automatically delivers either a 0–10 VDC or 4–20 mA signal to the controlled equipment.

The control action between the input signal and the output signal can be set up four different ways, depending on the values selected for the Setpoint (SP), End Point (EP), Percent Output Signal Strength at Setpoint (OSP), and Percent Output Signal Strength at End Point (OEP). The LCD displays different Control Ramp icons for the four control actions.

Figure 7 shows an example of the analog output setup values and the resulting output signal in a typical space heating application (SP > EP and OSP < OEP).

Relay Output Setup Start Screen: This Relay Output with Reset Setpoint is now set up in the UI.

9. Press to scroll through the remaining Setup Start screens and continue setting up your control system, or press and simultaneously to return to the System 450 Main screens.

Table 7: System 450 Relay Output with Reset Setup Screen Information and Procedures (Part 3 of 3)

LCD Screen Name, Description/Function, User Action, and Example

OUTR2

– – –

Figure 7: Control Ramp Example for a Typical Heating Application (SP > EP and OSP < OEP)

Sys

tem

Ou

tpu

t

0%

100%

Controlled ConditionLess Greater65°F

10%

70°F

SP > EP

OSP < OEP

SP = 70 ( ) EP = 65 ( )

OSP = 10 (%) OEP = 100 (%)

°F°F

OSP

OEP

SP

EP

ProportionalBand

Fig

:sys

450_

cntr

l_rm

p_ex

mpl

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

15

Page 16: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Figure 8 shows the four Control Ramp icons and describes their corresponding control actions and the setup value relationships required to configure the four control actions.

See Table 9 for setup information, procedures, and screen examples for standard analog outputs.

Table 8: System 450 Control Ramps, Analog Output Control Actions, and System Setup Value Relationships

Control Ramp Displayed

Control Action Set the Analog Output Value Relationships for the Desired Control Action and Corresponding Control Ramp

SP < EP

OSP < OEP

SP > EP

OSP < OEP

SP > EP

OSP > OEP

SP < EP

OSP > OEP

Output Minimum at SPPro

porti

onal

Band

OEP=100%

OSP=0%SP=50°F EP=60°F

Output Minimum at SP

Proportional

Band

EP=50°F SP=60°F

OEP=100%

OSP=0%

Output Maximum at SP

OSP=100%

OEP=0%

EP=50°F SP=60°F

Propo

rtion

al

Band

Output Maximum at SP

SP=50°F EP=60°F

OSP=100%

OEP=0%

Proportional

Band

Table 9: System 450 Standard Analog Output Setup Screen Information and Procedures (Part 1 of 3)

LCD Screen Name, Description/Function, User Action, Example

Analog Output Setup Start Screen: The output number and output type (relay or analog) are automatically assigned when you connect power to the module assembly. See the Standard Analog Output Setup Screens row in the setup screens flow chart in Figure 9 on page 24.Note: All Setup Start screens are view-only; selections cannot be made in Setup Start screens.

1. Press to go to the Sensor Selection screen. Screen example shows the Analog Output Setup-Start screen for Output 3. The remaining screens in this table show the parameter values selected for Analog Output 3 to control an outside air damper in Figure 3.

OUTA3

– – –

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

16

Page 17: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Sensor Selection Screen: The sensor you select here determines the output control type (standard or reset control), and output’s setup parameters and value ranges. If a sensor is not selected, the remaining output setup screens do not appear. If a sensor is already selected for this output, the Sensor Selection screen does not appear here and the next screen in the setup sequence appears instead. Note: To set up a Standard Analog Output, you must select Sn-1, Sn-2. or Sn-3 in this screen, and the selected sensor must already be set up in the System 450 UI. See Setting up System 450 Sensors on page 7 for information and procedures on setting up sensors.

2. Press or to select the Sensor (Sn-1, Sn-2, or Sn-3) that this output references, then press to save your sensor selection and go to the next screen.

Screen examples show the initial Analog Output 3 Sensor Selection screen with no sensor selected, followed by the same screen with the Sensor 3 (Sn-3) selected for Analog Output 3.

Setpoint Selection Screen: Select the Setpoint value that the controlled system drives towards and which, along with the End Point value, defines this output’s proportional band.Note: The output’s minimum proportional band (between Setpoint and End Point) is automatically enforced in the Setpoint and End Point Selection screens.

3. Press or to select this output’s Setpoint value, then press to save your selection and go to the next screen.

Screen example shows a Setpoint of 50 (%rH) selected for Output 3.

End Point Selection Screen: Select the End Point value that the controlled system drives away from (towards Setpoint) and which, along with the Setpoint value, defines this output’s proportional band.Note: The output’s minimum proportional band (between Setpoint and End Point) is automatically enforced in the Setpoint and End Point Selection screens.

4. Press or to select this output’s End Point value, then press to save your selection and go to the next screen.

Screen example shows a End Point of 60 (%rH) selected for Output 3.

Output Signal Strength at Setpoint Selection Screen: Select the strength of the signal that this output generates when the sensed condition is at the Setpoint value. Signal strength range is 0 to 100 (%).

5. Press or to select this output’s %Output Signal Strength at Setpoint value, then press to save your selection and go to the next screen.

Screen example shows Analog Output 3 is set up to generate 10% of the total signal strength when the input is at the Setpoint value (= 1 V or 5.6 mA).

Output Signal Strength at End Point Selection Screen: Select the strength of the signal that this output generates when the sensed condition is at the End Point value. Signal strength range is 0 to 100 (%).

6. Press or to select this output’s %Output Signal Strength at End Point value, then press to save your selection and go to the next screen.

Screen example shows Output 3 is set up to generate 90% of the total signal strength when the input is at the End Point value (= 9 V or 18.4 mA).

Unoccupied Setback Selection Screen: The selected setback (SbK) value (temperature or humidity) is added to the SP value (SP+SbK) and EP value (EP+SbK) to calculate a setback proportional band that this output references during the unoccupied times set up in the Occupied/Unoccupied Schedule Setup screens.Note: To use the Setback feature in your control system, you must also set up the (real) time and day of week, and a weekly occupied/unoccupied schedule. See Setting up Time and Day of Week and Setting up an Occupied/Unoccupied Schedule for more information and setup procedures.

7. Press or to select the Unoccupied Setback value, then press to save the selected value and go to the next screen.

Screen example shows 0 selected for the Unoccupied Setback value for Output 3.

Integration Constant Selection Screen: An integration constant allows you to set up Proportional plus Integral (P+I) control for this analog output. When properly set up, P+I control can drive the load closer to Setpoint than proportional-only control.Initially, you should select the I-C value of 0 (zero) for no integration constant. Refer to the System 450 Series Modular Controls Technical Bulletin (LIT-12011459) for more information on proportional plus integral control and setting an integration constant in the System 450 UI.

8. Press or to select the Integration Constant for this output, then press to save your selection and go to the next screen.

Screen example shows an Integration Constant of 0 (zero) selected for Output 3.

Table 9: System 450 Standard Analog Output Setup Screen Information and Procedures (Part 2 of 3)

LCD Screen Name, Description/Function, User Action, Example

SENS3

– –

SENS3Sn–3

50SP3

60EP3

10OSP3

90OEP3

0SbK3

0I–C3

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

17

Page 18: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Setting up an Analog Output with Reset Setpoint

An Analog Output with Reset Setpoint provides analog signal control for your application based the a Reset Setpoint sensor (rES) that you set up for your system.

See Setting up a Standard Analog Output for general information on setting up a System 450 Analog Output.

Table 10 provides information, procedures, and screen examples for setting up analog outputs with reset setpoint.

Sensor Failure Mode Selection Screen: You can select this output’s mode of operation in the event of a sensor or sensor wiring failure. The output operates in the selected mode until the failure is fixed. Sensor Failure Mode selections for Analog Outputs include: • ON: Output goes to the OEP value.• OFF: Output goes to the OSP value.

9. Press or to select the Sensor Failure Mode for this output, then press to save your selection and go to the next screen.

Screen example shows the OFF Sensor Failure Mode selected for Output 3.

Edit Sensor Screen: Displays the (selected) sensor that this output references. Unless you need to change the sensor, press to complete the output setup and return to the Output Setup Start screen. If you need to change the sensor that this output references, you can select a different sensor in this screen. Note: Changing the sensor that an output references (in the Edit Sensor screen) changes the default setup parameters and values for the output, and requires setting up the output again.

10. If you do not need to change this output’s sensor, press to save the current sensor selection, complete the output setup, and return to the Output Setup Start screen.

To change this output’s sensor, press or to select the sensor that this output references. After you select a different sensor, press to go to the required output selection screen and repeat the output setup procedure for the new Sensor Type values.

Analog Output Setup Start Screen: This Standard Analog Output is now set up in the UI.

11. Press to scroll through the remaining Setup Start screens and continue setting up your control system, or press and simultaneously to return to the System 450 Main screens.

Table 9: System 450 Standard Analog Output Setup Screen Information and Procedures (Part 3 of 3)

LCD Screen Name, Description/Function, User Action, Example

OFFSNF3

SENS3Sn–3

OUTA3

– – –

Table 10: System 450 Analog Output with Reset Setpoint Setup Screens Information and Procedures (Part 1 of 3)

LCD Screen Name, Description/Function, User Action, Example

Analog Output Setup Start Screen: The output number and output type (relay or analog) are automatically assigned when you connect power to the module assembly. See the Analog Output with Reset Setpoint Setup Screens row in the setup screens flow chart in Figure 9 on page 24.Note: All Setup Start screens are view-only; selections cannot be made in Setup Start screens.

1. Press to go to the Sensor Selection screen. Screen example shows the Analog Output Setup Start screen for Output 4. The remaining screens in this table show the parameter values selected for Analog Output 4 to control Boiler 2 in Figure 3 based on the RSP set up in Table 5.

Sensor Selection Screen: The sensor selected here determines the output control type (standard or reset control), and the output setup parameters and value ranges. If a sensor is not selected, the remaining output setup screens do not appear. If a sensor is already selected for this output, the Sensor Selection screen does not appear here, the next screen in the setup sequence appears instead. Note: To set up an Analog Output with Reset Setpoint, you must select rES in this screen. rES cannot be selected until the Reset Setpoint is set up in the System 450 UI. See Setting up the System 450 Reset Setpoint for information and procedures on setting up the RSP and rES.

2. Press or to select the Reset Setpoint Sensor (rES) for this output to reference, then press to save your sensor selection and go to the next screen.

Screen examples show the initial Analog Output 4 Sensor Selection screen with no sensor selected, followed by the same screen with the Reset Setpoint sensor (rES) selected for Analog Output 4.

OUTA4– – –

SENS4

– –

SENS4

rES

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

18

Page 19: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Proportional Band Selection Screen: The Pb value establishes the fixed proportional band between the (floating) setpoint and end point. The (floating) proportional band’s setpoint is RSP and the (floating) proportional band’s end point is RSP+Pb. See Table 3 on page 7 for the (fixed) minimum proportional band and the range of usable Pb values for outputs with RSP in your control system.

3. Press or to select this output’s Proportional Band value, then press to save your selection and go to the next screen.

Screen example shows a (floating) Proportional Band of +5 (F) selected for Output 4.

Offset from Reset Setpoint Point Selection Screen: Select an OSET value to shift the setpoint (RSP) (that the output references) to an offset reset setpoint (RSP+OSET). The OSET value also shifts the end point (RSP+Pb) to an offset end point (RSP+OSET+Pb), shifting the entire proportional band by the OSET value.A positive offset value (OSET = +n) raises the proportional band’s setpoint and end point values.A negative offset value (OSET = -n) lowers the proportional band’s setpoint and end point values.OSET is typically used to set up sequential offset reset setpoint values and stage multiple Analog Outputs.See Table 3 on page 7 for the range of usable OSET values for the outputs with RSP in your control system.

4. Press or to select the Reset Setpoint Offset value for this output, then press to save your selection and go to the next screen.

Screen example shows an Offset value of 0 (zero) selected for Output 4.

Output Signal Strength at Setpoint Selection Screen: Select the signal strength that this output generates when the sensed condition is at setpoint (RSP). The signal strength range is 0 to 100 (%).

5. Press or to select the %Output strength at Reset Setpoint value, then press to save your selection and go to the next screen.

Screen example shows Analog Output 4 is set up to generate 0% of the total signal strength when the input is at the Setpoint value (= 0 VDC or 4 mA).

Output Signal Strength at End Point Selection Screen: Select the signal strength that this output generates when the sensed condition is at end point (RSP+Pb). The signal strength range is 0 to 100 (%).

6. Press or to select the %Output strength at Reset End Point value, then press to save your selection and go to the next screen.

Screen example shows Output 4 is set up to generate 100% of the total output signal strength when the input is at the End Point value (= 10 VDC or 20 mA).

Integration Constant Selection Screen: An integration constant allows you to set up Proportional plus Integral (P+I) control for this analog output. When properly set up, P+I control can drive the load closer to Setpoint than proportional-only control.Initially, you should select the I-C value of 0 (zero) for no integration constant. Refer to the System 450 Series Modular Controls Technical Bulletin (LIT-12011459) for more information on proportional plus integral control and setting an integration constant in the System 450 UI.

7. Press or to select the Integration Constant for this output, then press to save your selection and go to the next screen.

Screen example shows an Integration Constant of 0 selected for Output 4.

Sensor Failure Mode Selection Screen:

8. Press or to select the Sensor Failure Mode for this output, then press to save your selection and go to the next screen.

You can select this output’s mode of operation in the event of a sensor or sensor wiring failure. The output operates in the selected mode until the failure is fixed. Sensor Failure Mode selections for Analog Outputs include: • ON: Output goes to the OEP value.• OFF: Output goes to the OSP value.Screen example shows the OFF Sensor Failure Mode selected for Output 4.

Table 10: System 450 Analog Output with Reset Setpoint Setup Screens Information and Procedures (Part 2 of 3)

LCD Screen Name, Description/Function, User Action, Example

+5Pb4

0OSET4

0OSP4

OEP4

100

0I–C4

OFFSNF4

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

19

Page 20: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Setting up Time and Day of Week

To use the System 450 Setback feature, you must set up the (real) time and day of the week. You can also set up time and day of week for any control system. However, time and day setup is not required for control systems that do not use the setback feature.

You must also set up a weekly occupied/unoccupied schedule and select setback values for outputs. See Setting up an Occupied/Unoccupied Schedule for setting up a weekly occupied/unoccupied schedule and Setting up the System 450 Reset Setpoint on page 9 for selecting setback values.

Edit Sensor Screen: Displays the (selected) sensor that this output references. Unless you need to change the sensor, press to complete the output setup and return to the Output Setup Start screen. If you need to change the sensor that this output references, you can select a different sensor in this screen. Note: Changing the sensor that an output references (in the Edit Sensor screen) changes the default setup parameters and values for the output, and requires setting up the output again.

9. If you do not need to change this output’s sensor, press to save the current sensor selection, complete the output setup, and return to the Output Setup Start screen.

To change this output’s sensor, press or to select the sensor that this output references. After you select a different sensor, press to go to the required output selection screen and repeat the output setup procedure for the new Sensor Type values.

Analog Output Setup Start Screen: This Analog Output with Reset Setpoint is now set up in UI.

10. Press to scroll through the remaining Setup Start screens and continue setting up your control system, or press and simultaneously to return to the System 450 Main screens.

Table 10: System 450 Analog Output with Reset Setpoint Setup Screens Information and Procedures (Part 3 of 3)

LCD Screen Name, Description/Function, User Action, Example

SENS4

rES

OUTA4– – –

Table 11: System 450 Sensor Setup Information and Procedures

LCD Screen Name, Description/Function, User Action, and Example

Time and Day Setup Start Screen: The Time Setup Start screen is displayed when you access the System 450 setup screens and scroll through the Setup Start screens by pressing repeatedly. See the Time and Day Setup Screens row in the setup screens flow chart in Figure 9 on page 24.Note: All Setup Start screens are view-only; selections cannot be made in Setup Start screens.

1. Press to go to the 12 or 24 Hour Clock Selection screen. Screen example shows the Time and Day Setup Start screen with four flashing dashes.

12 or 24 Hour Clock Selection Screen: The real-time clock can be set to display as a 12 hour or 24 hour format digital clock.

2. In the 12 or 24 Hour Clock Selection screen, press or to select either the 12 hour or 24 hour format clock display, then press to save your selection and go to the next screen.

Screen example shows 12 hour clock format selected.

Time of Day Setup Screen: Set the clock to real-time.

3. Press or to set the current time, then press to save the time setting and go to the next screen.

Screen example shows (real) time selected is 11:32 A.M.

Day of Week Setup Screen: Set the day to real-time. Note: 1 = MON, 2 = TUE, 3 = WED, 4 = THU, 5 = FRI, 6 = SA, and 7 = SUN.

4. Press or to select the current day of the week, then press to save the time setting and return to the Time and Day Setup Start screen.

Screen example shows day of week set to 2 (TUE, Tuesday).

Time and Day Setup Start Screen: The time of day and day of week are now set up in the System 450 UI and you have returned to the Setup Start screen.

5. Press to scroll through the remaining Setup Start screens and continue setting up your control system, or press and simultaneously to return to the System 450 Main screens.

TIME– – –

12HrCLK

11:32SETTAM

2SETd

TIME– – –

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

20

Page 21: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Setting up an Occupied/Unoccupied Schedule

To use the System 450 Setback feature, you must set up a weekly occupied/unoccupied schedule. However, a weekly occupied/unoccupied schedule is not required for control systems that do not use the setback feature. Table 12 provides occupied/unoccupied schedule setup information, procedures, and screen examples.

To use the System 450 Setback feature to provide setback control for a relay output, you must also select a Setback (SbK) value and set up the (real) time and day of the week. See Setting up the System 450 Reset Setpoint on page 9 for selecting setback values and Setting up Time and Day of Week for setting up time and day.

Occupied/Unoccupied Setback Modes

Relay Output That References an Input Sensor

See Figure 9. During the occupied time, OUTR4 relay turns ON at 55°F (13°C) and turns OFF at 65°F (18.5°C). During the unoccupied times with SbK = 0F° (0C°), there is no change to the On and OFF points.

Analog Output That References an Input SensorAn analog output can be added to a Reset control system and controlled by Sn-1, Sn-2, or Sn-3. This analog output can also be Setback according to the Time Clock Schedule. For example, if SbK = -5F° (-3C°) is selected in the OUTA setup screens, then during the unoccupied times, the SP becomes 5F° (3C°) lower and the EP becomes 5F° (3C°) lower.

Relay Output and Analog Output That Reference the Reset Function

See Figure 9. During the occupied time, the RSP is calculated using the Reset Applications from Figure 6. During the unoccupied time with the SbK = -10F° (-5.5C°), the RSP is calculated and 10F° (5.5C°) is subtracted. Using the example in Figure 9, the RSP would change from 153°F (67°C) to 143°F (61.5°C) during the unoccupied times.

The load balancing feature is not effected in its function as a result of Occupied/Unoccupied modes.

‐ ‐ ‐ ‐

SCHE

7:45

OC‐1AM

5:30

UN‐1PM

7:45

OC‐2AM

5:30

UN‐2PM

7:45

OC‐3AM

5:30

UN‐3PM

7:45

OC‐4AM

5:30

UN‐4PM

7:45

OC‐5AM

4:00

UN‐5PM

9:15

OC‐6AM

4:00

UN‐6PM

12:00

OC‐7AM

‐ ‐ : ‐ ‐

UN‐7AM

SundayDay 7

MondayDay 1

TuesdayDay 2

WednesdayDay 3

ThursdayDay 4

FridayDay 5

SaturdayDay 6

‐ ‐ ‐ ‐

SCHE

7: 45

OC‐1

17: 30

UN‐1

7:45

OC‐2

17:30

UN‐2

7:45

OC‐3

17:30

UN‐3

7:45

OC‐4

17:30

UN‐4

7:45

OC‐5

16:00

UN‐5

9:15

OC‐6

16:00

UN‐6

‐ ‐ :  ‐ ‐

OC‐7

0:00

UN‐7

SbKx must be entered and a 12 Hour Clock OR 24 Hour Clock must be set up before Occupied/Unoccupied  function  runs.

Unoccupied Mode 

for the entire day

17:30

Unoccupied

Mode

Occupied

mode

17:30

UnoccupiedMode

Occupiedmode

17:30

Unoccupied

Mode

Occupied

mode

16:00

UnoccupiedMode

Occupied

mode

16:00

Unoccupied

Mode

Occupied

mode

07:45 07:45 07:45 07:45 09:15

Weekly Occupied / Unoccupied  Schedule

00:00

6:00  

12:00

18:00

24 Hour Clock

12:00

3:00  

6:00

9:00

12 Hour Clock

Unoccupied Mode 

Midnight ‐ 7:45AM 

Occupied Mode

7:45AM to 5:30PM

Unoccupied Mode 

5:30PM ‐Midnight

06:00  

12:00

18:00

Unoccupied

Mode

17:30

07:45

Unoccupied Mode 

Midnight ‐ 7:45AM 

Occupied Mode

7:45AM to 5:30PM

Unoccupied Mode ‐

5:30PM ‐Midnight

Unoccupied Mode 

Midnight ‐ 7:45AM 

Occupied Mode

7:45AM ‐ 5:30PM

Unoccupied Mode 

5:30PM ‐Midnight

Unoccupied Mode 

Midnight ‐ 7:45AM 

Occupied Mode

7:45AM ‐ 5:30PM

Unoccupied Mode 

5:30PM ‐Midnight

Unoccupied Mode 

Midnight ‐ 7:45AM 

Occupied Mode

7:45AM ‐ 4:00PM

Unoccupied Mode 

4:00PM ‐Midnight

Unoccupied Mode 

Midnight ‐ 9:15AM 

Occupied Mode

9:15AM ‐ 4:00PM

Unoccupied Mode 

4:00PM ‐Midnight

Occupied

mode

Unoccupied

Mode

Figure 8: Example System 450 Reset Control Weekly Occupied/Unoccupied Setback Schedule

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

21

Page 22: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Table 12: System 450 Sensor Setup Information and Procedures (Part 1 of 2)

LCD Screen Name, Description/Function, User Action, and Example

Occupied/Unoccupied Schedule Setup Start Screen: The Occupied/Unoccupied Schedule Setup Start screen is displayed when you access the System 450 setup screens and scroll through the Setup Start screens by pressing repeatedly. See the Occupied/Unoccupied Schedule Setup Screens row in the setup screens flow chart in Figure 9 on page 24.Note: To use the System 450 Setback feature, you also must select a Setback (SbK) value for the outputs you want to set back and you must set up the (real) time and day of week. See Setting up the System 450 Reset Setpoint on page 9 and Setting up System 450 Outputs on page 11 for selecting output Setback (SbK) values. See Setting up Time and Day of Week on page 20 for setting up time and day of week.Note: You must set up the time and day of week before the schedule takes effect. You can select the output setback (SbK) values at any time.

1. Press to go to the Day 1 (SUN) Occupied Time Selection screen. Screen example shows the Occupied/Unoccupied Schedule Setup Start screen with four flashing dashes. The remaining screens in this table show how to set up the weekly schedule shown in Figure 8.

Day 1 (MON) Occupied Time Selection Screen: Select the time of day to begin the occupied time period for Day 1. (The time previous to this occupied time value is unoccupied time.)Note: You can set up one (only) Occupied time for each day of the week (days 1 through 7). When you select no time (- -:- -) in an Occupied Time Selection screen, there are no occupied time period for that day; the entire day is unoccupied and all outputs with setback values (other than 0) operate at their setback (unoccupied) setpoint value.Note: Occupied and Unoccupied time periods are available at 15-minute intervals only. For example, 12:00 AM, 2:45 PM, 11:15 AM, 19:30 or 23:45 are available time selections depending on the 12 or 24 Hour Clock selection you made when you set up time and day of week. You can press and hold either the or

to scroll quickly forward or back through the time selections.

2. In the Day 1 Occupied Time Selection screen, press or to select the time during Day 1 at which the Occupied time begins (and the previous Unoccupied time ends), then press to save your time of day selection and go to the next screen.

Screen example shows the Day 1 (MON, Monday) Occupied start time is set to 7:45 AM.

Day 1 (MON) Unoccupied Time Selection Screen: Select the time of day to begin the unoccupied time period for Day 1. (The time previous to this unoccupied time value is occupied time.)Note: You can set up one (only) unoccupied time for each day of the week (days 1 through 7). When you select no time (- -:- -) in an Unoccupied Time Selection screen, there are no unoccupied time periods for that day, and the entire day is occupied and all outputs operate at their occupied setpoint value.Note: Occupied and Unoccupied time periods are available at 15-minute intervals only. For example, 12:00 AM, 2:45 PM, 11:15 AM, 19:30, or 23:45 are available time selections depending on the 12 or 24 Hour Clock selection you made when you set up time and day of week. You can press and hold either the

or to scroll quickly forward or back through the time selections.

3. In the Day 1 Unoccupied Time Selection screen, press or to select the time during Day 1 at which the Unoccupied time begins (and the previous Occupied time ends), then press to save your time of day selection and go to the next screen.

Screen example shows the Day 1 (MON, Monday) Unoccupied start time is set to 5:30 PM.

Day 2 (TUE) through Day 6 (SAT) Occupied/Unoccupied Time Selection Screens: Select the time of day to begin the next occupied or unoccupied time period for the remaining days of the week.

4. Repeat Step 2 and Step 3 for each of the remaining days of the week, then press to save your time of day selection and go to the next screen.

Screen example shows the Day 2 (TUE, Tuesday) Occupied start time is set to 7:45 AM.

Day 7 (SUN) Occupied Time Selection Screen: Select the time of day to begin the occupied time period for Day 7 and end the previous occupied time period.

5. In the Day 7 Occupied Time Selection screen, press or to select the time during Day 7 at which the Occupied time begins (and the previous Unoccupied time ends), then press to save your time of day selection and go to the next screen.

Screen example shows the Day 7 (SUN, Sunday) Occupied start time is set to - -:- - (none).

SCHE– – –

7:45OC–1AM

5:30UN–1PM

7:45OC–2AM

- -:- -OC–7AM

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

22

Page 23: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Day 7 (SUN) Unoccupied Time Selection Screen: Select the time of day to begin the unoccupied time period for Day 7 and end the previous occupied time period.

6. In the Day 7 Unoccupied Time Selection screen, press or to select the time during Day 7 at which the Unoccupied time begins (and the previous Occupied time ends), then press to save your time of day selection and go to the next screen.

Screen example shows the Day 7 (SUN, Sunday) Unoccupied start time is set to 12:00 AM, which along with the Day 7 Occupied Start Time of - -:- -, establishes a 24 hour unoccupied time for Day 7 (SUN, Sunday).

Occupied/Unoccupied Schedule Setup Start Screen: The Weekly Occupied/Unoccupied Schedule is now set up in the System 450 UI and you have returned to the Setup Start screen.

7. Press to scroll through the remaining Setup Start screens and continue setting up your control system, or press and simultaneously to return to the System 450 Main screens.

Table 12: System 450 Sensor Setup Information and Procedures (Part 2 of 2)

LCD Screen Name, Description/Function, User Action, and Example

12:00UN–7AM

SCHE– – –

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

23

Page 24: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Figure 9: Menu, Status, and Setup Screens Flowchart Example (See Figure 3.)

OU

T O

UT

Ma

inS

cre

en

s

Sys

tem

Sta

tus

Sc

ree

ns

Se

nso

r S

etu

pS

tart

Scr

een

s

Res

et S

etp

oin

tS

etu

p S

tart

Scr

een

sB

oile

r W

ater

Te

mpe

ratu

re

Rel

ay O

utp

ut

wit

h R

SP

Set

up

Sta

rt S

cre

en

sB

oile

r 1

Res

et -

On/

Off

Rel

ay O

utp

ut

wit

h R

SP

S

etu

p S

tart

Scr

een

sB

oile

r 2

Res

et -

On/

Off

Rel

ay O

utp

ut

wit

h R

SP

S

etu

p S

tart

Scr

een

s B

oile

r 3

Res

et -

On/

Off

Tim

e a

nd

Day

Clo

ck

Se

tup

Sta

rt S

cree

ns

Oc

cup

ied

/Un

occ

up

ied

Sch

edu

le S

etu

pS

tart

Sc

ree

ns

No

te: A

fter

2 m

inu

tes

of in

activ

ity in

any

scr

een

,th

e d

ispl

ay r

etu

rns

to t

he M

ain

scr

een

s.

FF

TU

ER

SP

The

Mai

n sc

ree

ns a

uto

-scr

oll

dur

ing

nor

ma

l ope

ratio

n.

Pre

ss

repe

ate

dly

to s

crol

l thr

ough

all M

ain

and

Sys

tem

Sta

tus

scre

ens.

Press repeatedly to scroll through the System Setup Start screens*

*No

te:

In a

ny S

etup

Sta

rt s

cree

n, P

ress

and

si

mul

tane

ousl

y to

re

turn

to th

e M

ain

scre

ens

.

No

te:

req

uir

ed o

nly

Tim

e an

d D

ay, a

nd

Occ

upie

d/U

nocc

upie

d S

ched

ule

can

be

set

up f

or a

ny c

ontr

olsy

stem

, but

are

fo

r co

ntr

ol s

yste

ms

tha

t use

the

Se

tbac

k (S

bK)

feat

ure.

Pre

ss

to

scr

oll t

hro

ugh

and

se

t up

each

occ

upie

d/u

nocc

upie

d sc

hed

ule

scr

een

.

Pre

ss

a

nd

s

imu

ltane

ousl

y an

d

hol

d 5

seco

nds

to

go

to th

e

Sen

sor

Set

up

S

tart

scr

een.

FIG

:sys

450

_rst

_mnu

_flw

chrt

OF

FT

Sta

nd

ard

Rel

ay

Ou

tpu

t

Se

tup

Sta

rt S

cree

ns

Boi

ler

Circ

ula

tion

Pu

mp

- O

n/O

ff

Aft

er y

ou

ma

ke a

cha

nge

to a

Set

up S

tart

sc

ree

n, p

ress

to s

ave

the

chan

ge.

To r

eset

hou

rs (

HR

S),

h

old

dow

n th

e

k

eyfo

r 5

seco

nds

.

n

OC

-1A

M

- -

- -

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

24

Page 25: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

Technical Specifications

C450RxN-3 System 450 Reset Control Modules

Product C450RxN-3: System 450 Reset Control Module models are sensing controls and operating controls with LCD, four-button touch pad, and On/Off relay output.C450RBN-3: Reset Control Module with one SPDT output relay, one A99BC-25 temperature sensor, and one A99BC-300 temperature sensorC450RCN-3: Reset Control Module with two SPDT output relays, one A99BC-25 temperature sensor, and one A99BC-300 temperature sensor

Supply Power C450-YNN-1 Power Supply Module or 24 (20-30) VAC Safety Extra-Low Voltage (SELV) (Europe) Class 2 (North America) Transformer, 50/60 Hz, 10 VA minimum

Ambient Operating Conditions Temperature: -40 to 66C (-40 to 150F)Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29C (85F)

Ambient Shipping and Storage Conditions

Temperature: -40 to 80C (-40 to 176F)Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29C (85F)

Input Signal 0-5 VDC; 1,035 ohms at 25C (77F) for an A99 PTC Temperature Sensor

Output Relay Contacts General: 1/2 HP at 120/240 VAC, SPDT

Specific: AC Motor Ratings 120 VAC 208/240 VAC AC Full-load Amperes: 9.8 A 4.9 A AC Locked-Rotor Amperes: 58.8 A 29.4 A _____________________________________ 10 Amperes AC Non-inductive at 24/240 VAC Pilot Duty: 125 VA at 24/240 VAC

Clock Accuracy + 4 minutes per year

Clock Backup Power 12 hours (capacitor reserve)

Setback Events one occupied event and one unoccupied event per day; 7 day schedule

Analog Input Accuracy Resolution: 14 bit

Control Construction Independently mounted control, surface mounted with Lexan® 950 enclosure suitable for DIN rail mounting or direct mounting to a hard, even surface.

Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)

Weight C450RBN-3: 209 gm (0.46 lb)C450RCN-3: 222 gm (0.49 lb)

Compliance North America: cULus Listed; UL 60730, File E27734, Vol. 1; FCC Compliant to CFR47, Part 15, Subpart B, Class BIndustry Canada (IC) Compliant to Canadian ICES-003, Class B limits

Europe: CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive; Low Voltage Directive.

Australia and New Zealand: RCM, Australia/NZ Emissions Compliant

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

25

Page 26: System 450 Series Reset Control Modules with Real …cgproducts.johnsoncontrols.com/met_pdf/2476642888.pdfSystem 450™ Series Reset Control Modules with Real-Time Clock and Relay

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult Johnson Controls Application Engineering at (414) 524-5535. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

United States Emissions Compliance

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

- Reorient or relocate the receiving antenna.

- Increase the separation between the equipment and receiver.

- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

- Consult the dealer or an experienced radio/TV technician for help.

Canadian Emissions Compliance

This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:

JOHNSON CONTROLSWESTENDHOF 345143 ESSENGERMANY

JOHNSON CONTROLS507 E MICHIGAN STMILWAUKEE WI 53202USA

JOHNSON CONTROLSC/O CONTROLS PRODUCT MANAGEMENTNO. 22 BLOCK D NEW DISTRICTWUXI JIANGSU PROVINCE 214142CHINA

Published in U.S.A. www.johnsoncontrols.com

System 450™ Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

26

® Johnson Controls and PENN are registered trademarks of Johnson Controls, Inc. in theUnited States of America and/or other countries. All other trademarks used herein are the property

of their respective owners. © Copyright 2016 by Johnson Controls, Inc. All rights reserved.