System ManualVersion 5.40
01 / 2002
Copyright © 2002 by EPLAN Software & Service GmbH & Co. KG
EPLAN Software & Service GmbH & Co. KG assumes no liability for either techni-cal or printing errors or for deficiencies in this technical information and cannot beheld liable for damages that may directly or indirectly result from delivery, perform-ance, and use of this material.
This technical information includes information on the basis of a proprietary systemthat is protected by copyright laws. All rights reserved. These information or partthereof may not be copied or reproduced by any other means without the previouspermission of EPLAN Software & Service.
The software described in these technical information is subject to a licensingagreement. The software may only be used and copied within the scope of thisagreement.
EPLAN is a registered trademark of EPLAN Software & Service GmbH & Co. KG.
MS-DOS / Windows / Windows NT are registered trademarks of the MicrosoftCorporation.
SCAN is a registered trademark of McAfee Associates.
TNTVIRUS is a registered trademark of CARMEL Software Engineering.
PKZIP/PKUNZIP are registered trademarks of PKWARE, Inc.
ObjectStore is a registered trademark of Object Design, Inc.
C-ISAM is a registered trademark of Informix Software Inc.
Hardlock E-Y-E is a registered trademark of FAST Electronic GmbH.
InstallShield is a registered trademark of InstallShield, Inc.
PMS is a registered trademark of PMS Compelec GmbH.
AutoCAD is a registered trademark of Autodesk, Inc.
INTERGRAPH is a registered trademark of Intergraph, Inc.
MicroStation is a registered trademark of Bentley Systems.
Note: The hardware requirements indicated by the operating system manufac-turers must be considered. Hardware combinations that cause malfunctions ac-cording to the manufacturer’s specification may also have an effect on the opera-tion of EPLAN. Therefore an accurate basic installation of hardware, operatingsystem, and hardware drivers (e.g. graphics board driver etc.) is essential for asmooth operation of EPLAN. For this reason, the main conditions and areas ofapplication as specified by the hardware manufacturers also apply to the opera-tion of EPLAN.
Table of Contents
1
Table of contents
1 Description of the Messages ..............................................................11
1.1 Generate Table of Contents ..........................................................................121.1.1 F2201 Page doesn’t exist in project.............................................................12
1.2 Generate Bill of Materials.............................................................................131.2.1 F3004 Error opening bill-of-materials file(s) ..............................................131.2.2 F3007 Error creating terminal-strip text database .......................................131.2.3 F3008 Error opening schematic database....................................................141.2.4 F3009 Error reading project header data.....................................................141.2.5 F3013 Schematic page saving failed...........................................................15
1.3 Load Bill of Materials ...................................................................................151.3.1 F3101 Error writing to the schematic..........................................................161.3.2 H3103 Entry written to the file of differences.............................................161.3.3 F3104 Error reading schematic...................................................................161.3.4 H3105 Component not found in component database .................................16
1.4 Contact Cross-reference Run .......................................................................171.4.1 F4001, F4201 Component without designation...........................................181.4.2 F4002 Wrong symbol type .........................................................................181.4.3 F4003, F4023 Too many contacts/subelements...........................................181.4.4 F4004 Coil already exists ...........................................................................201.4.5 F4005, H4015 Duplicate connection designation........................................201.4.6 F4006 Counter cross-reference to main element already exists ...................211.4.7 W4007, W4207, W5018, W5518 Higher-level assignment does not exist...221.4.8 W4008, W4208, W5019, W5519, W5819 Location designation does not
exist ...........................................................................................................221.4.9 W4009, W4409 Mounting location does not exist ......................................221.4.10 F4010 Duplicate component designation or wrong type .............................231.4.11 W4013 Component without connection designation...................................231.4.12 W4014 Unnumbered DD............................................................................231.4.13 F4022 Change-over contact display incomplete..........................................241.4.14 W4024 Coil with no contact.......................................................................241.4.15 W4025 Contact with no coil.......................................................................241.4.16 H4026 No counter-cross-reference to auxiliary element .............................251.4.17 W4027 No counter cross-reference to main element...................................251.4.18 W4028 No motor-overload-switch main element .......................................25
1.5 Potential Cross-reference Run......................................................................261.5.1 F4202, F4411 Potential arrow without designation.....................................261.5.2 F4203, F4402, F5021 Ring closure/search depth exceeded .........................271.5.3 F4204, F4403, F5022, F5069 Too many targets .........................................271.5.4 F4206, F4225 Incorrect arrowheads ...........................................................27
System Manual EPLAN 5.40
2
1.5.5 W4209 Potential arrow without designation ...............................................281.5.6 F4226 Incomplete pairs..............................................................................281.5.7 W4227 Connection on one page.................................................................29
1.6 Wiring List ....................................................................................................291.6.1 F4404 Wiring point without definition .......................................................301.6.2 F4412 Potential arrow not found ................................................................311.6.3 F4421 Wiring designation too long ............................................................31
1.7 Wire Numbering............................................................................................321.7.1 W4601 The designation doesn’t lie on a connection....................................321.7.2 W4602 The designation lies on two connections (nodes)............................321.7.3 W4603 The designation does not contain a variable ...................................321.7.4 W4604 The following variable is not entered .............................................321.7.5 W4605 The following variable is incremented too high..............................331.7.6 F4610 Connection designation without symbol ..........................................331.7.7 F4611 Incorrect target wiring .....................................................................33
1.8 PLC Cross-references ...................................................................................331.8.1 F4701 Duplicate PLC device-end terminal designation ..............................341.8.2 F4702 Error while accessing the PLC cross-reference database ..................341.8.3 F4703 PLC device-end terminal without designation..................................351.8.4 F4704 There is no counterpart for the PLC end terminal in the overview....35
1.9 Edit PLC data................................................................................................351.9.1 H4801 Modified type of connection ...........................................................361.9.2 H4802 Modified symbolic address .............................................................361.9.3 H4803 Modified function text ....................................................................361.9.4 H4804 New PLC terminal ..........................................................................36
1.10 PLC Assignment List ....................................................................................361.10.1 F4901 Address has been assigned several times .........................................361.10.2 F4902 Symbolic address has been assigned several times...........................37
1.11 Generate Terminals.......................................................................................371.11.1 F5001, F5501 Terminal with no designation...............................................391.11.2 F5002, H5004, F5502 DD cannot be taken from the left.............................391.11.3 F5003, F5503 DD cannot be taken from above...........................................401.11.4 W4205, W5007, W5505 Sorting cannot be used.........................................401.11.5 F5008 Workstation and strip designation too long ......................................401.11.6 F5009 Terminal number and terminal subnumber too long.........................401.11.7 F5011, F5511, F5811 Incorrect workstation designation ............................401.11.8 F5012, F5512, F5812 Incorrect strip designation........................................411.11.9 F5013, F5513, F5813 Incorrect terminal number........................................421.11.10 F5015, F5515, F5815 Incorrect terminal subnumber .............................431.11.11 W5016, W5516, W5816 Incorrect designation (only DIN)....................441.11.12 F5017, F5517, F5817 Incorrect strip subnumber ...................................451.11.13 F5020, F5050 Duplicate terminal (page) ...............................................451.11.14 F5023 Target with incomplete DD ........................................................45
Table of Contents
3
1.11.15 F5024, F5057 Terminal subdivision too short for target ........................461.11.16 F5025, H5026 Duplicate strip designation (page) ..................................461.11.17 W5027 Connection designation too long ...............................................461.11.18 F5031, F5531 Arrow without designation .............................................461.11.19 F5032, F5532 Arrow not found .............................................................461.11.20 W5051 Wrong symbol type for terminal strip........................................471.11.21 W5052 Wrong symbol type for connector strip .....................................471.11.22 H5053 Strip not predefined ...................................................................471.11.23 H5054 Strip without terminals/connectors.............................................481.11.24 F5055 Connector file does not exist ......................................................481.11.25 F5056 Pin designation not contained in the connector file, but
expected................................................................................................481.11.26 W5058 Terminal number exceeds spare ................................................481.11.27 F5061 Incorrect jumper bar formation...................................................491.11.28 F5065 Dual entry in form field..............................................................491.11.29 F5071 Incorrect wire jumper formation.................................................491.11.30 F5072 Too many wire jumper levels .....................................................511.11.31 H5075 Form field shifted ......................................................................51
1.12 Generate Cable..............................................................................................511.12.1 F5201 Oblique cable line ...........................................................................531.12.2 F5202 Conductor designation without two targets ......................................541.12.3 F5203 Cable target with incomplete DD.....................................................551.12.4 F5204 Duplicate cable/conductor definition in path....................................561.12.5 F5205 Incorrect marking of cable conductor/shielding ...............................581.12.6 F5208 Cable between same strip ................................................................591.12.7 F5209 Missing cable designation to ...........................................................601.12.8 F5211 Incorrect cable designation..............................................................611.12.9 F5212 Invalid cable designation.................................................................611.12.10 F5215 Cable definition not between components ..................................621.12.11 H5218 Conductor color without cable line ............................................631.12.12 W5220 Part number not at first cable line..............................................631.12.13 F5221 Differing cable data....................................................................631.12.14 F5222, F5246 Cable designation too long .............................................641.12.15 F5223 Cable type does not exist ............................................................641.12.16 F5225, F5233, F5260, F5281, F6303 Number of conductors not
defined..................................................................................................651.12.17 F5231, F5237 No cable (type) defined for conductor ............................661.12.18 F5232 Number of conductors missing in the cable definition ................681.12.19 F5235 Color assigned twice ..................................................................681.12.20 F5236 Color not defined .......................................................................681.12.21 F5239, F5267, F5283 Too many conductors .........................................701.12.22 F5241 Cable definition not at the terminal.............................................711.12.23 W5243, W5285 One-sided cable definition ...........................................711.12.24 F5244, F5509 Counter target not found.................................................741.12.25 W5245 Cable not defined to..................................................................741.12.26 F5261 No PE conductor allowed for type..............................................741.12.27 F5262 Two/several PE conductors intersected.......................................75
System Manual EPLAN 5.40
4
1.12.28 F5263 No N conductor allowed for type................................................751.12.29 F5264 Two/several N conductors intersected ........................................751.12.30 F5265 No shielding allowed for type.....................................................761.12.31 F5266 Two/several shielding conductors intersected .............................761.12.32 H5268 Subcable generated....................................................................771.12.33 F5269 Too many subcables ...................................................................771.12.34 F5282 Cable without conductor ............................................................771.12.35 F5284 Invalid color assignment ............................................................78
1.13 Import Cable Data ........................................................................................78
1.14 Create Terminal Bill of Materials.................................................................791.14.1 F5701 No matching terminal marked .........................................................791.14.2 F5702 Accessories missing: .......................................................................791.14.3 F5703 Terminal / strip definition not found ................................................79
1.15 Import Terminal Bill of Materials................................................................791.15.1 F5801 Terminal not found in the terminal bill of materials .........................801.15.2 F5802 Strip header does not exist...............................................................80
1.16 Graphics Terminal-strip Overview ..............................................................801.16.1 H6001, H6101, H6201, H6301, H6601, H6701, H6801 Function text
truncated ....................................................................................................80
1.17 Graphics Cable Overview .............................................................................811.17.1 F6102, F6202 Cable file does not exist.......................................................81
1.18 Graphics Terminals.......................................................................................811.18.1 F6203 Terminal strip not found..................................................................811.18.2 F6205 Graphics page not output.................................................................81
1.19 Graphics Cables ............................................................................................821.19.1 W6306 Target not found ............................................................................821.19.2 F6307 Target 2 not found...........................................................................82
1.20 Graphics Terminal Connection ....................................................................821.20.1 W6401 Symbol macro not found................................................................821.20.2 W6402 Symbol not found in the schematic ................................................831.20.3 F6403 Differing macro connections ...........................................................831.20.4 F6404 Differing symbol numbers...............................................................83
1.21 Graphics Bill of Materials.............................................................................831.21.1 H6602, H6702, H6802 Designation truncated ............................................83
1.22 Graphics Device List .....................................................................................831.22.1 H6703 Symbol not within limits.................................................................84
1.23 Graphics Purchase-order List ......................................................................84
Table of Contents
5
1.24 Translation ....................................................................................................841.24.1 F7001 No source language found ...............................................................841.24.2 F7002 DRAW command error ...................................................................841.24.3 F7003 Data structure error (ESC)...............................................................841.24.4 W7011 Search term missing.......................................................................851.24.5 W7012 Target term missing .......................................................................85
1.25 HPGL Import ................................................................................................851.25.1 F7201 Lower X limit exceeded ..................................................................851.25.2 F7202 Upper X limit exceeded...................................................................851.25.3 F7203 Lower Y limit exceeded ..................................................................861.25.4 F7204 Upper Y limit exceeded...................................................................861.25.5 W7205 Unknown HPGL command............................................................861.25.6 F7206 Invalid numerical value ...................................................................87
1.26 Import Parts ..................................................................................................871.26.1 F7401 Part defined several times................................................................871.26.2 W7403 Importing of parts being aborted (number of errors > 50)..............88
2 Creating Print Forms ........................................................................89
2.1 The Report Processor....................................................................................892.1.1 Structure of Print Forms .............................................................................90
2.2 Overview of the Functions Valid for all Forms............................................922.2.1 Message Overview.....................................................................................96
2.3 The Field Codes of the Individual Programs (F Codes) .............................972.3.1 Cross-references, Wiring Lists, and Connection Bills of Materials ...........1002.3.2 Contactor Selection and Contactor Specification ......................................1022.3.3 Terminal and Interconnect Diagram .........................................................1032.3.4 Terminal Bill of Materials ........................................................................1082.3.5 Foreign-language Translation...................................................................1112.3.6 Message management ..............................................................................1112.3.7 Documentation Management EDOC ........................................................1132.3.8 Outputting Lists (Parts Management) .......................................................118
2.3.8.1 Outputting Lists (Parts Management): Project information ........................................1192.3.8.2 Outputting Lists (Parts Management): Schematic data ..............................................1202.3.8.3 Outputting Lists (Parts Management): Master data....................................................1212.3.8.4 Outputting Lists (Parts Management): Special codes .................................................1252.3.8.5 Outputting Lists (Parts Management): F codes for output settings .............................126
2.3.9 Standard Labeling ....................................................................................1262.3.9.1 Standard labeling: Devices .......................................................................................1272.3.9.2 Standard labeling: Terminals ....................................................................................1272.3.9.3 Standard labeling: Terminal strips ............................................................................1272.3.9.4 Standard labeling: PLC ............................................................................................1282.3.9.5 Standard labeling: Cables .........................................................................................1282.3.9.6 Standard labeling: Conductors..................................................................................1282.3.9.7 Standard labeling: Wirings .......................................................................................129
System Manual EPLAN 5.40
6
2.3.10 Phoenix Mark Labeling............................................................................1302.3.10.1 Phoenix Mark labeling: Devices............................................................................1302.3.10.2 Phoenix Mark labeling: Terminals ........................................................................1302.3.10.3 Phoenix Mark labeling: PLC.................................................................................1312.3.10.4 Phoenix Mark labeling: Cables .............................................................................1312.3.10.5 Phoenix Mark labeling: Conductors ......................................................................131
3 Import / Export Identifiers (Parts Management) ..........................133
4 Special Settings ................................................................................140
4.1 Editing the EPLAN Initialization File ........................................................1404.1.1 Format of the EPLFONT.INI File ............................................................141
4.2 EPLAN Call-up Parameters .......................................................................1414.2.1 Main Module (EPL6000.EXE).................................................................1434.2.2 Call-up Parameters for the Graphics Editing Module................................1444.2.3 Call-up Parameters for the Contact/Potential Cross-references Module ....1484.2.4 Call-up Parameters for the Contactor Selection Module ...........................1494.2.5 Call-up Parameter for the External Programs Module...............................1494.2.6 Call-up Parameters for the Data Backup Module......................................1504.2.7 Call-up Parameter for the Generate Table of Contents Module .................1514.2.8 Call-up Parameter for the Wire Numbering Module .................................1514.2.9 Call-up Parameter for the Reorganize Page Database Module ..................1514.2.10 Call-up Parameters for the EXF->EPLAN Data Exchange Module ..........1524.2.11 Call-up Parameters for the EPLAN->EXF Data Exchange Module ..........1544.2.12 Call-up Parameters for the Compress Project Module...............................1564.2.13 Call-up Parameters for the DXF->EPLAN Data Exchange Module ..........1564.2.14 Call-up Parameters for the Automatic Revision Module ...........................1564.2.15 Call-up Parameters for the PLC Cross-reference Generation ....................1584.2.16 Call-up Parameters for the Message Management Module .......................1584.2.17 Call-up Parameters for the Realize Bill of Materials Module ....................1594.2.18 Call-up Parameters for the Automatic Evaluation Module ........................1594.2.19 Call-up Parameters for the Parameter Management Module .....................1604.2.20 Call-up Parameters for the Parts Management Module .............................1604.2.21 Call-up Parameters for the "PHOENIX Mark" Labeling Module..............1644.2.22 Call-up Parameters for the Lists Output Module.......................................1654.2.23 Information on Notation...........................................................................172
5 Lists and Tables ...............................................................................173
5.1 Symbol Type: Contacts and Coils...............................................................173
5.2 Symbol Type: Terminals and Accessories..................................................174
5.3 Identifying Letters.......................................................................................1765.3.1 Identifiers for Identifying the Device Type...............................................1775.3.2 Identifiers for Identifying the Function of a Device Type .........................178
Table of Contents
7
5.4 Special Texts................................................................................................1795.4.1 Special Texts 0 – 99.................................................................................1805.4.2 Special Texts 100 - 199............................................................................1805.4.3 Special Texts 200 - 299............................................................................1815.4.4 Special Texts 300 - 399............................................................................1835.4.5 Special Texts 400 - 499............................................................................1845.4.6 Special Texts 500 – 599 ...........................................................................1875.4.7 Special Texts 600 – 699 ...........................................................................1895.4.8 Special Texts 700 - 799............................................................................1915.4.9 Special Texts 800 - 899............................................................................1915.4.10 Special Texts 900 - 999............................................................................1925.4.11 Special Texts 1000 - 1099........................................................................1935.4.12 Special Texts 1100 - 1199........................................................................193
6 Graphics Editing Menu...................................................................195
6.1 Page..............................................................................................................1956.1.1 New .........................................................................................................1956.1.2 Open ........................................................................................................1956.1.3 Save .........................................................................................................1966.1.4 Copy (Page) .............................................................................................1966.1.5 Rename/Move..........................................................................................1966.1.6 Read in backup page ................................................................................1966.1.7 Delete (Page) ...........................................................................................1966.1.8 Previous / Next ........................................................................................1966.1.9 Properties (Page)......................................................................................1976.1.10 Print .........................................................................................................1976.1.11 HPGL plot ...............................................................................................1976.1.12 Export ......................................................................................................197
6.1.12.1 EXF .....................................................................................................................1976.1.12.2 DXF.....................................................................................................................1986.1.12.3 HTML/DWF ........................................................................................................1986.1.12.4 Inter@View..........................................................................................................1986.1.12.5 EXF macro...........................................................................................................1986.1.12.6 Image file.............................................................................................................198
6.1.13 External programs....................................................................................1996.1.14 Number supplementary fields...................................................................1996.1.15 Close........................................................................................................199
6.2 Draw ............................................................................................................1996.2.1 Insert symbols..........................................................................................2006.2.2 Symbol macros ........................................................................................2006.2.3 Insert macros............................................................................................2006.2.4 Black box.................................................................................................2016.2.5 Device-end terminals................................................................................2016.2.6 PLC end terminal .....................................................................................2016.2.7 Potential arrows .......................................................................................2026.2.8 Cable definition........................................................................................2026.2.9 Shieldings ................................................................................................203
System Manual EPLAN 5.40
8
6.2.10 Wiring definition......................................................................................2036.2.11 DIN box...................................................................................................2036.2.12 Text .........................................................................................................204
6.3 Attachment ..................................................................................................2046.3.1 Angle .......................................................................................................2056.3.2 Node ........................................................................................................2056.3.3 Jumper .....................................................................................................2056.3.4 Double junction........................................................................................2056.3.5 Interrupt ...................................................................................................2066.3.6 Specify line data.......................................................................................206
6.3.6.1 Individual ................................................................................................................2066.3.6.2 Potentials .................................................................................................................2076.3.6.3 Comparison .............................................................................................................207
6.4 Edit ..............................................................................................................2076.4.1 Cancel......................................................................................................2086.4.2 Undo / Redo.............................................................................................2086.4.3 Cut (Clipboard) ........................................................................................2086.4.4 Copy (Clipboard) .....................................................................................2086.4.5 Paste (Clipboard) .....................................................................................2096.4.6 Delete (Graphics Object)..........................................................................2096.4.7 Move .......................................................................................................2096.4.8 Duplicate .................................................................................................2106.4.9 Create macro/form ...................................................................................210
6.4.9.1 Symbol macro..........................................................................................................2106.4.9.2 Path/PLC macro.......................................................................................................2116.4.9.3 Variable macro.........................................................................................................2116.4.9.4 Combined macro......................................................................................................2126.4.9.5 Window macro.........................................................................................................2126.4.9.6 Page macro ..............................................................................................................2126.4.9.7 Plot frame ................................................................................................................2126.4.9.8 Form........................................................................................................................213
6.4.10 Window ...................................................................................................2136.4.11 Change window corner ............................................................................2136.4.12 Properties (Graphics Object) ....................................................................2146.4.13 Part number..............................................................................................2146.4.14 Messages..................................................................................................2146.4.15 Increment.................................................................................................2146.4.16 Position....................................................................................................2156.4.17 Move DD.................................................................................................2156.4.18 PLC connection at terminal ......................................................................2156.4.19 Panel layout .............................................................................................215
6.5 Search ..........................................................................................................2166.5.1.1 Selection ..................................................................................................................2166.5.1.2 Insert into search database ........................................................................................2166.5.1.3 Next entry / Previous entry .......................................................................................2166.5.1.4 Jump to counterpiece................................................................................................217
6.5.2 Parts at components .................................................................................217
Table of Contents
9
6.6 Options ........................................................................................................2176.6.1 Multifunction menu..................................................................................217
6.6.1.1 Connection directions...............................................................................................2186.6.1.2 Point and/or target wiring .........................................................................................2186.6.1.3 Only target wiring ....................................................................................................2186.6.1.4 Cable display ...........................................................................................................2186.6.1.5 Plot invisible elements..............................................................................................2196.6.1.6 One arrow per page ..................................................................................................2196.6.1.7 Crosshair cursor .......................................................................................................2196.6.1.8 External targets ........................................................................................................2206.6.1.9 Mouse increment......................................................................................................2206.6.1.10 Replace [CTRL]+[INS] by [INS] ..........................................................................2206.6.1.11 Save cursor position .............................................................................................220
6.6.2 Insertion points ........................................................................................2206.6.3 Grid .........................................................................................................2216.6.4 Symbol extension.....................................................................................2216.6.5 Page offset ...............................................................................................2216.6.6 Alternative text display ............................................................................2216.6.7 Display properties ....................................................................................2216.6.8 Alternative operation................................................................................2226.6.9 Display message window .........................................................................222
6.7 Free graphics ...............................................................................................2226.7.1 Multiple editing........................................................................................2236.7.2 Polyline / Line..........................................................................................2236.7.3 Circle .......................................................................................................2236.7.4 Arc...........................................................................................................2246.7.5 Rectangle .................................................................................................2246.7.6 Ellipse......................................................................................................2246.7.7 Free graphics text.....................................................................................2256.7.8 Rotate ......................................................................................................2256.7.9 Move all...................................................................................................2256.7.10 Combine ..................................................................................................2256.7.11 Increase / Decrease...................................................................................2266.7.12 Element data ............................................................................................2266.7.13 Dimensioning start / Dimensioning end....................................................2266.7.14 Insert image files......................................................................................2266.7.15 Edit image file..........................................................................................227
6.8 Symbol .........................................................................................................2276.8.1 Save / Cancel ...........................................................................................2276.8.2 New .........................................................................................................2276.8.3 Angle variant ...........................................................................................2286.8.4 Revise ......................................................................................................2286.8.5 Import ......................................................................................................2286.8.6 Import basic symbols ...............................................................................2286.8.7 Export ......................................................................................................2296.8.8 Symbol data .............................................................................................2296.8.9 Describing block ......................................................................................2296.8.10 Identifying Block .....................................................................................230
System Manual EPLAN 5.40
10
6.8.11 Relative insertion point ............................................................................2306.8.12 Connecting point......................................................................................230
6.9 Parameters...................................................................................................2306.9.1 Project .....................................................................................................2316.9.2 Personal ...................................................................................................2316.9.3 Workstation .............................................................................................232
6.10 Window........................................................................................................2326.10.1 Cascade....................................................................................................2326.10.2 Tile horizontally.......................................................................................2326.10.3 Tile vertically...........................................................................................2336.10.4 Arrange icons...........................................................................................233
6.11 View .............................................................................................................2336.11.1 Toolbars...................................................................................................2336.11.2 Refresh screen..........................................................................................2336.11.3 Page format..............................................................................................2336.11.4 Change standards .....................................................................................2346.11.5 Attachment preview .................................................................................2346.11.6 Display scroll bars....................................................................................2346.11.7 Open zoom / Open zoom 80%..................................................................2346.11.8 Close zoom..............................................................................................2346.11.9 Set view to starting zoom.........................................................................2356.11.10 Increase quadrant zoom / Decrease quadrant zoom..............................2356.11.11 Save zoom levels ................................................................................2356.11.12 Activate zoom levels...........................................................................235
6.12 Help..............................................................................................................2356.12.1 Module help / Contents and index ............................................................2366.12.2 About.......................................................................................................236
7 Key commands.................................................................................237
8 Index.................................................................................................243
Description of the Messages
11
1 Description of the Messages
EPLAN differentiates between three different types of messages:
• Errors
• Warnings• Notes.
These message types are abbreviated as follows:
F For errors (displayed in red when generated)W For warnings (displayed in blue when generated)H For notes (displayed in green when generated)
All the messages have a message number, for example, "F4226". A message is thusmade up of the character for the message type and the message number.
The messages are divided into message groups and are assigned to certain generationruns.
The following table shows this assignment:
Message group Generation run
2200 Generate table of contents
3000 Create bill of materials
3100 Read in bill of materials
4000 Contact cross-reference run
4200 Potential cross-reference run
4400 Wiring list
4600 Wire numbering
4700 PLC cross-references
5000 Generate terminals
5200 Generate cables
5500 Write cable data back
5700 Create terminal bill of materials
5800 Write terminal bill of materials back
System Manual EPLAN 5.40
12
6000 Graphics terminal overview
6100 Graphics cable overview
6200 Graphics terminals
6300 Graphics cables
6400 Graphics terminal connection
6600 Graphics bill of materials
6700 Graphics device list
6800 Graphics terminal bill of materials
7000 Foreign-language translation
7200 HPGL import
7400 Import parts
The help text on a specific message can be accessed via the message window in theMessage management module and in the Graphics output module (for more informationplease refer to the module help or the User Guide).
1.1 Generate Table of Contents
2201 F Page doesn’t exist in project
1.1.1 F2201 Page doesn’t exist in project
When writing back data from the table of contents a page number was found that doesnot exist in the project any more (page was deleted).
Suggested remedy:
Regenerate the table of contents.
Description of the Messages
13
1.2 Generate Bill of Materials
3004 F Error opening bill-of-materials file(s)
3007 F Error creating terminal-strip text database
3008 F Error opening schematic database
3009 F Error reading project header data
3013 F Schematic page saving failed
1.2.1 F3004 Error opening bill-of-materials file(s)
EPLAN could not open the bill-of-materials file(s) specified in the error message.
Error cause:
The bill of materials file(s) or the directory containing these file(s) is (are) write-protected.
Suggested remedy:
Check the attributes of the file(s) or of the directory. De-activate the write protection forthe file(s) or the directory.
1.2.2 F3007 Error creating terminal-strip text database
EPLAN could not open the file of the terminal-strip text database specified in the errormessage.
Error cause:
Your TMP directory (...\TEMP\TMP), in which this database is only saved temporarily, iswrite-protected.
Suggested remedy:
Check the attributes of the TMP directory. De-activate the write protection for this di-rectory.
System Manual EPLAN 5.40
14
1.2.3 F3008 Error opening schematic database
EPLAN could not open the schematic database.
Possible error causes:
1. The project directory in which the file specified in the error message had been storedwas deleted.
2. The schematic database file specified in the error message or the project directory, inwhich this file was stored, is write-protected.
3. You are working in the network. Somebody accessed the schematic database beforeyou.
4. You are working in the network. You do not possess the corresponding access rightsfor the file.
Suggested remedies:
on 1st Check whether the specified file or the project directory still exist.
on 2nd Check the attributes of the file or of the project directory. De-activate the writeprotection for the file or for the project directory.
on 3rd Wait until you can re-access the schematic database or contact the user who isediting the schematic database.
on 4th Contact your system administrator and ask him for the corresponding accessrights for the schematic database.
1.2.4 F3009 Error reading project header data
EPLAN could not read the project header.
Possible error causes:
1. The project was filed off for external editing.
2. The project was compressed.
3. An error occurred in the project.
Suggested remedies:
on 1st Select Project in the main menu and then the Select, create, copy projects menuitem to call up the Project selection module. Check whether the project file ismarked by the graphics symbol (bmc treepras.bmp) in the project selection win-dow (tree view). If this is the case, first organize the storage media to which theproject was filed off.
If you want to know to which storage media the project was filed off, pleaserefer to the Backup tab (right-hand side). The Customer and Delivery input
Description of the Messages
15
fields in the Project is filed off at group box (right below) may – if entered - pro-vide information where the filed-off project is stored.
If the filed-off project is located on storage media (e.g. diskettes) return to themain menu. You can retrieve the filed-off project by following the menu pathUtilities / Backup / Reload / Projects.
on 2nd Select Project in the main menu and then the Select, create, copy projects menuitem to call up the Project selection dialog box. Check whether the project file ismarked by the graphic symbol (bmc treeprop.bmp) in the project selection win-dow (tree view). The project properties display (above right in the dialog) alsoprovides information on whether the project is compressed or not. A compressedproject is marked by the word "compressed" that is to be found behind the proj-ect name.
If the project is compressed return to the main menu. You can decompress theproject by using the Utilities / Backup / Reload / Decompress menu path.
on 3rd Contact EPLAN Software & Service. We will try to repair your project.
1.2.5 F3013 Schematic page saving failed
The system IDs (internal codes for the components in the schematic) cannot be writtenback.
Error cause:
You are working in the network. Somebody accessed the schematic page before you andis editing it.
Suggested remedy:
Wait until you can re-access the schematic page or contact the user who is editing theschematic page.
1.3 Load Bill of Materials
3101 F Error writing to the schematic
3103 H Entry written to the file of differences
3104 F Error reading schematic
3105 H Component not found in component database
System Manual EPLAN 5.40
16
1.3.1 F3101 Error writing to the schematic
EPLAN cannot write component data to the schematic.
Error cause:
You are working in the network. Somebody accessed the schematic page before you andis editing it.
Suggested remedy:
Wait until you can re-access the schematic page or contact the user who is editing theschematic page.
1.3.2 H3103 Entry written to the file of differences
Component entries that EPLAN could not insert or find in the component database arewritten to a so-called file of differences. You can view the contents of this file byopening the STKLDIFF.ASC file in the current project directory.
1.3.3 F3104 Error reading schematic
EPLAN cannot read component data from the schematic.
Possible error cause:
You are working in the network. Somebody accessed the schematic page before you andis editing it.
Suggested remedy:
Wait until you can reaccess the schematic page or contact the person who is editing theschematic page.
1.3.4 H3105 Component not found in component database
EPLAN could not find the component in the component database. Therefore the datawas not written back to the schematic.
Open the STKLEPX.ASC file in the current project directory and delete all componentsthat EPLAN could not find. Save the file and reload the bill of materials.
Description of the Messages
17
1.4 Contact Cross-reference Run
4001 F Component without designation
4002 F Incorrect symbol type
4003 F Too many contacts/subelements
4004 F Coil already exists
4005 F Duplicate connection designation
4006 F Reverse cross-reference to main element already exists
4007 W Higher-level assignment does not exist
4008 W Location designation does not exist
4009 W Mounting location does not exist
4010 F Duplicate component designation or incorrect type
4013 W Component without connection designation
4014 W Unnumbered DD
4015 H Duplicate connection designation
4022 F Change-over contact display incomplete
4023 F Too many contacts/subelements
4024 W Coil with no contact
4025 W Contact with no coil
4026 H No counter cross-reference to auxiliary element
4027 W No counter cross-reference to main element
4028 W No motor-overload-switch main element
System Manual EPLAN 5.40
18
1.4.1 F4001, F4201 Component without designation
Error cause:
EPLAN found a cross-referenceable symbol (component) without device tag.
Suggested remedies:
1. Use the page, row area and position information to find the symbol in the error list orin the schematic. Once you have found the symbol click on it. Afterwards add themissing device tag to the Symbol properties dialog. Save the schematic page(s) andstart running a new contact cross-reference
2. Eliminate the error by using the correction function. You will find it by selecting themenu path Generate / Cross-references/wiring list / Generate / Correction function(start from the main menu).
Activate the check box "4001 Components without DD: Set to symbol type 254",and confirm by clicking [OK]. EPLAN then changes the symbols into graphical ele-ments that are not considered at the cross-reference run.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.4.2 F4002 Wrong symbol type
Error cause:
You assigned the same device designation to several components with different cross-reference types. Example: There are two contactor coils with the same DD in yourschematic. One contactor coil is given the cross-reference type "50" (cross-referenceable), the other one "255" (standard symbol, not cross-referenceable).
Suggested remedy:
Check the device designations of the respective components and assign unique devicedesignations to the components.
1.4.3 F4003, F4023 Too many contacts/subelements
Error causes:
1. You inserted a contactor in the schematic provided with more contacts than specifiedin the parameter program. According to the parameter program you can assign atleast 4 and not more than 80 contacts to a contactor. The default setting is "12".
Description of the Messages
19
2. More subelements of a black box (black box with identical device designation) wereinserted in the schematic than specified in the parameter program.
In this case, too, at least 4 and not more than 80 black-box subelements can be placedin the schematic. The default setting is also "12".
The error message concerning to many black-box subelements is only dis-played if the "Include black box in the cross-reference" check box (Cross-references tab) was activated in the parameter program for contactor set-tings and cross-references.
Suggested remedies:
on 1st Call up the parameter program for contactor settings and cross-references byusing the menu path Utilities / Parameters / Project / Contactor/cross-reference/wiring (start from the main menu).
Afterwards click on the Cross-references/wirings tab.
Change the value in the Maximum number of contactor contacts input field sothat it corresponds to the maximum number of contacts of the inserted contactor(or exceeds this number of contacts), and restart the cross-reference run.
or
Eliminate the error by using the correction function. You will find it by selectingthe menu path Generate / Cross-references/wiring list / Generate / Correctionfunction (start from the main menu).
Activate the check box "4003 Too many subelements: Change components withspecific DD to symbol type 254", and confirm by clicking [OK]. EPLAN thenchanges the symbols into graphical elements that are not considered during thecross-reference run.
on 2nd Call up the parameter program for contactor settings and cross-references byusing the menu path Utilities / Parameters / Project / Contactor/cross-reference(start at the main menu).
Afterwards click on the Cross-references tab.
Change the value in the Maximum number of contactor contacts input field sothat it corresponds to the number of black boxes (identical DD) inserted in theschematic (or exceeds this number), and restart the cross-reference run.
Further possibility: Deactivate the Include black box in the cross-referencecheck box.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
System Manual EPLAN 5.40
20
1.4.4 F4004 Coil already exists
Error cause:
During the generation run, EPLAN found a coil whose device designation already ex-ists.
Suggested remedies:
1. Change the device designation of the coil in the schematic, save the schematicpage(s) and start running a new contact cross-reference.
2. Eliminate the error by using the correction function. You will find it by selecting themenu path Generate / Cross-references/wiring list / Generate / Correction function(start at the main menu).
Activate the check box "4004 Coil already exists: Renumber DDs" in the dialog boxthat appears, and confirm by clicking [OK]. EPLAN then changes the symbols intographical elements that are not considered at the cross-reference run. Depending onthe structure of the device designation, the counter of the device that exists twice ischanged so that the coil can be clearly identified in the schematic.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.4.5 F4005, H4015 Duplicate connection designation
EPLAN found a connection designation that had already been assigned. In case of the"PE" connection designation this message is output as a note.
Possible error causes:
1. EPLAN found a contactor contact that was inserted twice with an identical DD andan identical connection designation in the schematic. The contact is still included inthe cross-reference database.
2. In the case of a paired cross-reference (motor overload switch), two contacts with thesame device designation and the same symbol type were found.
Suggested remedies:
on 1st Change the connection designations of the respective contact in the schematic orassign another device designation to one of the contacts that exist twice.
on 2nd Call up the correction program by using the menu path Generate / Cross-references/wiring list / Generate / Correction function (start at the main menu).Activate the check box "4005 Duplicate connection designation: Change xx:xxto xx and xx’ ". Then click on [OK]. A supplementary character is added to theconnection designations. Regenerate the contact cross-reference run after that.
Description of the Messages
21
The changed connection designation is now found to be correct and is no longerrejected during the generation run
If the respective symbol is a contactor contact which has been assignedtwice, you can also re-specify the contacts by using the automatic contactorselection function.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.4.6 F4006 Counter cross-reference to main element already exists
Error cause:
You inserted two components with the identical symbol type (Main element of countercross-reference) and the same device designation in the schematic.
Suggested remedies:
1. Delete one of the main elements that exist twice in the schematic,
or
2. give a different device designation to one of the components and assign a auxiliaryelement for counter-cross-reference with the symbol type "153" to it.
or
3. Eliminate the error by using the correction function. You will find it by selecting themenu path Generate / Cross-references/wiring list / Generate / Correction function(start from the main menu).
Activate the check box "4006 Duplicate main element of counter cross reference:Renumber DDs" in the dialog box that appears, and confirm by clicking [OK].EPLAN then renumbers the device with the duplicate main element of counter cross-reference so that a new device designation is created.
Explanation:
A symbol cross-reference can be specified in the Symbol properties dialog while enter-ing a symbol. It is thus possible to cross-reference standard symbols.
It is important that these symbols have different symbol types. One symbol must bedesignated as the main element (identifier 150), and one as the auxiliary element (identi-fier 153). Multiple auxiliary elements are allowed, e.g. pushbuttons or black boxes.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
System Manual EPLAN 5.40
22
1.4.7 W4007, W4207, W5018, W5518Higher-level assignment does not exist
Cause of warning:
A higher-level assignment for a terminal was found that does not occur as a higher-levelassignment for a schematic page. This means that the DD cannot be sorted correctly.The name may furthermore be too long.
Suggestion for avoiding the warning:
Create a page in your project with the corresponding higher-level assignment. Thehigher-level assignment for the terminal is compared to a file containing the higher-level assignments of all schematic pages. If you want to use the higher-level assignmentonly at this terminal, you can delete the page with this higher-level assignment again -the entry is nevertheless retained in the file.
1.4.8 W4008, W4208, W5019, W5519, W5819Location designation does not exist
Cause of warning:
A location designation for a terminal was entered that does not occur as a location des-ignation for a schematic page. This means that the DD cannot be sorted correctly. Thename may furthermore be too long.
Suggestion for avoiding the warning:
Create a page in your project with the corresponding location designation. The locationdesignation for the terminal is compared to a file containing the location designations ofall schematic pages. If you want to use the location designation only for this terminal,you can delete the page with this location designation again - the entry is neverthelessretained in the file.
1.4.9 W4009, W4409 Mounting location does not exist
Cause of warning:
The specified mounting location has not been entered in the corresponding database.
Suggestion for avoiding the warning:
Select the menu path Utilities/Automatic revision/Revise project (starting at the mainmenu). Then call up the Create mounting location database menu item. In this caseEPLAN regenerates the database for mounting locations.
Description of the Messages
23
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.4.10 F4010 Duplicate component designation or wrong type
Error cause:
You are using identical components with the identical device designation twice in theschematic. The symbol type 150 "Main element" was assigned to one of the compo-nents, whereas the symbol type 255 "Standard symbol, not cross-referenceable" is givento the other one.
Suggested remedy:
Change the device designation of one of the two components, and change the symboltype 150 that has been assigned to one of the components to the symbol type 255.
Save the schematic page(s) and generate a new contact cross-reference run.
1.4.11 W4013 Component without connection designation
This warning message only appears in projects with the modified project parameter filePROJEKT.PPD if:
1. You have not assigned connection designations to a NO contact of the symbol type 1
and
2. the hidden parameter for Offset 639 is set to "1" in the PROJEKT.PPD.
1.4.12 W4014 Unnumbered DD
Cause of warning:
EPLAN found a cross-referenceable symbol (component) with a question mark.
Suggestion for avoiding the warning:
Correct the error by using the correction function. You will find it by selecting the menupath Generate / Cross-references/wiring list / Generate / Correction function (start at themain menu).
Activate the 4014 Number unnumbered DD check box in the displayed dialog box, andconfirm by clicking on [OK]. EPLAN automatically numbers the symbols.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
System Manual EPLAN 5.40
24
1.4.13 F4022 Change-over contact display incomplete
Error cause:
A NC contact with an invalid symbol type was used for a change-over contact. Youforgot for instance to change the symbol type of the NC contact symbol from "2" (NCcontact only) to "14" (2-path NC change-over contact).
Suggested remedy:
Call up the automatic correction program by using the menu path Generate / Cross-reference/wiring list / Generate / Correction function (start at the main menu). In thesubsequent Selection for correcting dialog, activate the "4022 Change-over contact dis-play incomplete: Change symbol type 2/15 (NC contact) to 14/15 (change-over con-tact)" and click on [OK]. All NC contacts with an incorrect symbol type are now con-verted into change-over NC contacts.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.4.14 W4024 Coil with no contact
Cause of warning:
EPLAN found a contactor coil without contact during the contact cross-reference run.
Suggestions for avoiding the warning:
1. Insert a contact in the schematic and provide it with the device designation of thecoil.
or
2. delete the contactor coil in the schematic.
1.4.15 W4025 Contact with no coil
Cause of warning:
No coil with the same device designation was found for a contact.
Suggestions for avoiding the warning:
1. Assign the device designation of a coil from the schematic to the contact
or
2. delete the contact.
Description of the Messages
25
This warning can also occur if another component, for example a motoroverload switch, was to be made cross-referenceable for this contact, but nocorresponding entry has been made. In this case the contact pair must alsobe made cross-referenceable.
1.4.16 H4026 No counter-cross-reference to auxiliary element
Each cross-reference includes a main element (symbol type "150") and one or severalauxiliary elements (symbol type "153"). During the contact cross-reference run EPLANfound a main element but no auxiliary element.
Check the symbol type of the device which is to be cross-referenced. By defining thesymbol type you can determine auxiliary and main elements.
After that, save the schematic page(s) and start running a new contact cross-reference!
1.4.17 W4027 No counter cross-reference to main element
Cause of warning:
Each counter cross-reference includes a main element (symbol type "150") and one orseveral auxiliary elements (symbol type "153"). During the contact cross-reference runEPLAN found a auxiliary element but no main element.
Suggestion for avoiding the warning:
Check the symbol type of the devices which are to be cross-referenced. By defining thesymbol type you can determine main and auxiliary elements.
After that, save the schematic page(s) and start running a new contact cross-reference!
1.4.18 W4028 No motor-overload-switch main element
Cause of warning:
EPLAN found a motor overload switch with a auxiliary element (auxiliary contact withthe symbol type "152") during the contact cross-reference run for which no main ele-ment (auxiliary contact with the symbol type "151") exists.
Suggestion for avoiding the warning:
Check whether you inserted the rejected contact as main element with the symbol type"151" or "154" (cross-reference under symbol) in the effective line of the motor over-load switch. If not, insert the contact next to the motor overload switch (on the effectiveline). In case the contact already exists, simply change its symbol type to "151" or to"154". Assign the symbol type "152" (cross-reference next to the symbol) to the auxil-iary element located somewhere in the schematic.
After that, save the schematic page(s) and start running a new contact cross-reference!
System Manual EPLAN 5.40
26
1.5 Potential Cross-reference Run
4201 F Component without designation
4202 F Potential arrow not found/without designation
4203 F Ring closure/search depth exceeded
4204 F Too many targets
4205 W Sorting cannot be used
4206 F Incorrect arrowheads
4207 W Higher-level assignment does not exist
4208 W Location designation does not exist
4209 W Potential arrow without connection
4225 F Incorrect arrowheads
4226 F Incomplete pairs
4227 W Connection on one page
1.5.1 F4202, F4411 Potential arrow without designation
Error cause:
One potential arrow of a potential arrow pair does not have a designation.
Suggested remedy:
• Assign the missing designation to the corresponding potential arrow, save the sche-matic page(s) and start running a new potential cross-reference run.
Description of the Messages
27
1.5.2 F4203, F4402, F5021 Ring closure/search depth exceeded
Target tracking was not successful.
Possible error causes:
1. The target wiring is incorrect, meaning that the target tracking leads back the originalsymbol without encountering another symbol representing a device (ring closure).
2. The maximum number of 19 changes of direction has been reached (search depthexceeded).
Suggested remedies:
on 1st Check whether incorrect target wiring causes target tracking to return to thesame terminal or the same potential arrow.
on 2nd Check to see if no more than 19 insertion points (angles, nodes) lie between thestarting point (terminal, potential arrow) and the target.
1.5.3 F4204, F4403, F5022, F5069 Too many targets
Error cause:
More targets were found than the available number of possible connections. This meansthat the validation key is incorrect. For example this problem occurs when a node isconnected to a potential arrow.
Suggested remedy:
Check the target wiring in the schematic around the specified potential arrow. Even ifnodes are drawn as point wiring in the graphics schematic display, target tracking iscarried out in accordance with the target wiring.
1.5.4 F4206, F4225 Incorrect arrowheads
Error cause:
Two potential arrows where the arrowhead does not connect to the shaft were found.
Suggested remedies:
1. Always draw the potential arrows in pairs in the schematic. One arrow must point"out of the schematic page", while the other one (on a subsequent page) points "intothe schematic" (target arrow).
2. The arrow head check can be suppressed by means of the parameter setting. You canfind the relevant Identifier for potential arrow check parameter on the Cross-references tab in the "Parameters for contactor selection and the cross-reference pro-
System Manual EPLAN 5.40
28
gram" dialog. You can call up this dialog by selecting the menu path Generate /Cross-references/Wiring list / Parameters / Cross-references (starting at the mainmenu). Set the parameter identifier to "0", "1" or "3".
3. Call up the correction program by using the menu path Generate / Cross-reference/wiring list / Generate / Correction function (start at the main menu). Acti-vate the "4225 Incorrect arrowheads: Rotate arrowheads" check box in the subse-quent Correct dialog box. EPLAN now automatically changes the direction of the in-correct potential arrow.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.5.5 W4209 Potential arrow without designation
Cause of warning:
EPLAN found a potential arrow without connection to a device.
Suggestion for avoiding the warning:
Link the potential arrow to a device or to a terminal. Connect the potential arrow thatpoints to the subsequent page with the arrow end to the component. Then connect thepotential arrow (target arrow) on the subsequent page with the arrow head to a compo-nent.
1.5.6 F4226 Incomplete pairs
Error cause:
An odd number of potential arrows with the same designation was used. As a result, onearrow does not have a target.
Suggested remedies:
1. Change the designation of the potential arrow that was inserted last in the schematic,and draw a further potential arrow as target for the renamed potential arrow in theschematic (on another schematic page).
or
2. Call up the correction program by using the menu path Generate / Cross-reference/wiring list / Generate / Correction function (start at the main menu). Acti-vate the "4226 Incomplete pairs: Convert arrow to device-end terminal" check box inthe subsequent Correct dialog box. EPLAN then automatically converts the incorrectpotential arrow to a device-end terminal.
Description of the Messages
29
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.5.7 W4227 Connection on one page
Cause of warning:
There is a connection between two potential arrows on one and the same schematicpage.
This message is only displayed if the Identifier for potential arrow checkparameter is set to the value "3" (arrow pairs and page) or "4" (arrowheadsand page) You will find this parameter on the Cross-references tab in the"Parameters for contactor selection and the cross-reference program" dia-log. You can call up this dialog by selecting the menu path Generate /Cross-references/Wiring list / Parameters / Cross-references (start at themain menu).
Suggestions for avoiding the warning:
1. Insert the target arrow into another schematic page,
or
2. Set the parameter identifier to the value "0", "1", or "2".
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.6 Wiring List
4401 F Terminal with no designation
4402 F Ring closure/search depth exceeded
4403 F Too many targets
4404 F Wiring point without definition
4409 W Mounting location does not exist
4411 F Potential arrow without designation
System Manual EPLAN 5.40
30
4412 F Potential arrow not found
4421 F Wiring designation too long
1.6.1 F4404 Wiring point without definition
EPLAN found a wiring point with no associated definition line during the generation ofthe wiring list.
Cause of error message:
You have moved the insertion point of the wiring point by mistake so that EPLAN can-not assign it to the definition line any more (see example).
Suggested remedy:
1. Open the message window in graphics editing by selecting the menu path Edit / Mes-sages.
2. Use the mouse to highlight the line with the error message, and click [OK]. The cur-sor in the schematic now jumps to the error source.
3. In addition, press the [i] key to have the insertion point indicated.
4. Then position the cursor on the insertion point, and keep the left-hand mouse buttonpressed down. The cursor will then become a circle.
5. Keep the left mouse button pressed down and move the wiring point to the inter-secting point of the definition line and the conductor. Release the mouse button af-terwards. The intersecting points is now marked with a transversal line.
6. Save the schematic page(s) and regenerate the wiring list.
In the left-hand graphic the insertion point of the wiring point has been moved down-wards. EPLAN therefore cannot assign the wiring point to the definition line.
In the right-hand graphic, the insertion point of the wiring point is correctly positionedon the intersecting point of the definition line and the conductor. The intersecting pointsis now marked with a small transversal line.
Description of the Messages
31
1.6.2 F4412 Potential arrow not found
EPLAN did not find a potential arrow of a potential arrow pair during the generation ofthe wiring list.
Possible error causes:
1. The potential arrow was not inserted.
2 The designation of the potential arrow was incorrect.
Suggested remedy:
on 1st Insert the missing potential arrow in the schematic. Make sure that the directionof the potential arrows is correct.
on 2nd Change the designation of the potential arrow. Both potential arrows of a poten-tial arrow pair must have the same designation.
Save the schematic page(s) after having inserted or renamed a potential arrow, and starta new wiring list generation run.
1.6.3 F4421 Wiring designation too long
Error cause:
The cross-reference field assigned for the wiring designation is not large enough. Thewiring designation is therefore incomplete.
Suggested remedies:
1. Select the menu path Utilities / Parameters / Project /. Contactor/cross-reference/wiring (start at the main menu). In the subsequent dialog box click on theCross-references/wirings tab and increase the value in the Field length for wiringdesignations input field (see also help window there).
You can specify a value between 7 and 20 characters in the Field length forwiring designations input field.After you have changed this parameter, EPLAN will ask you to start a newgeneration run.
2. Reduce the length of the wiring designation to the value that you fixed for this pa-rameter.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
System Manual EPLAN 5.40
32
1.7 Wire Numbering
4601 W The designation doesn’t lie on a connection
4602 W The designation lies on two connections (nodes)
4603 W The designation does not contain a variable
4604 W The following variable is not entered
4605 W The following variable is incremented too high
4610 F Connection designation without symbol
4611 F Incorrect target wiring
1.7.1 W4601 The designation doesn’t lie on a connection
A connection designation in the schematic, that is a type "4" special text, is not posi-tioned on the connection between two symbols. Move the connection designation to thedesired connection.
1.7.2 W4602 The designation lies on two connections (nodes)
A wiring text lies on a connection which consists of at least two wires. These are con-nections that pass through a node or a double junction. Shift the wiring text so that it islocated on a branch of the connection representing only one wire.
1.7.3 W4603 The designation does not contain a variable
The Variable identifier parameter is set to "2" or "3", but the wiring text does not con-tain a counting variable. The identifier for the default variable will be assigned to thewiring text.
1.7.4 W4604 The following variable is not entered
A wiring text contains a counting variable which is not defined.
Either change the wiring text in the schematic or define a new counting variable withthis letter.
Description of the Messages
33
1.7.5 W4605 The following variable is incremented too high
The end value of this counting variable was exceeded during numbering.
Either change the end value or select a different variable in the wiring text.
1.7.6 F4610 Connection designation without symbol
EPLAN found a connection on a schematics page that it cannot assign to a connectionpoint.
Error cause:
This message only occurs when the page layout is incorrect or on converted pages.
Suggested remedy:
Delete the connection in the schematic and generate it once again.
1.7.7 F4611 Incorrect target wiring
A target wiring was specified in the schematic for which the program cannot find theconnection to a wire or to a potential or where the connection is contradictory. Checkthe target wiring at the nodes and double junctions through which this connectionpasses.
1.8 PLC Cross-references
4701 F Duplicate PLC device-end terminal designation
4702 F Error while accessing the PLC cross-reference database
4703 F PLC device-end terminal without designation
4704 F There is no counterpart for the PLC end terminal in the overview
System Manual EPLAN 5.40
34
1.8.1 F4701 Duplicate PLC device-end terminal designation
EPLAN found a duplicate device-end terminal designation during the PLC cross-reference run.
Suggested remedy:
Change one of the duplicate device-end terminal designations in the schematic, save theschematic page(s), and start a new PLC cross-reference run.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.8.2 F4702 Error while accessing the PLC cross-reference database
EPLAN could not open the PLC cross-reference database.
Possible error causes:
1. The project directory in which the file specified in the error message had been storedwas deleted.
2. The schematic database file specified in the error message or the project directory, inwhich this file was stored, is write-protected.
3. You are working in the network. Somebody accessed the PLC cross-reference data-base before you.
4. You are working in the network. You do not possess the corresponding access rightsfor the file.
Suggested remedies:
on 1st Check whether the specified file or the project directory still exist.
on 2nd Check the attributes of the file or of the project directory. De-activate the writeprotection for the file or for the project directory.
on 3rd Wait until you can reaccess the PLC cross-reference database or contact the userwho is editing the file.
on 4th Contact your system administrator and ask him for the corresponding accessrights for the file.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
Description of the Messages
35
1.8.3 F4703 PLC device-end terminal without designation
EPLAN found a device-end terminal without designation during the PLC cross-reference run.
Suggested remedy:
Assign a designation to the device-end terminal in the schematic, save the schematicpage(s), and start a new PLC cross-reference run.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.8.4 F4704 There is no counterpart for the PLC end terminal in theoverview
Error cause:
You are using a PLC end terminal in the schematic that does not exist on the PLC over-view page. For this reason, EPLAN cannot generate cross-reference data.
Suggested remedy:
Enter the missing PLC end terminal in the PLC overview, save the schematic page, andstart a new PLC cross-reference run.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.9 Edit PLC data
4801 H Modified type of connection
4802 H Modified symbolic address
4803 H Modified function text
4804 H New PLC terminal
System Manual EPLAN 5.40
36
1.9.1 H4801 Modified type of connection
The type of connection of the PLC terminal was modified. In order to update the sche-matic correspondingly, the type of connection of the terminal must be entered manually.
1.9.2 H4802 Modified symbolic address
The symbolic address of the PLC terminal was modified. In order to update the sche-matic correspondingly, the symbolic address must be entered manually.
1.9.3 H4803 Modified function text
The function text of the PLC terminal was modified. In order to update the schematiccorrespondingly, the function text must be entered manually.
1.9.4 H4804 New PLC terminal
A new PLC terminal was defined. In order to update the schematic correspondingly, theterminal must be inserted manually.
1.10 PLC Assignment List
4901 F Address has been assigned several times
4902 F Symbolic address has been assigned several times
1.10.1 F4901 Address has been assigned several times
Error cause:
When generating the assignment list from the schematic, EPLAN found a PLC end ter-minal that is used more than once in the schematic.
Suggested remedy:
Check your project and rename addresses that occur several times. Save the page(s), andgenerate a new assignment list.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
Description of the Messages
37
1.10.2 F4902 Symbolic address has been assigned several times
Error cause:
When generating the assignment list from the schematic, EPLAN found a symbolic ad-dress that is used more than once in the schematic.
Suggested remedy:
Check your project and rename symbolic addresses that occur several times. Save thepage(s), and generate a new assignment list.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.11 Generate Terminals
5001 F Terminal with no designation
5002 F DD cannot be taken from the left
5003 F DD cannot be taken from above
5004 H DD cannot be taken from the left
5007 W Sorting cannot be used
5008 F Workstation and strip designation too long
5009 F Terminal number and terminal subnumber too long
5011 F Incorrect workstation designation
5012 F Incorrect strip designation
5013 F Incorrect terminal number
5015 F Incorrect terminal subnumber
5016 W Incorrect designation (only DIN)
5017 F Incorrect strip subnumber
System Manual EPLAN 5.40
38
5018 W Higher-level assignment does not exist
5019 W Location designation does not exist
5020 F Duplicate terminal (page)
5021 F Ring closure/search depth exceeded
5022 F Too many targets
5023 F Target with incomplete DD
5024 F Terminal subdivision too short for target
5025 F Duplicate strip designation (page)
5026 H Duplicate strip designation (page)
5027 W Connection designation too long
5031 F Arrow with no designation
5032 F Arrow not found
5050 F Duplicate terminal (page)
5051 W Wrong symbol type for terminal strip
5052 W Wrong symbol type for connector strip
5053 H Strip not predefined
5054 H Strip without terminals/connectors
5055 F Connector file does not exist
5056 F Pin designation not contained in the connector file, expected
5057 F Terminal subdivision too short for target
5058 W Terminal number exceeds spare
Description of the Messages
39
5061 F Incorrect jumper bar formation
5065 F Dual entry in form field
5069 F Too many targets
5071 F Incorrect wire jumper formation
5072 F Too many wire jumper levels
5075 H Form field shifted
1.11.1 F5001, F5501 Terminal with no designation
Error cause:
During the generation run, EPLAN found a terminal with the terminal strip designationbut the terminal number is lacking. Therefore the device designation of the terminal isnot complete.
Suggested remedies:
1. Enter the terminal number at the terminal in the schematic that was found byEPLAN,
or
2. call up the automatic correction program by using the menu path Generate / Termi-nal/terminal connection/interconnect diagram / Edit / Correction function (start at themain menu). Activate the "5001 Terminal with no designation: Use the questionmark for numbering" check box in the subsequent Correct dialog box, and click on[OK]. EPLAN now automatically provides the terminal with a question mark.
Click [OK] after the correction run, and start a new generation run.. The error mes-sage is not output any more.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.11.2 F5002, H5004, F5502 DD cannot be taken from the left
The page did not contain a terminal lying to the left of the terminal from which the stripdesignation could have been used. The direction from which the strip designation istaken can be specified by a parameter at the terminal input.
System Manual EPLAN 5.40
40
Suggested remedies:
• Enter a terminal designation at the terminal symbol in the schematic.
• Check the specified search direction in the input window of the terminal.
1.11.3 F5003, F5503 DD cannot be taken from above
The page did not contain a terminal lying above the terminal from which the strip des-ignation could have been used. The direction from which the strip designation is takencan be specified by a parameter at the terminal input.
Suggested remedies:
• Enter a terminal designation at the terminal symbol in the schematic.
• Check the specified search direction in the input window of the terminal.
1.11.4 W4205, W5007, W5505 Sorting cannot be used
Sort and check parameter 2 or 3 was defined, but the page contains no terminal behindwhich sorting can take place.
The sorting criterion 0/... will therefore be used at the indicated terminal.
1.11.5 F5008 Workstation and strip designation too long
For DIN, workstation and strip designation can contain a maximum of 20 characters,including the "X" or "L" and the minus sign.
1.11.6 F5009 Terminal number and terminal subnumber too long
The terminal and subnumber must not exceed 10 characters including the colon separa-tor and the period.
1.11.7 F5011, F5511, F5811 Incorrect workstation designation
The workstation designation, that is the terminal strip designation in front of the "X"identifier cannot be inserted in the terminal diagram.
Error cause:
The identifier specified in the schematic includes more characters than predefined in theparameter program.
Description of the Messages
41
Suggested remedies:
1. Select the menu path Utilities / Parameters / Project / Terminals/cables (start at themain menu). EPLAN opens a dialog in which you can set the parameters for the gen-eration of the terminal and interconnect diagrams. The cursor is automatically posi-tioned in the first input field of the Terminal breakdown parameter. This partial pa-rameter determines the number of characters preceding the terminal strip. Thefollowing example shows how to increase the specified value:
You gave the following designation to a terminal strip in the schematic:
41AX2:1, 41AX2:2, 41AX2:3 etc.
The parameter value "2" is assigned to the preceding identifier. But sincethree characters are used in front of the "X" identifier in the schematicEPLAN displays an error when the terminal diagram is being generated.
If you set the parameter value to "3" or to a higher number and restart thegeneration run this error will not occur any more.
If you enter a "0" or a number exceeding "18" EPLAN ignores the speci-fied value and replaces it automatically with the value "9".
2. Reduce the number of characters of the partial parameter in the schematic so that itcorresponds to the predefined number in the parameter program.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.11.8 F5012, F5512, F5812 Incorrect strip designation
The strip designation cannot be inserted in the terminal diagram.
Error cause:
The strip designation specified in the schematic includes more characters than prede-fined in the parameter program.
Suggested remedies:
1. Select the menu path Utilities / Parameters / Project / Terminals/cables (starting atthe main menu). EPLAN opens a dialog in which you can set the parameters for thegeneration of the terminal and interconnect diagrams. Move the cursor to the secondinput field of the Terminal breakdown parameter. This is the input field behind the"X" identifier. This partial parameter specifies the number of characters of the termi-nal strip designation. The following example shows how to correct an error:
System Manual EPLAN 5.40
42
You gave the following designation to a terminal strip in the schematic:
X33:1, X32:2, X33:3 etc.
The value "1" is given in the input field of this partial parameter. But sincetwo figures are used behind the "X" identifier in the schematic EPLAN dis-plays an error message when the terminal diagram is being generated.
If you set the parameter value to "2" or to a higher value and generate anew terminal diagram this error will not occur any more.
If you enter a "0" or a number exceeding "9" EPLAN ignores the specifiedvalue and replaces it automatically with the maximum value "9".
2. Reduce the number of characters of the respective partial parameter in the schematicso that it corresponds to the predefined number in the parameter program.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.11.9 F5013, F5513, F5813 Incorrect terminal number
The terminal number cannot be inserted in the terminal diagram.
Error cause:
The terminal number specified in the schematic includes more characters than prede-fined in the parameter program.
Suggested remedies:
1. Select the menu path Utilities / Parameters / Project / Terminals/cables (start at themain menu). EPLAN opens a dialog in which you can set the parameters for the gen-eration of the terminal and interconnect diagrams. Move the cursor to the fourth in-put field of the "Terminal breakdown" parameter. This is the input field behind the":" separator. This partial parameter specifies the number of terminal number char-acters. The following example shows how to increase the specified value:
Description of the Messages
43
You gave the following designation to a terminal strip in the schematic:
X1:110, X1:111, X1:112 etc.
The value "2" is given in the input field of the partial parameter Terminalnumber. But since three numbers behind the ":" separator were specified inthe schematic EPLAN displays the error message mentioned above whenthe terminal diagram is being generated.
If you set the parameter value to "3" or to a higher value and generate anew terminal diagram this error message will not be displayed any more.
Only parameter values between "1" and "7" will be accepted in the inputfields. If you enter a "0" or a number exceeding "7" EPLAN ignores thespecified value and replaces it automatically with the maximum value "7".
2. Reduce the number of characters of the respective partial parameter in the schematicso that it corresponds to the predefined number in the parameter program.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.11.10 F5015, F5515, F5815 Incorrect terminal subnumber
The terminal subnumber cannot be inserted in the terminal diagram.
Error cause:
The terminal subnumber specified in the schematic includes more characters than prede-fined in the parameter program.
Suggested remedies:
1. Select the menu path Utilities / Parameters / Project / Terminals/cables (start at themain menu). EPLAN opens a dialog in which you can set the parameters for the gen-eration of the terminal and interconnect diagrams. Move the cursor to the fifth inputfield of the Terminal breakdown parameter. This is the input field behind the "."separator. This partial parameter specifies the number of characters of the terminalsubnumber. The following example shows how to increase the specified value:
System Manual EPLAN 5.40
44
You gave the following numbering to terminals in the schematic:
X17:22.10, X17:22.12, X17:22.12 etc.
The value "1" is given in the input field of the partial parameter Terminalsubnumber. But since two numbers behind the "." separator were specifiedin the schematic EPLAN displays the error message mentioned above whenthe terminal diagram is being generated.
If you set the parameter value to "2" or to a higher value and generate anew terminal diagram this error message will not be displayed any more.
Only parameter values between "0" and "7" will be accepted in the inputfields. If you enter a number exceeding "7" EPLAN ignores the specifiedvalue and replaces it automatically with the value "1".
2. Reduce the number of characters of the respective partial parameter in the schematicso that it corresponds to the predefined number in the parameter program.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.11.11 W5016, W5516, W5816 Incorrect designation (only DIN)
The device designation of a terminal cannot be sorted into the terminal diagram becausea component designation is too long, or the separation character cannot be recognized.The number specifies where this error occurred.
0 = Cannot be specified: There is no separator between the strip and the terminal (":")
1 = Incorrect preceding identifier
2 = Strip designation incorrect
3 = Number incorrect
4 = Potential (behind slash) incorrect
5 = Subnumber incorrect
Suggestions for avoiding the warning:
1. Correct the lengths of the terminal subdivision in the terminal parameters (refer tohelp window there).
2. Change the designation of the respective terminal in the schematic.
In EPLAN COMPACT it is not possible to carry out all suggested remediessince it has less functions than the complete EPLAN version.
Description of the Messages
45
1.11.12 F5017, F5517, F5817 Incorrect strip subnumber
The strip subnumber of a terminal has a greater number of characters than specified inthe Terminals / Cables project parameters.
Suggested remedy:
Look at the recommended minimum subdivision in the message management and adaptthe Terminal subdivision parameter (under Utilities / Parameters / Project / Termi-nals/cables) correspondingly.
Please also note: If the strip subnumber is used, the minimum value must be "2" and themaximum value is "9".
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.11.13 F5020, F5050 Duplicate terminal (page)
Two terminals with the same device designation have been used without the terminalproperty for multiple use of the terminal number being set.
Suggested remedies:
• Change the designation of one of the two terminals.
• Check in the input window of the terminal under ’Check code’ whether the terminalnumber may be set several times within this terminal strip. When drawing a potential terminal you should set the value for the check code to 1so that the terminal number is allowed several times. Furthermore, you should alsoset the value for the sorting identifier to 1 so that the terminal is sorted behind theterminal lying to the left of it.
• Call up the Edit menu item in the Terminal and interconnect diagram module andclick on the error correction in order to allow a "duplicate" terminal.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.11.14 F5023 Target with incomplete DD
The DD of a terminal target contains only a higher-level assignment and/or locationdesignation. The DD for the target of a conductor specification is missing.
Change the designation for the corresponding DD.
System Manual EPLAN 5.40
46
1.11.15 F5024, F5057 Terminal subdivision too short for target
The character length of the target designations found consisting of the DD and the con-nection designation does not fit into the corresponding data field. The total length of thedata field is specified in the terminal parameters under "Terminal subdivision". The sumof the values determines the length of the targets.
Suggested remedy:
Go to the parameters and increase the size of the terminal breakdown at any point sothat the displayed target designation fits into the field.
1.11.16 F5025, H5026 Duplicate strip designation (page)
The strip designation in a strip definition for terminals or connectors (special text 2 or 3)has been assigned twice.
1.11.17 W5027 Connection designation too long
The field length of the connection designation is monitored. During the specification ofthe minimum subdivision this is taken into consideration with the value V#x.
1.11.18 F5031, F5531 Arrow without designation
The schematic contains a potential arrow which does not have a designation.
Enter the missing designation and generate the potential cross-references once more.
1.11.19 F5032, F5532 Arrow not found
The counterpart of a potential arrow could not be found. Possible causes:
• Arrow does not exist
• Arrow has an incorrect designation.
Suggested remedy:
Check the generated potential cross-references. Enter any potential arrows which maybe missing into the schematic. Then generate new potential cross-references. The cross-reference must be executed free of errors.
Description of the Messages
47
1.11.20 W5051 Wrong symbol type for terminal strip
A strip was defined as a terminal strip in the special text, but the terminals making upthe strip have the wrong symbol type.
1.11.21 W5052 Wrong symbol type for connector strip
A strip was defined as a connector strip in the special text, but the pins making up thestrip have the wrong symbol type.
Exceptions: For connectors 107 (N) and 112 (PE) are also allowed.
Suggestion for avoiding the warning:
Call up the automatic correction program by using the Generate / Terminal/terminalconnection/interconnect diagram / Edit / Correction function menu path (start at themain menu). Activate the "5052 Wrong symbol type for connector strip: Change to 135"check box in the subsequent Correct dialog box, and click [OK]. EPLAN now changesthe symbol type automatically.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.11.22 H5053 Strip not predefined
A strip designation which was not defined by a special text 2 or 3 has been used. Thefirst terminal will be used to define the strip type.
Suggested remedy:
Call up the correction program for terminals and cables by using the menu path Gener-ate / Terminal/terminal connection/interconnect diagram / Edit / Correction function(start at the main menu). Activate the "5053 Strip not predefined: Generate strip defini-tion" check box in the subsequent Correct dialog box, and click [OK]. EPLAN thengenerates the strip definition.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
System Manual EPLAN 5.40
48
1.11.23 H5054 Strip without terminals/connectors
A strip definition (special text 2 or 3) has been used for which no terminals or connec-tors have been drawn in the schematic.
Suggested remedy:
Call up the correction program for terminals and cables by using the menu path Gener-ate / Terminal/terminal connection/interconnect diagram / Edit / Correction function(start at the main menu). Activate the "5054 Strip without terminals/connector: Deletestrip definition" check box in the subsequent Correct dialog box, and click [OK].EPLAN then removes the strip definition.
In EPLAN COMPACT it is not possible to carry out all suggested remediesor corrections since it has less functions than the complete EPLAN version.
1.11.24 F5055 Connector file does not exist
A connector type that does not exist in the connector file being used was defined in theschematic.
1.11.25 F5056 Pin designation not contained in the connector file, butexpected
A pin connector designation not existing in the connector file was used. After this mes-sage the designation expected at this place is indicated.
If a connector type file is used, no sorting code with the character "/" may be used in theschematic.
1.11.26 W5058 Terminal number exceeds spare
Cause of warning:
You specified a minimum number of spare terminals for a terminal strip in the sche-matic. However, more terminals were inserted in the schematic. Thus, the specifiedminimum number of spare terminals was exceeded.
In the Text properties dialog you defined a minimum number of five spareterminals for the terminal strip "X1" by using the menu path (starting at thegraphics editor) Draw/Text. However, in the schematic you are using sixterminals with the terminal strip designation "X1".
Description of the Messages
49
Suggestions for eliminating the error:
1. Set the minimum number of spare terminals in the Terminal strip tab in the Textproperties dialog to "0",
or
2. increase the minimum number of spare terminals so that it exceeds the number ofterminals used in the schematic,
or
3. Launch the automatic correction program by using the menu path Generate / Termi-nal/terminal connection/interconnect diagram / Edit / Correction function (start at themain menu). Activate the "5058 Terminal number exceeds spare: Increase spare"check box in the subsequent Correct dialog box and click [OK]. EPLAN now auto-matically increases the number of spare terminals so that the warning message doesnot occur any more.
In EPLAN COMPACT it is not possible to carry out all suggested remediessince it has less functions than the complete EPLAN version.
1.11.27 F5061 Incorrect jumper bar formation
This error occurs with jumper bars when a jumper is defined from a terminal that can bejumpered to one that cannot, or if the target for a wire jumper is invalid.
1.11.28 F5065 Dual entry in form field
The same form position was assigned to two targets of a terminal.
1.11.29 F5071 Incorrect wire jumper formation
Error cause:
You have connected several terminals via wire jumpers. One or several terminals havean invalid terminal number (see example). This is the case if the terminal number(s)used in the schematic has/have more figures than specified in the parameter program.
In this case the error message F5013 ("Incorrect terminal number") is out-put (see F5013).
Suggested remedies:
Select the menu path Utilities / Parameters / Project / Terminals/cables (start at the mainmenu), and check the Terminal subdivision parameter on the Terminals/cables 1 tab.The value shown in the field for the length of the terminal number(s) (field behind the
System Manual EPLAN 5.40
50
colon) must agree with the number of figures for the terminal number(s) used in theschematic.
Either reduce the number of figures of the respective terminal number(s) used in theschematic to the value specified in the parameter program, or increase the value for thelength of the terminal number(s) in the parameter program. Generate a new terminaldiagram after that.
In EPLAN COMPACT it is not possible to carry out all suggested remediessince it has less functions than the complete EPLAN version.
By mistake, the terminal number "371" was assigned to the terminal "X10:37" in theschematic. However, according to the parameter settings (Terminal subdivision pa-rameter) only two figures are allowed for the length of the terminal number. ThereforeEPLAN cannot find the jumper targets of the terminal. The terminal "371" is not dis-played in the terminal diagram, but the two incomplete jumpers that originate from theterminals "X10:34" and "X10:42" (see illustration below). In addition to the error,EPLAN thus outputs the number of incomplete jumpers in the message window.
Description of the Messages
51
1.11.30 F5072 Too many wire jumper levels
More wire jumpers can be generated within a strip than are defined in the parameters.
1.11.31 H5075 Form field shifted
The position will be evaluated, but not exactly at the desired position.
1.12 Generate Cable
5201 F Oblique cable line
5202 F Conductor designation without two targets
5203 F Cable target with incomplete DD
5204 F Duplicate cable/conductor definition in path
5205 F Incorrect marking of cable conductor/shielding
5208 F Cable between same strip
5209 F Missing cable designation to
5211 F Incorrect cable designation
5212 F Invalid cable designation
5215 F Cable definition not between components
5218 H Conductor color without cable line
5220 W Part number not at first cable line
5221 F Differing cable data
5222 F Cable designation too long
5223 F Cable type does not exist
System Manual EPLAN 5.40
52
5225 F No. of conductors not defined
5231 F No cable (type) defined for conductor
5232 F Number of conductors missing in the cable definition
5233 F Number of conductors not defined
5235 F Color assigned twice
5236 F Color not defined
5237 F No cable (type) defined for conductor
5239 F Too many conductors
5241 F Cable definition not at the terminal
5243 W One-sided cable definition
5244 F Counter target not found
5245 W Cable not defined to
5246 F Cable designation too long
5260 F No. of conductors not defined
5261 F No PE conductor allowed for type
5262 F Two/several PE conductors intersected
5263 F No N-conductor allowed for type
5264 F Two/several N conductors intersected
5265 F No shielding allowed for type
5266 F Two/several shielding conductors intersected
5267 F Too many conductors
Description of the Messages
53
5268 H Subcable generated
5269 F Too many subcables
5281 F Number of conductors not defined
5282 F Cable without conductor
5283 F Too many conductors
5284 F Invalid color assignment
5285 W One-sided cable definition
1.12.1 F5201 Oblique cable line
EPLAN found an oblique cable line in the schematic.
Cables can only be defined correctly if the cable lines are drawn precisely horizontallyor vertically (see example).
Suggested remedy:
Use [i] on the keyboard to display the insertion points and markings of all schematicsymbols in the schematic.
Afterwards right-click on the insertion point of the incorrect cable line.
Click on the Change size menu item in the pop-up menu opened by the system. At theother end of the cable line the cursor is displayed as an "X". The color of the cable linechanges from yellow to white (only in case of default setting) and the cursor can bemoved in a circle around the insertion point of the cable line.
Move the cursor so that the cable line and all conductors of the cable establish a rightangle. Only when this is done, EPLAN is able to exactly specify the intersections be-tween the cable line and the conductors.
Once you have found the right position for the cable line double click with the left-handmouse button. The cable line becomes yellow again (only in case of default setting), andthe intersections between cable line and conductors are displayed.
In case you only clicked once by mistake EPLAN will move the cable textwhen the mouse is moved. Move the text, that you may have moved acci-dentally, to the right position again.
After that, save the schematic page(s) and start a new generation run.
System Manual EPLAN 5.40
54
In the left-hand graphics a cable line is drawn incorrectly (oblique). In the right-handgraphics you will find a correctly drawn cable line (horizontally).
1.12.2 F5202 Conductor designation without two targets
EPLAN found a cable line passing through one or several conductors which are withoutboth connection targets.
Error cause:
This message is output when one (several) devices are deleted accidentally that is (are)connected to a defined cable (see example).
Suggested remedy:
Reinsert the deleted device(s) in the schematic so that two targets can be assigned to theconductor(s) of the defined cable.
Save the schematic page(s) and start a new generation run.
The error F5202 "Cable specification not between components" is outputtogether with error F5215, as the cable line and therefore the cable specifi-cation, too, is no longer located between two devices (see F5215).
Description of the Messages
55
Terminal "X1:3" was deleted. Therefore the third conductor of the defined cable "W1"is without the two target connections "X1:3" and "M1:W1".
1.12.3 F5203 Cable target with incomplete DD
EPLAN found a cable target without a complete DD.
Possible error cause:
This error occurs when you deleted or failed to specify the device designation of a com-ponent that is the target of a cable (see example).
Suggested remedy:
Provide the component that is the target of the defined cable with a complete devicedesignation.
After that, save the schematic page(s) and start a new generation run.
The error F5203 "Cable specification not between components" is outputtogether with error F5215, as the cable line and therefore the cable specifi-cation, too, is no longer located between two devices (see F5215).
System Manual EPLAN 5.40
56
The device designation of the motor was deleted or not entered into the schematic.There is a cable connection but EPLAN could not assign the cable target.
1.12.4 F5204 Duplicate cable/conductor definition in path
EPLAN found a cable that was defined twice or a conductor that was defined twice.
Possible error causes:
1. More than one cable line or conductor line were inserted between two wiring targets(see example 1).
2. A cable line of a defined cable 1 intersects the conductor of a defined cable 2 (seeexample 2).
Suggested remedies:
on 1st Delete all inserted cable or conductor lines except for one.
on 2nd Shorten the cable line of cable 1 so that there is no longer an intersection withthe conductor of cable 2.
Save the changes to the schematic page(s) and start a new generation run.
Description of the Messages
57
Two cable lines were inserted by mistake between terminal strip "X1" and motor "M2".There is no unique cable or conductor specification.
The cable line of cable "W1" intersects a conductor of cable "W2". Therefore both ca-bles are defined incorrectly.
System Manual EPLAN 5.40
58
1.12.5 F5205 Incorrect marking of cable conductor/shielding
EPLAN found a wrong cable conductor/shielding marking.
Error cause:
You accidentally moved a cable line marking into a shielding (see example).
Suggested remedy:
Use the key on the keyboard to display the insertion points and markings of allschematic symbols in the schematic.
Move the shifted marking back to the intersection between the cable line and the cableconductor.
Save the schematic page and start a new generation run.
The marking of the left-hand conductor of cable "W1" "slipped" into the insertedshielding.
Description of the Messages
59
1.12.6 F5208 Cable between same strip
EPLAN found a cable between the same terminal strip.
Error cause:
You defined a cable in the schematic that connects two terminal strips with the samedesignation (see example). This error results in the error F5282 "Cable without con-ductors".
Suggested remedy:
Change the designation of one of the two terminal strips.
After that, save the schematic page(s) and start a new generation run.
The first and second target of cable "W2" are identical (terminal strip "X4" in bothcases). Therefore the cable cannot be generated.
System Manual EPLAN 5.40
60
1.12.7 F5209 Missing cable designation to
EPLAN found a missing cable designation.
Error cause:
This message will appear when the parameters specify that cables are to be assignedtarget designations but more than one connection without a cable designation was com-bined under a single cable line (see example).
Suggested remedy:
Enter the missing cable designation in the schematic, save the schematic page(s) andstart a new cable generation run.
The cable designation is missing at the specified cable line. Therefore EPLAN cannotassign the cable to the two targets ("S1" and "S2").
Description of the Messages
61
1.12.8 F5211 Incorrect cable designation
EPLAN found an incorrect cable designation.
Error cause:
A cable was defined with only one identifier in the cable definitions, but the designationparameters require two identifiers.
You gave the designation "W1" to a cable. However, the parameter settingsfor terminals and cables require two identifiers, namely "WA".
Suggested remedy:
Select the menu path Utilities / Parameters / Project / Terminals/cables (start at the mainmenu). Go to the Cable identifier input field on the Terminals/cables 1 tab. You willfind the specified cable designation there.
Now you can choose between deleting the second identifier in the parameter program orusing the two specified identifiers for cable designations in your project from now on.
In EPLAN COMPACT it is not possible to carry out all suggested remediessince it has less functions than the complete EPLAN version.
1.12.9 F5212 Invalid cable designation
EPLAN found an invalid cable designation.
Error cause:
The Cable number assignment parameter was preset to "1 = Automatic 1 target" or "2 =Automatic 2 targets". However you designated the cable(s) manually in the schematic.
Suggested remedies:
1. Select the menu path Utilities / Parameters / Project / Terminals/cables (start at themain menu). Open the dropdown list box next to the Cable number assignment inputfield on the Terminals/cables 1 tab, and select one of the manual options "0" or "3"up to "D" (depending on the desired cable designation). After that, save the sche-matic page(s) and start a new cable generation run.
2. Keep the parameter setting, and delete the cable designation entered manually in theschematic. After that, save the schematic page(s) and start a new cable generationrun.
In EPLAN COMPACT it is not possible to carry out all suggested remediessince it has less functions than the complete EPLAN version.
System Manual EPLAN 5.40
62
1.12.10 F5215 Cable definition not between components
The cable definition found in the schematic cannot be assigned.
Possible error causes:
1. You forgot to assign a complete device designation to a cable target.
In this case the error message F5203 ("Cable target without completeDD") is output (see F5203).
2. You deleted the (target) devices above and below the defined cable, but the cable linein the schematic was not deleted (see example).
In this case the error message F5202 ("Conductor designation with-out two targets") is output as the cable line does not have two targetsanymore.(see F5202).
Suggested remedies:
on 1st: See error F5203
on 2nd: Delete the cable line in the schematic, save the schematic page(s) and start a newgeneration run.
The terminal strip "X1" and the motor "M1" (see left-hand graphics) of the defined ca-ble "W1" were deleted, but the cable line was not. The cable line is no longer locatedbetween two devices, but "floats" undefined in the schematic (see right-hand graphics).
Description of the Messages
63
1.12.11 H5218 Conductor color without cable line
A conductor color could not be assigned to a cable line.
EPLAN stops the generation despite of this message.
1.12.12 W5220 Part number not at first cable line
Cause of warning:
You have defined a cable of the same designation several times within the schematicand assigned a part number to it. The part number was not entered in the symbol prop-erties dialog box (Part tab) of the first definition line of the cable but in the symbolproperties dialog box of the second or a further one.
Suggestion for avoiding the warning:
Always assign the part number to the symbol properties dialog box of the first cabledefinition line. The first cable line is the cable line EPLAN finds first in the evaluationdirection within the project hierarchy.
1.12.13 F5221 Differing cable dataEPLAN found different cable data for a single cable definition.
Error cause:
You defined one and the same cable on two pages in the schematic and entered on onepage different data concerning the cable type, the number of conductors, the cross sec-tion or the cable length.
Suggested remedies:
1. Change the cable specification so that the cable data are identical on all schematicpages,
or
2. Launch the automatic correction program by using the menu path Generate / Termi-nal/terminal connection/interconnect diagram / Edit / Correction function (start at themain menu). Activate the "5221 Differing cable data: Remove data of the 2nd defi-nition" check box in the subsequent Correct dialog and click on [OK]. EPLAN willnow delete the cable data on the page on which you defined the cable once againwith the exception of the cable designation.
In EPLAN COMPACT it is not possible to carry out all suggested remediessince it has less functions than the complete EPLAN version.
System Manual EPLAN 5.40
64
1.12.14 F5222, F5246 Cable designation too long
EPLAN found a cable designation that is too long.
Error cause:
A cable designation was specified or generated which exceeds the predefined parametervalue.
Suggested remedy:
Follow the menu path Parameters / Terminals/cables in the Terminal and interconnectdiagram module. Change the Maximum cable designation length parameter on the Ter-minals/cables 1 tab to the value shown in the message window
The Maximum cable designation length parameter has the default value"4" (4 characters). You generated a cable with the designation W12 (3characters) in the schematic. After the cable generation has been com-pleted the following message is output:
" ....W12[5255] Cable designation too long 5"
If you increase the parameter value to "5" as specified at the end of themessage you will not get another error message after a new generationrun.
Information on the example: When assigning cable designations EPLANadds two additional characters to the generated subcable designation. Sub-cables are defined by an enlargement of the cable designation consisting ofa separator (point) and a figure between 1 and 9 (e.g. "W12.1").For this reason check the parameter concerning the length of the cabledesignations before assigning cable designations. The value entered must atleast include two more characters than the longest cable designation.
1.12.15 F5223 Cable type does not exist
EPLAN found a cable type that does not exist.
Error cause:
You specified a cable type in the schematic or a standard cable in the parameter pro-gram that EPLAN could not find in one of the cable type files.
Suggested remedies:
Specify a cable that exists in the cable type file, or include the new cable in one of thecable type files. In the following sections you learn how to proceed to do this.
Description of the Messages
65
Follow the menu path Generate / Terminal/terminal connection/interconnect diagram /Edit / Cable types (start at the main menu).
In the subsequent Cable types dialog you can assign the new cable either to a project-specific file or to a general cable type file (*.KLB). Furthermore you can enter the newcable in a new cable type file here.
If you want to generate the cable project-specifically, click on the entry ’Project-specific’to be found in the tree that is located on the left-hand side in the dialog box.
If you want to assign the cable to a general cable type file just click on the desired cablefile in the tree view.
Whether you want to assign the new cable to a project-specific or to a general cable typefile, select New from the pop-up menu in both cases. In the subsequent dialog you cancreate a new cable type file by means of the Type file input field. Delete the name en-tered there and enter a new name. Afterwards enter the name of the new cable type andselect the type of cable. Enter the number of conductors in the subsequent window andclick on [OK]. Close the dialog afterwards.
Particular points to be regarded when selecting the color-coded cable:
When you create a color-coded cable you must assign the corresponding color to eachconductor. Click in the Cable types dialog on the specified number of conductors underthe cable type in the tree view (click on cable type first). On the right-hand side of thedialog the individual conductors will be listed which are sequentially numbered andprovided with a placeholder (#). The placeholder indicates that this a color-coded cablewhose conductor colors have to be added manually. To do this, click on each conductornumber twice (no double click), and enter the desired conductor color into the framedinput field. Afterwards, click on or click on any list entry to transfer the value.
1.12.16 F5225, F5233, F5260, F5281, F6303 Number of conductors notdefined
EPLAN found a cable in the schematic with an undefined number of conductors (seealso error message F5239 "Too many conductors").
Error cause:
You specified a number of conductors in the schematic which is not permitted for thiscable type. For example the cable line intersects more conductors in the schematic thanyou have defined for the cable.
The error message indicates the cable type with the incorrect number of conductors.
System Manual EPLAN 5.40
66
Suggested remedies:
1. Click on the insertion point of the cable line in the schematic. The Symbol propertiesdialog will then be displayed.
Then, click on the [...] button that is located next to the No. of conductors input fieldin the Cable tab. The subsequent dialog will indicate the selected cable type and willlist the numbers of conductors defined for the cable.
Select the number of conductors you need and click [OK]. EPLAN will now replacethe incorrect number of conductors by the right one.
After that, save the schematic page(s) and start a new cable generation run.
2. Alternately, you can define a new number of conductors for the cable (namely thenumber that was rejected by EPLAN).
Select the menu path Generate / Terminal/terminal connection/interconnect diagram /Edit / Cable types (start at the main menu). In the Cable types dialog box you willfind all defined cable type files with the associated cables. Select the cable in the treeview, and highlight it. EPLAN then displays the numbers of conductors of the cable.Now click on any number of conductor assigned to the cable. Afterwards, select theNew option from the pop-up menu. Define a new number of conductors for the cablein the subsequent dialog box by entering this number in the input field. Confirm thisentry by clicking on [OK], save the new cable data, and close the dialog.
Then, change over to the schematic. Find the cable, and click on the insertion pointof the cable line. In the subsequent Symbol properties dialog click on the [...] buttonthat is located next to the No. of conductors input field in the Cable tab. Select thenewly defined number of conductors for the cable in the subsequent dialog and clickon [OK]. Exit the Symbol properties dialog box by clicking on [OK], save the sche-matic page(s) and start a new generation run.
1.12.17 F5231, F5237 No cable (type) defined for conductor
EPLAN found conductor colors in the schematic that cannot be assigned to a cable (seeexample).
Error cause:
You presumably moved a schematic extract that contains a cable definition. In doing so,you forgot to highlight the cable line and move it as well, and therefore the conductorcolors cannot be assigned to a cable any longer.
Suggested remedies:
1. Move the cable line back so that all conductors intersect the cable line again,
or
Description of the Messages
67
2. Use the key on the keyboard to display the markings of all schematic symbols inthe schematic. Now the intersection and insertion points between the cable line andthe conductors are displayed.
Delete the intersection points one after the other. The conductor colors will be de-leted, too.
After that, delete the associated cable lines.
Save the schematic page(s) after each error correction and start a new cable generationrun.
The terminal strip "X2" and the connected switch "S1" were moved to the right. How-ever, the cable line of the defined cable "W12" remained on the old position. As thecable line is now located outside the connection and the intersection points of the cableline were moved with the conductors, no cable is defined for the conductor colors.
System Manual EPLAN 5.40
68
1.12.18 F5232 Number of conductors missing in the cable definition
EPLAN found a missing number of conductors in the cable definition.
Error cause:
You assigned conductor colors but no number of conductors to a color-coded cable ofthe type "3" (color-coded cable with different conductor variants and color sequences)in the schematic. Since the color sequence is different for each number of conductors,the program is unable to make any assignment.
EPLAN displays the cable type in the error message.
Suggested remedy:
Click on the insertion point of the cable line in the schematic to call up the Symbolproperties dialog, and enter the missing number of conductors for the cable in the Cabletab.
After that, save the schematic page(s) and start a new generation run.
1.12.19 F5235 Color assigned twice
EPLAN found a conductor color that was assigned twice.
Error cause:
When the conductor colors were manually assigned to a color-coded cable two conduc-tors were given the same color.
Suggested remedy:
Change one of the conductor colors, then save the schematic page(s) and start a newgeneration run.
1.12.20 F5236 Color not defined
EPLAN found a cable for which no conductor cables are defined.
Possible error causes:
1. You changed the cable type of one of the cables in the schematic at a later point intime. For example, you no longer use a color-coded cable but a numbered cable, thatdoes not require a conductor color. However, you did not delete the conductor colorsof the color-coded cable after the having made the change in the schematic (see ex-ample).
Description of the Messages
69
2. You assigned a color to a (several) cable conductor(s) in the schematic, that is (are)not defined for the selected cable. For example you assigned the color white (wt) tothe conductor of a four-conductor color-coded cable of the NIY type with the colorsblue (bl), brown (br), black (nr) and yellow (ye).
Suggested remedies:
on 1st Use the key on the keyboard to display the insertion points and markings ofall schematic symbols in the schematic. Delete all insertion points at the rejectedconductor colors, save the schematic page(s) and start a new generation run.
If you want the conductor numbers of the new cable type to be displayed in theschematic, proceed as follows:
Exit the Graphics editing module. Afterwards, select the menu path Generate /Terminal/terminal connection/interconnect diagram / Edit / Cable and conductordata / Delete. In the following window a selection of the cable data to be deletedis displayed. Activate the Conductor colors check box, and click [OK]. Selectthe incorrect cable from the subsequent dialog by highlighting it in the ’Avail-able’ list (on the left) and transfer it to the ’Output’ list (on the right) by using the
button. Then start the conductor colors deletion process by clicking [OK],and confirm the subsequent message window by clicking [OK] again.
Select the Cable and conductor data menu item once again. This time, click onTransfer in the subsequent menu. Select a conductor color font size in the fol-lowing dialog box, and click [OK] to confirm the your selection. Then re-selectthe cable by using the button, and click [OK] again. EPLAN now adds thecable numbers to the cable line. They are displayed in the Graphics editingmodule.
on 2nd Exit the Graphics editing module and select the menu path Generate / Termi-nal/terminal connection/interconnect diagram / Edit / Display/Edit / Interconnectdiagram. Click on the Conductor assignment tab in the subsequent dialog.EPLAN will show you the colors defined for the cable and which conductors arereserved or free. Close the dialog and change the color(s) of the conductorsfound by EPLAN in the schematic.
After that, save the schematic page(s) and start a new cable generation run.
In EPLAN COMPACT it is not possible to carry out all suggested remediessince it has less functions than the complete EPLAN version.
System Manual EPLAN 5.40
70
The type of the cable "W12" defined in the schematic was changed. A numbered cableof the Ölflex type was used instead of the color-coded cable (see cable identification).The conductors of the numbered cable still have the colors of the previous cable.
1.12.21 F5239, F5267, F5283 Too many conductors
EPLAN found a cable line in the schematic that intersects more conductors than it wasdefined for the cable. This error message is output together with the error F5225("Number of conductors not defined").
Error cause:
You determined a certain number of conductors for a cable in the schematic. However,the cable line intersects more conductors than it was defined.
The specified number of conductors will be displayed in the error message.
Suggested remedies:
1. Click on the insertion point of the cable line in the schematic. The Symbol propertiesdialog will then be displayed.
Description of the Messages
71
Then, click on the [...] button that is located next to the No. of conductors input fieldin the Cable tab. The subsequent dialog will indicate the selected cable type and willlist the numbers of conductors defined for the cable.
Select the number of conductors you need and click on [OK]. EPLAN will now re-place the incorrect number of conductors by the right one.
After that, save the schematic page(s) and start a new cable generation run.
2. Alternately, you can define a new number of conductors for the cable (namely thenumber that was rejected by EPLAN).
Select the menu path Generate / Terminal/terminal connection/interconnect diagram /Edit / Cable types (start at the main menu). In the Cable types dialog box you willfind all defined cable type files with the associated cables. Select the cable in the treeview, and highlight it. EPLAN then displays the numbers of conductors. Now clickon any number of conductors assigned to the cable. Afterwards, select the New op-tion from the pop-up menu. Define a new number of conductors for the cable in thesubsequent dialog box by entering this number in the input field. Confirm this entryby clicking on [OK], save the new cable data, and close the dialog.
Then, change over to the schematic. Find the cable, and click on the insertion pointof the cable line. In the subsequent Symbol properties dialog click on the [...] buttonthat is located next to the No. of conductors input field in the Cable tab. Select thenewly defined number of conductors for the cable in the subsequent dialog and clickon [OK]. Exit the Symbol properties dialog box by clicking on [OK], save the sche-matic page(s) and start a new generation run.
1.12.22 F5241 Cable definition not at the terminal
The cable definition of a terminal strip with multiple targets or the definitions of variouscables with the same targets, the cable definition must be marked at each terminal con-nection.
In addition, the terminal marking must also be defined when the terminal connection isto a non-terminal in various paths.
If this is not done, the program will be unable to recognize which specification belongsto which terminal/target connection.
1.12.23 W5243, W5285 One-sided cable definition
EPLAN found a one-sided cable definition.
Cause of warning:
In case of cables located between terminal strips the symbol property "Terminal con-nection for cable generation" was not correctly preset.
System Manual EPLAN 5.40
72
Depending on the defined direction of the connection for the cable definition, two dif-ferent warnings of the same title can be output: "W5243" and "W5285" (for details referto example).
Suggestion for avoiding the warnings or for error correction:
First, select the menu path Options / Multifunction menu / Cable display in the Graphicsediting module. The connection targets of the terminals for the cable connections willthen be displayed.
To avoid warning "W5243" proceed as follows:
1. Select Edit / Messages in the Graphics editing module. EPLAN now displays a listcontaining all messages which were output during the generation runs.
Click on the entry "W5243" on the list (the entry will be highlighted) and afterwardson the [OK] button at the bottom of the list. EPLAN will then close the list of mes-sages and jumps with the cursor to the terminal in the schematic that caused thewarning.
Click once on the respective terminal. EPLAN displays the Symbol properties dialog.Change the Connection for cable generation property in the Terminal tab from "U =Below" to "O = Above", and close the dialog by clicking [OK].
After that, save the schematic page(s) and start a new generation run. The warning isnot output any more.
2. Call up the correction program for terminals and cables by using the menu path Gen-erate / Terminal/terminal connection/interconnect diagram / Edit / Correction func-tion (start at the main menu).
Activate the "5243 One-sided cable definition: Generate a cable" check box and clickon [OK]. Now EPLAN has generated a cable for the connection.
Click [OK] after the correction run. The warning is not output any more.
In case of the warning "W5285" there are the following possibilities to avoid this mes-sage:
1. Select Edit / Messages in the Graphics editing module. EPLAN now displays a listcontaining all messages which were output during the generation runs.
Click on the entry W5285 on the list (the entry will be highlighted) and afterwards on[OK] at the bottom of the list. EPLAN will then close the list of messages and jumpswith the cursor to the terminal in the schematic that caused the warning.
Click once on the respective terminal. EPLAN displays the Symbol properties dialog.Change the Connection for cable generation property in the Terminal tab from "O =Above" to "K = No cable", and close the dialog by clicking [OK].
After that, save the schematic page(s) and start a new cable generation run. Thewarning is not output any more.
Description of the Messages
73
2. Call up the correction program for terminals and cables by using the menu path Gen-erate / Terminal/terminal connection/interconnect diagram / Edit / Correction func-tion (start at the main menu).
Activate the "5285 One-sided cable definition: Do not generate a cable" check box,and click on [OK]. EPLAN now removes the one-sided cable definition.
Click on [OK] after the correction run, and start a new cable generation run. Thewarning is not output any more.
In EPLAN COMPACT it is not possible to carry out all suggested remediessince it has less functions than the complete EPLAN version.
In the left-hand graphic the direction for the cable generation at the terminals "X2:12,13, 14" was predefined in the Symbol properties dialog to be "U = Below". Thus thecable definition is one-sided as far as the terminal strip "X1" is concerned. In this case,EPLAN will output the warning "W5243".
System Manual EPLAN 5.40
74
In the right-hand graphic the direction of the cable generation at the terminals "X5:12,13, 14" was predefined in the Symbol properties dialog to be "O = Above". In this case,too, there is a one-sided cable definition as to the terminals "X4:1, 2, 3". In this case,EPLAN will output the warning "W5285".
1.12.24 F5244, F5509 Counter target not found
The target to which the cable leads was not found in the terminal diagram during cablegeneration.
1.12.25 W5245 Cable not defined to
This message is directly connected to the parameter "Generate only those cables definedin the schematic" (Terminals/cables 2 tab). If this parameter is activated, the automaticcable generation is deactivated. Cables are only generated if a cable line exists.
Possible causes of warning:
You forgot to insert a cable line, or you deleted the cable line by mistake.
Suggestion for avoiding the warning or for error correction:
1. Insert the missing cable line in the schematic, save the schematic page(s) and start anew cable generation run.
2. Call up the correction program for terminals and cables by using the menu path Gen-erate / Terminal/terminal connection/interconnect diagram / Edit / Correction func-tion (start at the main menu).
Activate the check box "5245 Cable not defined to...: Do not generate a cable", andclick [OK]. EPLAN now removes the incomplete cable definition.
Click [OK] after the correction run, and start a new cable generation run. The warn-ing is not output any more.
In EPLAN COMPACT it is not possible to carry out all suggested remediessince it has less functions than the complete EPLAN version.
1.12.26 F5261 No PE conductor allowed for type
Error cause:
A cable line intersects a PE conductor that is not valid or permitted for the specifiedcable type.
Description of the Messages
75
Suggested remedy:
Change the cable type in the Symbol properties dialog. Select a cable provided with aPE conductor (e.g. type "Ölflex").
After that, save the schematic page(s) and start a cable generation run.
1.12.27 F5262 Two/several PE conductors intersected
A cable line intersects two or more PE conductors.
Error cause:
You converted two or more terminals, that are targets of a defined cable, to PE termi-nals (symbol type "111" to "113"). However, the cable line must not cross more thanone PE conductor.
Suggested remedy:
Change the symbol type of the terminals at all PE conductors that are assigned twice.The symbol types for feed-through terminals "100" to "106" are for instance suitable forthis.
After that, save the schematic page(s) and start a new cable generation run.
1.12.28 F5263 No N conductor allowed for type
Error cause:
A cable line intersects a N conductor that is not valid or permitted for the specified ca-ble type.
Suggested remedy:
Change the cable type in the Symbol properties dialog. Select a cable provided with a Nconductor.
After that, save the schematic page(s) and start a cable generation run.
1.12.29 F5264 Two/several N conductors intersected
A cable line intersects two or more N conductors.
Error cause:
You converted two or more terminals, that are targets of a defined cable, to "N termi-nals" (symbol type "107" to "110"). However, the cable line must not cross more thanone N conductor.
System Manual EPLAN 5.40
76
Suggested remedy:
Change the symbol type of the terminals at all N conductors that are assigned twice.The symbol types for feed-through terminals "100" to "106" are for instance suitable forthis.
After that, save the schematic page(s) and start a new cable generation run.
1.12.30 F5265 No shielding allowed for type
Error cause:
The cable line intersects a shielding conductor connection. The cable type specifieddoes not permit a shielding.
Suggested remedy:
Change the cable type in the Symbol properties dialog. Select a cable provided with ashielding.
After that, save the schematic page(s) and start a new cable generation run.
1.12.31 F5266 Two/several shielding conductors intersected
A cable line intersects two or more shielding conductors.
Error cause:
You drew a cable line through two ore more shielding conductors (see example). How-ever, the cable line of a defined cable must not cross more than one shielding conductor.
Suggested remedy:
Insert the cable line in the schematic, and make sure that it only intersects one shieldingconductor.
After that, save the schematic page(s) and start a new cable generation run.
Description of the Messages
77
The cable line of the cable "W8" intersects two shielding conductors.
1.12.32 H5268 Subcable generated
A subcable was generated, even though only defined cables are to be generated.
1.12.33 F5269 Too many subcables
More than 9 subcables have been generated (.1 through .9).
1.12.34 F5282 Cable without conductor
Cause of error message:
You have defined a cable in the schematic which intersects the connecting lines of ter-minals of the same terminal strip. In this case EPLAN recognizes a cable to which noconductors are assigned (see also error F5208 "Cable between same strip").
Suggested remedies:
1. Delete the cable definition line from the connection.
or
2. Rename one of the terminal strips.
After that, save the schematic page(s), and start a new generation run.
System Manual EPLAN 5.40
78
1.12.35 F5284 Invalid color assignment
This message is displayed if the number of conductors is not specified and conductorcolors not matching the color sequence are assigned at connections which are not termi-nals.
1.13 Import Cable Data
5501 F Terminal with no designation
5502 F DD cannot be taken from the left
5503 F DD cannot be taken from above
5504 W Sorting cannot be used
5509 F Counter target not found
5511 F Incorrect workstation designation
5512 F Incorrect strip designation
5513 F Incorrect terminal number
5515 F Incorrect terminal subnumber
5516 W Incorrect designation (only DIN)
5517 F Incorrect strip subnumber
5518 W Higher-level assignment does not exist
5519 W Location designation does not exist
5531 F Arrow with no designation
5532 F Arrow not found
Description of the Messages
79
1.14 Create Terminal Bill of Materials
5701 F No matching terminal marked
5702 F Accessories missing
5703 F Terminal / strip definition not found
1.14.1 F5701 No matching terminal marked
Mark the terminals with the identifiers and the cross-sections which you used in theschematic. The appropriate accessories for each terminal must also be marked. The ter-minal type and the cross-section are specified (0,2 mm² is the minimum cross-section).
1.14.2 F5702 Accessories missing:
The required terminal has not been selected for a terminal. The part number of the ter-minal, the type of accessory and the identifier are specified.
1.14.3 F5703 Terminal / strip definition not found
This error message only occurs in case of older projects. It is output when you deletedor shifted a terminal in the schematic and the terminal bill of materials has not been re-generated afterwards. In other words, the terminal bill of materials now contains a ter-minal that is not at the position specified.
1.15 Import Terminal Bill of Materials
5801 F Terminal not found in terminal bill of materials
5802 F Strip header does not exist
5811 F Incorrect workstation designation
5812 F Incorrect strip designation
5813 F Incorrect terminal number
System Manual EPLAN 5.40
80
5815 F Incorrect subnumber
5816 W Incorrect designation (only DIN)
5817 F Incorrect strip subnumber
5818 W Higher-level assignment does not exist
5819 W Location designation does not exist
1.15.1 F5801 Terminal not found in the terminal bill of materials
A terminal which does not exist in the terminal bill of materials has been entered in theschematic. Probably the terminal diagram or the terminal bill of materials is not up-to-date.
1.15.2 F5802 Strip header does not exist
The strip definition found during the generation of the terminal diagram is no longerpositioned on its original page, path, and position. The data can therefore not be writtenback.
1.16 Graphics Terminal-strip Overview
6001 H Function text truncated
1.16.1 H6001, H6101, H6201, H6301, H6601, H6701, H6801 Function text truncated
The function text exceeded the defined length and could not be broken down into 2lines.
Description of the Messages
81
1.17 Graphics Cable Overview
6101 H Function text truncated
6102 F Cable file does not exist
1.17.1 F6102, F6202 Cable file does not exist
A cable file that was available during the generation run no longer exists.
1.18 Graphics Terminals
6201 H Function text truncated
6202 F Cable file does not exist
6203 F Terminal strip not found
6205 F Graphics page not output
1.18.1 F6203 Terminal strip not found
This error message is output when a selected strip is not found in the terminal diagramduring the graphics output of the terminal diagram.
This error may occur in case of internal database problems.
1.18.2 F6205 Graphics page not output
The graphics page defined in the form could not be output, since it was not found.
System Manual EPLAN 5.40
82
1.19 Graphics Cables
6301 H Function text truncated
6302 F Cable file does not exist
6303 F Number of conductors not defined
6306 W Target not found
6307 F Target 2 not found
1.19.1 W6306 Target not found
No valid device was found.
The terminal will be included in the terminal diagram, but without a target.
1.19.2 F6307 Target 2 not found
The corresponding counter target was not found.
1.20 Graphics Terminal Connection
6401 W Symbol macro not found
6402 W Symbol not found in the schematic
6403 F Differing macro connections
6404 F Differing symbol numbers
1.20.1 W6401 Symbol macro not found
You have marked a symbol in such a way that the connection sequence should be readout of the symbol macro. However, the symbol macro has not been created.
Description of the Messages
83
1.20.2 W6402 Symbol not found in the schematic
You have marked a symbol in such a way that the connection sequence should be readout of the schematic. The symbol you are looking for cannot be found on the page of theterminal, or the output project is not the same as the original one.
1.20.3 F6403 Differing macro connections
The number of connections between the symbol and symbol macro is not the same.
1.20.4 F6404 Differing symbol numbers
The symbol number within the symbol macro is not the same as the symbol number ofthe symbol.
1.21 Graphics Bill of Materials
6601 H Function text truncated
6602 H Designation truncated
1.21.1 H6602, H6702, H6802 Designation truncated
In the case of this message, the text was longer than the settings specified in the coordi-nate parameters. The text was truncated.
1.22 Graphics Device List
6701 H Function text truncated
6702 H Designation truncated
6703 H Symbol not within limits
System Manual EPLAN 5.40
84
1.22.1 H6703 Symbol not within limits
The symbol belonging to a cross-reference could not be displayed. Only the page/pathinformation is shown.
1.23 Graphics Purchase-order List
6801 H Function text truncated
6802 H Designation truncated
1.24 Translation
7001 F No source language found
7002 F DRAW command error
7003 F Data structure error (ESC)
7011 W Search term missing
7012 W Target term missing
1.24.1 F7001 No source language found
The source language specified in the parameters does not exist in the text to be trans-lated.
1.24.2 F7002 DRAW command error
An entry for free-hand drawing contains, for example, an unknown command. Any textthat may be behind it will not be translated.
1.24.3 F7003 Data structure error (ESC)
There is an error in the file structure. The program cannot properly identify the start of aword for translation.
Description of the Messages
85
1.24.4 W7011 Search term missing
A word to be translated was not found in the database.
1.24.5 W7012 Target term missing
A word to be translated was found in the database, but it has not been translated into therequired language(s).
1.25 HPGL Import
7201 F Lower X limit exceeded
7202 F Upper X limit exceeded
7203 F Lower Y limit exceeded
7204 F Upper Y limit exceeded
7205 W Unknown HPGL command
7206 F Invalid numerical value
1.25.1 F7201 Lower X limit exceeded
The coordinates of the plot file which was read in do not fit onto the EPLAN page. Thevalue lies below the minimum value of 0.
Suggested remedy:
Adjust the magnification factor or the X offset in the parameters (Plot file / Scalings).
1.25.2 F7202 Upper X limit exceeded
The coordinates of the plot file which was read in do not fit onto the EPLAN page. Thevalue lies above the maximum value of 15970.
Suggested remedy:
Adjust the magnification factor or the X offset in the parameters (Plot file / Scalings).
System Manual EPLAN 5.40
86
1.25.3 F7203 Lower Y limit exceeded
The coordinates of the plot file which was read in do not fit onto the EPLAN page. Thevalue lies below the minimum value of 0.
Suggested remedy:
Adjust the magnification factor or the Y offset in the parameters (Plot file / Scalings).
1.25.4 F7204 Upper Y limit exceeded
The coordinates of the plot file which was read in do not fit onto the EPLAN page. Thevalue lies above the maximum value of 10870.
Suggested remedy:
Adjust the magnification factor or the Y offset in the parameters (Plot file / Scalings).
1.25.5 W7205 Unknown HPGL command
An HPGL command in the plot file was not recognized.
The following commands are recognized:
Command Meaning
AA "arc absolute" (arc around the entered absolute center)
AR "arc relative" (arc around the entered relative center)
CI "circle" (circle around the current point, with radius value)
DI "absolute direction" (absolute value for the pitch and line direction fortext)
LB "label" (text output)
LT "line type" (line type definition)
PA "plot absolute" (movement of the pen to an absolute position)
PD "pen down" (plotter pen movement and descent)
PG "advance full page" (page advance)
PR "plot relative" (movement of the pen to a relative position)
PU "pen up" (plotter pen lift and movement)
RA "fill rectangle absolute" (definition of a solid rectangle in absolute co-ordinates)
Description of the Messages
87
Command Meaning
RR "fill rectangle relative" (definition of a solid rectangle in relative coor-dinates)
SC "scale" (definition of a user-specific coordinate system, scaling)
SP "select pen" (pen selection according to number)
SR "relative character size" (size of an output character as a percentage).
1.25.6 F7206 Invalid numerical value
An HPGL command contained a value which lies outside the valid range, e.g. SP 37.
SP selects a pen which does not exist.
1.26 Import Parts
7401 F Part defined several times
7403 W Importing of parts being aborted (number of errors > 50)
1.26.1 F7401 Part defined several times
When importing parts EPLAN found components, that have been defined several times.
Suggested remedy:
Search parts in the import file or in the import database that have been entered severaltimes, delete the superfluous data, and start importing the parts again.
System Manual EPLAN 5.40
88
1.26.2 W7403 Importing of parts being aborted(number of errors > 50)
EPLAN stops importing parts since the number of errors exceeded 50.
Possible cause:
EPLAN found more than 50 parts that were defined several times.
Suggestion for avoiding the warning:
Search parts in the import file or in the import database that have been entered severaltimes, delete the superfluous data, and start importing the parts again.
Creating Print Forms
89
2 Creating Print Forms
This chapter contains information on the following topics:
• The Report Processor
• Functions for Print Forms
• F Codes.
2.1 The Report Processor
The report processor can be used to output data from your projects in the format of for-matted lists. Output can be to the screen, the printer, or a file. Please refer to the fol-lowing section.
To this purpose you can either use the form files included in the scope of delivery ordefine your own forms. The layout of the individual elements which you want to usefrom the projects is defined on the forms.
The form files for use with the report processor are called print forms below, in orderto differentiate them from the other form types (graphics forms, plot forms, plotframes).
System Manual EPLAN 5.40
90
You can also use a text editor to design print forms. It is advisable to create own printforms on the basis of the print forms supplied since experience is required in order toedit the forms.
If you use a word-processing program to edit the print forms, ensure that the file issaved in ASCII format. Only files which do not contain control characters can be proc-essed correctly by the report processor.
2.1.1 Structure of Print Forms
Print forms have two essential components. Their handling is described below.
Form description Field descriptionName: ########## Price: #######.## DM \1:1,1:39
The character \ (backslash) separates the form description from the field description.The information after the \ is not printed. It specifies which data are to be written intothe form.
The form description specifies the following criteria:
• Which fixed data the form is to contain
• Where the data fields are to be placed
• How long the data fields are
• How the data are to be prepared for printing.
Fixed texts are output on the printout exactly in the line and column specified in theform. You can enter explanatory texts and frames freely. The exceptions are the \ and adot in the first column which initiates a command or area sequence.
Texts not positioned within an area are treated as comments. This also applies to textspositioned behind a command or an area command. Comments are not printed. Lineswhich contain area commands, comments and commands (for example ..DA 0: Dataof the first page) are not counted.
The length of the data fields is determined by the number of # used. If you want theprintout to contain characters for decimal values or separators for the thousands, youmust also enter a # for these characters.
If several data fields are to be printed in one line, the length of all the data fields areentered in the form description in the form of #. The individual fields are then separatedby at least one blank, graphics character or fixed text.
The data can be prepared for printing by means of formatting characters. You can thusspecify whether, for example, decimal values are to be used for numerical data. Thisformatting is described in more detail under the topic "Preparing Data for Printing" (seebelow).
The lines may have a maximum length of 256 characters.
Creating Print Forms
91
The field description can contain various elements which are explained in the follow-ing overview.
• Number of a file: The file number is used to specify the file from which the data areto be taken.
The data of the control panels are contained in the SRK.DAT housing file.This file has the file number 5.
• Number of the data field: The data fields are differentiated within a file by meansof the field number. A colon separates the file from the field number.
The Purchase Order Number of a control panel has the field number 6. Ifyou want to print this P.O. Number in a form, you must enter 5:6 as thefield description.
• Special code: Certain data, for example the system date, can be inserted into a formby means of special codes.
• F code: These codes are only used for the so-called fixed print forms. These are fieldcodes for particular data. Which data these are depends on the program module fromwhich printing is to be carried out. You can therefore not use F codes for the univer-sal print forms described here. (Also refer to the F codes in the section "Field Identi-fiers of the Individual Programs".)
Notes:
• You can print several data in one line of a form. In this case you have to enter a fielddescription for each field. The individual field descriptions are separated by commasand must not contain spaces.
• If several data fields are to be printed in one line, the length of all the data fields areentered in the form description in the form of "#"’s. The individual length specifica-tions must be separated by at least one space (or possibly another character).
Data fields and variables: Print preparation means that data fields are output withdecimal places, with fillers, left- or right-aligned, etc.
The following sections differentiate between the print preparation of:
• Numerical data fields and variables
• Alphanumerical data fields and variables.
Numerical data fields and variables can contain the filler characters * or 0. They cancontain decimal places and signs.
Which entry in the form leads to which printout, will be illustrated on the basis of thedata field 15:176 with the contents 4567.89.
System Manual EPLAN 5.40
92
Printout Form description CommentTotal: 4568 Total: ########## DM\15:176 Printout without deci-
mal placesTotal: 4567,89 Total: ########.## DM\15:176 Printout with decimal
placesTotal: ***4578,89 Total: #*######.## DM\15:176 Printout with filler "*"Total: 0004567,89 Total: #0######.## DM\15:176 Printout with filler "0"Total: 4567,89 Total: #-######.## DM\15:176 Left-aligned printoutTotal: 4567,89 Total: #^######.## DM\15:176 Printout of the actual
length of the data fieldTotal: -4567,89 Total: -#######.## DM\15:176 Minus sign is inter-
preted as a mathemati-cal sign.
The decimal separator is printed out as a period or a comma, depending on the com-pany-parameter setting Decimal character in the Print form menu.
In alphanumerical data fields and variables you can specify whether the printout isleft-aligned or right-aligned.
The contents of the data fields and variables can be shorter than the field length. Youcan therefore specify whether subsequent characters are to be positioned directly afterthe field contents or whether space is to be reserved for the complete field length.
Printout Form description CommentCustomer: Mil(C des.) Customer: ###### (C des.) UnformattedCustomer: Mil(C des.) Customer: #-#### (C des.) Right-alignedCustomer: Mil(C des.) Customer: #^#### (C des.) Minimize length
2.2 Overview of the Functions Valid for all Forms
Lines which begin with two dots designate areas.
Command Meaning Explanation
..ST Starting area Initializations
..HE x Header area Upper common part of every page
..DA x Data area The lines with the data
..DA 20 Completing line behind the last record
..DA 21 Filler lines between the data area and footer
..FO x Footer area Lower common part of every page
.. Area end Conclusion of an area
Different control commands can be included between the individual area commands.
Creating Print Forms
93
The following applies for all commands:
• The command begins with a period.
• The command must be positioned in the first column of the line.
• The command itself is not printed.
The following commands are available:
Command Function
.CP=x New page at less than ’x’ characters
.CW=x Set characters/inch to 10, 12 or 17 (parameter)
.DC="." Use dot as character for separating thousands
.DP="," Use comma as character for the decimal separator
.IF IF condition
.ELSE ELSE condition
.ENDIF End of an IF condition
.LFREE Variable with number of free data lines on the page
.LS Printing in landscape format
.NOPF Ensures that the last form page is output without line feeds("NoPageFill").
.OL=x Specify left-hand margin with ’x’ characters
.PA Begin new page
.PL=x Set number of lines per page to ’x’ (default 66)
.PT Print in portrait format
.SP=x Output of ’x’ blank lines
.Sn=(string expres-sion)
Set string variable number ’n’ to any string. The string caneither be any text in quotation marks ("") or a compositeexpression containing the operator "&", such as in:.S1="A"&"B".S2=F1&F2.S3=S1&S2.S4=S1+"C"+F3Ensure that no blank is used before and after the "&"!
.Zn=x Set numerical variable ’n’ to ’x’ (’n’ lies between 1 and 10)
System Manual EPLAN 5.40
94
If you use the "GDI" Windows output function, the commands .LS and .PT as well asall the control characters, such as bold remain without any effect. The font appearance iscontrolled by means of the control panel. Any command from .CW6 to .CW20 can be used for the character width.
The printer is set and controlled for form output on the one hand by the output pa-rameters specified in the parameter program and on the other hand by certain controlcharacters which are entered directly in the form and which from there call up the con-trol sequences for the printer specified in the parameters.The control characters switch over the font for the printer. The lines may have a maxi-mum length of 255 characters.
ASCII 1 Expanded print on/off.
ASCII 2 Bold on/off.
ASCII 14 Normal type 10 CPI
ASCII 19 Underline on/off.
ASCII 20 Superscript on/off
ASCII 22 Subscript on/off.
The decimal value ("ASCII" column) is entered by pressing and at the same timeentering the ASCII decimal value of the corresponding control character on the keys ofthe numerical keyboard.
The "Bold on" or "Bold off" mode is activated or de-activated by pressing and simultaneously.
These control characters must be entered at those points in the form at which the re-spective change-over is to take place.
The following point commands furthermore use the printer parameters:
Command Point command
10 characters per inch (normal type) .CW10
12 characters per inch .CW12
17 characters per inch (condensed print) .CW17
Landscape mode on .LS
Portrait mode on .PT
For detailed information on the output parameters, refer to the section "SpecifyingProperties for HPGL and ASCII Output Devices" in the User Guide.
Creating Print Forms
95
Data field definitions:
Field Explanation
##### Output field for strings or numbers without decimal values
####.## Output fields for numbers with 4 values before and 2 valuesafter the decimal points.
#*##.## Filler characters * before the number
#0##.## Filler characters 0 before the number
#-##### Numerical value left-aligned, string field right-aligned
#^##### Field is not filled
###$### Output two fields directly after each other
The codes must be assigned after the data fields. Several codes are separated by com-mas (for example \F11,F12,F13). The following codes are available:
ID Output
\DT Of the current date
\Fn Of the data field of the application
\FA Of the higher-level assignment
\FB Of the device designation
\FKA Of the higher-level assignment, without leading separator
\FKB Of the device designation, without leading separator
\FKO Of the location designation, without leading separator
\FNn Of the company name (1 <= n <= 4)
\FO Of the location designation
\FS Of the page number
\NOCR No carriage return (line feed) after the line
\PN Of the current page number
\Sn Of the string variables ’n’
System Manual EPLAN 5.40
96
2.2.1 Message Overview
If errors occur during printing due to a faulty form, a general message is output on thescreen with the specification of the message number.
This number together with a description is written automatically into the SYSTEM.ERRfile. Use the Message management module to view this file.
The entries in the SYSTEM.ERR file have the following structure:
• Program• Module
• Error message• Date/Time
• Explanations / Further information.
The individual entries:
PROGRAMThe name of the module by which the message was created or from which printing wascarried out is entered under Program. The form entered in the corresponding parametersis used.
MODULEMessages generated by the report processor have the entry "REPORT".
ERROR NUMBERAn internal error number is entered here. If the program provides for an explanation, theexplanation text is output in the subsequent lines with the designation "Explana-tion/Information". The following error numbers can occur:
Number Explanation3520 Numerical variable outside valid range
3530 Numerical variable outside valid range
3840 String variable outside valid range
3850 String variable outside valid range
3621 ":" Missing at "?"
3622 Division by 0
3623 Parenthesis close ")" missing
3624 Comparison terminator missing
3625 Number expected
5000 Too many lines in the area ...
5010 Too many fields for # groups
5020 Incorrect command (.XYZ=)
5030 Incorrect code (\XYZ)
Creating Print Forms
97
Number Explanation5031 Command instead of field (\CW12)
5040 No ENDIF
9102 Last page has been reached
2.3 The Field Codes of the Individual Programs(F Codes)
The print forms can only be used to output certain data which are linked with certainprogram sections. These forms have field descriptions, the so-called F codes. These arefield codes for particular data. Which data these are depends on the program modulefrom which printing is to be carried out. They are therefore explained together with theindividual forms.
You can print the results of the evaluation runs (generation runs) of the EPLAN projectsin formatted form. The following forms are provided to this purpose:
For cross-references, wiring lists and connection bills of materials:
WUPQVW1.QVW Contact cross-references
WUPQVW1.PVW Potential cross-references
WUPQVW1.VDR Wiring lists
WUPQVW1.VST Connection bill of materials
For lists for contactor selection:
WUPSCH1.DEF Contactor specification file
WUPSCH1.AGW List of the selected contactors
WUPSCH1.NAW List of the contactors that were not selected
For terminal and interconnect diagrams:
WUPKLE1.KLE Terminal diagram
WUPKLE1.KAB Interconnect diagram
WUPKLE1.KTY Cable type file
WUPKLE1.KSY Connector-type file
For terminal bills of materials:
WUPKST1.KST Terminal bill of materials
System Manual EPLAN 5.40
98
For files for foreign-language translation:
WUPTRA1.TRA Language file
WUPTRA1.TRF File of missing translations
For message management:
P_FEHLER.PME Message management file
For the EDOC documentation management:
EDOC1.EKS Condensed overview
EDOC1.EGS Complete overview
EDOC1.ESL Selection criteria
EDOC1.ELG Log
For list output:
Outputting lists in graphics:
*.FRM Form file for the bill of materials
*.FRM Form file for the order list
*.FRM Form file for the parts list
Printing lists:
*.STK Form file for the bill of materials
*.BML Form file for the device list
*.BST Form file for the order list
*.ART Form file for the parts list
For the standard labeling:
5154*.FRM Form files for the standard labeling
For the Phoenix Mark labeling:
PHOE*.FRM Form files for the Phoenix Mark labeling
In contrast to the parameter lists, several similar records are printed underneath eachother in these forms. This means that special functions apply here.
Creating Print Forms
99
The forms for the cross-references, wiring lists, lists for contactor selection, terminaland interconnect diagrams, terminal bill of materials and foreign-language translationall have the following structure:
Form commands Meaning
..ST
..HE 0
..DA 0
..FO 0
..DA 21
Starting area
Headers
Data lines
Footers
Fill lines between the data area and thefooter
The footers and the blank line can be used optionally. These lines can be used, for ex-ample, to create a framed form and to fill the page length correspondingly.
The structure of the forms for the terminal diagrams and the cable type lists have someadditional characteristics which are described for the corresponding forms.
Structure of the form files on the basis of the form for potential cross-references:
• Starting area: You can, for example, set a specific font between the ..STStarting area and the next .. area.
• Headers: The section from ..HE 0 on contains some general informa-tion on the project. In addition page numbering (\PN) and the date (DT)also belong to this form. The empty field in the first line can be used byyou, for example, as the field for the company name. The last line of theheader (before the next .. area specification) contains the headline forthe following data lines.
• Data lines: This area starts with the characters" ..DA 0 and consists ofone line in this form. This line contains the data fields which are filledwith data during the printout. The corresponding F codes are positionedbehind the \ character (backslash) at the end of the line.
• Footers: The footers begin at ..FO 0. These complete the form frame atthe bottom and create a margin at the end of the page.
• Special data lines: ..DA 21 begins an area in which special data linesare entered. The blank lines are used to fill the last page of the form un-til the end of the page so that the frame has the same size on all thepages of the printout.
System Manual EPLAN 5.40
100
2.3.1 Cross-references, Wiring Lists, and Connection Bills of Mate-rials
The following table lists the variable designations for the form WUPQVW1.QVW used toprint the contact cross-references:
Designation of the data field F code
HEADERS (fields with page and project data)
Plant designation F10
Drawing number F11
Commission F12
DATA LINES (fields for the individual contacts)
Device designations F30
Connection F31
Page/Path F32
Mounting location F33
Symbol number F34
Symbol type F35
Part number F36
Type number F37
The data for the header are taken from the project data. The values in the data lines areevaluated while the cross-references are being created.
Potential cross-references (WUPQVW1.PVW):
Designation of the data field F code
HEADERS (fields with page and project data)
Plant designation F10
Drawing number F11
Commission F12
DATA LINES (fields for the individual potentials)
Potential designation F40
Target designation F41
Page/Path F42
Symbol number of the target F44
Creating Print Forms
101
The data for the header are taken from the project data. The values in the data lines areevaluated while the cross-references are being created.
Wiring list (WUPQVW1.VDR) and connection bill of materials (WUPQVW1.VST):
Designation of the data field F code
HEADERS (fields with page and project data)
Plant designation F10
Drawing number F11
Commission F12
DATA LINES (fields for the individual connections)
Conductor number F20
Target 1 F21
Target 2 F22
Cross-section F23
Conductor color F24
Conductor length F25
Page/Path 1 F26
Page/Path 2 F27
Page of the wiring definition F28
Text of the wiring definition F29
Mounting location 1 F51
Mounting location 2 F52
Function text 1 F59
Function text 2 F60
Number F91
Conductor number list F92
Cross-section dimension F93
Dimension length F95
Subsequent connection in next line F98
Internal potential number F99
DATA LINES (instead of F21/F22 for DIN)
Higher-level assignment 1 F53
Higher-level assignment 2 F54
System Manual EPLAN 5.40
102
Designation of the data field F code
Location designation 1 F55
Location designation 2 F56
DD 1 F57
DD 2 F58
2.3.2 Contactor Selection and Contactor Specification
Contactor specification file (WUPSCH1.DEF):
Designation of the data field F code
DATA LINES (fields for the individual contactors)
Part number F4
Type designation F44
ID F12
Coil 1 F20
Coil 2 F21
Contacts 1 -12 F22-F33
List of the selected contactors (WUPSCH1.AGW):
Designation of the data field F code
HEADER
Project name F1
DATA LINES (fields for the individual contactors)
Device designations F2
Contacts required/available F3
Part number contactor F4
Part number auxiliary block F5
Coil F6
Type designation contactor F44
Type designation auxiliary block F45
Contactor variations F46
Name of the contactor specification file F47
Creating Print Forms
103
List of the contactors that were not selected (WUPSCH1.NAW):
Designation of the data field F code
HEADER
Project F1
DATA LINES (fields for the individual contacts)
Device designations F2
Contact (symbol name) F7
Connection designation F8
Page F9
Path F10
Position F11
2.3.3 Terminal and Interconnect Diagram
The following table lists the variable designations for the form WUPKLE1.KLE used toprint the terminal diagrams:
Designation of the data field F code
HEADERS (fields with page and project data)
Plant designation F10
Drawing number F11
Commission F12
Generated on: F13
DATA LINES (fields for the terminal strips)
DD of the terminal strip F30
Strip designation F31
Number of terminals/pins F35
From terminal/pin F36
To terminal/pin F37
DATA LINES (fields for the terminals)
Terminal number F40
Function text F41
Page/Path F42
PLC designation F46
System Manual EPLAN 5.40
104
Designation of the data field F code
Type number F47
Jumper symbol 1 (first line) F51
Jumper symbol 2 (subsequent line) F52
Target A-D F61-F64
Cable A-D F71-F74
Wire number A-D F81-F84
Cross-section target 1-4 F101-F104
Length of cable F111-F114
Explanation of the individual terms:
• Strip designation: You can insert this text into the schematic in order to obtain anoverview of the used terminal strips. This is a special text which is evaluated in theterminal diagram.
• Function text: The function text which you entered while inserting the terminal in theterminal dialog is assigned to the terminal. If there is no such text, the function textfrom the schematic is used. The text lying below the terminal in the same path is as-signed to the terminal.
• Page: In the case of DIN projects the higher level assignments and location designa-tions also belong to the page number.
• Jumper symbols: The jumper symbol 1 is used in the first data line for a terminal, thesecond jumper symbol 2 correspondingly in the second line. Either the character " "or a blank is used as the jumper symbol 2. The jumper symbol for the saddle jumpersis inserted for the first # character in the data field. If there are several characters, thewire jumpers are represented there by writing the number of the level behind thejumper symbol.
• Target A-D: The characters A to D are assigned to the targets found during the targetsearch. This means that the target 1 is assigned to target A for the terminal diagram,target 2 is assigned to target B, etc. You can thus decide where the various terminaltargets are to be output in the terminal diagram. This means that the terminal diagramcan be divided into an "external" and an "internal" half.
• Cable A-D: If a cable is defined at a terminal, the cables are assigned to the targets Ato D and printed out.
• Wire number A-D: If a special text "Wire numbering" has been set at a connection, itis evaluated and printed out via this F-code.
Creating Print Forms
105
The structure of the WUPKLE1.KLE form for the terminal diagrams differs in some as-pects from the other forms:
• A numerical variable .Z1=0 as well as four string variables with the symbols for thejumpers are defined in the start area.
• This is followed by a header area, two data areas as well as two footer areas for theterminal strip overview.
• ..HE 1 is followed by two header areas, six data areas, and the footer area for thepages with the terminal data.
This sequence including the designations for the header, data and footer areas cannot bechanged. You can only leave away either the entire section for the terminal strip over-view or the section for the individual terminals.
Since the printout form for the terminal diagram is very complex, we recommend thatyou copy the original file supplied by us and then carry out the changes in the copy.
Form commands Meaning
..ST
.Z1=0
.S1=" "
.S2=" "
.S3=" "
.S4=" "
..
..HE 0
..
..DA 0
..
..DA 1
.SP 72
..
..FO 0
..
..FO 1
.SP 4
..
..HE 1
..
..HE 2
..
..DA 3
.CP 10
.IF Z1 != 0
Starting area
Headers overview
Data lines overview
Closing data lines
Footers overview
Headers terminal diagram
Headers strip
System Manual EPLAN 5.40
106
Form commands Meaning
.ENDIF
.
.
Closing data linesHeaders list
The following table lists the variable designations for the WUPKLE1.KAB form used toprint the interconnect diagrams:
Designation of the data field F code
HEADERS (project-specific data)
Higher-level assignment F10
Drawing number F11
Commission F12
Generated on: F13
DATA LINES (cable data)
Cable designation F40
Target specification from F41
Target specification to F42
Type of cable F43
Set number of conductors F44
Actual number of conductors F45
Cable length F46
Cross-section 1 F47
Cross-section 2 F48
Remarks F49
Texts: N, PE, shielding F50
Page number of the first cable definition of each cable F51
The following additional codes for the output of detailed interconnect diagrams areavailable within the data area ..DA1:
Designation of the data field F code
DATA LINES (cable data)
Conductor designation F60
Target designation 1 F61
Creating Print Forms
107
Designation of the data field F code
Page/Path 1 F62
Function text 1 F63
Target designation 2 F71
Page/Path 2 F72
Function text 2 F73
Conductor type F80
Conductor index F81
Conductor cross-section F82
Unit of measure F83
In addition, the data areas ..DA2 and ..FO1 are also required.
The following table lists the variable designations for the WUPKLE1.KTY form used toprint the cable type file:
Designation of the data field F code
Cable designation F30
Remarks F31
Type of cable F32
Shielding F33
Text for no. of conductors F34
No. of conductors F35
Colors F36
Colors, line continuation F37
The form WUPKLE1.KTY has the following structure:
Form commands Meaning
.ST
.S1="Number-coded cable"
.S2="Color-coded cable 2"
.S3="Color-coded cable 3"
.S4="Cable with shielding"
.S5="Cable without shielding"
..
..HE 0
..
Starting area
Beginning of first header
End of command area
System Manual EPLAN 5.40
108
Form commands Meaning
..HE 1
..
..DA 0
.S4="No. of conductors"
.S5=" No. of conductors andcolor"..DA 1
Beginning of header subsequentpage
End of command areaCable header
End of command areaBeginning data lines number ofconductors
Notes:
• Cables with two different numbers of conductors are also managed in the cable typefile.
• You may specify a maximum of 10 identical colors in a cable.
• Several shieldings can be entered at a color-coded cable of Type 3.
The following table lists the variable designations for the WUPKLE1.KSY form used toprint the connector type file:
Designation of the data field F code
Connector name F30
Remarks F31
Sorting flag F33
No. of pins F35
Connector designation F36
2.3.4 Terminal Bill of Materials
The following table lists the variable designations for the WUPKST1.KST form used toprint the terminal bills of materials:
Designation of the data field F code
HEADERS (fields with page and project data)
Plant designation F10
Drawing number F11
Commission F12
DD of the terminal strip F15
Creating Print Forms
109
Designation of the data field F code
DATA LINES (fields for the terminal strips)
Strip designation F16
Length of the mounting rail F17
DATA LINES for the terminals (data from parts file)
Part number F21
Supplier F22
Order number F23
Type number F24
Remark F25
Color F26
Material F27
Width F28
Height F29
Depth F30
Degree of protection IP F31
Nominal cross-section F32
Cross-section from F33
Cross-section to F34
AWG from F35
AWG to F36
Current DIN F37
Current UL F38
Current CSA F39
Voltage DIN F40
Voltage UL F41
Voltage CSA F42
Connection sequence and type F43
Connection point F44
Connection level F45
Designation possibility/component F46
Designation possibility/terminal connection F47
System Manual EPLAN 5.40
110
Designation of the data field F code
Mounting method F48
Separating plate control F49
Identifier F50
DATA LINES for terminals (from terminal bill of materials):
Terminal number F60
Labeling right F61
Labeling right Purchase Order Number F62
Labeling left F63
Labeling left Purchase Order Number F64
Jumper Purchase Order Number F65
Cover Purchase Order Number F66
Mounting plate bracket Purchase Order Number F67
Remarks for terminal F68
Jumper display F70
Jumper, subsequent line F71
Structure of the form WUPKST1.KST:
Form commands Meaning
..ST
.S1=" "
.S2=" "
.S3=" "
.S4=" "
.S5=" "
..HE 0
..
..DA 0
.SP 72
..
..DA 1
..
..FO 0
..
..FO 1
..
Starting areaCharacter for jumper beginningCharacter for jumper centerCharacter for jumper endCharacter for jumper centerpieceCharacter for no jumperEnd of the command area
Beginning of the header area (header)End of the command areaBeginning of the data area(data line)Command for printing 72 blank linesEnd of the command area
Closing frameEnd of the command areaBeginning of the footer area (footer)
End of the command areaFooter of last page
End of the command area
Creating Print Forms
111
2.3.5 Foreign-language Translation
Structure of the language file WUPTRA1.TRA:
Designation of the data field F code
HEADER
Translation file name F19
Source language name F20
Source language identifier F21
Target language name F30
Target language identifier F31
DATA LINES (fields for the individual connections)
Search text F40
Translation text F41
Structure of the file of the missing translations WUPTRA1.TRF:
Designation of the data field F code
DATA LINES (fields for the individual connections)
Translation file name F19
Source text F40
Target and missing translation languages F42
The page and path information of missing words can only be printed directly after atranslation.
2.3.6 Message management
In EPLAN messages generated during the various evaluations are all managed in acommon database in your project directory. The messages can be output sorted by themessage number, page designation or device designation.
Structure of the message management file P_FEHLER.PME:
Designation of the data field F code
HEADER
Plant designation F10
Drawing number F11
Commission F12
System Manual EPLAN 5.40
112
Designation of the data field F code
Project name F13
Output E(rrors), W(arnings), N(otes) F14
DATA LINES (fields for 0=run information)
Number F20
Date F21
Time F22
Runtime F23
Text "aborted" F24
Code (name) F25
Module version F29
DATA LINES (fields for 1 = message record)
Message number F20
Text "Error", "Warning", "Note" F24
Page / Path, internal format F30
Page / Path, external format F31
Devices F32
Text (error description) F33
Supplementary data F34
Text, 2nd line F35
F34 and F35 together F44
DATA LINES (fields for 2 = Overview + run information)
Number F20
Date F21
Time F22
Runtime F23
Text "aborted" F24
Code (name) F25
Module version F29
Number of errors F91
Number of warnings F92
Number of notes F93
Creating Print Forms
113
2.3.7 Documentation Management EDOC
You can print out the data of one or more projects from the documentation database orfrom the log. The following four form files are provided:
EDOC1.EKS Condensed overview
EDOC1.EGS Complete overview
EDOC1.ESL Selection criteria
EDOC1.ELG Log.
The EDOC1.EGS form for the overall overview is subdivided into several data areas be-cause a data area cannot encompass more than 72 lines.
Whereas all the fields of the project data are output in the overall overview formEDOC1.EGS, the condensed overview form EDOC1.EKS only contains the most importantdata. Further variable designations can be added to the condensed overview form.
The following table lists the variable designations for the form EDOC1.EGS used to printthe overall overview of the project documentation. The EDOC1.EKS form for printing thecondensed overview of the project documentation contains only a subset of these vari-able designations.
Designation of the data field F code
Project F1
Project type F4
Page numbering type F5
Devices F6
Terminals F7
Cables F8
Potential Arrows F9
Plant designation F10
Drawing number F11
Commission F12
Company name F13
Company address 1 F14
Company address 2 F15
Supplementary field 1 F16
Supplementary field 2 F17
Supplementary field 3 F18
System Manual EPLAN 5.40
114
Designation of the data field F code
Supplementary field 4 F19
Supplementary field 5 F20
Supplementary field 6 F21
Supplementary field 7 F22
Make F23
Type F24
Mounting location F25
Part features F26
Environmental consideration F27
Location F28
Regulation F29
Degree of protection F30
Control panels F31
Power input F32
Lead-in F33
Control voltage F34
Date of manufacture F35
Short name of customer F36
Customer title F37
Customer name 1 F38
Customer name 2 F39
Customer name 3 F40
Street F41
P.O. Box F42
Zip code F43
Location designation F44
State F45
Telephone F46
Fax F47
Telex F48
Short name of end user F49
Creating Print Forms
115
Designation of the data field F code
End user title F50
End user name 1 F51
End user name 2 F52
End user name 3 F53
Street F54
P.O. Box F55
Zip code F56
Location designation F57
State F58
Telephone F59
Fax F60
Telex F61
Responsible for project F62
Project beginning F63
Project end F64
Last editor F65
Modification date F66
Higher-level assignment F67
Location designation F68
Number of pages of schematic F69
Generation date of schematic F70
Number of pages of free graphics F71
Generation date of free graphics F72
Number of pages of control-panel layout (obsolete) F73
Generation date of control-panel layout (obsolete) F74
Number of pages of plot frame creation F75
Generation date of plot form creation F76
Number of pages of EDOC cover sheet F77
Generation date of EDOC cover sheet F78
Number of pages of RS diagram F79
Generation date of RS diagram F80
System Manual EPLAN 5.40
116
Designation of the data field F code
Number of pages of terminal module bearer overview F81
Generation date of terminal module bearer overview F82
Number of pages of SAPIM F83
Generation date of SAPIM F84
Number of pages of NCRS F85
Generation date of NCRS F86
Number of pages of table of contents F87
Generation date of table of contents F88
Number of pages of terminal diagram F89
Generation date of terminal diagram F90
Number of pages of terminal bill of materials F91
Generation date of terminal bill of materials F92
Number of pages of terminal connection diagram F93
Generation date of terminal connection diagram F94
Number of pages of interconnect diagram F95
Generation date of interconnect diagram F96
Number of pages of bill of materials F97
Generation date of bill of materials F98
Number of pages of device list F99
Generation date of device list F100
Number of pages of PLC page F101
Generation date of PLC pages F102
Number of pages of terminal-strip overview F103
Generation date of terminal-strip overview F104
Number of pages of cable overview F105
Generation date of cable overview F106
Total no. of pages F127
No. of pages input F128
No. of pages generated F129
Date of language translation F130
Current macros directory F131
Creating Print Forms
117
Designation of the data field F code
Current normal master files directory F132
Current stock and parts files directory F133
Current form directory F134
Customer code F139
ID F140
Workstation F141
Date F142
Hard disk designation F143
Label F144
Storage medium 1 F145
Storage medium: Quantity 1 F146
Storage site 1 F147
Archiving date 1 F148
Customer code of data backup 1 F149
User code of data backup F150
Workstation of data backup F151
Storage medium 2 F152
Storage medium: Quantity 2 F153
Storage site 2 F154
Archiving date 2 F155
Customer code of data backup 2 F156
User code of data backup F157
Workstation of data back-up F158
Storage medium 3 F159
Storage medium: Quantity 3 F160
Storage site 3 F161
Archiving date 3 F162
Customer code of data backup 3 F163
User code of data backup F164
Workstation of data backup F165
Customer F166
System Manual EPLAN 5.40
118
Designation of the data field F code
Supplementary text 1 F167
Supplementary text 2 F168
Supplementary text 3 F169
The EDOC1.ESL form is used to output the selection criteria as well as the projectswhich fulfil the selection criteria. Only those selection criteria are printed which werespecified in the selection dialog box.
The EDOC1.ELG form is used to output the actions which were logged during documen-tation management in the log.
The following table lists the variable designations for the form EDOC1.ELG.
Designation of the data field F code
Project F1
Date of the log entry F3
Customer code F4
ID F5
Workstation Number F6
Entered action F7
Information field F8
Hard disk designation F9
Label F10
2.3.8 Outputting Lists (Parts Management)
In order to output bills of materials, purchase-order lists and parts lists you require formfiles in which the elements to be output are positioned. The form file EPPSC.STK is usedto output the bill of materials. The possible F codes for this form file are divided intothe following part classifications:
• Project information• Schematic data
• Master data• Special codes
• F codes for output settings
Creating Print Forms
119
2.3.8.1 Outputting Lists (Parts Management): Project information
Designation of the data field F code
Plant designation F3050
Drawing number F3051
Commission number F3052
Supplementary field 1 F3053
Supplementary field 2 F3054
Supplementary field 3 F3055
Supplementary field 4 F3056
Supplementary field 5 F3057
Supplementary field 6 F3058
Supplementary field 7 F3059
Company name F3060
Company address 1 F3061
Company address 2 F3062
Higher-level assignment F3063
Location designation F3064
Project beginning (date) F3065
Project end (date) F3066
Make F3067
Project type F3068
Mounting location F3069
Location F3070
Part features F3071
Environmental consideration F3072
Regulation F3073
Degree of protection F3074
Control panel F3075
Power input F3076
Lead-in F3077
Control voltage F3078
System Manual EPLAN 5.40
120
Designation of the data field F code
Date of manufacture F3079
Responsible for project F3080
Last editor F3081
Modification date F3082
Project name F3083
2.3.8.2 Outputting Lists (Parts Management): Schematic data
Designation of the data field F code
Sequential number F1
Engraving data F2
DD F3
Quantity assigned in the schematic F4
Stored at F5
Type of part assigned in the schematic F6
Part classification F7
Function text F8
Symbol number (from the bill-of-materials file) F9
Symbol file (from the bill-of-materials file) F10
Page number F11
Path in the schematic F12
Position the schematic F13
Internal value for path in the schematic F14
Internal value for position in the schematic F15
Electrical characteristics F16
Supplementary text in DD F17
Mounting location (from the bill-of-materials file) F18
Value of the EPLAN flag F19
Value of the EPPS/X flag F20
Item type F21
System ID F22
Assembly name (if part belongs to an assembly) F23
Creating Print Forms
121
2.3.8.3 Outputting Lists (Parts Management): Master data
Master parts data
Designation of the data field F code
Part number F101
Model type F102
Manufacturer short name: F103
Manufacturer long name F115
Supplier short name: F104
Supplier long name F116
Designation 1 F105
Designation 2 F106
Designation 3 F107
Purchase price/pack unit Currency 1 F108
Purchase price/pack unit EURO F145
Purchase price/pack unit Currency 2 F136
Purchase price/unit Currency 1 F135
Purchase price/unit EURO F146
Purchase price/unit Currency 2 F137
Sales price in Currency 1 F109
Sales price in EURO F147
Sales price in Currency 2 F138
Price unit F110
Unit of quantity F111
Order number F112
Remark 1 F113
Remark 2 F133
Date last modified F114
Group number F117
Graphics macro F118
Transfer identifier F316
Identifying letters F119
System Manual EPLAN 5.40
122
Designation of the data field F code
Symbol file F120
Symbol number F121
Price updating F122
Electrical characteristics F126
Connection designation F127
Part classification F128
Type of part F129
Part type (component, housing, cable or assembly) F130
Packaging unit (quantity/packaging) F131
Quantity per part (packaging size is considered) F132
Product group F134
Voltage F301 or F501
Current F302
Power F303
Holding power F304
Power dissipation F305
Weight F306 or F506
Connection cross-section F307
Tripping current F308
Width F309 or F409
Height F310 or F410
Depth F311 or F411
Mounting location F312
Space requirement F313
Mounting clearance - width F314
Mounting clearance - height: F315
Usable width (panel) F401
Usable height (panel) F402
Max. mounting depth (panel) F403
Mounting space (panel) F404
Usable width (door) F405
Creating Print Forms
123
Designation of the data field F code
Usable height (door) F406
Max. mounting depth (door) F407
Mounting space (door) F408
Cable external diameter F502
Cable conductor cross-section F503
Cable type F504
Number of cable conductors F505
Cable with shielding (Yes / No) F507
Cable with PE conductor (Yes / No) F508
Cable with N conductor (Yes / No) F509
Medium bending radius (cable) F510
Assembly element type (component, housing, cable) F601-F609
Part number of assembly elements F611-F619
Quantity of assembly elements F621-F629
Type designation of assembly elements F631-F639
Manufacturer short name of assembly elements F641-F649
Manufacturer: Title F201
Manufacturer: Name F202
Manufacturer: Name 2 F203
Manufacturer: Name 3 F204
Manufacturer: Street F205
Manufacturer: Zip code of the P.O. Box F215
Manufacturer: P.O. Box F206
Manufacturer: Zip code of city F207
Manufacturer: Location designation F208
Manufacturer: State F209
Manufacturer: Customer No. F210
Manufacturer: Info F211
Manufacturer: Modification date F212
Manufacturer: Phone F213
Manufacturer: Fax F214
System Manual EPLAN 5.40
124
Designation of the data field F code
Manufacturer: Email address F216
Supplier: Title F251
Supplier: Name 1 F252
Supplier: Name 2 F253
Supplier: Name 3 F254
Supplier: Street F255
Supplier: Zip code of the P.O. Box F265
Supplier: P.O. Box F256
Supplier: Zip code of city F257
Supplier: Location designation F258
Supplier: State F259
Supplier: Customer No. F260
Supplier: Info F261
Supplier: Modification date F262
Supplier: Phone F263
Supplier: Fax F264
Supplier: E-mail address F266
Manufacturer / supplier / customer master data
Designation of the data field F code
Short name F200
Title F201
Name 1 F202
Name 2 F203
Name 3 F204
Street F205
Zip code of the P.O. Box F215
P.O. Box F206
Zip code of city F207
Location designation F208
State F209
Creating Print Forms
125
Designation of the data field F code
Customer No. F210
Info F211
Modification date F212
Phone F213
Fax F214
E-mail address F215
2.3.8.4 Outputting Lists (Parts Management): Special codes
Designation of the data field F code
Total quantity of same part F123
Total price of same parts, Currency 1 F124
Total price of same parts, Currency 2 F139
Total price of same parts, EURO F148
Total sum in Currency 1 F125
Total sum in Currency 2 F140
Total sum in EURO F149
Sub-total Currency 1 of one supplier F141
Sub-total Currency 2 of one supplier F142
Sub-total EURO of one supplier F150
Sub-total Currency 1 of one supplier, result of aconversion
F163
Sub-total Currency 2 of one supplier, result of aconversion
F143
Sub-total EURO of one supplier, result of a conver-sion
F153
Total sum in Currency 1, result of a conversion F164
Total sum in Currency 2, result of a conversion F144
Total sum in EURO, result of a conversion F154
Flag output type for Only assembly / Only compo-nents
F702
Parts as component of an assembly F700
Quantity of the parts (as component of an assembly) F701
System Manual EPLAN 5.40
126
Designation of the data field F code
Generation data and time, display after setting ofparameters
F2000
Generation date, display after parameter setting F2001
Flag DD sorting (for DIN projects) F3000
Higher-level assignment at DIN: DD with "=" F3001
Location designation at DIN: DD with "+" F3002
DD at DIN: DD with "-" F3003
Higher-level assignment at DIN: DD without "=" F3004
Location designation at DIN: DD without "+" F3005
DD at DIN: DD without "-" F3006
DD sorting type F3007
Graphics macro (in upper-case characters!) F3010
2.3.8.5 Outputting Lists (Parts Management): F codes for output settings
Designation of the data field F code
EURO as source currency for the conversion F3011
Currency 2 as source currency for the conversion F3012
2.3.9 Standard Labeling
In order to output labeling data you require form files in which the elements to be out-put are positioned. The form files 5154*.FRM are used for standard labeling. The possi-ble F codes for these form files are divided into the following subgroups:
• Devices
• Terminals
• Terminal strips
• PLC
• Cables
• Conductors
• Wirings.
Creating Print Forms
127
2.3.9.1 Standard labeling: Devices
Designation of the data field F code
Higher-level assignment F101
Location designation F102
Designation F103
Page (completely with HLA and LOD)
F3
Path F5
Function text at the component F106
Function text in the path F107
Engraving data F108
Mounting location F109
Symbol name F104
2.3.9.2 Standard labeling: Terminals
Designation of the data field F code
Higher-level assignment F101
Location designation F102
Strip designation F103
Terminal number F110
Page (completely with HLA and LOD)
F3
Path F5
2.3.9.3 Standard labeling: Terminal strips
Designation of the data field F code
Higher-level assignment F101
Location designation F102
Strip designation F103
Page (completely with HLA and LOD)
F3
Path F5
System Manual EPLAN 5.40
128
2.3.9.4 Standard labeling: PLC
Designation of the data field F code
Higher-level assignment F101
Location designation F102
Designation F103
I/O designation, F112
Function text F106
Page (completely with HLA and LOD)
F3
Path F5
2.3.9.5 Standard labeling: Cables
Designation of the data field F code
Cable designation F204
Higher-level assignment F101
Location designation F102
Designation F103
Target higher-level assignment F201
Target location designation F202
Target designation F203
Page (completely with HLA and LOD)
F3
Path F5
2.3.9.6 Standard labeling: Conductors
Designation of the data field F code
Cable designation F204
Conductor designation F210
Higher-level assignment F101
Location designation F102
Designation F103
Creating Print Forms
129
Target higher-level assignment F201
Target location designation F202
Target designation F203
Page (completely with HLA and LOD)
F3
Path F5
2.3.9.7 Standard labeling: Wirings
Designation of the data field F code
Higher-level assignment F101
Location designation F102
Designation F103
Target higher-level assignment F201
Target location designation F202
Target designation F203
Page (completely with HLA and LOD)
F3
Path F5
Target page(completely with HLA and LOD)
F13
Target path F15
Wire gauge in mm² F215
Conductor color F216
Conductor length F217
System Manual EPLAN 5.40
130
2.3.10 Phoenix Mark Labeling
In order to output labeling data you require form files in which the elements to be out-put are positioned. The form files PHOE*.FRM are used for the Phoenix Mark labeling.The possible F codes for these form files are divided into the following subgroups:
• Devices
• Terminals
• PLC
• Cables
• Conductors
2.3.10.1 Phoenix Mark labeling: Devices
Designation of the data field F code
Higher-level assignment F101
Location designation F102
Designation F103
Page (completely with HLA and LOD)
F3
Path F5
Function text F106
Engraving data F107
2.3.10.2 Phoenix Mark labeling: Terminals
Designation of the data field F code
Higher-level assignment F101
Location designation F102
Strip designation F103
Terminal number F110
Page(completely with HLA and LOD)
F3
Path F5
Creating Print Forms
131
2.3.10.3 Phoenix Mark labeling: PLC
Designation of the data field F code
Higher-level assignment F101
Location designation F102
Designation F103
I/O designation, F112
Function text F106
Page(completely with HLA and LOD)
F3
Path F5
2.3.10.4 Phoenix Mark labeling: Cables
Designation of the data field F code
Cable designation F204
Conductor designation F210
Higher-level assignment F101
Location designation F102
Designation F103
Target higher-level assignment F201
Target location designation F202
Target designation F203
Page (completely with HLA and LOD)
F3
Path F5
2.3.10.5 Phoenix Mark labeling: Conductors
Designation of the data field F code
Higher-level assignment F101
Location designation F102
Designation F103
Target higher-level assignment F201
System Manual EPLAN 5.40
132
Designation of the data field F code
Target location designation F202
Target designation F203
Page(completely with HLA and LOD)
F3
Target-page designation (completely with HLA and LOD)
F13
Target path F15
Wire gauge F215
Conductor color F216
Conductor length F217
Import / Export Identifiers (Parts Management)
133
3 Import / Export Identifiers (PartsManagement)
The parts database is subdivided as follows:
Type Designation
1 Components3 Housings5 Cables7 Assemblies16 Manufacturers/Suppliers18 Customers
The master data fields are subdivided into the following groups:
• General data
• Prices• Supplementary data (depending on the part type)• Technical data (depending on the part type)
• Elements (assembly only).
General data
Designation of the data field ID
Product group 266 *
Part number 101
Type designation 102
Order number 207
Designation 1 204
Designation 2 205
Designation 3 206
Manufacturer short name: 200
Manufacturer long name 201
Supplier short name: 202
Supplier long name 203
Remark 1 212
Remark 2 265
System Manual EPLAN 5.40
134
* The product group can assume the following values:
Designation ValueGeneral 0Relays, contactors 1Terminals 2Connector 3Converters 4Protective devices 5Valves, semiconductors 6Signaling devices 7Motors 8Measuring devices, test devices 9Resistors 10Switches, selectors 11Transformers 12Modulators 13Electr. operated mechanical devices 14Special components 15Miscellaneous 16Capacitors 17Digital elements 18Generators, power supply units 19Inductors 20Amplifiers, controllers 21Power switchgear 22Terminators, filters 23Transmission paths 24
Prices
Designation of the data field ID
Price unit 210
Quantity/packaging 264
Unit of quantity 211
Purchase price/unit, Currency 1 267
Purchase price/unit, EURO 324
Purchase price/unit, Currency 2 321
Purchase price/packaging, Currency 1 208
Purchase price/packaging, EURO 323
Purchase price/packaging, Currency 2 320
Import / Export Identifiers (Parts Management)
135
Designation of the data field ID
Selling price, Currency 1 209
Selling price, EURO 325
Selling price, Currency 2 322
Price updating (values: 0=No, 1=Yes) 218
Supplementary data of components/assemblies
Designation of the data field ID
Group number 213
Identifier 215
Part classification 221
Type of part 222
Graphics macro 214
Transfer identifier 261 *
Electrical characteristics(Character for line feed: | )
219
Connection designations (Character for line feed: | )
220
Symbol file 216
Symbol number 217
* The transfer identifier can assume the following values:
Designation ValueOnly DD 48X = Width 49Y = Height 50X = Width and Y = Height 51X = Height and Y = Width 52x and y to be prompted 53X = Depth 54X = Width and Y = Depth 55X = Height and Y = Width 56X = Depth and Y = Width 57X = Depth and Y = Height 58
System Manual EPLAN 5.40
136
Supplementary data of housings
Designation of the data field ID
Group number 213
Identifier 215
Part classification 221
Type of part 222
Graphics macro 214
Transfer identifier 261 *
* The transfer identifier can assume the following values:
Designation ValueOnly DD 48X = Width 49Y = Height 50X = Width and Y = Height 51X = Height and Y = Width 52x and y to be prompted 53X = Depth 54X = Width and Y = Depth 55X = Height and Y = Width 56X = Depth and Y = Width 57X = Depth and Y = Height 58
Supplementary data of cables
Designation of the data field ID
Group number 213
Identifier 215
Part classification 221
Type of part 222
Technical data of components/assemblies
Designation of the data field ID
Voltage [V] 223248
Current [A] 224
Power [kW] 225
Import / Export Identifiers (Parts Management)
137
Designation of the data field ID
Weight [kg] 228247
Holding power [mVA] 226
Power dissipation [mVA] 227
Trigger current [mA] 230
Connection cross-section [mm²] 229
Width [mm] 231236
Height [mm] 232237
Depth [mm] 233238
Mounting clearance width [mm] 262
Mounting clearance height [mm] 263
Required space [dm²] 235
Mounting location 234 *
* The mounting location can assume the following values:
Designation ValueMounting panel 49Pivoting frame 50Door 51Side section 52Top cover 53Not defined 54
Technical data of housings
Designation of the data field ID
Weight [kg] 228247
Width [mm] 231236
Height [mm] 232237
Depth [mm] 233238
Usable width (panel) [mm] 239
Usable height (panel) [mm] 240
System Manual EPLAN 5.40
138
Designation of the data field ID
Maximum mounting depth (panel) [mm] 241
Mounting space (panel) [dm²] 242
Usable width (door) [mm] 243
Usable height (door) [mm] 244
Maximum mounting depth (door) [mm] 245
Mounting space (door) [dm²] 246
Technical data of cables
Designation of the data field ID
Weight [kg] 228247
Cable type 252
No. of conductors 249
Conductor cross-section [mm²] 251
Maximum voltage [V] 223248
External diameter [mm] 250
Minimum bending radius [mm] 253
Shielding (values: 0=No, 1=Yes) 254
PE conductor (values: 0=No, 1=Yes) 255
N conductor (values: 0=No, 1=Yes) 256
Assembly elements
Designation of the data field ID
Type * 270-278
Part number 280-288
Quantity 290-298
Manufacturer (short name) 300-308
Type designation 310-318
Import / Export Identifiers (Parts Management)
139
* The type can assume the following values:
Designation ValueComponent 1Housings 3Cables 5
Manufacturer, supplier, and customer data
Designation of the data field ID
Short name 101
Long name 401
Title 402
Name 1 403
Name 2 404
Name 3 405
Street 406
Zip code (city) 408
City 409
Alternative zip code 415
P.O. Box 407
State 410
Phone 413
Fax 414
E-mail address 416
Customer No. 411
Info 412
System Manual EPLAN 5.40
140
4 Special Settings
In this chapter you learn how to:
• Edit the EPLAN initialization file
• Use the call-up parameters in EPLAN.
4.1 Editing the EPLAN Initialization File
Under Windows, initialization files contain information that defines the environment ofan application. All applications can access this information so that they can be tailoredto the user’s specific requirements and desires. These files are in ASCII format and canbe edited with any editor. Wherever possible, avoid special language characters such asumlauts, as these are often misinterpreted.
From version 5.30 on, there is only one initialization file for EPLAN, namelyEPLFONT.INI. It is to be found in the directory \EPLAN4\O\<customer_code>.
Since EPLAN 5.40 has been developed exclusively for the Windows 2000 and Win-dows NT 4.0 operating systems, the registry has been used to save information. There-fore there is no EPLAN5.INI as from version 5.30.
If you are using the MRP-system PPS for the parts management, only the followingentries are used in the [Init] section:
szDBExeFile=J:\PMS_D\FOXW2600.ESLszDBWindowTitle=Wiechers & Partner PMS02
If you are using a previous version of EPLAN or are working with PMS inparallel, you may not delete EPLAN5.INI since it is still required for theprevious version. For further information on the individual sections pleaserefer to the online documentation of the previous version in the topic sec-tion under "Overview of EPLAN.INI and KEYS.DAT".
Do not edit the registry file! Incorrect modifications can endanger the sta-bility of the operating system.
Special Settings
141
4.1.1 Format of the EPLFONT.INI File
EPLFONT.INI (to be found in the EPLAN4\O\<customer_code> directory) contains as-signments of characters of the ASCII character set to characters of the ANSI characterset. The sections are designated with the numbers for the character set table, for exam-ple 437 for the German-speaking countries (with umlauts) and 850 for the Slavic-speaking countries.
EPLFONT.INI does not have to be edited!
4.2 EPLAN Call-up Parameters
You can also call the individual program modules explicitly from the MS DOS inputcommand, from another console or via the Windows Run... command (Start / Run...).This allows you to activate certain program parts faster than would be possible fromEPLAN. You can also automate the execution of functions by creating batch files withthe call-up parameters.
The EPL6000.EXE command is used to launch EPLAN. During the input you have toconsider the path in which the EXE file was stored during the installation. The commandand parameter are separated by a blank during input. You can also enter several pa-rameters that are separated by a blank. Normally you can use the parameters in any or-der.
The following entry in the Run command in Windows will start EPLAN andlaunch the online help on the subject "Call-up parameters":<Drive character>:\EPLAN4\540\EPL6000.EXE_/H
Note:The underline in the example shows where a blank must be set during in-put.
Further modules that exist in addition to the main module are only existentas independent EXE files for reasons of compatibility with the existingbatch files. Additional modules are invoked via EPL6000.EXE /$EPL6xxx.Only this syntax should be used in new batch files. In the section "Main Module (EPL6000.EXE)" you will find additionalinformation on the new main module parameter /$EPL6xxx and on furtherimportant parameters (e.g. /P<Project>).
The following list gives all modules, for which the associated call-up parameters arespecified in the subsequent sections. Please also note the "Information on Notation"atthe end of this chapter.
System Manual EPLAN 5.40
142
• Main module (EPL6000.EXE)
• Graphics editing
• Contact/potential cross-references
• Contactor selection
• External programs
• Data backup
• Generating the table of contents
• Numbering connections
• Reorganizing a page database
• Data exchange EXF->EPLAN
• Data exchange EPLAN->EXF
• Compressing a project
• Data exchange DXF->EPLAN
• Automatic revision
• PLC cross-reference generation
• Message management
• Converting a bill of materials
• Automatic evaluation
• Parameter management
• Parts management
• Labeling module PHOENIX Mark
• Outputting lists.
Special Settings
143
4.2.1 Main Module (EPL6000.EXE)
Parameters Description
/$EPL6xxx If EPLAN immediately invokes the module xxx after thestart, /$EPL6001 will for example start the graphics editingmodule immediately after the page selection. Possible sub-sequent parameters are transferred to this module.
In contrast to EPLAN 5.20, the main moduledesignation must be put ahead when the mod-ules are called up in EPLAN 5.40!
You wish to call up the potential/contactcross-reference run module (EPL6004) via theMS-DOS input command:
EPL6000.EXE_/$EPL6004
Note: In this example the underline is used to makeclear where a blank is to be set.
If various modules (EPL6039, EPL6041,EPL6053, EPL6054, EPL6056, EPL6138) arelaunched with an external call, EPLAN will beterminated after the parameters have beenprocessed as if these modules were startedwith /AUTO.
/#<command ID> Enters the specified ID in the list of commands to be carriedout.
/AUTO Terminates EPLAN after all commands have been carriedout.
/H or /? Activates the EPLAN help function on the "Call-up pa-rameters" topic.
/L<Language identi-fier>
Starts with the specified language.
/P<Project> or/p<Project>
Calls up the specified project. The project specification isrelative to the set project path. If this parameter is not speci-fied the project that was last edited is taken.
/QUIET Starts EPL6000 in a minimized window and suppressesmessages.
/T Sets the project-specific directories of the current project aspersonal directories.
/Z Compresses the project after it has been edited.
System Manual EPLAN 5.40
144
EPL6000 can also be started by a file association for an EPLAN project file(we advise EDOC_PRJ.CUM).
For example, the following process for the file type CUM can be definedwith the file manager:
Call-up for this process:L:\EPLAN4\540\Epl6000.EXE "%1" /T /$EPL6001
A double-click on a CUM file in an EPLAN project launches EPLAN, setsthis project as the current one, sets the project-specific directories of thisproject as current directories, and opens graphics editing. A compressedproject will be extracted.
4.2.2 Call-up Parameters for the Graphics Editing Module
This module is called up via the main module by using the parameter /$6001.
Parameters Description Notes
/CHOOSEPAGE:<ID>:<operator>:<value>
Select specific pages only useful with/OUTPUT
<X> Meaning
ID Page property
Operator Comparison operator
Value Comparison value(ID-dependent)
Possible values for <ID>, <operator>and <value> are listed below.
ID Meaning
0 Page number (includingHLA/LOD)
2 Last modification auto-matically
3 Last modification manu-ally
5 Higher-level assignment
6 Location designation
19 Last editor
8,1 Supplementary field page
Special Settings
145
ID Meaning
8,2 Supplementary fieldgroup
8,3 Supplementary field 1
...
8,9 Supplementary field 7
Operator Meaning
EQ equal
GE greater or equal
GT greater
LE less or equal
LT less than
Value Comparison value at ID
"Pagenumber"
0 For page number-ing type "DIN",page number alsowith HLA / LOD
"Date" 2; 3
"String" 5; 6; 8,1; 8,2; 8,3...8,9
If the comparison value is a date, it must beentered in the YYYYMMDD format to corre-spond to the internal EPLAN format. Also re-fer to the examples below.
/D:<outputdirectory>
Output directory for illustrations (seeparameter /OUTPUT:TIF).
/F<DD> Searches for the page with the speci-fied component.
sets /AUTO
/O:<"Printer name"> Sends GDI output to the specifiedprinter.
The printer name should be included in quota-tion marks, if the printer name contains blanksor forward slashes ("/")
/OUTPUT:<outputtype>
Outputs project pages All pages are out-put unless onlyspecific pages areselected with the/CHOOSEPAGE pa-rameter.
System Manual EPLAN 5.40
146
Output method Meaning
DXF DXF output
EXF EXF output. Here,the EPL_ASC.EXFfile is created in theproject directory.
EXFMACRO EXF macro output
GDI Print
HTML HTML output
INTER@VIEW INTER@VIEWoutput
TIF EPLAN pages areoutput as images inTIF format
/D:<output di-
rectory> is usedto specify the out-put directory. Oth-erwise the imagefiles are created inthe project direc-tory.
If individual pages have been selected for theEXF, HTML or. INTER@VIEW output, theproject header is always included in the out-put.
/S<Page name> Starts graphics editing of the specifiedpage.
Sets /AUTO
/X<path> Searches for the specified path Only valid if /S isindicated, sets/AUTO
/Y<position> Searches for the specified position Only valid if /S isindicated, sets/AUTO
The first six examples should help clarify the various possibilities for the /CHOOSEPAGEparameter:
Special Settings
147
/CHOOSEPAGE:0:GT:20
Selects all pages, that have a page number exceeding 20 (page numberingtype: Serial numbering).
/CHOOSEPAGE:0:GT:=Hla1+Lod1/1
Selects all pages that have a page number which is greater than=Hla1+Lod1/1 (page numbering type: DIN).
/CHOOSEPAGE:2:GE:20000401
Selects all pages that have been modified after and on April 1st, 2000.
/CHOOSEPAGE:3:GT:20000401
Selects all pages whose manual modification data shows a modificationmade after April 1st, 2000.
/CHOOSEPAGE:5:EQ:HLA1
Selects all pages with the higher-level assignment "HLA1".
/CHOOSEPAGE:8,9:EQ:ClipSelect
Selects all pages containing the string "ClipSelect"in the 9th (and last) sup-plementary field.
The next two examples show what a complete entry for outputting EPLAN projectpages would look like. The underline character again represents a blank in these exam-ples:
C:\EPLAN4\540\EPL6000.EXE_/$EPL6001_/OUTPUT:GDI_/CHOOSEPAGE:0:EQ:6_/AUTO
Print output of page 6 of the current project to the Windows default printer.
C:\EPLAN4\540\EPL6000.EXE_/$EPL6001_/OUTPUT:TIF_/CHOOSEPAGE:0:EQ:6_/D:C:\Grafik_/AUTO
Output of page 6 of the current project as TIF image file to the C:\Grafikdirectory.
Notes:
• To suppress the call-up of the output dialog boxes during the output (e.g. a directoryselection during DXF output), you must add the /Auto parameter at the end of thecommand line.
• For an automated output of EPLAN project pages with the above-mentioned outputparameters the ’Display page dialog box when starting the graphics’ check box,which is to be found in the personal working parameters must be deactivated.
System Manual EPLAN 5.40
148
4.2.3 Call-up Parameters for the Contact/Potential Cross-referencesModule
This module is called up via the main module by using the parameter /$6004.
Parameters Description Notes
/#<switch function> Switchfunction
Meaning
11 Creates contact cross-references and a DD list
12 Creates potential cross-references.
13 Creates contact and po-tential cross-references.
14 Creates a wiring list.
16 Creates a list of specialcomponents.
18 Deletes the database.
21 Overview and edition ofcontact cross-referencesand normal components.
22 Overview and edition ofpotential cross-references.
23 Wiring overview.
41 Printing of contact cross-references.
42 Printing of potentialcross-references.
43 Printing of the wiring list.
/AUTO<switchfunction>
Execution of prompt If the /AUTO para-meter is not used,a prompt for con-firmation is dis-played.
Switchfunction
Meaning
<without> No prompt for confirma-tion
Special Settings
149
Switchfunction
Meaning
1 Prompt for confirmationStep 1
2 Prompt for confirmationStep 2
%P Refers to the currently set project.
4.2.4 Call-up Parameters for the Contactor Selection Module
This module is called up via the main module by using the parameter /$6008.
Parameters Description
/#<switch function> Switchfunction
Meaning
101 Compares the current contactor specificationfile with the transferred one(see parameter /D<file_name>)
102 Shows the comparison result (see switch func-tion /#101)
/AUTO No prompt for confirmation.
/D<file_name> Name of the contactor specification file to be compared(only with/AUTO)
4.2.5 Call-up Parameter for the External Programs Module
This module is called up via the main module by using the parameter /$6009.
Parameters Description
/M<file name> Name of the ETP file to be opened
System Manual EPLAN 5.40
150
4.2.6 Call-up Parameters for the Data Backup Module
This module is called up via the main module by using the parameter /$6013.
Parameters Description Notes
/#<switch function> Switchfunction
Meaning
11 Saves the project.
12 Saves macros.
13 Saves normal master files.
14 Saves stock and part files.
15 Saves forms.
16 Saves personal and work-station files
17 Compresses the project.
21 Reloads a project.
22 Reloads macros.
23 Reloads standard masterfiles.
24 Reloads stock and partfiles.
25 Reloads forms.
26 Reloads personal andworkstation files.
27 Decompresses projects.
/AUTO<switchfunction>
Execution of prompt If the /AUTO para-meter is not used, aprompt for confir-mation is displayed.
Switchfunction
Meaning
<without> No prompt for confirm.
1 Prompt for confirmationStep 1
2 Prompt for confirmationStep 2
%P Refers to the currently set project.
Special Settings
151
4.2.7 Call-up Parameter for the Generate Table of Contents Module
This module is called up via the main module by using the parameter /$6023.
Parameters Description Notes
/#<switch function> Switchfunction
Meaning /AUTO must bespecified
1 Generate
4.2.8 Call-up Parameter for the Wire Numbering Module
This module is called up via the main module by using the parameter /$6035.
Parameters Description
/AUTO Activates the numbering.
4.2.9 Call-up Parameter for the Reorganize Page Database Module
This module is called up via the main module by using the parameter /$6039.
If EPLAN is started with this parameter, it will be terminated after the pa-rameters have been processed as if this module had been started with/AUTO.
Parameters Description
/#<switch function> Switchfunction
Meaning
107 Creates the database for higher-level assign-ments.
108 Creates the database for location designations
109 Edits page data.
112 Creates a project page database.
113 Deletes a project page database.
System Manual EPLAN 5.40
152
4.2.10 Call-up Parameters for the EXF->EPLAN Data ExchangeModule
This module is called up via the main module by using the parameter /$6053.
If EPLAN is started with this parameter, it will be terminated after the pa-rameters have been processed as if this module had been started with/AUTO.
Parameters Description Notes
/#<switch function> Switchfunction
Meaning
1 Converts EXF to EPLAN.
10 Converts plot frames toEPLAN.
125 Specifies the control filefor the conversion.
129 Converts symbols toEPLAN.
Any Same as for switch func-tion 1
/@<control filename>
Determines the control file name.
/ADD Adds entries to the existing page.
/D<file_name> Specifies the EXF file. If /D is totallymissing, the cur-rent project withpath andEPL_ASC.EXF istaken as EXF fileby default.
Text Meaning
Empty Current project with path+ EPL_ASC.EXF
Withoutdrive andpath
Current project with path+ <text>
Withoutfile type
Extended with *.EXF
125 Specifies the control filefor the conversion.
Special Settings
153
Parameters Description Notes
/M<x> Specifies the panel scale. <X> is an integer
/RIT Creates a macro from a transferred BNFfile.
/TEST:1 Checks for duplicate insertion points. Message is sup-pressed at themoment.
/X<source_file_name>
Determines the source file name.
/Y<target_file_name>
Determines the target file name.
AUTO<switchfunction>
Switchfunction
Meaning
0 or empty Deactivates all interac-tions.
1 Only the prompt ’Over-write Yes/No’ must be an-swered.
SUB<text> This switch activates the replacementfunction. This means: If the þ1 - þ50placeholders are used in a macro, theplaceholder is replaced with the corre-sponding entry during the generationrun (see control code 254).
Menu item ’Import/EXF file -> project’: /#1_/D"file name"_/AUTO
Note:In this example, the underline is used to make clear where a blank is to beset.
Menu item ’Import/Control file’:/#125_/@"control file name"_/AUTO
Menu item ’Import/Plot frame’:/#103_/X"source file name"_/Y"target file name"_/AUTO
Menu item ’Import/Symbol files’:/#129_/Y"source file name"_/Y"target file name"
Create a macro from a transferred BNF file:/Rit_/D"file name"_/AUTO
System Manual EPLAN 5.40
154
4.2.11 Call-up Parameters for the EPLAN->EXF Data ExchangeModule
This module is called up via the main module by using the parameter /$6054.
If EPLAN is started with this parameter, it will be terminated after the pa-rameters have been processed as if this module had been started with/AUTO.
Parameters Description
/#<switch function> Switchfunction
Meaning
103 Exports plot frames.
105 Converts EPLAN to EXF.
125 Exports control file.
129 Exports symbol file.
340 Exports terminal diagram form.
341 Exports interconnect diagram form.
342 Exports terminal-strip overview form.
343 Exports cable overview form.
344 Exports terminal-connection diagram form.
345 Exports bill of materials form.
346 Exports device list form.
347 Exports terminal bill of materials form.
349 Exports control-panel layout form.
350 Exports page overview form.
351 Exports title page/cover sheet EDOC form.
352 Exports PLC overview page form.
Other Same as for 105
Parameters Description
/@<control filename>
Determines the control file name.
/A Evaluates the SEITE.DAT file (this file contains the pagesselected in graphics editing).
/D<file_name> Determines the EXF file.
/M:n-m Path parameters from (n) to (m)
Special Settings
155
Parameters Description
/MACRO Outputs page as EXF macros (file name from the Openpage dialog box, Directory / name filed under Macro on thePage data 2 tab.)
/SDA This switch suppresses the output of page entries to theASCII file. Only the page header data will be written.
/ST<no> This switch allows to output data to the ASCII file of a spe-cific page type. The page type is written directly behind the/ST characters.
/X<source_file_name>
Determines the source file name.
/Y<target_file_name>
Determines the target file name.
/Z Writes the symbol designation to an ASCII file.
AUTO<switchfunction>
Switchfunction
Meaning
0 or empty Switch off all interactions.
1 Only the prompt ’Overwrite Yes/No’ must beanswered.
Menu item ’Export/Plot frame’: /#103_/X"source file name"_/Y"target file name"_/AUTO
Note:In this example, the underline is used to make clear where a blank is to beset.
Menu item ’Export/Project’: /#105_/D"file name"_/AUTO1_/AUTO2
Menu item ’Export/Control file’: /#125_/@"control file name"_/AUTO
Menu item ’Export/Symbol files’:/#129_/X"source file name"_/Y"target file name"
Menu item ’Export/Forms’:/#340-352_/X"source file name"_/Y"target file name"_/AUTO
System Manual EPLAN 5.40
156
4.2.12 Call-up Parameters for the Compress Project Module
This module is called up via the main module by using the parameter /$6056.
If EPLAN is started with this parameter, it will be terminated after the pa-rameters have been processed as if this modules had been started with/AUTO.
Parameters Description
/A or /Auto Set AUTO flag, suppress document
/NDV Suppress document without setting AUTO flag
4.2.13 Call-up Parameters for the DXF->EPLAN Data ExchangeModule
This module is called up via the main module by using the parameter /$6065.
The use of the following parameters requires the specification of /AUTO:
Parameters Description
/CTR<value> Integer
/D<file_name> ASCII file name
/E<program name> Program name
/F<file_name> DXF file name
/NODEL ASCII file is not to be deleted.
/SC<value> Scaling factor as floating-point value
4.2.14 Call-up Parameters for the Automatic Revision Module
This module is called up via the main module by using the parameter /$6068.
The use of the following parameters requires the specification of /AUTO:
Parameters Description Notes
/#100 Corrects incorrect page header data.
/#:<switchfunction>
Switchfunction
Meaning
20 Display / print report file
24 Exchanges terminal symboltype (terminal identifier).
Special Settings
157
Switchfunction
Meaning
25 Replaces terminal checkand sort identifiers.
26 Exchanges cable genera-tion and external outputposition directions.
27 Exchanges line width ofthe black boxes.
28 Exchanges terminal con-nection direction for sym-bol variants 2 and 3.
29 Change terminals to poten-tial terminals, device endterminals to PLCs, or po-tentials.
31 Changes symbol types.
34 Recreates mounting loca-tion database on the basisof schematic data.
36 Deletes overlapping textson control panel pages.
38 Graphics objects obtainimproved format
40 Cable definitions obtainimproved format.
50 Deletes all system IDs oronly multiply assignedsystem Ids.
60 Changes graphics symbolnumbers at black boxes ofType -10 to type -13.
90 Revises line type.
271 Changes pen number ofconnection line.
/D Deletes search database before thesearch run is started.
/PROPATH Specify the log path under which thelog file is to be stored.
Only in combina-tion with /#100
System Manual EPLAN 5.40
158
Parameters Description Notes
/Q Program execution without display ofdialog boxes.
/S:<text> Search term
/SHOWERR Shows errors. Only in combina-tion with /#100
/V<text> Move function in XY direction Expected as fol-lows:/VX:number1Y:number2
4.2.15 Call-up Parameters for the PLC Cross-reference Generation
This module is called up via the main module by using the parameter /$6083.
Parameters Description
/#<switch function>
or
Switchfunction
Meaning
/N#<switch function> 260 Uses connection numbers at terminals.
or 270 Creates ASCII files.
-N#<switch function> 310 Generates PLC cross-reference.
320 Deletes QVW files.
444 Shows messages of the activated runs.
/D:<output file> Output file for PLC data.
/QUIET Suppresses the message output to the window.
4.2.16 Call-up Parameters for the Message Management Module
This module is called up via the main module by using the parameter /$6108.
Parameters Description
/#<switch function> Switchfunction
Meaning
11 Printing of the messages according to numbers
12 Printing of the messages according to pages
13 Printing of the messages according to devices
Special Settings
159
Switchfunction
Meaning
14 Printing of the overview
20 Lists project messages.
30 Compresses the message database.
40 View systems error messages.
50 Invokes parameter program for the messagemanagement.
4.2.17 Call-up Parameters for the Realize Bill of Materials Module
This module is called up via the main module by using the parameter /$6119.
Parameters Description
/#121 Transfers the bill of materials data from an ASCII file (STKLEPL.ASC) to the schematic.
/IN or /#102 Transfers the bill of materials data from an ASCII file (STKLEPX.ASC) to the schematic.
/M1 DDs without part information will be taken, too.
/OUT or /#100 Writes the bill-of-materials data into an ASCII file(STKLEPL.ASC).
4.2.18 Call-up Parameters for the Automatic Evaluation Module
This module is called up via the main module by using the parameter /$6125.
Parameters Description
/AUTO<x> Starts automatic run of the x type.
x Meaning
1 Suppress messages
2 Prompt: Delete SYSTEM.ERR file?
3 Display SYSTEM.ERR file after the runs.
/H or /? Shows all command line parameters of this module.
/L<switch function> Specifies selection files.
System Manual EPLAN 5.40
160
Switchfunction
Meaning
1 In current project
2 In projects which have to be evaluated
/M<x> Starts runs with the x value.
x Meaning
1 Call-up with menu
2 Select evaluation runs
3 Edit runs
4 Current project
5 Project directory
6 Project selection
7 Project with subdirectories
8 Project drive
4.2.19 Call-up Parameters for the Parameter Management Module
This module is called up via the main module by using the parameter /$6136.
Parameters Description Notes
/AUTO Document start is suppressed. If theproject was created with the Profes-sional version and has not been editedwith a COMPACT version yet, someparameters will be overwritten withCOMPACT-specific parameters.
/NO_ASK Suppresses the prompt whether pa-rameters are to be overwritten.
/AUTO is a precon-dition
4.2.20 Call-up Parameters for the Parts Management Module
This module is called up via the main module by using the parameter /$6138.
If EPLAN is started with this parameter, it will be terminated after the pa-rameters have been processed as if this modules had been started with/AUTO.
Special Settings
161
The call-up parameters of version 5.20 are still supported. However, as from version5.20, a separating colon was introduced for some parameters. For example, instead ofS:<source file name> you can still enter S<source file name>.
Parameters Description
/#<switch function> Switchfunction
Meaning
321 Imports EPPS parts data.
323 Imports Dbase parts data.
324 Imports parts data in the general ASCII for-mat.
325 Imports Parts-Lib parts data.
326 Imports parts data in EPLAN ASCII format.
331 Exports parts data.
500 Exports a part number.
501 Exports a manufacturer / supplier record.
502 Exports a customer record.
/APPEND Attaches the export data at the end of the target file.If this parameter is not specified, a new target file is createdeach time.
/ANSI This parameter determines the format of the source/targetfile. If this parameter is not specified the OEM format is set.
/ART:<part number> Part number whose data are to be exported.
/ART:<manufacturer/supplier shortname>
Manufacturer/supplier short name whose data are to be ex-ported.
/ART:<manufacturer/supplier shortname>
Manufacturer/supplier short name whose data are to be ex-ported.
/C:<comparisonfield identifier>
This parameter determines which comparison field is to beused.If this parameter is not specified the part number is used ascomparison field.
<Comparisonfield identifier>
Comparison field
101 Part number /short name
102 Type designation
207 Order number
System Manual EPLAN 5.40
162
Parameters Description
/DECISYMBOL:<decimal separator>
Determines the decimal separator. During the import ofparts data a period (".") or a comma (",") can be used asdecimal separator.
/D:<target filename>
Determines the target file name. A file name with full pathindication is required.In case of "DBase import and "General ASCII import" thisindication is not necessary. If the target file is specified forthe above-mentioned import functions, the part numbers arenot written to the parts database but to this file.
/F:<control filename>
Determines the control file name. A file name with full pathindication is required.
/F:<assignmentfile name>
Determines the control file name for the "Dbase import" Afile name with full path indication is required.
/LANGUAGE:<Partlanguage identi-fier>
Determines the parts database language identifier.
/NEWONLY If this call-up parameter is specified for the import, onlynew parts data will be added.
/PROG:<programname>
A program name with full path indication is required.If an external program is specified during exporting, thisprogram is started immediately after the export function. Ifan external program is specified during importing, it isstarted before the import function.
/SEPTAB If this parameter is specified, field identifier and field con-tents are separated by a tabulator character instead of ablank.
/S:<source filename>
Specifies the source file name when parts data are imported.A file name with full path indication is required.For a "DBase import" a DBase file name is required,whereas for a "Parts Lib import" a Parts Lib file name is re-quired. For the other import functions, an ASCII file namemust be used.
/SUBDIV:<ECADdesignation subdi-vider>
During the "Parts LiB import", this parameter is used tosubdivide the ECAD designation assigned to the EPLANdesignation 1
<ECADdesignationsubdivider>
Subdivision
1 into designation 1 / 2 / 3
2 into designation 1 / 2 / 3 and remark 1
Special Settings
163
Parameters Description
/T:<master datatype>
Specifies into which database type the data are to be writ-ten.If this parameter is not specified, the data will be written tothe component database unless another specification wasmade in the control file.
<masterdata type>
Database type
1 Components
3 Housings
5 Cables
7 Assemblies
16 Manufacturers/Suppliers
18 Customers
/UPDATE If this parameter is specified during the import, only exist-ing parts data will be updated.
Possible call-up parameters for the various import and export functions of the moduleare given below. The underline shows where a blank must be entered.
The call-up parameters are optional, i.e. the setting last used is taken if you do not spec-ify a call-up parameter during input.
Import EPPS 4.11:
EPL6000.EXE_/$EPL6138_/P<project name>_/#321_/S:<source file name> _/DECISYMBOL<decimal separator>_/UPDATE_/NEWONLY _/LANGUAGE:<part language identifier>
Import DBase:
EPL6000.EXE_/$EPL6138_/P<project name>_/#323_/S:<source file name>_/ANSI_/F:<assignment file name>_/T:<master data type> _/C:<comparison field identifier>_/DECISYMBOL<decimal separator> _UPDATE_/NEWONLY_/D:<target file name>_/LANGUAGE:<part language identifier>
Import ASCII general:EPL6000.EXE_/$EPL6138_/P<project name>_/#324_/S:<source file name>_/ANSI_/F:<control file name>_/T:<master data type> _/C:<comparison field identifier>_/DECISYMBOL<decimal separator> _UPDATE_/NEWONLY_/D:<target file name>_/LANGUAGE:<part language identifier>
System Manual EPLAN 5.40
164
Import Parts-Lib:
EPL6000.EXE_/$EPL6138_/P<project name>_/#325_/S:<source file name>_/ANSI_/F:<control file name>_/DECISYMBOL<decimal separator> _/UPDATE_/NEWONLY_/LANGUAGE:<part language identifier> _SUBDIV:<ECAD designation subdivider>
Import EPLAN ASCII format:
EPL6000.EXE_/$EPL6138_/P<project name>_/#326_/S:<source file name>_/UPDATE_/NEWONLY_/PROG:<program name> _/LANGUAGE:<part language identifier>
Export of parts data:
EPL6000.EXE_/$EPL6138_/P<project name>_/#331_/D:<target file name>_/ANSI _/SEPTAB_/PROG:<program name>_/LANGUAGE:<part language identifier>
Export of a part number:
EPL6000.EXE_/$EPL6138_/P<project name>_/#500_/D:<target file name>_/ANSI _/ART:<part number>_/LANGUAGE:<part language identifier>_/APPEND
Entering the /ART:<part number> call-up parameter is absolutely necessary for theexport of a part number. However, for the export of a manufacturer/supplier record(/#501) the /ART:<manufacturer/ supplier short name> parameter is required.Correspondingly, the /ART:<customer short name> parameter must be used for theexport of a customer record (/#502).
4.2.21 Call-up Parameters for the "PHOENIX Mark" Labeling Mod-ule
This module is called up via the main module by using the parameter /$6139.
Parameters Description Notes
/#<switch function> Switchfunction
Meaning
115 Terminals (with spareterminals)
Terminals are readfrom the terminaldiagram. Spareterminals are alsooutput to theASCII file.
201 Devices
202 Terminals (without spareterminals)
Terminals are readfrom the sche-matic.
203 PLC
Special Settings
165
Parameters Description Notes
204 Cables
205 Conductors
/AUTO No prompt for confirmation
/D<path> Output path
/OS Deactivates sorting
4.2.22 Call-up Parameters for the Lists Output Module
This module is called up via the main module by using the parameter /$6156.
The call-up parameters of version 5.20 are still supported. However, as from version5.20, a separating colon was introduced for some parameters. For example, instead ofF:<form name> it is still possible to enter F<form name>.
Parameters Description Notes
/#<switch function> Switchfunction
Meaning
21 Outputs bill of materialsto graphics.
232 Prints bill of materials.
233 Outputs purchase-orderlist to graphics.
234 Prints purchase-order list.
235 Outputs parts list tographics.
236 Prints parts list.
237 Outputs device list tographics.
/A:<type of partfilter>
Type of part for the filtering. The "*" wildcardis permitted.
/AE:<type of partfilter switch>
Type of type of part filtering.
Switch: Meaning
0 Only outputs elementsthat correspond to the fil-ter term <type of partfilter>.
System Manual EPLAN 5.40
166
Switch: Meaning
1 Outputs all elements ex-cept for the filter expres-sion <type of partfilter>
/ARTLG:<partlanguage identi-fier>
Language identifier of the parts data-base
/B:<assemblydisplay switch>
Specifies the type of assembly display.
Switch: Meaning
0 Only assembly – assem-bly elements are com-bined as assembly.
The list becomesshorter.
2 Only components -only components are out-put of which the assemblyconsists.
The list becomesmore detailed.
/CUSFROM:<fromcustomer>/CUSTO:<tocustomer>
Output is carried out from customershort name through customer shortname.
The "*" wildcardis permitted.
/D:<target filename>
The output is carried out to a targetfile. The file name must be specifiedwith the full path.
/F:<form name> Form name with file extension. Notethat the file extensions vary accordingto the list to be output.
Extensions Output
*.ART Print a parts list.
*.BST Print a purchase-order list.
*.FRM Output lists tographics.
*.STK Print a bill of mate-rials.
/FANL:<filter forHLA>
Higher-level assignment name for fil-tering (for DIN projects only).
The "*" wildcardis permitted.
/FBMK:<DDfilter> DD for the filtering. The "*" wildcardis permitted.
/FORT:<Filter forLOD>
Location designation name for filtering(for DIN projects only).
The "*" wildcardis permitted.
Special Settings
167
Parameters Description Notes
/FROM:<fromPart/order number>/TO:<toPart/order number>
Output is carried out from part numberor order number (depending on <type
of sorting>) through part number ororder number.
The "*" wildcardis permitted.
/G:<partclassification fil-ter>
Part classification for the filtering. The "*" wildcardis permitted.
/G:<partclassification fil-ter switch>
Type of part classification filtering.
Switch: Meaning
0 Only outputs elementsthat correspond to the fil-ter term <part classi-fication filter>.
1 Outputs all elements ex-cept for the filter expres-sion <part classifica-tion filter>
/L:<Form identi-fier>
The form can be found in the EPLANform directory \EPLAN\ <form iden-tifier>.
/NOKL Before the device list is output theschematic is read out again. Terminalsare not output.
/NOKB Before the device list is output theschematic is read out again. Cables arenot output.
/OUTPROJ:<outputproject>
Output project name.
/READALLPLAN Before the list is output the schematicis read out again. DDs without partnumber are output, too.
/READPLAN Before the list is output the schematicis read out again. However, only DDswith part number are output.
/SO:<type of sort-ing>
Specifies the sorting criteria for theoutput.
System Manual EPLAN 5.40
168
<Type of sort-ing>
Designation
0 None For the output ofparts lists, devicelists, and bill ofmaterials.
1 Part number For the output ofparts lists, pur-chase-order lists,and bill of materi-als.
2 Part number For the output ofpurchase-orderlists.
2 Supplier shortname:
For the output ofparts lists and billof materials.
3 Manufacturer shortname:
For the output ofbills of materials.
8 Mounting location For the output ofdevice lists andbills of materials.
10 DD For the output ofdevice lists andbill of materials;for none-DINprojects
10 HLA+LOD+DD For the output ofdevice lists andbill of materials;only for DIN proj-ects
11 HLA+DD+LOD For the output ofdevice lists andbill of materials;only for DIN proj-ects
12 LOC+HLA+DD For the output ofdevice lists andbill of materials;only for DIN proj-ects
Special Settings
169
<Type of sort-ing>
Designation
13 LOD+DD+HLA For the output ofdevice lists andbill of materials;only for DIN proj-ects
14 DD+HLA+LOD For the output ofdevice lists andbill of materials;only for DIN proj-ects
15 DD+LOD+HLA For the output ofdevice lists andbill of materials;only for DIN proj-ects
16 Order number For the output ofpurchase-orderlists.
/VD:<supplier list> List of supplier short names, separatedby commas. "*" is used to output allsuppliers.
/VDFROM:<fromManu-facturer/supplier/VDTO:<toManu-facturer/supplier>
Output is carried out from manufac-turer/supplier short name throughmanufacturer/supplier short name.
The "*" wildcardis permitted.
/XANL:<Switch forfiltering the HLA>
Type of filtering for the higher-levelassignment
Switch: Meaning
0 Only outputs elementsthat correspond to the fil-ter expression <switchfor filtering theHLA>
1 Outputs all elements ex-cept for the filter expres-sion <switch for fil-tering the HLA>
System Manual EPLAN 5.40
170
Parameters Description Notes
/XBMK:<DD filterswitch>
Type of DD filtering
Switch: Meaning
0 Only outputs elementsthat correspond to the fil-ter expression <DD fil-ter>.
1 Outputs all elements ex-cept for the filter expres-sion <DD filter>
/XORT:<switch forfiltering the LOD>
Type of filtering for the location desig-nation
Switch: Meaning
0 Only outputs elementsthat correspond to the fil-ter expression <switchfor filtering theLOD>
1 Outputs all elements ex-cept for the filter expres-sion <switch for fil-tering the LOD>
Possible call-up parameters for the various output functions of the module are givenbelow. The underline shows where a blank must be entered.
The call-up parameters are optional, i.e. the setting last used of the respective call-upparameter is taken if you do not specify a call-up parameter during input.
Outputting bills of materials as graphics:
EPL6000.EXE_/$EPL6156_/P<project name>_/#21_/F:<form name>_/FANL:<filter HLA>_/XANL:<switch for filtering the HLA>_/FORT:<filter LOD>_XORT:<switch for filtering the LOD>_/FBMK:<DD filter>_/XBMK:<DD filter switch> _/B:<assembly display switch> _/A:<type of part filter>_/AE:<type of part filter switch> _G:<function group filter>_GE:<function group filter switch> _/L:<form identifier>_SO:<type of sorting> _ARTLG:<part language identifier>_/READPLAN_/READALLPLAN
Printing bills of materials:
EPL6000.EXE_/$EPL6156_/P<project name>_/#232_/F:<form name> _/FANL:<filter HLA>_/XANL:<switch for filtering the HLA>_/FORT:<filter LOD>_XORT:<switch for filtering the LOD>_/FBMK:<DD filter>_/XBMK:<DD filter switch> _/B:<assembly display switch>
Special Settings
171
_/A:<type of part filter>_/AE:<type of part filter switch> _G:<function group filter>_GE:<function group filter switch> _/L:<form identifier>_SO:<type of sorting> _ARTLG:<part language identifier>_/READPLAN_/READALLPLAN _/D:<target file name>
Outputting purchase-order lists as graphics:
EPL6000.EXE_/$EPL6156_/P<project name>_/#233_/F:<form name> _/FANL:<filter HLA>_/XANL:<switch for filtering the HLA>_/FORT:<filter LOD>_XORT:<switch for filtering the LOD>_/FBMK:<DD filter>_/XBMK:<DD filter switch> _/B:<assembly display switch> _/A:<type of part filter>_/AE:<type of part filter switch> _G:<function group filter>_GE:<function group filter switch> _/L:<form identifier>_SO:<type of sorting> _ARTLG:<part language identifier>_/READPLAN_/READALLPLAN _/VD:<supplier list>_/FROM:<from part number/order number> _/TO:<to part number/order number>
Printing purchase-order lists:
EPL6000.EXE_/$EPL6156_/P<project name>_/#234_/F:<form name> _/FANL:<filter HLA>_/XANL:<switch for filtering the HLA>_/FORT:<filter LOD>_XORT:<switch for filtering the LOD>_/FBMK:<DD filter>_/XBMK:<DD filter switch> _/B:<assembly display switch> _/A:<type of part filter>_/AE:<type of part filter switch>_G:<function group filter>_GE:<function group filter switch> _/L:<form identifier>_SO:<type of sorting> _ARTLG:<part language identifier>_/READPLAN_/READALLPLAN _/VD:<supplier list>_/FROM:<from part number/order number> _/TO:<to part number/order number>_/D:<target file name>
Outputting device lists as graphics:
EPL6000.EXE_/$EPL6156_/P<project name>_/#237_/F:<form name> _/FANL:<filter HLA>_/XANL:<switch for filtering the HLA>_/FORT:<filter LOD>_XORT:<switch for filtering the LOD>_/FBMK:<DD filter>_/XBMK:<DD filter switch> _/B:<assembly display switch> _/A:<type of part filter>_/AE:<type of part filter switch>_G:<function group filter>_GE:<function group filter switch> _/L:<form identifier>_SO:<type of sorting> _ARTLG:<part language identifier>_/READPLAN_/READALLPLAN_/NOKL_/NOKB
Outputting a parts list as graphics:
EPL6000.EXE_/$EPL6156_/P<project name>_/#235_/F:<form name> _/L:<form identifier>_SO:<type of sorting> _ARTLG:<part language identifier> _/FROM:<from part number>_/TO:<to part number> _/VDFROM:<from manufacturer/supplier>_/VDTO:<from manufacturer/supplier> _/CUSFROM:<from customer>_/CUSTO:<to customer>_/OUTPROJ:<output project>
System Manual EPLAN 5.40
172
Printing a parts list:EPL6000.EXE_/$EPL6156_/P<project name>_/#236_/F:<form name> _/L:<form identifier>_SO:<type of sorting> _ARTLG:<part language identifier> _/FROM:<from part number>_/TO:<to part number> _/VDFROM:<from manufacturer/supplier>_/VDTO:<from manufacturer/supplier> _/CUSFROM:<from customer>_/CUSTO:<to customer>_/D:<target file name>
4.2.23 Information on Notation
The <project> style (angle brackets) is used when concrete values must be indicated, e.g.a project name.
The notation "/P<Projekt>" can be as follows when it is directly entered:
/Pfue/sym/dic_wupd.p
In this example, the underline is part of the project name and does not stand for a blank.When entering the project name it is not a must to enter ".p". Thus, the direct entry forthe above-mentioned example may be as follows:
/Pfue/sym/dic_wupd
Do not enter blanks between the switch (/P) and parameter value (<Proj-ect>), otherwise the module cannot start correctly!
Lists and Tables
173
5 Lists and Tables
This chapter contains an overview in tables of the following fields:
• Symbol types
• Identifiers• Special texts.
5.1 Symbol Type: Contacts and Coils
The symbol type can be changed in the symbol properties of the contacts and coils. Thisinfluences the cross-referencing property!
Contacts and coils (only single-path items permitted)
ID
Contact types:
Power NO contact 0
NO contact 1
NC contact 2
Power NC contact 4
Changeover contacts made up of three symbols:
NC change-over contact hook 11
Change-over contact center 12
NO change-over contact hook 13
Changeover contacts made up of two symbols:
NC change-over contact 14
NO change-over contact hook 15
Coils:
(Standard) 50
Symbol cross-reference(cross-reference for standard symbols)
ID
Main element made cross-referenceable 150
Secondary element made cross-referenceable 153
System Manual EPLAN 5.40
174
Pair cross-reference(cross-reference for contacts)
ID
Cross-reference under the symbol 151
Cross-reference next to the symbol 152
Cross-reference below the symbol, 90° vertical 154
Standard symbol type ID
Symbol without meaning, graphics element 254
Standard symbol, not cross-referenceable 255
5.2 Symbol Type: Terminals and Accessories
The symbol type of a terminal determines its maximum number of connections and itsability to form jumpers. Only symbol types between 100 and 255 are valid.
Terminal types (1) Connection Jumper ID
No specific type preselected 4 Bar 100
Feed-through terminal 2 None 101
Feed-through terminal 2 Bar 102
Feed-through terminal 3 None 103
Feed-through terminal 3 Bar 104
Feed-through terminal 4 None 105
Feed-through terminal 4 Bar 106
N feed-through terminal 2 Bar 107
N isolating terminal 1 Bar 108
N feed-through terminal 4 Bar 109
N isolating terminal (ground-fault monitor VDE0113)
4 2*N 110
PE isolating terminal(ground-fault monitor VDE0113)
4 2*PE 111
PE terminal/connector(connected via terminal housing)
2 None 112
PE terminal 4 None 113
PE for actuator terminal 2 None 114
Lists and Tables
175
Terminal types (1) Connection Jumper ID
N for actuator terminal 2 Bar 115
~ for actuator terminal 2 Bar 116
+ for actuator terminal 2 Bar 117
- for actuator terminal 2 Bar 118
Terminal/Connector adapter 2 None 119
Terminal/Connector adapter terminal connec-tion side
2 None 120
Terminal/Connector adapter connector connec-tion side
2 None 121
Two-wire initiator, actuator terminal1 connection in 2 directions, 1 connection jum-pered
2 None 122
Two-wire initiator, actuator terminal1 connection in 2 directions, 1 connection jum-pered, 1 connection PE
3 None 123
Two-wire initiator, actuator terminal1 connection in 2 directions, 1 connection jum-pered, 1 connection PE, 1 connection N
2(4) None 124
Three-wire initiator, actuator terminal1 connection in 2 directions, 2 connections jum-pered
2(3) None 125
Three-wire initiator, actuator terminal1 connection in 2 directions, 2 conn. jumpered,1 connection PE
2(4) None 126
Three-wire initiator, actuator terminal1 connection in 2 directions, 2 conn. jumpered1 connection PE, 1 connection N
2(5) None 127
Isolating terminal 2 None 129
LED terminal 2 None 130
Fused terminal 2 None 131
Diode components / multiple-path terminal(Weidmüller)
2 None 132
Connector pin 2 None 133
Connector socket 2 None 134
Connector socket/pin 2 None 135
Wrap pin 2 None 136
System Manual EPLAN 5.40
176
Custom terminals ID
Follower terminal for several targets 148
Terminals which the terminal diagram will not evaluate 149
Can only be used within the terminal bill of materials:
Manufacturer’s terminals that cannot be assigned. 255
Terminal accessories ID
Can only be used for the terminal bill of materials:
Mounting rail 410
End angle 420
Terminal marker + terminal-marker mounting 510
Other labels 520
Group labels 530
Cross-connections 610
Rails 630
Covers 710
Cover plates 720
Partitions 730
Connector housings 810
Connector accessories 820
Tool 910
Test accessories 920
5.3 Identifying Letters
This section deals with:
• Identifiers for identifying the device type
• Identifiers for identifying general functions.
Lists and Tables
177
5.3.1 Identifiers for Identifying the Device Type
DIN 40719, Part 2 (1978) lists the identifiers for identifying the type of a device.
Identifier Type of device
A Modules, submodules
B Converters of non-electrical quantities to electrical ones and viceversa
C Capacitors
D Delay and storage devices
E Various (lighting, heating)
F Protective devices (fuses)
G Generators, power supply units
H Signaling devices (optical and acoustical)
K Contactors, relays
L Inductors
M Motors
N Amplifiers, controllers
P Measuring and test equipment
Q Power switchgear (circuit breakers, miniature circuit breakers)
R Resistors, potentiometers
S Switches, pushbuttons, selectors
T Transformers
U Modulators, converters
V Semiconductors, valves
W Transmission paths, lines, cables
X Terminals, connectors, socket outlets
Y Electrically-operated mechanical devices (solenoid valves, brakes)
Z Terminating elements, filters, equalizers
System Manual EPLAN 5.40
178
5.3.2 Identifiers for Identifying the Function of a Device Type
DIN 40719, Part 2 (1978) lists the identifiers for identifying the function of a device.
Identifier Function
A Auxiliary function, function "off"
B Direction of movement
C Counting
D Differentiation
E Function "on"
F Fuse
G Check/Test
H Message
J Integration
K Jogging mode
L Conductor identification
M Main function
N Measuring
P Proportional
Q State
R Reset, cancel
S Save, record
T Time measurement, delay
V Speed
W Addition
X Multiplication
Y Analog
Z Digital
Lists and Tables
179
5.4 Special Texts
Special texts have the following features:
• They are used for various page types as retainers or to specify the position.
• You cannot write special text to Logic pages apart from some exceptions.Exceptions are: Schematic-specific texts (identifier 0-99), page-specific special texts(identifier 100...199), project-specific special texts (identifier 200...299), and textsfor special programming (identifier 1100...1199).
• When projects or pages are created, these placeholders have values assigned to themmanually or automatically, by the fact that either project or page data are entered orthat identifiers such as the modification date are read out automatically.
• Special text is also used to create the plot positions of plot frames and plot forms.
• Special texts can also be used as comment texts, for example, the field supplemen-tary data.
Special texts are divided into the following types:
Text style ID
Schematic page 0 - 99
Page-specific plot frame data 100 - 199
Project-specific plot frame data 200 - 299
Table of contents 300 - 399
Terminal diagram 400 - 499
Interconnect diagram 500 - 599
Bill of materials 600 - 699
Terminal bill of materials 700 - 799
Device list 800 - 899
Terminal-connection diagram 900 - 999
Control panel layout 1000-1099
Special programming 1100-1199
Each text style is assigned an identifier which is either imported upon selection orwhich can be entered directly.
The following sections list the special texts sorted by numbers.
For special texts marked with an "[x]" in the overview, you must also add a value in the"Text" input field. For those texts marked with an "[x,y]" you must enter 2 values, sepa-rated by a comma.
System Manual EPLAN 5.40
180
5.4.1 Special Texts 0 – 99
This range of values encompasses texts for the schematics page. These texts can onlybe implemented on logic pages.
Number Special text
0 Text
1 Function text
2 Terminal strip designation
3 Connector strip designation
4 Connection designation
5 Conductor designation
5.4.2 Special Texts 100 - 199
This range of values encompasses page-specific texts. As from EPLAN version 5.40,these texts are available for all page types.
Number Special text
100 Drawing number
101 Date 1 (manual)
102 Date 2 (automatic)
103 Created by
104 Higher-level assignment
105 Location designation
106 Page designation
107 Supplementary field page
108 Supplementary field group
109 Supplementary field 1
110 Supplementary field 2
111 Supplementary field 3
112 Supplementary field 4
113 Supplementary field 5
114 Supplementary field 6
115 Supplementary field 7
116 Document type
Lists and Tables
181
Number Special text
117 Documentation type
118 Last editor
119 Scale (only for Free Graphics)
120 Macro: Directory / name
121 Macro: Version number
122 Macro: Source / reference
5.4.3 Special Texts 200 - 299
This range of values encompasses project-specific texts. As from EPLAN version 5.40,these texts are available for all page types.
Number Special text
201 Plant designation
202 Drawing number
203 Commission
204 Supplementary field 1
205 Supplementary field 2
206 Supplementary field 3
207 Supplementary field 4
208 Supplementary field 5
209 Supplementary field 6
210 Supplementary field 7
211 Company/Customer
212 Higher level assignment project
213 Location designation project
214 Page number
215 Highest page number
216 Subsequent page
217 Previous page
218 Current date
219 Path area number
220 Number of pages
System Manual EPLAN 5.40
182
Number Special text
221 Date of creation
222 Company address 1
223 Company address 2
224 Make
225 Type
226 Mounting location
227 Part features
228 Environmental consideration
229 Location
230 Regulation
231 Degree of protection
232 Control panels
233 Power input
234 Lead-in
235 Control voltage
236 Date of manufacture
237 Customer abbreviation
238 Customer title
239 Customer name 1
240 End user abbreviation
241 End user title
242 End user name 1
243 Responsible for project
244 Project end
245 Last editor
246 Modification date
247 Project name
248 Project path
Lists and Tables
183
5.4.4 Special Texts 300 - 399
This range of values encompasses settings for the table of contents.
Number Special text
301 Page number
302 Drawing number
303 Created by
304 Higher-level assignment
305 Location designation
306 Page designation
307 Supplementary field page
308 Supplementary field group
309 Supplementary field 1
310 Supplementary field 2
311 Supplementary field 3
312 Supplementary field 4
313 Supplementary field 5
314 Supplementary field 6
315 Supplementary field 7
316 Modification date automatic
317 Modification date manual
318 Page serial number (absolute page number)
319 Identification for page editing
320 Document and documentation type
321 Documentation type
322 Document type
323 Resolution
324 Form
325 Scale
326 Plot form
327 Number of ladders
328 Plot Frame
329 Last editor
System Manual EPLAN 5.40
184
Number Special text
381 Lines/Page: Number [x]
382 Lines: Distance in mm [x]
383 Columns: Number [x] (default=1)
384 Columns: Distance in mm [x] (default=40)
385 Orientation: 0=Landscape, 1=Portrait [x]
5.4.5 Special Texts 400 - 499
This range of values encompasses both texts for the terminal diagram as well as forthe terminal strip overview:
1. Terminal diagram:
Number Special text
400 Jumpers: Distance in 1/10 mm [x]
401 Page/Path
402 PLC designation
403 Function text: Text length (default=30)
404 Strip designation
405 Terminal number
406 Target A
407 Connection A
408 Target B
409 Connection B
410 Target C
411 Connection C
412 Target D
413 Connection D
414 Cable A
415 Conductor A
416 Cable B
417 Conductor B
418 Cable C
419 Conductor C
Lists and Tables
185
Number Special text
420 Cable D
421 Conductor D
422 Cable type A
423 Cross-section A
424 Cable type B
425 Cross-section B
426 Cable type C
427 Cross-section C
428 Cable type D
429 Cross-section D
430 Cable length A
431 Remark Cable A
432 Cable length B
433 Remark Cable B
434 Cable length C
435 Remark Cable C
436 Cable length D
437 Remark Cable D
438 Wire number A
439 Wire number B
440 Wire number C
441 Wire number D
442 Wire number E
443 Wire number F
444 Target E
445 Connection E
446 Target F
447 Connection F
448 Terminal macro / terminal text
449 Type designation
450 Levels
System Manual EPLAN 5.40
186
Number Special text
479 Form type [x]
480 Form orientation [x] (0=Landscape, 1=Portrait)
481 Terminals: Number/Page [x]
482 Terminals: Distance in 1/10 mm [x]
483 Cable A: Number [x]
484 Cable A: Distance in 1/10 mm [x]
485 Cable B: Number [x]
486 Cable B: Distance in 1/10 mm [x]
487 Cable C: Number [x]
488 Cable C: Distance in 1/10 mm [x]
489 Cable D: Number [x]
490 Cable D: Distance in 1/10 mm [x]
491 Cable name (single-line, two-line, three-line)
492 Modification date(per strip, common)
2. Terminal strip overview:
Number Special text
400 Sequential counting number
401 Graphics page of the terminal strip
402 Graphics page of the terminal bill of materials
403 Text of the strip definition
404 Strip designation
405 Total number of all terminals
406 Terminal marking
407 First terminal
408 Connector marking
409 Last terminal
410 Connector type
411 Sum of all PE terminals
Lists and Tables
187
Number Special text
413 Sum of all N terminals
415 Sum of all terminals without PE/N terminals
479 Form type [x] (terminal overview=3)
480 Form orientation [x]
481 Number of entries [x]
482 Distance of the entries [x]
5.4.6 Special Texts 500 – 599
This range of values encompasses both texts for the interconnect diagram as well asfor the cable overview.
1. Interconnect diagram
Number Special text
500 Cable name
501 Cable type
502 No. of conductors
503 Cable length
504 Cross-section 1
505 Cross-section 2
506 Remarks
507 Conductor designation
508 Target 1
509 Target 2
510 Connection 1
511 Connection 2
512 Page 1
513 Page 2
514 Function text 1 [x] (default=30)
515 Function text 2 (text length from 514)
516 Wire number
517 Cable macro / cable text
518 Cable macro / cable text
System Manual EPLAN 5.40
188
Number Special text
519 Voltage
520 Conductor type
521 Index
522 Cross-section
579 Form type
580 Form orientation [x] 0=Landscape, 1=Portrait
581 Cable conductors: Number/Page [x]
582 Cable conductors: Distance in 1/10 mm [x]
584 Unit of measure (yes/no)
591 Cable name (single-line, two-line, three-line)
2. Cable overview:
Number Special text
500 Cable name
501 Cable type
502 No. of conductors
503 Cable length
504 Cross-section 1
505 Cross-section 2
506 Remarks
507 Number of conductors used
508 Source
509 Target
510 Sequential counting number
511 End of the cable specification
512 Graphic page of the interconnect diagram
513 ’X’ character for shielding
516 Number of free conductors
519 Voltage
579 Form type
Lists and Tables
189
Number Special text
580 Form alignment (down / up / right / left)
581 Number of entries
582 Distance of the entries
583 0 = Without .. 1 = With PE/N/shielding
584 Units of measure (yes/no)
591 Cable name (single-line, two-line, three-line)
5.4.7 Special Texts 600 – 699
This range of values encompasses texts for the bill of materials and the purchase-order list.
Number Special text
600 Item number
601 Device designations
602 Part number
603 Designation 1
604 Type number
605 Designation 2
606 Order number
607 Designation 3
608 Manufacturer
609 Supplier
610 Group number
611 CAD number
612 Graphic symbol file
613 Graphic symbol number
614 Remarks
615 Total amount
618 Voltage
619 Current
620 Power
622 Holding power
System Manual EPLAN 5.40
190
Number Special text
623 Power dissipation
624 Tripping current
625 Connection cross-section
626 Mounting width
627 Mounting height
628 Mounting depth
629 Mounting location
630 Weight
631 Space requirement
632 DIN number
633 Material number
634 Quantity
635 Total amount
636 Unit of quantity
637 Price unit
638 Page and path
639 Packaging unit
640 Function text
641 Part classification
642 Type of part
644 Unit price
645 Total price
646 Transfer
680 Form alignment: 0 = Portrait, 1 = Landscape [x]
681 Records: Number/Page [x]
682 Records: Distance in 1/10 mm [x]
Lists and Tables
191
5.4.8 Special Texts 700 - 799
This range of values encompasses texts for the terminal bill of materials.
Number Special text
700 Terminal strip
701 Purchase Order Number left
702 Purchase Order Number right
703 Labeling left
704 Labeling right
705 Type designation
706 Order number
707 Labeling right
708 Designation material right
709 Jumper Purchase Order Number
710 Cover
711 Mounting plate bracket
712 Remarks
720 Form alignment
781 Records: Number/Page [x]
782 Records: Distance in 1/10 mm [x]
5.4.9 Special Texts 800 - 899
This range of values encompasses texts for the device list.
Number Special text
800 Position
801 DD
802 Part number
803 Designation 1
804 Type number
805 Designation 2
806 Order number
807 Designation 3
System Manual EPLAN 5.40
192
Number Special text
808 Manufacturer
809 Supplier
831 Symbol
832 Line from
833 Line to
834 Quantity
838 Cross-reference
840 Function text
880 Column distance (to 881)
881 Lower margin
882 Distance between the text entries
883 Distance of the graphics
884 Distance between cross-references (X)
885 End of cross-references (X)
5.4.10 Special Texts 900 - 999
This range of values encompasses texts for the terminal-connection diagram.
Number Special text
900 Strip name
901 Jumper coordinates: Distance wire jumper in 1/10 mm[x]
902 PLC designation (X)
903 Terminal designation
904 Terminal connection
905 Cable text (with max. length)
906 Cable line (with line type, font size is master length)
907 Conductor designation
908 Shielding (with height)
909 Insertion point of symbol
910 Function text (with max. length)
911 Internal target 1
Lists and Tables
193
Number Special text
912 Internal target 2
913 Internal target 3
914 Second conductor designation
915 Terminal end
916 Wire number
917 Terminal macro / terminal text
919 Internal DD (PLC)
920 Internal connection (PLC)
921 PLC macro (with macro name)
922 Levels
979 Form type
981 Limitation
982 Terminal spacing
983 Macro name
5.4.11 Special Texts 1000 - 1099
This range of values encompasses texts for the control-panel layout.
Number Special text
1000 Legend display
5.4.12 Special Texts 1100 - 1199
This range of values encompasses texts for the special programming. As from EPLANversion 5.40, these texts are available for all page types.
Number Special text
1100 Control text 1
1101 Control text 2
1102 Control text 3
1103 Control text 4
System Manual EPLAN 5.40
194
Number Special text
1104 Control text 5
1105 Control text 6
1106 Control text 7
1107 Control text 8
1108 Control text 9
1109 Control text 10
Graphics Editing Menu
195
6 Graphics Editing Menu
The graphics editing menu contains the following entries:
Page Draw Attachment Edit Search Options Free graphics Symbol Parameters Window View Help
Click with the mouse on the menu entry in order to open the respective pulldown menu.
6.1 Page
The Page menu contains the following menu items:NewOpenSaveCopyRename / MoveRead in backup pagesDeletePrevious / NextPropertiesPrintHPGL plottingExportExternal programsNumber supplementary fieldsClose
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
6.1.1 New
This function creates a new page. To this purpose it branches into the page overview inwhich you can specify certain properties of the page.
6.1.2 Open
With this function you can branch to the page selection in order to select the page to beopened.
The page properties cannot be changed. The Page/Properties menu has to be used tothis purpose.
System Manual EPLAN 5.40
196
6.1.3 Save
This menu item saves the displayed page immediately. Normally EPLAN does not savea page until you leave it or want to terminate graphics editing.
6.1.4 Copy (Page)
This function is used to copy individual or several pages. Copying is possible bothwithin the current project as well as between different projects.
6.1.5 Rename/Move
This function can be used to rename one or more pages or to move them to anotherpoint in the project. To this purpose the program first branches to the page selection inwhich you can specify the pages to be renamed/moved.
6.1.6 Read in backup page
This function allows you to read backup pages into a project. To do so the followingrequirements must be met:
• The target page must be blank
• The page type of the blank page must be the same as that of the backup page.
An overview of the most recently saved pages from which to make your selection isdisplayed.
6.1.7 Delete (Page)
This function is used to delete individual or several pages. To this purpose the programfirst branches to the page selection in which you can specify the pages to be deleted.
6.1.8 Previous / Next
These functions allow you to move page-by-page. You can alternatively use the keys and .
If you have changed the page and wish to page on and the ’Save schematic automati-cally when leaving the page’ personal parameter has been deactivated, a prompt is dis-played whether the page is to be saved.
Graphics Editing Menu
197
6.1.9 Properties (Page)
This function allows you to view and edit the properties of the currently open page. Todo so you first have to activate the desired page.
Afterwards the dialog for specifying the page properties is opened.
6.1.10 Print
With this function you can branch to the page selection dialog in order to select thepages to be printed. Click on the [Output] command button in order to print. The re-spective pages are then transferred to the Windows print manager.
6.1.11 HPGL plot
With this function you can branch to the page selection in order to select the pages to beplotted. Click on the [Output] command button then displayed in order to plot. Thehighlighted pages are exported to a file in HPGL format whose file name can be speci-fied.
6.1.12 Export
The Export menu contains the following menu items:EXFDXFHTML/DWFInter@ViewEXF macroImage file
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
6.1.12.1 EXF
With this function you can branch to the page selection in order to select the pages to beexported. Click on the [Output] command button then displayed in order to trigger theexport process.
A dialog box is then opened in which you can specify the path and name of the exportfile.
System Manual EPLAN 5.40
198
6.1.12.2 DXF
With this function you can branch to the page selection in order to select the pages to beexported. Click on the [Output] command button then displayed in order to trigger theexport process.
A dialog box is opened in which you can specify further output settings for DXF ex-porting.
6.1.12.3 HTML/DWF
This function exports the entire EPLAN project into a format which is suitable for dis-tribution via the World Wide Web (WWW).
Only the complete project can be exported – a preselection of the pages tobe exported is not possible in this function.
6.1.12.4 Inter@View
This function exports selected project pages in HTML format for Inter@View, a sup-plementary program of EPLAN, in which you can configure specific settings for HTMLoutput.
6.1.12.5 EXF macro
With this function you can branch to the page selection in order to select the pages(macros) of a macro library project to be exported. Click on the [Output] commandbutton then displayed in order to trigger the export process.
This menu item is only active for projects in which the Macro library proj-ect type was specified.
6.1.12.6 Image file
With this function you can branch to the page selection in order to select the pages to beexported. Click on the [Output] command button then displayed in order to trigger theexport process.
A dialog box is then opened in which you can specify the output directory and furthersettings for the page export as image file.
Graphics Editing Menu
199
6.1.13 External programs
The subsequent menu of this menu item provides a selection of programs which can beset freely. These can be called easily from the graphics editing function. These pro-grams can be set up in the "External programs" module (in the main menu under "Utili-ties").
6.1.14 Number supplementary fields
This function is used to assign a consecutive number to any supplementary field. Num-bering begins with the first page.
You can specify the start value (not the starting page!).
Use the Formatting spaces input field to define the number of digits to be used for num-bering. If the numbers are smaller, a corresponding number of leading zeros is entered.If you enter "0", formatting is suppressed. A negative entry deletes the formatting. Theentry in the form is left-justified.
Specify the supplementary field to be numbered in the Field selection dropdown listbox.
When you select the supplementary field, take into consideration that itmust be possible to plot the supplementary field in the specified plot frame.Please refer to the online documentation for the graphics forms.
6.1.15 Close
Use this option to close the currently opened schematic page and leave the graphics ed-iting function at the same time.
6.2 Draw
The Draw menu contains the following menu items:Insert symbolsSymbol macrosInsert macrosBlack boxDevice-end terminalsPLC end terminalPotential arrowsCable definitionShieldingsWiring definitionDIN boxText
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
System Manual EPLAN 5.40
200
6.2.1 Insert symbols
This function lets you read symbols or terminals into the schematics pages. Dependingon their type, symbols can be evaluated in various ways.
Input involves the following steps:
• Select a symbol from the symbol library.
• Enter device data such as DD, parts data, and electrical characteristics
• If it does not exist yet: Enter connection designations.
Select the menu path Options/Multifunction menu/Replace + by to swap the shortcuts for Insert symbols and Symbol macros so that
you can use to insert symbol macros.
6.2.2 Symbol macros
This function lets you read symbol macros into the schematics pages.
Symbol macros can contain several symbols for which the device data such as DD, de-scribing block, parts data, and connection designations have already been defined. Thisdepends on the method used to create the symbol macro.
Select the menu path Options/Multifunction menu/Replace + by to swap the shortcuts for Insert symbols and Symbol macros so that
you can use to insert symbols.
6.2.3 Insert macros
A macro can be a page or a section of a page that is saved completely as a separate file.
This function allows you to read macros into the current page. A selection window fromwhich the directory, macro type, and macro name can be selected are displayed.
Only for Logic pages Symbols in macros are not identified by their com-plete designations, but only by an internal position number for the symbolwithin the symbol file. Therefore, the sequence of symbol files used todraw the macros must agree with that of the project, otherwise incorrectsymbols will be read in and drawn.
Graphics Editing Menu
201
6.2.4 Black box
You can use black boxes to represent devices with extensive functions and connectionsthat cannot be drawn with individual symbols (for example PLCs). These can then beincluded during subsequent automatic evaluation runs.
Input involves the following steps:
• Specify the dimensions of the block by using the cursor keys or the mouse.
• Enter device data such as DD, parts data, and electrical characteristics
• Specify data for the DD position as well as graphics data (line type etc.).
You must then enter the connection designations of a black box, using device-end ter-minals or terminal symbols.
Please note the following with respect to the automatic evaluation of DDs:
Terminal symbols: In the case of terminal symbols the DD of the blackbox is used as the terminal strip if:
• No terminal strip name was entered (input without blank or colon) or
• the terminal strip name could not be found (search direction for the ter-minal strip left/up).
DD: DDs of symbols within a black box are recognized during automaticevaluation. However, the DD of the black box is not supplemented or used.
6.2.5 Device-end terminals
Device-end terminals represent the connections of a device you have defined in a blackbox. In contrast to terminal symbols that you can enter in the schematic by pressing
, device-end terminals cannot be included into the terminal diagram. They are,however, recognized as targets.
This also applies to terminals with lateral attachments.
6.2.6 PLC end terminal
Using this function you can insert a PLC end terminal into the schematic. In the subse-quent Symbol properties window you can specify the PLC-specific properties of thePLC terminal, e.g. the address, the type of connection (input, output, supply, and busterminal) and the type of terminal display.
System Manual EPLAN 5.40
202
6.2.7 Potential arrows
Potential arrows (interruptions) are used to establish connections between symbols forwhich autoconnect cannot create them because, for example, they are located on sepa-rate pages.
Automatic evaluation is carried out by the cross-reference program. The operation de-pends on the following settings:
• ’Identifier for potential arrow check’ in the parameter program (under the menu pathProject / Contactor/cross-reference/wiring)
• in case of DIN projects on the ’Identifier method (potential arrows)’ in the projectdata.
Potential arrows have connections both in the direction of the arrowhead,as well as in the opposite direction.
6.2.8 Cable definition
This function allows you to manually enter cable specifications for cables that differfrom the general entries in the parameter program. These can then be evaluated in theterminal and interconnect diagram. In addition, you can also define cables between 2symbols that are not terminals (non-terminals).
Input involves the following steps:
• Define the identifier line.
• Enter the cable data, for example designation, type, etc.
• Specify the graphics data for the data.
• Enter the parts data.
The following prerequisites must be met in order to enter a cable specification manu-ally:
• "Manual / Number", "Manual / 1 Target" or "Manual / 2 Targets" must be entered inthe input field of the "Cable number assignment" parameter (under "Project" / "Ter-minals / Cables").
• Only for cable definitions between 2 non-terminals: You must enter a value in theNumber of conductors field of the cable definition. This number can be larger thanthe actual number of conductors.
If you do not enter any values in the input fields for the number of conductors, cabletype, or cross-section, the values from the terminal parameters will be used (except inthe case of non-terminals!).
Graphics Editing Menu
203
If you define a cable with a PE or N conductor under Type, these conductors will onlybe recognized if you enter either identifier 111 or 112 in the Symbol type field of thecorresponding terminal.
6.2.9 Shieldings
This function is used to call up a graphics character for shielding lines. You can use thecursor keys or the mouse to define its size.
In the terminal or interconnect diagram, the shielding can be evaluated as a target desig-nation if a designation for the shielding has been included in the terminal-diagram pa-rameters.
6.2.10 Wiring definition
The wiring definition function allows you to manually define the cross-section, length,and color of connections, and to add comments. These can then be evaluated in both thewiring list and the terminal diagram.
Input involves the following steps:
• Define the identifier line.
• Enter wiring-definition-specific data
• Specify the text position
• Enter line data.
6.2.11 DIN box
Only for processing according to DIN:
This function allows you to specify Higher-level assignment and/or Location designa-tion identifier blocks that differ from the current page. All devices lying within theframe will be recognized.
Input involves the following steps:
• Specify the dimensions of the frame by using the cursor keys or the mouse.
• Enter device data such as DD and electrical characteristics
• Specify the DD position as well as graphics line data.
Note the following for the automatic evaluation of the specified identifier blocks:
• Whether the higher-level assignment and/or the location designation are importeddepends on the ’Suppress duplicate HLA/LOD’ project parameter to be found under
System Manual EPLAN 5.40
204
the menu path (start at the graphics editing module) Parameters / Project / Termi-nals/Cables / Terminals/Cables 1 tab.
• In this function, only the identifier blocks for the higher-level assignment ("=")and/or the location ("+") are valid entries for "Device designation". Entries definingthe type of device (starting with "-") are not permitted.
• Priority: All identifier blocks defined when the symbol was input will be evaluated.If (identifying) identifier blocks are missing, they will be imported in the followingorder: 1. Symbol 2. DIN definition 3. Page 4. Project
• If the "=" or "+" prefix is followed by a period and a subsequent entry, this entry willbe attached to the current identifier block.
6.2.12 Text
This function allows you to add text to the schematic. There are various types of textavailable to you. These are:
• Text style "0":This text style has no effect on automatic evaluation runs.
• Text style ">0":These texts have a specific function which is explained in more detail in the UserGuide.
Function texts, strip designations, conductor designations as well as spe-cial texts acting as a retainer in Free graphics.
6.3 Attachment
The Attachment menu contains the following menu items:1 Angle down, right2 Angle down, left3 Angle up, right4 Angle up, left5 Node, down6 Node, up7 Node, right8 Node, left9 JumperDouble junctionInterruptSpecify line data
Graphics Editing Menu
205
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
6.3.1 Angle
EPLAN can only evaluate connections that have been created by the automatic connec-tion function (autoconnect) between symbols. Angles change the direction of the auto-matic connection. There will not be a prompt.
The angle is designated in accordance with the scheme "Angle direction, attachmentdirection" so that an angle "left, down" looks like follows:
Autoconnection can only be used for logical connections. It cannot be used to drawgraphic elements, otherwise errors will occur during automatic evaluation runs.
6.3.2 Node
EPLAN can only evaluate connections that have been created by the automatic connec-tion function (autoconnect) between symbols. Nodes split the automatic connectionpath.
Nodes also have an effect on target tracking during automatic evaluation. For this rea-son, a separate window appears once you have selected your basic type. This windowasks you about the desired effect on target tracking you want to occur.
6.3.3 Jumper
This function is used to insert a jumper distribution into the schematic. As in the otheroptions of the Attachment menu, autoconnecting is realized automatically, meaning thatconnection lines are drawn automatically between the symbols.
6.3.4 Double junction
EPLAN can only evaluate connections that have been created by the automatic connec-tion function (autoconnect) between symbols. Double junctions are used to split theautomatic connection path.
Double junctions also affect target tracking during automatic evaluation. For this rea-son, a separate window appears once you have selected your basic type. This windowasks you about the desired effect on target tracking you want to occur.
System Manual EPLAN 5.40
206
6.3.5 Interrupt
An automatic connection will be drawn wherever two connection points point eithervertically or horizontally towards each other.
This function interrupts such connections.
Input involves the following steps:
• Call up the function
• Position the cursor between two connection points.
• Exit the Interrupt mode, e.g. by pressing .
The interruption will be graphically displayed after the next screen refresh.
An insertion point is created between the connection points. Press to display thisinsertion point.
6.3.6 Specify line data
The Specify line data menu contains the following menu items:IndividualPotentialsComparison
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
6.3.6.1 Individual
An automatic connection will be drawn wherever two connection points point eithervertically or horizontally towards each other. The line data of the connection, such asline type, line thickness, and pattern length are defined in the symbol editor at the timethe symbol is created. Pen numbers for angles, nodes, etc. are specified in the graphicsparameters (Graphics 3 tab, Output parameters group box).
This function allows you to change the line data of a connection point.
Input involves the following steps:
• Call up the function
• Position the cursor on a connection point. An input window in which you can changethe line data for this connection is displayed.
If two connecting points that have been assigned different line data point at each other,the following applies:
• The line data of the lower connecting point take precedence.
• The line data of the right-hand connecting point take precedence.
Graphics Editing Menu
207
6.3.6.2 Potentials
An automatic connection will be drawn wherever two connection points point eithervertically or horizontally towards each other. The line data of the connection, such asline type, line thickness, and pattern length are defined in the symbol editor at the timethe symbol is created. Pen numbers for angles, nodes, etc. are specified in the graphicsparameters (Graphics 3 tab, Output parameters group box).
This function allows you to change the line data of an automatic potential connection.
Input involves the following steps:
• Call up the function
• Position the cursor on a connection point located inside the potential you want tochange. An input window in which you can change the line data for this connectionof the potential is displayed.
6.3.6.3 Comparison
An automatic connection will be drawn wherever two connection points point eithervertically or horizontally towards each other. The line data of the connection, such asline type, line thickness, and pattern length are defined in the symbol editor at the timethe symbol is created. Pen numbers for angles, nodes, etc. are specified in the graphicsparameters (Graphics 3 tab, Output parameters group box).
Working on the current page, this function checks the line data generated by the auto-matic connection for differences within the potential. If differences are found, the corre-sponding connection points are marked, and the line data can be changed.
6.4 Edit
The Edit menu contains the following menu items:CancelUndoRedoCut (Clipboard)Copy (Clipboard)Paste (Clipboard)DeleteMoveDuplicateCreate macro / form WindowChange window cornerPropertiesPart numberMessagesIncrementPositionMove DDPLC connection at terminalPanel layout
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
System Manual EPLAN 5.40
208
6.4.1 Cancel
Editing functions such as Move, Duplicate, etc. can be terminated by using this optionor .
6.4.2 Undo / Redo
The Edit/Undo (or Edit / Redo) menu can be used to undo (redo) up to 20 steps.
A step is any action which changes the data structure.
Duplicating elements represents one step, irrespective of the number of elements placed.A new step does not start until the Duplicate function has been terminated. This alsoapplies to the insertion of macros.
If you are editing a graphics which is attached to a single insertion point, not every entryof a line is a step, but the change to the complete graphics.
Exception: Each action of inserting a symbol represents a step.
6.4.3 Cut (Clipboard)
Using the Cut function you can move a graphics object across more than one page orproject. The object is then deleted on the graphics page and saved as file in the EPLANClipboard. The EPLAN Clipboard may include up to twelve Clipboard files.
(However, if you wish to use only one Clipboard, you have to activate the Use one clip-board only personal graphics parameter.
To cut a graphics object you must first select the Cut menu item. Afterwards use thecursor to drag a frame around the insertion point of the object to be cut. In the subse-quent Clipboard dialog box you can enter a text that will identify the graphics object tobe cut when it is pasted later. (This dialog does not come up if you have activated theSuppress description dialog parameter to be found in the personal graphics parametersor if you are working with one Clipboard only.)
6.4.4 Copy (Clipboard)
Using the Copy function you can duplicate a graphics object to more than one page orproject. The object is then saved as file in the EPLAN Clipboard. The Clipboard cancontain up to twelve Clipboard files.
(However, if you wish to use only one Clipboard, you have to activate the Use one clip-board only personal graphics parameter.
To copy a graphics object you must first select the Copy menu item. Afterwards use thecursor to drag a frame around the insertion point of the object to be copied. In the sub-sequent Clipboard dialog box you can enter a text that will identify the graphics object
Graphics Editing Menu
209
to be copied when it is pasted later. (This dialog box does not come up if you have acti-vated the Suppress description dialog parameter to be found in the personal graphicsparameters or if you are working with one Clipboard only.)
6.4.5 Paste (Clipboard)
Use this option to paste graphics objects from the EPLAN Clipboard into one and/ormore graphics pages/projects
To paste a graphics object you must first select the Paste menu item. EPLAN then dis-plays the Paste dialog box in which you can select the desired graphics object by thedescription shown there. If you activate the Preview check box in this dialog box thegraphics object is shown in a separate window. (The Paste dialog box does not come upif you have activated the ’Use only one clipboard’ parameter to be found in the personalgraphics parameters.)
Finally you have to decide how the device designations are to be transferred.
6.4.6 Delete (Graphics Object)
This function is used to delete individual or several objects. To do this, the insertionpoints of all objects you want to delete must be combined in a single window.
Input involves the following steps:
• Call up the function
• Define the window section.
No further prompt for confirmation is displayed.
You can delete symbols simply by positioning the cursor on the insertion point and thenpressing .
Several graphic elements can be combined under a single insertion point. The pointdoes not have to lie where the individual elements are drawn. Press to display theinsertion points.
6.4.7 Move
This function is used to move the position of individual or several objects. The insertionpoints of all objects you want to modify must be combined in a single window.
Input involves the following steps:
• Call up the function
• Define the screen section
System Manual EPLAN 5.40
210
• Specifying the new position.
Several graphic elements can be combined under a single insertion point. The pointdoes not have to lie where the individual elements are drawn. Press to display theinsertion points.
6.4.8 Duplicate
This function is used to copy the position of individual or several objects. The insertionpoints of all objects you want to modify must be combined in a single window.
Input involves the following steps:
• Call up the function
• Define the screen section
• Specify the new position
• Select mode for using the DD.
This function remains active until you press to end it.
Several graphic elements can be combined under a single insertion point. The pointdoes not have to lie where the individual elements are drawn. Press to display theinsertion points.
6.4.9 Create macro/form
The Create macro/form menu contains the following menu items:Symbol macroPath/PLC macroVariable macroCombined macroWindow macroPage macroPlot frameForm
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
6.4.9.1 Symbol macro
Symbol macros can contain several symbols for which the device data such as DD, de-scribing block, parts data, and connection designations have already been defined.
Graphics Editing Menu
211
Input involves the following steps:
• Call up the function
• Define the screen section
• Enter the macro name and any comments.
6.4.9.2 Path/PLC macro
A macro can be a page or a section of a page that is saved completely as a separate file.
This function lets you define a section of the current schematics page as a macro. Theheight of the window corresponds to the height of the schematic page. The width can beset.
Input involves the following steps:
• Call up the function
• Define the screen section
• Enter the macro type, macro name, and comment text.
Several graphic elements can be combined under a single insertion point.The point does not have to lie where the individual elements are drawn.Press to display the insertion points.
6.4.9.3 Variable macro
A variable macro is used to draw graphics objects whose length and height are not de-fined until they are actually inserted. The saved macro is used as the base macro.
Input involves the following steps:
• Call up the function
• Define the screen section
• Click on the insertion point
• Enter the macro name, comment text as well as variable texts and formulae.
Several graphic elements can be combined under a single insertion point.The point does not have to lie where the individual elements are drawn.Press to display the insertion points.
System Manual EPLAN 5.40
212
6.4.9.4 Combined macro
A macro can be a page or a section of a page that is saved completely as a separate file.In contrast to window macros, the following special conditions apply when combinedmacros are read into the schematic:
• Part numbers can be filed.
• The macro file must be available (as a separate file) when the screen is refreshed.
This function allows you to define graphic elements that were combined under a singleinsertion point as a macro.
Input involves the following steps:
• Call up the function
• Specify macro name and comment.
Several graphic elements can be combined under a single insertion point.The point does not have to lie where the individual elements are drawn.Press to display the insertion points.
6.4.9.5 Window macro
This function is used to define a rectangular section of the current page ("window")and save it as a macro.
Here, too, you have to enter the macro name and the comment text after having speci-fied the screen section.
6.4.9.6 Page macro
A macro can be a page or a section of a page that is saved completely as a separate file.
This function allows you to define the current schematic page (without plot frames) as amacro. This means that no screen section has to be specified. Only the macro name andcomment text must be entered.
6.4.9.7 Plot frame
Use this function to save the current project page as plot frame (*.skg) in the\EPLAN4\N\<customer code> directory. This means that no screen section has to bespecified. Only the macro name and comment text must be entered.
The plot frame can be created with the aid of graphic elements and text. Special textsare used as retainers, whereby entries such as commission that belong to the project orthe page are displayed directly.
Graphics Editing Menu
213
6.4.9.8 Form
In a form, the plot coordinates for interconnect diagrams, bill of materials etc, can beedited. These are read from the positions of the special texts.
This function saves the current page as a form. The form type, the form name, and thecomment text must be specified. Since EPLAN differentiates between the forms bymeans of the extensions, you have to enter the name without an extension.
6.4.10 Window
Using this function of the Edit menu you can execute the following actions in graphicsediting for individual and several objects:
• Write macro• Move
• Duplicate• Cut
• Copy• Delete.
To do so, the insertion points of all objects you want to edit must be combined in a sin-gle window.
Input involves the following steps:
• Call up the function
• Define the screen section
• Select the action.
No prompt is displayed for the Delete function.
Several graphic elements can be combined under a single insertion point. The pointdoes not have to lie where the individual elements are drawn. Press to display theinsertion points.
6.4.11 Change window corner
When you open a zoom window you can use this function of the Edit menu to jumpbetween the opposing corners of the window.
This is particularly useful when you use the cursor keys to expand the window and donot want to use the window corner first selected as the reference point but rather theopposing one.
System Manual EPLAN 5.40
214
6.4.12 Properties (Graphics Object)
At every object used in the schematic you can edit the properties. To do so move thecursor onto the insertion point of the object and then either press the key or se-lect this menu option.
Depending on the selected object type different dialog boxes are displayed when thisfunction is called.
You can activate and deactivate the display of the object insertion points inthe schematic by pressing the key .
6.4.13 Part number
Part numbers can be entered on the insertion points of symbols, cable definitions orgraphic elements. In the case of symbols the parts data can also be entered directly whenyou insert the symbol in the Symbol properties window, Parts tab card.
Position the cursor on the insertion point of an element and call up this function. (Thefunction can also be activated by pressing the right-hand mouse button to call up thepop-up menu.) The part numbers already assigned are listed in a table. Click on [Select]to activate the part selection.
You can only write those parts data from a bill of materials back into the schematicwhich have a DD assigned to them. It is thus not possible to change parts data automati-cally which have been assigned to terminal strips.
6.4.14 Messages
A window displays all the messages belonging to the project. Press to jumpautomatically to the displayed positions.
Select the menu path Parameters / Project / Message management you can specifywhich message groups are to be output.
6.4.15 Increment
After this function has been called up an input window is displayed in which you canenter the horizontal and vertical distance you want the cursor to move when you pressthe cursor keys.
Input is carried out in grid coordinates.
The setting remains in effect until you either leave graphics editing, or until the entry ischanged by a renewed entry.
Graphics Editing Menu
215
6.4.16 Position
After this function has been called up an input window where you can directly enter thehorizontal and vertical cursor position in "mm" is displayed.
In contrast to the increment the positioning determines to which fixed coordinate on theschematics page the cursor is to jump. This does not mean the relative position to thecurrent cursor position.
6.4.17 Move DD
The device designations are usually placed as was specified in the symbol editor (as arule on the left). This function is used to move the device designation. The symbol itselfis not moved.
The function is particularly useful when the device designation and a neighboring sym-bol overlap.
Proceed as follows:
• Position the cursor on the symbol whose DD is to be moved, and press .The DD can now be moved by using the mouse or the arrow keys.
• Press the left-hand mouse button or to specify the end position of the DD.
• If you press when the cursor is not positioned on a symbol, connectinglines are displayed between the symbols and their DDs.
• You can undo the moving of a symbol by positioning the cursor on the insertionpoint of a symbol and pressing and .
6.4.18 PLC connection at terminal
Not only the PLC address but also the actual connection designations can be entered onpages of the page type "T=PLC overview".
Through this function these connection designations of the PLC overview pages areread into the schematic pages as connection designations of the terminals or connectorswhen these have been cross-referenced by the PLC cross-reference function.
6.4.19 Panel layout
This function is used to place component macros on a mounting panel.
System Manual EPLAN 5.40
216
6.5 Search
The Search menu contains the following menu items:SelectionInsert into search databaseNext entryPrevious entryJump to counterpiecePart at components
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
6.5.1.1 Selection
If your search database is empty, this option branches into the dialog box for entering asearch term. If, on the other hand, the search database contains at least one entry, thisoption branches into a dialog box in which you can choose to which entry in the data-base you want to jump.
6.5.1.2 Insert into search database
This menu option is used to insert all the elements within the window section of a proj-ect page into the search database. After the option has been called up, the cursorchanges its form and you can define a rectangle which contains all the elements to beinserted into the search database.
Use the mouse to drag a rectangle around the desired elements and complete the defini-tion by pressing on the left-hand mouse button.
This function cannot be used to enter texts on the project pages into thesearch database. Use the menu option Search / Selection for texts.
6.5.1.3 Next entry / Previous entry
In order to use this option you must already have selected at least one element of thesearch database during the current EPLAN session by calling up the menu path Search/Insert into search database.
If your search database contains at least two entries, you can use these options to jumpto the respective next or previous element of the search database.
If your search database is empty or only contains one entry, these two op-tions are without any effect.
Graphics Editing Menu
217
6.5.1.4 Jump to counterpiece
In order to use this option you must already have selected at least one element of thesearch database during the current EPLAN session by calling up the menu path Search/Insert into search database.
This option is used to jump in the search database between pairs of elements (for ex-ample, arrow / counter-arrow).
If your search database is empty or only contains one entry, this option iswithout any effect.
6.5.2 Parts at components
This function is used to have the part numbers of all the components located on the cur-rent page displayed.
As soon as you have activated this function (this can also be done via the pop-up menu)a list with all components and cable definitions including part numbers of the currentpage is displayed. Click [OK] or double-click on an entry to quit this window. The cur-sor is then positioned on the selected symbol in graphics editing. Press [Cancel] to exitthe window.
6.6 Options
The Options menu contains the following menu items:Multifunction menuInsertion pointsGridSymbol extensionPage offsetAlternative text displayDisplay propertiesAlternative operationDisplay message window
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
6.6.1 Multifunction menu
The Multifunction menu contains the following menu items:Connection directionsPoint and/or target wiringOnly target wiringCable displayPlot invisible elementsOne arrow per pageCrosshair cursor
System Manual EPLAN 5.40
218
External targetsMouse incrementReplace [CTRL]+[INS] by [INS]Save cursor position
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
6.6.1.1 Connection directions
By entering , arrows will show the direction from which an automatic connection(autoconnect) is possible.
You can use this function to check whether there are any unconnected connectionpoints.
The display returns to its original state if you change pages or press to re-fresh the screen.
6.6.1.2 Point and/or target wiring
The change in the display depends on the Point wiring setting for the Display targetwiring as point wiring parameter (Graphics 2 tab card of the project-specific graphicsparameters).
The display returns to the style defined in the graphics parameters if you change pagesor press to refresh the screen.
6.6.1.3 Only target wiring
Enter to display all junctions and double junctions as target wiring. This menu itemis used to display target tracking problems if Point wiring was specified for the Displaytarget wiring as point wiring graphics parameter (Graphics 2 tab card of the project-specific graphics parameters) or if Point wiring was selected for graphics input.
The display returns to the style defined in the graphics parameters if you change pagesor press to refresh the screen.
6.6.1.4 Cable display
This function is used to display all the connections at which a cable was specified. Thedisplay is carried out by means of arrows. Calling up this function again reverses thedisplay.
Graphics Editing Menu
219
6.6.1.5 Plot invisible elements
The graphics editing program allows you to use this menu item to mark texts and linesas hidden so that these will be suppressed during graphics output. You have the follow-ing options:
• Lines and text defined in this way are plotted with the line type and font size settingsyou made.
• The plot output is suppressed.
Irrespective of this setting a separate parameter ("Project" / "Graphics","Graphics 1" tab card) can be used to specify the display for the screen.
6.6.1.6 One arrow per page
This setting is only taken into consideration, if one of the entries By lines or By col-umns was selected under Display of overviews for potential arrows (Graphics 2 tab ofthe project-specific graphics parameters).
An overview of all potential arrows with the same name will be entered for the definedsource arrow (refer to the "Symbol properties" input window). You have the followingoptions:
• Display: Page only The numbers of the pages containing potential arrows with the same name will beentered under the designation. Each page will only be listed once. We recommendthis setting for users who have so many potential arrows that they spill over the sidesof a standard A3 plot frame.
• Display: page and path The complete cross-reference with page and path will be entered. This is the defaultsetting.
6.6.1.7 Crosshair cursor
This setting allows you to change the cursor appearance so that the horizontal and verti-cal lines of the cursor cover an entire page (cross-hair cursor).
This setting remains in force, also after you have quit the program, until the function iscalled up again.
System Manual EPLAN 5.40
220
6.6.1.8 External targets
When entering terminal or connector symbols, one of the things you must define isConnection of the external output position in form.
This function allows you to show the defined, external targets on the graphic by meansof corresponding arrows. This simplifies target tracking for terminals.
This function remains active until it is deactivated by a new call-up.
6.6.1.9 Mouse increment
When you stipulate the mouse increment in the corresponding input window(Edit/Increment), you determine the smallest increment within the grid.
This switch allows the entered increment to be stipulated additionally for the mouse.When you call up this function again, the mouse reverts to the grid size.
This setting remains in force, also after you have quit the program, until the function iscalled up again.
If paths or insertion points cannot be reached because the increment is toolarge, press to access them.
6.6.1.10 Replace [CTRL]+[INS] by [INS]
Using this function you can swap the key commands for the Insert symbols and Symbolmacros menu items (Draw menu) so that you can insert symbol macros with andsymbols by pressing .
6.6.1.11 Save cursor position
This function is used to save the active cursor position when leaving graphics editing.When you call up graphics editing again, the cursor is positioned automatically at thisposition, irrespective of the page which you have selected for editing.
This setting remains in force, also after you have quit the program, until the function iscalled up again.
6.6.2 Insertion points
This function is used to display the insertion points of all the symbols additionally.Calling up this function again deactivates the display of the insertion points.
Graphics Editing Menu
221
6.6.3 Grid
This function is used to additionally display the grid valid for the respective page type.The grid results from the set increment.
Calling up this function again deactivates the display of the grid.
6.6.4 Symbol extension
This function is used to have the required space displayed with every symbol. Callingup this function again deactivates the display of the space required.
6.6.5 Page offset
The current coordinates on the graphics screen are shown on the status bar as grid di-mensions. The origin (the coordinates X=0 and Y=0) is the lower left-hand corner ongraphics pages and the upper left-hand corner on all other types of pages.
Use this function to call up further coordinates that show the origin of the cursor posi-tion. To do so, place the cursor to the position on the graphics screen that you wouldlike to define as the new coordinate origin, then press , or select this function. Theadditional coordinate position for the new origin will also be displayed.
Calling up this function again deactivates the display of the additional coordinates.
6.6.6 Alternative text display
Using this function you can switch between the following possibilities of text display onproject pages:
• If this option has been set, the font textnorm.fnt from the directory for standardmaster files is used for the display.
• If this option has not been set, the TrueType graphics character set specified in thecorresponding workstation-specific parameter (Workstation / GDI output formatmenu path) is used for the screen output.
6.6.7 Display properties
When a component has been selected, this function opens a device-specific windowwhich displays the information on the current component (device designation, connec-tion designations, electrical characteristics, parts data etc.).
System Manual EPLAN 5.40
222
The data of a component cannot be modified here! To edit a symbol, acti-vate the Symbol properties dialog by double-clicking on the desired symbolor selecting Edit/Properties.
6.6.8 Alternative operation
This function allows to switch to the operation used in previous EPLAN versions. In-stead of calling a function first and specifying afterwards for which objects it is to beused, you select the objects for which an action is to be carried out first in this mode andafterwards the corresponding option from the Edit menu.
Note that actions can only be carried out step-by-step in this mode!
6.6.9 Display message window
Use this function to activate and deactivate the display of the message window con-taining the current runtime messages.
The message window can now be positioned anywhere on the graphics screen, just likethe toolbars.
6.7 Free graphics
The Free graphics menu contains the following menu items:Multiple editingPolylineLineCircleArcRectangleEllipseFree graphics textRotateMove allCombineIncrease/DecreaseElement dataDimensioning startDimensioning endInsert image filesEdit image file
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
Graphics Editing Menu
223
6.7.1 Multiple editing
Use this option to change to a mode with which all the consecutively drawn graphicselements are combined into one object (with one insertion point).
In order to change between different element types (for example, a line and an ellipse)no longer press the key, but simply use the menu, keyboard, or toolbar to changeto the next element type. The definition of the currently combined graphics element isnot completed until you press .
6.7.2 Polyline / Line
The following steps are required to draw a line or polyline:
• Call up the function
• Use the left-hand mouse button or to specify the starting point.
• Specify the length and direction by using the cursor keys or the mouse.
• Use the left-hand mouse button or to specify the end point (or the angle of thepolyline).
• Press to abort the line function.
If you wish to draw a polyline, you can draw further sections instead of carrying out thefourth step. In both cases you can use the pop-up menu (right-hand mouse button) tocall up the element data in order, for example, to modify the line data.
The line function has no effect on automatic evaluation runs.
6.7.3 Circle
Entering a circle involves the following steps:
• Call up the function
• Use the left-hand mouse button or to specify the center.
• Specify the radius by using the cursor keys or the mouse.
• Use the left-hand mouse button or to confirm the radius.
Use the pop-up menu (right-hand mouse button) to call up the element data in order, forexample, to fill a circle.
System Manual EPLAN 5.40
224
6.7.4 Arc
Entering an arc involves the following steps:
• Call up the function
• Use the left-hand mouse button or to specify the center.
• Specify the radius and angle by using the cursor keys or the mouse.
• Use two left-hand mouse clicks or press twice to specify the end points of thecircle line.
Use the pop-up menu (right-hand mouse button) to call up the element data in order, forexample, to select the "Sector" display type.
6.7.5 Rectangle
Entering a rectangle involves the following steps:
• Call up the function
• Use the left-hand mouse button or to specify the first point.
• Specify the radius by using the cursor keys or the mouse.
• Use the left-hand mouse button or to specify the second point.
Use the pop-up menu (right-hand mouse button) to call up the element data in order, forexample, to modify the line data.
Only for "PLC overview" page types:This function draws an overview of those PLC inputs and outputs that canbe evaluated automatically. To this purpose cross-referenceable device-endterminals must be entered. This function is equivalent to that of a black boxon logic pages.
6.7.6 Ellipse
Entering an ellipse involves the following steps:
• Call up the function
• Use the left-hand mouse button or to specify the center.
• Specify the size by using the cursor keys or the mouse.
• Use the left-hand mouse button or to confirm the size and position.
Use the pop-up menu (right-hand mouse button) to call up the element data in order, forexample, to fill an ellipse.
Graphics Editing Menu
225
6.7.7 Free graphics text
This function is used to save texts on those pages of your project to which no text typeis assigned and which are therefore not taken into consideration during evaluations.
First determine the position at which the text is to be inserted, then enter the actual textin the dialog box that comes up, and specify the alignment (left-aligned, centered, orright-aligned), the size and the angle of the text by using the corresponding dropdownlists.
The Text coordinates group box displays the text coordinates specified by means of themouse or the arrow keys. These values can be overwritten, as necessary.
6.7.8 Rotate
The Rotate function can only be used for graphics elements. After having called up thefunction select the object to be rotated by using the mouse or the arrow keys.
The graphics object is rotated by 90° each time you click with the left-hand mouse but-ton.
Notes:
• If you call the function up four times, the object will be in the same position as at thebeginning.
• If several graphics elements are combined into one insertion point, all the elementscombined under the insertion point are rotated.
6.7.9 Move all
This menu option provides a particular function while a combined object is being de-fined or revised : This allows you to move the entire combined element while leavingthe insertion point at the original position.
6.7.10 Combine
You can combine several graphics elements at a later point into one element. First callup the Combine menu option. Click where you want the new insertion point of the ele-ments to be combined to be located. The cursor changes its shape, and you can nowdefine a rectangular area which must contain the graphics elements to be combined (tobe more precise: their insertion points). After you have pressed the left-hand mousebutton once more, the elements are combined into one object.
The individual elements can be edited later on, their size can for examplebe changed.
System Manual EPLAN 5.40
226
6.7.11 Increase / Decrease
With this function you can resize any graphics object by a freely selectable factor. Tothis purpose select the corresponding object by pressing the left-hand mouse buttonwhile the cursor is positioned on the insertion point of the object.
Now select the menu option Increase/Decrease. Enter the factor in the subsequent win-dow.
In order to simplify its use, an integer value is used at this point: if you want to zoomin, enter a positive value. If you want to zoom out, enter a negative value.
6.7.12 Element data
Once you have selected an Free Graphics element you can call up this function andview or edit the data of the current element in the corresponding dialog box. Dependingon the element type, the appearance of the element-specific tabs of this dialog varies.
6.7.13 Dimensioning start / Dimensioning end
With the Dimensioning start function you can define the point at which you want thecalculation to start.
The Dimensioning end function is used to define a dimensioning point and to specifythe position of the dimensioning number.
6.7.14 Insert image files
This function allows you to insert image files of the following file formats into graphicspages:
• *.BMP• *.GIF• *.JPG• *.ICO
Image files can only be selected from directories located below EPLAN4\N.
You can adjust the image size on graphics pages as well as change the dimension(height and/or width) of the image that is inserted.
A check box can be used to have a preview window displayed that shows the graphicsof the desired image.
Graphics Editing Menu
227
6.7.15 Edit image file
Use this function to edit image files that have been inserted. When the function has beenactivated, the cursor symbol changes it shape, and you can drag a frame around the im-age file. Afterwards the graphics editor linked to the respective file extension islaunched. The image shown in the graphics editor can now be edited.
This graphics editor is not included in the EPLAN scope of delivery.
6.8 Symbol
The Symbol menu contains the following menu items:Save/CancelNewAngle variantReviseImportImport basic symbolsExportSymbol dataDescribing blockIdentifying blockRelative insertion pointConnecting point
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
6.8.1 Save / Cancel
When you have revised or created a symbol, you can use this function to save the modi-fications and to exit the editing mode.
When first saving a new symbol the Symbol data window is opened in which youshould enter the data for the device designation, connection designations etc.
6.8.2 New
This function allows to create a new symbol. Open the symbol editor to this end.
After having activated this function determine the symbol position by clicking themouse button. In the subsequent dialog box select whether you want to create a newsymbol or an angle variant of an already existing symbol. (This prompt window will notbe displayed if you are editing the first symbol of an empty symbol file.)
When you are finished, specify whether you want the symbol to be entered in the sym-bol file and, if necessary, assign the necessary properties.
System Manual EPLAN 5.40
228
6.8.3 Angle variant
This function allows to specify the angle variant (this is a variant rotated by 90°, 180°,or 270°) of a symbol. Open the symbol editor to this end.
Then specify the insertion point for the rotated variant and select the symbol for whichyou wish to generate the angle variant. You can edit the angles of rotation to, for exam-ple, move text fields out of the way when you rotate a symbol.
When you are finished, specify whether you want the symbol to be entered in the sym-bol file and, if necessary, assign the necessary properties.
Symbols created using the Angle variant function are filed as subsymbols. You can thenuse the symbol editor functions to edit and modify the subsymbols.
6.8.4 Revise
Symbols consist of logical and graphics components. A symbol consists of:
• Identifying characteristics such as the symbol number, symbol name, commentarytext, and symbol type
• Insertion points
• Connecting points
• Symbol graphics
• Text fields for the "identifying" and "describing" block.
Using the Revise function you can edit the graphics components of a symbol.
6.8.5 Import
All the symbol files in the \EPLAN4\N\<customer code>\SYMBOL.EIP\<Symbol
file> directory are displayed for selection in the Import symbol name window. Selectthe desired symbol there.
6.8.6 Import basic symbols
Select this function if you want to import basic symbols (*.gsb) from the EPLAN4\Ndirectory. These consist of graphics elements as well as insertion and connecting pointsand overwrite the corresponding elements of the current symbol. However, the existingsymbol data are retained.
Graphics Editing Menu
229
6.8.7 Export
You can export symbols in order to import them into other symbol files. To do so, acti-vate the symbol editor by selecting the Symbol/Revise menu item. Click on the symbolto be exported and select the Export option from the Symbol pulldown menu.
A special file called SYMBOL.EIP is required in order to use the import/export function.When a symbol is exported for the first time this directory is automatically created be-low the \EPLAN4\N\<customer code> directory.
The file name given to the exported symbol is the designation of the symbol from thesymbol file, with no extension.
If you export the symbol M6 from the DIN_WUP symbol file, the following fileis created:\EPLAN4\N\<customer code>\SYMBOL.EIP\DIN_WUP\M6
6.8.8 Symbol data
Any symbol data you entered when the symbol was created can be modified subse-quently. Select the Symbol data option from the Symbol pulldown menu as soon as youhave activated the symbol editor. The Edit symbol window is opened.
The following fields are available:
Symbol name: The symbol name is the designation by which the symbol is identified inthe symbol file. This name is displayed in the symbol selection window during sche-matic editing.
Description: This field is for a freely selectable text entry that describes the symbol inmore detail.
DD: In this field enter the identifier that is taken into account during online DD assign-ment.
Symbol type: The symbol type is used during the evaluation of symbols for cross-references. In the case of terminals and contacts the input windows for the symbol prop-erties also change.
6.8.9 Describing block
The describing block (represented by B>>in the graphics editor) contains additional in-formation on a symbol. It consists of text fields for electrical characteristics, functiontexts etc.
Select this function to redefine the position of the describing block.
System Manual EPLAN 5.40
230
6.8.10 Identifying Block
The device is identified by its device designation. The text block of a symbol in whichthe DD is entered is therefore known as the "identifying block".
EPLAN uses the identifying block to differentiate the symbols within a project. Thedevice designation is written to the location in the schematic at which the identifyingblock was positioned.
Select this function to redefine the position of the identifying block.
6.8.11 Relative insertion point
You can use the symbol editor to shift a symbol’s relative insertion point. To do so, se-lect the corresponding option and drag the insertion point to the new position.
When you insert the symbol into the schematic later on, its relative insertion point islocated at the center of the symbol cursor.
6.8.12 Connecting point
The connecting point of a symbol defines the location at which a connection in theschematic will be made. If two symbols lie precisely above one another on the samepath, or if they are next to each other in the schematic, a connection will be drawn be-tween the two symbols if the points have the appropriate directions (autoconnecting).
Connecting points are inserted by using the Symbol/ Connecting point menu item andselecting the corresponding connecting direction.
6.9 Parameters
The "Parameters" menu contains the following menu items:ProjectPersonalWorkstation
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
Graphics Editing Menu
231
6.9.1 Project
In the subsequent menu of this menu item you can choose between the following pa-rameter fields:
• GraphicsOpens a dialog box in which you can set the graphics parameters
• Graphics displayOpens a dialog box in which you can set the general display parameters
• Symbol fileOpens a dialog box in which you can specify the symbol files
• Terminals / cablesOpens a dialog box in which you can specify the parameters for generating terminaland interconnect diagrams
• Contactor / cross-reference / wiringOpens the dialog box in which the parameters for the contactor selection, the cross-reference program, and the wirings are specified.
• PLC dataOpens a dialog box in which you can specify the parameters for the display of PLCdata
• Foreign languagesOpens a dialog box in which you can specify the parameters for foreign languagetranslation
• Message management / DD syntax checkOpens a dialog box in which you can specify the parameters for the management ofmessages that occur during automatic evaluation runs.
6.9.2 Personal
In the subsequent menu of this menu item you can choose between the following pa-rameter fields:
• GraphicsOpens a dialog box in which you can specify personal parameters for the graphics(such as Angle of type rotation, Schematics cursor, settings for the Clipboard etc.)
• Zoom levelsOpens a dialog box in which you can specify the parameters for the zoom levels onthe graphics screen
• IncrementsOpens a dialog box in which you can specify the parameters for the user-specific in-crements
System Manual EPLAN 5.40
232
• Cursor positionsOpens a dialog box in which you can specify the parameters for the user-specificcursor positions
• ColorsOpens a dialog box in which you can specify the parameters for the color settings onthe graphics screen
6.9.3 Workstation
In the subsequent menu of this menu item you can choose between the following pa-rameter fields:
• Define output devicesOpens a dialog box in which you can specify the parameters for the output devices
• GDI output formatOpens a dialog box in which you can specify the parameters for the GDI output for-mat
• DXF output parametersOpens a dialog box in which you can specify the parameters for DXF output.
6.10 Window
The Window menu contains the following menu items:CascadeTile horizontallyTile verticallyArrange icons
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
6.10.1 Cascade
When you use this option the current windows will be cascaded.
6.10.2 Tile horizontally
When you use this option the current windows will be placed next to each other.
Graphics Editing Menu
233
6.10.3 Tile vertically
When you use this option the current windows will be placed one below the other.
6.10.4 Arrange icons
Use this option to arrange the icons in the lower window area.
6.11 View
The View menu contains the following menu items:ToolbarsRefresh screenPage formatChange standardsAttachment previewDisplay scroll barsOpen zoomOpen zoom 80%Close zoomSet view to starting zoomIncrease quadrant zoomDecrease quadrant zoomSave zoom levelsActivate zoom levels
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
6.11.1 Toolbars
These menu items are used to activate and deactivate the display of the available tool-bars. Every pulldown menu of the graphics editing function has an own toolbar con-taining the functions most often used.
6.11.2 Refresh screen
This function refreshes the screen, updating the automatic functions such as autocon-necting.
6.11.3 Page format
These menu items allow you to reduce/enlarge the graphics screen to match the paperformats you use (for example, A2).
System Manual EPLAN 5.40
234
6.11.4 Change standards
This function toggles the display between the "DIN" and "JIC" schematic standards.The project data are not changed.
6.11.5 Attachment preview
When inserting, duplicating, and moving symbols and macros containing connectingpoints, an attachment (vertical or horizontal) which may result therefrom is displayed bya line. It is therefore possible to create an autoconnecting connection to a component,which is not located in the visible screen section, in a safe and reliable way.
If you use the orthogonal key [<] the dashed lines will help you to determine the heightof the other components in order to place the component at exactly the same height.
6.11.6 Display scroll bars
By using the scrollbars at the right-hand and lower window margin you have the possi-bility to move the entire screen section. The scroll bars can be deactivated via the Viewmenu in order to enlarge the visible screen section.
6.11.7 Open zoom / Open zoom 80%
An entire schematics page is displayed on the graphics screen. EPLAN offers you sev-eral options to enlarge a particular section of the display.
When you call up this function the shape of the cursor changes, and you can open awindow which defines the new screen section.
You can consecutively define several screen sections.The zoom function remains in effect until you exit graphics editing or the zoom func-tion.
Zoom levels can be saved.
6.11.8 Close zoom
This function returns the window for the screen section to the most recent setting.
If you have consecutively defined several sections, you will also have to repeat this pro-cess several times.
Graphics Editing Menu
235
6.11.9 Set view to starting zoom
This functions resets the graphics screen to the A3 default size unless you have definedanother start zoom.
You can save the current zoom setting for the next start of graphics editingby using the View/Save zoom levels/Save start zoom features.
6.11.10 Increase quadrant zoom / Decrease quadrant zoom
An entire schematics page is displayed on the graphics screen. EPLAN offers you sev-eral options to enlarge a particular section of the display.
• Pressing enlarges the quadrant of the screen in which the cursor is located.
• Pressing returns the screen section to its original size.
The zoom function remains in effect until you exit graphics editing or the zoom func-tion.
6.11.11 Save zoom levels
Use this function to define the starting zoom and ten further zoom levels (zoom levels"0" through "9") to have them always available.
6.11.12 Activate zoom levels
These functions are used to activate the previously defined additional ten zoom levels.
6.12 Help
The Help menu contains the following menu items:Module helpContents and indexAbout
Move the mouse onto the menu entry in order to have information about the respectivemenu item in the status bar.
System Manual EPLAN 5.40
236
6.12.1 Module help / Contents and index
These menu items are used to access the online help system of EPLAN.
When you call up the Module help an overview page is displayed for the currentlyloaded module together with general explanations on its function. From this point youcan often branch to other pages which contain detailed information.
Contents and index branches to the Help Navigator. Here a table of contents and anindex are available. You can change between them by clicking on the tab cards of thesame names. The table of contents and index provide rapid access to all the requiredinformation of the help system.
6.12.2 About
This menu item branches to a dialog box in which you can view general information onyour EPLAN installation (for example, version numbers of individual modules and en-vironment variables used by EPLAN).
Key commands
237
7 Key commands
This section provides an overview of the key commands which are available within thegraphics editing function.
Edit symbol properties
Define a window (selected area)
Change window corner
Increase the quadrant zoom
In quadrant zoom mode: Decrease quadrant zoomClose zoom
Display properties of an object
Set view to A1
Set view to A2
Set view to A3
Set view to starting zoom
Open zoom 80%
Edit part data of a component
Generate symbol macro
Duplicate window (selected area)
Insert ellipse
Search function: Jump to counterpiece
On a connecting point: Change the line type for a potential
Activate/Deactivate display of the insertion points
Insert circle
Insert polyline
Insert macros
Update line types in case of differing potentials
Activate/Deactivate page offset
Position cursor, i.e. jump directly to the path and position
Insert rectangle
Set increment
Insert text
System Manual EPLAN 5.40
238
Combine elements, i.e. create an insertion point
Move
Create variable macro
Create combined macro
Open zoom
Save pages
Angle down, right
Angle down, left
Angle up, right
Angle up, left
Node, down
Node, up
Node, right
Node, left
Insert symbols
Delete contents of a window (selected area)
Left-hand screen edge
Right-hand screen edge
Next page
Previous page
Cancel
Insert device-end terminals
Insert potential arrows
Insert cable definition
Insert shieldings
Insert wiring definition
Insert jumper
Open zoom
Drawing Black Boxes
Move screen section to the left
Move screen section to the right
Move screen section upwards
Move screen section downwards
Key commands
239
Refresh screen
to Activate zoom levels 0 through 9
Alternative text display
Move DD
Copy elements to the EPLAN Clipboard
Free graphics: Element data
Page properties
Call up selection of search function
Insert arcs
Plot pages via HPGL
Insert elements into search database
Copy pages
Free graphics: Move all
Create page
Open pages
Print pages
Read in backup pages
Free graphics: Rotate
Save pages
Dimensioning end
Paste elements from the EPLAN Clipboard
Mouse increment on/off
Cut elements and copy them to the EPLAN Clipboard
Repeat last step
Undo last step
Activate help system
Insert lines
Insert PLC end terminals
Close graphics editing
Create window macros
Duplicate window (selected area)
Insert macros
Create path/PLC macro
System Manual EPLAN 5.40
240
Create page macros
Insert DIN box
Insert symbol macros
Jump to left-hand path
Jump to right-hand path
Jump to the insertion point at the top of the current path
Jump to the insertion point at the bottom of the current path
Symbol editing: Connecting point above
Symbol editing: Connecting points below
Symbol editing: Connecting point above/below
Symbol editing: Connecting point on the right
Symbol editing: Connecting point on the left
Symbol editing: Connecting point on the left/right
Start dimensioning
Symbol editing: Describing block
Edit messages.
Search function: Next entry
On a connecting point: Change line type for connection
Symbol editing: Identifying Block
Display parts data at components
Panel layout
Symbol editing: Edit symbol data
Symbol editing: Relative insertion point
PLC connection at terminal
Interrupt the connections
Search function: Previous entry
Position cursor, i.e. jump directly to the path and position
Draw circles
Grid on/off
Display symbol extensions
Activate/Deactivate page offset
Change standards (DIN/JIC)
Left-hand insertion point on same level
Key commands
241
Right-hand insertion point on same level
Upper insertion point in same path
Lower insertion point in same path
System Manual EPLAN 5.40
242
Index
243
8 Index
A
ASCII format...............................................................................................................90
B
Bill of materials.........................................................................................................118
C
Cable type file ...........................................................................................................107Cables .......................................................................................................................104Call-up parameters ....................................................................................................141Command line ...........................................................................................................141Comment.....................................................................................................................90Connection bill of materials.................................................................................97, 101Connector-type file....................................................................................................108Console .....................................................................................................................141Contact cross-reference .............................................................................................100Contactor selection ......................................................................................................97Contactor specification file ........................................................................................102Control characters .......................................................................................................94Control command ........................................................................................................92Cross-reference............................................................................................................97
D
Data area .....................................................................................................................92Data field.....................................................................................................................90
alphanumerical.........................................................................................................92definition..................................................................................................................95numerical .................................................................................................................91
Data lines ....................................................................................................................99Documentation database............................................................................................113
E
EDOCselection criteria .....................................................................................................118
EPLAN5.INI .............................................................................................................140Error number ...............................................................................................................96Evaluation run .............................................................................................................97
System Manual EPLAN 5.40
244
F
F code ...................................................................................................................91, 97Field description..........................................................................................................90Field number ...............................................................................................................91File number .................................................................................................................91Font.............................................................................................................................99Footer area ..................................................................................................................92Form description .........................................................................................................90Function text .............................................................................................................104
G
GDI.............................................................................................................................94
H
Header area .................................................................................................................92Headers .......................................................................................................................99
I
ID................................................................................................................................95Initialization file ........................................................................................................140Interconnect diagram...........................................................................................97, 106
J
Jumper symbol ..........................................................................................................104
L
Labeling ....................................................................................................................126Phoenix Mark...........................................................................................................98standard....................................................................................................................98
Language file.............................................................................................................111List output ...................................................................................................................98Log form ...................................................................................................................118
M
Message ......................................................................................................................96number.....................................................................................................................96
Message management..................................................................................................98Message management file..........................................................................................111MS DOS input command...........................................................................................141
Index
245
P
Page ..........................................................................................................................104Parameter program
output parameter ......................................................................................................94Phoenix Mark Labeling .............................................................................................130Point commands ..........................................................................................................94Potential cross-reference............................................................................................100Print form....................................................................................................................89Printer .........................................................................................................................94
font ..........................................................................................................................94Printer parameters
point commands .......................................................................................................94
R
Registry.....................................................................................................................140Report processor..........................................................................................................89
S
Special codes...............................................................................................................91Special text................................................................................................................179Standard labeling.........................................................................................................98Starting area ..........................................................................................................92, 99Strip designation........................................................................................................104SYSTEM.ERR ............................................................................................................96
T
Target........................................................................................................................104Terminal bill of materials ....................................................................................97, 108Terminal diagram ................................................................................................97, 103Text
fixed.........................................................................................................................90Translation ..................................................................................................................98
V
Variable.......................................................................................................................91
W
Wire number .............................................................................................................104Wiring list ...................................................................................................................97Wiring List ................................................................................................................101