system overview - pejawar electronicspejawarelectronics.com/catalogs/nexgen 5000...
TRANSCRIPT
A U T O M A T I O N P E O P L E
AN ICON OF THE FUTURE
TM
PLC
TM
S Y S T E M O V E R V I E W
SaIient Features : Nexgen 5000 CPU...................................................... 2-3
CoDeSys : PLC Program Development Suite......................................... 4-6
Modbus Connectivity .............................................................................. 7-8
Data Exchange via Modem......................................................................... 9
Fault Message Alert ................................................................................. 10
Servo Connectivity .............................................................................. 10-11
Nexgen Slave .......................................................................................... 12
Micro PLCs in Multidrop Connectivity ....................................................... 12
Variable Frequency Drives in Multidrop .................................................... 13
Nexgen 522x Series of CPU ................................................................ 16-19
Nexgen 521x Series of CPU ................................................................ 20-23
Ladder Diagram (LD) ............................................................................ 25
Instruction List (IL)...................................................................................25
Structured Text (ST) .............................................................................. 26
Function Block Diagram (FBD) ............................................................. 26
Sequential Function Chart (SFC) .......................................................... 26
Continuous Function Chart (CFC) ......................................................... 27
Dynamic Data Exchange ........................................................................ 28
Sample Trace Function with Graphical Display ..................................... 29
Process Visualisation for On Line Testing .............................................. 30
POUs & Data Types .......................................................................... 30-31
HMI Connectivity ................................................................................ 46
Nexgen CPU 5000 Series .................................................................... 47
Base & Expansion Plates ..................................................................... 48
Input / Output Modules ..........................................................................48
Power Supply Modules ......................................................................... 48
Introduction : Nexgen 5000 PLC............................................................................1
Product Highlights
Nexgen CPU 521x & 522x : Application Schemes
Specifications : Nexgen 521x & 522x Series of CPUs ...................................14-15
Detailed CPU Information
CoDeSys : Programming Software for Nexgen 5000 Series
CoDeSys: Instructions & Libraries .............................................................. 32
Communication Basics ................................................................................ 32-35
Base & Expansion Plates ................................................................................. 36
Power Supply Modules ..................................................................................... 36
Digital I/O Modules ....................................................................................... 37-38
Analog I/O Modules ..................................................................................... 38-41
Counter Modules ............................................................................. 42
Smartline Jr. & Sr. ............................................................................................. 43
E-Series Operator Terminals ....................................................................... 44-45
Ordering Information
CONTENTS
IntroductionINTRODUCTION
1
IEC
611
31
-3 Messung Systems, a leading pioneer in indigenous PLC in India, has constantly innovated to achieve global
standards in designing and manufacturing PLC products. With pride, it has now launched a high performance
series of world class CPUs viz. Nexgen 5000; coupled with basic building blocks of its earlier launched and
established Nexgen 4000 PLC. This Nexgen 5000 PLC family offers a wide range of CPU variants, with
IEC 61131-3 compatibility, having performance excellence and Windows based programming software.®
In the earlier days of industrial automation, application specific machines or process plants were designed with
huge control panels having Relay Contactor Logic and Hardware Timers, Counters, Thumbwheels. These were
very bulky in size, complex for fault finding, less reliable with limited and unpredictable life. Similarly these
systems were very rigid in terms of any up-gradation.
This has evolved concept of Programmable Logic Controllers (PLC) which were compact in size, having better
edge over earlier electro-mechanical devices. PLC implementation has resulted in several benefits like:
minimized panel and wiring volume, expedited program development, reliability of operations with an improved
life, PLC re-usability across the applications (conditionally), easy and quick fault finding, and ease of interface
with HMIs, SCADA like external devices.
Over the time, only application specific hardware and software products were developed by various vendors,
which addressed the problem of compatibility and portability. This has initiated necessity of products
standardization in terms of hardware as well as software.
Subsequently, International Electro-technical Commission worked upon complete design of PLC, which
comprised of hardware design, installation, testing, programming and documentation. Several inputs from
various machine manufacturers, end-users and research institutes has evolved five part IEC 61131 standard.
This international standard IEC 61131-3 is the first substantial endeavor to standardize programming languages
for industrial automation. It emphasizes on consistent method of PLC programming which encourages the
development of quality software. IEC 61131-3 provides tools to improve intrinsic quality of software in terms of its
persistent correctness, integrity, reliability, robustness, modularity, flexibility and safety. It also deals with
programming, installation and maintenance phases of software development projects in industrial control.
Similarly, with the growing Industrial Automation, industry has started facing typical problems of PLC
processing speed, memory, handling of a complex or very big program, logic re-usability, avoiding
duplicate variables in programming, choice of programming language selection as per application, user
friendly software along with documentation, standardized program interface.
IEC 61131-3 compatible programming yields Rapid Application Development.
Nexgen 5000 series of CPU family is programmed with CoDeSys, the Windows based, IEC 61131-3
compatible programming software.
®
Evolution Of PLCs on IEC 61131-3 Platform
AN ICON OF THE FUTURE
PLC
an
ico
no
fth
efu
tu
re
Max. 32
modules
Nexgen 5000 PLC : Product Highlights
max.
upto
9 mtrs.
2
NEXGEN
Nexgen 5000 PLC with full capacity
NEXGEN 5000 PLC : AN ICON OF THE FUTURE
� A truly modular PLC
�
�
�
�
�
More I/O Capacity - 1024 Inputs / 1024 Outputs
Enhanced Data Memory - 160 KB
64 KB - Data Memory (Selectively retainable)
32 KB - Marker Memory (Selectively retainable)
64 KB - File Marker Memory (Super retainable)
Better processing speed - Boolean - 0.4 sec
Word - 1.2 sec
Higher program memory -
Application Program Code - 256 KB
Application Source Code - 1 MB
Wide assortment of Analog modules - Thermocouple,
RTD, Fast Analog Input and Output Modules
µ
µ
ENHANCED FILE MARKER MEMORY
�
�
�
Super retained battery backed up memory
Not cleared by cold start or even after program change
Large capacity of 64K bytes
PLUGGABLE KEYBOARD DISPLAY UNIT
The Keyboard Display interface is a extremely user & maintenance
friendly tool, which provides 4-character alpha-numeric display
with 6 keys key-pad.
User has an optional choice of pluggable keyboard display
Highlights :
�
�
�
�
�
�
�
It has built-in freely programmable 6 functions keys &
4 character alphanumeric display
The keyboard display can be used as a self diagnostic tool.
This is helpful for assistance in :
Displaying fault messages
Displaying systems messages
Viewing / modifying PLC variables
Redirection of Digital I/O pointsan
ico
no
fth
efu
tu
re
2
IMPROVED PG PORT OPERATION
�
�
�
�
�
Supports RS-232C interface
Dual operation - Program mode or Open Protocol
Auto detect programming cable plug in & switch
to program mode
User memory cassette interface
Supports all protocol FBs
(OPTIONAL)
Fig : Set Up to download the Program to Memory Cassette
3
Programming cable 9910Cassette adapter
Memory
Cassette
5 VDC Power supply
To 230 VAC power supply
30 VAC to 5 VDC
power supply
PC COMPort
Bootstrap
Loader Tool / CoDeSys
Nexgen 5000 PLC : Product Highlights
APPLICATION PROGRAM DOWNLOADING
�
�
�
First, cassette needs to be set using PC based software 'Bootstrap Loader Tool'.
For transferring a program, memory cassette is plugged in to serial port-1 of PLC. Now pressing a
push button twice, initiates the 'Program Transfer'.
If an application program code is valid, green LED will be ON. If the application program code
is blank, green LED blinks with 1Hz frequency. In case of invalid application program, red LED will
be ON.
�
�
�
The display and keyboard are freely programmable for application specific functionality. Display and
keyboard is accessible in the application program through the system variables. Using these system
variables, the user can develop their own function blocks to handle display and keypad as per the
application need
Standard FB library for I/O/M Monitoring, Redirection of Digital I/O points are also available.
The Keyboard Display Unit can be fixed to / removed from, the Processor module during the
module powered ON condition.
.
COMPACT & HANDY MEMORY CASSETTE :
The memory cassette is used to store an application program code and
source code. It is a flash PROM type of intelligent memory cassette.
The cassette is compatible with all the Nexgen 522x series CPUs and it
is available in various memory sizes. The application program code
and source code can be downloaded to processor module (Nexgen
CPU) from the cassette.
The front side provides a push button and two LED indications for user
interface. The backside provides 9-pin D female connector for the
interface with PC or processor module.
Application Program Transfer : CoDeSys to Memory Cassette
IEC
61
13
1-3
CoDeSys
4
PLC Program Development Suite
ST : Structured Text
LD : Ladder Diagram
FBD :FunctionBlock Diagram
INCREASED PROGRAMMING FUNCTIONALITY
�
�
�
�
Online functionality : Program modifications, Monitoring of all
variables, Power flow monitoring
Offline simulation now possible (limited)
Variable trace function with graphical display
Visualization (Limited for process monitoring)
ADVANTAGE - BUILT IN PROTOCOL FUNCTION BLOCKS
�
�
�
�
�
Modbus RTU Slave / RTU Master
Nexgen Slave
XMP8-10 Micro PLC Master
Frequrol - Inverter
Printer
Windows Based IEC Programming Software
IEC 61131-3 : A GLOBAL STANDARD
�
�
�
Better Structuring of large programs
High Reusability
Combination of ladder program and high level programming language
VARIETY OF PROGRAM EDITORS
�
�
�
�
�
�
LD : Ladder Diagram
ST : Structured Text
FBD : Function Block
Diagram
IL : Instruction List
SFC : Sequential
Function Chart
CFC : Continuous
Function Chart
HIGH PERFORMANCE EVENT TASK SUPPORT
�
�
�
Execution of POU on an event occurrence (Immediate action, as per priority)
Dynamic attach / detach POUs to events
Global masking via application program
REMOTE PROGRAMMING VIA MODEM
re
mo
teo
pe
ra
tio
n
5
New Possibilities of Remote Operation
Remote programming / on-line monitoring of Nexgen-5000
PLC via dial-up modem is possible on PG port. The PLC
programming software- CoDeSys can communicate with
Nexgen-5000 PLC via modem.
Users can remote Login via dial-up modems.
The modem used at PC end could be internal modem or it
could be external modem. The communication speed
depends upon the line conditions and the link may establish
at lower Baud-Rate than default setting of 38.4kB.
Highlights :
Project, source upload/download extended via modem
On-line project modification is possible
Remote on-line debugging via modem support
�
�
�
�
PSTN
Network PC
Configuration : Communication Parameters
Dial-up modem Dial-up modem
Port - 1,RS-232 C CoDeSys
REMOTE PROGRAMMING VIA LAN :
re
mo
teo
pe
ra
tio
n
6
New Possibilities of Remote Operation
In this setup, the programming software 'CoDeSys' is running on PC1 and the gateway server is
running on PC 2. The link between CoDeSys & Gateway Server is established via TCP/IP bus. The
Nexgen-5000 PLC is connected to COM port of PC2, the link between Gateway Server & PLC is
established via RS-232 bus. Or otherwise the PC2 can be directly interfaced with PLC via
programming cable.
The PLC programming software-CoDeSys can
communicate with Nexgen-5000 PLC via TCP/IP
connection.
Gateway Icon
PC2 PC1
Nexgen 522x CPU
P : PG Port, RS 232C
P
COM Port
TCP/IP (LAN)
7
Network having 31 nos. of Enercon Energy Meters as slave connected to one Master Nexgen-522x CPU, using MODBUS Master.
Master : Nexgen 5000 PLCSlave : Enercon Energy MeterP : Port - 2 / 3, RS 485
Slave-1 Slave-2 Slave-31
Master
P
MODBUS MASTER
mo
db
us
co
nn
ec
tiv
ity
Nexgen 5000 PLC Based Application Schemes
Master FB : This FB handles serial communication with RTU Protocol as master device. It is
useful to interface HMI, SCADA as a slave with Nexgen 5000 PLC. PLC communication can be
established with one PLC as Master and other(s) as slave(s). It can also be used to have CPU as data
logger to collect the data from Energy meters, VFDs etc.
User need not know the MODBUS protocol.
MODBUS
Protocol implementation is physical layer independent i.e. it can be used with RS232C, RS422 or
RS485.
Communicates with any third party MODBUS RTU slaves inclusive of Messung PLCs with the
MODBUS RTU_Slave FB
Easy interface with various SCADA and HMI packages as slaves is possible with appropriate FBs. No
need to develop any special driver.
Easy connection to multiple Beijer E-terminals with it's MODBUS Slave driver
Easy application interface by defining data exchange records with various stations
Allows exchanging data via I, Q and M devices in Nexgen 5000 with MODBUS devices in various
stations
Data exchange records can be grouped and called in manual, auto-cyclic and super cyclic modes.
Flexibility in data exchange records programming.
Programmable Retry and Time-out facility if a station fails to respond.
Supports variety of baud rates to suit the application needs.
Highlights :
�
�
�
�
�
�
�
�
�
�
�
MODBUS CONNECTIVITY MADE EASIER
�
�
�
�
MODBUS Master and MODBUS Slave
Nexgen 5000 series PLC provides MODBUS connectivity as software feature rather than any
hardware module. This is quite fascinating feature for every application developer.
While communicating with SCADA or other Nexgen 5000 PLC, one may implement MODBUS Slave.
Similarly, while communicating with the field devices like relays, energy meters (which implement
MODBUS), PLC implements MODBUS Master.
MODBUS Slave FB :
MODBUS MASTER AND MODBUS SLAVE
mo
db
us
co
nn
ec
tiv
ity
Nexgen 5000 PLC Based Application Schemes
8
It emulates MODBUS slave functionality. This FB handles serial communication with MODBUS RTU
Protocol as slave device. The RTU slave FB is useful to communicate with any external master PLC,
SCADA or DCS systems. Communication speed can be up to 56Kbps.
User need not know the MODBUS protocol
Highlights :
Protocol implementation is physical layer independent i.e. it can be used with RS232C, RS422 or
RS485.
Communicates with any third party MODBUS RTU master or Messung PLC with MODBUS
RTU_Master FB Easy connection to various SCADA and HMI packages. No need to develop any
special driver.
Easy connection to Beijer E-terminals with it's MODBUS Master driver
Allows to exchange data via I, Q and M devices in Nexgen.
Ready to use FB with few parameters to define to go
Flexibility in station number programming.
Supports variety of baud rates to suit the application needs.
�
�
�
�
�
�
�
�
These FBs are useful -
�
�
�
To interface Beijer make E terminals as master or slave with MODBUS RTU Driver.
To interface any SCADA software as master or slave which supports MODBUS RTU protocol.
For PLC to PLC communication in Nexgen 5000 PLC. One PLC can be a Master PLC and other/s can
be slave/s.
Slave-1 Slave-2 Slave-31
Master
P P P
P
OR
Master : Nexgen 5000 PLCSlave :P : Port - 2 / 3, RS 485
Nexgen 5000 PLC
Converter forRS 232C to RS 485
Network having 31 Nos. of Nexgen 522x PLCs as slave connected to one Master Nexgen 5222-B0 CPU, using MODBUS Master andMODBUS Slave.
Multiple PLC Data Collection Via Modem
9
mo
de
mc
on
ne
cti
vi t
yNexgen 5000 PLC Based Application Schemes
Multiple PLCs can be connected to PSTN network via modem. Multiple PLCs can communicate with one
or more PC/PLC at a time through modem. Either of PLC / PC or both can initiate a communication.
Once the communication is established, Protocol FB like MODBUS, Nexgen or Micro can take over a
control for Data Exchange.
PLC to PLC Connection Via Modem
PLC initiates a call via modem FB. Now, modem FBs establish a communication between any of the two
Nexgen-522x PLCs ( As shown in above figure ). Once the connection is established, the control is
passed to protocol FBs like MODBUS, Nexgen protocol.
The calling line / connection status can be monitored and failure of the link can be detected. In case of
lines getting busy or unreachable auto redial, auto retry is possible. Dial-In facility with auto connect
modems & Dial-Out predefined number is also feasible. Various communication speeds can be gained
based on line conditions. Connect, Initialize and Hang-up sequence for the modem can be also
controlled.
Nexgen-522x PLC, which initiates a call will implement Dial-Out FB. While PLC at other end i.e.the
responding PLC, will implement Dial-In FB.
Note : The calling PLC ( i.e. PLC which has initiated a communication call ) can be a Master or Slave.
Multiple PLC Data Collection Via Modem
DATA EXCHANGE VIA MODEM
PSTNNetwork
Dial-up modem
Dial-up modem
Dial-up modem
Dial-up modem
PLC 1
PLC 2
PLC 3
PLC : Nexgen with 522x CPU
PC
SCADA
SCADA package withprotocol driver andmodem connectivity
PSTNNetwork
Dial-up modem
Dial-up modem
Dial-up modem
Dial-up modem
PLC 1
PLC 4
PLC 3
PLC : Nexgen with 522x CPU
PLC 2
10
CONVENIENT FAULT MESSAGE ALERT
se
rv
oc
on
ne
cti
vit
y
SERVOS NOW CONNECTABLE
Nexgen 5000 PLC Based Application Schemes
Special CPU varieties with HSC/PTO and motion control :
The special features offered are High-speed counter (HSC) & Pulse train output (PTO). Processor
modules with following extensions support added functionalities. These functionalities are
summarized as below.
A Typical Nexgen 5000 PLC Set-up with CPU-5214
PLC
Interface Cable 4944
MRJ2-A AC Servo Motor
Patch Panel4960
PLC : Nexgen 5000, with 5214 or 522x - P4
The relevant FBs can be implemented, as per application requirement.
Dial up modem connected to Nexgen 522x CPU , sendsNumeric Messages on pager, or only Ring Alert on mobile.
GSM modem connected to Nexgen 522x CPU, sendsSMS (text messages )
MobilePLC
P
GSM modemwith SIM card
Pager
NumericMessage
Mobile
PSTN
Network
PLC
P
Dial-up modem
PLC : Nexgen 522xP : Port 1 / 2 / 3 , RS-232C
PLC : Nexgen 522xP : Port 1 / 2 / 3 , RS-232C
11
se
rv
oc
on
ne
cti
vit
yNexgen 5000 PLC Based Application Schemes
Its based on PLC open motion control FB guidelines. It's a universal method of motion control
irrespective of front-end interface.
HSC PTO features supported in Motion Control applications :
HSC, Potentiometer position input, Infrared position input
Pulse Train Output, Analog output, PWM output, Motorised potentiometer control
(PTO) features supported in Motion Control
Point To Point Positioning
Absolute and Relative Positioning
Acceleration / Deceleration control
Emergency stop with controlled deceleration
Velocity Control FBs
Positioning Profile Handling
Co-ordination Interrupts
These special modules can be used in variety of applications like Packaging, Printing, Cut to length,
Bottling, M/C tools etc.
�
�
�
�
�
�
�
�
�
�
CP522x P2 : 1 HSC + 1 PTO + 2 Interrupt I/Ps (Under Development)
CP522x P3 : 2 PTO channels + 2 Interrupt I/Ps (Under Development)
CP522x P4 : 2 ch HSC + 2 ch PTO + 2 Interrupt I/Ps
There are two variants in the patch panel
a. PNP type ( 4960 ) : The output of PTO is PNP type & can be interfaced to 24V signal level.
b. Differential type ( 4962) : The output of PTO is differential type & can be interfaced to
Rs422 differential signal level
:
Nexgen 5000 CPU provides 2 channels of HSC I/P and 2 channels of PTO O/P. To handle these
hardware resources the OS of Nexgen 5000 CPU supports external FB library PTO lib.
HSC-PTO Function Library
Axis1
Axis2
DataIn
DataOut
H/WDriver
FBs
Axis_RefData
PLC openMotion Control
FBs
H/WDriver
FBsSchematic diagramdepicting motion control
Under Development
MC-MoveAbsoluteMC-MoveMC-MoveVelocity
MC-StopMC-ReadActualPosition
MC-ReadParameter
MC-MoveHome
Relative
MC-ReadBoolParameterMC-WriteParameter
MC-WriteBoolParameter
2 Axis_InterpolationElectronic_Gearing
PhasingCAM_Control
HSCMFIP
AnalogPot
PTO
CANbus
PWM
PTO
AnalogOut
CANbus
NEXGEN SLAVE
12
MICRO PLCs IN MULTIDROP CONNECTIVITY
HM
Ic
on
ne
cti
vit
yNexgen 5000 PLC Based Application Schemes
Nexgen slave FB is provided in FB library. By defining input parameters of FB, user can select
communication port and communication parameters to establish communication with HMI. This FB
handles serial communication with Nexgen 5000 as slave device and interfaces HMI, SCADA as a
Master.
Terminals
and SCADA with Nexgen Drivers
56K for connecting E-Terminals or SCADA
This FB is useful to interface -
Messung make HMIs SMARTLINE and SMARTLINE
Beijer make E terminals with NEXGEN 4000 Driver
SCADA software which supports Nexgen protocol
It emulates Nexgen 4000 HMI port protocol
Allows connection to Smartline, E-
The HMIs or E-Terminal can be attached to any
Com port and can be instantiated as desired
Communication speed can be set, up to
Modbus RTU is used for serial Communication
Nexgen 5000 CPU works as Modbus Slave
Memory mapping of I(X), Q(Y), M(M&D) supported
Sr Jr
HMI & E TERMINAL CONNECTIVITY
Graphic Operator Terminal ( GOT ) Connectivity
GOT-F Series and A Series are supported
�
�
�
�
�
�
�
�
�
�
l
Master
Sr. HMIE-Series
Operator Terminal
Mitsubishi MakeGraphic Operator
Terminals
Slave
F 940F 930
Here, 31 Micro PLCs are networked with one master, where master can be :
- Nexgen 5000 PLC using RS 485 port
- PC with SCADA
Here, FB used is XMP8_10Master.
Network having 31 Micro PLCs (XMP81x Series i.e. XMP-8 11/12/13/15/16/17) are connected to a Master Nexgen 5000 PLC, where PLCimplements XMP8_10 Master block.
Master
Slave-1 Slave-2 Slave-31
P
OR
Master : Nexgen 5000 PLC or PCSlave : Micro PLCP : Port - 2 / 3, RS 485
PC
Converter forRS 232C to RS 485
13
co
mb
inin
gs
tre
ng
ths
Nexgen 5000 PLC Based Application Schemes
VARIABLE FREQUENCY DRIVES IN MUTIDROP
Master
P
Slave 1
HMI
Slave 2 Slave 3 Slave 31
Master : Nexgen 5000 PLC or PCSlave : Freqrol (Mitsubishi make Inverter)P : Port - 2 / 3, RS 485
�
�
�
�
�
�
�
�
�
�
�
User need not know the Inverter interface protocol. It Reads/Writes data to multiple inverters.
It can have direct serial inverter control from user program
Transfer data to central SCADA / HMI on other port
Extendible to serial connection up to 31 inverters
Fast response to set point changes
Direct Inch, On/Off control
Cyclic updation of actual data from inverters
Individual Inverter Error handling
Automatic communication recovery as soon as Inverter is switched ON
Inverter data may be modified or controlled from HMI, SCADA or result of application program
Communication on 9.6K or 19.2K baud
Easy access to parameters via structured data for each inverter.
Support some On-demand command execution such as initialisations etc.
Predefined Parameters Handling (selectable)
- Write control : Start, Stop, Reset, Set Frequency.
- Read info : Frequency, Voltage, Current, Inv-status.
�
�
Nexgen5222- BO interfaced with Beijer HMI E-Terminal on 2'nd port and network of Mitsubishi make Inverter is interfaced with 3'rd port.
CPU Specifications
14
SPECIFICATIONS :
NEXGEN 521x & 522x SERIES OF CPUs
RemarksSpecificationsAttributes
16 bit Micro controller
1 Sec
-
User can modifywith System variable _wLimitMaxScan
Processor
ProcessingTime
MaximumScan Time
Boolean ( Move )
Word ( Move )
0.6 µSec
1.2 µSec
Standard
Software
(Version)
IEC 61131-3
CoDeSys Windows ® based
Programming
Language
LD
IL
ST
FBD
SFC
CFC
Instruction List
Structured Text
Function Block Diagram
Sequential Function Chart
Continuous Function Chart
Ladder Diagram
CPU 521x CPU 522x
Permissible up to
Default setting
0.4 µSec
1.2 µSec
250 mSec
All available Version 2.3* * Recommended Version 2.3 or onwards
64 KBApplication Memory For run time execution256 KB
Remote Programming Supported, using dial-up modem
-
-
32 KB
15,872 bytesMarker(Retainable)
Used as application data memory.Essentially consumed by instances ofFBs (e.g.Timers,Counters etc.)
Memory available for HMI / SCADAConnectivity
MemoryConfiguration(RAM)
Data(Retainable)
64 KB
32,256 bytes
-File Marker(SuperRetainable)
Memory Retains after cold start oreven after a program change.
64 KB
64 KBApplication ProgramCode
MemoryConfiguration( Flash :On-board )
256 KB
DataMemory
-
On-lineFeatures
Source codeModifications
Write / ForceVariables
Watch-Receiptfor PLC Variables
Supported
Supported
Supported
192 KBApplication ProgramSource Code
128 KBOperating System
Program Execution is through RAMAutomatic program transfer takesplace from Flash to RAM, atevery power on.
Program Execution
Marker bits
Data Memory
I/O
Supported
Supported
Not Applicable
Except MB0 to MB127
Retentivity
1 MBCan be uploaded along withcomments, with password protection
Not ApplicableUsed for storing an application programcode and an application source code.
MemoryCassette 256 KB
Type Lithium,3 V DC
521x has plugaable battery522x has on-board battery
BatteryBack-up No
2 Years
Re-Chargeable
Life
Ni-MH, 3.6 VDC, 800 mAH
Yes
6 Months**
* If powered on, battery starts charging
** If PLC is not powered on,battery gets discharged
-
Bootstrap Loader is a PC basedutility for downloading OS
- Supported
CPU Specifications
15
RemarksSpecificationsAttributes
CPU 521x CPU 522x
Project File
POU
Source CodeUploading
ApplicationProgramSecurity
Password Facility Read / Write Password available
TaskSupported
Cyclic
Periodic Event
Interrupt Event
Available
-
-
Available
Available
Available
Timers
Numbers
Resolution
Max. Range
Retentivity
Unlimited *
1 ms
24.855 Days
User Selectable
*Limited by available data memory.
Counters
Numbers
Max. Count
Retentivity
Unlimited *
65536
User Selectable
*Limited by available data memory.CUP, CDN, CUD
I/O CapacityInput points
Output points
1024
1024
Presently supported 1024 I/O points( Free Mix )
Rack
Capacity
Basic
Expansion
1
3
Racks are available accommodating3 I/O / 5 I/O or 8 I/O Modules
Keyboard Keyboard & Display are programmablethrough an application program* 522x series has Pluggable Display-Keyboard, as against 521x series.
8 Keys 6 Keys
Run , Stop ,Single CycleOperating Modes
Diagnostic
ToolsUser Configurable
Display 4 Character Alpha-numeric
Run
CPU
I/O
MEM
LOW BAT
DiagnosticLEDIndications
Green
Red
Red
Red
Red
Communica-tion Ports(All ports arewith OpenProtocol )
Port 1
Port 2
Port 3
RS 422
RS 232C
CPU 522x has
identical ports (2'nd/3'rd)
Default as programming port(PG)
Communica-tion Baud Rate
Up to 57.6 Kbps User selectable
Communica-tion BufferMemory
For Transmission
For Reception
256 Bytes
256 Bytes
RS 232C/
RS 422/485
(Identical Ports)RS 232 C Or
RS 422/RS 485
NoiseImmunity
Power Supply
Serial Ports
As per
IEC 1000 - 4 - 4
2 KV conductive noise
1 KV capacitive coupled noise
CurrentConsumption At 5V DC 600 mA
-
-
-
-
TON, TOFF,TP
CPU Specifications
16
* CP 522x P2, CP 522x P3 and CP 522x P4 requires a patch panel and cables.
The processor module supports three independent serial communication ports with well defined availability criteria as :
CP 5222-P4Special CPU
CP 5222-B03 port CPU
CP 5221-P4Special CPU
CP 5221-B02 port CPU
CP 5220-P4Special CPU
CP 5220-B01 port CPU
NEXGEN 522x SERIES OF CPUs
Nexgen 521x and 522x series of PLCs is an outcome of fundamental thought of modular PLC with IEC 61131-3 compatible CPU
and windows based programming software. This definitely has widened the scope of communication and interfacing multiple, as
well as variety of third party devices.
To reinforce the standardization, not only in programming techniques, but in hardware also, Messung Systems has launched a
step ahead, Nexgen 522x series of CPUs, with further faster and memory efficient CPU.
In nutshell, Nexgen 522x series of CPUs has an edge over existing Nexgen 521x series of CPUs in terms of ports standardization
and enhanced memory..
Nexgen 522x series itself has 6 CPU variants. This wide range of CPU empowers user to select a CPU as per application specific
requirement, with enhanced memory viz. feature wise as well as capacity wise.
This has a well defined ordering code system, which explains the complete portfolio of a Nexgen 522x series of CPUs.
This essentially has Standard CPU, 3 Port CPUs (2 No.), Low cost CPU and Special CPU.
Nexgen 522x : CPU Variants And Communication Ports
The processor module supports three independent serial communication ports with well defined availability criteria as :
All the serial ports are provided on-board and are open for user to define communication parameters and handle serial
communication using function blocks as per requisite protocol.
The communication port-1 is RS 232C hardware interface port and it automatically gets assigned for programming through
programming software 'CoDeSys', if programming cable (having an ordering code 9910) is connected. Otherwise it is open for user
to define protocol and handle serial communication through application program. Port 1 is used to transfer an application program,
from memory cassette to PLC, when ever required.
* CP 522x P2, CP 522x P3 and CP 522x P4 requires a patch panel and cables.
Ordering Code CP 5220 CP 5221 CP 5222
BO Port 1 Port1,Port2 Port1, Port2, Port3
P2 Port 1, Port1, Port2, Port1, Port2, Port3,
1 HSC + 1 PTO 1 HSC + 1 PTO 1 HSC + 1 PTO
P3 Port 1 Port1,Port2 Port1, Port2, Port3
2 PTO 2 PTO 2 PTO
P4 Port 1 Port1,Port2 Port1, Port2, Port3
2 HSC + 2 PTO 2 HSC + 2 PTO 2 HSC + 2 PTO
Port-1 is RS 232C only (Applicable to 5220, 5221, 5222 CPUs)
Port-2 is RS 232C/422/485 (Applicable to 5221 and 5222 only)
Port-3 is RS 232C/422/485 (Applicable to 5222 only)
CPU Specifications
17
The detailed pin configuration is illustrated in below diagram. For the communication port 1, 9-pin D male connector is provided on
the Processor module. The figure below shows front view of the connector.
This 5 V DC is strongly recommended only for restricted use. ( Not for driving the 5V DC operated external devices).
95
16
9 : Modem Ring Indicator
8 : Reserved for programming
7 : No Connection
6 : No Connection
GND: 5
5 V : 4
TxD : 3
RxD : 2
Carrier Detect : 1
Interrupt feature is not available in Nexgen 5214.
Special Interfaces
Nexgen 522x series has specialized interfaces as :
95
6
9 : Rx+ (RS 422)
8 : Rx- (RS 422)
7 : Tx- (RS 422)
6 : No Connection
GND : 5
Tx+(RS 422) : 4
TxD (RS 232C) : 3
RxD (RS 232C) : 2
Carrier Detect (RS 232C) : 11
Communication Port 2 and Port 3
Communication Port-2 and Port-3 are open for RS 232C/422/485 hardware interface. The signals are terminated on different pins
on 9 pin D connector. The processor module provides requisite hardware for serial interface. The operating system provides driver
functions and function blocks which directly controls the hardware interface. For a serial port, processor provides system buffer of
256 bytes each for reception and transmission. The relevant driver function blocks like Nexgen_slave and RTU_Slave are
provided in the library Nexgen 522x.lib.
For the communication ports 2 and port 3, 9-pin D male connectors are provided on the Processor module. The figure below
shows front view of the connector. The connections for both ports are identical.
Pin-1 provides carrier detection status when modem is connected. This status is available in application program on activating
PORT_STATUS. Pin-9 provides ring indicator when modem is connected and if any controlling device is dialing. Pin-4 and Pin-5
provides 5 VDC and Ground, which is used for memory cassette operation.
The detailed pin configuration is illustrated in above diagram. Pin-1 provides carrier detection status when modem is connected.
This status is available in application program on activating PORT_STATUS.
CP 522x-P2 : 1 HSC Channel + 1 PTO Channel + 2 Interrupt inputs ( Under Development)
CP 522x-P3 : 2 PTO Channels + 2 Interrupt inputs (Under Development)
CP 522x-P4 : 2 HSC Channel + 2 PTO Channel + 2 Interrupt inputs
Nexgen 522x : Port 1
Nexgen 522x : Port 2 / 3
CPU Specifications
18
MOST ADVANCED NEXGEN 522x SERIES OF CPUs
On-board Interrupt Inputs
Industrial automation applications are ever demanding with increased level of sophistication. Especially real-time systems
demand flexible and configurable control over the execution of different parts of program, which can be in response to any
Interrupt Event.
Interrupts suspend the current (normal) execution, completes the interrupt-linked POU execution and then returns back to
suspended point, to resume normal execution.
In case of multiple interrupt events, these event needs to be prioritized. System interrupt events like serial communication interrupt,
internal timer interrupt are executed at highest priority. Here scheduler manages the execution of queued events as per defined
priority.
The general specifications are as:
Nexgen 522x : Memory & Configuration
RAM
Nexgen 522x series CPU has two on-board memory resources viz. RAM and Flash PROM. This is similar to Nexgen 521x, but it
has enhanced memory capacity and also has file marker memory.
Nexgen 522x series CPU has 256 KB RAM with battery back-up. This has various memory components like Input process image,
Output process image, Application program code memory, Data memory, Marker memory, File marker memory and system
variable memory.
Memory TypeAddress Specifier InApplication Program Size
Input process image %I 128 Bytes
128 Bytes%QOutput process image
%MMarker 32768 Bytes
64 KBAddressable by Name
Addressable indirectly 64 KB
Data
File marker
System Variables Addressable by Name System Area
256 KBNot AddressableApplication program Memory
Two Maximum
Event Number
2 EVENT_Z1_R_TRIG
3 EVENT_Z1_F_TRIG
5 EVENT_Z2_R_TRIG
6 EVENT_Z2_F_TRIG
Enum
No . of on-board inputs
Selectable by inputs atpatch panel
Open collector ( 18-30 V DC inclusive of ripple )
Differential ( 5V DC )
7 mA for open collector type input
15 mA for differential type input
5 s�
5 s�
Current
Min. ON time duration
Min. OFF time duration
Accessories Required
Patch
Panel
Ordering code 4960
Ordering code 4962
Ordering code 4945
Ordering code 4946
Interface
cable
CPU Specifications
19
Operating System 198 KB
256 KBApplication Program Code
Application Program Sourcecode memory 1 MB
Input Process Image Output Process Imageand are input and output status respectively, for the configured IO modules.
These images are stored in global memory area, in every input and output scan. These images are accessible to external devices
like HMI and SCADA. Input and Output scan, can be executed on demand in a logic scan by calling Refresh_In and Refresh_Out
respectively.
Marker Memory
File Marker Memory
Data Memory
System Variables
Flash PROM
is used to store the intermediate results and stored at addressable global memory area, accessible to external
devices like HMI, SCADA.
is the data memory, which needs to retain after a PLC cold start or even after program change. Thus it is used
to store the reciepe, history and data logged. This memory is accessible to user only by using specific functions and function blocks
in application program. It is possible to access the file marker area for external devices also via serial communication by
MODBUS_RTU and Nexgen protocol.
is used to store the intermediate results like instances of function blocks and variables used in application program.
Unlike marker memory, data memory addressing is not handled by application developer, but these addresses are generated by
compiler. Hence data memory is not accessible to external devices like HMI and SCADA.
are implicitly global and used to exchange the information with PLC operating system and its functionalities.
Nexgen 522x series CPU has 512 KB Flash PROM. This serves as on-board backup memory.
Battery Back Up
Keypad and Display Unit
PLC variables are stored in RAM, which is of volatile nature, demands a battery backup to retain its contents. This battery
also serves as a backup to on-board RTC. Nexgen 522x CPUs use 3.6V Ni-MH (Nickel Metal Hydride) rechargeable battery,
which is mounted on board. The battery provides backup period around 6 months, from its fully charge status.
Optional pluggable keyboard display unit can be used as diagnostic tool. It provides 4-character alpha-numeric display with
6 keys keypad. This is helpful for:
Displaying fault messages� �
� �
Displaying system messages
Viewing / modifying PLC Variables Redirection of I/O points
Operating System
This contains core code of processor module which
handles various functions of the processor. Operating
system code can be upgraded by a software tool
'Bootstap loader’
�
�
�
This display and keypad are accessible to application program and its information is available in form of system variables.
Application developer can develop customised function blocks to handle the display and keypad routines as per required
by application.
_BKEYSTATUS is the system variable associated with keypad. This is a byte & its six bits are accessible corresponding to
each of the key.
_ADISPLAY is the system variable associated for four character alphanumeric display. This is a array of 4 bytes & each of
the byte represents individual characters corresponding to display position
CPU Specifications
20
NEXGEN 521x SERIES OF CPUs
Communication Port 3 (RS 232)(9 pin D male connector, CPU 5211)
RTS
CTS
Rx
Tx
GND
6
1
59
Communication Port 3 (RS 422)(9 pin D female connector, CPU 5212)
RTS+
CTS+
Rx+
Tx+
GND
95
16
RTS-
CTS-
Rx-
Tx-
Nexgen 521x series itself has 5 CPU variants. This wide range of CPU empowers user to select a CPU as per application specific
requirement. This essentially has Standard CPU, 3 Port CPUs (2 Nos.), Low-cost CPU and Special CPU.rd
Communication Port 1 : RS 232C( 8 pin mini DIN female connector )
8 5 2
+12 V
Rx
Tx
GND
6 3 1
GND
Communication Port 2 : RS 422( 8 pin mini DIN female connector )
8 5 2
+12 V
RxD+
RxD-
GND
6 3 1
GND
TxD-TxD+
* CPU 5214 : Requires a patch panel and an interface cable.
Communication (Connector Type)
Port 1 Port 3
Keyboard /Display
HSC / PTOCode Name
CPU
Port 2
Not Available
Not Available
RS 232C,8 pinMini DinFemale
RS 422/485 9 Pin DFemale
Yes
RS 422 / 4858 pinMini DinFemale
Not Available
RS232C,9 Pin DMale
Not Available
Not Available
No
No
Not Available
CPU with 3’rdport as RS-232C
CPU with 3’rdport as RS 422/485
5211
5212
Yes Yes *
Yes
Yes
Standard
Economy
Special
5210
5213
5214
Nexgen 521x : CPU Variants And Communication Ports
CPU 5214 (Specially madewith Motion Control Features)
CPU 5210 (Standard) CPU 5213 (Low Cost) CPU 5211(CPU with 3 Serial Ports)
CPU Specifications
21
Nexgen 521x series CPUs are faster in execution, which makes it suitable for any sophisticated application, where processing
speed and computation matters.
Nexgen CPU 521x : Faster Instruction Execution
Nexgen CPU 521x : Memory & Configuration
Nexgen 521x series CPU has two on-board memory resources viz. RAM and Flash PROM.
RAM
Nexgen 521x series CPU has 256 KB RAM with battery back-up. This has various memory components like Input process image,
Output process image, Application source code memory, Data memory, Marker bits memory and other for system variables.
Input Process Image (%I)
Output Process Image (%Q)
Marker (%M)
Data
Application Program (for RUN time execution)
Application Program (storage for on-line change)
System Variables, Communication port buffer area, etc
128 Bytes
128 Bytes
15872 Bytes
32 KB
64 KB
64 KB
Remaining RAM utilised
Flash PROM
Nexgen 521x series CPU has 512 KB Flash PROM. This serves as on-board back-up memory.
Operating System
Application Program Code
Application Program Source code memory
128 KB
64 KB
192 KB
Nexgen CPU 521x : Run-time Execution, Downloading and Boot Project
PLC run-time execution takes place through RAM only. PLC programming software downloads executable binary code in RAM
and the same is optionally transferred to Flash PROM, creating Boot Project.
Programming software (CoDeSys) facilitates user to select source code downloading option. Unless specified explicitly,
Executable Binary code will get transferred to RAM.
Execution Speed for Various Instructions and Data Types
Above execution time is in micro seconds (µsec)
DATA TYPE
LOAD
MOVE (Load & Store)
ADD / SUB
MUL / DIV
Square Root
Logical AND / OR / XOR
Compare
BOOLEAN
00.75
01.20
--
--
--
--
--
BYTE
--
01.20
02.10
02.50
--
02.10
02.50
WORD
--
01.20
02.10
02.50
--
02.10
02.50
DWORD
--
02.00
03.50
12.00
--
03.50
03.40
REAL
--
02.00
12.60
12.80
19.50
--
15.40
INSTRUCTION
Motion Control
22
CPU 5214 (Specially developed forMotion Control)
NEXGEN CPU 5214WITH MOTION CONTROL FEATURES
Depending upon type of pulse output interface two varieties of patch panel are provided
for wiring. These are 2 HSC & 2 PTO (PNP type) and 2 HSC & 2 PTO (RS 422 type)
Special CPU 5214 has a provision for two independent channels for High Speed Counters (HSC) and Pulse Train Outputs (PTO).
For external interface, a cable with 25-pin D connector at both ends is provided. One end of cable is to be connected to 25-pin male
D connector provided at bottom side of CPU module. Other end of cable is to be connected to 25 pin female D connector on patch
panel for field interface. On this patch panel, connectors are provided where HSC inputs and PTO outputs can be connected. The
technical specifications are as per page 23.
Nexgen CPU 5214 :Specially Developed with Motion Control Features
On-Line Application Program Change
During run-time, program executes from RAM. When on-line change in an application program occurs, modified application
program is transferred to additional memory space in RAM. During this download, PLC continues to execute the earlier program
from standard memory location of RAM. When downloading is completed, from immediate next scan, latest (modified) program
gets executed.
For every power ON operation, program gets transferred from Flash PROM to RAM. In case of no program in Flash PROM,
'MEMR' gets displayed on CPU Display.
In case boot project is not created, RAM and Flash PROM will have two different programs. On next power ON, this will cause
copying of old program from Flash PROM to RAM.
Application Program Source Code
PLC programming software (CoDeSys) generates application program project file in a compressed format. This file gets
downloaded to Flash PROM as source code download occurs. This project file contains all project related data like ladder,
comments, variable name, variable declaration, password, libraries (optional).
Source Code Uploading
This uploads the complete project from CPU to PC. Usually this should be password protected to restrict the source code
uploading.
Motion Control
23
Channels
Outputs
Frequency
Duty Cycle
FP and RP
100 KHz, ±1% maximum for differential output with patch panel 4962.
5 KHz, ±1% maximum for open collector (PNP) output with patch panel 4960.
50 %
Pulse output range 0 to 4294967296 with Direction
2 Nos.
Type (Selectable bytype of patch panel)
Open collector(18-30 VDC including ripple)
With patch panel 2 HSC & 2 PNP type PTO
DifferentialWith patch panel 2 HSC & 2 RS 422 type PTO
(Ordering Code-4960)
(Ordering Code-4962)
Current1.5 Amp maximum for open collector (PNP) output with patch panel 4960.
Mode of Operation(Software selectable)
Mode 0
Mode 1
Pulses and Direction
Forward Pulses and Reverse Pulses
External PowerSupply
For pulse output driving circuit.
24 VDC ( 18-30 VDC including ripple), 100 mA
Pulse Train Output
60 mA maximum for differential output with patch panel 4962.
Pulse Train Output
5214 processor module provides 2 independent channels for pulse train outputs. This channel provides two output interfaces
where output functionality depends on mode of operation selected. Relevant function blocks are located in PTO.lib. The driver
function block selects mode of operation, number of pulses, output frequency and direction.
High Speed Counter Input
Channels
Inputs
Frequency
Counting Range
Type (Selectable by inputconnections at Patch Panel)
Current
2 nos.
A, B and Z
100 KHz Maximum
-2147483648 to 2147483647
Open Collector* (18-30 VDC inclusive of ripple)
Differential / TTL (5V DC)
Min. ON time duration
Min. OFF time duration
7 mA
15 mA
5 µs
5 µs
For open collector type of Input.
For differential type of Input.
Mode 0
(100 kHz)
Phase A input,Phase B input andZero Marker input
Counts at rising and falling edgeof input depending upon Direction.
Counts at rising edge of inputdepending upon Direction.
Counts at rising and falling edgeof phase A input and phase B input.
Pulse input,Direction input andReset input
Pulse input,Direction input andReset input
Mode of Operation(Software Selectable)
5214 processor module provides 2 independent channels for high speed counters. Each channel provides three input interfaces
as A, B and Z. This channel provides hardware interface for open collector (PNP/NPN) inputs of 24 VDC or differential 5 V inputs.
To configure for its use, processor 5214 provides driver function blocks for each channel in library PTO.lib. This facilitates
application developer to set the mode of operation and fetch the accumulated count and status of Z input. Counter provides pulse
count in double integer format.
High Speed Counters
* Open collector : PNP / NPN
Mode 1
(100 kHz)
Mode 2
(50 kHz)
CoDeSys
24
IEC
61131-3
SUITE FOR NEXGEN-5000 PLC SERIES
CoDeSys PLC PROGRAM DEVELOPMENT
CoDeSys is a Windows based, an
international quality software which is IEC
61131-3 compatible.
CoDeSys is Controlled Development System
for Nexgen 5000 series of programmable logic
controllers. It is a PLC program developer's
suite.
®
Microsoft Windows (32 bit) Platform®
With the Windows based platform, application developer can avail the inherent benefits like Copy, Cut, Paste
and Delete operations. Using Import-Export facility developer can copy/re-use the Program Organisation Unit
(POU) across the applications. Global Search and Global Replace are features for the ease of program
modifications.
®
Modular Programming
CoDeSys encourages use of modular programming. Developed application is called as project, which has .pro as
file extension. Every CoDeSys project must have at least one POU. POU stands for program organisation unit
which either could be a program, function-block (FB) or function. One project can have many POUs.
PLC_PRG is a program, which is mandatory POU in every project. This PLC_PRG is a master routine where from
all the other POUs (sub-routines) are called. In a way, PLC_PRG can be viewed as main function in C language.
Hence, rather than dumping the complete logic into one POU (PLC_PRG), multiple POUs are developed, as per
objectives. Thus any project can be developed into split components. This approach resembles with object
oriented programming in higher level languages like C++ or Java.
Powerful Library Management
CoDeSys provides a powerful way of library management. Modular programming facilitates having multiple
POUs in the same project. But it sensed more to have a provision of external storage of POUs, which are
application specific or required frequently i.e. just develop a POU once and for all, store it in application specific
library and implement it,as and when/where required.
This reduces development time for a machine manufacturer or end-user. Simply write it once and implement
many times. Password protection facility conceals the application logic in POUs (function & function blocks).
Modular programming and library management has indeed eased the task of application program development,
to a great extent.
Powerful Program Editor
CoDeSys has powerful program editor which facilitates a user set of six programming languages: two textual
languages and four graphical languages.
CoDeSys
25
LADDER DIAGRAM & INSTRUCTION LIST
Ladder Diagram (LD)
It is the simplest graphical method of PLC
programming comprised of normally open and
normally closed contacts and coils, widely used in
discrete control applications.
As per IEC 61131-3, symbolic addressing is
implemented rather than absolute addressing. IEC
ladder can deploy function, function block or
program, in a ladder irrespective of IEC
programming language, in which the POU is written.
IEC ladder program
encourages, use of other program organization
units (POU) i.e. functions, function blocks and
programs. This has enhanced its wide acceptance
to process control applications also.
Instruction List (IL)
It is a textual language which follows simple
microprocessor assembler level instructions, similar
to mnemonics used in earlier PLC program
development language. It is the most primitive and
fundamental level programming language; hence
every PLC programming language can be converted
to Instruction List. It is comprised of sequence of
instructions and operates single instruction per line.
It is a bit tricky and tedious for novice to implement. It
has its own unique grace and glory, especially while
dealing with compact and crucial applications, where
performance and optimization are of prime
importance.
Its program editor is characterized with line numbers
- visible for quick reference error messages and
comment mode to have programs translated by
non-programmers.
In a nutshell, Instruction List has a series of
instructions, where each instruction begins with new
line and contains an operator and one or more
operands separated by comma.
Typical example of ladder programming comprised of normally opencontacts, normally closed contacts, coil outputs and Function Block.
Example narrating series of instructions in a typical Instruction List Program
Sequential Function Chart (SFC)
It is a graphic language which provides the
diagrammatic representation of a process. It provides
fragmenting of a program into manageable logical
sequences. This function chart is made up of steps and
transitions which are interconnected with directed links.
Steps are linked with action blocks and transitions.
Each state represents a particular state of system being
controlled. A transition is associated with a condition,
activating or deactivating an earlier and next step as per
status of condition. Steps are linked with action blocks,
which are performing a certain control action. Each
element can be programmed with IEC language,
including SFC itself.
Structured Text (ST)
It is a textual language resembling with high level
programming language like Ada, Pascal or C. It exhibits
its suitability for logic with complex algorithms or
mathematical computations. It can be used to build
POUs i.e. functions, function blocks or programs.
This can be very well harmonized with ladder.
ST supports powerful control structures like IF ELSE -
THEN, DO - WHILE, REPEAT, FOR and many more.
It eases use of data structures like ARRAY,
STRUCTURE and User Defined Data Types. It also
supports SIZEOF operator and Pointers for memory
optimization.
Function Block Diagram (FBD)
It provides graphical development of a program using
the basic building block from IEC Function Block
Library. It has wide acceptance in process control
application development as it expresses behavior of
functions, function blocks and the programs as a set of
interconnected graphical blocks.
In a nutshell, FBD works with a list of networks whereby
each network having a structure which represents
either a logical or an arithmetic expression, the call of
function block and the return instruction.
26
Typical network in function block diagram
Snapshot for typical POU with Structured Text (ST) as programming language
This snippet explains a program with various steps and,an action for the 'init' step.
STRUCTURED TEXT, FUNCTION BLOCK DIAGRAM
SEQUENTIAL FUNCTION CHART
CoDeSys
27
A simplified step consists of an action and flag to indicate whether the step is active. An IEC step has a flag and one or more
associated actions or Booleans. An action has series of instructions in either of IEC language. In addition to step action, there can
be an entry action and/or an exit action. These entry and exit steps get executed once only, right after the step is activated or just
before step is deactivated, respectively.
Off-line Simulation
CoDeSys has an off-line simulation facility. This is very vital utility for an application program developer, as one can develop
complete program logic independent of PLC. This feature helps the developer to complete the application program development
on or before scheduled time. Off-line simulation is built-in* feature of CoDeSys.
Continuous Function Chart (CFC)
Apart from these five programming languages,
CoDeSys also supports Continuous Function Chart
(CFC), which is of graphical type. In operates with freely
placeable elements, rather then network like in FBD.
This allows a feedback. The elements of sequential
process list includes boxes, input, output, jump, return,
label and comment. Inputs and outputs of the element
can be connected by dragging a connection with
mouse. The connection lines are automatically drawn
and automatically adjusted when elements are moved.
Graphical flexibility and ease of feedback makes it
suitable to use it in any process application or
application where SFC or FBD can be used. CoDeSys
has powerful program editors where toolbar icons,
menu items are automatically adjusted as per IEC
language selected.
On-line Functionality
CoDeSys has on-line program monitoring and on-line
program modifications features. This makes it suitable
for continuous process application, where program
modifications without process interrupt may be
required. Watch and Receipt window facilitates to
monitor multiple variables, simultaneously from
multiple program organization units (POUs). On-line
power flow monitoring serves as ready tool for fault
diagnostics.
Sample for CFC programming displays freely placedblocks rather than a grid.
Watch & Receipt window, shows, different variables from, various POUs.
*In case of some PLC vendors, Application program development software and simulation software are different.
Please note that offline simulation does not support some of the CPU resource specific function / function blocks.
(e.g. it does not support RTC related, System variable related functions and function blocks.
CONTINUOUS FUNCTION CHART
OFF LINE SIMULATION, ONLINE FUNCTIONALITY
PLC I/O Configuration
Hierarchical and Graphical method of PLC rack
configuration and module configuration minimises the
chance of errors in I/O addresses.
Once, user selects the module, I/O addresses are
automatically assigned to the selected module. Hence
the user is not required to calculate or memorise the I/O
addresses.
PLC configuration for 3 IO Rack System with module details
PLC Browser
CoDeSys facilitates use of PLC Browser for viewing or
setting certain PLC parameters. PLC Browser is textual
command monitor which is a analogous to DOS prompt.
It has command entry line cum result display window,
which is like a combo-box.
It has smart history of latest executed commands, which
CoDeSys
28
displays it without repetition of command. User can
check /set RTC from PLC browser.
The above snippet depicts implementation of DDE, where a current valueof a counter in PLC project is monitored.
Dynamic Data Exchange
CoDeSys facilitates Dynamic Data Exchange utility. This
makes user to fetch the PLC variable information in
Microsoft Excel Sheet or Microsoft Word. The
concurrent and continual data logging is possible by
devising advanced programming techniques in
Microsoft Excel spreadsheet.
CoDeSys is responsible only for the displaying dynamic
values of PLC variables in Microsoft Excel spreadsheet
cells. These values in Excel spreadsheet sheet cells get
overwritten, on very next pre-defined time interval in
CoDeSys project. This assists the handling and storing,
these dynamic values, with advanced programming
techniques in Microsoft Excel.
® ®
®
®
In case direct DDE Server is used, which works with symbols rather than addresses, CoDeSys is not required to read the variables
from PLC and transfer them to application with DDE interface. Direct Addresses are not read with DDE Server. One needs to use
symbolic variables.
CoDeSys has assured and tested DDE interface, with Microsoft® Excel 97 and Microsoft Word 97, only with Microsoft
Windows NT 4.0
®
®
Sample for using PLC browser, a handy and quick tool for developer
DYNAMIC DATA EXCHANGE
CoDeSys
29
This on-line feature of CoDeSys enables user to
monitor progression of maximum eight different
analog or digital variables, simultaneously in trace
window (graphical format). This sampling rate is user
settable. The sampled values are stored in internal
trace buffer. If this ring buffer gets full, data purging
takes place i.e. older values are overwritten with
newer ones.
Trace configuration facilitates user to set various
parameters for sample trace. The trace configuration
settings can be saved to a file, which can be reloaded
with option load trace feature. Similarly, sampled
data can be saved in text file. The detailed
parameters description for trace configuration is as
explained here.
Other features like stretch, compress, Y Scaling
allows user to adjust the trace window for the
requisite visibility. Enabled show grid option makes
grid as well as X-Y axis values to be visible.
Trigger Variable
Trigger Level
Trigger Position
Triggering Edge
Numberof Samples
Recording
SamplingRate (ms)
Variables
Positive
Negative
Both
None
Minimum
Maximum
Minimum
Maximum
Single
Continuous
Manual
Description
This terminates sampling activity. (Trigger OFF)
This initiates sampling activity. (Trigger ON)
This decides percentage of measured values, which will be recordedbefore Trigger On event occurs.
Triggering occurs after the rising edge of Boolean
Triggering occurs after the falling edge of Boolean
Triggering occurs both at, rising and falling edge of Boolean
Triggering does not occur at all.
32
1024
1 ms
20000 ms
Displays only once the samples 'Number of samples'
Displays continuously selects 'Number of samples'
Used to read trace recording with 'Read Trace' from ‘Extras'
These are variable for sampling ( Maximum 8 )
This is a navigator to locate/select 'Variable' from the entire project,for sample tracing.
Help Manager
Parameter
Similarly the saved text file for sampled data can be readily transported to Microsoft Excel, where user can take further
analytical and database storage actions.
Sample Trace Function with Graphical Display
Typical example of sampled temperature and pressure,in a process application
SAMPLE TRACE FUNCTION
CoDeSys
30
Process Visualisation for On-Line Testing
This on-line feature of CoDeSys facilitates a user for
designing interactive graphic user interface or screens.
This allows user to design application specific screens,
using various GUI elements or visualisation elements like:
rectangles, rounded rectangles, ellipse, polygon, polyline,
curves, BMP images, buttons (with limited events) and the
other visualisation itself. It also facilitates a user to have a
regular configuration of these elements. e.g. rectangle has
shape, text, line-width, color, motion-absolute, motion-
relative, variables, input and tool-tip. These configuration
parameters vary as per visualisation element.
This makes Visualisation as very handy tool for viewing the
dynamically changing data in textual or even graphical
form. User can simulate a mimic or even a process using
these visualisation elements.
Also user can force PLC outputs from this interactive
screen.
In comparison with other front end tools (Visual Basic, Power Builder, Oracle Forms), this has limited capacity and features.
Even though it is comparable to SCADA, one should not use this feature as SCADA, as its response and performance are not
assured. It is strongly recommended to use this tool for test and monitoring purpose rather than control action.
POUs and Data Types
POU stands for Program Organising Unit and it can be either a program, function or a function block. Hierarchy of POU
entities is as :
i) Program ii) Function Block iii) Function
As a general rule, any POU (calling POU) can call other POU (called POU), which is hierarchically at equal or lower level of calling
POU. A POU can not call other POU, which is hierarchically above the calling POU. Thus, a function block can call other function
block or function and cannot call program.
Sample for Visualisation for PLC output andPLC display scrolling speed control
CoDeSys supports standard data types, which are as:
REAL
BOOL
BYTE
WORD
DWORD
SINT
USINT
INT
UINT
DINT
UDINT
String
Range
TRUE or FALSE
0 to 255
0 to 65535
0 to 4294967295
-128 to 127
0 to 255
-32768 to 32767
0 to 65535
-2147483648 to 2147483647
0 to 4294967295
-3.4 E to -1.176 E+38 -38
It is a set of characters.( '/0' is the termination character,automatically added by system )
Memory
8 Bit
8 Bit
16 Bit
32 Bit
8 Bit
8 Bit
16 Bit
16 Bit
32 Bit
32 Bit
User defined size ( default 80 Bytes )
32 bit (IEEE floating point)
Type
± 0
+1.176 E to +3.4 E-38 +38
PROCESS VISUALISATION &
POUs AND DATA TYPES
CoDeSys
31
Class
Class defines the scope of the variable viz. local and global. Global elements are accessible to all the POUs in a project. CoDeSys
compiler forcibly insists data type declaration for an every variable used in the project, except PLC addresses.
Local Variables:
These variables are declared & defined specifically for the POU, thus the scope is valid only for the declared POU.
Global Variables:
These variables are declared and defined for a POU, with its widen accessibility. Thus these variables can be referred in other
POUs of the same project.
VAR
These are the local variables, necessarily meant for storing intermittent results of any POU. VAR variables restrict their
accessibility to the POU itself.
VAR_IN
These are read only type local variables, acting as inputs to POU (e.g. function block). Value of the variable can be given along with
the call, in calling POU.
VAR_OUT
These are local variables, acting as output to POU (e.g. function block). Value of these variables are returned back at the calling
POU. These variables can be used further, in the POU.
VAR_IN_OUT
These are local variables, acting as input as well as output of any POU. Value of such a variable is always passed by reference
rather than value. These variables are not applicable to the function.
CoDeSys supports special data types, which are as:
CoDeSys supports other data types, which are specific to date and time.
Type
TIME
DATE
DATE_AND_TIME
TIME_OF_DAY
Resolution
1 ms
1 sec
1 sec
1 ms
Remark
25 Days ( Max Value )
Counts from 1'st Jan.1970
Counts from 1'st Jan.1970
Counts from 12.00 am, everyday
Example
t#23h02m12s247ms
d#2003-05-23
dt#2003-05-12-15:36:57
tod#14:27:09.986
Memory
32 Bit
32 Bit
32 Bit
32 Bit
Type
ARRAYS
STRUCTURE
Similarly, an application developer can have, User defined Data Types.
Remark
It is sequential storage of same type of data
It is collection of different types of data in a record type approach
CoDeSys
Communication is handled with seven layers. But, still most of the time communication is handled with Application Layer, Protocol
Layer, Data Link Layer and Physical Layer.
Physical layer is comprised of several elements viz. media of transmission (like wires, fiber optics, wire-less), signal drivers, method
of transmission, inter connections, connectors and inter signal converters. Most commonly employed physical layer protocols are
RS 232C, RS 422 and RS 485.
Physical Layer
* Isolator drivers are required for a distance more than 50 m. ( Maximum supported distance is 1 KM )
Basic Signals
Signal Voltage
Distance
Communication
RS 232C
3 Wires TXD,RXD,GND
-12 V / +12 V
15 Feet
1:1
RS 422
4 Wires TX+,TX-,RX+,RX-
5 V Differential
Up to 1 KM *
1:1, 1:N
RS 485
2 Wires Data +, Data -
5 V Differential
Up to 1 KM *
1:1, 1:N, N:N
At Both ends,4* 120 ohm RX,TX
At Both ends,4* 120 ohm (Data +, Data -)
No resistor reqd.Termination
COMMUNICATION BASICS
32
Nexgen 5000 Series of CPUs supports extensive instruction set to built the control logic across variety of applications, from
machine tools to process industry. The CPU is capable of handling various data types.
Data types supported are
Boolean
8, 16, 32 bit signed / unsigned numbers
Real numbers (32 bit IEEE floating point format)
Date, Time, Date and Time.
�
�
�
�
The CPU can handle various instructions like:
Boolean instructions
Timer instructions
Counter instructions
Comparison instructions
Data type conversion instructions
Logical instructions like AND, OR, XOR, NOT
Application specific instructions like SHL, SHR, ROL, ROR
Arithmetic instructions like ADD, SUB, MUL, DIV, MOD, SQRT
Trigonometric instructions like SIN COS, TAN, ASIN, ACOS, ATAN
Statistical instructions like MIN, MAX, MOD, variance etc.
Logarithmic instructions like EXP, LN
�
�
�
�
�
�
�
�
�
�
�
Variety of application specific libraries
Process FB libraries like P, PI, PID
Communication FB's like MODBUS RTU master, RTU slave, Mitsubishi Frequrol master, Mitsubishi UC24 slave, printer
and many more
FBs for data exchange via. modem interface, sending SMS via GSM modem etc.
Motion control FBs as per IEC61131 guidelines
�
�
�
�
� String of sequential ASCII characters
1-, 2-, 3- dimensional arrays
Structures (User Defined Data Types)
�
�
�
�
�
�
�
�
�
String handling instructions compare, search, left,
right etc.
Real time clock handling instructions
I/O module handling instructions
Event interrupt handling instructions
Serial communication handling instructions
High Speed Counter handling instructions
Pulse Train Output handling instructions
CoDeSys : INSTRUCTIONS & LIBRARIESCOMMUNICATION BASICS
RS 232 to RS 422 / RS 485 Conversions
These are used in various networking schemes where PC (RS 232) side is interfaced with RS 422 / RS 485
or vice versa.
This is characterized by:
Optical isolation between input and output signals
Operates directly on 85-260 V range
Does signal level correction
Provides auxiliary output power supply for
local device connection
�
�
�
�
CommunicationBasics
33
RS 422 to RS 485 Conversion
As a common practice, RX+ is shorted to TX+ and RX- is shorted to TX-. The RS 485 connected station is called as Half
Duplex as it either receives or transmits the signal. In some cases, TX needs to put to tri-state when receiving starts. Such
convertible ports are marked as RS 422 / RS 485.
Nexgen 521x series having serial 2'nd and 3'rd port, are convertible from RS 422 to RS 485 and vice versa.
Signal Converters Used in various Interface Schemes
RS 422 / RS 485 To RS 422 / RS 485 Isolator Conversions
These are used in high speed long distance serial communication as an isolated signal repeater, RS 422 ( 4 wire ) to RS 485
( 2 wire ) converter and vice versa conversion.
This is characterized by :
Optical isolation between input and output signals
Can be used as RS 422 isolated repeater
Can be used as RS 485 isolated repeater
Operates directly on 85-260 V AC range
Does signal level correction
Provides auxiliary output power supply for local device connection
�
�
�
�
�
�
�
�
�
�
�
Auto detection of direction, in case of RS 485
Supports 3 baud rates viz. 9600,19.2,38.4 Kbps
Provides diagnostic LED indications
DIN rail mountings
Provides output signal short circuit protection
Item
Function
Input supply voltage
Operating modes
Auto direction sensing
Baud rates supported
Signal isolation
RS 422(4 Wire) to RS 485(2 Wire) Conversion or Vice versa
85-260 VAC,15VA, 50/60Hz
RS 422 (4-wire) or RS 485(2 wire ), set by switch settings
Facility available for RS 485(2-wire) interface
9600, 19200 and 38400 ( set by DIP Switch setting )
1.5 KV optical isolation
Description
Model 6012 24 V DC, 250 mA
Model 6013 12 V DC, 250 mA
Model 6014 5 V DC, 500 mA
2 Amp miniature glass fuse protection at input supply
Diagnostics LEDs for communication signals
TX ( Down Arrow ) , RX ( Up Arrow )
Auxiliary power output
Supply protection
Diagnostics
Mounting
Dimensions (H x W x D)
DIN rail
100 mm X 60 mm X 75mm
ApplicableSignal short circuit protection
�
�
�
�
�
Auto detection of direction, in case of RS 485
Supports 3 baud rates viz. 9600,19.2,38.4 Kbps
Provides diagnostic LED indications
DIN rail mountings
Provides output signal short circuit protection
Communication Basics
Protocol
MODBUS RTU
Nexgen 4000
XMP8-10 PLC
Mitsubishi UC-24
Freqrol
Master FB
Slave FB
Slave FB
Micro Master FB
Slave FB
Freqrol Master FB
SCADA, E-series HMIs Connectivity, Compatible Field Devices
Nexgen 5000 to Nexgen 5000 Network, SCADA Connectivity
Purpose
HMI Connectivity Messung Smartline Sr, Jr and Beijer E Series
Network of Micro PLC Slaves with Nexgen 5000 Master PLC
Mitsubishi GOT Connectivity
Read/Write Data to Multiple Inverter, Serial control for inverter.
Transfer data to HMI/ SCADA on other port
Protocol Function Blocks
MODBUS is a widely used protocol in industry being established and open for use. Messung Protocols are specific to Messung
products and are not open for its use. To communicate with Messung products, application developer has to write a protocol
converter like SCADA driver.
Typical communication string has Header, Station ID, Length, Command/Response byte, Data, Checksum and Trailer.
Protocol
Protocol is synonymous to language as both the devices should communicate and understand the same language. It is predefined
sequence of codes for data exchange. By using protocol converter, two devices having un-identical protocols can communicate.
A protocol is command and response having, header, body and a trailer. Header is indicative of a new message begin, body is
comprised of command number, data and any other information need to communicate. Trailer has error checking checksum and
end of transmission character. Protocols work independent of physical layer.
Communication parameters are Baud rate, Data bits, Parity bits and Number of stop bits. Typically one byte frame consumes 11
bits and at 9600 bits per seconds, it takes 1ms per byte frame.
Nexgen 5000 has an Application Layer and Protocol Layer, which are open to user, Data Link Layer which is implicitly handled by
PLC operating system and Physical Layer which is hardware dependent.
Function blocks for MODBUS master and slave are developed by Messung, for Nexgen 5000 PLCs.
Nexgen5000 has two buffers viz. RX buffer and TX buffer which simultaneously handle transmission and reception, functions
independently and in parallel to PLC scan. Data Link Layer handles conversion of Data Frame to Byte Frame.
RS 232(3 Wire) to RS 422/485(4/2 Wire) Conversion or Vice versa
85 260 VAC,15VA, 50/60Hz
RS 422 (4-wire) or RS 485(2 wire ), set by DIP switch settings
Facility available for RS 485(2-wire) interface
9600, 19200 and 38400 ( set by DIP Switch setting )
1.5 KV optical isolation
Description
Model 6010 24 V DC, 250 mA
Model 6015 12 V DC, 250 mA
Model 6016 5 V DC, 500 mA
2 Amp miniature glass fuse protection at input supply
Diagnostics LEDs for communication signals
TX ( Down Arrow ) , RX ( Up Arrow )
DIN rail
100 mm X 60 mm X 75mm
Applicable
Item
Function
Input supply voltage
Operating modes
Auto direction sensing
Baud rates supported
Signal isolation
Supply protection
Mounting
Dimensions (H x W x D)
Signal short circuit protection
Diagnostics
Auxiliary power output
34
COMMUNICATION BASICS
CommunicationBasics
35
Protocol FB get executed in logic scan and consumes application as well as data memory. It delivers same throughput, facilitates
variety of communication speeds and exerts complete control on communication scheme.
01 Read Coil Status ( 1 bit )
03 Read Holding Register ( 16 bit )
04 Read Input Register ( 16 bit )
05 Write Single Coil / Preset single holding register
15 Write Multiple Coils / Preset multiple holding register
MODBUS RTU_Slave
It emulates MODBUS Slave functionality. User can create only single instance of the block and can be attached to any port . It is
interface able with SCADA, DCS, E Terminals, Nexgen PLC with MODBUS Master FB.
RTU-MAST
EN Status
Port LastRec
Init Set LastResult
Mode Sel
RecNo
AutoRestart
AddRecTable
MaxRec
MODBUS RTU_Master
Its design is characterized by its facility to handle Cyclic, Super Cyclic and
On-demand data updates, User defined exchange requirements in source
as well as destination formats of records and Error reporting with record
number.
MODBUS Protocol
MODBUS protocol, introduced by MODICON, is open to
everybody for use, which has MODBUS RTU (binary),
MODBUS ASCII and MODBUS TCP protocols. Presently
Messung supports MODBUS RTU protocol, which is efficient
being in binary format. Messung FB has MODBUS Master
and MODBUS Slave which support various commands as :
ModeSel can have values as 0, 1 or greater than 1. Its 0 value stands for on-demand or manual updation, only once but in
overriding mode. Its value 1 stands for cyclic execution but only once per network scan. When ModeSel has value greater than 1,
it can be grouped and gets executed along with cyclic.
MODBUS supporting devices may not support all the MODBUS commands, this emphasizes due care while putting such a device
to network. Nexgen 5000 to Nexgen 5000 communication can be established with MODBUS Master function block.
Nexgen_Slave
It emulates Nexgen 4000 HMI port protocol, facilitating connectivity for Smartline Sr., Smartline Jr., E-Series HMIs and SCADA
with Nexgen Drivers. Communication speed is selectable up to 56 Kbps, incase of E-series HMIs and SCADA only. This can be
attached to any of the Nexgen 5000 communication port.
Freqrol Inverter FB
This block facilitates a user to connect 31 freqrol Inverters and user need not know Inverter interface protocol. User can have
control over Direct Inch, ON/OFF operations, Cyclic data updation, Individual error handling and automatic communication
recover on Inverter switched ON. It reflects fast changes to set point changes. Communication speed is settable to 9.6 Kbps or
19.2 Kbps.
Power Supply
36
The base plate holds Power Supply, CPU and I/O modules. It is available in varieties to suit I/O and expansion requirement. The
base plate is available with or without expansion connector to offer economic solution. Both the base plates are available in 3 I/O, 5
I/O and 8 I/O slots.
Base Plate
Expansion Plate
In multi-rack system, the expansion plate can be mounted
next to each other or one below other. The expansion
plate is available in varieties to suit I/O and power supply
requirement. It is available with or without power supply
connection facility. Both the expansion plates are
available in 3 I/O, 5 I/O and 8 I/O slots. At the most 3
expansion plates can be connected to the base plate.
POWER SUPPLY MODULE
The power supply provides 5 V DC power to the processor, I/O modules and 12 V DC power for interfacing HMI Jr to HMI port. In
multi-rack system, additional power supplies can be connected into expansion plates.
Power Supply Module, with 220VAC Supply Input
Connector
Ordering Code
Protections
Fuse protection for
incoming mains
Inrush current
Output voltages
Input supply
8 pin (removable)
4110
�
�
MOV for incoming over voltage
Output short circuit protection
3A / 20 mm glass fuse
8A for 2 msec
5V DC - 5A, 12V DC - 0.5A
220VAC, ± 15 %,
50 Hz, ± 6%, 50VA
Power Supply Module, with 24VDC Supply Input
Protections provided
Fuse protection for
incoming supply
Inrush current
Output voltages
Input supply
Connector 8 Pin (removable)
�
�
Reverse polarity diode protectionOutput short circuit protection
5A / 20 mm glass fuse
25A for 10 msec
5V DC - 5A, 12V DC - 0.5A
24VDC (18 TO 30 VDC including ripple)
45 Watt
4112Ordering Code
3 I/O Base Plate (248 mm)
5 I/O Base Plate (332 mm)
8 I/O Base Plate (458 mm)
19
0m
m
(Depth 145 mm)
(Base plate and Expansion plate are of the same size)
NEXGEN
16
1.5
mm
x mm
Plate
x mm
3 I/O
230 mm
5 I/O
314 mm
8 I/O
440 mm
Base & Expansion Plate Pin Hole to Pin Hole Length
NC
R 1
R 2
-
250V 5A
+24 VDCNC
224 VDC
224 VDC
BASE AND EXPANSION PLATE &
POWER SUPPLY MODULE
Digital Modules
37
Digital Input Modules
On Off On Off
16AC 88 @ 230V AC
4 @ 120V AC15-35 79-26515-35 0-40 90 4617
32DC Sink/Sourceselectable
8 6 @ 24V DC 15-20 18-3015-20 0-5 110 4632
16DC Sink/Sourceselectable
8 6 @ 24V DC 15-20 18-3015-20 0-5 110 4616
InputsInputsType
InputCurrent(mA)
ResponseTime (ms)
OperatingVoltage (V) Backplane
Current(mA)
OrderingCode
Total PerCommon
Output Type
DC Source
DC Source
AC
Off
16
32
8
16
8
8
1
1
1.5
0.2
1.5
0.75
4.0
1.5
1.5
Nil
200
315
210
185
4716
4732
4711
4721
0.1
0.1
1.0
10.0
0.4
0.4
10.0
5.0
10
10
3mA
3mA
�
�
A
A
OnOff StateLeakage
Output Load Current (A) ResponseTime (ms)
Back-plane
Current(mA)
OrderingCode
Total Output Group
Max perPer
Common
Relay(Potential free) type
To use 16pt. Relay (Potential free) type module "4721" with "2 independent commons" arrangement,we recommend to use Prewired Terminal Block, 38 pin
4910
16 pt DC Input Module32 pt DC Input Module 16 pt AC Input Module
16 pt DC OutputModule
32 pt DC OutputModule
8 pt AC OutputModule
16 pt Relay (Potential Free)Output Module
Digital Output Modules
DIGITAL I/O MODULES
38
DIGITAL I/O MODULES
16 pt DC Input8 pt DC Output Module
MIXED DIGITAL I/O MODULES
16 pt DC Input8 pt Relay Output Module
16DC Sink/Source selectable
8 6 @ 24V DC 15-20 18-3015-20 0-5
8DC Source 4 4.01.5 0.110 A� 0.4
OnOutput
Max Per
Group
Off stateLeakage
Off
Inputs Type
Outputs Type
Back-plane
Current(mA)
Order-ing
Code
Total
On OnOff Off
Inputs InputCurrent (mA)
Input Configuration
Response Time (ms) Operating Voltage (V)
Total Per Common
Output Load Current(A)
Output Configuration
Response Time (ms)
8Relay (Potential free) 1 NA0.75 103mA 5
220 4425
220 4424
Per Common
The module incorporates microprocessor for carrying
out scaling and on-board diagnostic operations. High
resolution - 16 bit provides accurate control. Input
channel filtering rejects high frequency noise coupled
with signal.
8 Channel Non-isolated Analog Input Module
8
Voltage
No. of Input Channels
Types
305.176 V305.176 V305.176 V305.176 V
1.22071.2207
��������
-10 to +10VDC0 to 10VDC0 to 5VDC1 to 5VDC
0 to 20 mA4 to 20 mA
-10 to +10VDC0 to 10VDC0 to 5VDC1 to 5VDC0 to 20 mA4 to 20 mA
16 Bits15 Bits14 Bits
13.67 Bits14 Bits
13.67 Bits
Resolution
Voltage/CurrentRange Significant Bits
Resolutionper LSB
Channel Updatetime
Analog to Digitalconversion time (mSec)
�
�
�
�
No 24 VDCCPU ErrorConfiguration Error8 Channel Status
24 V DC, 200 mA
No
1.5 KV optical
Channel to Channel
Channel to internal circuit
Back-plane current
I/O points consumed
Terminal / Connection
Ordering Code
Indications
External voltage requirement
Isolation
60 ms50 ms12 ms
6 ms
50 Hz60 Hz
250 Hz500 Hz
Current
Removable 38 pin Terminal Block
8 Input Bits & 8 Output Bits
400 mA
Filter frequency
4308
DIGITAL & ANALOG I/O MODULES
39
8 Channel Thermocouple Input Module
The module converts thermocouple input mV values
into equivalent temperature values of 0.1 C resolution
with Cold Junction Compensation and Linearisation.
o
8
Sigma Delta with digital filter
No. of Input Channels
Conversion Method
760.01370.0
400.01000.01760.01760.01820.01300.0
JKTERSBN
-210.0-270.0-270.0-270.0
0.00.00.0
-270.0
From (°C) To (°C)
No 24 V SupplyCPU FaultCJC FaultChannel Status(8)
�
�
�
�
24 V DC, 100 mA(18-30 VDC Including Ripple)
315 mA miniature glass fuse on module.Reverse polarity protection.
�
�
1 M Ohms
External SupplyRequirement
External Supply Protection
Indications
Input Impedance
Nil1.5 KV optical
Channel to ChannelChannel to internal circuit
Isolation
ThermocoupleInput Types AndOutput Range
0.1°C
In Steps Of 10°C
60 mSec per channel
LM 35 IC Sensor Mounted OnTerminal Block Itself
Temperature Resolution
Thermocouple Linearization
Analog to DigitalConversion Time
Cold Junction Compensation
250 mA
8 Input Bits And 8 Output Bits
Removable 38 Pin Terminal Block4310
Back-plane current
I/O points consumed
Terminal/ConnectionOrdering Code
The module converts RTD input resistance values into
equivalent temperature values of 0.1 C resolution with
Lead Compensation.
o
8 Channel RTD Input Module
8
Sigma Delta with digital filter
No. of Input Channels
Conversion Method
Temperature Resolution
Analog To DigitalConversion Time
3 Wire
PT 100 -200°C To 850°C
250 mA
8 Input Bits And 8 Output Bits
Removable 38 Pin Terminal Block
4311
�
�
�
No 24 V SupplyCPU FaultChannel Status (8)
24 V DC, 100 mA(18-30 VDC Including Ripple)
315 mA miniature glass fuse on module.Reverse polarity protection.
�
�
1 mA
Back-plane current
I/O points consumed
Terminal/Connection
Ordering Code
External Supply Requirement
External Supply Protection
Indications
Excitation Current
Nil1.5 KV optical
Channel to ChannelChannel to internal circuit
Isolation
RTD Input TypeAndOutput Range
0.1°C
60 mS per Channel
ANALOG I/O MODULES
40
2 Channel Isolated Analog Output Module (Voltage/Current)
The module provides 2 isolated channels with 12-bit
resolution. Output type can be Voltage/Current.2 Isolated, 12 BitNo. Of Output Channels
R-2R LadderConversion Method
No 24 V Supply
Reverse Polarity Protection
24 V DC, 500 mA
External Supply Protection
Indications
External Power Requirement
1.5 KV opticalChannel to Channel
Channel to internal circuitIsolation
150 mA
32 Input Bits and 32 Output Bits
Removable 20 Pin Terminal Block
4332
Back-plane current
I/O points consumed
Terminal/Connection
Ordering Code
Load ResistanceVoltage
Current
Conversion Time
> 1 K Ohms
500 Ohms
20 S�
Resolution
Voltage / CurrentRange
SignificantBits
12 Bits11 Bits 7.8 A�
4.88 mV
Resolutionper LSB
TypesVoltage -10 to +10 VDC
-10 to +10 VDC4 to 20 mA
Current 4 to 20 mA
2 Channel Isolated Voltage Analog Output Module.
The module provides 2 isolated channels with 12 bit
resolution. Output type is Voltage only.2 Isolated, 12 BitNo. Of Output Channels
R-2R LadderConversion Method
No 24 V Supply
Reverse Polarity Protection
24 V DC, 500 mA
External Supply Protection
Indications
External Power Requirement
1.5 KV opticalChannel to Channel
Channel to internal circuitIsolation
150 mA
32 Input Bits and 32 Output Bits
Removable 20 Pin Terminal Block
4333
Back-plane current
I/O points consumed
Terminal/Connection
Ordering Code
OutputVoltageRange -10 V To +10 V
Resolution 12 Bits (11 Bits + 1 Sign Bit)
Load Resistance > 1 K Ohm
Load Current 10 mA
Conversion Time 20 S�
ANALOG I/O MODULES
41
The module converts digital values data from CPU to
equivalent analog output voltage.It provides 4 non-
isolated channels with 16 bit resolution.
4 Channel Non Isolated Analog Output Module
4 Non Isolated, 16 Bit
R-2R Ladder
No. Of Output Channels
Conversion Method
150 mA
8 Input Bits And 8 Output Bits
Removable 20 Pin Terminal Block
4334
Back-plane current
I/O points consumed
Terminal/Connection
Ordering Code
Output Protection
Accuracy
Conversion Time
Output Voltage Range
Input Range
-10 To +10 V DC
-32,000 To +32,000
Resolution
Load Resistance
Load Current
312.5 V�
> 1 K Ohm
10 mA Maximum
0.5 % of Full Scale Reading.
50 S (Irrespective ofNo. of ON Channels)
�
Infinite Short Circuit Protection.
Nil1.5 KV optical
Channel to ChannelChannel to internal circuit
Isolation
�
�
No 24 V SupplyChannel On (For Each Channel)
315 mA miniature glassfuse on module
External Supply Protection
Indications
24 V DC, 300 mA18-30 VDC, Including Ripple)
External Power Requirement
This module converts 4 differential analog voltage inputs
to equivalent binary numbers with ADC, 16 bit resolution.
Similarly it converts binary data from CPU to analog
voltage output with DAC, 12 bit resolution.
Fast Analog I/O Module
Note: This module does not require any external power supply.
4 Differential
Sigma Delta with digital filter
No. Of Input Channels
Conversion Method
ADC Resolution
Output Range
Input Range
312.5 V (15 bit)�0 - 32000 (unipolar)
0 - 10 VDC, 0 - 20 mA
Analog To Digital Conversion Time 1 mS per Channel
2 Non-Isolated
R-2R Ladder
No. Of AnalogOutput Channels
Conversion Method
OutputVoltageRange
OutputVoltage
0 - 32000 (unipolar)
0 To 10 V DC
Resolution
Load Resistance
Load Current
Output Short Circuit Protection
Maximum Conversion Time
2.50 mV (12 bit)
> 1 K Ohm
10 mA Maximum
Yes
200 S�
Isolation(InputChannels)
Input ImpedanceVoltage
Current
1 M Ohms
500 Ohms
Nil1.5 KV optical
Channel to ChannelChannel to internalcircuit
NilInput Channel ToOutput ChannelIsolation
1000 mA
8 Input Bits And 8 Output Bits
Removable 38 Pin Terminal Block
4366
Back-plane current
I/O points consumed
Terminal/Connection
Ordering Code
�
�
�
No 5 V SupplyCPU FaultAnalog Input Channel Status (8)
Indications
625 A (15 bit)�
ANALOG I/O MODULES
42
4 Channel Counter Input Module
4 Channel Counter Input Modul provides: 4 channels for
counter inputs as A, B & Z. Four Z inputs can be
configured individually either as normal inputs (with
minium 10 mS pulse width) or as pulse catch input (with
minimum 10 mS pulse width) or reset to computer Counter Input Channels 4 maximum
Filter
Maximum frequency
ON time minimum 10 S for counter inputs�
Isolation Optical (1.5KV from internal bus)
Current 7 mA for Sink/source input17 mA for Differential input�
�
Indications GREEN LED for each inputYellow LED for Error
�
�
OFF time minimum 10 S for counter inputs�
50 Khz in Counter Mode of Operation25 Khz in Encoder Mode of Operation
Minimum Pulse Width 10 S for pulse catch type of input &reset type of input
�10 S�
Type of Inputs Sink/source/differential selectable bytype of connections to module
Back Plane Current 205 mA
IO points consumed 16 Input bits and 8 output bits
Terminal Connections Removable 38 pin terminal block
Ordering code 4634
Inputs 12
The Multifunction Input module provides mix of inputs with programmable filter
time, pulse catch input, interrupt input and counters with programmable 16 bit
operational mode. Programmable filter (10ms) and up counter is the default
configuration. In such case, the inputs are not available as normal inputs.
The pulse having minimum 500 sec ON time can be detected. Upon detection of
interrupt signal, the operating system of PLC branches to predefined interrupt
task.
The counters can be configured for :
i) 4 up counters or ii) 2 up/down counters or iii) 2 up & 1 up/down counter
�
The counters can be programmed for external reset using normal inputs.
Counting direction for up/down counter can be selected by external inputs
Multifunction Input Module
Filter Time /Max freq.
Remark
Counter
Input type
Back plane current :
I/O points consumed :
Ordering code
Channels
Up-Down counter with direction
input and programmable reset2
10 sec /10 Khz
�
24 V field interface. These inputscan be selected in groups of 4.
12 / 24 V field interface. These are accumulating typecounters. The count is added to predefined register
12 / 24 V field interface. The counter has external directioninput. This count is available in predefined register.
100 sec1ms, 10 ms
�
Discrete
Programmable Delay
Up Counter withprogrammable reset
12 (max)
205 mA
16 Input Bits and 16 Output Bits
4633
Programmable DelayPulse catch
10 sec /10 Khz
�
500 sec�2
4
COUNTER INPUT MODULE
HMIsHuman-Machine Interfaces (HMI) are panel mounted devices that provide effective dialogue between the operator and machine.
Equipped with programmable display and keys, HMIs allow easy operation and monitoring in the production area. HMIs display
operational and fault messages, enable machine specific parameters to be monitored and modified in suitable format. HMI keeps
the operator fully informed of the current status of operations at all times.
Benefits of using Human Machine Interface along with PLC
Replaces conventional push button panel (and related wiring), indicating lamps etc.
Connects to PLC via serial interface. So easy and quick installation
Simple operation and control
Clear display of information
Fault messages and instructions help reduce down time thereby improving productivity directly
�
�
�
�
�
The table summarises key features of Smartline series of Human Machine Interfaces.
HMI - JrItem
Display
Display type
LEDs
User Configurable Keys
Buzzer
Password
Memory
Maximum screens
Power
Dimensions W X H X D mm
16 charaters X 2 lines
LCD with back-lit
4 bicolour LEDs with 2 flash frequencies
4 (+ fixed function keypad)
-
-
8 K EEPROM
256
Derives power from PLC
125 X 75 X 45
HMI - Sr
20 characters X 4 lines
LCD with back-lit / VFD
28 LEDs
28
Potential free contact
3 levels
16 K EEPROM
256
External 24 V DC
200 X 180 X 55
Product development is a continuous process. Consequently specifications are subject to change without prior notice.For latest information please contact our nearest sales office.
Item Description
SMART
SMART
SMART
LINE
LINE
LINE
Jr
Sr
Sr
HMI with 16 Ch. X 2 Lines LCD (Backlit)
HMI with 20 Ch. X 4 Lines LCD (Backlit)
HMI with 20 Ch. X 4 Lines VFD
PC Based Software PackageV4.02, DOS based HMI configuration software on IBM compatible PC-XT/ATSOFTLINE
Serial Link Cable
From HMI Jr to IBM compatible PC-XT/AT & Link Adapter/Power Supply Unit
(Length 3 Mtrs.)
From HMI Sr to IBM compatible PC-XT/AT (Length 3 Mtrs.)
From E-Series operator terminal to IBM compatible PC-XT/AT (length 3 Mtrs.)
�
�
�
Ordering Code
SL JR 1602 LN
SL 2004 LN
SL 2004 VN
SFL V4.02
SL JR CAB 0300
SL CAB 0300E CAB 0300
Serial Port ConverterFor Port conversion of IBM compatible PC-XT/AT XMP8 SPC 2010
43
MESSUNG MAKE HMIs
E Series
�
-
1
Backlight Lifetime (h)
Text height (mm)
LEDs
Function keys
Dual drivers
Transparent mode (1)
Passthrough mode
Web functionality
Display type LCD
Presentation form
Backlit STN
Text
Active area of displayW x H (mm)
2 rows x16 characters
55.7 x 11.0
Ambient temperature
Multi Language / Unicode
Recipe handler
Alarm management
Time channels
Real-time clock
Trend graphs
Report printouts
Password for security
Buzzer
Terminal reflectionvia Internet
Communication interfaces
Support for Palm handheldsTM
Support for extendedkeyboard
EMC
LVD
UL
DNV
Power supply
Power consumption
Dimensions W x H x D (mm)
Weight (kg)
Memory for application
Number of expansioncard positions
50,000
5
-
4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0 ºC - + 50 ºC
-
EN 50081 -1,EN 61000-6-2
-
UL 508, UL 1604 (3)
+ 5 V DC ± 5 %
200 mA (5 V)
104 X 69 X 38(401” X 2.7” X 1.5”)
0.2
16 kb Flash
-
Backlit STN
Text
2 rows x20 characters
73.5 X 11.5
50,000
5
-
4
-
-
�
�
�
� / -
�
�
�
�
-
-
8 levels
-
RS422 and RS 232C
�
-
EN 50081 -1,EN 61000-6-2
-
UL 508, UL 1604 (3)
+ 5 V DC ± 5 %
200 mA (5 V)
142 X 100 X 29(5.6” X 3.5” X 1.1”)
0.5
64 kb Flash
-
RS422 or RS 232C
�
�
Waterproof front IP65, NEMA 4X (2)
0 ºC - + 50 ºC
IP65, NEMA 4X (2)
Backlit STN
Text
2 rows x20 characters
73.5 X 11.5
50,000
5
-
6 (text strip)
-
-
�
�
�
-
EN 50081 -1,EN 61000-6-2
-
UL 508, UL 1604 (3)
+ 5 V DC ± 5 %
200 mA (5 V)
142 X 100 X 29(5.6” X 3.5” X 1.1”)
0.5
64 kb Flash
-
0 ºC - + 50 ºC
IP65, NEMA 4X (2)
Backlit STN
Text
4 rows x20 characters
70.4 x 20.8
50,000
5
5 (two colors)
5 (text strip)
-
-
�
�
�
-
EN 50081 -1,EN 61000-6-2
-
UL 508, UL 1604 (3)
+24 V DC, 20-30 V
150 mA (24 V)
147 X 163.5 X 38(5.8” X 6.4” X 1.5”)
0.7
64 kb Flash
-
0 ºC - + 50 ºC
IP65, NEMA 4X (2)
Backlit STN
Graphic + Text
240 x 64 pixels
127.2 x 33.9 (5.2”)
50,000
Variable
16 (two colors)
8 (text strip)
�
�
�
�
�
EN 50081 -1,EN 61000-6-2
UL 508, UL 1604 (3)
+24 V DC, 20-30 V
450 mA (24 V)
211 X 198 X 69(8.3” X 7.8” X 2.7”)
1.5
400 kb Flash /8 Mb expansion
0 ºC - + 50 ºC
IP65, NEMA 4X (2)
Graphic + Text
240 x 128 pixels
120 x 64 (5.3”)
15,000
Variable
16 (two colors)
16 ( 8 with text strip)
�
�
�
�
�
EN 50081 -1,EN 61000-6-2
-
UL 508, UL 1604 (3)
+24 V DC, 20-30 V
450 mA (24 V)
214 X 232 X 879(8.4” X 9.1” X 3.4”)
1.4
400 kb Flash /8 Mb expansion
1
0 ºC - + 50 ºC
IP65, NEMA 4X (2)
Display size
Backlit STN,black / white
� � � � �
RS422 and RS 232C
�
RS422 and RS 232C
�
RS422 and RS 232C
�
RS422 and RS 232C
�
�
� / -
�
�
�
�
-
-
8 levels
-
� / -
�
�
�
�
1 group
-
8 levels
-
� �/ � �/
�
�
�
�
Up to 4 groups
Real time
8 levels
-
�
�
�
�
Up to 4 groups
Historic
8 levels
-
E50 E100 E150 E200 E300 E600
44
A COMPLETE FAMILY OFBEIJER MAKE E-SERIES OPERATOR TERMINALS
E Series
Backlit STN,16 grays, touch
Backlit STN / TFAcolour, touch
Backlit STN colour,touch
Backlit TFT colour, touch
E615 / E615T E710
Graphic + Text
320 x 240 pixels
115.2 x 86.4 (5.7”)
25,000
Variable
-
-
�
�
�
�
�
RS485, RS422,RS 232C (4)
EN 50081 -1,EN 61000-6-2
-
UL 508, UL 1604 (3)
+24 V DC, 20-30 V
400 mA (24 V)
200 X 150 X 69(7.8” X 5.9” X 2.7”)
1.5
400 kb Flash /8 Mb expansion
1
0 ºC - + 50 ºC
IP65, NEMA 4X (2)
Graphic + Text
320 x 240 pixels
115.2 x 86.4 (5.7”)
40,000 / 50,000
Variable
-
-
�
�
�
�
�
RS485, RS422,RS 232C (4)
EN 50081-2, EN 61000-6-2 /EN 50081-1, EN 61000-6-2 /
-
UL 508, UL 1604 (3) / -
+24 V DC, 20-30 V
450 mA (24 V)
200 X 150 X 69(7.8” X 5.9” X 2.7”)
1.5
400 kb Flash /8 Mb expansion
1
0 ºC - + 50 ºC
IP65, NEMA 4X (2)
Graphic + Text
320 x 240 pixels
115.2 x 86.4 (5.7”)
40,000
Variable
14 (two colors)
16 ( 8 with text strip)
�
�
�
�
�
RS422 and RS232C
EN 61000-6-3,EN 61000-6-2
-
UL 508, UL 1604 (3)
+24 V DC, 20-30 V
550 mA (24 V)
276 X 198 X 89(10.9” X 7.8” X 3.5”)
1.7
400 kb Flash /8 Mb expansion
2
0 ºC - + 50 ºC
IP65, NEMA 4X (2)
Backlit STN colour
Graphic + Text
320 x 240 pixels
115.2 x 86.4 (5.7”)
40,000
Variable
8 (two colors)
8 (text strip)
�
�
�
�
�
RS422 and RS232C
EN 61000-6-3,EN 61000-6-2
-
UL 508, UL 1604 (3)
+24 V DC, 20-30 V
550 mA (24 V)
276 X 198 X 89(10.9” X 7.8” X 3.5”)
1.7
400 kb Flash /8 Mb expansion
2
0 ºC - + 50 ºC
IP65, NEMA 4X (2)
Graphic + Text
640 x 480 pixels
211.25 x 158.4 (10.4”)
50,000
Variable
20 (two colors)
22 (10 with text strip)
�
�
�
�
�
RS422 and RS232C
EN 50081-2, EN 61000-6-2 /EN 61000-6-4, EN 61000-6-2
EN 60950 / -
UL 1950, UL 1604 (3) /UL 508, UL 1604 (3)
100-240 V AC /24 V DC, 20-30 V
Max 0.35 A / 1A
367 X 274 X 90(14.4” X 10.8” X 3.5”)
3.5
1,600 kb Flash /8 Mb expansion
2
0 ºC - + 50 ºC
IP65, NEMA 4 /IP 65, NEMA 4X (2)
Backlit TFT colour
Graphic + Text
640 x 480 pixels
211.25 x 158.4 (10.4”)
50,000
Variable
-
-
�
�
�
�
�
RS422 and RS232C
EN 50081-2, EN 61000-6-2 /EN 61000-6-4, EN 61000-6-2
EN 60950 / -
UL 1950, UL 1604 (3) /UL 508, UL 1604 (3)
100-240 V AC /24 V DC, 20-30 V
Max 0.35 A / 1A
290 X 250 X 105(11.4” X 9.8” X 4.1”)
3.3
1,600 kb Flash /8 Mb expansion
2
0 ºC - + 50 ºC
IP65, NEMA 4 /IP 65, NEMA 4X (2)
� / -� � � � �
� � � � � �
������
� �/
�
�
�
�
Uup to 5 groups
Historic
8 levels
-
�
�
�
�
Up to 5 groups
Historic
8 levels
-
� �/ � �/
�
�
�
�
Up to 16 groups
Historic
8 levels
-
� �/ � �/
�
�
�
�
Up to 5 groups
Historic
8 levels
-
�
�
�
�
Up to 16 groups
Historic
8 levels
-
�
�
�
�
Up to 11 groups
Historic
8 levels
-
� �/
E700 E900T / E900TDE610 E910T / E910TD
45
HMI ConnectivityNexgen 5000 PLCs and HMI Interface
Note: When HMI Smartline Jr.
is interfaced with Nexgen
521x Third port, operational
power for HMI, needs to be
externally provided.
HMI
5210 / 5213 / 5214
Port 2
RS 422
SL JR CAB 07��
SL CAB 07��
5211
Port 3
RS 232C
NA
U.D.
5211
RS 232C
U.D.
U.D.
Features
Jr. HMI
Sr. HMI
: 3, 5, 10, 15, 20, 25 Mtrs.��
Nexgen 521x Series of CPU Connectivity to Messung HMI
HMI5221-B0 / P4 & 5222-B0 / P4
SL JR CAB PS 09 23��
SL CAB 09 23��
Port 2 / Port 3Features
Jr. HMI
Sr. HMI
: 3, 5, 10, 15, 20, 25 Mtrs.��
Nexgen 522x Series of CPU Connectivity to Messung HMI
HMI
5210 / 5213 / 5214
Port 2
RS 422
U.D.
5211
Port 3
RS 232C
NA
U.D.
5211
U.D.
NA
Features
BeijerE100 - E50
** : 5 Mtrs. Only available
: 3, 5, 10, 15, 20, 25 Mtrs.��
Nexgen 521x Series of CPU Connectivity to Beijer HMI & Mitsubishi GOT
RS 422
Port 1 : RS 422
Port 2 : RS 232 C
ECAB 07�� NA
U.D.
U.D.
NA
Beijer E200onwards
Port 1 : RS 422
Port 2 : RS 232 C
GOT CAB �� 08 02 NA GOT 05 08 03**Mitsubishi GOT 930 / 940
NA
NA
Nexgen 522x Series of CPU Connectivity to Beijer HMI & Mitsubishi GOT
HMI
U.D.
Port 2 / Port 3
U.D.
Features
BeijerE100 - E50
: 3, 5, 10, 15, 20, 25 Mtrs.��
Port 1 : RS 422
Port 2 : RS 232 C
ECAB 09 23��
U.D.
Beijer E200onwards
Port 1 : RS 422
Port 2 : RS 232 C
GOT CAB �� 08 23Mitsubishi GOT 930 / 940
46
5221-B0 / P4 & 5222-B0 / P4
P2 P3
24VSupply
MasterCPU 521x Setup
P2 P3
24VSupply
12VSupply
MasterCPU 522x Setup
U.D. : UNDER DEVELOPMENT
ORDERING INFORMATION :
HMI CONNECTIVITY
Nexgen 5000 CPU
The expansion cable is used in multi-rack system for connecting
base or expansion plate to expansion plate. These cables are
available in different lengths.
Expansion Cable (Length)
0.5 meter
1 meter
2 meters
3 meters
Ordering Code
4940
4941
4942
4943
Item Description
BASE PLATES
8 I/0 without expansion connector
5 I/0 without expansion connector
3 I/0 without expansion connector
8 I/0 with expansion connector
5 I/0 with expansion connector
3 I/0 with expansion connector
OrderingCode
4906
4932
4930
4937
4938
4939
EXPANSION PLATES
8 I/0 without Slot for Aux Power Supply
5 I/0 without Slot for Aux Power Supply
3 I/0 without Slot for Aux Power Supply
8 I/0 with Slot for Aux Power Supply
5 I/0 with Slot for Aux Power Supply
3 I/0 with Slot for Aux Power Supply
4934
4935
4936
4907
4933
4931
Item DescriptionOrdering
Code
Item Description OrderingCode
Processor Series : 521x
5210
5211
5212
5213
5214
Sr.No.
Basic CPU
CPU, with 3rd Port - RS 232
CPU, with 3rd Port - RS 422 / 485
Low-cost CPU
CPU with 2 Ch. HSC + 2 Ch. PTO
I
1
2
3
4
5
Processor Series : 522x
CP 5220-B0
CP 5220-P4
CP 5221-B0
CP 5221-P4
CP 5222-B0
CP 5222-P4
5910
5911
* Back Plane
Current (mA) at 5 V DC
600
600
600
600
600
600
600
600
600
600
600
Basic CPU with Only PG Port .
CPU with PG Port & 2HSC+2PTO.
Basic CPU with 1 AUX Port.
CPU with 1 AUX Port & 2HSC+2PTO.
Basic CPU with 2 AUX Ports.
CPU with 2 AUX Ports & 2HSC+2PTO.
Pluggable Keyboard + Display for CPU 522x Series.
Blanking Module for CPU 522x Series.
II
1
2
3
4
5
6
7
8
Accessories to be used along with CPU 5214 as well as with CP 522x-P4,
as per the application requirements...
Patch Panel, 2 Ch.,100 KHz Max. HSC & 2 Ch.,5 KHz Max. PNP Type PTO
Patch Panel, 2 Ch.HSC,100 KHz Max. & 2 Ch.,100 KHz RS-422 Type PTO
Interface Cable (0.5 Meter Length)
Interface Cable (1 Meter Length)
1
2
3
4
Program Memory Cassette - 256 KB1
2 Serial Communication Cable betweenCPU 521x series & PC, for programming purpose
Docking Station
'CoDeSys' - Windows based Programming & Documentation Software
3 Serial Communication Cable betweenCPU 522x series & PC, for programming purpose
4960
4962
4944
4945
9904
4806
9911
9920
9910
4
5
47
ORDERING INFORMATION :
NEXGEN CPU 5000 SERIES
I/O Modules
48
* Please note that if current consumption at 5 V DC of CPU, for all Digital & Analog Module I/O modules exceeds 5 A,an additional power supply is required to be ordered.
I/O MODULESOrdering
Code
TerminalBlock
Required
* Back Plane
Current (mA)at 5 V DC
DISCRETE OUTPUT MODULES
8 Triac O/Ps, 110/220 V AC @ 1.5 A with fuse protection
32 DC O/Ps, 24 V DC @ 0.2 A with short circuit protection, Source Type
16 DC O/PS 24 V DC @ 1.5 A with short circuit protection, Source Type
16 Relay O/Ps (Potential Free) 24-250 V AC @ 750 mA
4711
4732
4716
4721
20 pin
38 pin
20 pin
38 pin
210
315
200
185
DISCRETE INPUT MODULES
16 I/Ps 24 V DC, Source/Sink Selectable
16 I/Ps, 110/220 V AC:
32 l/Ps, 24 V DC, Source/Sink Selectable
16 Channels, Multifunction Input, Source/Sink Selectable
4 Channel Counter Input Module
4616
4617
4632
4633
4634
20 pin
20 pin
38 pin
38 pin
38 pin
110
90
110
205
205
MIXED DIGITAL INPUT-OUT MODULES
16 DC I/Ps, 24 V Source/Sink Selectable, 8 Relay O/Ps (Potential Free)
24-250 V AC @ 0.75 A
16 DC I/Ps, 24 V Source/Sink Selectable, 8 DC O/Ps 24 V @ 1.5 A
With shot circuit protection, source type
4424
4425
38 pin
38 pin
220
220
ANALOG OUTPUT MODULES
2 Channel, 12 bit, Isolated Output Module (Voltage/Current Type)
2 Channel, 12 bit, Isolated Output Module (Voltage Type)
4 Channel, 16 bit, Non-Isolated Output Module
4332
4333
4334
20 pin
20 pin
20 pin
150
150
300
FAST ANALOG INPUT & OUTPUT MODULES
4 Channel, High Speed , Non-isolated, 16 Bit Analog Input (V / I) &
2 Channel, Non-isolated, 12 Bit, Analog Output (Voltage type)
4366 38 pin1000
4308
4310
4311
38 pin
38 pin
38 pin
400
250
250
ANALOG INPUT MODULES
8 Channel, 16 bit, non-isolated Input Module
8 Channel, 16 bit, Thermocouple Input Module,For Interfacing J,K,T,E,N,R,S,B type of thermocouples
8 Channel, 16 bit, RTD Input Module, For Interfacing PT-100 Sensors
POWER SUPPLY MODULE Ordering Code
PSU 220 V AC, 5 V DC - 5 A,
12 V DC - 0.5 A4110
4112PSU 24 V DC, 5 V DC - 5 A,
12 V DC - 0.5 A
TERMINAL BLOCKS Ordering Code
Terminal blocks - 20 pin
Terminal blocks - 38 pin
Prewired Terminal Block - 38 pin
4908
4909
4910
ORDERING INFORMATION :
PSU, I/O MODULES
�
�
�
�
Nexgen CPU 523x series supports CANbus connectivity
Distributed configuration: Low cost, shielded, twisted cable
Maximum of 31 stations of digital / analog remote I/Os over adistance of 500 meters
Network configuration through software
Highlights
�
�
�
Reduced wiring leads to quick installation
Network expansion by add on
Easy diagnostics & troubleshooting
Benefits
" A STEP IN TO THE FUTURE "
INTR
ODUCING
-Bus Based Automation SystemsCAN
GATEWAY
"CANopen" - An Internationally Accepted Fieldbus System
Nexgen CPU -523x Series PLC - Slave
indiCAN -Remote Analog I/Os
indiCAN -Remote Digital I/Os
Under Development
CANopen GATEWAYS
Text HMI
Graphic HMI
MitsubishiAC VFD / Inverter -
Slave
MitsubishiAC Servo System -
Slave
GATEWAY
GATEWAY
GATEWAY
GATEWAY
Nexgen CPU -523x Series PLC - Master
IPC - Master / Slave PLC Configurator &Network Monitor
GATEWAY
PC
OPC Server
ww
w.inte
ricsdesig
ns.c
om
EL-2, J BLOCK, M.I.D.C. BHOSARI,PUNE - 411 026. INDIATEL : +91(20)27102000FAX : +91(20)27102100email : [email protected]:www.messungautomation.com
MESSUNG SYSTEMSMANUFACTURER OF PLCs & HMIs
TM
DOCUMENT NO. : 6317 (2000;10/2003)
MESSUNG AREA OFFICES
NEW DELHI
MESSUNG SYSTEMSTEL:+91(11)26385609 /
26386128FAX:+91(11)26384389
BARODA
MESSUNG SYSTEMSTEL:+91(265)2314699 /
2358137FAX:+91(265)2333307
PUNE
MESSUNG SYSTEMS91(20)7110862 /
7110865FAX:+91(20)7121402
TEL:+
HYDERABAD
MESSUNG SYSTEMSTEL:+91(40)27722519 /
27720308FAX:+91(40)27722519
BANGALORE
MESSUNG SYSTEMSTEL:+91(80)5092119 /
5320480FAX:+91(80)5320480
MUMBAI
MESSUNG SYSTEMSTEL:+91(22)26177700 /
56949564FAX:+91(22)26177710
AREA DISTRIBUTORS
CHENNAI
C/MOS PROCESSORS91(44)26287653 /
26217942FAX:+91(44)26287653
TEL:+
KOLKATA
TTS SYSTEMATIX PVT. LTD91(33)24635645
FAX:+91(33)24635646TEL:+
BANGALORE
LEONARDO AUTOMATION(80)3283030 /
3287161FAX:+91(80)3282613
TEL:+91
NASIK
DIGILOG SYSTEMS91(253)2578834 /
2570085FAX:+91(253)2573834
TEL:+