t-line condensing units pprroodduucctt ddproduct …docs.t-rp.com/archive/t-line 1064622.pdf · •...

28
INDOOR & OUTDOOR AIR COOLED SEMI-HERMETIC CONDENSING UNITS 3 TO 30 HP 1064622 Bulletin T40-T-PDS-13 T-LINE CONDENSING UNITS PRODUCT D PRODUCT D PRODUCT D PRODUCT D PRODUCT DATA & A & A & A & A & SPECIFICA SPECIFICA SPECIFICA SPECIFICA SPECIFICATIONS TIONS TIONS TIONS TIONS CONTENTS Page Features................................................................................................................................ 2 Nomenclature........................................................................................................................ 2 CAPACITY DATA Copeland R22 - High/Medium Temp................................................................................. 3 Carlyle R22 - High/Medium Temp...................................................................................... 4 Copeland R134a - High/Medium Temp............................................................................. 5 Carlyle R134a - High/Medium Temp.................................................................................. 6 Copeland R404A, R507 High/Medium Temp................................................................... 7 Copeland R404A, R507 Low Temp................................................................................... 8 Carlyle R404A/R507 - Low Temp....................................................................................... 9 Copeland R22 High/Medium Temp.................................................................................... 10 Copeland R502 Low Temp................................................................................................. 11 Carlyle R502 - Low Temp.................................................................................................... 12 Dimensional Data................................................................................................................ 13, 14 Specifications....................................................................................................................... 15, 16, 17 Electrical Specifications...................................................................................................... 18 - 27 We are on the Internet We are on the Internet We are on the Internet We are on the Internet We are on the Internet www.trentonrefrigeration.com DISCONTINUED PRODUCT

Upload: others

Post on 18-Jan-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

INDOOR & OUTDOORAIR COOLED SEMI-HERMETICCONDENSING UNITS

3 TO 30 HP

1064622

Bulletin T40-T-PDS-13

T-LINECONDENSINGUNITS

PRODUCT DPRODUCT DPRODUCT DPRODUCT DPRODUCT DAAAAATTTTTA &A &A &A &A &SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS

CONTENTSPage

Features................................................................................................................................ 2Nomenclature........................................................................................................................ 2

CAPACITY DATACopeland R22 - High/Medium Temp................................................................................. 3Carlyle R22 - High/Medium Temp...................................................................................... 4Copeland R134a - High/Medium Temp............................................................................. 5Carlyle R134a - High/Medium Temp.................................................................................. 6Copeland R404A, R507 High/Medium Temp................................................................... 7Copeland R404A, R507 Low Temp................................................................................... 8Carlyle R404A/R507 - Low Temp....................................................................................... 9Copeland R22 High/Medium Temp.................................................................................... 10Copeland R502 Low Temp................................................................................................. 11Carlyle R502 - Low Temp.................................................................................................... 12

Dimensional Data................................................................................................................ 13, 14Specifications....................................................................................................................... 15, 16, 17Electrical Specifications...................................................................................................... 18 - 27

We are on the InternetWe are on the InternetWe are on the InternetWe are on the InternetWe are on the Internetwww.trentonrefrigeration.com

DISC

ONTI

NUED

PROD

UCT

Page 2: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

OPTIONAL FEATURES(FACTORY MOUNTED)• Suction accumulator• Sealed or replaceable core suction filter with vibration eliminator• Oil separator c/w oil return filter and solenoid valve• Over-sized receiver• Heated and insulated receiver• Receiver inlet valve• Sealed or replaceable core liquid line filter drier and sight glass• Liquid line solenoid valve with 230 volt coil (shipped loose)• Ball valve (shipped loose)• Sentronic oil failure control• Two valve adjustable flooded head pressure control• Flex hose on all controls• Compressor circuit breaker• Compressor time delay relay• Pump down toggle switch• Time clock• Defrost contactor with fuse block• Evaporator fan contactor with fuse block• Adjustable pressure or ambient fan cycling control on 2 fan models only• Fused disconnect• Phase / voltage monitor

STANDARD FEATURES INCLUDE:

FEATURES

- 2 -

Indoor UnitStandard Features Include:• Weatherproof electrical control box with compressor contactor and fused control circuit• Spring mounted, accessible semi-hermetic compressor• Discharge vibration eliminator• Copper tubing secured with Hydra-Zorb / Cush-A- Clamp• Receiver with fusible plug and liquid shut off valve• Fan Guard• Adjustable dual high / low pressure control• Oil failure control on all applicable models• Demand Cooling TM on R22 low temp. models• Sealed liquid line filter drier and sight glass (Standard in R404A units only)

Outdoor UnitAll Standard Features of Indoor Unit Plus:• Outdoor weather-resistant housing with removable hood• Sealed liquid line filter drier and sight glass• Flooded head pressure control (non adjustable)• Adjustable pressure fan cycling control on 2 fan models only• Crankcase heater• Pump down toggle switch• Two valve adjustable flooded head pressure control (standard on M8 units)

T(C) 300 M 8 - H T3 AT = CopelandTC = Carlyle

Nominal Horsepower030 = 3 hp 065 = 6 1/2 hp031 = 3+ hp 075 = 7 1/2 hp035 = 3 1/2 hp 076 = 7 1/2+ hp040 = 4 hp 090 = 9 hp050 = 5 hp 100 = 10 hp051 = 5+ hp 101 = 10+ hp060 = 6 hp 150 = 15 hp061 = 6+ hp 200 = 20 hp (22 low)062 = 6++ hp 250 = 25 hp (27 low)063 = 6+++ hp 300 = 30 hp

Application RangeL = Low (-40 oF to 0 oF Suction)M = Medium / High(-5 oF to +40 oF Suction)unless otherwise specified

Series / Generation

Voltage*S2 = 208-230/1/60S6 = 200-220/1/50T3 = 208-230/3/60T4 = 460/3/60T5 = 575/3/60T7 = 200-220/3/50T8 = 380/3/60T9 = 380-400/3/50* Subject to compressor availability

H = OutdoorI = Indoor

Refrigerant1 = R134a2 = R225 = R5026 = R404A/R5078 = R22, R404A, R507

OTHER OPTIONS AVAILABLE AT YOUR REQUEST - CONSULT FACTORY

NOMENCLATURE

Fused Control Circuit

Compressor Contactor

Semi Hermetic Compressor

Fan Cycling Control

Dual Pressure Control

Oil Failure Control

Liquid Line Filter Drier,Sight Glass

Receiver Outlet Shut-Off Valve

DISC

ONTI

NUED

PROD

UCT

Page 3: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

60Hz COPELAND PERFORMANCE CAPACITYApplication Data Calculated at 65° F Return Gas, 0°F Liquid Subcooling

R22 - HIGH/MEDIUM TEMPERATURE - CAPACITY (BTU/HR)Unit Shipped with polyolester oil

- 3 -

* COMPRESSOR MODEL SHOWN IS FOR 208-230/3/60, EXACT MODEL MAY VARY WITH OTHER VOLTAGES.

COND. UNITMODEL *

SAT. SUCTIONTEMP. °F 80°F Amb. 90°F Amb. 95°F Amb. 100°F Amb. 105°F Amb.

T030M8Compressor Model

ERFA-031E

4030252010

3699030520276102486019990

3490028880260802345018800

3394028060253302276018220

3298027420245802207017640

3202023830238302139017060

T050M8Compressor Model

2DC3-050E

4030252010

6558054880498404507036450

6133051290465604208034010

5938049550449704062032760

5733047810433703916031550

5519046070417803771030350

T051M8Compressor Model

2DD3-050E

4030252010

7418062240566105125041540

6957058230529304789038790

6728056280511404625037390

6498054330493504461036030

6259052390475704298034670

T075M8Compressor Model

2DL3-075E

4030252010

9401078590711206435052030

8837073590667806033048710

8530071230646205834047030

8252068870624505637045380

7974066520603005439043740

T076M8Compressor Model

3DA3-075E

4030252010

125480104550950608596069530

11776098460893708075065180

11434095430865807819063050

11078092400838007565060920

10723089380810307310058800

T100M8Compressor Model

3DB3-100E

4030252010

14778012317011188010129091850

1394201160601053509520076870

1352901125201021009222074370

130510108980988508924071880

126510105460956108627069400

T150M8Compressor Model

3DS3-150E

4030252010

192840162330147750133860108670

181440152350138570125450101630

17602014768013410012134098190

17032014265012963011725094760

16464013881012518011316091340

T200M8Compressor Model

4DA3-200E

4030252010

220750183300166570150200120800

207290172780156600140790113380

201100167500151190136350109670

194900161600146350131900105970

188770156340141500127490102280

T250M8Compressor Model

4DH3-250E

4030252010

280170234830213800193060156490

262240220560199560180650145800

254260212600193000174600140730

244590205450186370167900135600

236600198290179090161860130600

T300M8Compressor Model

4DJ3-300E

4030252010

308300259900235900214000173100

291000243900222000200000162500

281000236400214000193700156300

271000228000207300187300150900

262000220100200300180200145500DI

SCON

TINU

ED

PROD

UCT

Page 4: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

60Hz CARLYLE PERFORMANCE CAPACITYApplication Data Calculated at 65 °F. Return Gas, 0 °F. Liquid Subcooling

R22 - HIGH/MEDIUM TEMPERATURE - CAPACITY (BTU/HR)Unit Shipped with mineral oil

- 4 -

COND. UNIT

MODEL

SAT. SUCTION

TEMP. °F80°F Amb. 90°F Amb. 95°F Amb. 100°F Amb. 105°F Amb.

TC030M2

Compressor Model

06DM808

40

30

25

20

10

40970

33880

30610

27500

21870

38160

32630

28560

25640

20410

37040

30570

27590

24760

19630

35780

29510

26620

23880

18910

34510

28450

25660

23000

18190

TC050M2

Compressor Model

06DM313

40

30

25

20

10

64770

53910

48780

43890

35000

60080

49970

45190

40640

32470

58140

48140

43510

39110

31100

55940

46270

41820

37570

29840

53510

44430

40130

36040

28590

TC075M2

Compressor Model

06DA818

40

30

25

20

10

92430

76780

69400

62160

49470

86920

71640

64710

58110

46150

84160

69310

62580

56180

44560

81390

66990

60460

54250

42980

78320

64660

58340

52320

41400

TC076M2

Compressor Model

06DA824

40

30

25

20

10

120300

100040

90610

81600

65160

111320

92790

83990

75590

60430

107620

89370

80840

72720

57900

103530

85920

77690

69860

55560

99430

82440

74540

66990

53220

TC100M2

Compressor Model

06DA-328

40

30

25

20

10

140950

117170

105250

94920

75600

132620

109330

98780

88750

70540

128450

105820

95570

85830

68130

123820

102310

92370

82900

65730

119650

98800

89160

79990

63330

TC150M2

Compressor Model

06DA537

40

30

25

20

10

187350

155850

141060

127040

101490

174870

146250

131890

118690

94610

169300

141500

128000

114730

91350

164330

136750

123650

110790

88090

158740

132010

118950

106850

84840

TC200M2

Compressor Model

O6EA250

40

30

25

20

10

252160

210090

189490

171070

136050

233500

194860

176480

158900

126570

225110

188130

169980

152410

121440

217140

181030

162860

146490

116570

208780

172910

156360

140570

111700

TC250M2

Compressor Model

06EA265

40

30

25

20

10

322560

270990

246880

223420

119360

301640

253160

229120

207090

166350

291030

242900

220760

199750

159410

279380

233800

212400

192010

153070

268870

224690

204020

184420

146730

DISC

ONTI

NUED

PROD

UCT

Page 5: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

60Hz COPELAND PERFORMANCE CAPACITYApplication Data Calculated at 65 °F. Return Gas, 0 °F. Liquid Subcooling

R134a - HIGH/MEDIUM TEMPERATURE - CAPACITY (BTU/HR)Unit Shipped with polyolester oil

- 5 -

* COMPRESSOR MODEL SHOWN IS FOR 208-230/3/60, EXACT MODEL MAY VARY WITH OTHER VOLTAGES.

COND. UNITMODEL *

SAT. SUCTIONTEMP. °F

80°F Amb. 90°F Amb. 95°F Amb. 100°F Amb. 105°F Amb.

T029M1Compressor Model

LAHA-031E

2520100-5

2745124262187521459512297

2536822517172031321011107

2447721479165641256810716

2353920450156771206010162

224621959014932114249613

T030M1Compressor Model

2DF3-030E

4030252010

5313043370389903415027540

4935040250361003235025590

4766038800349003105024490

4578037400335002980023490

4410035980321902866022480

T060M1Compressor Model

2DA3-060E

4030252010

6535053840484204308034360

6134049980448404000031800

5908048170432003856030430

5698046390415703705029160

5463044600399403555027880

T062M1Compressor Model

3DA3A060E

4030252010

7627062740566705084040500

7176058990529604732037460

6902056890509304553036000

6670054680491304387034540

6438052730473304220033080

T063M1Compressor Model

3DA3A060E

4030252010

8002065780589205277041920

7529061700549204906038910

7257059160531504743037160

7013057140512904543035650

6739055120494204370034150

T075M1Compressor Model

3DB3A075E

4030252010

9280075890683506102048420

8654070890637305668044860

8375068520612105466042930

8097065800590205264041170

7783083420568305069039420

T090M1Compressor Model

3DF3A090E

4030252010

10945090330810207265057590

10232084140756806742053580

9874081310731806502051430

9559074870701106261049390

9224075260675006022047350

T100M1Compressor Model

3DS3A100E

4030252010

11934098530883007929063220

11215091920826907387058450

10791088670696707092056090

10427085540764506825053850

10062082420735606560051600

T101M1Compressor Model

4DA3-100E

4030252010

133100106680948008360066150

12403099430883807846061690

11956096040845807542059490

11460092690825207281057420

11030089320792207024055340

T150M1Compressor Model

4DH3-150E

40302520

172190141050126910113640

159850131450118200104880

153840126200112950100740

14726012123010840096660

14132011573010389092580DI

SCON

TINU

ED

PROD

UCT

Page 6: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

60Hz CARLYLE PERFORMANCE CAPACITYApplication Data Calculated at 65 °F. Return Gas, 0 °F. Liquid Subcooling

R134a - HIGH/MEDIUM TEMPERATURE - CAPACITY (BTU/HR)Unit Shipped with polyolester oil

- 6 -

COND. UNIT

MODEL

SAT. SUCTION

TEMP. °F80°F Amb. 90°F Amb. 95°F Amb. 100°F Amb. 105°F Amb.

TC029M1

Compressor Model

06DR013

40

30

25

20

10

0

39700

31730

28840

25150

18080

14560

36680

29210

25910

22830

17440

12810

35200

27980

24700

21830

16600

12100

33760

26770

23100

20810

15610

11280

32260

25560

22460

19810

14560

10480

TC051M1

Compressor Model

06DR316

40

30

25

20

10

0

55630

44310

39800

35380

27450

20900

51280

41120

36900

32560

25380

19280

49600

39740

35100

31440

24270

18420

47870

38130

33900

30360

23390

17710

45830

36670

32200

28940

22310

16860

TC052M1

Compressor Model

O6DR718

40

30

25

20

10

0

64580

51710

46400

41280

32230

24550

59840

49390

42740

37560

29550

22640

57810

46320

41230

36580

28490

21630

55770

44240

39820

35300

27180

20600

53310

42640

37920

33360

25930

19780

TC060M1

Compressor Model

O6DR820

40

30

25

20

10

0

71890

58050

51900

46330

36390

27850

66690

54180

48700

43510

33800

25820

64610

52090

46520

41760

32340

24560

62560

50410

45160

40010

30920

23610

60460

48260

43430

38260

29720

22450

TC065M1

Compressor Model

O6DR724

40

30

25

20

10

0

84390

67800

60710

53620

41260

30980

78620

62320

55720

49180

37550

27600

74930

59930

53120

46630

35490

26270

72020

56980

50210

44640

33880

24610

69180

51110

46910

42270

31930

23020

TC075M1

Compressor Model

O6DR228

40

30

25

20

10

0

96240

78080

70540

63030

49710

38210

90920

73660

66220

58880

46300

35360

87540

71450

64200

57040

44370

34080

84870

68430

61520

54710

42850

32490

82210

66430

59140

52890

40950

31200

TC100M1

Compressor Model

O6DR337

40

30

25

20

10

0

124100

102080

92510

82910

65920

51180

116710

96020

85960

77860

61580

47940

113510

93230

83990

74740

59810

45860

110220

89810

81450

72960

57370

44240

105970

87500

78620

69820

54930

42130DISC

ONTI

NUED

PROD

UCT

Page 7: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

60Hz COPELAND PERFORMANCE CAPACITYApplication Data Calculated at 65 °F. Return Gas, 0 °F. Liquid Subcooling

R404A, R507 - HIGH/MEDIUM TEMPERATURE - CAPACITY (BTU/HR)Unit Shipped with polyolester oil

- 7 -

* COMPRESSOR MODEL SHOWN IS FOR 208-230/3/60, EXACT MODEL MAY VARY WITH OTHER VOLTAGES.

COND. UNITMODEL *

SAT. SUCTIONTEMP. °F 80°F Amb. 90°F Amb. 95°F Amb. 100°F Amb. 105°F Amb.

T030M8Compressor Model

ERFA-031E

4030252010

4113035420326702993024570

3708032150296402713022050

3519030510281402557020870

3331028900264502419019700

3144027080249502281018530

T050M8Compressor Model

2DC3-050E

4030252010

6702055930509104587036850

6104050910463404172033460

5805048710440703939031780

5549046230418103761029910

5253043750395503532028220

T051M8Compressor Model

2DD3-050E

4030252010

7727065450592405392043610

7089059670539304909339680

6698056790512904669037720

6410053910486604399035530

6024050620463904192033560

T075M8Compressor Model

2DL3-075E

4030252010

9744081570739206718054610

8857074450679906080049600

8451071390640805795047290

8092068010609505547044750

7691063700578805234042430

T076M8Compressor Model

3DA3-075E

4030252010

127560108110981608847072710

11714099570897308150066780

11192094080863207800063970

10738090320819907456061180

10224085520786707155058360

T100M8Compressor Model

3DB3-100E

4030252010

15025012989011639010648087870

1386501170101075109669080200

1317501124701028309235076250

126450107350967008812072730

120370100770920608445069180

T150M8Compressor Model

3DS3-150E

4030252010

199090170590156330140900117170

183460155380142410129150107560

172450148360136010123280102160

16783014137012861011837097400

15581013323012329011260092610

T200M8Compressor Model

4DA3-200E

4030252010

226250192910175330161800130540

206050174500160160146700118110

197300165820152150139250111930

187290158230144170131800105060

17731014962013621012436098830

T250M8Compressor Model

4DH3-250E

4030252010

267590231730212110195230160940

256900211100195400178700146980

233970201460186500169200140050

223010193250176240162300132220

213710182090168790154140125250

T300M8Compressor Model

4DJ3-300E

4030252010

315130268170249740225290187340

290520244600224585205380170850

278640232890215700195300161410

260890223380203010187190153240

245030209560194310177390146380DI

SCON

TINU

ED

PROD

UCT

Page 8: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

- 8 -

60Hz COPELAND PERFORMANCE CAPACITYApplication Data Calculated at 65 °F. Return Gas, 0 °F. Liquid Subcooling

R404A / R507 - LOW TEMPERATURE - CAPACITY (BTU/HR)Unit Shipped with polyolester oil

* COMPRESSOR MODEL SHOWN IS FOR 208-230/3/60, EXACT MODEL MAY VARY WITH OTHER VOLTAGES.

COND. UNITMODEL *

SAT. SUCTIONTEMP. °F 80°F Amb. 90°F Amb. 95°F Amb. 100°F Amb. 105°F Amb.

T030L6Compressor Model

LAHA-032E

0-10-20-30-40

268002130016100117007800

245001910014200102006700

23200181001330095006199

21900170001230088005600

20800158001140080005000

T035L6Compressor Model

2DF3-030E

0-10-20-30-40

3540028530223701698012920

3188025880200401498010990

3040024270188801399010060

283802306017740130109140

266702166016600120408310

T040L6Compressor Model

2DL3-040E

0-10-20-30-40

4098033180262202024015360

3753030010237001794013330

3540028440223601680012320

3323027100210401568011250

3140025550197301455010340

T060L6Compressor Model

2DA3-060E

0-10-20-30-40

4756038520307202371018050

4286034900276702110015720

4105033100261601981014570

3852031570246701853013510

3677029790231801726012380

T061L6Compressor Model

3DA3A060E

0-10-20-30-40

5477045090355102767021470

5070040810324602488018780

4798039170308502350017520

4515037230292502214016260

4279035300276702079015120

T075L6Compressor Model

3DB3A075E

0-10-20-30-40

6478053020420603261025200

5913048070383102939022210

5634046170364602781020740

5303043920346302625019290

5026041690328102470017960

T090L6Compressor Model

3DF3A090E

0-10-20-30-40

8108066490520604049031300

7492060240477503661027820

7163057480455003469026100

6728054780432603279024400

6405052120410403091022720

T100L6Compressor Model

3DS3A100E

0-10-20-30-40

9143074810595904660035970

8448068970546204204031710

8079065510520103979029680

7655062400494203756027800

7347059750468603536025800

T150L6Compressor Model

4DL3-150E

0-10-20-30-40

120540100649805806310048460

11087090610728105691043110

10569086250696105387040480

9885081930660105084037870

9375077670624404785035290

T200L6Compressor Model

4DT3-220E

0-10-20-30-40

143230119560973307610058040

130420108000876606787050340

122310103120828806380046700

11545097410781305977043170

10861091730734305577039780

T250L6Compressor Model

6DL3-270E

0-10-20-30-40

1803101475001171009054068120

1652701351601068908247061190

1577401289901017807843057720

150220122820966707439054250

142700116650915607036050790

T300L6Compressor Model

6DT3-300E

0-10-20-30-40

20643016840013531010531081210

1875201527401221409394070620

1781501461601156308832065480

1670201384301091808275060870

1578301307601028007725055830

DISC

ONTI

NUED

PROD

UCT

Page 9: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

60Hz CARLYLE PERFORMANCE CAPACITYApplication Data Calculated at 65 °F. Return Gas, 0 °F. Liquid Subcooling

R404A / R507 - LOW TEMPERATURE - CAPACITY (BTU/HR)Unit Shipped with polyolester oil

- 9 -

COND. UNITMODEL

SAT. SUCTIONTEMP. °F

80°F Amb. 90°F Amb. 95°F Amb. 100°F Amb. 105°F Amb.

TC030L6Compressor Model

O6DR013

-5-10-20-30-40

290792265017068122208559

257942002314887104317093

24290187351380995486366

22773176241274086725699

21547163341168078044978

TC035L6Compressor Model

O6DR316

-5-10-20-30-40

3428030761236511779413019

3105027574212351558611052

2972026311199701449510077

279102485218715134119142

265802340517473123418244

TC040L6Compressor Model

06DR718

-5-10-20-30-40

4484036007280392159216205

4108732424254911920014095

3921530883241451802213054

3754429368228131686012024

3618427851214941570311001

TC060L6Compressor Model

06DR820

-5-10-20-30-40

5123341197320262410917680

4732837054287282126915227

4485835258270981986913995

4277533574254831848212767

4107531707238841710811736

TC061L6Compressor Model

06DR724

-5-10-20-30-40

5001344586342012566418585

4485239840306212232315548

4254537990287282067414112

4025035823268511904112681

3831833680249931742411417

TC075L6Compressor Model

06DR228

-5-10-20-30-40

6105054847431803285724162

5591149614388862898420533

5291947630367662707618739

5040545268346632518617096

4837342931325932331715532

TC090L6Compressor Model

06DR337

-5-10-20-30-40

7910074304586674574235407

7340066896529354057730932

7002063237498723803129022

6519060212468403550926904

6153056582438263301424796

TC150L6Compressor Model

06ER150

-5-10-20-30-40

119400106252812046073546160

10900096636728785210235875

10497092205687744784531498

9955088382647124362626213

9489084027606933943821582

TC200L6Compressor Model

06ER165

-5-10-20-30-40

1456591295391016107668957046

129477115425894576626847808

121956109184834506112043376

114483102232774925602439186

10792895334715815095934886

TC250L6Compressor Model

06ER175

-5-10-20-30-40

1701641516521171678723462771

1531321358561042667585752526

146578128591979017025347553

137708122387915966471542801

130054115231853505921438141

TC300L6Compressor Model

06ER099

-5-10-20-30-40

20182918037614350111170284816

1804031620061282499728571542

1707291542601202189017565193

1610621452241122648313659192

1530351362541042907614053265

DISC

ONTI

NUED

PROD

UCT

Page 10: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

- 10 -

60Hz COPELAND PERFORMANCE CAPACITYApplication Data Calculated at 65 °F. Return Gas, 0 °F. Liquid Subcooling

R22 - LOW TEMPERATURE - CAPACITY (BTU/HR)Unit Shipped with mineral oil - All Models (except T030L2) Utilize Copeland’s Demand CoolingTM

* COMPRESSOR MODEL SHOWN IS FOR 208-230/3/60, EXACT MODEL MAY VARY WITH OTHER VOLTAGES.

COND. UNITMODEL *

SAT. SUCTIONTEMP. °F 80°F Amb. 90°F Amb. 95°F Amb. 100°F Amb. 105°F Amb.

T030L2Compressor Model

LAHA-0310

0-10-20-30-40

250901944014440102807130

23000176901299090706100

21930168001225084605580

20890159201153078505060

19840150501080072404540

T035L2Compressor Model

2DF3-0300

0-10-20-30-40

3254025280189901395010480

296202292016980121708770

281902170015960112807920

267602051014960103907070

25330193201395095006220

T040L2Compressor Model

2DL3-0400

0-10-20-30-40

3740029600226601680012150

3439026910202901471010340

329402554019070136509430

314602421017890126008520

299502288016690115507610

T060L2Compressor Model

2DA3-0600

0-10-20-30-40

4408034870267101972014050

4072031810239701733012050

3897030230225701613011050

3728028690211901494010050

355902716019840137409050

T061L2Compressor Model

3DA3A0600

0-10-20-30-40

5021039700303102272017090

4620036360275002014014590

4429034560259301871013300

4239032920244701738011950

4050031270230201605010720

T075L2Compressor Model

3DB3A0750

0-10-20-30-40

6132049230385802965022680

5656045120348302612019300

5431042990329102436017620

5198040910310202260015940

4966038870291602085014250

T090L2Compressor Model

3DF3A0900

0-10-20-30-40

7600060620472903573026140

7044055690426803158022620

6782053170403502954020860

6521050690380602749019110

6260048250358002544017350

T100L2Compressor Model

3DS3A1000

0-10-20-30-40

8422067170522003932028810

7836061820472603491025000

7539059080447803272023100

7249056400423303052021210

6959053750399202835019310

T150L2Compressor Model

4DL3-1500

0-10-20-30-40

11018088400688005230038900

10190081100622004610033100

9800077180586004280030100

9430073500553003970027200

9040069900520003560024200

T200L2Compressor Model

4DT3-2200

0-10-20-30-40

132000104870815006170046600

12268096990744705519040500

11825092960705805194037470

11333088990671204878034400

10887085000635704553031340

T250L2Compressor Model

6DL3-2700

0-10-20-30-40

1664801317101025207736054930

155910122430942807089048940

150620117790901606765045940

145330113150860406441042950

140050108510819306118039950

T300L2Compressor Model

6DT3-3000

0-10-20-30-40

1973001576501220009246069170

1825001446001113008278060340

1755601383001056507777055940

1683001320801040007310051500

160200126000949606828047060

DISC

ONTI

NUED

PROD

UCT

Page 11: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

60Hz COPELAND PERFORMANCE CAPACITYApplication Data Calculated at 65 °F. Return Gas, 0 °F. Liquid Subcooling

R502 - LOW TEMPERATURE - CAPACITY (BTU/HR)Unit Shipped with mineral oil

- 11 -* COMPRESSOR MODEL SHOWN IS FOR 208-230/3/60, EXACT MODEL MAY VARY WITH OTHER VOLTAGES.

COND. UNITMODEL *

SAT. SUCTIONTEMP. °F

80°F Amb. 90°F Amb. 95°F Amb. 100°F Amb. 105°F Amb.

T030L5Compressor Model

LAH1-0310

0-10-20-30-40

268502122016210122709680

241301910014420106408100

22860180501349098307320

21590170001259090306530

20380159001170082305750

T035L5Compressor Model

2DF3-0300

0-10-20-30-40

3521028350220801668012390

3210025680197501465010610

305702436018590136409720

290402298017440126408840

275202165016290116507960

T040L5Compressor Model

2DL3-0400

0-10-20-30-40

3961032280256301987015330

3616029580233601789013510

3453028250222201691012610

3292026850211001594011700

3131025500199901498010800

T060L5Compressor Model

2DA3-0600

0-10-20-30-40

4629037710299302336018300

4275034780274302117016310

4100033320261902009015310

3927031800249601902014320

3755030340237301796012240

T061L5Compressor Model

3DA3A0600

0-10-20-30-40

5420044260354002743020100

5005040620319902456018420

4790038720303502303017100

4587036880287102157015780

4372035040271002017014470

T075L5Compressor Model

3DB3A0750

0-10-20-30-40

6443052850422903309025750

6000049850387803001022640

5781046930370402846021560

5565044980353202693020170

5335043040336102540018790

T090L5Compressor Model

3DF3A0900

0-10-20-30-40

7869064610514904032031200

7246059170469203624027540

6954056620446603422025720

6663054000424003222023910

6374051440401403023022100

T100L5Compressor Model

3DS3A1000

0-10-20-30-40

8941072960581604546035220

8312067450533504114031430

8001064720508703901029560

7692061940484603690027690

7385059210460603479025830

T150L5Compressor Model

4DL3-1500

0-10-20-30-40

11680095260756005920046000

10887087670692005323040690

10484084100658405029038000

10037080450626004746035370

9635076980594804454032700

T200L5Compressor Model

4DT3-2200

0-10-20-30-40

138120114090930307450059510

128000105800851406770053280

123280101540814606399050170

11870096990777306060047070

11394092750739505724043980

T250L5Compressor Model

6DL3-2700

0-10-20-30-40

1835601501201203109416070110

1708401392101111708652063700

1644901337601066008269060490

1581301283001020307887057290

151780122850974707504054080

T300L5Compressor Model

6DT3-3000

0-10-20-30-40

20627016854013446010413079890

1890901537001218309344070940

1797401463201148708804066500

1711701381901085808283062080

1624901308101023607754057660

DISC

ONTI

NUED

PROD

UCT

Page 12: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

60Hz CARLYLE PERFORMANCE CAPACITYApplication Data Calculated at 65 °F. Return Gas, 0 °F. Liquid Subcooling

R502 - LOW TEMPERATURE - CAPACITY (BTU/HR)Unit Shipped with mineral oil

- 12 -

COND. UNITMODEL

SAT. SUCTIONTEMP. °F

80°F Amb. 90°F Amb. 95°F Amb. 100°F Amb. 105°F Amb.

TC035L5Compressor Model

06DR316

0-10-20-30-40

3643029520230801760

13000

3339026700206501551011310

3181025250194401447010450

302202389018240134309580

28660253017040123608720

TC040L5Compressor Model

06DR718

0-10-20-30-40

4287034720276002144016760

3973032050252501943014920

3796030670240501837013950

3641029330228901735013020

3480028000217401634012090

TC060L5Compressor Model

06DR820

0-10-20-30-40

4843039230308602380018360

4465035930281502144016340

4266034340267002026015310

4079032650253301909014480

3894031040239701793013230

TC061L5Compressor Model

06DR724

0-10-20-30-40

5529044840355602744020850

5139041240320302420017800

4934039360303402251016240

4742037550286502097014680

4537035750269601932013120

TC075L5Compressor Model

06DR228

0-10-20-30-40

6594054700446103498025040

6098049370391603003021630

5838046380363102772019930

5592043620335802530018230

5331040900309402290016540

TC090L5Compressor Model

06DR337

0-10-20-30-40

8753071590570004462034820

8078065560520904045031270

7740062660495703831029460

7372059810471503632027710

7034057010448003427026010

TC100L5Compressor Model

06DR337

0-10-20-30-40

9170074150587604589035650

8393068150537904156032010

8043065080511703936030210

7695062050486503725028410

7350059200462403521026630

TC150L5Compressor Model

06ER150

0-10-20-30-40

11797095800753905836044960

10896087660687905247039590

10439083840653404944036910

9942079890620204660034240

9486076160588104369031570

TC200L5Compressor Model

06ER165

0-10-20-30-40

145740118080935507195054560

134400107950839506388047490

128180102690793905973044030

12252097100749705583040660

11676092120704105182037180

TC250L5Compressor Model

06ER175

0-10-20-30-40

1779201432901115308551066720

1597201292601011407700058780

151260122560959607272054840

142640115860908006859050910

133390109240857206440046990

TC300L5Compressor Model

06ER099

0-10-20-30-40

21724017794014267011111085670

2002901630301287809942075240

1911301556201221809350070050

1828301480801156208773064870

1742801406601090508190059680

DISC

ONTI

NUED

PROD

UCT

Page 13: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

T - LINE DIMENSIONAL DATA

- 13 -

* Indoor units only† Center leg not required for all models

CONDENSING UNIT MODEL NUMBERS

DIMENSIONSA B C D E F G † H

T(C)029M1, T030M8, TC030M2, T030L2, T030L5, T(C)030L6 35 1/2" 38 1/4" 35 1/4" 46" 9 13/16" 2 1/8" N/A 3 1/2"

T035L2, T(C)035L5, T(C)035L6, T040L2, T(C)040L5, T(C)040L6

35 1/2" 48 1/4" 35 1/4" 46" 9 13/16" 2 1/8" N/A 3 1/2"

T030M1, T050M8, TC050M2, TC051M1 T051M8, TC052M1, T(C)060M1, T060L2, T(C)060L5, T(C)060L6, T061L2, T(C)061L5, T(C)061L6, T062M1, T075L2, T(C)075L5, T(C)075L6,

35 1/2" 58 1/4" 35 1/4" 46" 9 13/16" 2 1/8" N/A 3 1/2"

T063M1, TC065M1, T(C)075M1, T075M8, TC075M2, T076M8, TC076M2, T090M1, T090L2, T(C)090L5, T(C)090L6, T(C)100M1

39" 68 1/4" 42 1/4" 55" 9 13/16" 2 1/8" 34 1/8" 3 1/2"

T100M8, T(C)100M2, T100L2, T(C)100L5, T100L6, T101M1, T150M1, T150M8, TC150M2, T150L2, T(C)150L5, T(C)150L6, T200L2, T(C)200L5, T(C)200L6

49" 68 1/4" 42 1/4" 57" 9 13/16" 2 1/8" 34 1/8" 3 1/2"

T200M8, TC200M2, T250M8, TC250M2, T250L2, T(C)250L5, T(C)250L6, T300M8, T300L2, T(C)300L5, T(C)300L6

49" 98 1/4" 46 1/4" 66 1/4" 9 13/16" 2 1/8" 49 1/8" 3 1/2"

T250M8, TC250M2, T250L2, T(C)250L5, T(C)250L6, T300M8, TC300M2, T300L2, T(C)300L5, T(C)300L6

**53" 98 1/4" 46 1/4" 66 1/4" 13 13/16" 4" 49 1/8" 6"

** For outdoor units only, dimension 'A' is increased due to larger receiver

DISC

ONTI

NUED

PROD

UCT

Page 14: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

- 14 -

T - LINE SPECIFICATIONS

* COMPRESSOR MODEL SHOWN IS FOR 208-230/3/60, EXACT MODEL MAY VARY WITH OTHER VOLTAGES.

MODEL COMPRESSOR *CONNECTIONS

RECEIVER CAPACITY 90%FULL (LBS) SHIPPING

Wt. (LBS)LIQUID (OD) SUCTION (OD) INDOOR OUTDOOR

T029M1 - HS2, HT3, HT4 LAHB-031E 1/2 1 1/8 29 29 540

T030M1 - HS2, HT3, HT4, HT5 2DF3-030E 1/2 1 1/8 44 70 788

T060M1 - HT3, HT4, HT5 2DA3-060E 5/8 1 3/8 44 70 810

T062M1 - HT3, HT4, HT5 3DA3-060E 5/8 1 3/8 44 70 880

T063M1 - HT3, HT4, HT5 3DA3-060E 5/8 1 3/8 70 70 1090

T075M1 - HT3, HT4, HT5 3DB3-075E 5/8 1 3/8 70 70 1090

T090M1 - HT3, HT4, HT5 3DF3-090E 5/8 1 3/8 70 82 1140

T100M1 - HT3, HT4, HT5 3DS3-100E 5/8 1 3/8 82 119 1186

T101M1 - HT3, HT4, HT5 4DA3-100E 7/8 1 5/8 82 119 1210

T150M1 - HT3 ,HT4, HT5 4DH3-150E 7/8 1 5/8 82 119 1335

TC029M1 - HS2, HT3, HT4, HT5 06DR013 1/2 1 1/8 29 29 435

TC051M1 - HT3, HT4, HT5 06DR316 1/2 1 1/8 44 71 650

TC052M1 - HT3, HT4, HT5 06DR718 1/2 1 1/8 44 71 765

TC060M1 - HT3, HT4, HT5 06DR820 5/8 1 3/8 44 70 765

TC065M1 - HT3, HT4, HT5 06DR724 5/8 1 3/8 70 70 780

TC075M1 - HT3, HT4, HT5 06DR228 5/8 1 3/8 70 70 840

TC100M1 - HT3, HT4, HT5 06DR337 7/8 1 5/8 82 119 1240

MODEL COMPRESSOR *

CONNECTIONS RECEIVER CAPACITY 90%FULL (LBS)

SHIPPINGWt. (LBS)LIQUID

(OD)SUCTION

(OD)

INDOOR OUTDOOR

R22 R404A/R507 R22 R404A/

R507T030M8 - HS2, HT3, HT4, HT5 ERFA-031E 1/2 1 1/8 29 25 29 25 450

T050M8 - HS2, HT3, HT4, HT5 2DC3-050E 5/8 1 3/8 44 38 70 61 730

T051M8 - HT3 ,HT4, HT5 2DD3-050E 5/8 1 3/8 44 38 70 61 730

T075M8 - HT3, HT4, HT5 2DL3-075E 5/8 1 3/8 44 38 70 61 890

T076M8 - HT3 ,HT4, HT5 3DA3-075E 5/8 1 3/8 70 38 70 61 1000

T100M8 - HT3, HT4, HT5 3DB3-100E 5/8 1 3/8 70 72 95 72 1000

T150M8 - HT3, HT4, HT5 3DS3-150E 7/8 1 5/8 82 72 119 104 1075

T200M8 - HT3, HT4, HT5 4DA3-200E 7/8 1 5/8 119 72 119 104 1417

T250M8 - HT3, HT4, HT5 4DH3-250E 1 1/8 2 1/8 119 82 181 125 1470

T300M8 - HT3, HT4, HT5 4DJ3-300E 1 1/8 2 1/8 119 104 181 125 1475

DISC

ONTI

NUED

PROD

UCT

Page 15: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

- 15 -

T - LINE SPECIFICATIONS

* COMPRESSOR MODEL SHOWN IS FOR 208-230/3/60, EXACT MODEL MAY VARY WITH OTHER VOLTAGES.

MODEL COMPRESSOR *CONNECTIONS

RECEIVER CAPACITY

90% FULL (LBS)SHIPPING

Wt. (LBS)LIQUID (OD) SUCTION (OD) INDOOR OUTDOOR

T030L2 - HS2,HT3,HT4,HT5 LAHA-0310 1/2 1 1/8 29 29 540

T035L2 - HS2.HT3,HT4,HT5 2DF3-0300 1/2 1 1/8 35 35 685

T040L2 - HT3,HT4,HT5 2DL3-0400 1/2 1 1/8 35 35 685

T060L2 - HT3,HT4,HT5 2DA3-0600 5/8 1 3/8 44 70 788

T061L2 - HT3,HT4,HT5 3DA3A0600 5/8 1 3/8 44 70 878

T075L2 - HT3,HT4,HT5 3DB3A0750 5/8 1 3/8 70 70 880

T090L2 - HT3,HT4,HT5 3DF3A0900 5/8 1 3/8 70 70 1090

T100L2 - HT3,HT4,HT5 3DS3A1000 5/8 1 3/8 70 95 1125

T150L2 - HT3,HT4,HT5 4DL3-1500 7/8 1 5/8 82 119 1260

T200L2 - HT3,HT4,HT5 4DT3-2200 1 1/8 2 1/8 119 119 1330

T250L2 - HT3,HT4,HT5 6DL3-2700 1 1/8 2 1/8 119 181 1473

T300L2 - HT3,HT4,HT5 6DT3-3000 1 1/8 2 1/8 119 181 1805

T030L5 - HS2,HT3,HT4,HT5 LAHA-0310 1/2 1 1/8 29 29 540

T035L5 - HS2,HT3,HT4,HT5 2DF3-0300 1/2 1 1/8 35 35 685

T040L5 - HT3,HT4,HT5 2DL3-0400 1/2 1 1/8 35 35 685

T060L5 - HT3,HT4,HT5 2DA3-0600 5/8 1 3/8 44 44 760

T061L5 - HT3,HT4,HT5 3DA3A0600 5/8 1 3/8 44 44 850

T075L5 - HT3,HT4,HT5 3DB3A0750 5/8 1 3/8 44 71 880

T090L5 - HT3,HT4,HT5 3DF3A0900 5/8 1 3/8 71 71 1090

T100L5 - HT3,HT4,HT5 3DS3A1000 5/8 1 3/8 83 83 1125

T150L5 - HT3,HT4,HT5 4DL3-1500 7/8 1 5/8 83 120 1260

T200L5 - HT3,HT4,HT5 4DT3-2200 1 1/8 2 1/8 83 120 1330

T250L5 - HT3,HT4,HT5 6DL3-2700 1 1/8 2 1/8 120 145 1443

T300L5 - HT3,HT4,HT5 6DT3-3000 1 1/8 2 1/8 120 145 1775

DISC

ONTI

NUED

PROD

UCT

Page 16: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

- 16 -

T - LINE SPECIFICATIONS

* COMPRESSOR MODEL SHOWN IS FOR 208-230/3/60, EXACT MODEL MAY VARY WITH OTHER VOLTAGES.

MODEL COMPRESSOR *CONNECTIONS

RECEIVER CAPACITY

90% FULL (LBS)SHIPPING

Wt. (LBS)LIQUID (OD) SUCTION (OD) INDOOR OUTDOOR

T030L6 - HS2,HT3,HT4 LAHA-032E 1/2 1 1/8 25 25 540

T035L6 - HT3,HT4,HT5 2DF3-030E 1/2 1 1/8 30 30 685

T040L6 - HT3,HT4,HT5 2DL3-040E 1/2 1 1/8 30 30 685

T060L6 - HT3,HT4,HT5 2DA3-060E 5/8 1 3/8 38 38 760

T061L6 - HT3,HT4,HT5 3DA3A060E 5/8 1 3/8 38 38 850

T075L6 - HT3,HT4,HT5 3DB3A075E 5/8 1 3/8 38 61 880

T090L6 - HT3,HT4,HT5 3DF3A090E 5/8 1 3/8 61 61 1090

T100L6 - HT3,HT4,HT5 3DS3A100E 5/8 1 3/8 72 72 1125

T150L6 - HT3,HT4,HT5 4DL3-150E 7/8 1 5/8 72 104 1260

T200L6 - HT3,HT4,HT5 4DT3-220E 1 1/8 2 1/8 72 104 1330

T250L6 - HT3,HT4,HT5 6DL3-270E 1 1/8 2 1/8 104 125 1443

T300L6 - HT3,HT4,HT5 6DT3-300E 1 1/8 2 1/8 104 125 1775

TC030L6 - HS2,HT3,HT4,HT5 06DR013 1/2 1 1/8 25 25 400

TC035L6 - HT3,HT4,HT5 06DR316 1/2 1 1/8 30 30 425

TC040L6 - HT3,HT4,HT5 06DR718 1/2 1 1/8 30 30 450

TC060L6 - HT3,HT4,HT5 06DR820 5/8 1 3/8 38 38 655

TC061L6 - HT3,HT4,HT5 06DR724 5/8 1 3/8 38 38 690

TC075L6 - HT3,HT4,HT5 06DR228 5/8 1 3/8 38 61 750

TC090L6 - HT3,HT4,HT5 06DR337 5/8 1 3/8 61 61 800

TC150L6 - HT3,HT4,HT5 06ER150 5/8 1 5/8 72 104 1225

TC200L6 - HT3,HT4,HT5 06ER165 1 1/8 2 1/8 72 104 1500

TC250L6 - HT3,HT4,HT5 06ER175 1 1/8 2 1/8 104 125 1500

TC300L6 - HT3,HT4,HT5 06ER099 1 1/8 2 1/8 104 125 1500

DISC

ONTI

NUED

PROD

UCT

Page 17: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

T - LINE ELECTRICAL SPECIFICATIONS (COPELAND)

- 17 -

M.O.P. = Maximum Overcurrent ProtectionM.C.A. = Minimum Circuit Ampacity

MODEL POWER SUPPLYCOMPRESSOR CONDENSER FANS TOTAL

AMPSM.C.A. M.O.P.

RLA LRA QTY Hp @ FLA @

T029M1 - HS2 208-230/1/60 16.6 93 1 1/3 3.2 19.8 24.0 40

T029M1 - HT3 208-230/3/60 8.5 82 1 1/3 3.2 11.7 13.8 20

T029M1 - HT4 460/3/60 6.0 56 1 1/3 1.6 7.6 9.1 15

T030M1 - HS2 208-230/1/60 25.8 125 2 1/2 4.6 35.0 41.5 60

T030M1 - HT3 208-230/3/60 16.8 102 2 1/2 4.6 26.0 30.2 40

T030M1 - HT4 460/3/60 8.1 52 2 1/2 2.3 12.7 14.7 20

T030M1 - HT5 575/3/60 6.7 41 2 1/2 2.3 11.3 13.0 20

T060M1 - HT3 208-230/3/60 28.8 161 2 1/2 4.6 39.0 45.2 70

T060M1 - HT4 460/3/60 10.2 60 2 1/2 2.3 14.8 17.3 25

T060M1 - HT5 575/3/60 9.1 49 2 1/2 2.3 13.7 16.0 25

T062M1 - HT3 208-230/3/60 30.3 150 2 1/2 4.6 39.5 47.1 70

T062M1 - HT4 460/3/60 13.7 77 2 1/2 2.3 18.3 21.7 30

T062M1 - HT5 575/3/60 10.5 62 2 1/2 2.3 15.1 17.9 25

T063M1 - HT3 208-230/3/60 30.3 150 2 3/4 4.2 38.7 46.3 70

T063M1 - HT4 460/3/60 13.7 77 2 3/4 2.1 17.9 21.3 30

T063M1 - HT5 575/3/60 10.5 62 2 3/4 2.1 14.7 17.3 25

T075M1 - HT3 208-230/3/60 31.5 161 2 3/4 4.2 39.9 47.8 80

T075M1 - HT4 460/3/60 16.1 83 2 3/4 2.1 20.3 24.3 40

T075M1 - HT5 575/3/60 11.0 67 2 3/4 2.1 15.2 18.0 30

T090M1 - HT3 208-230/3/60 39.0 215 2 3/4 4.2 47.4 57.2 90

T090M1 - HT4 460/3/60 16.9 106 2 3/4 2.1 21.1 25.3 40

T090M1 - HT5 575/3/60 16.5 84 2 3/4 2.1 20.7 24.8 40

T100M1 - HT3 208-230/3/60 42.0 215 2 3/4 4.2 50.4 60.9 100

T100M1 - HT4 460/3/60 18.6 106 2 3/4 2.1 22.8 27.5 40

T100M1 - HT5 575/3/60 16.8 84 2 3/4 2.1 21.0 25.2 40

T101M1 - HT3 208-230/3/60 42.0 240 2 3/4 4.2 50.8 60.9 100

T101M1 - HT4 460/3/60 21.0 120 2 3/4 2.1 25.2 30.5 50

T101M1 - HT5 575/3/60 17.5 106 2 3/4 2.1 21.7 26.1 40

T150M1 - HT3 208-230/3/60 58.0 278 2 3/4 4.2 66.4 80.9 125

T150M1 - HT4 460/3/60 29.0 139 2 3/4 2.1 33.2 40.5 70

T150M1 - HT5 575/3/60 24.3 113 2 3/4 2.1 28.5 34.6 50

DISC

ONTI

NUED

PROD

UCT

Page 18: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

- 18 -

T - LINE ELECTRICAL SPECIFICATIONS (CARLYLE)

M.O.P. = Maximum Overcurrent ProtectionM.C.A. = Minimum Circuit Ampacity

MODEL POWER SUPPLYCOMPRESSOR CONDENSER FANS TOTAL

AMPSM.C.A. M.O.P.

RLA LRA QTY Hp @ FLA @

TC029M1 - HS2 208-230/1/60 23.4 100 1 1/3 3.2 26.5 32.3 50

TC029M1 - HT3 208-230/3/60 12.4 71 1 1/3 3.2 15.6 18.7 30

TC029M1 - HT4 460/3/60 6.2 35 1 1/3 1.6 7.8 9.4 15

TC029M1 - HT5 575/3/60 5.0 28 1 1/3 1.6 8.2 9.5 15

TC051M1 - HT3 208-230/3/60 19.3 100 2 1/2 4.6 28.5 33.3 50

TC051M1 - HT4 460/3/60 9.7 50 2 1/2 2.3 14.3 16.7 25

TC051M1 - HT5 575/3/60 7.7 40 2 1/2 2.3 12.3 14.2 20

TC052M1 - HT3 208-230/3/60 19.3 100 2 1/2 4.6 28.5 33.3 50

TC052M1 - HT4 460/3/60 9.6 50 2 1/2 2.3 14.2 16.6 25

TC052M1 - HT5 575/3/60 7.7 40 2 1/2 2.3 12.3 14.2 20

TC060M1 - HT3 208-230/3/60 31.4 160 2 1/2 4.6 40.6 48.4 80

TC060M1 - HT4 460/3/60 15.7 80 2 1/2 2.3 20.3 24.2 40

TC060M1 - HT5 575/3/60 12.6 64 2 1/2 2.3 17.2 20.3 30

TC065M1 - HT3 208-230/3/60 31.4 160 2 1/2 4.6 40.6 48.4 80

TC065M1 - HT4 460/3/60 15.7 80 2 1/2 3.2 22.1 26.0 40

TC065M1 - HT5 575/3/60 12.6 64 2 1/2 3.2 19.0 22.2 30

TC075M1 - HT3 208-230/3/60 39.6 198 2 3/4 4.2 48.0 57.9 100

TC075M1 - HT4 460/3/60 19.8 99 2 3/4 2.1 24.0 29.0 50

TC075M1 - HT5 575/3/60 15.9 79 2 3/4 2.1 20.1 24.1 40

TC100M1 - HT3 208-230/3/60 44.2 228 2 3/4 4.2 52.6 63.7 100

TC100M1 - HT4 460/3/60 22.1 114 2 3/4 2.1 26.3 31.8 50

TC100M1 - HT5 575/3/60 17.9 91 2 3/4 2.1 22.1 26.6 40

DISC

ONTI

NUED

PROD

UCT

Page 19: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

T - LINE ELECTRICAL SPECIFICATIONS (CARLYLE)

M.O.P. = Maximum Overcurrent ProtectionM.C.A. = Minimum Circuit Ampacity

- 19 -

MODEL POWER SUPPLYCOMPRESSOR CONDENSER FANS TOTAL

AMPSM.C.A. M.O.P.

RLA LRA QTY Hp @ FLA @

TC030M2 - HS2 208-230/1/60 20.0 110 1 1/3 3.2 23.2 28.2 40

TC030M2 - HT3 208-230/3/60 12.4 71 1 1/3 3.2 15.6 18.7 30

TC030M2 - HT4 460/3/60 6.2 35.5 1 1/3 1.6 7.8 9.4 15

TC030M2 - HT5 575/3/60 5.0 28.4 1 1/3 1.6 6.6 7.9 15

TC031M2 - HS2 208-230/1/60 20.0 110 1 1/2 4.0 24.6 29.6 50

TC031M2 - HT3 208-230/3/60 12.4 71 1 1/2 4.6 17.0 20.1 30

TC031M2 - HT4 460/3/60 6.2 36 1 1/2 2.3 8.5 10.1 15

TC031M2 - HT5 575/3/60 5.0 28 1 1/2 2.3 7.3 8.6 15

TC050M2 - HT3 208-230/3/60 19.3 100 2 1/2 4.6 28.5 33.3 50

TC050M2 - HT4 460/3/60 9.6 50 2 1/2 2.3 14.2 16.6 25

TC050M2 - HT5 575/3/60 7.7 40 2 1/2 2.3 12.3 14.2 20

TC075M2 - HT3 208-230/3/60 31.4 160 2 3/4 4.2 39.8 47.7 80

TC075M2 - HT4 460/3/60 15.7 80 2 3/4 2.1 19.9 23.8 40

TC075M2 - HT5 575/3/60 12.6 64 2 3/4 2.1 16.8 20.0 30

TC076M2 - HT3 208-230/3/60 39.6 198 2 3/4 4.2 48.0 57.9 100

TC076M2 - HT4 460/3/60 19.8 99 2 3/4 2.1 24.0 29.0 50

TC076M2 - HT5 575/3/60 15.9 79 2 3/4 2.1 20.1 24.1 40

TC100M2 - HT3 208-230/3/60 44.3 228 2 3/4 4.2 57.2 63.8 100

TC100M2 - HT4 460/3/60 22.1 114 2 3/4 2.1 26.3 31.8 50

TC100M2 - HT5 575/3/60 17.9 91 2 3/4 2.1 22.1 26.6 40

TC150M2 - HT3 208-230/3/60 63.6 266 2 3/4 4.2 72.3 88.3 150

TC150M2 - HT4 460/3/60 28.6 120 2 3/4 2.1 32.8 40.0 60

TC150M2 - HT5 575/3/60 22.9 96 2 3/4 2.1 29.2 34.9 50

TC200M2 - HT3 208-230/3/60 87.0 345 3 3/4 4.2 99.6 121.4 200

TC200M2 - HT4 460/3/60 44.0 173 3 3/4 2.1 50.3 61.3 100

TC200M2 - HT5 575/3/60 36.0 120 3 3/4 2.1 42.3 51.3 80

TC250M2 - HT3 208-230/3/60 112.0 446 3 3/4 4.2 124.6 152.6 250

TC250M2 - HT4 460/3/60 56.0 223 3 3/4 2.1 62.3 76.3 125

TC250M2 - HT5 575/3/60 46.0 164 3 3/4 2.1 52.3 63.8 100

DISC

ONTI

NUED

PROD

UCT

Page 20: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

T - LINE ELECTRICAL SPECIFICATIONS (COPELAND)

- 20 -

M.O.P. = Maximum Overcurrent ProtectionM.C.A. = Minimum Circuit Ampacity

MODEL POWER SUPPLYCOMPRESSOR CONDENSER FANS TOTAL

AMPS M.C.A. M.O.P.RLA LRA QTY Hp @ FLA @

T030M8 - HS2 208-230/1/60 17.0 86 1 1/3 3.2 20.2 24.5 40

T030M8 - HT3 208-230/3/60 12.4 82 1 1/3 3.2 15.6 18.7 30

T030M8 - HT4 460/3/60 5.8 41 1 1/3 1.6 7.4 8.9 15

T030M8 - HT5 575/3/60 5.2 30 1 1/3 1.6 6.8 8.1 15

T050M8 - HT3 208-230/3/60 22.3 120 2 1/2 4.6 31.5 37.5 60

T050M8 - HT4 460/3/60 10.4 60 2 1/2 2.3 15.0 17.6 25

T050M8 - HT5 575/3/60 7.7 49 2 1/2 2.3 12.3 14.2 20

T051M8 - HT3 208-230/3/60 22.3 120 2 1/2 4.6 31.5 37.1 60

T051M8 - HT4 460/3/60 10.5 60 2 1/2 2.3 15.1 17.7 25

T051M8 - HT5 575/3/60 7.9 49 2 1/2 2.3 12.5 14.5 20

T075M8 - HT3 208-230/3/60 31.6 169 2 3/4 4.2 40.0 47.9 80

T075M8 - HT4 460/3/60 13.8 85 2 3/4 2.1 18.0 21.5 35

T075M8 - HT5 575/3/60 13.2 67 2 3/4 2.1 17.4 20.7 30

T076M8 - HT3 208-230/3/60 41.0 215 2 3/4 4.2 49.4 59.7 100

T076M8 - HT4 460/3/60 20.0 106 2 3/4 2.1 24.2 29.2 50

T076M8 - HT5 575/3/60 16.5 84 2 3/4 2.1 20.7 24.8 40

T100M8 - HT3 208-230/3/60 43.6 215 2 3/4 4.2 52.0 62.9 100

T100M8 - HT4 460/3/60 20.0 106 2 3/4 2.1 24.2 29.4 50

T100M8 - HT5 575/3/60 16.5 84 2 3/4 2.1 20.7 24.8 40

T150M8 - HT3 208-230/3/60 59.6 275 2 3/4 4.2 68.0 82.9 125

T150M8 - HT4 460/3/60 29.0 138 2 3/4 2.1 33.2 40.5 70

T150M8 - HT5 575/3/60 23.6 110 2 3/4 2.1 27.8 33.7 50

T200M8 - HT3 208-230/3/60 66.0 308 3 3/4 4.2 78.6 95.1 150

T200M8 - HT4 460/3/60 33.0 154 3 3/4 2.1 39.3 47.6 80

T200M8 - HT5 575/3/60 24.7 135 3 3/4 2.1 31.0 37.2 60

T250M8 - HT3 208-230/3/60 82.2 428 3 3/4 4.2 94.8 115.4 200

T250M8 - HT4 460/3/60 41.1 214 3 3/4 2.1 47.4 57.7 100

T250M8 - HT5 575/3/60 34.4 172 3 3/4 2.1 40.7 49.3 80

T300M8 - HT3 208-230/3/60 94.0 470 3 3/4 4.2 106.6 130.1 225

T300M8 - HT4 460/3/60 47.0 235 3 3/4 2.1 53.3 65.1 110

T300M8 - HT5 575/3/60 39.3 200 3 3/4 2.1 45.6 55.4 90

DISC

ONTI

NUED

PROD

UCT

Page 21: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

- 21 -

T - LINE ELECTRICAL SPECIFICATIONS (COPELAND)

M.O.P. = Maximum Overcurrent ProtectionM.C.A. = Minimum Circuit Ampacity

MODEL POWER SUPPLYCOMPRESSOR CONDENSER FANS TOTAL

AMPSM.C.A. M.O.P.

RLA LRA QTY Hp @ FLA @

T030L6 - HS2 208-230/1/60 16.7 105 1 1/3 3.2 19.9 24.1 40

T030L6 - HT3 208-230/3/60 12.8 112 1 1/3 3.2 16.0 19.2 30

T030L6 - HT4 460/3/60 6.0 56 1 1/3 1.6 7.6 9.1 15

T035L6 - HS2 208-230/1/60 25.8 125 1 1/3 3.2 29.0 35.5 60

T035L6 - HT3 208-230/3/60 16.8 102 1 1/2 4.6 21.4 25.6 40

T035L6 - HT4 460/3/60 8.1 52 1 1/2 2.3 10.4 12.4 20

T035L6 - HT5 575/3/60 6.7 41 1 1/2 2.3 9.0 10.7 15

T040L6 - HT3 208-230/3/60 26.3 161 1 1/2 4.6 30.9 37.5 60

T040L6 - HT4 460/3/60 10.2 60 1 1/2 2.3 12.5 15.0 25

T040L6 - HT5 575/3/60 7.7 49 1 1/2 2.3 10.0 11.9 20

T060L6 - HT3 208-230/3/60 28.8 161 2 1/2 4.6 38.0 45.2 70

T060L6 - HT4 460/3/60 10.2 60 2 1/2 2.3 14.8 17.3 25

T060L6 - HT5 575/3/60 9.1 49 2 1/2 2.3 13.7 16.0 25

T061L6 - HT3 208-230/3/60 30.3 150 2 1/2 4.6 39.5 47.1 70

T061L6 - HT4 460/3/60 13.7 77 2 1/2 2.3 18.3 21.7 30

T061L6 - HT5 575/3/60 10.5 62 2 1/2 2.3 15.1 17.7 25

T075L6 - HT3 208-230/3/60 31.5 161 2 1/2 4.6 40.7 48.8 80

T075L6 - HT4 460/3/60 16.1 83 2 1/2 2.3 20.7 24.7 40

T075L6 - HT5 575/3/60 11.0 67 2 1/2 2.3 15.6 18.4 30

T090L6 - HT3 208-230/3/60 39.0 215 2 3/4 4.2 47.4 57.2 90

T090L6 - HT4 460/3/60 16.9 106 2 3/4 2.1 21.1 25.3 40

T090L6 - HT5 575/3/60 16.5 84 2 3/4 2.1 20.7 24.8 40

T100L6 - HT3 208-230/3/60 42.0 215 2 3/4 4.2 50.4 60.9 100

T100L6 - HT4 460/3/60 18.6 106 2 3/4 2.1 22.8 27.5 40

T100L6 - HT5 575/3/60 16.8 84 2 3/4 2.1 21.0 25.2 40

T150L6 - HT3 208-230/3/60 52.6 278 2 3/4 4.2 61.0 74.2 125

T150L6 - HT4 460/3/60 26.3 139 2 3/4 2.1 30.5 37.1 60

T150L6 - HT5 575/3/60 20.9 113 2 3/4 2.1 25.1 30.3 50

T200L6 - HT3 208-230/3/60 66.0 374 2 3/4 4.2 74.4 90.9 150

T200L6 - HT4 460/3/60 33.0 187 2 3/4 2.1 37.2 45.5 75

T200L6 - HT5 575/3/60 24.2 135 2 3/4 2.1 28.4 34.5 60

T250L6 - HT3 208-230/3/60 80.8 450 3 3/4 4.2 93.4 113.6 175

T250L6 - HT4 460/3/60 40.4 225 3 3/4 2.1 46.7 56.8 90

T250L6 - HT5 575/3/60 32.5 172 3 3/4 2.1 38.8 46.9 70

T300L6 - HT3 208-230/3/60 95.6 470 3 3/4 4.2 108.2 132.1 225

T300L6 - HT4 460/3/60 47.8 235 3 3/4 2.1 54.1 66.1 110

T300L6 - HT5 575/3/60 39.6 200 3 3/4 2.1 45.9 55.8 90DISC

ONTI

NUED

PROD

UCT

Page 22: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

T - LINE ELECTRICAL SPECIFICATIONS (COPELAND)

M.O.P. = Maximum Overcurrent ProtectionM.C.A. = Minimum Circuit Ampacity

MODEL POWER SUPPLYCOMPRESSOR CONDENSER FANS TOTAL

AMPS M.C.A. M.O.PRLA LRA QTY Hp @ FLA @

T030L2 - HS2 208-230/1/60 16.6 93 1 1/3 3.2 19.8 24.0 40

T030L2 - HT3 208-230/3/60 10.7 82 1 1/3 3.2 13.9 16.6 25

T030L2 - HT4 460/3/60 5.2 41 1 1/3 1.6 6.8 8.1 15

T030L2 - HT5 575/3/60 4.0 30 1 1/3 1.6 5.6 6.6 15

T035L2 - HS2 208-230/1/60 25.8 125 1 1/2 4.6 30.4 36.9 60

T035L2 - HT3 208-230/3/60 16.8 102 1 1/2 4.6 21.4 25.6 40

T035L2 - HT4 460/3/60 8.1 52 1 1/2 2.3 10.4 12.4 20

T035L2 - HT5 575/3/60 6.7 41 1 1/2 2.3 9.0 10.7 15

T040L2 - HT3 208-230/3/60 26.3 161 1 1/2 4.6 30.9 37.5 60

T040L2 - HT4 460/3/60 10.2 60 1 1/2 2.3 12.5 15.0 25

T040L2 - HT5 575/3/60 7.7 49 1 1/2 2.3 10.0 11.9 20

T060L2 - HT3 208-230/3/60 28.8 161 2 1/2 4.6 38.0 45.2 70

T060L2 - HT4 460/3/60 10.2 60 2 1/2 2.3 14.8 17.3 25

T060L2 - HT5 575/3/60 9.1 49 2 1/2 2.3 13.7 16.0 25

T061L2 - HT3 208-230/3/60 30.3 150 2 1/2 4.6 39.5 47.1 70

T061L2 - HT4 460/3/60 13.7 77 2 1/2 2.3 18.3 21.7 35

T061L2 - HT5 575/3/6 10.5 62 2 1/2 2.3 15.1 17.7 25

T075L2 - HT3 208-230/3/60 31.5 161 2 1/2 4.6 40.7 48.6 80

T075L2 - HT4 460/3/60 16.1 83 2 1/2 2.3 20.7 24.7 40

T075L2 - HT5 575/3/60 11.0 67 2 1/2 2.3 15.6 18.4 30

T090L2 - HT3 208-230/3/60 39.0 215 2 3/4 4.2 47.4 57.2 100

T090L2 - HT4 460/3/60 16.9 106 2 3/4 2.1 21.1 25.3 40

T090L2 - HT5 575/3/60 16.5 84 2 3/4 2.1 20.7 24.8 40

T100L2 - HT3 208-230/3/60 42.0 215 2 3/4 4.2 50.4 60.9 90

T100L2 - HT4 460/3/60 18.6 106 2 3/4 2.1 22.8 27.5 40

T100L2 - HT5 575/3/60 16.8 84 2 3/4 2.1 21.0 25.2 40

T150L2 - HT3 208-230/3/60 52.6 278 2 3/4 4.2 61.0 74.2 125

T150L2 - HT4 460/3/60 26.3 139 2 3/4 2.1 30.5 37.1 60

T150L2 - HT5 575/3/60 20.9 113 2 3/4 2.1 25.1 30.3 50

T200L2 - HT3 208-230/3/60 66.0 374 2 3/4 4.2 74.4 90.9 150

T200L2 - HT4 460/3/60 33.0 187 2 3/4 2.1 37.2 45.5 80

T200L2 - HT5 575/3/60 24.2 135 2 3/4 2.1 28.4 34.5 50

T250L2 - HT3 208-230/3/60 80.8 450 3 3/4 4.2 93.4 113.6 175

T250L2 - HT4 460/3/60 40.4 225 3 3/4 2.1 46.7 56.8 90

T250L2 - HT5 575/3/60 32.5 172 3 3/4 2.1 38.8 46.9 70

T300L2 - HT3 208-230/3/60 95.6 470 3 3/4 4.2 108.2 132.1 225

T300L2 - HT4 460/3/60 47.8 235 3 3/4 2.1 54.1 66.1 110

T300L2 - HT5 575/3/60 39.6 200 3 3/4 2.1 45.9 55.8 90

- 22 -

DISC

ONTI

NUED

PROD

UCT

Page 23: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

- 23 -

T - LINE ELECTRICAL SPECIFICATIONS (COPELAND)

M.O.P. = Maximum Overcurrent ProtectionM.C.A. = Minimum Circuit Ampacity

MODEL POWER SUPPLYCOMPRESSOR CONDENSER FANS TOTAL

AMPSM.C.A. M.O.P.

RLA LRA QTY Hp @ FLA @

T030L5 - HS2 208-230/1/60 15.1 86 1 1/3 3.2 18.3 22.1 40

T030L5 - HT3 208-230/3/60 10.7 82 1 1/3 3.2 13.9 16.6 25

T030L5 - HT4 480/3/60 5.7 41 1 1/3 1.6 7.3 8.7 15

T030L5 - HT5 575/3/60 4.0 30 1 1/3 1.6 5.6 6.6 15

T035L5 - HS2 208-230/1/60 25.8 125 1 1/2 4.6 30.4 36.9 60

T035L5 - HT3 208-230/3/60 16.8 102 1 1/2 4.6 21.4 25.6 40

T035L5 - HT4 460/3/60 8.1 52 1 1/2 2.3 10.4 12.4 20

T035L5 - HT5 575/3/60 6.7 41 1 1/2 2.3 9.0 10.7 15

T040L5 - HT3 208-230/3/60 26.3 161 1 1/2 4.6 30.9 37.5 60

T040L5 - HT4 460/3/60 10.2 60 1 1/2 2.3 12.5 15.0 25

T040L5 - HT5 575/3/60 7.7 49 1 1/2 2.3 10.0 11.9 20

T060L5 - HT3 208-230/3/60 28.8 161 2 1/2 4.6 38.0 45.2 70

T060L5 - HT4 460/3/60 10.2 60 2 1/2 2.3 14.8 17.3 25

T060L5 - HT5 575/3/60 9.1 49 2 1/2 2.3 13.7 16.0 25

T061L5 - HT3 208-230/3/60 26.5 150 2 1/2 4.6 35.7 42.3 70

T061L5 - HT4 460/3/60 12.0 77 2 1/2 2.3 16.6 19.6 30

T061L5 - HT5 575/3/60 10.5 62 2 1/2 2.3 15.1 17.7 25

T075L5 - HT3 208-230/3/60 31.5 161 2 1/2 4.6 40.7 48.6 80

T075L5 - HT4 460/3/60 16.1 83 2 1/2 2.3 20.7 24.7 40

T075L5 - HT5 575/3/60 11.0 67 2 1/2 2.3 15.6 18.4 30

T090L5 - HT3 208-230/3/60 39.0 215 2 3/4 4.2 47.4 57.2 90

T090L5 - HT4 460/3/60 16.9 106 2 3/4 2.1 21.1 25.3 40

T090L5 - HT5 575/3/60 16.5 84 2 3/4 2.1 20.7 24.8 40

T100L5 - HT3 208-230/3/60 42.0 215 2 3/4 4.2 50.4 60.9 90

T100L5 - HT4 460/3/60 18.6 106 2 3/4 2.1 22.8 27.5 40

T100L5 - HT5 575/3/60 16.8 84 2 3/4 2.1 21.0 25.2 40

T150L5 - HT3 208-230/3/60 52.6 278 2 3/4 4.2 61.0 74.2 125

T150L5 - HT4 460/3/60 26.3 139 2 3/4 2.1 30.5 37.1 60

T150L5 - HT5 575/3/60 20.9 113 2 3/4 2.1 25.1 30.3 50

T200L5 - HT3 208-230/3/60 66.0 374 2 3/4 4.2 74.4 90.9 150

T200L5 - HT4 460/3/60 33.0 187 2 3/4 2.1 37.2 45.5 80

T200L5 - HT5 575/3/60 24.2 135 2 3/4 2.1 28.4 34.5 50

T250L5 - HT3 208-230/3/60 80.8 450 3 3/4 4.2 93.4 113.6 175

T250L5 - HT4 460/3/60 40.4 225 3 3/4 2.1 46.7 56.8 90

T250L5 - HT5 575/3/60 32.5 172 3 3/4 2.1 38.8 46.9 70

T300L5 - HT3 208-230/3/60 95.6 470 3 3/4 4.2 108.2 132.1 225

T300L5 - HT4 460/3/60 47.8 235 3 3/4 2.1 54.1 66.1 110

T300L5 - HT5 575/3/60 39.6 200 3 3/4 2.1 45.9 55.8 90DISC

ONTI

NUED

PROD

UCT

Page 24: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

T - LINE ELECTRICAL SPECIFICATIONS (CARLYLE)

M.O.P. = Maximum Overcurrent ProtectionM.C.A. = Minimum Circuit Ampacity

MODEL POWER SUPPLYCOMPRESSOR CONDENSER FANS TOTAL

AMPSM.C.A. M.O.P.

RLA LRA QTY Hp @ FLA @

TC035L5 - HS2 208-230/1/60 28.6 150 1 1/2 4.6 33.2 40.4 60

TC035L5 - HT3 208-230/3/60 19.3 100 1 1/2 4.6 23.9 28.7 40

TC035L5 - HT4 460/3/60 9.6 50 1 1/2 2.3 11.9 14.3 20

TC035L5 - HT5 575/3/60 7.7 40 1 1/2 2.3 10.0 11.9 15

TC040L5 - HS2 208-230/1/60 28.6 150 1 1/2 4.6 33.2 40.4 70

TC040L5 - HT3 208-230/3/60 19.3 100 1 1/2 4.6 23.9 28.7 50

TC040L5 - HT4 460/3/60 9.6 50 1 1/2 2.3 11.9 14.3 20

TC040L5 - HT5 575/3/60 7.7 40 1 1/2 2.3 10.0 11.9 20

TC060L5 - HT3 208-230/3/60 31.4 160 2 1/2 4.6 40.6 48.4 80

TC060L5 - HT4 460/3/60 15.7 80 2 1/2 2.3 20.3 24.2 40

TC060L5 - HT5 575/3/60 12.6 64 2 1/2 2.3 17.2 20.3 30

TC061L5 - HT3 208-230/3/60 31.4 160 2 1/2 4.6 40.6 48.4 80

TC061L5 - HT4 460/3/60 15.7 80 2 1/2 2.3 20.3 24.2 40

TC061L5 - HT5 575/3/60 12.6 64 2 1/2 2.3 17.2 20.3 30

TC075L5 - HT3 208-230/3/60 39.6 198 2 1/2 4.6 48.8 58.7 100

TC075L5 - HT4 460/3/60 19.8 99 2 1/2 2.3 24.4 29.4 50

TC075L5 - HT5 575/3/60 15.9 79 2 1/2 2.3 20.5 24.5 40

TC090L5 - HT3 208-230/3/60 44.3 228 2 3/4 4.2 52.7 63.8 100

TC090L5 - HT4 460/3/60 22.1 114 2 3/4 2.1 26.3 31.8 50

TC090L5 - HT5 575/3/60 17.9 91 2 3/4 2.1 22.1 26.6 40

TC100L5 - HT3 208-230/3/60 44.3 228 2 3/4 4.2 52.7 63.8 100

TC100L5 - HT4 460/3/60 22.1 114 2 3/4 2.1 26.3 31.8 50

TC100L5 - HT5 575/3/60 17.9 91 2 3/4 2.1 22.1 26.6 40

TC150L5 - HT3 208-230/3/60 72.0 283 2 3/4 4.2 80.4 98.4 150

TC150L5 - HT4 460/3/60 36.0 142 2 3/4 2.1 40.2 49.2 80

TC150L5 - HT5 575/3/60 31.0 98 2 3/4 2.1 35.2 43.0 70

TC200L5 - HT3 208-230/3/60 87.0 345 2 3/4 4.2 95.4 117.2 200

TC200L5 - HT4 460/3/60 44.0 173 2 3/4 2.1 48.2 59.2 100

TC200L5 - HT5 575/3/60 36.0 120 2 3/4 2.1 40.2 49.2 80

TC250L5 - HT3 208-230/3/60 87.0 345 3 3/4 4.2 99.6 121.4 200

TC250L5 - HT4 460/3/60 44.0 173 3 3/4 2.1 50.3 61.3 100

TC250L5 - HT5 575/3/60 36.0 120 3 3/4 2.1 42.3 51.3 80

TC300L5 - HT3 208-230/3/60 135.0 506 3 3/4 4.2 147.6 181.4 300

TC300L5 - HT4 460/3/60 68.0 253 3 3/4 2.1 74.3 91.3 150

TC300L5 - HT5 575/3/60 52.0 176 3 3/4 2.1 58.3 71.3 110

- 24 -

DISC

ONTI

NUED

PROD

UCT

Page 25: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

- 25 -

MODEL POWER SUPPLYCOMPRESSOR CONDENSER FANS TOTAL

AMPSM.C.A. M.O.P.

RLA LRA QTY Hp @ FLA @

TC030L6 - HT3 208-230/3/60 12.4 71 1 1/3 3.2 15.6 18.7 30

TC030L6 - HT4 460/3/60 6.2 35.5 1 1/3 1.6 7.8 9.4 15

TC030L6 - HT5 575/3/60 5.0 28.4 1 1/3 1.6 6.6 7.9 15

TC035L6 - HT3 208-230/3/60 19.3 100 1 1/2 4.6 22.5 27.3 40

TC035L6 - HT4 460/3/60 9.6 50 1 1/2 2.3 11.2 13.6 20

TC035L6 - HT5 575/3/60 7.7 40 1 1/2 2.3 9.3 11.2 15

TC040L6 - HT3 208-230/3/60 19.3 100 1 1/2 4.6 22.5 27.3 40

TC040L6 - HT4 460/3/60 9.6 50 1 1/2 2.3 11.2 13.6 20

TC040L6 - HT5 575/3/60 7.7 40 1 1/2 2.3 9.3 11.2 15

TC060L6 - HT3 208-230/3/60 31.4 160 2 1/2 4.6 40.6 48.4 80

TC060L6 - HT4 460/3/60 15.7 80 2 1/2 2.3 20.3 24.2 40

TC060L6 - HT5 575/3/60 12.6 64 2 1/2 2.3 17.2 20.3 30

TC061L6 - HT3 208-230/3/60 31.4 160 2 1/2 4.6 40.6 48.4 80

TC061L6 - HT4 460/3/60 15.7 80 2 1/2 2.3 20.3 24.2 40

TC061L6 - HT5 575/3/60 12.6 64 2 1/2 2.3 17.2 20.3 30

TC075L6 - HT3 208-230/3/60 39.6 198 2 1/2 4.6 48.8 58.7 100

TC075L6 - HT4 460/3/60 19.8 99 2 1/2 2.3 24.4 29.4 50

TC075L6 - HT5 575/3/60 15.9 79 2 1/2 2.3 20.5 24.5 40

TC090L6 - HT3 208-230/3/60 44.3 228 2 3/4 4.2 52.7 63.8 100

TC090L6 - HT4 460/3/60 22.1 114 2 3/4 2.1 26.3 31.8 50

TC090L6 - HT5 575/3/60 17.9 91 2 3/4 2.1 22.1 26.6 40

TC150L6 - HT3 208-230/3/60 72.0 283 2 3/4 4.2 80.4 98.4 150

TC150L6 - HT4 460/3/60 36.0 142 2 3/4 2.1 40.2 49.2 80

TC150L6 - HT5 575/3/60 31.0 96 2 3/4 2.1 35.2 43.0 70

TC200L6 - HT3 208-230/3/60 87.0 345 2 3/4 4.2 95.4 117.2 200

TC200L6 - HT4 460/3/60 44.0 173 2 3/4 2.1 48.2 59.2 100

TC200L6 - HT5 575/3/60 36.0 120 2 3/4 2.1 40.2 49.2 80

TC250L6 - HT3 208-230/3/60 87.0 345 3 3/4 4.2 99.6 121.4 200

TC250L6 - HT4 460/3/60 44.0 173 3 3/4 2.1 50.3 61.3 100

TC250L6 - HT5 575/3/60 36.0 120 3 3/4 2.1 42.3 51.3 80

TC300L6 - HT3 208-230/3/60 135.0 506 3 3/4 4.2 147.6 181.4 300

TC300L6 - HT4 460/3/60 68.0 253 3 3/4 2.1 74.3 91.3 150

TC300L6 - HT5 575/3/60 52.0 176 3 3/4 2.1 58.3 71.3 110

T - LINE ELECTRICAL SPECIFICATIONS (CARLYLE)

M.O.P. = Maximum Overcurrent ProtectionM.C.A. = Minimum Circuit Ampacity

DISC

ONTI

NUED

PROD

UCT

Page 26: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

- 26 -

DISC

ONTI

NUED

PROD

UCT

Page 27: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

- 27 -

DISC

ONTI

NUED

PROD

UCT

Page 28: T-LINE CONDENSING UNITS PPRROODDUUCCTT DDPRODUCT …docs.t-rp.com/archive/t-line 1064622.pdf · • Crankcase heater • Pump down toggle switch • Two valve adjustable flooded head

NATIONAL REFRIGERATION & AIR CONDITIONING CANADA CORP.159 Roy Blvd.• Brantford • Ontario, Canada N3R 7K1

PHONE: (519) 751-0444 • 800-463-9517 • FAX (519) 753-1140

Due to National Refrigeration’s policy of continuous product improvement, we reserve the right to make changes without notice.

DISC

ONTI

NUED

PROD

UCT