ENGINEERING ADVANTAGE
TA-SCOPE
Balancing instrumentInstruments
TA-SCOPE is a tough, effective balancing instrument for measuring and documenting of differential pressure, flow, temperature and power in hydronic systems. Robust, accurate and easy-to-use, TA-SCOPE delivers quicker, more cost-efficient balancing and enables rapid troubleshooting. TA-SCOPE links effortlessly to the TA-Select PC software gaining the maximum benefit from recorded data and enabling professional report writing and automatic software upgrades.
Pressurisation & Water Quality Balancing & Control Thermostatic Control
InsTrumenTs - TA-SCOPE
2
User-friendly designErgonomic and custom designed user-interface ensures easy and more comfortable balancing.
Interactive softwareStep by step software wizards for measuring, balancing and trouble shooting ensure a fast commissioning process.
Wireless communicationFor reliable balancing, a fully charged TA-SCOPE provides three days of power-efficient wireless performance.
Technical description
TA-SCOPE is a balancing instrument for measuring and documenting of differential pressure (Δp), flow, temperature and power in hydronic systems. TA-SCOPE consists of two main components:Handheld unit – computer-based unit programmed with the TA valve characteristics. Straightforward functions with easy-to-follow instructions on the colour display.Differential Pressure Sensor unit – the Dp Sensor communicates wirelessly with the Handheld unit and has LED indicators for indicating communication status and battery capacity. The units can optionally be connected via cable. TA-SCOPE automatically demands calibration when needed. The design of the sensor unit and a short flow-through during calibration eliminate measurement errors caused by insufficient venting of the measuring device.
Measurement range:Total pressure: max. 2 500 kPaDifferential pressure: TA-SCOPE 0 - 200 kPaTA-SCOPE HP 0 - 1 000 kPaRecommended pressure range during flow measurements: TA-SCOPE 3 - 200 kPaTA-SCOPE HP 3 - 1 000 kPa
Temperature liquid medium measurement:-20°C – 120°C
Measurement deviation: Differential pressure: TA-SCOPE 0.1 kPa or 1% of reading, whichever is the highestTA-SCOPE HP 0.2 kPa or 1% of reading, whichever is the highestFlow: as for differential pressure + valve deviationTemperature: <0.2°C
Battery capacity, operating and charge times:Handheld unit:- battery capacity: 4 400 mAh- operating time (with backlight on): >25 h- charge time to full capacity: 6-7 hDp Sensor unit:- battery capacity: 1 100 mAh- operating time (continuous measurements): >25 h- charge time to full capacity: 1,5 hLogging time (in sleep mode): >100 days
Enclosure class:Handheld unit (in wireless mode): IP 64Dp sensor unit (in wireless mode): IP 64Safety pressure and temperature probe: IP 65Digital temperature sensor: IP 65
Ambient temperature for the instrument:During operation and charging: 0-40°CDuring storage*: -20-60°C*) Do not leave water in the sensor when there is a risk of freezing.
Humidity:Ambient humidity: max. 90%RH
Charger:Output voltage: 5,2 V DC (minimum 5,0 V, maximum 5,3 V)Output current: Minimum 1 A.Isolation: Class II.Certification: IEC (868 MHz) and/or UL, CSA (915 MHz).Complying with the LPS (Low Power Source) regulation.
InsTrumenTs - TA-SCOPE
3
Hydronic functions
Quick MeasureStraightforward function to measure flow, differential pressure (Δp), temperature and power. To be used when only one or a few valves are of interest. The function does not require any predefinition of network or module.
Hydronic NetworksComplex networks created in TA-Select are easily downloaded to TA-SCOPE. Use a network for measuring and balancing at any time; during commission, for control and inspection. All hydronic functions can be applied to a selected valve from a Hydronic Network.
BalancingThe powerful TA-Wireless and TA-Diagnostic methods for balancing hydronic systems. TA-Wireless makes use of two Dp sensors with wireless technology to easily perform balancing of a hydronic module. With TA-Diagnostic, you measure all valves in a module. The method calculates a Dp diagnostic for the module and correct valve openings to attain design flows.
TroubleshootingSoftware wizards take you step-by-step through the process of locating and diagnosing problems and errors in hydronic systems, e.g., Dp (Δp) analysis.
Data LoggingMeasurement during a predetermined period of time to analyse any fluctuations in flow, differential pressure (Δp), temperature and power. The logged data is stored and listed or displayed as a graph, both in TA-SCOPE and TA-Select.
Support functions
FluidSettings of fluid in the system to be explored and diagnosed. Water is the most common fluid in hydronic systems but water with various additives can also be handled by TA-SCOPE.
Hydronic calculatorPerform calculations based on the relationship between flow, differential pressure (Δp), Kv-value, power and differential temperature (ΔT). The function also gives guidance in selecting pipes and valves when designing hydronic systems and enables unit conversions.
Settings Manage adjustments regarding the instrument and appearance of information from the Settings function.
InformationDisplays information like software version, last calibration and battery details on Handheld, Dp Sensor and also Temperature Sensor when connected.
InsTrumenTs - TA-SCOPE
4
Articles
Case contents:- Handheld unit (Hh)- Dp Sensor unit (DpS)- Digital Temperature Sensor (DTS)- Measuring hoses, 500 mm, red/blue - Safety pressure and temperature probe (SPTP)- Safety pressure probes (SPP)- Measuring hoses with twin needle, 150 mm- Flashlight- Mirror- Chucks for older valves, red/blue- Allen Keys 3 mm/5 mm- Spanner for measuring points on older valves- Presetting tool TBV-C/TBV-CM/TBV-CMP- Spare filters (4 pcs)- Chain for mounting
- Neckstrap- USB-cables for connection; Hh – DpS and Hh – PC- Multi-charger for Handheld, Dp Sensor(s) and TA-SCOPE Relays- DC cables (2 pcs)- AC cable (EU, UK, US or AU/NZ)- Cable wrapping- Case- TA-Select Software- User manual- Calibration certificates for DpS, DTS and SPTP- Quick Guide- SPTP/SPP instruction- SPTP/SPP stickers
TA-SCOPE
Version* Manual language EAN Article No
AT Austria/Germany DE 7318793982605 52 199-006AU/NZ Australia/New Zealand EN 7318793986603 52 199-023BE Belgium FR, NL 7318793986702 52 199-024CEE Central Eastern Europe CS 7318793982803 52 199-010CEE Central Eastern Europe PL 7318793984609 52 199-011CEE Central Eastern Europe RU 7318793984708 52 199-012CEE Central Eastern Europe HU 7318793984807 52 199-013CEE Central Eastern Europe EN 7318793986801 52 199-025CH Switzerland DE, FR, IT 7318793985309 52 199-022DK Denmark DA 7318793984104 52 199-003ES Spain ES 7318793984500 52 199-009FI Finland FI 7318793984302 52 199-005FR France FR 7318793982704 52 199-007GB Great Britain EN 7318793985002 52 199-015INT International version EN 7318793982506 52 199-002IT Italy IT 7318793985200 52 199-021JP Japan JA 7318793986207 52 199-016KR Korea KO 52 199-026LAM Latin America PT, ES 7318793986405 52 199-018MEA Middle East EN 7318793986306 52 199-017NL Netherlands NL 7318793984401 52 199-008NO Norway NO 7318793984203 52 199-004SAS South Asia EN 7318793986504 52 199-019SE Sweden SV 7318793982407 52 199-001TR Turkey TR 52 199-027US USA EN 7318793984906 52 199-014zh-CN China (simplified Chinese) zh-CN 7318793985101 52 199-020zh-TW Taiwan (traditional Chinese) zh-TW 52 199-029
InsTrumenTs - TA-SCOPE
5
TA-SCOPE HP
Version* Manual language EAN Article No
AT Austria/Germany DE 7318793987709 52 199-106AU/NZ Australia/New Zealand EN 7318793989406 52 199-123BE Belgium FR, NL 7318793989505 52 199-124CEE Central Eastern Europe CS 7318793988102 52 199-110CEE Central Eastern Europe PL 7318793988201 52 199-111CEE Central Eastern Europe RU 7318793988300 52 199-112CEE Central Eastern Europe HU 7318793988409 52 199-113CEE Central Eastern Europe EN 7318793989604 52 199-125CH Switzerland DE, FR, IT 7318793989307 52 199-122DK Denmark DA 7318793987402 52 199-103ES Spain ES 7318793988003 52 199-109FI Finland FI 7318793987600 52 199-105FR France FR 7318793987808 52 199-107GB Great Britain EN 7318793988607 52 199-115INT International version EN 7318793986900 52 199-102IT Italy IT 7318793989208 52 199-121JP Japan JA 7318793988706 52 199-116KR Korea KO 52 199-126LAM Latin America PT, ES 7318793988904 52 199-118MEA Middle East EN 7318793988805 52 199-117NL Netherlands NL 7318793987907 52 199-108NO Norway NO 7318793987501 52 199-104SAS South Asia EN 7318793989000 52 199-119SE Sweden SV 7318793987303 52 199-101TR Turkey TR 52 199-127US USA EN 7318793988508 52 199-114zh-CN China (simplified Chinese) zh-CN 7318793989109 52 199-120zh-TW Taiwan (traditional Chinese) zh-TW 52 199-129
*) Version = Market related product range. All instrument versions include all of the above languages.
InsTrumenTs - TA-SCOPE
6
Additional equipment
Dp sensor unit (DpS)The handheld unit (Hh) can communicate with several Dp sensor units (DpS). Establish communication by connecting the cable (included in the TA-SCOPE case) between the handheld unit and the Dp sensor unit.Included: 2 measuring hoses 500 mm, 2 identification rings for marking the DpS, 2 safety pressure probes (SPP) and 1 DC-cable.
Version EAN Article No
Standard 7318793983404 52 199-931HP (high pressure) 7318793987006 52 199-932
Measuring hose
Length EAN Article No
500 mm Red 7318793998507 52 199-953500 mm Blue 7318793998606 52 199-954
Measuring hose with twin needle
Length EAN Article No
150 mm 7318793985903 52 199-999
Safety pressure probe (SPP)
EAN Article No
7318793998309 52 199-951
Safety pressure and temperature probe (SPTP)
EAN Article No
7318793998408 52 199-952
Cable wrappingTo keep SPTP cable and hose together
EAN Article No
310 355-01
Digital temperature sensor (DTS)
EAN Article No
7318793983503 52 199-941
RelayFor long-range transmission.1 DC cable per relay included.For further information on TA-SCOPE Relay, see separate leaflet.
Version EAN Article No
Relay kit, case with 3 relays (2 Kensington locks and 1 belt clip included)868 MHz Europe 7318793998903 52 199-961915 MHz US/AU/NZ 7318793999009 52 199-962
Relay, separate868 MHz Europe 7318793999108 52 199-963915 MHz US/AU/NZ 7318793999207 52 199-964
InsTrumenTs - TA-SCOPE
7
Accessories
Measuring hoseExtension with shut-off valve
Length EAN Article No
3 m Red 7318793817709 52 199-9973 m Blue 7318793817808 52 199-998
Extension cable for digital temperatur sensor
EAN Article No
5 m 7318793985408 52 199-994
Measuring nippleThread connections G1/2 and G3/4
EAN Article No
G1/2 7318793536808 52 197-303G3/4 7318793536907 52 197-304
Measuring nippleExtension 60 mmCan be installed without draining of the system.
L EAN Article No
60 7318792812804 52 179-006
Measuring needle, angle
EAN Article No
7318793787507 307 635-62
k
Belt With instrument pockets
Size Length EAN Article No
M/L ~ 1,25 m 7318793983602 52 199-991L/XL ~ 1,51 m 7318793983701 52 199-992Extra pocket for accessories 7318793983800 52 199-993
FilterSpare part to measuring hoses
EAN Article No
7318793741301 309 206-01
Identification rings“DpS 1” and “DpS 2” for marking the DpS when using TA-Wireless. To be placed on measuring hoses.
EAN Article No
DpS 1 310 399-01DpS 2 310 399-02
InsTrumenTs - TA-SCOPE
8
Multi-chargerWith 6 DC cable connection points.Excl. AC and DC cables.
EAN Article No
310 395-01
DC cableTo connect a device to the multi-charger
EAN Article No
310 397-01
AC cable
EAN Article No
Europe 310 396-01UK 310 396-02US 310 396-03AU/NZ 310 396-04
The products, texts, photographs, graphics and diagrams in this document may be subject to alteration by TA Hydronics without prior notice or reasons being given. For the most up to date information about our products and specifications, please visit www.tahydronics.com.
7-5-6 TA-SCOPE 12.2011
ENGINEERING ADVANTAGE
TA-SCOPE Relay
Wireless transmission relayInstruments
TA-SCOPE relay is a long-range transmission relay for measuring, balancing and diagnosing hydronic systems with multiple TA-SCOPE sensors. It is to be used in particular for applying the TA-Wireless method with the TA-SCOPE in large buildings.
Pressurisation & Water Quality Balancing & Control Thermostatic Control
InsTrumenTs - TA-SCOPE RElAy
2
long range wireless transmissionRange between two relays reaches 5 to 6 floors indoor.
Easy configurationA software wizard integrated in the TA-SCOPE takes you step-by-step through an illustrated configuration process.
long-standing batteriesFully charged TA-SCOPE relays provide three days of power-efficient wireless performance.
Technical description
Applications:TA-SCOPE relay is a long-range transmission relay for measuring, balancing and diagnosing hydronic systems with multiple TA-SCOPE sensors.It is to be used in particular for applying the TA-Wireless method with the TA-SCOPE in large buildings.
Configuration:In order to configure long-distance transmission with the optional TA-SCOPE Relays select Configure Relays in the Options menu. A software wizard takes you step-by-step through the configuration process. The option Add intermediate Relays allows adding more intermediate Relays to an existing relay configuration.
Ambient temperature:During operation: 0°C – +40°CDuring charging: 0°C – +40°CDuring storage: -20°C – +60°C
Humidity:Ambiant humidity: max 90% RH
Battery capacity, operating and charge times:Capacity: 4 400 mAhOperating time: >25 hCharge time to full capacity: 6-7 hRemark: Replacing the battery by another type is strictly forbidden and could lead to an explosion.
Wireless:Between two relays: 868 MHz – EC version. 915 MHz – FCC version.Range in open space: approx. 500 m.Range indoors: approx. 5-6 floors.
Enclosure class:IP 44
Colour:Black
Charger:Output voltage: 5,2 V DC (minimum 5,0 V, maximum 5,3 V)Output current: Minimum 1 A.Isolation: Class II.Certification: IEC (868 MHz) and/or UL, CSA (915 MHz).Complying with the LPS (Low Power Source) regulation.
InsTrumenTs - TA-SCOPE RElAy
3
Functions
The TA-SCOPE relay is a high power transmission relay allowing to receive measurements performed by multiple TA-SCOPE Dp sensors located across a whole building.It uses 868 MHz (Europe) or 915 MHz (US) radio for obtaining a large transmission range and bridges this signal with the 2,4 GHz used by the TA-SCOPE handheld and Dp sensors.The elementary configuration is:- Relay 1 near the operator- Relay 2 near the second Dp sensorIf larger range is needed, up to 5 intermediate relays can be added.
Hh = Handheld DpS = Dp Sensor R = Relay
ChargingCharging of TA-SCOPE relays is performed by using the multi-charger available in the TA-SCOPE case.
Operation
For best wireless rangeInstall the relays- at some height (1 - 2 m) from the floor- not too close to reinforced concrete walls- not on a wet surfaceUse technical shafts when available as channel for the radio waves (see Fig. 1).Place relays near windows or outdoor to extend propagation of radio waves in larger buildings (see Fig. 2).
Fig. 1
Fig. 2
I R = Intermediate Relay
DpS 1DpS 2
R 2R 1
Hh
R 1Hh
I R
DpS 2
R 2
DpS 1
R 2
I R
R 1
Hh
I R
InsTrumenTs - TA-SCOPE RElAy
4
Articles
Relay1 DC cable per relay included.
Version l H1 H2 B EAN Article No
Relay kit, case with 3 relays (2 Kensington locks and 1 belt clip included)868 MHz Europe 90 130 100 45 7318793998903 52 199-961915 MHz US/AU/NZ 90 130 100 45 7318793999009 52 199-962
Relay, separate868 MHz Europe 90 130 100 45 7318793999108 52 199-963915 MHz US/AU/NZ 90 130 100 45 7318793999207 52 199-964
Accessories
Multi-chargerWith 6 DC cable connection points.Excl. AC and DC cables.
Article No
310 395-01
DC cableTo connect a device to the multi-charger
Article No
310 397-01
AC cable
Version Article No
Europe 310 396-01UK 310 396-02US 310 396-03AU/NZ 310 396-04
The products, texts, photographs, graphics and diagrams in this document may be subject to alteration by TA Hydronics without prior notice or reasons being given. For the most up to date information about our products and specifications, please visit www.tahydronics.com.
7-5-7 TA-SCOPE 03.2012
H2
H1
LB
Pressurisation & Water Quality Balancing & Control Thermostatic Control ENGINEERING ADVANTAGE
TA Link
Differential pressure sensor – 0-10 V / 4-20 mA
The crucial connection between the hydronic system and the building management system (BMS), TA Link provides an accurate measurement of the differential pressure. With data you know you can rely on, troubleshooting is quicker and system analysis is made more cost-effective. TA Link also boosts your system’s safety thanks to its ability to signal an alarm in the event of incorrect flow rates.
SenSorS - TA LINk
2
Self-sealing measuring pointsEnables TA Link to be fitted snugly onto the balancing valve’s measuring port in just a few seconds.
MeasuringRapid measurement of differential pressure, enabling quicker troubleshooting.
Technical description
Application:Heating and cooling systems
Function:Measuring
Range:0-40 kPa or 0-100 kPa
Pressure class:PN 25
Max. differential pressure:2 bar or 5 bar
Temperature:Max. working temperature: 80°CMin. working temperature: -15°C
Output signal:0-10 V or 4-20 mA
Accurancy:<±1.0 kPa
Power supply:18-33 VDC or 24 VAC +15/-10 % (0-10 V)11-33 VDC (4-20 mA)
Response time:< 5 ms
Protection class:IP 65
Material:Sensor housing of stainless steel X8CrNiS18-9 (No 1.4305 EN 10 088-3).Ceramic membrane.EPDM seal.
SenSorS - TA LINk
3
Valve characteristics
The valve characteristics of TA valves are available in the software TA Select, for calculation of flow/differential pressure measurement. It is also available on calculation disc and catalogue leaflet.
TA Select and catalogue leaflet can be downloaded from www.tahydronics.com.
Electrical connection
0-10 VElectrical connection is by means of a 1.5 m long 3-core cable. Core colours are as follows:White: System neutralBrown: 18-33 VDC or 24 VAC +15/-10% power supply. Current consumption, 5 mA.Green: 0-10 V output signal, proportional to the differential pressure. Load: not less than 10 kΩ.
4-20 mAElectrical connection is by means of a 1.5 m long 2-core cable. Core colours are as follows:Brown: 11-33 VDC power supply.Green: 4-20 mA output signal, proportional to the differential pressure. Load: not more than 650 Ω (at 24 VDC).
Connection to measurement points
Safety valveThe safety valve must be in position B when connecting and disconnecting the unit. Note: This opens the valve between P1 and P2. When measuring, the safety valve must be in position A to bring the sensor into operation.
Pressure connectionsConnect the red connection (P1) to the higher pressure (i.e. upstream of the balancing valve). Connect the blue connection (P2) to the lower pressure (i.e. downstream of the balancing valve). The connections have compression couplings for 6 mm (O.D.) copper pipe. (Pipe is not included).
CalibrationThe sensor has been calibrated when supplied.
VentingThe sensor must be vented in order to ensure correct measurement accuaracy. When venting, the safety valve must be in position B. Continue the venting until the pipes to and from the sensor is filled with water.
P1
P2
B
A
SenSorS - TA LINk
4
Articles
Range EAN Article No
0-10 V0-40 kPa 7318792750106 52 010-0040-100 kPa 7318792750205 52 010-010
4-20 mA0-100 kPa 7318793746207 52 110-010
Accessories
Measuring point, two-wayFor connection of 6 mm copper pipe while permitting simultaneous use of TAs measuring or balancing instruments.
EAN Article No
7318792813306 52 179-100
Capillary pipe
L EAN Article No
1 m 7318792750304 52 010-901
The products, texts, photographs, graphics and diagrams in this document may be subject to alteration by TA Hydronics without prior notice or reasons being given. For the most up to date information about our products and specifications, please visit www.tahydronics.com.
7-10-5 TA Link 05.2013
18
Ø40
115
Ø5
90
35
Ø6
Ø6
6