TAB STATIONARY BATTERIES

TAB POLARTAB MAGICTAB POLAR TRUCKTAB MAGIC TRUCKTAB EFB Stop amp GoTAB AGM Stop amp Go

ENGLISH

OPzSOGiUPSTOPzSOPzV

IN CASE OF PROBLEMS WITH ORDERING WE WILL BE GLAD TO ADVISE AND ASSIST YOU IN THE SELECTION OF THE SUITABLE TYPE OF BATTERY

Low maintenance TAB OPzS vented stationary batteries6V 4 OPzS 200

Rated voltage

Max

Min

H

W

L

Number ofpositive plate

Type of plates

Capacity at 10-hour

discharging

TECHNICAL DATA AND DIMENSIONS IN ORDER THAT THE BATTERIES WOULD MEET ALL YOUR DEMANDS WE

KINDLY ASK YOU TO ENCLOSE THE FOLLOWING DATA WITH YOUR ORDER

LET US LEAD YOU INTO THE WORLD OF EVERLASTING ENERGY AND INTRODUCE YOU WITH OPzS STATIONARY BLOCKS AND CELLS PRODUCED IN THE CONVENTIONAL LEAD-ACID TECHNOLOGY

The batteries are distinguished for highcapacity longlifetime reducedmaintenance lowself-discharging quickandsimpleacid level control economicalwater consumption appropriatedimensions andweight thelowestandconstant maintenance currentTheindividualcells(2V)andblocks(6V and 12V) are in translucent plastic containers made of styrenacrylnitril (SAN)amaterialwhichisextraordinaryresistant to chemical influences and mechanical damageThe stationary batteries of the type OPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations

APPLICATIONStationary batteries of the OPzS type are intended for the supply of telecommunication facilities computers emergency lightning alarm control and monitoringsystemsinpowerplantsanddistributionstationsatrailwaystationsairports etcDuetotheirextremelylowself-discharg-ing they are suitable for plants supplied by solar cells

OPERATION MAINTENANCEIT IS RECOMMENDED THAT THE OPzS BATTERIES ARE INSTALLED IN THE SYSTEMS WHERE THEY ARE CONSTANTLY CONNECTED TO THE RECTIFIER The battery can be float-charged withvoltageof223to225Vcellor in case of rapid charging after dischargewithvoltageof235to240VcellRapid charging usually lasts another 3-5hoursafterthevoltagehasalreadyreached235to240VcellAfterthatanautomaticswitchoverto the constant maintaining voltage of223to225VcelltakesplaceBattery maintenance is reduced to amimimumandrequiredonlyfrom time to timeAt normal operation only some destilledwaterhastobeaddedonce in a 2-3 year period and if necessary the surface of cells has to be cleaned All stated voltage values are valid for the temperature range from15to25degreesCOutofthisrange the corrections given by the battery producer are necessary

FOR DETAIL INFORMATION PLEASE CHECK OUR OPERATION MANUAL

ORDERS

kind of consuming device (telephone plant DC-AC converter emergency lightning etc) operating energy of the consumer (kWkVAcosΦ) minimumandmaximumallowable rated voltage at consuming device (V) time diagram of a consumer loadandtherequiredtime autonomy (reserve) expected voltage drop in the supply lines surrounding temperature in the battery room (average minimum maximum)

type of rectifier its characteristics regulating point I (A) or U (V) respec- tively float voltage (V) (direct voltage ofrapid-chargingcurrentImax(A) float charging voltage) outline or dimensions of a battery room type of installation(weldedbolted onwoodenormetalracksincaseon earthquake-proofracks) battery maintenance accessories (areometers thermometers jug ) battery typefilledupwith electrolyte and electrically charged or dry-charge battery

PLANE AND CLEAN SURFACE OF PLASTIC PART IN COMBINATION WITH RUBBER SEALING RING ENSURES PERFECT SEAL LONG PLASTIC INJECTED PART ALLOWS POLE GROWTH AND MOVING UPWARDS BY THE GROWTH OF POSITIVE PLATE SUCH CONSTRUCTION ENSURES TIGHT POLE BUSHING WITHOUT ANY CORROSION OR DETERIORATION DURING BATTERY LIFE

NEW TYPE OF POLE FOR STATIONARY APPLICATIONS HAS A SPECIAL DESIGN WITH EMBRACED INJECTED PLASTIC AROUND PRE-MACHINED LEAD PART IN THE SEALING AREA

IMPROVED DESIGNFOR BOLTEDVERSIONTERMINAL POST

TERMINAL POSTBOLTED VERSION

TERMINAL POSTWELDED VERSION

CONSTRUCTION The positive armored plate is of a tubu-lartypewhichmeansthattheactivesubstance (PbO2) is contained in special gauntletmadeofpolyesterfibresandhardened by an impregnation com-pound Such construction prevents es-caping of an active substance during the operation and ensures a long life timeThe grids of a positive and a negativeplatearemadeofspeciallowpercentage(lessthan2)antimonyalloywithaddi-tion agents for improvement of crystalline structure of castingNegative plates are pasted-type plateswithspecialalloysmaintainingporosity of an active substance during the operation As an electrolyte a diluted sulphuric acid (H2SO4)withadensityof124plusmn001kglat20degreesCandatamaximumpermittedlevelisusedSepara-tors separating the positive plates from the negative ones are made of micropo-rousplasticmaterialwithalowelectricresistanceThe cell containers are made of transpa-rentSANwhilelidofnontransparentSANorABSmaterial(SANforblocksABsfor2V cells) In a special process the lids are tightlysealed to the container The terminalplugsaresealedwithrubbersealsThisprevents any escape of electrolyte from the cellsDue to the transparent containers theelectrolyte level is clearly visible themaximumandminimumlevelsaremarkedonaself-adhesiveacid-prooflabel on a container side

Acellplugsealswell(ceramicfilter)andpreventsleakageofanysulphuricacidvapourshoweveritletsthroughhydrogenandoxygen

TWO VERSIONS OF BATTERIES ARE BEING MANUFACTURED DRY-CHARGE VERSION abatteryhastobefilledupwith an electrolyte and supplementary charged before use The plates are already formed and in a special process protected againstoxidation Theycanbestoredwithoutproblems ELECTROLYTE-CHARGE battery can be installed immediately becauseitisalreadyfilledupwith electrolyte and electrically charged aswellThecapacitytesthasalready been performed by the producer

TAB OPzS

CONNECTIONS DIMENSIONS

Number ofpositive plate

Armored OPzS plates

Capacity at 10-hour

discharging

Electrolyte density 124 plusmn 001kgl at 20 degC

All measures and weights are within standard production tolerances Electrical values are approximative Technical modifications are reserved without prior notice

12V 2 OPzS 100Rated

voltageNumber of

positive plate

Armored OPzS plates

Capacity at 10-hour

discharging

H

L L

H

W108

Electrolyte density 124 plusmn 001kgl at 20 degC

All measures and weights are within standard production tolerances Electrical values are approximative Technical modifications are reserved without prior notice

DESIGNOPzS cells (block)POSITIVE ELECTRODE Tubular plate with low antimony alloy (lt2 )NEGATIVE ELECTRODE Flat with long life expander active material SEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 124 kgl at 20 degCCONTAINER High impact transparent SANLID ABS (SAN) in grey color BLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-poleCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mm2 (35 50 or 70 mm2)KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGOPzS cells (block)IU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 223 Vcell plusmn 1 between 10 degC and 30 degC ∆U∆T=-0004VK below 10 degC or above 30 degC in the monthly averageBOOST CHARGE U = 235 to 240 Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSOPzS cells (block)REFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEOPzS cells (block)EVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA OPzS cells (block)DESIGN LIFE Up to 20 years (18 years) at 20 degCWATER REFILLING INTERVAL More than 2 years at 20 degCIEC 896-1 CYCLES 1500 (1200) SELF-DISCHARGE Approx 2 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 1TESTS ACCORDING IEC 896-1SAFETY STANDARDS VDE0510part2and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

TAB OPzS BLOCKS TAB OPzS CELLS

TAB OPzS STATIONARY BLOCKS (CELLS) ARE PRODUCED IN THE CONVENTIONAL LEAD-ACID TECHNOLOGY

Stationary batteries of the OPzS type are intended for the supply of telecommunication facilities computers emergency lightning alarm control and monitoring systems in power plants and distribution stations at railway stations airports etc

Uf (Vcell) 180 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 5 3 1 Ri Isc L W H Dry Wet

Type Ah Ah Ah Ah mΩ A mm mm mm kg kg12V 1 OPzS 50 51 409 380 284 200 613 272 205 392 26 3912V 2 OPzS 100 103 818 757 567 93 1290 272 205 392 38 5012V 3 OPzS 150 154 1226 1137 851 69 1739 380 205 392 53 696V 4 OPzS 200 204 1670 1493 1152 22 2703 272 205 392 36 476V 5 OPzS 250 255 2086 1866 1436 19 3175 380 205 392 44 616V 6 OPzS 300 307 2505 2237 1720 16 3846 380 205 392 52 68

Uf (Vcell) 180 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 5 3 1 Ri Isc L W H Dry Wet Poles

Type Ah Ah Ah Ah mΩ A mm mm mm kg kg Nr2 OPzS 100 111 97 85 62 148 1350 103 206 420 87 137 23 OPzS 150 160 142 122 89 108 1845 103 206 420 110 160 24 OPzS 200 215 187 163 119 084 2376 103 206 420 130 180 25 OPzS 250 268 232 204 149 069 2887 124 206 420 160 220 26 OPzS 300 321 277 242 177 058 3438 145 206 420 180 260 25 OPzS 350 393 336 290 212 064 3137 124 206 536 200 290 26 OPzS 420 470 403 348 254 055 3641 145 206 536 240 340 27 OPzS 490 550 470 406 296 048 4169 166 206 536 280 390 26 OPzS 600 685 582 510 372 045 4466 145 206 711 350 500 27 OPzS 700 798 681 598 436 038 5280 210 191 711 420 620 48 OPzS 800 912 778 683 499 033 6035 210 191 711 460 650 49 OPzS 900 1025 875 767 560 029 6948 210 233 711 530 770 410 OPzS 1000 1140 972 852 622 026 7720 210 233 711 570 800 412 OPzS 1200 1365 1165 1020 745 023 8814 210 275 711 660 930 412 OPzS 1500 1645 1410 1220 890 023 8605 210 275 861 880 1190 414 OPzS 1750 1910 1640 1420 1035 019 10536 212 397 837 1050 1520 615 OPzS 1875 2050 1760 1520 1110 018 11289 212 397 837 1100 1560 616 OPzS 2000 2185 1875 1625 1185 017 12042 212 397 837 1150 1600 618 OPzS 2250 2455 2105 1825 1335 015 13506 212 487 837 1340 1920 820 OPzS 2500 2730 2340 2030 1480 013 15007 212 487 837 1450 2000 822 OPzS 2750 3000 2575 2230 1625 013 15941 212 576 837 1590 2320 824 OPzS 3000 3270 2805 2430 1775 012 17390 212 576 837 1700 2400 8

3 OPzS 150

Max

Min

Electrolyte density 124 plusmn 001kgl at 20 degC

All measures and weights are within standard production tolerances Electrical values are approximative Technical modifications are reserved without prior notice

DESIGNPOSITIVE ELECTRODE Robust-grid plate with circular bars in a corrosion-resistant PbSe alloy lt 2 SbNEGATIVE ELECTRODE Flat plate with long life expander and low antimony alloy SEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 124 kglCONTAINER High impact transparent SANLID SAN in dark grey colourBLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs or optional ceramic funnel plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-polePOLE M10 brass insertCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mmsup2 KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 223 Vcell plusmn 1 between 10degC and 55degC dUdT = -0004 mVK below 10 degC in the monthly averageBOOST CHARGE U = 235 to 240Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA

OPERATIONAL LIFE Up to 15 years at 20 degC Up to 75 years at 30 degC Up to 4 years at 40 degCWATER REFILLING INTERVAL More than 3 years at 20 degCIEC 896-1 CYCLES 1000SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 3TESTS ACCORDING IEC 896-1APPLICABLE STANDARDS VDE 0510 part 2 and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

6V 7 OGi 175Rated

voltageNumber of

positive plate

Robust OGi plates

Capacity at 10-hour

discharging

W

L

L

H

W108

TAB OGi BLOCK BATTERIES ARE ROBUST VENTED LEAD-ACID BATTERIES DESIGNED FOR INDUSTRIAL APPLICATIONS IN POWER SUPPLY WITH HIGH SAFETY REQUIREMENTS

TAB OGi block batteries can be used for both long duration discharge (10 hours) and short duration discharge (few minutes) The main areas of application are DC power supply systems in power stations UPS systems industrial systems and emergency power supply systems They can also be used for engine starting and PV power systems

CONNECTIONS DIMENSIONS

TAB OGi BATTERIES

Max

Min

Uf (Vcell) 180 175 175 170 165 165 160 IEC 896-1 Dimensions Weight Discharging time (h) 10 5 3 1 12 16 112 Ri Isc L W H Dry Wet

Type Ah Ah Ah Ah Ah Ah Ah mΩ (kA) mm mm mm kg kg12V 1 OGi 25 290 255 225 168 143 92 67 1679 072 272 205 375 234 35012V 2 OGi 50 550 495 447 328 280 180 131 881 141 272 205 375 303 41212V 3 OGi 75 800 745 675 496 422 273 198 594 211 272 205 375 366 47012V 4 OGi 100 1050 985 894 657 561 361 261 446 281 272 205 375 441 54112V 5 OGi 125 1350 1230 1113 816 690 443 317 357 352 380 205 375 550 68912V 6 OGi 150 1650 1485 1338 982 825 527 371 297 422 380 205 375 618 7536V 7 OGi 175 1872 1673 1513 1107 912 569 396 127 493 272 205 375 359 4666V 8 OGi 200 2280 1975 1788 1300 1080 673 468 111 563 272 205 375 394 4986V 9 OGi 225 2540 2215 2007 1458 1215 755 526 099 636 380 205 375 480 6326V 10 OGi 250 2700 2470 2235 1617 1330 805 553 089 704 380 205 375 512 6626V 11 OGi 275 3040 2715 2451 1776 1460 885 607 081 778 380 205 375 535 6836V 12 OGi 300 3200 2960 2682 1944 1595 965 663 074 844 380 205 375 564 7082V 3 OGi 75 800 745 675 496 422 273 198 099 192 103 206 420 65 992V 4 OGi 100 1050 985 894 657 561 361 261 074 252 103 206 420 77 1112V 5 OGi 125 1350 1230 1113 816 690 443 317 060 324 103 206 420 90 1262V 6 OGi 150 1650 1485 1338 982 825 527 371 050 396 103 206 420 107 1442V 7 OGi 175 1872 1673 1513 1107 912 569 396 042 449 103 206 420 117 1532V 8 OGi 200 2280 1975 1788 1300 1080 673 468 037 547 103 206 420 136 1732V 9 OGi 225 2540 2215 2007 1458 1215 755 526 033 610 103 206 420 154 1922V 10 OGi 250 2700 2470 2235 1617 1330 805 553 030 665 124 206 420 172 2132V 11 OGi 275 3040 2715 2451 1776 1460 885 607 027 755 145 206 420 190 2282V 12 OGi 300 3200 2960 2682 1944 1595 965 663 025 768 145 206 420 218 2512V 13 OGi 325 3467 3207 2906 2106 1728 1045 718 023 832 145 206 420 238 2762V 14 OGi 350 3733 3453 3129 2268 1861 1126 774 021 896 145 206 420 259 3002V 24 OGi 600 6840 5925 5364 3900 3240 2019 1404 013 1642 205 272 392 394 498

CONNECTIONS DIMENSIONS

TAB UPS BATTERIES ARE ROBUST AND FOR HIGH DISCHARGE - PERFORMANCES OPTIMISEDLEAD-ACID BATTERIES

The main application for TAB UPS are Uninterruptable Power Supplies (UPS)in the size of 50 to 250 kVA The battery is perfectly suited to start diesel engines for the auxiliary power supply

DESIGNPOSITIVE ELECTRODE Robust-plate with circular bars in a corrosion-resistant PbSe alloy lt 2 SbNEGATIVE ELECTRODE Flat plate with long life expander and low antimony alloySEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 128 kglCONTAINER High impact transparent SANLID SAN in dark grey colourBLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs or optional ceramic funnel plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-polePOLE M10 brass insertCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mmsup2 KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 225 to 227 Vcell plusmn 1 between 10 degC and 55 degC dUdT = -0004 mVdegK below 10 degC in the monthly averageBOOST CHARGE U = 235 to 240 Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA OPERATIONAL LIFE Up to 12 years at 20 degC Up to 6 years at 30 degC Up to 3 years at 40 degCWATER REFILLING INTERVAL More than 3 years at 20 degCIEC 896-1 CYCLES 800SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 3TESTS ACCORDING IEC 896-1APPLICABLE STANDARDS VDE 0510 part 2 and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

6V 7 UPS 700Rated

voltageNumber of

positive plate

Robust platesfor UPS

Power _ Wattcell10 min _ Uf=163 Vcell

LL

H

WWM

ax

Min

100W is the averaged power per plate at the 10 min rate Uf = 163Vcell

Electrolyte density 128 plusmn 001 kgl at 20 degC

All measures and weights are within standard production tolerances

Electrical values are approximative Technical modifications are reserved

without prior notice

TAB UPS BATTERIES

Uf (Vcell) 180 175 170 165 163 160 IEC 896-1 Dimensions Weight Discharging time (min) 60 30 15 10 5 Ri Isc L W H Dry Wet

Type C10(Ah) Wcell Wcell Wcell Wcell Wcell mΩ (kA) mm mm mm kg kg12V 1 UPS 100 41 42 64 92 120 181 1680 073 272 205 375 234 35412V 2 UPS 200 59 73 112 169 218 323 840 146 272 205 375 303 41612V 3 UPS 300 86 103 162 246 313 465 560 22 272 205 375 366 47312V 4 UPS 400 114 135 210 322 410 606 420 293 272 205 375 441 54512V 5 UPS 500 147 169 264 412 520 755 336 366 380 205 375 550 69412V 6 UPS 600 179 204 327 500 629 895 280 439 380 205 375 618 7586V 7 UPS 700 206 237 384 588 737 1040 120 513 272 205 375 359 4706V 8 UPS 800 247 272 440 676 848 1187 105 586 272 205 375 394 5026V 9 UPS 900 271 306 492 742 913 1294 093 659 380 205 375 480 6386V 10 UPS 1000 293 342 558 812 1014 1403 084 732 380 205 375 512 6676V 11 UPS 1100 325 381 592 879 1098 1509 076 805 380 205 375 535 6886V 12 UPS 1200 347 418 640 946 1178 1613 070 879 380 205 375 564 7152V 24 UPS 2400 742 816 1321 2027 2544 3562 013 1758 205 272 375 394 5022V 30 UPS 3000 879 1027 1674 2437 3042 4209 010 219 205 380 375 512 6672V 36 UPS 3600 1041 1253 1920 2837 3535 4838 008 263 205 380 375 554 715

The batteries are distinguished for HIGHCAPACITY LONGLIFETIME REDUCEDMAINTENANCE LOWSELF-DISCHARGING QUICKANDSIMPLEACID LEVEL CONTROL ECONOMICALWATERCONSUMPTION APPROPRIATEDIMENSIONS AND WEIGHT THELOWESTANDCONSTANT MAINTENANCE CURRENTThe stationary batteries of the type TOPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations Individual cells (2V) are made from translucent PP containersThe stationary batteries of the type OPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations

APPLICATIONStationary batteries of the TOPzS type are specially designed for solar systemsDuetotheirextremelylowself-discharging and tubular positive plates they are suitable for off-grid solar systems

CONSTRUCTIONThe positive armored plate is of a tubulartypewhichmeansthattheactivesubstance (PbO2) is contained in special gauntletmadeofpolyesterfibresandhardened by an impregnation compound Such construction prevents escaping of an active substance during the operation and ensures a long life timeThe grids of a positive and a negativeplatearemadeofspeciallowpercentage(lessthan2)antimonyalloywithaddi-tion agents for improvement of crystalline structure of castingNegative plates are pasted-type plateswithspecialalloysmaintainingporosity of an active substance during the operationAs an electrolyte a diluted sulphuric acid (H2SO4)withadensityof124plusmn001kglat20degreesCandatamaximumpermitted level is usedSeparators separating the positive plates from the negative ones are made of microporousplasticmaterialwithalowelectric resistanceIn a special process the lids are tightly sealedwiththermoweldingtothecon-tainerTheterminalplugsaresealedwithrubber seals This prevents any escape of electrolyte from the cellsDue to the transparent containers theelectrolyte level is clearly visible themaximumandminimumlevelsaremarkedonaself-adhesiveacid-prooflabel on a container side

TWO VERSIONS OF BATTERIES ARE BEING MANUFACTURED DRY-CHARGE VERSION abatteryhastobefilledupwith an electrolyte and supplementary charged before use The plates are already formed and in a special pro- cessprotectedagainstoxidationThey canbestoredwithoutproblems ELECTROLYTE-CHARGE battery can be installed immediately becauseitisalreadyfilledupwith electrolyte and electrically charged aswellThecapacitytesthasalready been performed by the producer

H

L

OPERATION-MAINTENANCEFor more detail information please check our operation manual

TRANSPORTBatteries are not subject to ADR (road transport)

DESIGNPOSITIVE ELECTRODE Tubular positive plate with low antimony alloy (lt2 )NEGATIVE ELECTRODE Flat plate with long life expanderSEPARATION Microporous separatorELECTROLYTE Sulphuric acid of 124 kglCONTAINER Transparent PPLID PP in green colourPOLE SEALING 100 gas-and electrolyte-tight rubber sealPOLE M10 brass insertCONNECTOR flexible insulated copper cable with cross-section of 35 50 or 70 mm2

POLE SCREW M10 steel insulated

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT VOLTAGE U=223Vcell plusmn 1 BOOST CHARGE U=235to 240 Vcell

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degC at C10 (180 Vcell) and 25 degC at C100 (185 Vcell)INITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATAOPERATIONAL LIFE Up to 15 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427SAFETY STANDARD VENTILATION ENIEC62485-2

Electrolyte density 124 plusmn 001kgl at 20 degC Uf=185Vcell at 25 degC

LOW MAINTENANCE TAB TOPzS VENTED STATIONARY BATTERIES

CONNECTIONS DIMENSIONS

TAB TOPzS BATTERIES

W W

Uf (Vcell) 180 180 185 IEC 896-1 Dimensions Weight Capacity C10 C20 C100 Ri Isc L W H Dry Wet

Type Ah Ah Ah mΩ A mm mm mm kg kg3 TOPzS 265 265 289 345 056 3721 198 83 472 124 1844 TOPzS 353 353 384 460 046 4514 198 101 472 160 2335 TOPzS 442 442 481 575 038 5461 198 119 472 202 2904 TOPzS 500 499 545 650 035 6005 198 101 720 243 3525 TOPzS 625 624 681 815 028 7448 198 119 720 303 4326 TOPzS750 749 817 975 030 6991 198 137 720 380 5357 TOPzS 875 874 953 1140 026 7888 198 173 720 440 6428 TOPzS 1000 999 1089 1300 024 8848 198 191 720 502 725

FEATURES SAFE VERSATILE RELIABLE MINIMALGASSING DEEPDISCHARGE RESISTANCE

TAB Tovarna Akumulatorskih Baterij dd Polena 6 SI-Mežica 2392 Slovenia | infotabsi | +386 (0)2 8702 300 | wwwtabsi

According to DIN 40742 IEC 60896-2

TAB OPzV range of valve regulated lead acid stationarybatteriescombinethebenefitsof recombination technology (i e virtually nomaintenanceduetoverylowgasemissions)plus the advantages of conventional vented batterieswithpositivetubularplates(ielonglifeandexcellentcyclingcapability)

TAB OPzV VALVE REGULATED LEADACID BATTERIES ARE THE IDEAL ENERGY SOURCE FOR MANY DIFFERENT STANDBY APPLICATIONS

DESIGNTUBULAR POSITIVE PLATES Special grid construction pressure cast from antimony free alloy with highly porous gauntlets that retain the active materialPASTED NEGATIVE PLATES Service lives consistent with the positive platesELECTROLYTE Gel structureSEPARATORS Extremely high porosity and low internal resistanceCONTAINERS AND LIDS Made of plastic (ABS) material Also available in ABS flame retardant material as an option (according to IEC 707 FV0)TERMINALS Female treated terminal (M10) perfect contact and low resistance with flexible cable connectorsPOST SEALS Prevents electrolyte leakage and terminal corrosionCONNECTORS Flexible fully insulated cable con nectors screwed (with 20 plusmn1 Nm) to the termi- nal with an insulated screw having a probe hole on the top for electrical measurementONE WAY RELIEF VALVE Opens at low pressure

INSTALLATIONCELLS ARE NORMALLY INSTALLED IN AN UPRIGHT POSITION ON STEEL STANDS

CHARGINGFLOAT VOLTAGE Standby use 225 VcellBOOST RECHARGE Maximum voltage of 235 - 240 Vcell with a maximum current of 025 C10 (A)

OPERATIONAL DATAOPERATIONAL LIFE Up to 20 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 2 per month at 20 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427

11-0

1-20

20 (a

telje

jkreg

)

H1W H2

TAB OPzV BATTERIES

L

Uf (Vcell) 18 18 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 10 5 3 1 Ri Isc L W H1H2 Wet Poles

Type NomCap(Ah) Capacity(Ah)at20degC mΩ A mm mm mm kg Nr4 OPzV 200 200 204 172 150 110 122 1660 103 206 354380 19 25 OPzV 250 250 255 215 188 138 098 2080 124 206 354380 23 26 OPzV 300 300 306 258 225 166 085 2490 145 206 354380 28 25 OPzV 350 350 357 305 263 190 075 2770 124 206 471496 31 26 OPzV 420 420 429 365 315 226 061 3350 145 206 471496 36 27 OPzV 490 490 500 425 370 264 052 3900 166 206 471496 41 26 OPzV 600 600 612 520 450 322 051 4060 145 206 643668 49 28 OPzV 800 800 816 700 600 441 038 5390 210 191 643668 65 410 OPzV 1000 1000 1020 870 750 546 030 6760 210 233 643668 80 412 OPzV 1200 1200 1250 1045 900 653 026 8120 210 275 643668 93 412 OPzV 1500 1500 1530 1330 1116 774 023 8810 210 275 796821 115 416 OPsV 2000 2000 2040 1770 1488 1032 017 11510 214 399 771796 155 620 OPzV 2500 2500 2560 2160 1860 1289 014 14400 214 482 769794 200 824 OPzV 3000 3000 3060 2550 2232 1547 012 17260 214 576 771796 235 8

Page 2: TAB STATIONARY BATTERIES€¦ · tab stationary batteries tab polar tab magic tab polar truck tab magic truck tab efb stop & go tab agm stop & go english opzs ogi ups topzs opzv

IN CASE OF PROBLEMS WITH ORDERING WE WILL BE GLAD TO ADVISE AND ASSIST YOU IN THE SELECTION OF THE SUITABLE TYPE OF BATTERY

Low maintenance TAB OPzS vented stationary batteries6V 4 OPzS 200

Rated voltage

Max

Min

H

W

L

Number ofpositive plate

Type of plates

Capacity at 10-hour

discharging

TECHNICAL DATA AND DIMENSIONS IN ORDER THAT THE BATTERIES WOULD MEET ALL YOUR DEMANDS WE

KINDLY ASK YOU TO ENCLOSE THE FOLLOWING DATA WITH YOUR ORDER

LET US LEAD YOU INTO THE WORLD OF EVERLASTING ENERGY AND INTRODUCE YOU WITH OPzS STATIONARY BLOCKS AND CELLS PRODUCED IN THE CONVENTIONAL LEAD-ACID TECHNOLOGY

The batteries are distinguished for highcapacity longlifetime reducedmaintenance lowself-discharging quickandsimpleacid level control economicalwater consumption appropriatedimensions andweight thelowestandconstant maintenance currentTheindividualcells(2V)andblocks(6V and 12V) are in translucent plastic containers made of styrenacrylnitril (SAN)amaterialwhichisextraordinaryresistant to chemical influences and mechanical damageThe stationary batteries of the type OPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations

APPLICATIONStationary batteries of the OPzS type are intended for the supply of telecommunication facilities computers emergency lightning alarm control and monitoringsystemsinpowerplantsanddistributionstationsatrailwaystationsairports etcDuetotheirextremelylowself-discharg-ing they are suitable for plants supplied by solar cells

OPERATION MAINTENANCEIT IS RECOMMENDED THAT THE OPzS BATTERIES ARE INSTALLED IN THE SYSTEMS WHERE THEY ARE CONSTANTLY CONNECTED TO THE RECTIFIER The battery can be float-charged withvoltageof223to225Vcellor in case of rapid charging after dischargewithvoltageof235to240VcellRapid charging usually lasts another 3-5hoursafterthevoltagehasalreadyreached235to240VcellAfterthatanautomaticswitchoverto the constant maintaining voltage of223to225VcelltakesplaceBattery maintenance is reduced to amimimumandrequiredonlyfrom time to timeAt normal operation only some destilledwaterhastobeaddedonce in a 2-3 year period and if necessary the surface of cells has to be cleaned All stated voltage values are valid for the temperature range from15to25degreesCOutofthisrange the corrections given by the battery producer are necessary

FOR DETAIL INFORMATION PLEASE CHECK OUR OPERATION MANUAL

ORDERS

kind of consuming device (telephone plant DC-AC converter emergency lightning etc) operating energy of the consumer (kWkVAcosΦ) minimumandmaximumallowable rated voltage at consuming device (V) time diagram of a consumer loadandtherequiredtime autonomy (reserve) expected voltage drop in the supply lines surrounding temperature in the battery room (average minimum maximum)

type of rectifier its characteristics regulating point I (A) or U (V) respec- tively float voltage (V) (direct voltage ofrapid-chargingcurrentImax(A) float charging voltage) outline or dimensions of a battery room type of installation(weldedbolted onwoodenormetalracksincaseon earthquake-proofracks) battery maintenance accessories (areometers thermometers jug ) battery typefilledupwith electrolyte and electrically charged or dry-charge battery

PLANE AND CLEAN SURFACE OF PLASTIC PART IN COMBINATION WITH RUBBER SEALING RING ENSURES PERFECT SEAL LONG PLASTIC INJECTED PART ALLOWS POLE GROWTH AND MOVING UPWARDS BY THE GROWTH OF POSITIVE PLATE SUCH CONSTRUCTION ENSURES TIGHT POLE BUSHING WITHOUT ANY CORROSION OR DETERIORATION DURING BATTERY LIFE

NEW TYPE OF POLE FOR STATIONARY APPLICATIONS HAS A SPECIAL DESIGN WITH EMBRACED INJECTED PLASTIC AROUND PRE-MACHINED LEAD PART IN THE SEALING AREA

IMPROVED DESIGNFOR BOLTEDVERSIONTERMINAL POST

TERMINAL POSTBOLTED VERSION

TERMINAL POSTWELDED VERSION

CONSTRUCTION The positive armored plate is of a tubu-lartypewhichmeansthattheactivesubstance (PbO2) is contained in special gauntletmadeofpolyesterfibresandhardened by an impregnation com-pound Such construction prevents es-caping of an active substance during the operation and ensures a long life timeThe grids of a positive and a negativeplatearemadeofspeciallowpercentage(lessthan2)antimonyalloywithaddi-tion agents for improvement of crystalline structure of castingNegative plates are pasted-type plateswithspecialalloysmaintainingporosity of an active substance during the operation As an electrolyte a diluted sulphuric acid (H2SO4)withadensityof124plusmn001kglat20degreesCandatamaximumpermittedlevelisusedSepara-tors separating the positive plates from the negative ones are made of micropo-rousplasticmaterialwithalowelectricresistanceThe cell containers are made of transpa-rentSANwhilelidofnontransparentSANorABSmaterial(SANforblocksABsfor2V cells) In a special process the lids are tightlysealed to the container The terminalplugsaresealedwithrubbersealsThisprevents any escape of electrolyte from the cellsDue to the transparent containers theelectrolyte level is clearly visible themaximumandminimumlevelsaremarkedonaself-adhesiveacid-prooflabel on a container side

Acellplugsealswell(ceramicfilter)andpreventsleakageofanysulphuricacidvapourshoweveritletsthroughhydrogenandoxygen

TWO VERSIONS OF BATTERIES ARE BEING MANUFACTURED DRY-CHARGE VERSION abatteryhastobefilledupwith an electrolyte and supplementary charged before use The plates are already formed and in a special process protected againstoxidation Theycanbestoredwithoutproblems ELECTROLYTE-CHARGE battery can be installed immediately becauseitisalreadyfilledupwith electrolyte and electrically charged aswellThecapacitytesthasalready been performed by the producer

TAB OPzS

CONNECTIONS DIMENSIONS

Number ofpositive plate

Armored OPzS plates

Capacity at 10-hour

discharging

Electrolyte density 124 plusmn 001kgl at 20 degC

All measures and weights are within standard production tolerances Electrical values are approximative Technical modifications are reserved without prior notice

12V 2 OPzS 100Rated

voltageNumber of

positive plate

Armored OPzS plates

Capacity at 10-hour

discharging

H

L L

H

W108

Electrolyte density 124 plusmn 001kgl at 20 degC

All measures and weights are within standard production tolerances Electrical values are approximative Technical modifications are reserved without prior notice

DESIGNOPzS cells (block)POSITIVE ELECTRODE Tubular plate with low antimony alloy (lt2 )NEGATIVE ELECTRODE Flat with long life expander active material SEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 124 kgl at 20 degCCONTAINER High impact transparent SANLID ABS (SAN) in grey color BLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-poleCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mm2 (35 50 or 70 mm2)KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGOPzS cells (block)IU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 223 Vcell plusmn 1 between 10 degC and 30 degC ∆U∆T=-0004VK below 10 degC or above 30 degC in the monthly averageBOOST CHARGE U = 235 to 240 Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSOPzS cells (block)REFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEOPzS cells (block)EVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA OPzS cells (block)DESIGN LIFE Up to 20 years (18 years) at 20 degCWATER REFILLING INTERVAL More than 2 years at 20 degCIEC 896-1 CYCLES 1500 (1200) SELF-DISCHARGE Approx 2 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 1TESTS ACCORDING IEC 896-1SAFETY STANDARDS VDE0510part2and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

TAB OPzS BLOCKS TAB OPzS CELLS

TAB OPzS STATIONARY BLOCKS (CELLS) ARE PRODUCED IN THE CONVENTIONAL LEAD-ACID TECHNOLOGY

Stationary batteries of the OPzS type are intended for the supply of telecommunication facilities computers emergency lightning alarm control and monitoring systems in power plants and distribution stations at railway stations airports etc

Uf (Vcell) 180 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 5 3 1 Ri Isc L W H Dry Wet

Type Ah Ah Ah Ah mΩ A mm mm mm kg kg12V 1 OPzS 50 51 409 380 284 200 613 272 205 392 26 3912V 2 OPzS 100 103 818 757 567 93 1290 272 205 392 38 5012V 3 OPzS 150 154 1226 1137 851 69 1739 380 205 392 53 696V 4 OPzS 200 204 1670 1493 1152 22 2703 272 205 392 36 476V 5 OPzS 250 255 2086 1866 1436 19 3175 380 205 392 44 616V 6 OPzS 300 307 2505 2237 1720 16 3846 380 205 392 52 68

Uf (Vcell) 180 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 5 3 1 Ri Isc L W H Dry Wet Poles

Type Ah Ah Ah Ah mΩ A mm mm mm kg kg Nr2 OPzS 100 111 97 85 62 148 1350 103 206 420 87 137 23 OPzS 150 160 142 122 89 108 1845 103 206 420 110 160 24 OPzS 200 215 187 163 119 084 2376 103 206 420 130 180 25 OPzS 250 268 232 204 149 069 2887 124 206 420 160 220 26 OPzS 300 321 277 242 177 058 3438 145 206 420 180 260 25 OPzS 350 393 336 290 212 064 3137 124 206 536 200 290 26 OPzS 420 470 403 348 254 055 3641 145 206 536 240 340 27 OPzS 490 550 470 406 296 048 4169 166 206 536 280 390 26 OPzS 600 685 582 510 372 045 4466 145 206 711 350 500 27 OPzS 700 798 681 598 436 038 5280 210 191 711 420 620 48 OPzS 800 912 778 683 499 033 6035 210 191 711 460 650 49 OPzS 900 1025 875 767 560 029 6948 210 233 711 530 770 410 OPzS 1000 1140 972 852 622 026 7720 210 233 711 570 800 412 OPzS 1200 1365 1165 1020 745 023 8814 210 275 711 660 930 412 OPzS 1500 1645 1410 1220 890 023 8605 210 275 861 880 1190 414 OPzS 1750 1910 1640 1420 1035 019 10536 212 397 837 1050 1520 615 OPzS 1875 2050 1760 1520 1110 018 11289 212 397 837 1100 1560 616 OPzS 2000 2185 1875 1625 1185 017 12042 212 397 837 1150 1600 618 OPzS 2250 2455 2105 1825 1335 015 13506 212 487 837 1340 1920 820 OPzS 2500 2730 2340 2030 1480 013 15007 212 487 837 1450 2000 822 OPzS 2750 3000 2575 2230 1625 013 15941 212 576 837 1590 2320 824 OPzS 3000 3270 2805 2430 1775 012 17390 212 576 837 1700 2400 8

3 OPzS 150

Max

Min

Electrolyte density 124 plusmn 001kgl at 20 degC

All measures and weights are within standard production tolerances Electrical values are approximative Technical modifications are reserved without prior notice

DESIGNPOSITIVE ELECTRODE Robust-grid plate with circular bars in a corrosion-resistant PbSe alloy lt 2 SbNEGATIVE ELECTRODE Flat plate with long life expander and low antimony alloy SEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 124 kglCONTAINER High impact transparent SANLID SAN in dark grey colourBLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs or optional ceramic funnel plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-polePOLE M10 brass insertCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mmsup2 KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 223 Vcell plusmn 1 between 10degC and 55degC dUdT = -0004 mVK below 10 degC in the monthly averageBOOST CHARGE U = 235 to 240Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA

OPERATIONAL LIFE Up to 15 years at 20 degC Up to 75 years at 30 degC Up to 4 years at 40 degCWATER REFILLING INTERVAL More than 3 years at 20 degCIEC 896-1 CYCLES 1000SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 3TESTS ACCORDING IEC 896-1APPLICABLE STANDARDS VDE 0510 part 2 and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

6V 7 OGi 175Rated

voltageNumber of

positive plate

Robust OGi plates

Capacity at 10-hour

discharging

W

L

L

H

W108

TAB OGi BLOCK BATTERIES ARE ROBUST VENTED LEAD-ACID BATTERIES DESIGNED FOR INDUSTRIAL APPLICATIONS IN POWER SUPPLY WITH HIGH SAFETY REQUIREMENTS

TAB OGi block batteries can be used for both long duration discharge (10 hours) and short duration discharge (few minutes) The main areas of application are DC power supply systems in power stations UPS systems industrial systems and emergency power supply systems They can also be used for engine starting and PV power systems

CONNECTIONS DIMENSIONS

TAB OGi BATTERIES

Max

Min

Uf (Vcell) 180 175 175 170 165 165 160 IEC 896-1 Dimensions Weight Discharging time (h) 10 5 3 1 12 16 112 Ri Isc L W H Dry Wet

Type Ah Ah Ah Ah Ah Ah Ah mΩ (kA) mm mm mm kg kg12V 1 OGi 25 290 255 225 168 143 92 67 1679 072 272 205 375 234 35012V 2 OGi 50 550 495 447 328 280 180 131 881 141 272 205 375 303 41212V 3 OGi 75 800 745 675 496 422 273 198 594 211 272 205 375 366 47012V 4 OGi 100 1050 985 894 657 561 361 261 446 281 272 205 375 441 54112V 5 OGi 125 1350 1230 1113 816 690 443 317 357 352 380 205 375 550 68912V 6 OGi 150 1650 1485 1338 982 825 527 371 297 422 380 205 375 618 7536V 7 OGi 175 1872 1673 1513 1107 912 569 396 127 493 272 205 375 359 4666V 8 OGi 200 2280 1975 1788 1300 1080 673 468 111 563 272 205 375 394 4986V 9 OGi 225 2540 2215 2007 1458 1215 755 526 099 636 380 205 375 480 6326V 10 OGi 250 2700 2470 2235 1617 1330 805 553 089 704 380 205 375 512 6626V 11 OGi 275 3040 2715 2451 1776 1460 885 607 081 778 380 205 375 535 6836V 12 OGi 300 3200 2960 2682 1944 1595 965 663 074 844 380 205 375 564 7082V 3 OGi 75 800 745 675 496 422 273 198 099 192 103 206 420 65 992V 4 OGi 100 1050 985 894 657 561 361 261 074 252 103 206 420 77 1112V 5 OGi 125 1350 1230 1113 816 690 443 317 060 324 103 206 420 90 1262V 6 OGi 150 1650 1485 1338 982 825 527 371 050 396 103 206 420 107 1442V 7 OGi 175 1872 1673 1513 1107 912 569 396 042 449 103 206 420 117 1532V 8 OGi 200 2280 1975 1788 1300 1080 673 468 037 547 103 206 420 136 1732V 9 OGi 225 2540 2215 2007 1458 1215 755 526 033 610 103 206 420 154 1922V 10 OGi 250 2700 2470 2235 1617 1330 805 553 030 665 124 206 420 172 2132V 11 OGi 275 3040 2715 2451 1776 1460 885 607 027 755 145 206 420 190 2282V 12 OGi 300 3200 2960 2682 1944 1595 965 663 025 768 145 206 420 218 2512V 13 OGi 325 3467 3207 2906 2106 1728 1045 718 023 832 145 206 420 238 2762V 14 OGi 350 3733 3453 3129 2268 1861 1126 774 021 896 145 206 420 259 3002V 24 OGi 600 6840 5925 5364 3900 3240 2019 1404 013 1642 205 272 392 394 498

CONNECTIONS DIMENSIONS

TAB UPS BATTERIES ARE ROBUST AND FOR HIGH DISCHARGE - PERFORMANCES OPTIMISEDLEAD-ACID BATTERIES

The main application for TAB UPS are Uninterruptable Power Supplies (UPS)in the size of 50 to 250 kVA The battery is perfectly suited to start diesel engines for the auxiliary power supply

DESIGNPOSITIVE ELECTRODE Robust-plate with circular bars in a corrosion-resistant PbSe alloy lt 2 SbNEGATIVE ELECTRODE Flat plate with long life expander and low antimony alloySEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 128 kglCONTAINER High impact transparent SANLID SAN in dark grey colourBLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs or optional ceramic funnel plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-polePOLE M10 brass insertCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mmsup2 KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 225 to 227 Vcell plusmn 1 between 10 degC and 55 degC dUdT = -0004 mVdegK below 10 degC in the monthly averageBOOST CHARGE U = 235 to 240 Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA OPERATIONAL LIFE Up to 12 years at 20 degC Up to 6 years at 30 degC Up to 3 years at 40 degCWATER REFILLING INTERVAL More than 3 years at 20 degCIEC 896-1 CYCLES 800SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 3TESTS ACCORDING IEC 896-1APPLICABLE STANDARDS VDE 0510 part 2 and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

6V 7 UPS 700Rated

voltageNumber of

positive plate

Robust platesfor UPS

Power _ Wattcell10 min _ Uf=163 Vcell

LL

H

WWM

ax

Min

100W is the averaged power per plate at the 10 min rate Uf = 163Vcell

Electrolyte density 128 plusmn 001 kgl at 20 degC

All measures and weights are within standard production tolerances

Electrical values are approximative Technical modifications are reserved

without prior notice

TAB UPS BATTERIES

Uf (Vcell) 180 175 170 165 163 160 IEC 896-1 Dimensions Weight Discharging time (min) 60 30 15 10 5 Ri Isc L W H Dry Wet

Type C10(Ah) Wcell Wcell Wcell Wcell Wcell mΩ (kA) mm mm mm kg kg12V 1 UPS 100 41 42 64 92 120 181 1680 073 272 205 375 234 35412V 2 UPS 200 59 73 112 169 218 323 840 146 272 205 375 303 41612V 3 UPS 300 86 103 162 246 313 465 560 22 272 205 375 366 47312V 4 UPS 400 114 135 210 322 410 606 420 293 272 205 375 441 54512V 5 UPS 500 147 169 264 412 520 755 336 366 380 205 375 550 69412V 6 UPS 600 179 204 327 500 629 895 280 439 380 205 375 618 7586V 7 UPS 700 206 237 384 588 737 1040 120 513 272 205 375 359 4706V 8 UPS 800 247 272 440 676 848 1187 105 586 272 205 375 394 5026V 9 UPS 900 271 306 492 742 913 1294 093 659 380 205 375 480 6386V 10 UPS 1000 293 342 558 812 1014 1403 084 732 380 205 375 512 6676V 11 UPS 1100 325 381 592 879 1098 1509 076 805 380 205 375 535 6886V 12 UPS 1200 347 418 640 946 1178 1613 070 879 380 205 375 564 7152V 24 UPS 2400 742 816 1321 2027 2544 3562 013 1758 205 272 375 394 5022V 30 UPS 3000 879 1027 1674 2437 3042 4209 010 219 205 380 375 512 6672V 36 UPS 3600 1041 1253 1920 2837 3535 4838 008 263 205 380 375 554 715

The batteries are distinguished for HIGHCAPACITY LONGLIFETIME REDUCEDMAINTENANCE LOWSELF-DISCHARGING QUICKANDSIMPLEACID LEVEL CONTROL ECONOMICALWATERCONSUMPTION APPROPRIATEDIMENSIONS AND WEIGHT THELOWESTANDCONSTANT MAINTENANCE CURRENTThe stationary batteries of the type TOPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations Individual cells (2V) are made from translucent PP containersThe stationary batteries of the type OPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations

APPLICATIONStationary batteries of the TOPzS type are specially designed for solar systemsDuetotheirextremelylowself-discharging and tubular positive plates they are suitable for off-grid solar systems

CONSTRUCTIONThe positive armored plate is of a tubulartypewhichmeansthattheactivesubstance (PbO2) is contained in special gauntletmadeofpolyesterfibresandhardened by an impregnation compound Such construction prevents escaping of an active substance during the operation and ensures a long life timeThe grids of a positive and a negativeplatearemadeofspeciallowpercentage(lessthan2)antimonyalloywithaddi-tion agents for improvement of crystalline structure of castingNegative plates are pasted-type plateswithspecialalloysmaintainingporosity of an active substance during the operationAs an electrolyte a diluted sulphuric acid (H2SO4)withadensityof124plusmn001kglat20degreesCandatamaximumpermitted level is usedSeparators separating the positive plates from the negative ones are made of microporousplasticmaterialwithalowelectric resistanceIn a special process the lids are tightly sealedwiththermoweldingtothecon-tainerTheterminalplugsaresealedwithrubber seals This prevents any escape of electrolyte from the cellsDue to the transparent containers theelectrolyte level is clearly visible themaximumandminimumlevelsaremarkedonaself-adhesiveacid-prooflabel on a container side

TWO VERSIONS OF BATTERIES ARE BEING MANUFACTURED DRY-CHARGE VERSION abatteryhastobefilledupwith an electrolyte and supplementary charged before use The plates are already formed and in a special pro- cessprotectedagainstoxidationThey canbestoredwithoutproblems ELECTROLYTE-CHARGE battery can be installed immediately becauseitisalreadyfilledupwith electrolyte and electrically charged aswellThecapacitytesthasalready been performed by the producer

H

L

OPERATION-MAINTENANCEFor more detail information please check our operation manual

TRANSPORTBatteries are not subject to ADR (road transport)

DESIGNPOSITIVE ELECTRODE Tubular positive plate with low antimony alloy (lt2 )NEGATIVE ELECTRODE Flat plate with long life expanderSEPARATION Microporous separatorELECTROLYTE Sulphuric acid of 124 kglCONTAINER Transparent PPLID PP in green colourPOLE SEALING 100 gas-and electrolyte-tight rubber sealPOLE M10 brass insertCONNECTOR flexible insulated copper cable with cross-section of 35 50 or 70 mm2

POLE SCREW M10 steel insulated

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT VOLTAGE U=223Vcell plusmn 1 BOOST CHARGE U=235to 240 Vcell

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degC at C10 (180 Vcell) and 25 degC at C100 (185 Vcell)INITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATAOPERATIONAL LIFE Up to 15 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427SAFETY STANDARD VENTILATION ENIEC62485-2

Electrolyte density 124 plusmn 001kgl at 20 degC Uf=185Vcell at 25 degC

LOW MAINTENANCE TAB TOPzS VENTED STATIONARY BATTERIES

CONNECTIONS DIMENSIONS

TAB TOPzS BATTERIES

W W

Uf (Vcell) 180 180 185 IEC 896-1 Dimensions Weight Capacity C10 C20 C100 Ri Isc L W H Dry Wet

Type Ah Ah Ah mΩ A mm mm mm kg kg3 TOPzS 265 265 289 345 056 3721 198 83 472 124 1844 TOPzS 353 353 384 460 046 4514 198 101 472 160 2335 TOPzS 442 442 481 575 038 5461 198 119 472 202 2904 TOPzS 500 499 545 650 035 6005 198 101 720 243 3525 TOPzS 625 624 681 815 028 7448 198 119 720 303 4326 TOPzS750 749 817 975 030 6991 198 137 720 380 5357 TOPzS 875 874 953 1140 026 7888 198 173 720 440 6428 TOPzS 1000 999 1089 1300 024 8848 198 191 720 502 725

FEATURES SAFE VERSATILE RELIABLE MINIMALGASSING DEEPDISCHARGE RESISTANCE

TAB Tovarna Akumulatorskih Baterij dd Polena 6 SI-Mežica 2392 Slovenia | infotabsi | +386 (0)2 8702 300 | wwwtabsi

According to DIN 40742 IEC 60896-2

TAB OPzV range of valve regulated lead acid stationarybatteriescombinethebenefitsof recombination technology (i e virtually nomaintenanceduetoverylowgasemissions)plus the advantages of conventional vented batterieswithpositivetubularplates(ielonglifeandexcellentcyclingcapability)

TAB OPzV VALVE REGULATED LEADACID BATTERIES ARE THE IDEAL ENERGY SOURCE FOR MANY DIFFERENT STANDBY APPLICATIONS

DESIGNTUBULAR POSITIVE PLATES Special grid construction pressure cast from antimony free alloy with highly porous gauntlets that retain the active materialPASTED NEGATIVE PLATES Service lives consistent with the positive platesELECTROLYTE Gel structureSEPARATORS Extremely high porosity and low internal resistanceCONTAINERS AND LIDS Made of plastic (ABS) material Also available in ABS flame retardant material as an option (according to IEC 707 FV0)TERMINALS Female treated terminal (M10) perfect contact and low resistance with flexible cable connectorsPOST SEALS Prevents electrolyte leakage and terminal corrosionCONNECTORS Flexible fully insulated cable con nectors screwed (with 20 plusmn1 Nm) to the termi- nal with an insulated screw having a probe hole on the top for electrical measurementONE WAY RELIEF VALVE Opens at low pressure

INSTALLATIONCELLS ARE NORMALLY INSTALLED IN AN UPRIGHT POSITION ON STEEL STANDS

CHARGINGFLOAT VOLTAGE Standby use 225 VcellBOOST RECHARGE Maximum voltage of 235 - 240 Vcell with a maximum current of 025 C10 (A)

OPERATIONAL DATAOPERATIONAL LIFE Up to 20 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 2 per month at 20 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427

11-0

1-20

20 (a

telje

jkreg

)

H1W H2

TAB OPzV BATTERIES

L

Uf (Vcell) 18 18 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 10 5 3 1 Ri Isc L W H1H2 Wet Poles

Type NomCap(Ah) Capacity(Ah)at20degC mΩ A mm mm mm kg Nr4 OPzV 200 200 204 172 150 110 122 1660 103 206 354380 19 25 OPzV 250 250 255 215 188 138 098 2080 124 206 354380 23 26 OPzV 300 300 306 258 225 166 085 2490 145 206 354380 28 25 OPzV 350 350 357 305 263 190 075 2770 124 206 471496 31 26 OPzV 420 420 429 365 315 226 061 3350 145 206 471496 36 27 OPzV 490 490 500 425 370 264 052 3900 166 206 471496 41 26 OPzV 600 600 612 520 450 322 051 4060 145 206 643668 49 28 OPzV 800 800 816 700 600 441 038 5390 210 191 643668 65 410 OPzV 1000 1000 1020 870 750 546 030 6760 210 233 643668 80 412 OPzV 1200 1200 1250 1045 900 653 026 8120 210 275 643668 93 412 OPzV 1500 1500 1530 1330 1116 774 023 8810 210 275 796821 115 416 OPsV 2000 2000 2040 1770 1488 1032 017 11510 214 399 771796 155 620 OPzV 2500 2500 2560 2160 1860 1289 014 14400 214 482 769794 200 824 OPzV 3000 3000 3060 2550 2232 1547 012 17260 214 576 771796 235 8

Page 3: TAB STATIONARY BATTERIES€¦ · tab stationary batteries tab polar tab magic tab polar truck tab magic truck tab efb stop & go tab agm stop & go english opzs ogi ups topzs opzv

CONNECTIONS DIMENSIONS

Number ofpositive plate

Armored OPzS plates

Capacity at 10-hour

discharging

Electrolyte density 124 plusmn 001kgl at 20 degC

All measures and weights are within standard production tolerances Electrical values are approximative Technical modifications are reserved without prior notice

12V 2 OPzS 100Rated

voltageNumber of

positive plate

Armored OPzS plates

Capacity at 10-hour

discharging

H

L L

H

W108

Electrolyte density 124 plusmn 001kgl at 20 degC

All measures and weights are within standard production tolerances Electrical values are approximative Technical modifications are reserved without prior notice

DESIGNOPzS cells (block)POSITIVE ELECTRODE Tubular plate with low antimony alloy (lt2 )NEGATIVE ELECTRODE Flat with long life expander active material SEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 124 kgl at 20 degCCONTAINER High impact transparent SANLID ABS (SAN) in grey color BLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-poleCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mm2 (35 50 or 70 mm2)KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGOPzS cells (block)IU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 223 Vcell plusmn 1 between 10 degC and 30 degC ∆U∆T=-0004VK below 10 degC or above 30 degC in the monthly averageBOOST CHARGE U = 235 to 240 Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSOPzS cells (block)REFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEOPzS cells (block)EVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA OPzS cells (block)DESIGN LIFE Up to 20 years (18 years) at 20 degCWATER REFILLING INTERVAL More than 2 years at 20 degCIEC 896-1 CYCLES 1500 (1200) SELF-DISCHARGE Approx 2 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 1TESTS ACCORDING IEC 896-1SAFETY STANDARDS VDE0510part2and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

TAB OPzS BLOCKS TAB OPzS CELLS

TAB OPzS STATIONARY BLOCKS (CELLS) ARE PRODUCED IN THE CONVENTIONAL LEAD-ACID TECHNOLOGY

Stationary batteries of the OPzS type are intended for the supply of telecommunication facilities computers emergency lightning alarm control and monitoring systems in power plants and distribution stations at railway stations airports etc

Uf (Vcell) 180 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 5 3 1 Ri Isc L W H Dry Wet

Type Ah Ah Ah Ah mΩ A mm mm mm kg kg12V 1 OPzS 50 51 409 380 284 200 613 272 205 392 26 3912V 2 OPzS 100 103 818 757 567 93 1290 272 205 392 38 5012V 3 OPzS 150 154 1226 1137 851 69 1739 380 205 392 53 696V 4 OPzS 200 204 1670 1493 1152 22 2703 272 205 392 36 476V 5 OPzS 250 255 2086 1866 1436 19 3175 380 205 392 44 616V 6 OPzS 300 307 2505 2237 1720 16 3846 380 205 392 52 68

Uf (Vcell) 180 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 5 3 1 Ri Isc L W H Dry Wet Poles

Type Ah Ah Ah Ah mΩ A mm mm mm kg kg Nr2 OPzS 100 111 97 85 62 148 1350 103 206 420 87 137 23 OPzS 150 160 142 122 89 108 1845 103 206 420 110 160 24 OPzS 200 215 187 163 119 084 2376 103 206 420 130 180 25 OPzS 250 268 232 204 149 069 2887 124 206 420 160 220 26 OPzS 300 321 277 242 177 058 3438 145 206 420 180 260 25 OPzS 350 393 336 290 212 064 3137 124 206 536 200 290 26 OPzS 420 470 403 348 254 055 3641 145 206 536 240 340 27 OPzS 490 550 470 406 296 048 4169 166 206 536 280 390 26 OPzS 600 685 582 510 372 045 4466 145 206 711 350 500 27 OPzS 700 798 681 598 436 038 5280 210 191 711 420 620 48 OPzS 800 912 778 683 499 033 6035 210 191 711 460 650 49 OPzS 900 1025 875 767 560 029 6948 210 233 711 530 770 410 OPzS 1000 1140 972 852 622 026 7720 210 233 711 570 800 412 OPzS 1200 1365 1165 1020 745 023 8814 210 275 711 660 930 412 OPzS 1500 1645 1410 1220 890 023 8605 210 275 861 880 1190 414 OPzS 1750 1910 1640 1420 1035 019 10536 212 397 837 1050 1520 615 OPzS 1875 2050 1760 1520 1110 018 11289 212 397 837 1100 1560 616 OPzS 2000 2185 1875 1625 1185 017 12042 212 397 837 1150 1600 618 OPzS 2250 2455 2105 1825 1335 015 13506 212 487 837 1340 1920 820 OPzS 2500 2730 2340 2030 1480 013 15007 212 487 837 1450 2000 822 OPzS 2750 3000 2575 2230 1625 013 15941 212 576 837 1590 2320 824 OPzS 3000 3270 2805 2430 1775 012 17390 212 576 837 1700 2400 8

3 OPzS 150

Max

Min

Electrolyte density 124 plusmn 001kgl at 20 degC

All measures and weights are within standard production tolerances Electrical values are approximative Technical modifications are reserved without prior notice

DESIGNPOSITIVE ELECTRODE Robust-grid plate with circular bars in a corrosion-resistant PbSe alloy lt 2 SbNEGATIVE ELECTRODE Flat plate with long life expander and low antimony alloy SEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 124 kglCONTAINER High impact transparent SANLID SAN in dark grey colourBLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs or optional ceramic funnel plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-polePOLE M10 brass insertCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mmsup2 KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 223 Vcell plusmn 1 between 10degC and 55degC dUdT = -0004 mVK below 10 degC in the monthly averageBOOST CHARGE U = 235 to 240Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA

OPERATIONAL LIFE Up to 15 years at 20 degC Up to 75 years at 30 degC Up to 4 years at 40 degCWATER REFILLING INTERVAL More than 3 years at 20 degCIEC 896-1 CYCLES 1000SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 3TESTS ACCORDING IEC 896-1APPLICABLE STANDARDS VDE 0510 part 2 and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

6V 7 OGi 175Rated

voltageNumber of

positive plate

Robust OGi plates

Capacity at 10-hour

discharging

W

L

L

H

W108

TAB OGi BLOCK BATTERIES ARE ROBUST VENTED LEAD-ACID BATTERIES DESIGNED FOR INDUSTRIAL APPLICATIONS IN POWER SUPPLY WITH HIGH SAFETY REQUIREMENTS

TAB OGi block batteries can be used for both long duration discharge (10 hours) and short duration discharge (few minutes) The main areas of application are DC power supply systems in power stations UPS systems industrial systems and emergency power supply systems They can also be used for engine starting and PV power systems

CONNECTIONS DIMENSIONS

TAB OGi BATTERIES

Max

Min

Uf (Vcell) 180 175 175 170 165 165 160 IEC 896-1 Dimensions Weight Discharging time (h) 10 5 3 1 12 16 112 Ri Isc L W H Dry Wet

Type Ah Ah Ah Ah Ah Ah Ah mΩ (kA) mm mm mm kg kg12V 1 OGi 25 290 255 225 168 143 92 67 1679 072 272 205 375 234 35012V 2 OGi 50 550 495 447 328 280 180 131 881 141 272 205 375 303 41212V 3 OGi 75 800 745 675 496 422 273 198 594 211 272 205 375 366 47012V 4 OGi 100 1050 985 894 657 561 361 261 446 281 272 205 375 441 54112V 5 OGi 125 1350 1230 1113 816 690 443 317 357 352 380 205 375 550 68912V 6 OGi 150 1650 1485 1338 982 825 527 371 297 422 380 205 375 618 7536V 7 OGi 175 1872 1673 1513 1107 912 569 396 127 493 272 205 375 359 4666V 8 OGi 200 2280 1975 1788 1300 1080 673 468 111 563 272 205 375 394 4986V 9 OGi 225 2540 2215 2007 1458 1215 755 526 099 636 380 205 375 480 6326V 10 OGi 250 2700 2470 2235 1617 1330 805 553 089 704 380 205 375 512 6626V 11 OGi 275 3040 2715 2451 1776 1460 885 607 081 778 380 205 375 535 6836V 12 OGi 300 3200 2960 2682 1944 1595 965 663 074 844 380 205 375 564 7082V 3 OGi 75 800 745 675 496 422 273 198 099 192 103 206 420 65 992V 4 OGi 100 1050 985 894 657 561 361 261 074 252 103 206 420 77 1112V 5 OGi 125 1350 1230 1113 816 690 443 317 060 324 103 206 420 90 1262V 6 OGi 150 1650 1485 1338 982 825 527 371 050 396 103 206 420 107 1442V 7 OGi 175 1872 1673 1513 1107 912 569 396 042 449 103 206 420 117 1532V 8 OGi 200 2280 1975 1788 1300 1080 673 468 037 547 103 206 420 136 1732V 9 OGi 225 2540 2215 2007 1458 1215 755 526 033 610 103 206 420 154 1922V 10 OGi 250 2700 2470 2235 1617 1330 805 553 030 665 124 206 420 172 2132V 11 OGi 275 3040 2715 2451 1776 1460 885 607 027 755 145 206 420 190 2282V 12 OGi 300 3200 2960 2682 1944 1595 965 663 025 768 145 206 420 218 2512V 13 OGi 325 3467 3207 2906 2106 1728 1045 718 023 832 145 206 420 238 2762V 14 OGi 350 3733 3453 3129 2268 1861 1126 774 021 896 145 206 420 259 3002V 24 OGi 600 6840 5925 5364 3900 3240 2019 1404 013 1642 205 272 392 394 498

CONNECTIONS DIMENSIONS

TAB UPS BATTERIES ARE ROBUST AND FOR HIGH DISCHARGE - PERFORMANCES OPTIMISEDLEAD-ACID BATTERIES

The main application for TAB UPS are Uninterruptable Power Supplies (UPS)in the size of 50 to 250 kVA The battery is perfectly suited to start diesel engines for the auxiliary power supply

DESIGNPOSITIVE ELECTRODE Robust-plate with circular bars in a corrosion-resistant PbSe alloy lt 2 SbNEGATIVE ELECTRODE Flat plate with long life expander and low antimony alloySEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 128 kglCONTAINER High impact transparent SANLID SAN in dark grey colourBLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs or optional ceramic funnel plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-polePOLE M10 brass insertCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mmsup2 KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 225 to 227 Vcell plusmn 1 between 10 degC and 55 degC dUdT = -0004 mVdegK below 10 degC in the monthly averageBOOST CHARGE U = 235 to 240 Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA OPERATIONAL LIFE Up to 12 years at 20 degC Up to 6 years at 30 degC Up to 3 years at 40 degCWATER REFILLING INTERVAL More than 3 years at 20 degCIEC 896-1 CYCLES 800SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 3TESTS ACCORDING IEC 896-1APPLICABLE STANDARDS VDE 0510 part 2 and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

6V 7 UPS 700Rated

voltageNumber of

positive plate

Robust platesfor UPS

Power _ Wattcell10 min _ Uf=163 Vcell

LL

H

WWM

ax

Min

100W is the averaged power per plate at the 10 min rate Uf = 163Vcell

Electrolyte density 128 plusmn 001 kgl at 20 degC

All measures and weights are within standard production tolerances

Electrical values are approximative Technical modifications are reserved

without prior notice

TAB UPS BATTERIES

Uf (Vcell) 180 175 170 165 163 160 IEC 896-1 Dimensions Weight Discharging time (min) 60 30 15 10 5 Ri Isc L W H Dry Wet

Type C10(Ah) Wcell Wcell Wcell Wcell Wcell mΩ (kA) mm mm mm kg kg12V 1 UPS 100 41 42 64 92 120 181 1680 073 272 205 375 234 35412V 2 UPS 200 59 73 112 169 218 323 840 146 272 205 375 303 41612V 3 UPS 300 86 103 162 246 313 465 560 22 272 205 375 366 47312V 4 UPS 400 114 135 210 322 410 606 420 293 272 205 375 441 54512V 5 UPS 500 147 169 264 412 520 755 336 366 380 205 375 550 69412V 6 UPS 600 179 204 327 500 629 895 280 439 380 205 375 618 7586V 7 UPS 700 206 237 384 588 737 1040 120 513 272 205 375 359 4706V 8 UPS 800 247 272 440 676 848 1187 105 586 272 205 375 394 5026V 9 UPS 900 271 306 492 742 913 1294 093 659 380 205 375 480 6386V 10 UPS 1000 293 342 558 812 1014 1403 084 732 380 205 375 512 6676V 11 UPS 1100 325 381 592 879 1098 1509 076 805 380 205 375 535 6886V 12 UPS 1200 347 418 640 946 1178 1613 070 879 380 205 375 564 7152V 24 UPS 2400 742 816 1321 2027 2544 3562 013 1758 205 272 375 394 5022V 30 UPS 3000 879 1027 1674 2437 3042 4209 010 219 205 380 375 512 6672V 36 UPS 3600 1041 1253 1920 2837 3535 4838 008 263 205 380 375 554 715

The batteries are distinguished for HIGHCAPACITY LONGLIFETIME REDUCEDMAINTENANCE LOWSELF-DISCHARGING QUICKANDSIMPLEACID LEVEL CONTROL ECONOMICALWATERCONSUMPTION APPROPRIATEDIMENSIONS AND WEIGHT THELOWESTANDCONSTANT MAINTENANCE CURRENTThe stationary batteries of the type TOPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations Individual cells (2V) are made from translucent PP containersThe stationary batteries of the type OPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations

APPLICATIONStationary batteries of the TOPzS type are specially designed for solar systemsDuetotheirextremelylowself-discharging and tubular positive plates they are suitable for off-grid solar systems

CONSTRUCTIONThe positive armored plate is of a tubulartypewhichmeansthattheactivesubstance (PbO2) is contained in special gauntletmadeofpolyesterfibresandhardened by an impregnation compound Such construction prevents escaping of an active substance during the operation and ensures a long life timeThe grids of a positive and a negativeplatearemadeofspeciallowpercentage(lessthan2)antimonyalloywithaddi-tion agents for improvement of crystalline structure of castingNegative plates are pasted-type plateswithspecialalloysmaintainingporosity of an active substance during the operationAs an electrolyte a diluted sulphuric acid (H2SO4)withadensityof124plusmn001kglat20degreesCandatamaximumpermitted level is usedSeparators separating the positive plates from the negative ones are made of microporousplasticmaterialwithalowelectric resistanceIn a special process the lids are tightly sealedwiththermoweldingtothecon-tainerTheterminalplugsaresealedwithrubber seals This prevents any escape of electrolyte from the cellsDue to the transparent containers theelectrolyte level is clearly visible themaximumandminimumlevelsaremarkedonaself-adhesiveacid-prooflabel on a container side

TWO VERSIONS OF BATTERIES ARE BEING MANUFACTURED DRY-CHARGE VERSION abatteryhastobefilledupwith an electrolyte and supplementary charged before use The plates are already formed and in a special pro- cessprotectedagainstoxidationThey canbestoredwithoutproblems ELECTROLYTE-CHARGE battery can be installed immediately becauseitisalreadyfilledupwith electrolyte and electrically charged aswellThecapacitytesthasalready been performed by the producer

H

L

OPERATION-MAINTENANCEFor more detail information please check our operation manual

TRANSPORTBatteries are not subject to ADR (road transport)

DESIGNPOSITIVE ELECTRODE Tubular positive plate with low antimony alloy (lt2 )NEGATIVE ELECTRODE Flat plate with long life expanderSEPARATION Microporous separatorELECTROLYTE Sulphuric acid of 124 kglCONTAINER Transparent PPLID PP in green colourPOLE SEALING 100 gas-and electrolyte-tight rubber sealPOLE M10 brass insertCONNECTOR flexible insulated copper cable with cross-section of 35 50 or 70 mm2

POLE SCREW M10 steel insulated

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT VOLTAGE U=223Vcell plusmn 1 BOOST CHARGE U=235to 240 Vcell

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degC at C10 (180 Vcell) and 25 degC at C100 (185 Vcell)INITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATAOPERATIONAL LIFE Up to 15 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427SAFETY STANDARD VENTILATION ENIEC62485-2

Electrolyte density 124 plusmn 001kgl at 20 degC Uf=185Vcell at 25 degC

LOW MAINTENANCE TAB TOPzS VENTED STATIONARY BATTERIES

CONNECTIONS DIMENSIONS

TAB TOPzS BATTERIES

W W

Uf (Vcell) 180 180 185 IEC 896-1 Dimensions Weight Capacity C10 C20 C100 Ri Isc L W H Dry Wet

Type Ah Ah Ah mΩ A mm mm mm kg kg3 TOPzS 265 265 289 345 056 3721 198 83 472 124 1844 TOPzS 353 353 384 460 046 4514 198 101 472 160 2335 TOPzS 442 442 481 575 038 5461 198 119 472 202 2904 TOPzS 500 499 545 650 035 6005 198 101 720 243 3525 TOPzS 625 624 681 815 028 7448 198 119 720 303 4326 TOPzS750 749 817 975 030 6991 198 137 720 380 5357 TOPzS 875 874 953 1140 026 7888 198 173 720 440 6428 TOPzS 1000 999 1089 1300 024 8848 198 191 720 502 725

FEATURES SAFE VERSATILE RELIABLE MINIMALGASSING DEEPDISCHARGE RESISTANCE

TAB Tovarna Akumulatorskih Baterij dd Polena 6 SI-Mežica 2392 Slovenia | infotabsi | +386 (0)2 8702 300 | wwwtabsi

According to DIN 40742 IEC 60896-2

TAB OPzV range of valve regulated lead acid stationarybatteriescombinethebenefitsof recombination technology (i e virtually nomaintenanceduetoverylowgasemissions)plus the advantages of conventional vented batterieswithpositivetubularplates(ielonglifeandexcellentcyclingcapability)

TAB OPzV VALVE REGULATED LEADACID BATTERIES ARE THE IDEAL ENERGY SOURCE FOR MANY DIFFERENT STANDBY APPLICATIONS

DESIGNTUBULAR POSITIVE PLATES Special grid construction pressure cast from antimony free alloy with highly porous gauntlets that retain the active materialPASTED NEGATIVE PLATES Service lives consistent with the positive platesELECTROLYTE Gel structureSEPARATORS Extremely high porosity and low internal resistanceCONTAINERS AND LIDS Made of plastic (ABS) material Also available in ABS flame retardant material as an option (according to IEC 707 FV0)TERMINALS Female treated terminal (M10) perfect contact and low resistance with flexible cable connectorsPOST SEALS Prevents electrolyte leakage and terminal corrosionCONNECTORS Flexible fully insulated cable con nectors screwed (with 20 plusmn1 Nm) to the termi- nal with an insulated screw having a probe hole on the top for electrical measurementONE WAY RELIEF VALVE Opens at low pressure

INSTALLATIONCELLS ARE NORMALLY INSTALLED IN AN UPRIGHT POSITION ON STEEL STANDS

CHARGINGFLOAT VOLTAGE Standby use 225 VcellBOOST RECHARGE Maximum voltage of 235 - 240 Vcell with a maximum current of 025 C10 (A)

OPERATIONAL DATAOPERATIONAL LIFE Up to 20 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 2 per month at 20 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427

11-0

1-20

20 (a

telje

jkreg

)

H1W H2

TAB OPzV BATTERIES

L

Uf (Vcell) 18 18 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 10 5 3 1 Ri Isc L W H1H2 Wet Poles

Type NomCap(Ah) Capacity(Ah)at20degC mΩ A mm mm mm kg Nr4 OPzV 200 200 204 172 150 110 122 1660 103 206 354380 19 25 OPzV 250 250 255 215 188 138 098 2080 124 206 354380 23 26 OPzV 300 300 306 258 225 166 085 2490 145 206 354380 28 25 OPzV 350 350 357 305 263 190 075 2770 124 206 471496 31 26 OPzV 420 420 429 365 315 226 061 3350 145 206 471496 36 27 OPzV 490 490 500 425 370 264 052 3900 166 206 471496 41 26 OPzV 600 600 612 520 450 322 051 4060 145 206 643668 49 28 OPzV 800 800 816 700 600 441 038 5390 210 191 643668 65 410 OPzV 1000 1000 1020 870 750 546 030 6760 210 233 643668 80 412 OPzV 1200 1200 1250 1045 900 653 026 8120 210 275 643668 93 412 OPzV 1500 1500 1530 1330 1116 774 023 8810 210 275 796821 115 416 OPsV 2000 2000 2040 1770 1488 1032 017 11510 214 399 771796 155 620 OPzV 2500 2500 2560 2160 1860 1289 014 14400 214 482 769794 200 824 OPzV 3000 3000 3060 2550 2232 1547 012 17260 214 576 771796 235 8

Page 4: TAB STATIONARY BATTERIES€¦ · tab stationary batteries tab polar tab magic tab polar truck tab magic truck tab efb stop & go tab agm stop & go english opzs ogi ups topzs opzv

Electrolyte density 124 plusmn 001kgl at 20 degC

All measures and weights are within standard production tolerances Electrical values are approximative Technical modifications are reserved without prior notice

DESIGNPOSITIVE ELECTRODE Robust-grid plate with circular bars in a corrosion-resistant PbSe alloy lt 2 SbNEGATIVE ELECTRODE Flat plate with long life expander and low antimony alloy SEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 124 kglCONTAINER High impact transparent SANLID SAN in dark grey colourBLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs or optional ceramic funnel plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-polePOLE M10 brass insertCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mmsup2 KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 223 Vcell plusmn 1 between 10degC and 55degC dUdT = -0004 mVK below 10 degC in the monthly averageBOOST CHARGE U = 235 to 240Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA

OPERATIONAL LIFE Up to 15 years at 20 degC Up to 75 years at 30 degC Up to 4 years at 40 degCWATER REFILLING INTERVAL More than 3 years at 20 degCIEC 896-1 CYCLES 1000SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 3TESTS ACCORDING IEC 896-1APPLICABLE STANDARDS VDE 0510 part 2 and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

6V 7 OGi 175Rated

voltageNumber of

positive plate

Robust OGi plates

Capacity at 10-hour

discharging

W

L

L

H

W108

TAB OGi BLOCK BATTERIES ARE ROBUST VENTED LEAD-ACID BATTERIES DESIGNED FOR INDUSTRIAL APPLICATIONS IN POWER SUPPLY WITH HIGH SAFETY REQUIREMENTS

TAB OGi block batteries can be used for both long duration discharge (10 hours) and short duration discharge (few minutes) The main areas of application are DC power supply systems in power stations UPS systems industrial systems and emergency power supply systems They can also be used for engine starting and PV power systems

CONNECTIONS DIMENSIONS

TAB OGi BATTERIES

Max

Min

Uf (Vcell) 180 175 175 170 165 165 160 IEC 896-1 Dimensions Weight Discharging time (h) 10 5 3 1 12 16 112 Ri Isc L W H Dry Wet

Type Ah Ah Ah Ah Ah Ah Ah mΩ (kA) mm mm mm kg kg12V 1 OGi 25 290 255 225 168 143 92 67 1679 072 272 205 375 234 35012V 2 OGi 50 550 495 447 328 280 180 131 881 141 272 205 375 303 41212V 3 OGi 75 800 745 675 496 422 273 198 594 211 272 205 375 366 47012V 4 OGi 100 1050 985 894 657 561 361 261 446 281 272 205 375 441 54112V 5 OGi 125 1350 1230 1113 816 690 443 317 357 352 380 205 375 550 68912V 6 OGi 150 1650 1485 1338 982 825 527 371 297 422 380 205 375 618 7536V 7 OGi 175 1872 1673 1513 1107 912 569 396 127 493 272 205 375 359 4666V 8 OGi 200 2280 1975 1788 1300 1080 673 468 111 563 272 205 375 394 4986V 9 OGi 225 2540 2215 2007 1458 1215 755 526 099 636 380 205 375 480 6326V 10 OGi 250 2700 2470 2235 1617 1330 805 553 089 704 380 205 375 512 6626V 11 OGi 275 3040 2715 2451 1776 1460 885 607 081 778 380 205 375 535 6836V 12 OGi 300 3200 2960 2682 1944 1595 965 663 074 844 380 205 375 564 7082V 3 OGi 75 800 745 675 496 422 273 198 099 192 103 206 420 65 992V 4 OGi 100 1050 985 894 657 561 361 261 074 252 103 206 420 77 1112V 5 OGi 125 1350 1230 1113 816 690 443 317 060 324 103 206 420 90 1262V 6 OGi 150 1650 1485 1338 982 825 527 371 050 396 103 206 420 107 1442V 7 OGi 175 1872 1673 1513 1107 912 569 396 042 449 103 206 420 117 1532V 8 OGi 200 2280 1975 1788 1300 1080 673 468 037 547 103 206 420 136 1732V 9 OGi 225 2540 2215 2007 1458 1215 755 526 033 610 103 206 420 154 1922V 10 OGi 250 2700 2470 2235 1617 1330 805 553 030 665 124 206 420 172 2132V 11 OGi 275 3040 2715 2451 1776 1460 885 607 027 755 145 206 420 190 2282V 12 OGi 300 3200 2960 2682 1944 1595 965 663 025 768 145 206 420 218 2512V 13 OGi 325 3467 3207 2906 2106 1728 1045 718 023 832 145 206 420 238 2762V 14 OGi 350 3733 3453 3129 2268 1861 1126 774 021 896 145 206 420 259 3002V 24 OGi 600 6840 5925 5364 3900 3240 2019 1404 013 1642 205 272 392 394 498

CONNECTIONS DIMENSIONS

TAB UPS BATTERIES ARE ROBUST AND FOR HIGH DISCHARGE - PERFORMANCES OPTIMISEDLEAD-ACID BATTERIES

The main application for TAB UPS are Uninterruptable Power Supplies (UPS)in the size of 50 to 250 kVA The battery is perfectly suited to start diesel engines for the auxiliary power supply

DESIGNPOSITIVE ELECTRODE Robust-plate with circular bars in a corrosion-resistant PbSe alloy lt 2 SbNEGATIVE ELECTRODE Flat plate with long life expander and low antimony alloySEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 128 kglCONTAINER High impact transparent SANLID SAN in dark grey colourBLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs or optional ceramic funnel plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-polePOLE M10 brass insertCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mmsup2 KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 225 to 227 Vcell plusmn 1 between 10 degC and 55 degC dUdT = -0004 mVdegK below 10 degC in the monthly averageBOOST CHARGE U = 235 to 240 Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA OPERATIONAL LIFE Up to 12 years at 20 degC Up to 6 years at 30 degC Up to 3 years at 40 degCWATER REFILLING INTERVAL More than 3 years at 20 degCIEC 896-1 CYCLES 800SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 3TESTS ACCORDING IEC 896-1APPLICABLE STANDARDS VDE 0510 part 2 and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

6V 7 UPS 700Rated

voltageNumber of

positive plate

Robust platesfor UPS

Power _ Wattcell10 min _ Uf=163 Vcell

LL

H

WWM

ax

Min

100W is the averaged power per plate at the 10 min rate Uf = 163Vcell

Electrolyte density 128 plusmn 001 kgl at 20 degC

All measures and weights are within standard production tolerances

Electrical values are approximative Technical modifications are reserved

without prior notice

TAB UPS BATTERIES

Uf (Vcell) 180 175 170 165 163 160 IEC 896-1 Dimensions Weight Discharging time (min) 60 30 15 10 5 Ri Isc L W H Dry Wet

Type C10(Ah) Wcell Wcell Wcell Wcell Wcell mΩ (kA) mm mm mm kg kg12V 1 UPS 100 41 42 64 92 120 181 1680 073 272 205 375 234 35412V 2 UPS 200 59 73 112 169 218 323 840 146 272 205 375 303 41612V 3 UPS 300 86 103 162 246 313 465 560 22 272 205 375 366 47312V 4 UPS 400 114 135 210 322 410 606 420 293 272 205 375 441 54512V 5 UPS 500 147 169 264 412 520 755 336 366 380 205 375 550 69412V 6 UPS 600 179 204 327 500 629 895 280 439 380 205 375 618 7586V 7 UPS 700 206 237 384 588 737 1040 120 513 272 205 375 359 4706V 8 UPS 800 247 272 440 676 848 1187 105 586 272 205 375 394 5026V 9 UPS 900 271 306 492 742 913 1294 093 659 380 205 375 480 6386V 10 UPS 1000 293 342 558 812 1014 1403 084 732 380 205 375 512 6676V 11 UPS 1100 325 381 592 879 1098 1509 076 805 380 205 375 535 6886V 12 UPS 1200 347 418 640 946 1178 1613 070 879 380 205 375 564 7152V 24 UPS 2400 742 816 1321 2027 2544 3562 013 1758 205 272 375 394 5022V 30 UPS 3000 879 1027 1674 2437 3042 4209 010 219 205 380 375 512 6672V 36 UPS 3600 1041 1253 1920 2837 3535 4838 008 263 205 380 375 554 715

The batteries are distinguished for HIGHCAPACITY LONGLIFETIME REDUCEDMAINTENANCE LOWSELF-DISCHARGING QUICKANDSIMPLEACID LEVEL CONTROL ECONOMICALWATERCONSUMPTION APPROPRIATEDIMENSIONS AND WEIGHT THELOWESTANDCONSTANT MAINTENANCE CURRENTThe stationary batteries of the type TOPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations Individual cells (2V) are made from translucent PP containersThe stationary batteries of the type OPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations

APPLICATIONStationary batteries of the TOPzS type are specially designed for solar systemsDuetotheirextremelylowself-discharging and tubular positive plates they are suitable for off-grid solar systems

CONSTRUCTIONThe positive armored plate is of a tubulartypewhichmeansthattheactivesubstance (PbO2) is contained in special gauntletmadeofpolyesterfibresandhardened by an impregnation compound Such construction prevents escaping of an active substance during the operation and ensures a long life timeThe grids of a positive and a negativeplatearemadeofspeciallowpercentage(lessthan2)antimonyalloywithaddi-tion agents for improvement of crystalline structure of castingNegative plates are pasted-type plateswithspecialalloysmaintainingporosity of an active substance during the operationAs an electrolyte a diluted sulphuric acid (H2SO4)withadensityof124plusmn001kglat20degreesCandatamaximumpermitted level is usedSeparators separating the positive plates from the negative ones are made of microporousplasticmaterialwithalowelectric resistanceIn a special process the lids are tightly sealedwiththermoweldingtothecon-tainerTheterminalplugsaresealedwithrubber seals This prevents any escape of electrolyte from the cellsDue to the transparent containers theelectrolyte level is clearly visible themaximumandminimumlevelsaremarkedonaself-adhesiveacid-prooflabel on a container side

TWO VERSIONS OF BATTERIES ARE BEING MANUFACTURED DRY-CHARGE VERSION abatteryhastobefilledupwith an electrolyte and supplementary charged before use The plates are already formed and in a special pro- cessprotectedagainstoxidationThey canbestoredwithoutproblems ELECTROLYTE-CHARGE battery can be installed immediately becauseitisalreadyfilledupwith electrolyte and electrically charged aswellThecapacitytesthasalready been performed by the producer

H

L

OPERATION-MAINTENANCEFor more detail information please check our operation manual

TRANSPORTBatteries are not subject to ADR (road transport)

DESIGNPOSITIVE ELECTRODE Tubular positive plate with low antimony alloy (lt2 )NEGATIVE ELECTRODE Flat plate with long life expanderSEPARATION Microporous separatorELECTROLYTE Sulphuric acid of 124 kglCONTAINER Transparent PPLID PP in green colourPOLE SEALING 100 gas-and electrolyte-tight rubber sealPOLE M10 brass insertCONNECTOR flexible insulated copper cable with cross-section of 35 50 or 70 mm2

POLE SCREW M10 steel insulated

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT VOLTAGE U=223Vcell plusmn 1 BOOST CHARGE U=235to 240 Vcell

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degC at C10 (180 Vcell) and 25 degC at C100 (185 Vcell)INITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATAOPERATIONAL LIFE Up to 15 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427SAFETY STANDARD VENTILATION ENIEC62485-2

Electrolyte density 124 plusmn 001kgl at 20 degC Uf=185Vcell at 25 degC

LOW MAINTENANCE TAB TOPzS VENTED STATIONARY BATTERIES

CONNECTIONS DIMENSIONS

TAB TOPzS BATTERIES

W W

Uf (Vcell) 180 180 185 IEC 896-1 Dimensions Weight Capacity C10 C20 C100 Ri Isc L W H Dry Wet

Type Ah Ah Ah mΩ A mm mm mm kg kg3 TOPzS 265 265 289 345 056 3721 198 83 472 124 1844 TOPzS 353 353 384 460 046 4514 198 101 472 160 2335 TOPzS 442 442 481 575 038 5461 198 119 472 202 2904 TOPzS 500 499 545 650 035 6005 198 101 720 243 3525 TOPzS 625 624 681 815 028 7448 198 119 720 303 4326 TOPzS750 749 817 975 030 6991 198 137 720 380 5357 TOPzS 875 874 953 1140 026 7888 198 173 720 440 6428 TOPzS 1000 999 1089 1300 024 8848 198 191 720 502 725

FEATURES SAFE VERSATILE RELIABLE MINIMALGASSING DEEPDISCHARGE RESISTANCE

TAB Tovarna Akumulatorskih Baterij dd Polena 6 SI-Mežica 2392 Slovenia | infotabsi | +386 (0)2 8702 300 | wwwtabsi

According to DIN 40742 IEC 60896-2

TAB OPzV range of valve regulated lead acid stationarybatteriescombinethebenefitsof recombination technology (i e virtually nomaintenanceduetoverylowgasemissions)plus the advantages of conventional vented batterieswithpositivetubularplates(ielonglifeandexcellentcyclingcapability)

TAB OPzV VALVE REGULATED LEADACID BATTERIES ARE THE IDEAL ENERGY SOURCE FOR MANY DIFFERENT STANDBY APPLICATIONS

DESIGNTUBULAR POSITIVE PLATES Special grid construction pressure cast from antimony free alloy with highly porous gauntlets that retain the active materialPASTED NEGATIVE PLATES Service lives consistent with the positive platesELECTROLYTE Gel structureSEPARATORS Extremely high porosity and low internal resistanceCONTAINERS AND LIDS Made of plastic (ABS) material Also available in ABS flame retardant material as an option (according to IEC 707 FV0)TERMINALS Female treated terminal (M10) perfect contact and low resistance with flexible cable connectorsPOST SEALS Prevents electrolyte leakage and terminal corrosionCONNECTORS Flexible fully insulated cable con nectors screwed (with 20 plusmn1 Nm) to the termi- nal with an insulated screw having a probe hole on the top for electrical measurementONE WAY RELIEF VALVE Opens at low pressure

INSTALLATIONCELLS ARE NORMALLY INSTALLED IN AN UPRIGHT POSITION ON STEEL STANDS

CHARGINGFLOAT VOLTAGE Standby use 225 VcellBOOST RECHARGE Maximum voltage of 235 - 240 Vcell with a maximum current of 025 C10 (A)

OPERATIONAL DATAOPERATIONAL LIFE Up to 20 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 2 per month at 20 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427

11-0

1-20

20 (a

telje

jkreg

)

H1W H2

TAB OPzV BATTERIES

L

Uf (Vcell) 18 18 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 10 5 3 1 Ri Isc L W H1H2 Wet Poles

Type NomCap(Ah) Capacity(Ah)at20degC mΩ A mm mm mm kg Nr4 OPzV 200 200 204 172 150 110 122 1660 103 206 354380 19 25 OPzV 250 250 255 215 188 138 098 2080 124 206 354380 23 26 OPzV 300 300 306 258 225 166 085 2490 145 206 354380 28 25 OPzV 350 350 357 305 263 190 075 2770 124 206 471496 31 26 OPzV 420 420 429 365 315 226 061 3350 145 206 471496 36 27 OPzV 490 490 500 425 370 264 052 3900 166 206 471496 41 26 OPzV 600 600 612 520 450 322 051 4060 145 206 643668 49 28 OPzV 800 800 816 700 600 441 038 5390 210 191 643668 65 410 OPzV 1000 1000 1020 870 750 546 030 6760 210 233 643668 80 412 OPzV 1200 1200 1250 1045 900 653 026 8120 210 275 643668 93 412 OPzV 1500 1500 1530 1330 1116 774 023 8810 210 275 796821 115 416 OPsV 2000 2000 2040 1770 1488 1032 017 11510 214 399 771796 155 620 OPzV 2500 2500 2560 2160 1860 1289 014 14400 214 482 769794 200 824 OPzV 3000 3000 3060 2550 2232 1547 012 17260 214 576 771796 235 8

Page 5: TAB STATIONARY BATTERIES€¦ · tab stationary batteries tab polar tab magic tab polar truck tab magic truck tab efb stop & go tab agm stop & go english opzs ogi ups topzs opzv

CONNECTIONS DIMENSIONS

TAB UPS BATTERIES ARE ROBUST AND FOR HIGH DISCHARGE - PERFORMANCES OPTIMISEDLEAD-ACID BATTERIES

The main application for TAB UPS are Uninterruptable Power Supplies (UPS)in the size of 50 to 250 kVA The battery is perfectly suited to start diesel engines for the auxiliary power supply

DESIGNPOSITIVE ELECTRODE Robust-plate with circular bars in a corrosion-resistant PbSe alloy lt 2 SbNEGATIVE ELECTRODE Flat plate with long life expander and low antimony alloySEPARATION Microporous separator ELECTROLYTE Sulphuric acid of 128 kglCONTAINER High impact transparent SANLID SAN in dark grey colourBLOCKS WITH BLIND CELLS 4V 6V 8V 10VPLUGS Ceramic plugs or optional ceramic funnel plugs according to DIN 40740POLE SEALING 100 gas-and electrolyte-tight sliding-polePOLE M10 brass insertCONNECTOR Flexible insulated copper cable with cross-section of 35 50 70 95 or 120 mmsup2 KIND OF PROTECTION IP 25 regarding DIN 40050 touch protected according VBG 4

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT CHARGE U = 225 to 227 Vcell plusmn 1 between 10 degC and 55 degC dUdT = -0004 mVdegK below 10 degC in the monthly averageBOOST CHARGE U = 235 to 240 Vcell time limitedCHARGING TIME UP TO 92 6h with 15I10 initial current 223 Vcell 50 C10 discharged

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degCINITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATA OPERATIONAL LIFE Up to 12 years at 20 degC Up to 6 years at 30 degC Up to 3 years at 40 degCWATER REFILLING INTERVAL More than 3 years at 20 degCIEC 896-1 CYCLES 800SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCVENTILATION REQUIREMENT according to EN IEC 62485-2MEASUREMENTS ACCORDING DIN 40 737 part 3TESTS ACCORDING IEC 896-1APPLICABLE STANDARDS VDE 0510 part 2 and EN IEC 62485-2TRANSPORT No dangerous goods during road transport

6V 7 UPS 700Rated

voltageNumber of

positive plate

Robust platesfor UPS

Power _ Wattcell10 min _ Uf=163 Vcell

LL

H

WWM

ax

Min

100W is the averaged power per plate at the 10 min rate Uf = 163Vcell

Electrolyte density 128 plusmn 001 kgl at 20 degC

All measures and weights are within standard production tolerances

Electrical values are approximative Technical modifications are reserved

without prior notice

TAB UPS BATTERIES

Uf (Vcell) 180 175 170 165 163 160 IEC 896-1 Dimensions Weight Discharging time (min) 60 30 15 10 5 Ri Isc L W H Dry Wet

Type C10(Ah) Wcell Wcell Wcell Wcell Wcell mΩ (kA) mm mm mm kg kg12V 1 UPS 100 41 42 64 92 120 181 1680 073 272 205 375 234 35412V 2 UPS 200 59 73 112 169 218 323 840 146 272 205 375 303 41612V 3 UPS 300 86 103 162 246 313 465 560 22 272 205 375 366 47312V 4 UPS 400 114 135 210 322 410 606 420 293 272 205 375 441 54512V 5 UPS 500 147 169 264 412 520 755 336 366 380 205 375 550 69412V 6 UPS 600 179 204 327 500 629 895 280 439 380 205 375 618 7586V 7 UPS 700 206 237 384 588 737 1040 120 513 272 205 375 359 4706V 8 UPS 800 247 272 440 676 848 1187 105 586 272 205 375 394 5026V 9 UPS 900 271 306 492 742 913 1294 093 659 380 205 375 480 6386V 10 UPS 1000 293 342 558 812 1014 1403 084 732 380 205 375 512 6676V 11 UPS 1100 325 381 592 879 1098 1509 076 805 380 205 375 535 6886V 12 UPS 1200 347 418 640 946 1178 1613 070 879 380 205 375 564 7152V 24 UPS 2400 742 816 1321 2027 2544 3562 013 1758 205 272 375 394 5022V 30 UPS 3000 879 1027 1674 2437 3042 4209 010 219 205 380 375 512 6672V 36 UPS 3600 1041 1253 1920 2837 3535 4838 008 263 205 380 375 554 715

The batteries are distinguished for HIGHCAPACITY LONGLIFETIME REDUCEDMAINTENANCE LOWSELF-DISCHARGING QUICKANDSIMPLEACID LEVEL CONTROL ECONOMICALWATERCONSUMPTION APPROPRIATEDIMENSIONS AND WEIGHT THELOWESTANDCONSTANT MAINTENANCE CURRENTThe stationary batteries of the type TOPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations Individual cells (2V) are made from translucent PP containersThe stationary batteries of the type OPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations

APPLICATIONStationary batteries of the TOPzS type are specially designed for solar systemsDuetotheirextremelylowself-discharging and tubular positive plates they are suitable for off-grid solar systems

CONSTRUCTIONThe positive armored plate is of a tubulartypewhichmeansthattheactivesubstance (PbO2) is contained in special gauntletmadeofpolyesterfibresandhardened by an impregnation compound Such construction prevents escaping of an active substance during the operation and ensures a long life timeThe grids of a positive and a negativeplatearemadeofspeciallowpercentage(lessthan2)antimonyalloywithaddi-tion agents for improvement of crystalline structure of castingNegative plates are pasted-type plateswithspecialalloysmaintainingporosity of an active substance during the operationAs an electrolyte a diluted sulphuric acid (H2SO4)withadensityof124plusmn001kglat20degreesCandatamaximumpermitted level is usedSeparators separating the positive plates from the negative ones are made of microporousplasticmaterialwithalowelectric resistanceIn a special process the lids are tightly sealedwiththermoweldingtothecon-tainerTheterminalplugsaresealedwithrubber seals This prevents any escape of electrolyte from the cellsDue to the transparent containers theelectrolyte level is clearly visible themaximumandminimumlevelsaremarkedonaself-adhesiveacid-prooflabel on a container side

TWO VERSIONS OF BATTERIES ARE BEING MANUFACTURED DRY-CHARGE VERSION abatteryhastobefilledupwith an electrolyte and supplementary charged before use The plates are already formed and in a special pro- cessprotectedagainstoxidationThey canbestoredwithoutproblems ELECTROLYTE-CHARGE battery can be installed immediately becauseitisalreadyfilledupwith electrolyte and electrically charged aswellThecapacitytesthasalready been performed by the producer

H

L

OPERATION-MAINTENANCEFor more detail information please check our operation manual

TRANSPORTBatteries are not subject to ADR (road transport)

DESIGNPOSITIVE ELECTRODE Tubular positive plate with low antimony alloy (lt2 )NEGATIVE ELECTRODE Flat plate with long life expanderSEPARATION Microporous separatorELECTROLYTE Sulphuric acid of 124 kglCONTAINER Transparent PPLID PP in green colourPOLE SEALING 100 gas-and electrolyte-tight rubber sealPOLE M10 brass insertCONNECTOR flexible insulated copper cable with cross-section of 35 50 or 70 mm2

POLE SCREW M10 steel insulated

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT VOLTAGE U=223Vcell plusmn 1 BOOST CHARGE U=235to 240 Vcell

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degC at C10 (180 Vcell) and 25 degC at C100 (185 Vcell)INITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATAOPERATIONAL LIFE Up to 15 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427SAFETY STANDARD VENTILATION ENIEC62485-2

Electrolyte density 124 plusmn 001kgl at 20 degC Uf=185Vcell at 25 degC

LOW MAINTENANCE TAB TOPzS VENTED STATIONARY BATTERIES

CONNECTIONS DIMENSIONS

TAB TOPzS BATTERIES

W W

Uf (Vcell) 180 180 185 IEC 896-1 Dimensions Weight Capacity C10 C20 C100 Ri Isc L W H Dry Wet

Type Ah Ah Ah mΩ A mm mm mm kg kg3 TOPzS 265 265 289 345 056 3721 198 83 472 124 1844 TOPzS 353 353 384 460 046 4514 198 101 472 160 2335 TOPzS 442 442 481 575 038 5461 198 119 472 202 2904 TOPzS 500 499 545 650 035 6005 198 101 720 243 3525 TOPzS 625 624 681 815 028 7448 198 119 720 303 4326 TOPzS750 749 817 975 030 6991 198 137 720 380 5357 TOPzS 875 874 953 1140 026 7888 198 173 720 440 6428 TOPzS 1000 999 1089 1300 024 8848 198 191 720 502 725

FEATURES SAFE VERSATILE RELIABLE MINIMALGASSING DEEPDISCHARGE RESISTANCE

TAB Tovarna Akumulatorskih Baterij dd Polena 6 SI-Mežica 2392 Slovenia | infotabsi | +386 (0)2 8702 300 | wwwtabsi

According to DIN 40742 IEC 60896-2

TAB OPzV range of valve regulated lead acid stationarybatteriescombinethebenefitsof recombination technology (i e virtually nomaintenanceduetoverylowgasemissions)plus the advantages of conventional vented batterieswithpositivetubularplates(ielonglifeandexcellentcyclingcapability)

TAB OPzV VALVE REGULATED LEADACID BATTERIES ARE THE IDEAL ENERGY SOURCE FOR MANY DIFFERENT STANDBY APPLICATIONS

DESIGNTUBULAR POSITIVE PLATES Special grid construction pressure cast from antimony free alloy with highly porous gauntlets that retain the active materialPASTED NEGATIVE PLATES Service lives consistent with the positive platesELECTROLYTE Gel structureSEPARATORS Extremely high porosity and low internal resistanceCONTAINERS AND LIDS Made of plastic (ABS) material Also available in ABS flame retardant material as an option (according to IEC 707 FV0)TERMINALS Female treated terminal (M10) perfect contact and low resistance with flexible cable connectorsPOST SEALS Prevents electrolyte leakage and terminal corrosionCONNECTORS Flexible fully insulated cable con nectors screwed (with 20 plusmn1 Nm) to the termi- nal with an insulated screw having a probe hole on the top for electrical measurementONE WAY RELIEF VALVE Opens at low pressure

INSTALLATIONCELLS ARE NORMALLY INSTALLED IN AN UPRIGHT POSITION ON STEEL STANDS

CHARGINGFLOAT VOLTAGE Standby use 225 VcellBOOST RECHARGE Maximum voltage of 235 - 240 Vcell with a maximum current of 025 C10 (A)

OPERATIONAL DATAOPERATIONAL LIFE Up to 20 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 2 per month at 20 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427

11-0

1-20

20 (a

telje

jkreg

)

H1W H2

TAB OPzV BATTERIES

L

Uf (Vcell) 18 18 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 10 5 3 1 Ri Isc L W H1H2 Wet Poles

Type NomCap(Ah) Capacity(Ah)at20degC mΩ A mm mm mm kg Nr4 OPzV 200 200 204 172 150 110 122 1660 103 206 354380 19 25 OPzV 250 250 255 215 188 138 098 2080 124 206 354380 23 26 OPzV 300 300 306 258 225 166 085 2490 145 206 354380 28 25 OPzV 350 350 357 305 263 190 075 2770 124 206 471496 31 26 OPzV 420 420 429 365 315 226 061 3350 145 206 471496 36 27 OPzV 490 490 500 425 370 264 052 3900 166 206 471496 41 26 OPzV 600 600 612 520 450 322 051 4060 145 206 643668 49 28 OPzV 800 800 816 700 600 441 038 5390 210 191 643668 65 410 OPzV 1000 1000 1020 870 750 546 030 6760 210 233 643668 80 412 OPzV 1200 1200 1250 1045 900 653 026 8120 210 275 643668 93 412 OPzV 1500 1500 1530 1330 1116 774 023 8810 210 275 796821 115 416 OPsV 2000 2000 2040 1770 1488 1032 017 11510 214 399 771796 155 620 OPzV 2500 2500 2560 2160 1860 1289 014 14400 214 482 769794 200 824 OPzV 3000 3000 3060 2550 2232 1547 012 17260 214 576 771796 235 8

Page 6: TAB STATIONARY BATTERIES€¦ · tab stationary batteries tab polar tab magic tab polar truck tab magic truck tab efb stop & go tab agm stop & go english opzs ogi ups topzs opzv

The batteries are distinguished for HIGHCAPACITY LONGLIFETIME REDUCEDMAINTENANCE LOWSELF-DISCHARGING QUICKANDSIMPLEACID LEVEL CONTROL ECONOMICALWATERCONSUMPTION APPROPRIATEDIMENSIONS AND WEIGHT THELOWESTANDCONSTANT MAINTENANCE CURRENTThe stationary batteries of the type TOPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations Individual cells (2V) are made from translucent PP containersThe stationary batteries of the type OPzS are manufactured according to the DIN 40736 EN 60896 and IEC 896-1 regulations

APPLICATIONStationary batteries of the TOPzS type are specially designed for solar systemsDuetotheirextremelylowself-discharging and tubular positive plates they are suitable for off-grid solar systems

CONSTRUCTIONThe positive armored plate is of a tubulartypewhichmeansthattheactivesubstance (PbO2) is contained in special gauntletmadeofpolyesterfibresandhardened by an impregnation compound Such construction prevents escaping of an active substance during the operation and ensures a long life timeThe grids of a positive and a negativeplatearemadeofspeciallowpercentage(lessthan2)antimonyalloywithaddi-tion agents for improvement of crystalline structure of castingNegative plates are pasted-type plateswithspecialalloysmaintainingporosity of an active substance during the operationAs an electrolyte a diluted sulphuric acid (H2SO4)withadensityof124plusmn001kglat20degreesCandatamaximumpermitted level is usedSeparators separating the positive plates from the negative ones are made of microporousplasticmaterialwithalowelectric resistanceIn a special process the lids are tightly sealedwiththermoweldingtothecon-tainerTheterminalplugsaresealedwithrubber seals This prevents any escape of electrolyte from the cellsDue to the transparent containers theelectrolyte level is clearly visible themaximumandminimumlevelsaremarkedonaself-adhesiveacid-prooflabel on a container side

TWO VERSIONS OF BATTERIES ARE BEING MANUFACTURED DRY-CHARGE VERSION abatteryhastobefilledupwith an electrolyte and supplementary charged before use The plates are already formed and in a special pro- cessprotectedagainstoxidationThey canbestoredwithoutproblems ELECTROLYTE-CHARGE battery can be installed immediately becauseitisalreadyfilledupwith electrolyte and electrically charged aswellThecapacitytesthasalready been performed by the producer

H

L

OPERATION-MAINTENANCEFor more detail information please check our operation manual

TRANSPORTBatteries are not subject to ADR (road transport)

DESIGNPOSITIVE ELECTRODE Tubular positive plate with low antimony alloy (lt2 )NEGATIVE ELECTRODE Flat plate with long life expanderSEPARATION Microporous separatorELECTROLYTE Sulphuric acid of 124 kglCONTAINER Transparent PPLID PP in green colourPOLE SEALING 100 gas-and electrolyte-tight rubber sealPOLE M10 brass insertCONNECTOR flexible insulated copper cable with cross-section of 35 50 or 70 mm2

POLE SCREW M10 steel insulated

CHARGINGIU - CHARACTERISTIC Imax without limitationFLOAT VOLTAGE U=223Vcell plusmn 1 BOOST CHARGE U=235to 240 Vcell

DISCHARGE CHARACTERISTICSREFERENCE TEMPERATURE 20 degC at C10 (180 Vcell) and 25 degC at C100 (185 Vcell)INITIAL CAPACITY 100DEPTH OF DISCHARGE Normally up to 80 More than 80 DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided

MAINTENANCEEVERY 6 MONTH Check battery voltage pilot block voltage temperatureEVERY 12 MONTH Take down battery voltage block voltage temperature

OPERATIONAL DATAOPERATIONAL LIFE Up to 15 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 3 per month at 20 degCOPERATIONAL TEMPERATURE -20 degC to 55 degC recommended 10 degC to 30 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427SAFETY STANDARD VENTILATION ENIEC62485-2

Electrolyte density 124 plusmn 001kgl at 20 degC Uf=185Vcell at 25 degC

LOW MAINTENANCE TAB TOPzS VENTED STATIONARY BATTERIES

CONNECTIONS DIMENSIONS

TAB TOPzS BATTERIES

W W

Uf (Vcell) 180 180 185 IEC 896-1 Dimensions Weight Capacity C10 C20 C100 Ri Isc L W H Dry Wet

Type Ah Ah Ah mΩ A mm mm mm kg kg3 TOPzS 265 265 289 345 056 3721 198 83 472 124 1844 TOPzS 353 353 384 460 046 4514 198 101 472 160 2335 TOPzS 442 442 481 575 038 5461 198 119 472 202 2904 TOPzS 500 499 545 650 035 6005 198 101 720 243 3525 TOPzS 625 624 681 815 028 7448 198 119 720 303 4326 TOPzS750 749 817 975 030 6991 198 137 720 380 5357 TOPzS 875 874 953 1140 026 7888 198 173 720 440 6428 TOPzS 1000 999 1089 1300 024 8848 198 191 720 502 725

FEATURES SAFE VERSATILE RELIABLE MINIMALGASSING DEEPDISCHARGE RESISTANCE

TAB Tovarna Akumulatorskih Baterij dd Polena 6 SI-Mežica 2392 Slovenia | infotabsi | +386 (0)2 8702 300 | wwwtabsi

According to DIN 40742 IEC 60896-2

TAB OPzV range of valve regulated lead acid stationarybatteriescombinethebenefitsof recombination technology (i e virtually nomaintenanceduetoverylowgasemissions)plus the advantages of conventional vented batterieswithpositivetubularplates(ielonglifeandexcellentcyclingcapability)

TAB OPzV VALVE REGULATED LEADACID BATTERIES ARE THE IDEAL ENERGY SOURCE FOR MANY DIFFERENT STANDBY APPLICATIONS

DESIGNTUBULAR POSITIVE PLATES Special grid construction pressure cast from antimony free alloy with highly porous gauntlets that retain the active materialPASTED NEGATIVE PLATES Service lives consistent with the positive platesELECTROLYTE Gel structureSEPARATORS Extremely high porosity and low internal resistanceCONTAINERS AND LIDS Made of plastic (ABS) material Also available in ABS flame retardant material as an option (according to IEC 707 FV0)TERMINALS Female treated terminal (M10) perfect contact and low resistance with flexible cable connectorsPOST SEALS Prevents electrolyte leakage and terminal corrosionCONNECTORS Flexible fully insulated cable con nectors screwed (with 20 plusmn1 Nm) to the termi- nal with an insulated screw having a probe hole on the top for electrical measurementONE WAY RELIEF VALVE Opens at low pressure

INSTALLATIONCELLS ARE NORMALLY INSTALLED IN AN UPRIGHT POSITION ON STEEL STANDS

CHARGINGFLOAT VOLTAGE Standby use 225 VcellBOOST RECHARGE Maximum voltage of 235 - 240 Vcell with a maximum current of 025 C10 (A)

OPERATIONAL DATAOPERATIONAL LIFE Up to 20 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 2 per month at 20 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427

11-0

1-20

20 (a

telje

jkreg

)

H1W H2

TAB OPzV BATTERIES

L

Uf (Vcell) 18 18 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 10 5 3 1 Ri Isc L W H1H2 Wet Poles

Type NomCap(Ah) Capacity(Ah)at20degC mΩ A mm mm mm kg Nr4 OPzV 200 200 204 172 150 110 122 1660 103 206 354380 19 25 OPzV 250 250 255 215 188 138 098 2080 124 206 354380 23 26 OPzV 300 300 306 258 225 166 085 2490 145 206 354380 28 25 OPzV 350 350 357 305 263 190 075 2770 124 206 471496 31 26 OPzV 420 420 429 365 315 226 061 3350 145 206 471496 36 27 OPzV 490 490 500 425 370 264 052 3900 166 206 471496 41 26 OPzV 600 600 612 520 450 322 051 4060 145 206 643668 49 28 OPzV 800 800 816 700 600 441 038 5390 210 191 643668 65 410 OPzV 1000 1000 1020 870 750 546 030 6760 210 233 643668 80 412 OPzV 1200 1200 1250 1045 900 653 026 8120 210 275 643668 93 412 OPzV 1500 1500 1530 1330 1116 774 023 8810 210 275 796821 115 416 OPsV 2000 2000 2040 1770 1488 1032 017 11510 214 399 771796 155 620 OPzV 2500 2500 2560 2160 1860 1289 014 14400 214 482 769794 200 824 OPzV 3000 3000 3060 2550 2232 1547 012 17260 214 576 771796 235 8

Page 7: TAB STATIONARY BATTERIES€¦ · tab stationary batteries tab polar tab magic tab polar truck tab magic truck tab efb stop & go tab agm stop & go english opzs ogi ups topzs opzv

FEATURES SAFE VERSATILE RELIABLE MINIMALGASSING DEEPDISCHARGE RESISTANCE

TAB Tovarna Akumulatorskih Baterij dd Polena 6 SI-Mežica 2392 Slovenia | infotabsi | +386 (0)2 8702 300 | wwwtabsi

According to DIN 40742 IEC 60896-2

TAB OPzV range of valve regulated lead acid stationarybatteriescombinethebenefitsof recombination technology (i e virtually nomaintenanceduetoverylowgasemissions)plus the advantages of conventional vented batterieswithpositivetubularplates(ielonglifeandexcellentcyclingcapability)

TAB OPzV VALVE REGULATED LEADACID BATTERIES ARE THE IDEAL ENERGY SOURCE FOR MANY DIFFERENT STANDBY APPLICATIONS

DESIGNTUBULAR POSITIVE PLATES Special grid construction pressure cast from antimony free alloy with highly porous gauntlets that retain the active materialPASTED NEGATIVE PLATES Service lives consistent with the positive platesELECTROLYTE Gel structureSEPARATORS Extremely high porosity and low internal resistanceCONTAINERS AND LIDS Made of plastic (ABS) material Also available in ABS flame retardant material as an option (according to IEC 707 FV0)TERMINALS Female treated terminal (M10) perfect contact and low resistance with flexible cable connectorsPOST SEALS Prevents electrolyte leakage and terminal corrosionCONNECTORS Flexible fully insulated cable con nectors screwed (with 20 plusmn1 Nm) to the termi- nal with an insulated screw having a probe hole on the top for electrical measurementONE WAY RELIEF VALVE Opens at low pressure

INSTALLATIONCELLS ARE NORMALLY INSTALLED IN AN UPRIGHT POSITION ON STEEL STANDS

CHARGINGFLOAT VOLTAGE Standby use 225 VcellBOOST RECHARGE Maximum voltage of 235 - 240 Vcell with a maximum current of 025 C10 (A)

OPERATIONAL DATAOPERATIONAL LIFE Up to 20 yearsIEC 896-1 CYCLES 1200SELF-DISCHARGE Approx 2 per month at 20 degCTESTS ACCORDING IEC 896-1 EN 60896-1 EN 61427

11-0

1-20

20 (a

telje

jkreg

)

H1W H2

TAB OPzV BATTERIES

L

Uf (Vcell) 18 18 177 175 167 IEC 896-1 Dimensions Weight Discharging time (h) 10 10 5 3 1 Ri Isc L W H1H2 Wet Poles

Type NomCap(Ah) Capacity(Ah)at20degC mΩ A mm mm mm kg Nr4 OPzV 200 200 204 172 150 110 122 1660 103 206 354380 19 25 OPzV 250 250 255 215 188 138 098 2080 124 206 354380 23 26 OPzV 300 300 306 258 225 166 085 2490 145 206 354380 28 25 OPzV 350 350 357 305 263 190 075 2770 124 206 471496 31 26 OPzV 420 420 429 365 315 226 061 3350 145 206 471496 36 27 OPzV 490 490 500 425 370 264 052 3900 166 206 471496 41 26 OPzV 600 600 612 520 450 322 051 4060 145 206 643668 49 28 OPzV 800 800 816 700 600 441 038 5390 210 191 643668 65 410 OPzV 1000 1000 1020 870 750 546 030 6760 210 233 643668 80 412 OPzV 1200 1200 1250 1045 900 653 026 8120 210 275 643668 93 412 OPzV 1500 1500 1530 1330 1116 774 023 8810 210 275 796821 115 416 OPsV 2000 2000 2040 1770 1488 1032 017 11510 214 399 771796 155 620 OPzV 2500 2500 2560 2160 1860 1289 014 14400 214 482 769794 200 824 OPzV 3000 3000 3060 2550 2232 1547 012 17260 214 576 771796 235 8