Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
1 of 29
Tank Farm Plant Operating Procedure VENTILATION
USQ # N/A-4
CHANGE HISTORY ( LAST 5 REV-MODS )
Rev-Mod Release Date Justification: Summary of Changes
B-1 08/08/2016 First time use change to comply
with field (HMI) label.
Updated the labels, in the tables applicable to steps 5.5.11,
5.5.13, 5.6.3, 5.7.10, and 5.8.2.
B-0 04/05/2016 Maintenance Request Reactivated
A-1 10/18/2005 Engineering Request Inactivated 04/28/2006
Table of Contents Page
1.0 PURPOSE AND SCOPE ................................................................................................................ 3
1.1 Purpose ................................................................................................................................ 3
1.2 Scope ................................................................................................................................... 3
2.0 INFORMATION............................................................................................................................. 3
2.1 General Information ............................................................................................................ 3
3.0 PRECAUTIONS AND LIMITATIONS......................................................................................... 4
3.1 Personnel Safety.................................................................................................................. 4
3.2 Radiation and Contamination Control ................................................................................ 4
3.3 Environmental Compliance ................................................................................................ 5
4.0 PREREQUISITES .......................................................................................................................... 6
4.1 Special Tools, Equipment, and Supplies............................................................................. 6
4.2 Performance Documents ..................................................................................................... 6
4.3 Field Preparation ................................................................................................................. 7
5.0 PROCEDURE ................................................................................................................................. 8
5.1 Initial Conditions ................................................................................................................ 8
5.2 CAM Slow Alarm Setpoint ............................................................................................... 10
5.3 CAM Fast Alarm Setpoint ................................................................................................ 11
5.4 CAM Beta Net Alarm Setpoint ......................................................................................... 12
5.5 Simulate Stack CAM Detector Failure ............................................................................. 13
5.6 Low Sample Flow Rate Alarm Test.................................................................................. 16
5.7 High Radiation Alarm and Fan Interlock.......................................................................... 19
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
2 of 29
5.8 Exhaust Stack CAM Power Failure .................................................................................. 23
5.9 Restoration ........................................................................................................................ 24
5.10 Review .............................................................................................................................. 26
5.11 Records ............................................................................................................................. 26
POR126 Data Table 1 ............................................................................................................................... 27
Attachment 1 - Comments Sheet .............................................................................................................. 28
Functional Check Signature Sheet 1 ......................................................................................................... 29
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
3 of 29
1.0 PURPOSE AND SCOPE
1.1 Purpose
To provide instructions to perform a functional check of Portable Exhauster POR126
CAM interlock. This procedure proves the functionality of the fan shutdown relay for all
interlocks.
1.2 Scope
This functional check includes:
A simulated detector failure
A simulated CAM power failure
A simulated high radiation condition
Associated alarms and interlocks.
2.0 INFORMATION
2.1 General Information
2.1.1 During the performance of this Test, any step, group of steps or data entry
that is not applicable shall be identified by "N/A" and an explanation that is
initialed and dated shall be recorded on Attachment 1 - Comments Sheet.
2.1.2 All deviations or discrepancies shall be reported to the Shift Manger
immediately upon completion of this procedure.
2.1.3 Alarms may be acknowledged when activated, but will only clear when the
alarm cause condition has changed.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
4 of 29
3.0 PRECAUTIONS AND LIMITATIONS
3.1 Personnel Safety
3.1.1 If during performance of this procedure any of the following conditions are
found immediately stop work, place equipment in a safe condition, notify
FWS and proceed as directed.
Any equipment malfunction which could prevent fulfillment of its
functional requirements
Personnel error or procedural inadequacy which could prevent
fulfillment of procedural requirements.
3.1.2 If a lock and tag is required during the performance of this procedure, comply
with the DOE-0336, Hanford Site Lockout/Tagout Procedure.
3.1.3 TVIS-AX-001 and the appropriate SEG shall be utilized for work in or on the
exhauster. IH will provide the correct sample plan when contacted.
3.2 Radiation and Contamination Control
3.2.1 Work in Radiological Areas will be performed using a Radiological Work
Permit following review by Radiological Control per the ALARA Work
Planning procedure TFC-ESHQ-RP_RWP-C-03.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
5 of 29
3.3 Environmental Compliance
3.3.1 Tank farm ventilation systems and exhaust monitoring systems are regulated
under Washington State Administrative Code (WAC) Chapters 173-303,
173-400, 173-401, 173-460, and 246-247 and applicable Notices of
Construction issued to ensure compliance with these regulations. To ensure
reporting requirements are met, all planned and unplanned outages of Tank
Farm ventilation equipment and exhaust monitoring systems, including
portable exhausters, (on actively ventilated tanks) must be immediately
reported to Environmental Compliance per Environmental On-Call List.
Environmental will determine and make the required notifications pertaining
to ventilation system outages.
3.3.2 Exhauster and stack monitoring record sampler equipment outage, both
planned and unplanned, must be reported to Environmental per the
Environmental On-Call List.
3.3.3 If functional testing of the Continuous Air Monitor fails, Environmental shall
be notified per Environmental On-Call List.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
6 of 29
4.0 PREREQUISITES
4.1 Special Tools, Equipment, and Supplies
The following supplies may be needed to perform this procedure:
Beta-Gamma Radiation Source capable of generating 10,000 counts per minute
in the CAM
Source Number
Two-way radio or cellular phone required for personnel inside the tank farm
Hearing protection for the noise from radiation cabinet alarms
Password for CAM "Air Monitor System-4 (AMS-4) Beta/Gamma Particle
Monitor" Obtain from instrument supervisor/lead
HP access level password for exhauster HMI, from Shift Manager
CAM Bypass key, from Shift Manager
Vacuum grease, rags
Stopwatch.
4.2 Performance Documents
The following documents may be needed to perform this procedure:
DOE-0336, Hanford Site Lockout/Tagout Procedure
TO-060-126, Operate POR126 Portable Exhaust Ventilation System
6-RM-168, Eberline AMS-4 Continuous Air Monitor Calibration and Field
Installation
TF-OPS-024, Inspections and Source Checks of AMS-4 CAMs and Effluent
Record Samplers an HMI-Controlled Exhausters
DOE-0336, Hanford Site Lockout/Tagout Procedure.
TO-100-052, Perform Waste Generation, Segregation, Accumulation and Clean-
up.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
7 of 29
4.3 Field Preparation
4.3.1 CONDUCT a pre-job safety meeting prior to starting the test. All personnel
participating in the test shall read and understand the test and complete the
Functional Test Signature Sheet.
/ /
Signature Print (First and Last) Date
FWS
4.3.2 IF equipment is found out of service, NOTIFY Shift Manager and OE
immediately.
4.3.3 VERIFY Shift Manager/OE has been informed of planned maintenance,
possible expected alarms, potential impact on waste transfer equipment, and
that there are no ongoing waste transfers associated with this equipment and
approves of the performance of this procedure.
/ /
Signature Print (First and Last) Date
Shift Manager /OE
4.3.4 The OE has notified Environmental Compliance per Section 3.3 that exhaust
stack continuous air monitor functional checking will be conducted.
/ /
Signature Print (First and Last) Date
OE
4.3.5 The Shift Manager shall be notified that all prerequisites in Section 4.3 of this
procedure have been met:
/ /
Signature Print (First and Last) Date
FWS
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
8 of 29
5.0 PROCEDURE
Special Instructions
Failed functional checks require documenting results on work record and data sheet and
following the requirements in the Tank Farm Contractor Work Control procedure (reference
TFC-OPS-MAINT-C-01).
- Data recording is done on POR126 Data Table 1 within this procedure, and attached to
data sheet after completion.
- Exhaust fan may shut down unexpectedly and may be restarted per applicable
operating procedure, as necessary to facilitate completion of this procedure.
- Alarms/annunciators at the following locations may be re-acknowledged as necessary:
Exhauster HMI
Continuous air monitor.
5.1 Initial Conditions
5.1.1 IF functional checking cannot be performed in accordance with this
procedure, PERFORM the following:
5.1.1.1 RETURN equipment to a safe configuration,
5.1.1.2 STOP work
5.1.1.3 NOTIFY Shift Manager and OE.
NOTE - It is not unusual for the "LOW BETA COUNT" alarm to be activated upon
initially energizing the CAM which is done by the Programmable Logic
Controller after the exhauster motor is started. This may be due to software and
clearing status registers anomalies. The "LOW BETA COUNT" alarm will
shut the exhauster back down. If this should occur it is permissible to reset the
alarm and continue with exhauster startup NO MORE THAN twice after which
it should be treated as an actual CAM failure alarm and action taken as
required by alarm response procedures.
5.1.2 LOGIN at HMI with Technician User Name and access level password.
5.1.3 CHECK CAM calibration AND RECORD
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
9 of 29
5.1 Initial Conditions (Cont.)
5.1.4 IF continuous air monitor is within calibration, GO TO Section 5.2.
5.1.5 IF CAM calibration is NOT VALID, PERFORM the following:
5.1.5.1 NOTIFY Shift Manager
5.1.5.2 RECORD the out of calibration condition on Attachment 1 -
Comments Sheet
5.1.5.3 REPLACE CAM per appropriate work package
5.1.6 RECORD the serial number and calibration due date of CAM being tested
on POR126 Data Table 1.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
10 of 29
5.2 CAM Slow Alarm Setpoint
5.2.1 PRESS key [5] on CAM keypad.
5.2.2 RECORD As-Found SLOW ALARM SETPOINT shown on the top line of
the CAM display on POR126 Data Table 1.
5.2.3 IF As-Found slow alarm setpoint is 300 dpm/ft3, GO TO Step 5.2.5.
5.2.4 IF As-Found slow alarm setpoint is NOT 300 dpm/ft3, RESET the slow
alarm setpoint to 300 dpm/ft3 through the following menus:
Press Menu
Enter Password, “Enter”
( -) Key to Alarm Parameters “Enter”
( -) Slow Alarm Setpoint
5.2.4.1 PRESS “EDIT” AND
TYPE “300” to change slow alarm setpoint to 300 dpm/ft3.
5.2.4.2 PRESS “ENTER” on keypad to accept changed setpoint.
5.2.4.3 PRESS “MENU” twice to return CAM to operation.
5.2.5 RECORD SLOW ALARM SETPOINT shown on the top line of the CAM
display on POR126 Data Table 1.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
11 of 29
5.3 CAM Fast Alarm Setpoint
5.3.1 PRESS key [6] on CAM keypad.
5.3.2 RECORD As-Found FAST ALARM SETPOINT shown on the top line of
the CAM display on POR126 Data Table 1.
5.3.3 IF As-Found FAST ALARM SETPOINT is 7,000 dpm/ft3, GO TO
Step 5.3.5.
5.3.4 IF As-Found FAST ALARM SETPOINT is NOT 7,000 dpm/ft3, RESET the
FAST ALARM SETPOINT to 7,000 dpm/ft3 through the following menus:
Press Menu
Enter Password, “Enter”
( -) Key to Alarm Parameters “Enter”
( -) FAST ALARM SETPOINT.
5.3.4.1 PRESS “EDIT” AND
TYPE “7000” to change fast alarm setpoint to 7000 dpm/ft3.
5.3.4.2 PRESS “ENTER” on keypad to accept changed setpoint.
5.3.4.3 PRESS “MENU” twice to return CAM to operation.
5.3.5 RECORD As-left FAST ALARM SETPOINT shown on the top line of the
CAM display on POR126 Data Table 1.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
12 of 29
5.4 CAM Beta Net Alarm Setpoint
NOTE - For the purposes of this test the more conservative environmental limit from
HNF-EP-0479, Tank Farm Facility Effluent Monitoring Plan of 3,000 counts
per minute shall be used.
5.4.1 PRESS key [7] on CAM keypad.
5.4.2 RECORD As-Found (BETA) NET ALARM SETPOINT shown on the top
line of the CAM display on POR126 Data Table 1
5.4.3 IF As-Found (BETA) NET ALARM SETPOINT is 3,000 CPM, GO TO
Step 5.4.6.
5.4.4 IF As-Found (BETA) NET ALARM SETPOINT is not 3,000 CPM, Go-To
Step 5.4.5.
5.4.5 RESET (BETA) NET ALARM SETPOINT to 3,000 CPM through the
following menus:
Press Menu
Enter Password, “Enter”
( -) Key to Alarm Parameters “Enter”
( -) Net Alarm Setpoint
5.4.5.1 PRESS “EDIT” AND
TYPE “3000” to change net alarm setpoint to 3000 cpm.
5.4.5.2 PRESS “ENTER” on keypad to accept changed setpoint.
5.4.5.3 PRESS “MENU” twice to return CAM to operation.
5.4.6 RECORD As-Left (BETA) NET ALARM SETPOINT shown on the top line
of the CAM display on POR126 Data Table 1.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
13 of 29
5.5 Simulate Stack CAM Detector Failure
NOTE - The CAM shuts down the fan on CAM Failures and High Rad conditions.
- Expect a delay of approximately 2 minutes for exhauster alarm interlock to
activate.
5.5.1 CHECK stack CAM ALARM/INDICATOR status per Table:
ALARM/INDICATOR LOCATION STATUS
GREEN READY Lamp VTP-CP-110 CAM Keypad
Inside Panel LIT
AMBER MALFUNCTION Lamp VTP-CP-110 CAM Keypad
Inside Panel NOT LIT
CLEAR STROBE Lamp, VTP-YA-554 Above Sample Cabinet NOT FLASHING
RED STROBE Lamp, VTP-YA-550 Above Sample Cabinet NOT FLASHING
BELL VTP-ENCL-118 Panel SILENT
MONITOR SCREEN ALARM (AMS-4)
NOTIFICATION CHIME "VTP-RT-554" VTP-ENCL-110 Inside Panel SILENT
NO VISIBLE GEMS ALARMS ON HMI
ALARM SCREEN CP-110 VTP-ENCL-110 Panel
HMI ALARM SCREEN
CLEAR
5.5.2 IF any acknowledgeable alarm/indicator status is NOT as listed, RESET the
alarm/indicator.
5.5.2.1 IF NOT correctable, CONTACT Shift Manager for
determination AND
RECORD on Attachment 1 - Comments Sheet.
5.5.3 PRESS MENU on the CAM keypad AND
ENTER the password to access the Maintenance Menu.
5.5.4 PRESS DOWN [] arrow until DETECTOR PARAMETERS is
DISPLAYED.
5.5.5 PRESS ENTER.
5.5.6 PRESS DOWN [] arrow until BETA HIGH VOLTAGE is DISPLAYED.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
14 of 29
5.5 Simulate Stack CAM Detector Failure (Cont.)
NOTE - As-found high voltage value will be restored as recorded.
5.5.7 RECORD As-found BETA HIGH VOLTAGE on POR126 Data Table 1.
5.5.8 PRESS EDIT AND
TYPE "0" to change voltage to zero.
5.5.9 PRESS ENTER on keypad to accept changed voltage.
5.5.10 PRESS MENU twice to return CAM to operation.
NOTE - Expect 1-5 minutes for CAM MALFUNCTION indicator to display on
AMS-4.
- Expect 2 minute delay for Strobe and Exhauster alarms.
5.5.11 CHECK stack CAM ALARM/INDICATOR status per Table below:
ALARM/INDICATOR LOCATION STATUS
GREEN READY Lamp VTP-CP-110 CAM Keypad
Inside Panel NOT LIT
AMBER MALFUNCTION Lamp VTP-CP-110 CAM Keypad
Inside Panel LIT
CLEAR STROBE Lamp, VTP-YA-554 Above Sample Cabinet FLASHING
RED STROBE Lamp, VTP-YA-550 Above Sample Cabinet NOT FLASHING
BELL VTP-Encl-118 Panel NOT SOUNDING
MONITOR SCREEN ALARM (AMS-4)
NOTIFICATION CHIME "VTP-RT-554" VTP-ENCL-110 Inside Panel CHIMING
CAM DETECTOR FAILURE VISIBLE ON
HMI ALARM SCREEN CP-110 VTP-ENCL-110 Panel
Visible on HMI Alarm
Screen "CAM
INSTRUMENT FAILURE"
5.5.12 CHECK exhauster has SHUT DOWN.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
15 of 29
5.5 Simulate Stack CAM Detector Failure (Cont.)
5.5.13 CHECK annunciator status at VTP-ENCL-110:
DISPLAY ANNUNCIATOR TITLE STATUS
HMI Alarm Screen
CP-110
CAM INSTRUMENT FAILURE ALARMED
5.5.14 PRESS "Alarm Ack" BUTTON on CAM VTP-RA-554 to acknowledge
alarm.
5.5.15 CHECK the following:
INDICATOR "Malfunction" AMBER is ON
Horn on Radiation Cabinet is silenced.
RESTORE CAM BETA HIGH VOLTAGE to as-found value:
5.5.16 PRESS MENU on the CAM keypad AND
ENTER password to access the Maintenance Menu.
5.5.17 PRESS DOWN [] arrow until DETECTOR PARAMETERS is
DISPLAYED AND
PRESS ENTER.
5.5.18 PRESS DOWN [] arrow until BETA HIGH VOLTAGE is DISPLAYED
AND
PRESS EDIT.
5.5.19 ENTER as-found value from Step 5.5.7.
5.5.20 RECORD As-Left BETA HIGH VOLTAGE on POR126 Data Table 1.
5.5.21 PRESS ENTER on keypad to accept voltage input.
5.5.22 WAIT for Green Ready Light ON AMS-4
5.5.23 PRESS MENU (twice) to return CAM to operation.
5.5.24 START fans per applicable operating procedure.
5.5.25 RECORD satisfactory completion of “Simulate Stack CAM Detector
Failure” testing on POR126 Data Table 1.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
16 of 29
5.6 Low Sample Flow Rate Alarm Test
NOTE - Expect 2-10 minutes for CAM READY indicator to respond.
- HMI Alarm Screen may display “POR126-VTP-FCV-554 CAM SAMPLE
FLOW LO.”
5.6.1 CHECK stack CAM ALARM/INDICATOR status per Table below:
ALARM/INDICATOR LOCATION STATUS
GREEN READY Lamp VTP-CP-110 CAM Keypad
Inside Panel LIT
AMBER MALFUNCTION Lamp VTP-CP-110 CAM Keypad
Inside Panel NOT LIT
CLEAR STROBE Lamp, VTP-YA-554 Above Sample Cabinet NOT FLASHING
RED STROBE Lamp, VTP-YA-550 Above Sample Cabinet NOT FLASHING
BELL VTP-ENCL-118 Panel SILENT
MONITOR SCREEN ALARM (AMS-4)
NOTIFICATION CHIME "VTP-RT-554" VTP-ENCL-110 Inside Panel SILENT
NO VISIBLE GEMS ALARMS ON HME
ALARM SCREEN CP-110 VTP-ENCL-110 Panel
HMI ALARM SCREEN
CLEAR
5.6.2 CLOSE hand valve VTP-V-554.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
17 of 29
5.6 Low Sample Flow Rate Alarm Test (Cont.)
5.6.3 CHECK stack CAM ALARM/INDICATOR status per Table below:
ALARM/INDICATOR LOCATION STATUS
GREEN READY Lamp VTP-CP-110 CAM Keypad
Inside Panel LIT
AMBER MALFUNCTION Lamp VTP-CP-110 CAM Keypad
Inside Panel NOT LIT
CLEAR STROBE Lamp, VTP-YA-554 Above Sample Cabinet FLASHING
RED STROBE Lamp, VTP-YA-550 Above Sample Cabinet NOT LIT
BELL VTP-ENCL-118 Panel SILENT
MONITOR SCREEN ALARM (AMS-4)
NOTIFICATION CHIME "VTP-RT-554" VTP-ENCL-110 Inside Panel NOT CHIMING
NO VISIBLE GEMS ALARMS ON HMI
ALARM SCREEN CP-110 VTP-ENCL-110 Panel
Visible on HMI ALARM
CAM SAMPLE FLOW LO LO *
* Note - CAM Sample Flow LO will also be received during testing.
5.6.4 CHECK exhauster has SHUT DOWN.
5.6.5 OPEN hand valve VTP-VT-554.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
18 of 29
5.6 Low Sample Flow Rate Alarm Test (Cont.)
5.6.6 ACKNOWLEDGE “POR126-VTP-FCV-554 CAM SAMPLE FLOW LO”
alarm.
5.6.7 ACKNOWLEDGE all secondary alarms displayed in HMI Alarm Screen.
5.6.8 RESTART fan per applicable operating procedure or approved work plan.
5.6.9 CHECK stack CAM ALARM/INDICATOR status per Table below:
ALARM/INDICATOR LOCATION STATUS
GREEN READY Lamp VTP-CP-110 CAM Keypad
Inside Panel LIT
AMBER MALFUNCTION Lamp VTP-CP-110 CAM Keypad
Inside Panel NOT LIT
CLEAR STROBE Lamp, VTP-YA-554 Above Sample Cabinet NOT LIT
RED STROBE Lamp, VTP-YA-550 Above Sample Cabinet NOT LIT
BELL VTP-ENCL-118 Panel SILENT
MONITOR SCREEN ALARM (AMS-4)
NOTIFICATION CHIME"VTP-RT-554" VTP-ENCL-110 Inside Panel SILENT
NO VISIBLE GEMS ALARMS ON HMI
ALARM SCREEN CP-110 VTP-ENCL-110 Panel
HMI ALARM SCREEN
CLEAR
5.6.10 RECORD satisfactory completion of “Low Sample Flow Rate Alarm Test”
testing on POR126 Data Table 1.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
19 of 29
5.7 High Radiation Alarm and Fan Interlock
5.7.1 ENSURE exhaust fan is operating.
SIMULATE HIGH alarm condition:
5.7.2 PRESS MENU on CAM AND
ENTER password to access the Maintenance Menu.
5.7.3 PRESS DOWN [] arrow key until INSTRUMENT PARAMETERS is
DISPLAYED AND
PRESS ENTER.
5.7.4 PRESS DOWN [] arrow UNTIL GAMMA SUBTRACT FACTOR is
DISPLAYED.
NOTE - As-found GAMMA SUBTRACT FACTOR will be restored as the value
recorded.
5.7.5 RECORD As-Found GAMMA SUBTRACT FACTOR onto
POR126 Data Table 1.
5.7.6 PRESS EDIT AND
ENTER zero to change value to zero.
5.7.7 PRESS ENTER to accept input value.
5.7.8 PRESS MENU (twice) to return CAM to operation.
5.7.9 USING an extension handle and/or rod, PLACE AND HOLD gamma
source (V-block) at detector head, pointing towards the beta detector located
at the stack in the "Beta/Gamma Enclosure".
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
20 of 29
5.7 High Radiation Alarm and Fan Interlock (Cont.)
NOTE - CAM Ready light and malfunction light may change status with loss of flow
and fast alarm monitoring conditions, but have no bearing on outcome of
functional check.
5.7.10 CHECK stack CAM ALARM/INDICATOR status per Table below:
ALARM/INDICATOR LOCATION STATUS
GREEN READY Lamp VTP-CP-110 CAM Keypad
Inside Panel LIT
AMBER MALFUNCTION Lamp VTP-CP-110 CAM Keypad
Inside Panel NOT LIT
CLEAR STROBE Lamp, VTP-YA-554 Above Sample Cabinet FLASHING
RED STROBE Lamp, VTP-YA-550 Above Sample Cabinet FLASHING
BELL VTP-Encl-118 Panel RINGING
MONITOR SCREEN ALARM (AMS-4)
NOTIFICATION CHIME"VTP-RT-554" VTP-ENCL-110 Inside Panel CHIMING
CAM BETA HI VISIBLE ON HMI ALARM
SCREEN CP-110 VTP-ENCL-110 Panel
VISIBLE ON HMI ALARM
SCREEN "CAM HI
RADIATION"
5.7.11 CHECK exhauster has SHUT DOWN.
5.7.12 ATTEMPT to RESTART exhaust fan per applicable operating procedure.
5.7.13 CHECK exhaust fan DOES NOT start.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
21 of 29
5.7 High Radiation Alarm and Fan Interlock (Cont.)
5.7.14 REMOVE the gamma source from the CAM area.
5.7.15 PRESS "ALARM ACK" button twice on CAM (AMS-4).
5.7.16 ACKNOWLEDGE “POR126-VTP-RA-554A BETA HI RAD” alarm.
5.7.17 ACKNOWLEDGE all secondary alarms displayed in Alarm HMI ALARM
SCREEN CP-110.
5.7.18 RESTORE GAMMA SUBTRACT FACTOR to As-Found value as recorded
from Step 5.7.5
5.7.18.1 PRESS MENU key on CAM AND
ENTER password to access the Maintenance Menu.
5.7.18.2 PRESS DOWN [] arrow until INSTRUMENT PARAMETERS
is DISPLAYED AND
PRESS ENTER.
5.7.18.3 PRESS DOWN [] arrow until GAMMA SUBTRACT
FACTOR is DISPLAYED AND
PRESS EDIT.
5.7.18.4 ENTER As-Found GAMMA SUBTRACT FACTOR value from
Step 5.7.5 AND
RECORD As-Left GAMMA SUBTRACT FACTOR onto
POR126 Data Table 1.
5.7.18.5 PRESS ENTER to accept input value.
5.7.18.6 PRESS MENU twice to return CAM to OPERATION.
NOTE - CAM malfunction light may be on and should clear within 2-10 minutes of fan
startup.
5.7.19 WAIT for Green Light Ready Light ON AMS-4
5.7.20 START fan per applicable operating procedure, or approved work plan.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
22 of 29
5.7 High Radiation Alarm and Fan Interlock (Cont.)
5.7.21 CHECK stack CAM ALARM/INDICATOR status per Table below:
ALARM/INDICATOR LOCATION STATUS
GREEN READY Lamp VTP-CP-110 CAM Keypad
Inside Panel LIT
AMBER MALFUNCTION Lamp VTP-CP-110 CAM Keypad
Inside Panel NOT LIT
CLEAR STROBE Lamp, VTP-YA-554 Above Sample Cabinet NOT FLASHING
RED STROBE Lamp, VTP-YA-550 Above Sample Cabinet NOT FLASHING
BELL VTP-Encl-118 Panel SILENT
MONITOR SCREEN ALARM (AMS-4)
NOTIFICATION CHIME "VTP-RT-554" VTP-CP-110 Inside Panel SILENT
NO VISIBLE GEMS ALARMS ON HMI
ALARM SCREEN CP-110 VTP-ENCL-110 Panel
HMI ALARM SCREEN
CLEAR
5.7.22 RECORD satisfactory completion of “High Radiation Alarm and Fan
Interlock” testing on POR126 Data Table 1.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
23 of 29
5.8 Exhaust Stack CAM Power Failure
5.8.1 POSITION CAM power switch (located on back of CAM) to OFF.
5.8.2 VERIFY stack CAM ALARM/INDICATOR status per Table below:
ALARM/INDICATOR LOCATION STATUS
GREEN READY Lamp VTP-CP-110 CAM Keypad
Inside Panel NOT LIT
AMBER MALFUNCTION Lamp VTP-CP-110 CAM Keypad
Inside Panel NOT LIT
CLEAR STROBE Lamp, VTP-YA-554 Above Sample Cabinet FLASHING
RED STROBE Lamp, VTP-YA-550 Above Sample Cabinet NOT FLASHING
BELL VTP-Encl-118 Panel NOT SOUNDING
CAM DETECTOR FAILURE VISIBLE ON
HMI ALARM SCREEN CP-110 VTP-ENCL-110 Panel
VISIBLE ON HMI
ALARM SCREEN "CAM
INSTRUMENT FAILURE"
5.8.3 CHECK exhauster has SHUT DOWN.
5.8.4 ACKNOWLEDGE “POR126-VTP-RA-554A BETA CAM FAIL” alarm.
5.8.5 POSITION CAM power switch (located in back of CAM) to ON.
5.8.6 WAIT for Green Ready Light ON AMS-4.
5.8.7 RESTART fan per applicable operating procedure, or approved work plan.
5.8.8 RECORD satisfactory completion of “Exhaust Stack CAM Power Failure”
testing on POR126 Data Table 1.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
24 of 29
5.9 Restoration
5.9.1 CHECK stack CAM ALARM/INDICATOR status per Table below:
ALARM/INDICATOR LOCATION STATUS
GREEN READY Lamp VTP-CP-110 CAM Keypad
Inside Panel LIT
AMBER MALFUNCTION Lamp VTP-CP-110 CAM Keypad
Inside Panel NOT LIT
CLEAR STROBE Lamp, VTP-YA-554 Above Sample Cabinet NOT LIT
RED STROBE Lamp, VTP-YA-550 Above Sample Cabinet NOT LIT
BELL VTP-ENCL-118 Panel SILENT
MONITOR SCREEN ALARM (AMS-4)
NOTIFICATION CHIME "VTP-RT-554" VTP-ENCL -110 Inside Panel SILENT
NO VISIBLE GEMS ALARMS ON HMI
ALARM SCREEN CP-110 VTP-ENCL-110 Panel
HMI ALARM
SCREEN CLEAR
5.9.2 RESTORE Exhaust Stack Radiation Monitor components to the pre-test
configuration,
OR
CONFIGURE Exhaust Stack Radiation Monitor components as directed by
Shift Manager.
5.9.2.1 RECORD directions in Comments Section of Attachment 1 -
Comments Sheet.
5.9.3 REPORT deviations or discrepancies to the Shift Manager/OE AND.
RECORD in Comments Section of Data Sheet.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
25 of 29
5.9 Restoration (Cont.)
5.9.4 FWS and Shift Manager REVIEW POR126 Data Table 1 and Attachment 1
- Comments Sheet AND
RECORD review on POR126 Data Table 1. Radiological Survey Report
(RSR) number(s) or N/A.
RSR Number RSR Number
5.9.5 NOTIFY Shift Manager that testing is COMPLETED.
/ /
Signature Print (First and Last) Date
Field Work Supervisor
/ /
Signature Print (First and Last) Date
Shift Manager /OE
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
26 of 29
5.10 Review
5.10.1 Engineer shall REVIEW AND EVALUATE test data for acceptability.
/ /
Signature Print (First and Last) Date
Responsible Engineer
5.11 Records
The following records are generated during the performance of this procedure and are
maintained in the work package as record material.
5.11.1 SUBMIT the completed records/work package to the supervisor for record
retention.
Steps 4.3.1, 4.3.3, 4.3.4, 4.3.5, 5.10.1, and 5.10.1
POR126 Data Table 1
Attachment 1 - Comments Sheet
Functional Check Signature Sheet 1
The record custodian identified in the Company Level, Records Inventory
and Disposition Schedule (RIDS) is responsible for record retention in
accordance with TFC-BSM-IRM_DC-C-02.
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
27 of 29
POR126 Data Table 1
Serial Number: __________________ Calibration Due Date:____________________ (AC) Acceptance Criteria
As-Found Desired Value As-Left Initial Setpoints: Slow alarm setpoint (DPM/ft³) __________________ 300 (299-301) DPM/ft³ ___________________
Fast alarm setpoint (DPM/ft³) __________________ 7000 (6999-7001) DPM/ft³ ___________________
Beta alarm setpoint (DPM/ft³) __________________ 3000 (2999-3001) DPM/ft³ ___________________
Test Steps * Signature and Date test satisfactorily completed
Stack CAM Detector
Failure Test (Section 5.5)
Tech: / ../.. Signature Print (First and Last) Date
Low Sample Flow Rate Alarm Test
(Section 5.6)
Tech: / ../..
Signature Print (First and Last) Date
High Radiation Alarm and Fan Interlock Test
(Section 5.7)
Tech: / ../..
Signature Print (First and Last) Date
Exhaust Stack CAM Power Failure Test
(Section 5.8)
Tech: / ../..
Signature Print (First and Last) Date
Review Complete
Restoration
(Section 5.9)
FWS: / ../.. Signature Print (First and Last) Date
Shift Manager: / ../.. Signature Print (First and Last) Date
As-Found
As-Left
CAM Detector Failure:
___________ ___________
CAM Power Failure:
Beta High Voltage
Check camber and detector clear: Yes No
High Radiation:
___________ ___________
Gamma Subtract Factor: Check and lube O-Rings (as req’d): Yes No
(If time is greater than 10 minutes, notify Shift Manager/OE)
* - Any discrepancies are to be noted on Comment Sheet 1
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
28 of 29
Attachment 1 - Comments Sheet
Record any comments encountered during performance of test below. *
WORK PACKAGE NO.: DATE:
* If no comments are made, a signature is not required, just N/A.
/ /
Signature Print (First and Last) Date
Commenter
ENVIRONMENTAL RECORD
Perform Portable Exhauster POR126 CAM Interlock Functional Check
Type
CONTINUOUS Document No.
3-RM-694 Rev/Mod
B-1 Release Date
08/08/2016 Page
29 of 29
Functional Check Signature Sheet 1
All persons participating in performance of this Test shall enter their printed name, signature and
initials below.
NAME (PRINT FIRST AND LAST) SIGNATURE INITIALS
lo