April 1, 2014 creative thinking. custom solutions.® creative thinking. custom solutions.® Key Operational Elements of NFPA 99 and “Other” NFPA Standards: Significant Risks in Healthcare Facilities

Upload: ngoquynh

Post on 26-Jun-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

April 1, 2014

creative thinking. custom solutions.®creative thinking. custom solutions.®

Key Operational Elements of NFPA 99 and “Other” NFPA Standards: Significant Risks in Healthcare Facilities

Page 2: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Which Version(s) of NFPA 99 Apply?

1999 2002 2005 2012

Page 3: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

NFPA Standards Referenced By TJC

10 (fire extinguishers) 13 (sprinklers) 25 (inspect/test of

water-based suppress.) 30 (flammable liquids) 45 (labs) 72 (fire alarm) 80 (fire doors)

82 (waste/linen) 90A (air condit./vent.) 96 (cooking) 99 (healthcare) 101 (LSC) 105 (smoke doors) 110 (emergency power) 111 (SEPSS) 1962 (fire hose/nozzles)

3

Page 4: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

What We Know about Healthcare Fires…

Annual Averages, 2006-2010, Healthcare Facilities 6,240 structure fires 6 civilian deaths 171 civilian injuries $52M in property damage

4[Fires in Healthcare Facilities, NFPA, 11/12]

Page 5: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

What We Know about Healthcare Fires…

Structure Fires by Occupancy Type, 2006-2010 Nursing homes – 46% Hospitals and hospices – 23% Mental health facilities – 21% Clinics and doctors offices – 11%

5[Fires in Healthcare Facilities, NFPA, 11/12]

Page 6: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

What We Know about Healthcare Fires…

Structure Fire Deaths/Injuries by Occupancy Type, 2006-2010 Nursing homes – 5 deaths / 110 injuries Hospitals and hospices – <1 death / 32 injuries Mental health facilities – <1 death / 23 injuries Clinics and doctors offices – 0 death / 6 injuries

6[Fires in Healthcare Facilities, NFPA, 11/12]

Page 7: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

What We Know about Healthcare Fires…

Leading Cause (2006-2010)? Playing with heat source Electrical distribution or lighting equipment Heating equipment Smoking materials Intentional Clothes dryer or washer Cooking equipment

7[Fires in Healthcare Facilities, NFPA, 11/12]

Page 8: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

What We Know about Healthcare Fires…

8[Fires in Healthcare Facilities, NFPA, 11/12]

Page 9: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

What We Know about Healthcare Fires…

How Do We Compare with Other Industries (2006-2010)? 1.2% of U.S. structure fires 0.2% of U.S. structure fire deaths 1.1% of U.S. structure fire injuries 0.5% of U.S. direct property loss

9[Fires in Healthcare Facilities, NFPA, 11/12]

Page 10: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

What We Know about Healthcare Fires…

Sprinkler Systems in Structure Fires, 2006-2010 Present in 55% of fires 98% effective in controlling fire, when operating Average loss per fire:

– $13,000 without automatic extinguishing system– $5,000 with sprinkler protection

10[Fires in Healthcare Facilities, NFPA, 11/12]

Page 11: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

What We Know about Healthcare Fires…

11[Fires in Healthcare Facilities, NFPA, 11/12]

Page 12: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

What We Know about Healthcare Fires…

12[Fires in Healthcare Facilities, NFPA, 11/12]

Page 13: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are
Page 14: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Corridor – NFPA Standards

Lighting/emergency lighting – 101/99/110/70 Corridor width - 101 Corridor construction – 101/220 Possible fire barriers – 101/251 Finishes – 101 Smoke-resistant ceiling - 101 Door construction/latching/undercut – 101/80/252 Smoke barrier doors – 101/105/80

14

Page 15: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Corridor – NFPA Standards (contd.)

Fire extinguisher – 101/10 Sprinkler system – 101/13/25/20 Fire alarm system – 101/72 Smoke detector – 101/72 Exit signs -101/170 Communication system (speaker) – 101/99 HVAC system – 101/90A/99

15

Page 16: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are
Page 17: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Generator – NFPA / Other Standards

Generator – 99/110 Fuel oil storage – 30/704/IFC Battery maintenance/safety – 110/1926.441 Sprinkler system – 13 Lighting/emergency lighting – 101/99/70/110

Noise exposure – 1910.95 Portable wood ladders – 1910.25

17

Page 18: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

2000 LSC References to 1999 NFPA 99

8.4.4 exception 8.4.5 9.2.4 18.2.9.2 18.2.10.2 Table 18.3.2.1 18.3.2.2 18.3.2.3 18.3.2.4 18.5.1.2

18.5.1.3 19.3.2.2 19.3.2.3 19.3.2.4 20.2.9.2 20.3.2.1 20.3.2.2 21.2.9.2 21.3.2.1 21.3.2.2

[101: 2.1]

Page 19: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

1999 NFPA 99 - Hospital Requirements

1.2.3.4.5.6.7.8.9.10.11.12.13.14.15.16.17.18.19.20.

IntroductionDefinitions

General Chapters

Hospital Requirements

Other Healthcare Facilities

Page 20: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

True or False?

New ConstructionNFPA 99 applies to new construction.

Page 21: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

True or False?

Existing FacilitiesNFPA 99 applies to existing facilities.

Page 22: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Application of NFPA 99

“This document shall apply to all healthcare facilities. Construction and equipment requirements shall be applied only to new construction and new equipment, except as modified in individual chapters. Only the altered, renovated, or modernized portion of an existing system or individual component shall be required to meet the installation and equipment requirements stated in this standard.”

[99: 1.2]

Page 23: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

“The scope of this document is to establish criteria to minimize the hazards of fire, explosion and electricity in health care facilities...”

[99: 1-1; 3-2]

Scope

Electrical Hazards

Electrical shock

Thermal injury

Power interruption

Page 24: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

3,095 Federal/State inspections of Ambulatory Healthcare, Hospitals and Nursing/Residential Care Facilities

582 Federal/State inspections of hospitals

1,472 Federal/State inspections of Nursing/Residential Care Facilities

– (5,724 hospitals in U.S., AHA 2013)– (15,683 nursing homes in U.S., CMS 2011)– (31,100 residential care facilities in U.S., CDC 2010)

OSHA in Healthcare FY2013

Page 25: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

OSHA Top 11 List for Healthcare (Federal OSHA Inspections, FY2013)

1. Bloodborne Pathogens2. Hazard Communication3. Wiring Methods,

Components and Equipment for General Use

4. General Requirements (Electrical)

5. Lockout/Tagout

6. Medical Services and First Aid

7. General Requirements (PPE)

8. Maintenance, Safeguards, and Operational Features for Exit Routes

9. Respiratory Protection10. Eye and Face Protection11. Forms (Injuries/Illnesses)

Page 26: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Temporary power and lighting used for renovations, maintenance, 90-day decorations, experiments, and emergencies only

Unused openings in cabinets closed Junction boxes provided with covers No live parts on appliances, fixtures, lamps, and

receptacles Ventilation for battery storage areas No storage in transformer vaults

Wiring Methods, Components, and Equipment for General Use (29 CFR 1910.305)

Page 27: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Electrical equipment free of damaged parts Electrical equipment marked with manufacturer and

rating Disconnecting means for motors, appliances, and

circuits marked with purpose Clearance (3 ft) for <600v electrical equipment Live parts (≥50v) guarded against accidental contact

(cabinet, vault, 8 ft elevation, etc.) “DANGER-HIGH VOLTAGE” signs for rooms or

enclosures with live parts >600v

General (Electrical) (29 CFR 1910.303)

Page 28: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Working Clearances for Electrical Equipment (OSHA)

3’ minimum clear distance 2.5’ width clear distance 6.25’ headroom

Page 29: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

OSHA Clearances around Electrical Equipment

Equipment @ 0-150 volts = 3 feet Equipment @ 151-600 volts with exposed live parts

on one side and no live or grounded parts on the other side = 3 feet

Equipment @ 151-600 volts with exposed live parts on one side and grounded parts on the other side = 3.5 feet

Equipment @ 151-600 volts with exposed live parts on both sides of the work space = 4 feet.

Plus more for 600+ volts…29

Page 30: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Adequate Clearance

Page 31: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Working Clearance around Generating Equipment?

a) 24”b) 30”c) 36”d) 42”e) No requirement

31

Page 32: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Electrical Protective Devices

Insulating blankets, matting, covers, line hose, gloves, and sleeves made of rubber

Written, certified hazard assessment Maintained in safe, reliable condition Periodic testing:

– Insulating gloves every 6 months– Insulating sleeves at least annually

32

Page 33: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

January, 2011 5 Serious and 1 Repeat Citations $63,000 (including $35,000 for repeat citation) Key Citations:

– Unused openings in cabinets, boxes, and fittings shall be effectively closed ($35,000 penalty) (1910.305)

– Electrical protective devices (1910.137)– Selection and use of work practices, electrical

(1910.333)

Hospital (MA) - Inspection

Page 34: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Oxygen Cylinder Storage

Oxygen CylindersHow many “E” sized oxygen cylinders may be stored within 1 smoke compartment without taking any special separation or enclosure precautions?

Page 35: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Oxygen Cylinder Storage

Oxygen CylindersHow many “E” sized oxygen cylinders may be storedwithin 1 smoke compartment without taking any special separation or enclosure precautions?

300 ft3 ÷ 25 ft3/container = 12 containersApplies to all non-flammable compressed gases

Page 36: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Compressed Gas Cylinder Storage Requirements

Storage and manifold rooms for piped gas systems –Chapter 4, 1999 NFPA 99

Other cylinder storage rooms (e.g., Respiratory Therapy) – Section 9.4, 2005 NFPA 99

Page 37: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Storage Requirements?

Exit access corridor

Respiratory therapy department

20’

25’

Shelving

RT storage room

O2 cylinder storage area

Page 38: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Storage Requirements – 2005 NFPA 99 (applies to all nonflammable gases)

Exit access corridor

Respiratory therapy department

20’

25’

RT storage room

Shelving

O2 cylinder storage area

Less than 3000 ft3: -Noncombustible construction-Doors preventing unauthorized entry-No flammable gas/liquid stored with O2 / N2O

No combustibles within 5’ (sprinklered)No combustibles within 20’ (non-sprinklered)Or cylinders in ½-hr FPR cabinet

Page 39: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Storage Requirements – 2005 NFPA 99(applies to all nonflammable gases)

Exit access corridor

New healthcare, respiratory therapy department

20’

25’

RT storage room

Shelving

O2 cylinder storage area

≥ 3000 ft3: -1-hr FRR barrier-Individual securing ofcylinders not required-Dedicated mechanical ventilation-More…

Page 40: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Door Signage

CAUTION

OXIDIZING GASES STORED WITHIN

NO SMOKING

Page 41: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Posted at Patient Rooms?

Page 42: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

New healthcare

Required Separation?

Exit access corridor

Oxidizing gas cylinder manifold room(any quantity)

Page 43: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

New healthcare

Required Separation

Exit access corridor

Oxidizing gas cylinder manifold room(any quantity)

1-hr FRR barrier

No other purpose for roomNo storage of combustible materials

Page 44: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Bulk System

An assembly of equipment with storage capacities of more than

– 28,000 cubic feet (NTP) of nitrous oxide, or – 20,000 cubic feet (NTP) of oxygen, including

unconnected reserves

Bulk O2 – see NFPA 50Bulk Nitrous Oxide – See CGA Standard for Installation of Nitrous Oxide Systems at Consumer Sites

Page 45: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Securing of Gas Cylinders

Page 46: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Required Labeling for Medical Gas, Vacuum and WAGD Piping?

Exit access corridor

New or existing healthcare

Medical gas piping

40’

50’

Page 47: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Exit access corridor

New or existing healthcare

Medical gas piping

40’

50’

Gas name & operating pres.At least every 20’At least once in each roomEvery story

Required Labeling for Medical Gas, Vacuum and WAGD Piping?

Page 48: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Shutoff Valve Labeling

Name of gas Caution not to close except in emergency Rooms or areas served

CAUTION

(Name of gas) VALVE

DO NOT CLOSE EXCEPT IN EMERGENCY

THIS VALVE CONTROLS SUPPLY TO _____

Page 49: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Vacuum Valve Labeling

CAUTION

MEDICAL-SURGICAL VACUUM VALVE

DO NOT CLOSE EXCEPT IN EMERGENCY

THIS VALVE CONTROLS VACUUM TO…

Page 50: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Inhaled Anesthetic Agents

Generic or chemical name Commercial name Year of

introduction Currently in use?

Diethyl ether Ether 1842 NoNitrous oxide Nitrous oxide 1844 YesChloroform Chloroform 1847 No

Cyclopropane Cyclopropane 1933 NoTrichloroethylene Trilene® 1934 No

Fluroxene Fluoromar® 1954 NoHalothane Fluothane® 1956 Yes

Methoxyflurane Penthrane® 1960 InfrequentlyEnflurane Ethrane® 1974 YesIsoflurane Forane® 1980 YesDesflurane Suprane® 1992 YesSevoflurane Ultane® 1995 Yes

[Anesthetic Gases: Guidelines for Workplace Exposures, OSHA, 5/18/00]

Page 51: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Exposure Limits

Anesthetic Gas

OSHA PEL (ppm)

NIOSH REL (ppm)

ACGIHTLV-TWA

(ppm)Nitrous Oxide None 25 50

Isoflurane None 2 (1-hr ceiling) None Halothane None 2 (1-hr ceiling) 50 Desflurane None 2 (1-hr ceiling) None Sevoflurane None 2 (1-hr ceiling) None Enflurane None 2 (1-hr ceiling) 75

Methoxyflurane None 2 (1-hr ceiling) None

Page 52: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

52

Patient Room Door

Reprinted with permission from Report on Hartford, CT Nursing Home Fire, Copyright © 2003 NFPA.

Page 53: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

53

16 Fatalities

Fire origin

XX X

XX XXXXXX

Smoke barriers

Reprinted with permission from Report on Hartford, CT Nursing Home Fire, Copyright © 2003 NFPA.

Page 54: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

54

Name Requirements for Fire Doors

Page 55: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

55

No deadbolt/lock*

Fire Doors

Rating

Latch hardware

Self-closing

1/8” gap 3/4” undercut*

Coordinator

Plates <16”*

No coverings

Vision panelFPR/sizeSwing w/ egress*

[101:7.2.1, 8.2.3 and NFPA 80]

Page 56: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

NFPA 80 Maintenance

15-2.5.4 When holes are left in a door or frame due to changes or removal of hardware or plant-ons, the holes shall be repaired by the following methods:(a) Install steel fasteners that adequately fill the holes(b) Fill the screw or bolt holes with the same material as the door or frame

56

Page 57: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

57

Fire Extinguishers - Compliant or Not?

Exit access corridor

New or existing constructionFire Extinguisher

40’

50’

Page 58: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

58

Fire Extinguishers

Exit access corridor

New or existing construction (ordinary hazard*)Fire Extinguisher

40’

50’

Travel distance ≤ 75’ for class A hazards

1,500 ft2 coverage per unit of A*(e.g. 2A = 3,000 ft2)

[NFPA 10:6.2.1]

Page 59: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Compliant or Not?

Laboratory

Exit access corridor

New or existing healthcare

Flammableliquid storage cabinet

Fire Extinguisher

40’

50’

Page 60: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Class B Hazards

Laboratory

Exit access corridor

New or existing healthcare, ordinary hazard

Flammableliquid storage cabinet

Fire Extinguisher

40’

50’

Travel distance for class B hazards: ≤ 30’ for 10B rating≤ 50’ for 20B rating

Page 61: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Compliant or Not?

Kitchen

Exit access corridor

New or existing healthcare

Fryer with oil

Fire Extinguisher

40’

50’

Page 62: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Probably Not Compliant

Kitchen

Exit access corridor

New or existing healthcare

Fryer with oil

Fire Extinguisher

40’

50’

K extinguisher*Travel distance ≤ 30’Placard instructing to

activate fire suppress. system first

Page 63: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Auto Extinguishing System for Grease-Producing Cooking Devices

Activates fire alarm Deactivates fuel source LS.02.01.35 Controls exhaust fans Inspected semi-annually (EC.02.03.05) Fusible links/sprinkler heads replaced annually if

they have buildup of grease

63

Page 64: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

29 CFR 1910.151 (First Aid) and NFPA 99: 10-6 (1999 edition):

“Where the eyes or body…may be exposed to corrosive materials…facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use.”

Emergency Eye Wash and Shower Equipment

Page 65: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

OSHA Top 11 List for Healthcare (Federal OSHA Inspections, FY2013)

1. Bloodborne Pathogens2. Hazard Communication3. Wiring Methods,

Components and Equipment for General Use

4. General Requirements (Electrical)

5. Lockout/Tagout

6. Medical Services and First Aid

7. General Requirements (PPE)

8. Maintenance, Safeguards, and Operational Features for Exit Routes

9. Respiratory Protection10. Eye and Face Protection11. Forms (Injuries/Illnesses)

Page 66: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

True or False?

Emergency Eye Wash and Shower EquipmentEmergency eye wash and shower units shall be flushed weekly.

[ http://path.upmc.edu]

Page 67: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Maintenance

Eye wash fountains inspected at least every 3 months (OSHA recommendation)

Emergency eye wash and shower equipment tested periodically (NFPA 99)

Page 68: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Practical Considerations

Privacy curtains Drains “Tepid” water Travel time of 10 seconds Weekly activation vs. annual

performance testing Inspection tags

Page 69: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Expiration Dates!

Page 70: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Laboratory Chemical Hoods

Page 71: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Signage Required on EFs?

New or Existing healthcare

Laboratory

EF

Exhaust duct

Exhaust fan EF

General exhaust duct

Fume hood

Page 72: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Signage Required on EFs

New or Existing healthcare

Laboratory

EF

Exhaust duct

Exhaust fan EF

General exhaust duct

Arrow indicating fan rotationHoods/areas servedHazard warning

Fume hood

Page 73: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

True or False?

Laboratory Fume HoodsA permanently-installed airflow measuring device is required on fume hoods.

Page 74: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Fans and Motors

Air supply and exhaust fans, motors, and components shall be inspected at least annually.

Page 75: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

Is Healthcare a Priority for OSHA?

Page 76: TAHFM NFPA 99 2014 - c.ymcdn.comc.ymcdn.com/.../resmgr/interlink_2014/tahfm_2014_-_nfpa_99_leo_old… · 96 (cooking) 99 (healthcare) ... NFPA 80 Maintenance 15-2.5.4 When holes are

OSHA National Emphasis Program:“Targeted Enforcement”

Recordkeeping Ergonomics (musculoskeletal disorders associated

with resident handling) Slips, trips, and falls Bloodborne pathogens Tuberculosis Workplace violence