tan delta / dissipation factor as an effective tool in ... educational program spring 2001. benefits...

17
ICC Educational Program Spring 2001. Tan Delta / Dissipation Factor As An Effective Tool In Determining The Insulation Condition Of Power Cables Using The BAUR PHG VLF System. Craig Goodwin, HV Diagnostics Inc. GA, USA e-mail: [email protected]

Upload: tranduong

Post on 12-Mar-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Tan Delta / Dissipation Factor As AnEffective Tool In Determining The

Insulation Condition Of Power CablesUsing The BAUR PHG VLF System.

Craig Goodwin, HV Diagnostics Inc. GA, USAe-mail: [email protected]

Page 2: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Summary of Presentation

• Theory / Background

• Description of Diagnostic Method/s

• Field Examples

Page 3: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Benefits of Voltage Testing with VLFSinusoidal Waveforms in the field.

� Low Power Requirement for on site testing. � Compact portable design of test equipment.� Easier diagnosis of water tree deteriorated insulation at low frequencies compared to higher frequencies such as 60Hz using TD.� Easier to integrate Cable diagnostic interfaces such as TD and PD etc.

Page 4: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

"WATER TREEING" in polymeric insulation(schematic layout)

● electrical field conditions for possible● water water development of● disturbance field "water trees"● time

outer semiconductinglayer

insulation

inner semiconductinglayer

conductor

"bow-tie trees"

"vented trees"

Page 5: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.ICC Educational Program Spring 2001.

Vented- tree growing from the inner semiconVented- tree growing from the inner semiconlayer of a 30 kV- PE- cable

Page 6: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Dielectric Failure of insulation originating from a watertree

Page 7: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

What is Dissipation Factor ( tan δ) ??

time/sec0 10

voltage

current

= U RU C

²/².ω

1ωCR.

dissipation factor tan δ = true power reactive power

=

Page 8: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Simplified Dielectric Equivalent Circuit of aWater Tree

w t

R1C1

R2 C2

>>

Page 9: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

AC Pure Sinewave Output Voltage andCurrent.

Page 10: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Do I have a DF dependancy regarding thetotal length or the amount of joints in acable?

NO!

Q & AQ & A

Page 11: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Voltage Dependence of 0,1 Hz Tan Delta on Newand Service-aged XLPE-insulated Medium Voltage

Cables.

0

1

2

3

4

5

6

7

8

9

1 0

0 0 .5 1 1 .5 2 2 .5 3

V /V 0 (A p p lie d V o lta g e )

0.1

Hz

Dis

sip

ati

on

Fa

c

G ood c ab le S ligh tly s e rvic e -aged (1 ) Mode ra te ly s e rvic e -a ged (2 )

Mode ra te ly s e rvic e -a ged (3 ) S trong ly s e rv ic e -aged (4 )

Ta nD e lta . (1 0 - 3)

Page 12: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Cables are still in good condition, if :

tan δ (2 Uo) < 1,2 ‰ and

[tan δ (2 Uo) - tan δ (Uo)] < 0,6 ‰

Cables in bad condition (or to be replaced immediately ) if :

tan δ (2 Uo) ≥ 2,2 ‰ or

[tan δ (2 Uo) - tan δ (Uo)] ≥ 1,0 ‰

EPR and TR - XLPE cables have higher absolute values of TanDelta than the above XLPE values, however the change in TanDelta is still the important criteria to take note of.

Criteria For tan Criteria For tan δδ – for PE or XLPE – for PE or XLPE

Page 13: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Field Test Result for an 1974 XLPE Cable

Good Resultfor an old Cable.

Page 14: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Field Test Result for an 1984 XLPE Cable

Nominal OperatingVoltage: Vo = 14kV

PDIV: only at 19kV

Note: TD values are poor even at Vo.

Page 15: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Comparison of Cable Diagnostic SystemsIR C R e c o v e r y D is s . F a c to r S p e c tr o s c o p y

A n a ly s is V o lta g e V L F ta n d V L F ta n d

D ia g no s is s t ro n g ly a g e d c a b le s 0 - + +

In f lue nc e o f d is tu rb a n c e s - 0 + +

R e pro du c ib i li ty o f m e a s u re m e n ts - + + +

D ia g no s t ic te s t t im e - - + +

In f lue nc e o f T e m p e ra tu re + - + -

R E F .: R E F .: I P H B e r lin

S IN T E F R e p o rt, N 7 4 6 5 T ro n d h e im D r. I n g . R . P la th T U B e r lin

S . H v id s te n , J .T . B e n ja m in s e n P ro f . D r. W . K a lk n e r V E W E U R O T E S T

T R A 5 0 7 2 , A u g . 2 0 0 0 D ip l. I n g . I . K ra g e

Key:0 OK+ Pos. - Neg.

Page 16: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Other Applications and Techniques available using theTan Delta measurement:

● Measurement of TD and Capacitance with respect to

Frequency ( Dielectric Spectroscopy).

● Application of TD as a reference signature andmethod

for determining moisture ingress for PILC cables.

Page 17: Tan Delta / Dissipation Factor As An Effective Tool In ... Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement

ICC Educational Program Spring 2001.

Conclusions of Tan Delta Diagnostics

● A TD cable assessment system can clearlydistinguish between new, medium and strongly aged extruded

cable insulation.

● Water trees which are a major original source of insulation failures in aged extruded cables can be detected in a non-destructive manner.

● Excellent Field Results.

● To detect singular defects, a combined assessment system including the application of partial discharge measurement and location in addition to TD is necessary.