On replying indicate: Ref No. FB.292/369/01/K/145 Date: 27th October, 2021 TO ALL BIDDERS, RE: TENDER NO. PA/031/2020-21/W/23 FOR ENGINEERING, PROCUREMENT
AND CONSTRUCTION CONTRACT FOR CONSTRUCTION, INSTALLATION, TESTING AND COMMISSIONING OF COMPRESSED NATURAL GAS (CNG)
REFUELLING STATION FOR DART BUSES AT UBUNGO DEPOT; DAUGHTER CNG STATIONS AT FERRY FISH MARKET, KIBAHA AND MUHIMBILI.
Sub: Clarification response
TPDC acknowledges receipt of the clarifications on the above mentioned tender and would like to provide responses as per attached matrix. 2. We look forward to your firm participation.
Yours faithfully,
Edwin Riwa
For: MANAGING DIRECTOR
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
NO. ITB SECTION SUBJECT BIDDER’S REQUEST TPDC RESPONSE
1
19028-DES-
ME-DPL-008
(DAUGHTER
STATION 1 _ 3
REST ROOM)-
REV A
19028-DES-
ME-DPL-009
(DAUGHTER
STATION
2 REST
ROOM)-REV A
Bathroom
Please kindly clarify whether there
is a sanitary ware inside the
bathroom and whether there is a
drainage facility for the bathroom.
Bidders should note that, the detailed
Sanitary ware includes ablutions such as
CV’s and sinks.
The sites have the existing drainage
facilities, bidders will have to undertake all
the pipeline works for the connection from
bathrooms to the existing drainage system
at each specific site. Contractor can refer to
the provided civil drawings.
2
PA/031/2020-
21/W/23
Control
Philosophy
Telecommunicati
on
According to Control Philosophy,
2.1 Mother Station Control
Philosophy, "Through use of
wireless connections (serial link),
signals will be transmitted from the
various daughter station and other
mother station to the centralized
control room located at mother
station 1, enabling an overview of
operations at all mother and
daughter station."
Please kindly clarify the specific
communication mode of wireless
connection (serial link). Please
kindly clarify whether the signals to
be transmitted by the daughter
Refer to Item No. 3 below. It is confirmed
that among the signals to be transmitted by
the daughter stations are instrument data,
CCTV, security alarm system and fire alarm
system.
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
station are instrument data, CCTV,
security alarm system and fire
alarm system.
3
PA/031/2020-
21/W/23
TENDERING
DOCUMENT
Telecommunicati
on
According to TENDERING
DOCUMENT, 3.7 BATTERY
LIMITS "The meters should be
supplied with pressure regulators,
Pressure Gauges, Safety Valves,
PTZ, electronic volume correctors
and its associated connection
fittings with the ability to transfer the
collected data remotely via
GSM/GPRS/SMS modem. "
Please kindly confirm that the
installation position of the meters
are covered by GSM / GPRS / SMS
signal.
Yes it is confirmed that the installation
position of the meters are covered by GSM
/ GPRS / SMS signal. Also there is network
coverage on the proposed stations.
4
PA/031/2020-
21/W/23
TENDERING
DOCUMENT
Security
The bidder understands that the
security alarm system refers to the
access control system. Bidder
requests Owner to confirm Bidder’s
understanding.
It is confirmed
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
5
19028-DES-
ME-DPL-005
(MOTHER
STATION 2)
OPTION A
Fence and
pavement in
MS2
Please kindly clarify whether the
fence and concrete pavement for
vehicle in MS2 are in Bidder's
scope of work or in DART Bus
Terminal’s scope of work.
Bidders’ scope of work does not involve the
pavement of the parking area for the
vehicle/ buses. Bidders who have visited
the site on 12th October 2021 for MS2
station witnessed that the whole area of the
depot was fenced and concrete paved.
Thus fences and modification of the
concrete base/ foundation will be applicable
to only areas where CNG project equipment
will be installed.
6
Pressure
Equipment
Data Sheets
(Such as
19028-TPDC-
ME-DAS-002
(Cascade
Storage MS2
Rev C), 19028-
TPDC-ME-
DAS-004
(Compressor
M2 Rev
C),etc.)
Mechanical
As per Pressure Equipment Data
Sheets (Such as 19028-TPDC-ME-
DAS-002 (Cascade Storage MS2
Rev C), 19028-TPDC-ME-DAS-
004 (Compressor M2 Rev C),etc.):
Pressure Equipment shall be
marked CE or ASME U-stamped.
Owner is requested to confirm
ASME U-stamped or CE-PED
marked is mandatory requirement?
if yes, please provide the list of CE
directives as applicable to project.
It is confined that ASME U-stamped or CE-
PED marked is mandatory requirement for
all pressure vessels.
For CE marking, please refer to the
requirements as set out in: Pressure
Equipment Directive 2014/68/EU
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
7
PA/031/2020-
21/W/23
TENDERING
DOCUMENT
3.12 3.13
Electrical
As per TENDERING DOCUMENT,
the selected 11kV overhead line will
be inspected, connected to the
station’s miniature substation and
recommissioned for use. Bidder
requests Owner to clarify the
location of station’s miniature
substation.
Bidders should refer to the plot layout
designs and detailed drawings of each
station.
Bidder’s may undertake further own site
visits to verify the locations.
8
1)
TENDERING
DOCUMENT -
CONSTRUCTI
ON, TESTING
AND
COMMISSION
ING OF
COMPRESSE
D NATURAL
GAS (CNG)
2)19028-
TPDC-PR-
RPT-001 Rev
0.5 (Basis of
Design)
Cathodic
protection
Bidder notice the cathodic
protection for underground piping is
not mentioned in technical
documents. And there is no
cathodic protection BOQ for
underground piping in SECTION
VIII (BILL OF QUANTITIES) of
TENDERING DOCUMENT.
Bidder understands that the
underground piping do not require
cathodic protection.
Bidder requests Owner to confirm
Bidder’s understanding.
Bidder’s are advised to adhere to SECTION
VI: EMPLOYER’S REQUIREMENTS AND
TECHNICAL SPECIFICATIONS
where under item 3.11 it specified that any
below ground steel infrastructure will
require cathodic protection, which will be
designed according to the actual site soil
resistivity.
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
9
19028-TPDC-
PR-RPT-005
(Hydraulic
Report);
19028-TPDC-
ME-LST-
002(MS2 Line
List)
Pipeline Material
According to the Hydraulic Report
(19028-TPDC-PR-RPT-005)-
Chapter 2.2.1.2 Table2-3,the value
for the pipeline is HDPE PE100
PN16. However, the MS2 Line List
(19028-TPDC-ME-LST-002)
mentioned that the Material for the
pipeline is HDPE PE100 PN 10
SDR 11. Considering the
requirements of specification 4437,
Bidder understands that the
pipeline material is HDPE PE100
PN 10 SDR 11.
Bidder requests Owner to confirm
Bidder’s understanding.
Bidders must note that, the pipeline material
required is HDPE PE100 PN 16 SDR 11.
10
19028-TPDC-
PR-RPT-001
Rev 0.5 (Basis
of Design)
Pipeline Tie-
in(MS2)
According to the Basis of Design
(19028-TPDC-PR-RPT-001)-
Chapter 8.1 CNG Tie-in and
Distribution Lines, for gas supply to
the mother stations, buried HDPE
distribution lines will be used to
supply gas from the existing 12''
HDPE pipeline, using the NNGI
BVS No.15 distribution network.
Bidder understands that the
welding operation for the pipeline
tie-in will be conducted after
shutdown of the NNGI BVS No.15
The tie-in will be made at the existing 12”
HDPE PE 100 SDR 11 where hot tapping
will be required. The Contractor shall
ensure that the supply of natural gas to
downstream customers is not affected
when undertaking hot tapping exercise.
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
and will not operate under
pressure.
Bidder requests Owner to confirm.
11
19028-TPDC-
PR-RPT-002
(Process
Description):
Design
Drawings (
PID for Mother
Station 2)
Desiccant Dryer
System
According to contractor’s project
experience, desiccant dryer system
is commonly composed of 2 gas
dryers, one is for dehydration, and
the other is for regeneration.
Moreover, upstream coalescing
filters, desiccant dryer system and
upstream coalescing filters will be
combined and supplied as pre-
Dehydration Skid. And there will be
a dehydration regen gas heater for
regeneration.
However, in the drawings, there is
only one desiccant dryer for each
line. Contractor understand that
one combination of upstream
coalescing filters, desiccant dryer
system and upstream coalescing
filters is for dehydration, while the
standby combination is for
regeneration. Both of combinations
will be supplied together as one
pre-Dehydration Skid. And a
dehydration regen gas heater is
added in pre-Dehydration Skid.
The provided desiccant system on the
drawings was indicated as a vendor item,
desiccant dryer system will most likely
consist out of two separate vessels, with a
centralised control panel.
Bidders should take note that, the
combination as referred in this clarification
(i.e the mainstream combination and
standby combination) each stream should
have a complete set of dehydration and
regeneration system.
The indicated lines are for duty/standby
operation. One line will be used to
continuously operate whereas the other
will be used during maintenance activities
of the duty line.
Duty line and standby line will included its
own desiccant drying system (as supplied
by vendor)
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
Please confirm whether
contractor’s understanding is
correct.
12
PA/031/2020-
21/W/23
TENDERING
DOCUMENT
Telecommunicati
on;
Instrumentation
According to 3.7 BATTERY LIMITS
from TENDERING DOCUMENT
Prepaid smart meter is required for
DS1, and the meters shall be inte
grated with the existing vending sy
stem.
Please Provide the existing vendin
g system information
model, specification, mode of data
transfer. etc.
The following are the details requirement for
meters to integrated with the existing
vending software
1. Supports Windows server 2012 and
above
2. Supports bidirectional data
communication
3. Mode of communication via GPRS
and/or WIFI
4. Compliant to STS standard
IEC62055-41/51
5. Generate customizable reports
6. Capture GIS info
7. Generate tokens
8. Token generation software should
be able to generate an STS token for
a specific meter using a decoder key
without direct communication to the
meter.
9. The meter software should be able to
generate tokens (encrypt) which can
then be used to decode tokens
(decrypt) on existing LAISON LAPIS
meters.
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
13
PA/031/2020-
21/W/23
TENDERING
DOCUMENT
19028-TPDC-
PR-RPT-005
(Hydraulic
Report)
Piping
According to site survey, all the 48
sets of cooking burners meters
Daughter Station 1 will be installed
in the station rest room.
And refer to the tendering
document and Hydraulic Report ,
Bidder understands that :
All burners are in in the point A (fish
market) which is shown in the
‘’Hydraulic Report Figure 2-3:
Daughter Station 1 HDPE
Distribution Network’’, and the
piping connection from the meters
to the individual stoves is under
bidder’s scope.
For point F and G, PE pipeline is
under bidder’s scope, the
downstream installation is out of
bidder’s scope, the interface is 2m
outside the building of F and G.
Bidder requests Owner to confirm
Bidder’s understanding.
CONFIRMED the scope of the assignment
is as given in the SECTION VI:
EMPLOYER’S REQUIREMENTS AND
TECHNICAL SPECIFICATIONS
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
14
PA/031/2020-
21/W/23
TENDERING
DOCUMENT
Control room
refer to the tendering document 3.5
:This control room will be hosted
in the general office building block,
to be provided by DART.
Bidder consider power distribution
room is also needed for this project.
So bidder consider all the room
needed will be provided by DART,
and only equipment and associated
installation is under bidder’s scope.
Bidders should note that, the control room
will be hosted in the general office building
block which will be provided by DART. The
room also will host the power distribution
boards, severs, etc. The room will not host
gas generators.
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
Bidder requests Owner to confirm
Bidder’s understanding.
15
TPDC’s
Response
For 4th NO.2
clarification
(3D drawing)
3D drawing
Refer to Owner’s response:
Axle side diagram for restroom for
DS1&2&3 should be submitted as
part of the 3D drawings for each
station.
Bidder requests Owner to clarify
drawing types included in the 3D
drawing.
Bidders are advised to adhere to the
requirement of the Tender document where
bidders needs to provide Civil structure
drawings and Architectural drawings for all
stations. Including Architectural 3D
drawings for all equipments layout for all the
sites plus 3D model of design drawings for
each station
Drawing types should be in DWG. as well
as PDF format, drawn using an Autodesk or
other similar drawing software
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
16
GCC 50.1
Section IV
General
Conditions of
Contract
SCC 18
Section V
Special
Conditions of
Contract
Payment
Schedule
According to GCC 50.1, payment
shall be certified by Project
Manager and be paid by Employer
on monthly basis.
According to SCC 18, payment will
be made as per five (5) milestones,
not monthly payment.
TPDC is requested to clarify which
payment term shall apply.
Payments shall be made based on the
milestones. This has been further modified
and clarified in the previous responses to
the clarifications as follows:
Payment Schedule, Certificates and Terms:
i. First Payment: The amount of
Advance Payment shall be 15% of
Contract price. The Contractor will
be paid Advance Payment after
submission of the Acceptable
Advance Payment Guarantee,
verification of front end engineering
design documents and endorsement
of Approved for Construction (AFC)
documents.
ii. Second Payment: The Contractor
to be paid 30% of Contract price
upon submission of evidence of
order placement and supply
acknowledgement of all equipment.
iii. Third Payment: The Contractor
shall be paid 30% of Contract price
upon satisfactory completion of
Factory Assessment Test (FAT)
witnessed by the Client, Project
Consultant and endorsed and
approved by the recognized third
party inspector; and upon
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
submission of evidence of the
delivery notice and release for
freight/shipment.
iv. Fourth Payment: The Contractor
shall be paid 20% of Contract price
upon completion of all civil works,
installation, testing and
commissioning works and issuance
of project completion certificate.
v. Fifth Payment: The Contractor shall
be paid 5% of Contract price upon
lapse of defect liability period.
17
SCC 18 & 26
Section V
Special
Conditions of
Contract
Advance
Payment
According to SCC 26, advance
payment (15% of contract price) will
be paid to Contractor without
monthly recovery.
As per bidder’s understanding to
SCC 18, this payment (15% of
contract price) is milestone
payment instead of advance
payment.
TPDC is requested to remove the
requirement of submission of
Payments shall be made based on the
milestones.
Please refer to the response in the Item line
number 16 above.
PSSSF Kambarage Tower, 8th Floor, Jakaya Kikwete Road, P. O. Box 1191, Dodoma, Telephone: +255262323519,
Email: [email protected], Website: www.tpdc.co.tz
Advance Payment Bank Guarantee
from SCC 18 & 26.
18
SCC 28
Section V
Special
Conditions of
Contract
Site Hand over
As per GCC 64.1, when the
Certificate of Completion is issued
by the Project Manager, the
Contractor shall handover the site
and the works to the Employer
within time specified in the SCC
As per the description of SCC 28,
Site handover date will be on the
Effective Contract Date.
The Employer is requested to
clarify when the Contractor shall
handover the site and the works to
the Employer.
According to Clause 64 of the GCC States
that: When Certificate of Completion is
issued by the Project Manager, the
Contractor shall handover the site and the
works to the Employer within time specified
in the SCC. It can be clarified that, the
Contractor will handover the site to Client
after a successful commissioning of the
project, where all snag lists will have been
cleared and Certificate of project
completion signed off.
The Bidders should also note that the
Intended Completion date of the Project is
eight (8) months from the Effective Contract
date as stipulated in the Special Conditions
of Contract (SCC) Clause 1.